World Headquarters: 10900 S.W. Avery Street • Tualatin, Oregon 97062 U.S.A.
To Our Customers. . .
Congratulations on your recent purchase of a Gaylord
kitchen exhaust hood system. We are proud to be able to
provide you with a quality product that incorporates the latest engineering concepts and is a result of over 50 years of
experience in the foodservice kitchen exhaust industry.
If you have other Gaylord equipment, such as a Gaylord
Utility Distribution System, GPC and CUV Controls, or Roof
Top Pollution Control Unit, etc., please refer to the corresponding supplementary equipment manuals.
If you have further questions, please call us toll free at
1-800-547-9696. We are more than happy to help.
ALL RIGHTS RESERVED. NO PART OF THIS BOOK MAY BE REPRODUCED, STORED
IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRIC, MECHANICAL, PHOTOCOPYING, RECORDING MEANS OR OTHERWISE WITHOUT PRIOR
WRITTEN PERMISSION OF GAYLORD INDUSTRIES COPYRIGHT 2010.
The manufacturer reserves the right to modify the materials and
specifications resulting from a continuing program of product
improvement or the availability of new materials.
ELX SERIES VENTILATOR MODEL DESCRIPTION
MODEL “ELX”
APPLICATION - Wall mounted
canopy style.
MODEL “ELX-BBC”
APPLICATION - Used for cafeteria lines or
any other single line island arrangement.
FIGURE 1
Standard Ventilator Models
MODEL “ELX-BB”
APPLICATION - Used for typical island
style back to back cooking arrangement.
High Efficiency XGS Extractor
Will remove up to 4 times as much
grease as a Standard Baffle Filter
Enlarged Grease Cup to Collect
Captured Grease
(Regular Service May Be Required)
FIGURE 2
Model ELX Shown
1
Gaylord Ventilator model numbers are made up of an alphabetic prefix followed by a series of
alphabetic and/or numeric suffixes to designate the style of the ventilator and various options.
Sequence of model numbers is as follows.
1.______ 2.______ 3._______ 4._______ 5._________ 6.________ 7. _______
Series Damper Style Front lip Apron Design Canopy Front Spark
Type Design (If Applicable) Height Option Arrestor Option (If Applicable)
Explanation of Prefixes and Suffixes
1.
Series
"
EL…………………….. Non water-wash ventilator with UL 1046 filters
ELX ........................... Non water-wash ventilator incorporating XGS Extractors
ELX-UV .................... Non water-wash ventilator incorporating XGS Extractors and UV Lamps
ELX-ENL……………. Non water-wash ventilator incorporating XGS18 Enlarged extractor.
Damper Type
2.
GBD.......................... Gaylord Balancing Damper. Has a mechanical balancing damper located at the duct collar
GFBD ....................... Gaylord Fire Balancing Damper. Has an electric, thermostatically activated Fire/Balancing
GEBD ....................... Gaylord Electric Balancing Damper. Has an electric balancing damper located at the duct collar
FDD…………….. ...... Weighted Fuse Link activated damper located at the duct collar. 280°F Fuse link standard.
CL ............................. Island style for single line
BBC-CL .................... Island style for single line
BBC ......................... Island style for double line
BB ........................... Island style for double line
Front Lip Design
4.
Blank......................... Facetted front design with 6 inch return flange. (3 Break or greater 90° at front lip)
C ............................... Chamfer (6 x 6) with 6 inch return flange
S ............................... Square front with 12" “Super Capture” lip
Apron Design Designation
5.
Blank ......................... Rear Wall to be added below hood
A ............................... Hood to have an Apron, which will terminate at the bottom lower edge of the canopy.
UW ............................ Utility Wall to be added below hood. Note: DCR-WM model Utility Distribution System to be
Canopy Front Height Option
6.
Blank......................... 30 inch
MP ............................ Medium Profile - 24 inch
LP ............................. Low Profile - 12 inch
Spark Arrestor
7.
SPA .......................... Uses “XGS-SPA” or “XGS18-SPA” Spark Arrestor Extractors – for solid fuel applications.
ENERGLINK"
(Standard)
damper located at the duct collar and back draft feature. 325°F Thermostat standard.
with back draft feature.
of cooking equipment using one extraction chamber (Light-Medium
Duty only)
of cooking equipment using one extraction chamber with one common
exhaust duct (Light-Extra Heavy Duty)
of cooking equipment using one extraction chamber. Has one
exhaust duct.
of cooking equipment using two extraction chambers. Has two
separate exhaust ducts.
(Front lower edge of the hood)
added as a separate piece of equipment.
or greater Canopy Height
Front height hoods. Extractors range from 24 to 30 inches tall.
Models containing UV are required to have 30 inch tall extractors.
to 23 inch front height. Extractors range from 24 to 30 inches tall.
(If Applicable – 700°F Applications only)
2
PRINCIPLES OF OPERATION
UL 710 Recognized XGS
Model Commercial Kitchen
Grease Extractor Must Always
be in Place to Protect Downstream
Ductwork
and IMC
or
UL 710 Recognized XGS
Model Commercial Kitchen
Grease Extractor
FAN OPERATION
To operate the exhaust fan turn on the fan switch that
is typically mounted on a wall near the hood. The “EL”
Series hood may be equipped with a fan, auto start
controller, and/or light switch mounted on the face of
the hood.
GREASE EXTRACTION
The Gaylord Industries Patent Pending “XGS” Extractor
Cartridge is designed to deliver the absolute optimum
in collection efficiency at the lowest possible pressure
drop. The units are ETL recognized as part of the “ELX”
Ventilator. They are constructed of corrosion resistant
stainless steel.
FIGURE 4
Grease Extraction
FIGURE 5
Cleaning
FIGURE 6
Fire Protection
3
PRINCIPLES OF OPERATION
UV LAMPS
Systems incorporating UV lamps will have the extra added benefit
of futher break down of grease, in some cases down to CO
and base minerals. The processes called “Photolytic Oxidation”, and
“Ozonolysis” are the drivers behind keeping your ducts clean and
free of containments for much greater durations over conventional
kitchen exhaust systems not utilizing the UVC technology. The
processes break down, and condition grease dramatically reducing
its ability to burn or in some cases even combust. For proper UV
operation, the hoods must be maintained in good working order.
UV lamps will accumulate a gray-brown dust on them that will have
to be periodically wiped off from below. Duct work will have to be
inspected in accordance with NFPA-96 or local guidelines, though
frequency of duct cleanings will be dramatically reduced.
Important Notice:
Extractors in place. The XGS Extractor is a light attenuation barrier
to remain in place at all times during the use of your UV system.
Never operate your ventilator without the XGS
, H2O,
2
CLEANING
At the end of the cooking day the fan is to be turned off and the
XGS Extractors are to be removed from the hood and cleaned. The
XGS Extractors can be washed either in a dishwasher or soaked
and rinsed off. Periodic scrubbing of the extractors may be necessary in lines servicing busy kitchens, or lines using sugary sauces
or bastings.
The UV lamps will develop a coating of dust, and sometimes debris
that will have to be wiped away to optimize the UVC Systems performance. The lamps should be inspected weekly after the filters
are removed. When necessary, the lamps can be cleaned from
below by carefully wiping the bulbs with a wet cloth using some
mild detergent. A maintenance rotation should be initiated at the
point of start up by a Gaylord Industries certified Service Agent to
address any maintenance, or repair issues that may be required.
FIRE PROTECTION
NFPA-96 and the IFC requires the use of Surface Fire Protection
(Duct, Plenum, Surface/Appliance) on all hoods. It is these systems
that are the first line of defense against equipment fires. Refer to
the fire extinguishing system owner’s manual for operation and
maintenance instructions for these systems.
The “ELX-GFBD” Series ventilator incorporates a fire / balancing damper installed in the duct collar to protect your ducts, fans,
and roof tops from the threat of fire in the event your primary fire
protection system fails to extinguish the fire. In the event of a fire
when the thermostat reaches it set point of 325°F, the power to the
damper will be cut allowing the dual blade damper to spring shut
sealing the duct entrance and keeping the fire contained in the
plenum, where it can be properly managed. Exhaust dampers are
an excellent way to reduce the threat of fire spreading to your roof
top and loaded grease ducts.
The hood may also be supplied without a fire damper, which would
be designated by either the suffix “ND” or “GBD” in the model number. “GBD” designates a balancing ONLY damper. Refer to the
nameplate on the hood for the exact model number designation.
FIGURE 7
ELX-GFBD Model
4
MAINTENANCE AND CLEANING INSTRUCTIONS
ELUDEHCSNOITCEPSNIMETSYSTSUAHXE
snoitarepognikoocleufdilosgnivressmetsySylhtnoM
snoitarepognikoocemulov-hgihgnivressmetsyS
kowrogniliorbrahc,gnikoocruoh-42sahcus
gnikooc
ylretrauQ
gnikoocemulov-etaredomgnivressmetsyS
snoitarepo
yllaunna-imeS
,snoitarepognikoocemulov-wolgnivressmetsyS
lanosaes,spmacyad,sehcruhcsahcus
sretnecroinesro,sessenisub
yllaunnA
At the end of each cooking day, the exposed interior surfaces of the hood
should be wiped down and the grease cup emptied. During the course of
operation, grease particles are gradually collecting inside the XGS extractors. Daily, or at periodic intervals, depending on the type of cooking, the
XG extractors must be removed and cleaned. To clean, proceed as follows:
1. Remove extractors. CAUTION: Care should be taken when removing extractors, especially over fryers. It is recommended that the
cooking equipment be cooled down and the fryers be covered prior
to removing extractors. To remove, lift up slightly on extractors and
pull out at the bottom, then straight down.
2. Extractors may be cleaned either by using a dishwasher or by soaking in deep well sink using hot water with a degreasing detergent,
scrubbed and rinsed. Formula G-510 is highly recommended for
this application. For information contact:
20/10 Products
P.O. Box 7609
Salem, Oregon 97303
Phone: 800-286-2010
Fax: 503-363-4296
email: twentyten@juno.com
3. With extractors removed, wipe and clean the back wall and top of the
plenum area and the grease gutter with hot detergent water. NOTE: If
steam or hot water pressure wash is used for periodic cleaning of the
interior, remove the grease drawer and connect a hose to the gutter
drain and lead it to a floor sink or large bucket to drain off water.
4. When applicable, periodic cleaning of the UV lamps will be required.
After removing extractors for servicing, wipe the UV bulbs down with
a clean wet rag to remove any contaminants or grease that may have
collected on the lamps. Failure to maintain the cleanliness of the
lamps will reduce the UVC systems ability to reduce the build-up of
grease and debris on ducts and fans.
5. Replace extractors. Be sure to replace extractors with openings running vertical as shown in Fig. 9. Note: Arrow will designate “UP”.
IMPORTANT NOTE: In the event of a fire the thermostat must be replaced.
(Applicable to GFBD models only.)
NOTE: NEVER OPERATE THE HOOD
FIGURE 8
IF THE FILTERS ARE NOT IN PLACE.
INSPECTION AND CLEANING REQUIREMENTS
The 2008 edition of NFPA-96 (Standard for Ventilation Control and Fire
Protection of Commercial Cooking Operations) require that hoods, ducts
and exhaust fans be inspected by a properly trained, qualified and certified
company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from greaseladen vapors, the entire exhaust system shall be cleaned by a properly
trained, qualified, and cer tified company or person(s) acceptable to the
authority having jurisdiction in accordance.
When a vent cleaning service is used, a certificate showing date of inspection or cleaning shall be maintained on the premises. After cleaning
is completed, the vent cleaning contractor shall place or display within
the kitchen area a label indicating the date cleaned and the name of the
servicing company. It shall also indicate areas not cleaned.
Facto r y tr a ined ser vi c e agenci e s ar e cer t ified by Gayl o r d
Industries to perform these inspections. For the name and phone number of your nearest agent, call 1-800-547-9696 or go online to visit our
website at www.gaylordusa.com.
FIGURE 9
NOTE: FILTERS MUST BE INSTALLED WITH
BAFFLES RUNNING VERTICAL AS SHOWN.
CAUTION: Care should be taken when removing
extractors, especially over fryers. It is recommended that the cooking equipment be cooled down and
the fryers be covered prior to removing filters.
5
UV PREVENTATIVE MAINTENANCE
CERTIFIED SERVICE AGENT MAINTENANCE WARNING!
Warning: Do NOT defeat any interlocks during cleaning and maintenance!
system inspection schedule described in NFPA-96 and on the previous
page in this tech manual. These tasks involve potential exposure to high
doses of UV light and live electrical components. There is risk of injury
to skin and eyes and in the case of electrical shock, injury or death! For
a list of CSAs go to www.gaylordusa.com and go to “Service Agencies”
for a list of companies nearest you.
1. Inspection of the Lamps and Ballasts
(Check the lamps for proper operation)
a. Turn on the fan at your CUV-1000
2. Inspect the Plenum (Around the UV lamps)
a. Turn off Exhaust fan at CUV-1000
controller. Look for green “UV System On”
light at your CUV-1000 controller. If the
b.
audible alarm sounds, refer to “UV Trouble-
shooting” on pages 17 - 18.
Confirm the green status light on each hood
section controlled by your CUV-1000
controller.
b. Remove the UV Module access cover.
(Philips head screwdriver required.)
c. Disconnect the UV Module power connector.
(Half turn required.)
d. Remove the UV Module from the ventilator.
(Caution! Care must be taken to keep the connector
from hitting the lamps while removing the module.)
e. Carefully inspect the UV access cover and
replace gasket as needed to ensure a good seal.
f. Clean the UV Module as needed with a mild
detergent, water and non-abrasive rag. Lamps
should be free of all grease and debris.
g. Reinstall the UV Module, being careful to not
hit the lamps. Re-secure the Module connector
and UV access door.
Replacing UV Lamps
Danger!
Certified Service Agency (CSA). These tasks involve potential
exposure to high doses of UV light and live electrical components.
There is a risk of serious injury to skin and eyes from UV light. There
is risk of shock, injury, and/or death from electrical. For a list of CSA’s
go to www.gaylordusa.com and go to the “Service Agencies” for a
Secure all power to the CUV-1000 control1.
Secure all circuits that provide power to the UV lamps2.
Open the UV Module Access door3.
Disconnect the UV module power connector4.
Remove the UV module from the ventilator 5.
Remove the bolts on the end of the UV module (2 total) 6.
that hold the end cap on. (see below)
3. Test the Safety Interlocks, (Pressure Switches)
a. Activate fan at CUV-1000, all Hood sections will
show the “UV System On” lamp activated at the
extractor.
b. Remove the XGS Extractor at the left side of the
hood. Lamps will deactivate. If lamps do not
activate, immediately shut down the CUV-1000
and go to “UV Troubleshooting” pages 17 - 18.
(Caution! Wear Polycarbonate Safety Glasses
when testing the UV Interlocks.)
c. Repeat the above steps for the right most XGS
Extractor and the center most Extractor. UV
System will deactivate accordingly, if not, shut
down, and refer to “UV Troubleshooting” pages
17 - 18.
4. Check all gaskets for damage
a. Replace any gaskets that are worn or damaged only
5. Check the Hour Meter
a. Record the hours
c. Determine when the 8000-hour life of the lamps will
with factory provided replacements.
b. Determine the approximate hours between inspection
intervals.
occur and inform the operator of the approximate date
when the lamps will need to be replaced.
FIGURE 11
Disconnect the lamp connector(s) on the UV lamp(s) to be 7.
replaced
Each lamp connector should be labeled from 1 to 4 •
Lamp #1 is at the Front of the ventilator when the UV •
module is installed
Lamp #4 is at the Back of the ventilator when the UV •
module is installed
Be sure to re-label the lamp connectors if necessary•
Lubricate the lamps around the grommets on each end of the 8.
UV lamp with a small amount of G-510 or similar detergent
Slide the UV lamp out one end, CAREFULLY!9.
Inspect the grommets around the lamps10.
Replace any grommets that show cracks, or any other •
damage
6
UV PREVENTATIVE MAINTENANCE CONTINUED
CERTIFIED SERVICE AGENT MAINTENANCE WARNING!
Warning: Do NOT defeat any interlocks during cleaning and maintenance!
11. Check all wires for damage
Replace any wires showing damage•
12. Lubricate each of the new UV lamp(s) before installing with a
small amount of G-510 or similar detergent
13. Re-connect the lamp connectors
Each lamp connector should be labeled from 1 to 4 •
Lamp #1 is at the Front of the ventilator when the UV •
Module is installed
Lamp #4 is at the Back of the ventilator when the UV •
Module is installed
14. Re-install the UV Module end cap and torque the bolts to
7-10 in-lbs.
15. Re-install the UV Module in the ventilator
16. Re-connect the UV Module power coNNECTOR
17. Tighten all quarter-turn screws holding the UV Module
cover to the ventilator
18. Check for proper operation of UV lamps & pressure
switches
FIGURE 12
SAFETY CONCERNS WITH UVC
As with many types of technology if it is not used properly and/or
proper precautions are not taken there is the potential for injury
or harm. This is especially true with UVC light due to the fact that
it does not physically hurt at the time of exposure. While UVC is
very effective at breaking down grease molecules, direct exposure
generated in these hoods is greater than that what results from
direct exposure to the sun. Under no circumstances is it acceptable
to view the lighted lamps without proper eye protection or expose
bare skin directly to the light. All interlocks and safety precautions
called for in this manual must be followed to avoid the potential for
harm to service personnel and/or operators. In addition, only trained
and authorized personnel may perform some maintenance See
previous page for details.
Personal Protective Equipment
Eye protection that prevents 100% of UVC being transmitted 1.
through the lens must be worn at all times when performing
service work on any ELX-UV that is energized and/or has
the potential to be energized and expose personnel to UVC
light.
Whenever service work is performed it is recommended that 2.
long sleeve pants and shirts be worn to minimize the potential
for inadvertent exposure of the skin to UVC.
Safety Interlocks
This product comes equipped with redundant pressure switches to
ensure the Exhaust Fan is running, and that every filter is in place.
All of the switches must be working and/or adjusted properly in
CVU fo tnuoma ehT .seye dna niks ot lufmrah si stnuoma egral ot
order for the system to operate properly.
7
OPTIONAL FIRE / BALANCING DAMPER GBD SERIES
Gaylord System Balancing (GBD)
The ELX Serie s Venti lator will optionally come with a Gaylor d
Industries Listed balancing damper. The options available are the
GBD-IS (balancing only damper), GEBD (electrical balancing damper), and the GFBD (fire balancing damper). The GBD-IS is set
from below and performs the task of raising or lowering the exhaust
airflow to any section that it is installed on. The GFBD is a fire / balancing damper that will close upon the thermostat reaching its set
point. The thermostat for the XG series ventilator is set to 325°F,
and must be factory installed. The balancing of the GFBD and GEBD
is done by way of a potentiometer found in the UV electrical box (see
Figure 19) or in another dedicated electrical box, accessed from
inside the canopy. (See Figures 4 & 8). The GFBD is intended to
close upon the deactivation of the exhaust fan every night. The
feature is intended to eliminate cool air from drafting down the exhaust ducts, and entering the kitchen.
For further details on the Gaylord Industries commercial kitchen
exhaust dampers, please consult the GBD technical manual.
Damper Motor
GFBD Commercial Fire / Balancing Damper
FIGURE 14
Self Locking
Fastener
Damper Blade
Brass Support
Ring
Oil Seal
FIGURE 15
GBD “DSD” Damper Set Dimension
The adjustment of both systems relies on the internal dimension between
the two blades. Called the “DSD”. The manipulation of that distance will
accomplish your air balancing needs. See Figure 15, above, the GBD
FIGURE 13
details.
8
Loading...
+ 24 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.