Gaylord CUV-1000 User Manual

MODEL “CUV-1000”
C US
CONTROL CABINET FOR VENTILATORS
GENERAL SPECIFICATIONS
DESCRIPTION: Control cabinet Model CUV-1000-________ shall be
furnished to house electrical components for operation of the ventilator(s) and UV system. The cabinet shall be constructed of 18 gauge stainless steel, type 300 series, number 4 nish, with welded corners and a hinged door. Cabinet shall be watertight to protect against direct hose spray. The electrical controls shall include a programmable logic controller (PLC) for controlling all functions of the exhaust and supply fans, UV lamps, “Autostart” and electric dampers (if applicable). The control shall include a programmable digital interface module (Command Center) that includes “Start Fan” and “Stop Fan” buttons and a digital display that shows current operating mode. The control shall continuously monitor the UV lamps, access doors and exhaust volume with visual and audible indicators. It shall also include volt-free contacts for supply and exhaust fans for interfacing with building management system or other control circuits, and volt-free contacts for the re cycle for interconnection to the building re alarm or monitoring systems. The control shall include contacts to remotely Start and Stop the exhaust and supply fan(s) when interfacing with a building management system. It shall monitor “Autostart” sensors, mounted in the ventilator(s), if equipped, and automatically start the exhaust and supply fan(s) if cooking occurs when the fans are o. All components shall be pre­wired for eld hook-up by applicable trades. Control cabinet shall be listed.
OPTIONAL EQUIPMENT:
o Light Switch The control cabinet shall include a built-in light switch for interconnection to the ventilator lighting circuit.
o Trim Ring The control cabinet shall include a full perimeter one piece adjustable trim ring.
o Security Access Control cabinet door shall be equipped with keyed latch to prevent unauthorized access to the controls.
ELECTRICAL LEGEND
E1 120VAC 50/60Hz Non-Interrupted Service or
o
o
o
o
o
o
o
o
o
o
o
o
220VAC 50/60Hz Non-Interrupted Service
E2 Two Wires to Magnetic Starter(s) For Exhaust and Supply
Fans
E3 Two Wires to Fire Suppression System
E4 Five wires and ground, for UV System to Ventilator(s)
E5 Two wires and ground, for “Autostart” to Ventilator(s)
E6 Four wires and ground, for Electric Dampers to
Ventilator(s) (If Specied)
E7 Optional - Two Wires and ground, from Light Switch to
Supply voltage service.
E8 Optional - Two Wires and ground, from Light Switch to
Lights in Ventilator.
E9 Optional - Two Wires From Volt Free Contacts To Building
Management System (BMS) to Control Exhaust Fan(s) (If Specied, E2 Not Used.)
E10 Optional - Two Wires From Volt Free Contacts To BMS to
Control Supply Fan(s) (If Specied, E2 Not Used.)
E11 Optional - Two Wires to BMS To Monitor Fire Cycle If
Specied.
CUV
E1
E2
E3
E4
E5
E6
E7
E8
UV Ventilators require either:
• Separate 120VAC, 60Hz, 20 Amp circuit for UV lamps for each section
OR
• 220VAC, 50/60Hz , 20 Amp circuit for UV lamps for every two sections
-1000
ITEM NO. _______________
Form No. CUV-1000 0310-20201 © Copyright 2010, Gaylord Industries Litho USA
GAYLORD INDUSTRIES
10900 SW AVERY ST • TUALATIN, OREGON 97062 U.S.A.
PHONE: 800.547.9696 • FAX: 503.692.6048 • email: info@gaylordusa.com