MODEL “ELX-UV”
HIGH EFFICIENCY EXTRACTOR VENTILATOR
GENERAL SPECIFICATIONS
Furnish Gaylord Ventilator Model “ELX-UV-___________” as shown on
plans and in accordance with the following specications:
DESCRIPTION: The ventilator shall include a stationary grease collecting
gutter at the bottom of the grease extraction device, sloped to a drain at
one end to a 0.5 gallon built-in stainless steel grease drawer. The sloped
gutter shall be concealed by an apron which extends the full length of
the hood. Each ventilator shall contain two or more “XGS” Super High
Eciency Filtration Extractors. “XGS” Extractors shall utilize the “capture
and drain” principle.
The ventilator shall include an integrated capture wall to achieve its
low air ow rates. It shall achieve its low air ow rates without the use
of internal motors, plenums, or jets. The ventilator shall also include a
“Super Capture”TM lip on the front panel for enhancement of smoke and
grease capture. The ventilator shall perform at airow rates as tested to
ASTM 1704-09 by the Architectural Energy CKV lab and published on the
Food Service Technology Center web site. The ventilator shall include an
“Autostart” controller and sensors to meet current IMC standards.
The ventilator shall also include a built-in 1” air space at the rear that is
listed for reduced clearance to limited combustibles, and is NFPA- 96 and
IMC compliant when mounting against a limited combustible wall. The
ventilator shall include a static pressure port in each section to be used in
balancing the static pressure. Continuous front and rear mounting brackets
shall be provided to facilitate mounting to the wall and hanging from the
overhead building structure.
The ventilator shall include ultraviolet lamps mounted in modules located
in the plenum section. There shall be one or more UV modules, as dictated
by the ventilator length, and each module shall be on a slide track for easy
removal. Access to the UV modules shall be through tooled removable
UV module doors. A pressure switch shall be provided to monitor the
airow and prevent operation of the UV lamps if the tooled removable
UV module doors are opened, or if any “XGS” Extractor is removed, or if
the airow is inadequate. Mounted on the face of the plenum of each
ventilator section shall be indicating lights to monitor “UV System On”,
“UV Lamp Failure” and “UV Safety Interlock Activated”.
o Gaylord Balancing Damper (GBD - Stand ard Equip men t)
The ventilator shall be equipped with an opposed blade balancing damper.
The damper shall be manually adjustable and accessible from below.
o G ay lord Fir e B al an cing D ampe r (GF BD - O ptio na l)
The ventilator shall be equipped with an opposed blade balancing damper
that is controlled by an electrically driven actuator, and shall be activated
by fail-safe thermostat(s) located at each duct collar.
o Gaylord El ect ric Balancin g Damper (GEBD - Optional )
The ventilator shall be equipped with an opposed blade balancing
damper that is controlled by an electrically driven actuator located at
each duct collar.
o Fuse Link Damper (FDD - Optional)
The ventilator shall be equipped with a fuse link activated re damper
located at the duct collar.
o No Damper (ND - Optional)
ELX
SERIES
ITEM NO. _______________
APPLICATION
Wall mounted canopy for use over all types of equipment; ovens, broilers,
griddles, fryers, ranges, steam equipment, etc.
CONSTRUCTION: The ventilator shall be of all stainless steel construction,
not less than 18 gauge, type 300 series. All exposed surfaces shall be a
number 4 nish. The use of aluminized steel, galvanized steel, or 430
stainless steel is not acceptable.
LIGHT FIXTURES: The ventilator shall be equipped with:
o Recessed LED
o Recessed uorescent
o 100 watt surface mounted incandescent
o 150 watt recessed incandescent
Light xtures shall be factory pre-wired to a single connection point.
Ventilators built in multiple sections shall be furnished with coiled ex
conduit for interconnecting sections.
ACCEPTANCE & APPROVALS: The ventilator shall be listed to UL
standard 710 and be ETL Sanitation listed. The ventilator shall comply
with all requirements of NFPA-96, IMC, UMC, BOCA and SBCCI mechanical
codes. The ventilator shall be capture tested to ASTM 1704-09. The “XGS”
Extractors shall be tested to ASTM 2519.
ENERGLINK DESIGN FEATURES
• Internal Canopy Radius
• Enhanced “XGS” Extractor Angle and Slot Spacing
• Faceted “Super Capture”™ Lip
• Integrated Capture Wall
(Utilities may be integrated into Capture Wall)
OPTIONAL EQUIPMENT
1. “XGS” Spark Arrestor Extractors
2. Decorative Facings and Trim
3. Exhaust Fans, Supply Fans, & Roof Top Units
4. Fire Extinguisher Systems
5. Utility Distribution Systems
6. Pollution Control Systems
7. Demand Ventilation Controls
6 Watts / Ft. Min.
12 Watts / Ft. Min.
24 Watts / Ft. Min.
36 Watts / Ft. Min.
GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordusa.com
www.gaylordusa.com
30” STANDARD
ALSO AVAILABLE 24” HIGH,
OR WITH A 12” FRONT
*16’ -0” MAX. UNIT LENGTH.
FOR GREATER LENGTH, JOIN T WO OR MORE
SECTIONS TOGETHER. ALLOW 6” MIN.
OVERHANG AT EACH END. IF CHARBROILER
IS AT END, OVERHANG 12”
48” MINIMUM.
DIMENSION VARIES
WITH DEPTH OF THE
EQUIPMENT.
LIGHT FIXTURE
CONTINUOUS
HANGING BRACKET
10”
OR 12”
ELX
The manu facturer res erves the r ight to modif y the materi als and spe cifications r esulting
from a co ntinuing progr am of product improvement o r the availab ility of new materials
“AUTOSTART” SENSOR
GAYLORD BALANCING DAMPER (LISTED)
1” MINIMUM AIR SPACE
(LISTED FOR REDUCED CLEARANCE TO
LIMITED COMBUSTIBLES)
“XGS” SUPER HIGH EFFICIENCY
FILTRATION EXTRACTOR
SERIES
0.5 GALLON GREASE DRAWER
SUPERCAPTURE™ LIP
NOTE: 18” OVERHANG
REQUIRED OVER
UPRIGHT BROILER
6’-8”
MTG. HT.
Mechanical Requirements
The amount of exhaust volume required is dependent upon the type of cooking
equipment and the type and volume of cooking. Contact factory for exhaust
volumes, duct sizes, and static pressures.
Electrical
o Provide a 120 volt 20 amp, o 220/240 volt, 50/60 Hz., Non-Interrupted
service to Gaylord CUV-1000 Control Cabinet, to be fused separately. Provide
a separate 220/240 volt, 50/60 Hz, 20 amp service for every 2 ventilator sections to power UV lamps. Ventilator lights to be on separate circuit, 120 volt
15 amp standard, 220/240 volt optional
Form No. ELX-UV 0310-20195 © Copyright 2010, Gaylord Industries Litho USA
12”
MIN.
ENGINEERING DATA
Ventilator Lengths
Maximum unit length 16’-0”. For greater lengths, join two or more sections together.
Check to ensure that there is adequate access into building and kitchen area.
Note: Ventilators manufactured outside North America; maximum unit length
*
10’-0”.
Hanging Weight
Ventilator Width 48” 54” 60”
Ventilator Wt. / Lineal Ft. Lbs. 95 100 105
Capture Wall Wt. / Lineal Ft. Lbs. 20 20 20
CAPTURE WALL
(UTILITIES MAY BE INTEGRATED
INTO CAPTURE WALL)
OPTIONAL SIDE PANELS MAY BE
USED TO ENHANCE CAPTURE
PERFORMANCE