Gaylord ELX-UV-BB User Manual

MODEL “ELX-UV-BB”
HIGH EFFICIENCY EXTRACTOR VENTILATOR
GENERAL SPECIFICATIONS
Furnish Gaylord Ventilator Model “ELX-UV-BB-___________” as shown on plans and in accordance with the following specications:
The ventilator shall achieve its low air ow rates without the use of internal motors, plenums, or jets. The ventilator shall also include a “Super Capture”TM lip on the front panel for enhancement of smoke and grease capture. The ventilator shall include an “Autostart” controller and sensors to meet current IMC standards.
The ventilator shall include a static pressure port in each section to be used in balancing the static pressure. Continuous front and rear mounting brackets shall be provided to facilitate hanging from the overhead building structure.
The ventilator shall include ultraviolet lamps mounted in modules located in the plenum section. There shall be one or more UV modules, as dictated by the ventilator length, and each module shall be on a slide track for easy removal. Access to the UV modules shall be through tooled removable UV module doors. A pressure switch shall be provided to monitor the airow and prevent operation of the UV lamps if the tooled removable UV module doors is opened, or if any “XGS” Extractor is removed, or if the airow is inadequate. Mounted on the face of the plenum of each ventilator section shall be indicating lights to monitor “UV System On”, “UV Lamp Failure” and “UV Safety Interlock Activated”.
o Gaylord Ba lancing Damper (GBD - Standard Equipment) The ventilator shall be equipped with an opposed blade balancing damper. The damper shall be manually adjustable and accessible from below.
o G ay lo rd F ire B al anc ing D amper (GF BD - Op tion al ) The ventilator shall be equipped with an opposed blade balancing damper that is controlled by an electrically driven actuator, and shall be activated by fail-safe thermostat(s) located at each duct collar.
o Gaylord E lec tri c B ala nc in g D amper (GEBD - O ptional) The ventilator shall be equipped with an opposed blade balancing damper that is controlled by an electrically driven actuator located at each duct collar.
o Fuse Link Damper (FDD - Optional) The ventilator shall be equipped with a fuse link activated re damper located at the duct collar.
o No Damper (ND - Optional)
ELX
SERIES
ITEM NO. _______________
APPLICATION
Island style for all double island arrangements
CONSTRUCTION: The ventilator shall be of all stainless steel construction, not less than 18 gauge, type 300 series. All exposed surfaces shall be a number 4 nish. The use of aluminized steel, galvanized steel, or 430 stainless steel is not acceptable.
LIGHT FIXTURES: The ventilator shall be equipped with:
o Recessed LED
o Recessed uorescent o 100 watt surface mounted incandescent o 150 watt recessed incandescent
Light xtures shall be factory pre-wired to a single connection point. Ventilators built in multiple sections shall be furnished with coiled ex conduit for interconnecting sections.
ACCEPTANCE & APPROVALS: The ventilator shall be listed to UL standard 710 and be ETL Sanitation listed. The ventilator shall comply with all requirements of NFPA-96, IMC, UMC, BOCA and SBCCI mechanical codes. The ventilator shall be capture tested to ASTM 1704-09. The “XGS” Extractors shall be tested to ASTM 2519.
ENERGLINK DESIGN FEATURES
• Internal Canopy Radius
• Enhanced “XGS” Extractor Angle and Slot Spacing
• Faceted “Super Capture”™ Lip
OPTIONAL EQUIPMENT
1. “XGS” Spark Arrestor Extractors
2. Decorative Facings and Trim
3. Exhaust Fans, Supply Fans, & Roof Top Units
4. Fire Extinguisher Systems
5. Utility Distribution Systems
6. Pollution Control Systems
7. Demand Ventilation Controls
6 Watts / Ft. Min. per side
12 Watts / Ft. Min. per side
24 Watts / Ft. Min. per side
36 Watts / Ft. Min. per side
GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordusa.com
www.gaylordusa.com
30” STANDARD ALSO AVAILABLE 24” HIGH, OR WITH A 12” FRONT
*16’ -0” MAX. UNIT LENGTH. FOR GREATER LENGTH, JOIN TWO OR MORE SECTIONS TOGETHER. ALLOW 12” MIN. OVERHANG AT EACH END.
96” MINIMUM.
DIMENSION VARIES
WITH DEPTH OF THE
EQUIPMENT.
LIGHT FIXTURE
CONTINUOUS
HANGING BRACKET
10”
OR 12”
10”
OR 12”
ELX
The manu facturer res erves the r ight to modif y the materi als and spe cifications resulting from a co ntinuing progr am of product improvement o r the availab ility of new materials
“AUTOSTART” SENSOR
GAYLORD BALANCING DAMPER (LISTED)
SERIES
SUPERCAPTURE™ LIP
NOTE: 18” OVERHANG
REQUIRED OVER
UPRIGHT BROILER
6’-8”
MTG. HT.
VENTILATOR BROKEN FOR
SHIPMENT AT THIS POINT
12”
MIN.
0.5 GALLON
GREASE DRAWER
“XGS” SUPER HIGH EFFICIENCY FILTRATION EXTRACTOR
12”
MIN.
Mechanical Requirements
The amount of exhaust volume required is dependent upon the type of cooking equipment and the type and volume of cooking. Contact factory for exhaust volumes, duct sizes, and static pressures.
Electrical
o Provide a 120 volt 20 amp, o 220/240 volt, 50/60 Hz., Non-Interrupted
service to Gaylord CUV-1000 Control Cabinet, to be fused separately. Provide a separate 220/240 volt, 50/60 Hz, 20 amp service for every 2 ventilator sec­tions to power UV lamps. Ventilator lights to be on separate circuit, 120 volt 15 amp standard, 220/240 volt optional
Form No. ELX-UV-BB 0310-20197 © Copyright 2010, Gaylord Industries Litho USA
Ventilator Lengths
Maximum unit length 16’-0”. For greater lengths, join two or more sections together. Check to ensure that there is adequate access into building and kitchen area.
Note: Ventilators manufactured outside North America; maximum unit length
*
10’-0”.
Hanging Weight
Ventilator Width 96” 108” 120” 132”
Wt. / Lineal Ft. Lbs. 190 200 210 220
ENGINEERING DATA