10900 SW Avery Street – Tualatin, Oregon 97062 USA
Email: info@gaylordventilation.com
www.gaylordventilation.com
Toll Free 800-547-9696 – Fax 503-692-6048
Page ii
All rights reserved. No part of this book may be reproduced, stored in a retrieval
system, or transmitted in any form by an electronic, mechanical, photocopying,
recording means or otherwise without prior written permission of Gaylord
Industries.
The manufacturer reserves the right to modify the materials and
specifications resulting from a continuing program of product
improvement or the availability of new materials
Model Description ………………………………………………………………………………………………………………………… 1-2
Model Number Sequence …………………………………………………………………………………………………………….. 1-3
Explanation of Damper Options …………………………………………………………………………………………………… 1-5
Chapter 2 – Principles of Operation
Principle of Operation Overview …………..……………………………………………………………………………………… 2-1
Grease Extraction ………………………………….…………………………………………………………………………………….. 2-2
Optional Continuous Cold Water Mist ..……………………………………………………………………………………….. 2-4
Wash Cycle ………………………… ……………………………………………………………………………………………………….. 2-5
Internal Fire Mode ..……………………………………………………...………………………………………………………………. 2-8
Fire Extinguishing Systems ……………………………………………….……………………………………………………………. 2-9
Chapter 3 - Daily Operation
Starting the Exhaust and UV System ……………………………………………………………………………………………. 3-1
Turning Off the Exhaust Fan and Starting the Wash Cycle …………………………………………………………… 3-5
Recommend Detergent ………………………………………………………………………………………………………………… 3-8
Chapter 4 – Maintenance
Operator Preventive Maintenance ……………………………………………………………………………………………… 4-1
Preventive Maintenance Required by Code ………………………………………………………………………………… 4-2
UV System - Scheduled Preventive Maintenance ……………………………………………………………………….. 4-3
The purpose of this manual is to provide the Operator, Maintenance and Service personnel instructions
for operating, maintaining, troubleshooting and repairing the Gaylord Ventilator Model CG3-UVi Series.
Ventilators incorporating UV Systems, most maintenance and all repairs must be performed by a trained
and certified service company. This manual also includes information and guidance to contractors for
initial installation of the Ventilator.
The manual is divided into chapters for easy reference to a particular subject. The pages in the chapters
are numbered with the chapter number, then a dash, and then the page number. So for example pages
in Chapter 2 are numbered 2-1, 2-2, 2-3 etc. Figures and Tables are numbered in a similar manor. For
example Figure 5-3-2 is on page 5-3 and is the second figure. Please keep your manual in a convenient
location for so it can be accessed easily.
If you have any questions or concerns with the installation, operation, maintenance or service of your
Gaylord Ventilator, please contact Gaylord Industries;
Web: www.gaylordventilation.com
E-Mail: info@gaylordventilation.com
Main Phone: 503-691-2010
Toll Free: 800-547-9696
Safety
It is important that the operator read Chapter 2, Principle of Operation, and Chapter 3, Maintenance,
before operating the Ventilator for the first time. Particular attention should be given to all the Caution
and Warning statements.
Related Technical Manuals
CG3-UVi Series Ventilators are controlled by a Gaylord Command Center. The model number of the
Command Center is dictated by when the Ventilator was purchased. Typical models are C-6000 and C7000 Series. The model number of your Command Center can be found on the nameplate located on
the back of the electrical compartment door. AllInstallation Operation and Maintenance Manuals may
be downloaded from the Gaylord website: www.gaylordventilation.com or be obtained by calling
Gaylord Industries.
The Gaylord Model CG3-UVi Series Ventilator is a high grease extraction efficiency Ventilator that
includes the additional feature of an Ultraviolet Light System that dramatically reduces grease
accumulation in the exhaust plenum, ductwork and exhaust fans. The Ventilator incorporates a hot
water Wash Cycle that automatically washes the accumulated grease and particles out of the Ventilator
and into the building drain system.
The CG3-UVi Ventilators come in many different models, Wall Mounted Canopy, Single Island Style, and
Double Island Style. All Gaylord Ventilators are custom designed to fit the space and application of your
facility.
Inlet damper is fixed and no damper motor, and has fuse link activated fire
Model Number Sequence
The CG3-UVi Series model numbers are made up of an alphabetic prefix followed by a series of
alphabetic and/or numeric suffixes to designate the style of ventilator and various options. Sequence of
model numbers is as follows.
Type
Profile
Design
(Option)
Built in
Make-up
Air If
Applicable
Air If
Applicable
Water
Mist, If
Applicable
If
Applicable
Back
Dimension
of the
Ventilator
in Inches
Explanation of Prefixes and Suffixes
1. Series
CG3-UVi ……………… Water Wash Ventilator with ultraviolet light feature.
2. Damper Type
Blank Space …………. Electrically activated three position damper located at air inlet slot (Refer to
Figure 1-5-1).
FDD ……………………… Same as CG3-UVi except inlet damper is fixed and has a fuse link activated fire
damper located at the duct collar (Refer to Figure 1-6-1)
FDT ……………………….
FDL ….………………….. Same as CG3-UVi except a bracket (Fire Damper Lockout) has been added to
ND ………….…………… Same as CG3-UVi except inlet damper is fixed and has no fire damper (Refer to
3. Style
BDL ……………………... Wall mounted canopy.
BDL-BB ................. Island style for back-to-back cooking equipment using two extraction chambers
BBC ……………………… Island style for back-to-back cooking equipment using two extraction chambers
BDL-DS ………………… Island style for back-to-back cooking equipment using one extraction chamber
BDL-DS-CL …………… Island style for single line of cooking equipment.
4. Profile
LP ........................... Low Profile. Reduced height of front face of Ventilator and sloping end panels.
damper located at the duct collar with a thermostat to detect fire to send
notification (Refer to Figure 1-5-3)
prevent the damper from closing to the fire position (Refer to Figure 1-5-2)
1. CG3-UVi Ventilator – This is the standard Ventilator and
incorporates a damper at the air inlet slot that during a
wash mode closes forward by and electric motor to seal
off the inlet slot and opens to the exhaust position when
the exhaust fan is started. During a fire mode, that is
activated by a thermostat the damper closes backwards
to the fire position and stays closed until the thermostat
drops below its set point and then closes to the wash
position.
2. CG3-UVi-FDL Series – The FDL in the model number
stands for Fire Damper Lockout. This Ventilator
incorporates the same inlet damper as the CG3-UVi that
during a wash mode closes forward by and electric
motor to seal off the inlet slot and opens to the exhaust
position when the exhaust fan is started. The main
difference is the CG3-UVi-FDL has a Fire Damper
Lockout (FDL) bracket added that prevents the inlet
damper from closing to the fire position, so it does
NOT have a fire damper. This Ventilator does include a
thermostat to send a signal to fire alarm systems.
3. CG3-UVi-FDT Series – The FDT in the model number
stands for a fuse link Fire damper in the Duct collar
with a Thermostat. The fire damper is weighted and
when the fuse link reaches its melting point, the
damper closes. The thermostat sends a signal to the
fire alarm systems.
4. CG3-UVi-FDD Series – The FDD in the model number
stands for Fire Damper in the Duct collar. The fire
damper is weighted and when the fuse link reaches its
melting point, the damper closes. There is no
thermostat.
5. CG3-UVi-ND Series – The ND in the model number stands for
No Damper.
Section View
CG3-UVi-FDD
Section View
CG3-UVi-ND
__________________________________________________Chapter 2 - Principle of Operation, Page 2-1
Figure 2-1-1
Figure 2-1-2
Principle of Operation Overview
The Gaylord Model CG3-UVi Series Ventilator is a high grease extraction efficiency Ventilator that
includes the additional feature of an Ultraviolet Light System that dramatically reduces grease
accumulation in the exhaust plenum, ductwork and exhaust fans. The Ventilator incorporates a hot
water Wash Cycle that automatically washes the accumulated grease and other particles out of the
Ventilator and into the building drain system. The standard CG3-UVi Ventilator has a full length fire
damper located at the air inlet slot, two models have a fire damper in the exhaust duct collar and one
model does not have a fire damper.
The operation of the exhaust fan and the Wash Cycle is controlled by the Gaylord Command Center
which is located on the face of the Wash Control Cabinet (Refer to Figure 2-1-1). All the plumbing
components, detergent pump and detergent tank are located inside the Wash Control Cabinet (Refer to
Figure 2-1-2 andFigure 2-7-2).
Typical Command Center
Typical Wash Control Cabinet
Chapter 2 - Principle of Operation, Page 2-2__________________________________________________
Grease Extraction
Overview
The Gaylord “CG3-UVi” Series Ventilator extracts up to 95% of the grease, dust and lint particles from
the airstream passing through it, when operated and maintained in accordance with design
specifications. This high rate of grease extraction is accomplished by the use of grease extraction
baffles, particulate separators and UV lamps. The following describes the function of each.
Grease Extraction Baffles
When the exhaust fan is started the hot, grease-laden air rising from the cooking surface merges with
the higher velocity air that wipes the front of the cooking equipment and extends, like an air blanket, from
the front edge of the cooking equipment to the air inlet slot of the
through the Ventilator’s extraction chamber at a high speed, it is forced to make a series of turns
around three baffles. As this high velocity air turns around each baffle, the
thrown out of the airstream by centrifugal force and collected on the baffles. The extracted grease,
dust and lint are collected in the interior of the ventilator, remaining out of the airstream until
removed daily by the wash cycle.
Baffle #1
Important Note: The following description of Baffle #1 is for the standard CG3-UVi series Ventilator.
For operation of Baffle #1 for series FDL, FDT, FDD, and ND refer to TableT-2-9-1).
This baffle, located at the air entrance of the ventilator, is a
the exhaust on mode as
2-6-1, and
pushed on the Command Center, the damper opens to the exhaust mode position 1 to become
is
the preliminary grease
back side of the damper which drains off liquefied
airstream.
Baffle #2
This baffle is located on the interior back wall of the ventilator
equipped with brass spray nozzles on 8" to 10" centers (Refer to Figure 2-3-1). During the wash
cycle, hot detergent water is released through the nozzles.
Baffle #3
This baffle is located on the back of the inspection doors (Refer to Figure 2-3-1). This baffle is also a
grease collecting gutter, collecting the grease extracted by the ventilator preventing the contaminants
from dropping back into the high velocity airstream.
Optional Custom Air Baffles
Some Ventilators may be equipped with optional Custom Air baffles, shown dotted, which reduces
the exhaust volume where the baffles occur (Refer to Figure 2-3-1).
Particulate Separator
Once the larger particles of grease have been captured through inertial impaction by the baffles, the
smaller particles will be arrested in the Particulate Separator using the principles of diffusion and inertial
impaction (Refer to Figure 2-3-1). These collected particles will be washed away each day by the
automatic wash.
position 3 is the fire mode as shown in Figure 2-8-1. When the "START FAN" button
shown in Figure 2 -3 - 1 , position 2 is the wash mode as shown in Figure
extraction baffle. There is a small sloped grease collecting gutter on the
grease, preventing it from re-entraining into the
V
entilator. As the air moves
larger
three position damper. Position 1 is
and is a stainless steel pipe,
particles of grease are
__________________________________________________Chapter 2 - Principle of Operation, Page 2-3
Figure 2-3-1
Grease Extraction Mode
Baffle #1
Baffle #3
Particulate
Baffle #2
Optional
Dotted
UV Module
UV Lamps
Air Inlet Slot
Grease Extraction – Cont.
UV Lamps
Once the baffles and particulate separator have collected the grease particles larger than 1 micron, the
UV lamps will break down the remaining grease particles by direct exposure to 254nm light and by the
Ozone, Hydroxyl Radicals and Anionic oxygen created by the 187nm UV light and oxidizing the grease into
a light gray dust. The Ozone will carry down the ductwork and continue to break down the grease
particulate and odor molecules keeping the ductwork much cleaner. The byproducts of this process are
CO2, H20 and the base minerals from the grease and particulate matter coming off of the cooking
surface. The light gray dust that collects on the lamps is washed away each day during the Wash Cycle.
UV Systems are used to remove a high percentage of grease that the baffles and particulate separator
cannot remove, offering many benefits to the owner/operator.
The UV Lamps are mounted in an UVi Module which slide into a track downstream of the Particulate
Separator (refer to Figure 2-3-1). The ballasts are mounted in the front portion of the module and other
electronics are mounted in the electrical raceway (Refer to Figure 6-7-1 and 6-15-1).The Command
Center monitors and displays text indicating the status of the UV System, and Safety Interlocks. Refer to
your Command Center Tech Manual for specific text displayed.
Separator
Custom Air
Baffle Shown
Chapter 2 - Principle of Operation, Page 2-4__________________________________________________
Figure 2-4-1
Cold Water Mist Nozzles
Grease Extraction – Cont.
UV Lamps – Cont.
For proper UV operation, the Ventilators must be maintained in good working order. The UV system
must be inspected periodically and the lamps replaced as necessary. The Ventilator, ductwork and
exhaust fan must be inspected in accordance with NFPA-96 or local guidelines, though frequency of duct
cleanings should be significantly reduced. Refer to Chapter 4for maintenance details.
UV Safety
Caution: Exposure to UV light is harmful to skin and eyes.
The CG3-UVi Series Ventilator is equipped with panels and Safety Interlocks to protect operators from
direct exposure to UV light. All safety precautions called for in this manual must be followed to avoid the
potential for harm to operators or service personnel. Refer to Page 4-3 for complete description of
safety precautions.
Optional Continuous Cold Water Mist
Overview
Some ventilators may be equipped with optional continuous cold water mist. NFPA-96 requires that all
hoods used over solid fuel burning appliances be equipped with a “spark arrester” to knock down any
embers, created by the burning of solid fuel, to reduce the possibility of embers or sparks being drawn
up into the exhaust duct and fan where it could ignite collected grease. Continuous cold water mist is
one of the acceptable spark arresters.
Continuous cold water mist ventilators incorporate a water manifold with spray nozzles, located at
the lower edge of the air inlet slot (Refer to Figure 2-4-1). When the exhaust fan is started, the
solenoid valve in the cold water loop in the Wash Control Cabinet opens (Refer to Figure 2-5-1), turning
on the mist nozzles which remain on as long as the exhaust fan is on. The nozzles produce a very fine mist
and are located so
that the entire air stream passes through the mist.
Optional Cold Water Mist
__________________________________________________Chapter 2 - Principle of Operation, Page 2-5
Figure 2-5-1
With Continuous Cold Water Mist Loop
Cold Water Loop
Cold Water Line to
Ventilator
Cold Water Inlet
Solenoid Valve
Pressure Regulator
Optional Continuous Cold Water Mist – Cont.
Engineering Notes
1. Water pressure: The optimal water flow pressure of the nozzle is 40 psi. There is a pressure
regulator and pressure gauge in the plumbing loop to accomplish this pressure.
2. Water Consumption: .66 GPH per lineal ft. of Ventilator at 40 psi.
Typical Wash Control Cabinet
Wash Cycle
The wash system is comprised of two wash manifolds with spray nozzles are located on 8" to 10" centers
(Refer to Figure 2-6-1). The wash cycle is activated each time the exhaust fan is shut off by pushing the
START WASH button on the Command Center or automatically at a specific time as programmed in the
Command Center (Refer to Figure 2-7-1). When activated the UV lamps shut off, the exhaust and
supply fans shut off, the electric damper motor is energized and the damper begins closing forward
to the wash position, and once closed the hot water wash sprays come on (Refer to Figure 2-6-1).
Chapter 2 - Principle of Operation, Page 2-6__________________________________________________
Wash Manifold
Wash Manifold
Pre-Flushed Drain
Sloping Gutter
Figure 2-6-1
Damper Closed to
Wash Cycle – Cont.
The detergent pump, detergent tank, solenoid valve and other plumbing components are located in the
Wash Control Cabinet (Refer to Figure 2-7-1). This hot detergent water washes the day’s grease, dust
and lint accumulation from the baffles, the Particulate Separator, and gray dust from the UV Lamps,
flushing it down to the main gutter which slopes to a pre-flushed drain which leads to the building
drain system. At the end of the wash cycle, the water automatically shuts off, and the interior of the
Ventilator is clean and ready for the next day’s operations. The damper remains in the wash position
until the exhaust fan is restarted. This is to prevent conditioned air from going up the exhaust system
during off hours.
The length of the wash cycle may be set between 3 minutes and 9 minutes. The length of time is
dependent upon the type of cooking equipment being used. Typical settings are 3 minutes for lightduty equipment, 5 minutes for medium-duty equipment, and 9 minutes for heavy-duty equipment.
However, adequate cleaning is dependent upon water pressure, water temperature, daily grease
accumulation, the length of the wash cycle, frequency of wash cycle and the type of detergent being
used. It may be necessary to increase the wash time to achieve proper cleaning. Refer to your Command
Center Technical Manual for instructions on programming wash times.
Engineering Notes
1. Hot Water Pressure: 40 PSI Min. – 80 PSI Max.
2. Hot Water Temperature: 140° Min. - 180° Max.
3. Water Consumption: 1.14 GPM/ lineal ft. of Ventilator at 40 PSI Average
1.67 GPM/ lineal ft. of Ventilator at 80 PSI Average
Wash Mode
Wash Position
__________________________________________________Chapter 2 - Principle of Operation, Page 2-7
Outlet to Ventilator
Detergent Pump
Figure 2-7-1
Detergent
Pressure
Detergent
Backflow
Command Center
Hot Water Inlet
Figure 2-7-2
Line Strainer
Wash Cycle – Cont.
Command Center
Electronic Boards
Injection Point
/Temperature
Gauge
Container
Preventer
Typical Wash Control Cabinet With Electrical
and Plumbing Doors Open
Chapter 2 - Principle of Operation, Page 2-8__________________________________________________
Baffle #1 Closed to
Figure 2-8-1
Fire Mode
Fire
Fire Extinguishing
Fire Extinguishing
Fire Thermostat
Internal Fire Mode
Important Note: The following description of the Internal Fire Mode is for the standard CG3-UVi series
Ventilator only. Refer to Table T-2-9-1for a description of the Internal Fire Mode for series FDL, FDT,
FDD, and ND.
Automatic internal fire protection is accomplished by the action of the thermostat(s), which are located
at the point where the ductwork joins the ventilator (Refer to Figure 2-8-1). When the temperature of
the conveying airstream, which must pass over the thermostats, reaches 250°F, the system is activated,
and the following occurs:
1. Baffle #1 begins closing back to the fire position, position #3, stopping the combustion supporting
natural draft through the ventilator and creating a fire barrier to contain the fire in the kitchen (Refer
to Figure 2-8-1).
2. The UV lamps shut off.
3. The exhaust fan serving the ventilator is shut off. The supply fan is also shut off.
4. A fire signal is sent from the Command Center to the build fire alarm system (if wired).
5. The display on the Command Center will indicate a fire. Important Note: Refer to your Command
Center Technical Manual for specific text displayed during a Fire Mode.
6. Upon cooling of the thermostat below 250°F, a 2 minute Cool Down Cycle begins and Baffle #1
moves to the exhaust position. Important Note: Refer to your Command Center Technical Manual
for specific text displayed during a Cool Down Cycle.
7. At the end of the Cool Down Cycle the damper closes to the wash position. Important Note: Refer to
your Command Center Tech Manual for specific text displayed upon completion of a Cool Down
Cycle.
8. The exhaust fan can now be restarted.
Important Note: The water sprays do not come on during a Fire Mode
System Duct
Nozzle
System Plenum
Nozzle
the Closed Position
Extinguishing
System
Appliance
Nozzle
__________________________________________________Chapter 2 - Principle of Operation, Page 2-9
Signal sent to
(if wired)
CG3-UVi
Closes to Fire
Position
None
Yes
CG3-UVi-FDL
Baffle Fixed
None
Yes
CG3-UVi-FDT
Baffle Fixed
Closes if fuse link reaches
activation temp
Yes
CG3-UVi-FDD
Baffle Fixed
Closes if fuse link reaches
activation temp
No Thermostat
CG3-UVi-ND
Baffle Fixed
None
No Thermostat
Table T-2-9-1
Internal Fire Mode – Cont.
Series Baffle #1 Duct Collar Damper
Internal Fire Mode (Thermostat Activated)
building fire
alarm system
Fire Extinguishing Systems
The National Fire Protection Association Standard 96 (NFPA-96) and the International Fire Code (IFC)
requires the use of a Fire Extinguishing System to cover the cooking surfaces, Ventilator exhaust plenums
(the area behind the grease extractors), and the exhaust duct (Refer to Figure 2-8-1). Upon activation of
the Fire Extinguishing System the follow will occur:
1. Fire extinguishing agent will discharge through the cooking equipment nozzles, the plenum nozzles
and the duct nozzle(s).
2. The protected cooking equipment and possibly other cooking equipment will shut off. Refer to the
above referenced codes for specific equipment that must shut off.
3. If the Fire Extinguishing System is wired to a building fire alarm system the alarm will activate.
4. If the Fire Extinguishing System is wired to a building management system it will notify of a fire
condition.
5. The Fire Extinguishing System should be wired to the Gaylord Command Center. If wired the
following will occur:
a) If the exhaust and supply fan were on the exhaust fan would stay on and the supply fan would
b) If the Ventilator Wash Cycle was on it would shut off.
6. After discharge, the Fire Extinguishing System must be recharged and certified by a fire system
contractor before the cooking equipment can be turned back on.
For Operation and Maintenance of the Fire Extinguishing System, refer to the system manufacture’s
Owner’s Manual.
Important: NFPA-96 requires inspection and certification of Fire Extinguishing Systems every 6 months.
shut off. It the exhaust and supply fans were off, the exhaust fan would come on and the supply
fan would stay off.
Chapter 2 - Principle of Operation, Page 2-10_________________________________________________
Caution: Exposure to UV light is harmful to skin and eyes.
The CG3-UVi Ventilator is equipped with panels and Safety Interlocks to protect operators from direct
exposure to UV light. All safety precautions called for in this manual must be followed to avoid the
potential for harm to operators or service personnel. Refer to Page 4-3 for complete description of
safety precautions.
Caution: Always turn on the exhaust fan before turning on the cooking equipment.
Caution: The chemical fire extinguishing system may discharge if the exhaust fan is not on while the
cooking equipment is on or still hot.
Caution: Never operate the Ventilator with the UV Module Access Doors or the Extractor Inspection
Doors open (Refer to Figure 2-3-1).
Operation of the exhaust fan and UV Lamps is controlled by the Gaylord Command Center located on the
Wash Control Cabinet (Refer to Figure 3-2-1). To start the exhaust fan and turn on the UV Lamps push
the START FAN button on the Command Center. The Command Center may be programmed to
automatically start the exhaust fan at a specific time. Refer to the Technical Manual for your specific
Gaylord Command Center for complete operating instructions of the Command Center.
When the START FAN button is pushed the following occurs:
1. Baffle #1 begins opening from the wash position to the exhaust position (Refer to Figure 2-6-1
and 3-2-3). Note: Baffle #1 only opens on Models CG3-UVi and CG3-UVi-FDL Series. Baffle #1 is
fixed on Models CG3-UVi-FDT, CG3-UVi-FDD and CG3-UVi-ND Series. The Ventilator model
number can be found on the Ventilator Nameplate (Refer to Appendix “A” for a sample of the
Nameplate). Refer to page 1-3 for a complete explanation of model numbers.
Important Note: Refer to your Command Center Technical Manual for specific text displayed
while the baffle #1 is opening.
2. The supply fan comes on.
3. After baffle #1 fully opens (elapsed time approximately
(Refer to Figure 3-3-1). Important Note: Refer to your Command Center Technical Manual for
specific text displayed after baffle #1 opens.
4. Once the exhaust fan reaches operating speed, the UV
Status Light on each Ventilator section will come on (Refer to Figure 3-4-1). The Ventilator is
now in the operational exhaust mode. Important Note: Refer to your Command Center
Technical Manual for specific text displayed when the Ventilator is in the operational exhaust
mode.
Note 1: Typically CG3-UVi Series Ventilators installed in the United States are equipped with a Gaylord
Autostart Controller that automatically turns on the exhaust fan if the temperature at the sensors
mounted in the canopy exceeds 90°F. (Refer to Figure 3-3-1). In some instances Ventilators installed
outside the United States will include an Autostart Control. Inclusion of an Autostart Control is
designated by the suffix “AS” in the model number. The Ventilator model number can be found on the
Ventilator Nameplate (Refer to Appendix “A” for a sample of the Nameplate). Refer to your Command
Center Technical Manual for complete information on the Autostart Control.
Note 2: The UV Lamps will not come on unless all the Extractor Inspection Doors and UV Module Access
Doors are closed as shown in Figure 3-2-3.
UV Status Lights
Each Ventilator section contains a bank of UV Status Lights to monitor the UV System (Refer to Figure 34-1). There are three colored lights, Green, Yellow and Blue. They indicate the system status as follows:
1. Green On: The UV system is operating properly.
2. Yellow On: One or more UV Lamps are not operating. If the yellow is on, less UV is being generated;
3. Blue On: One or more Extractors Inspection Doors or UV Module Access Doors are not closed or
Autostart Sensors
Depending Upon
Length of Ventilator
Ventilator Showing Autostart Sensor
however it does not prevent the operation of the Ventilator or indicate an unsafe condition.
latched properly. During this condition the UV System is not operating.
for complete instructions on programming wash times. If you do not have a Technical
Manual for your Command Center, obtain the model number from the nameplate on the
Figure 3-4-1
Starting the Exhaust Fan and UVi System – Cont.
In addition to the Status Lights on the Ventilator, the Gaylord Command Center displays text indicating
the similar message as the Status Lights. Refer to your Command Center Technical Manual for specific
text displayed.
Note: If either the Yellow or Red light are on refer the Troubleshooting section of this manual beginning
on page 5-1 for corrective action.
The Command Center illustrated in this manual may not represent the model of Command
Center you have. Refer to the Technical Manual for your specific model of Command Center
Command Center and contact Gaylord Industries. Refer to page 1-1 for contact information.
Turning Off the Exhaust Fan and Starting the Wash Cycle
Caution: Always turn off the cooking equipment and allow to cool before turning off the exhaust fan.
The chemical fire extinguishing system may discharge if the cooking equipment is on or hot when the
exhaust fan is off.
To turn off the exhaust fan and UV Lamps and start the Wash Cycle push the START WASH button on the
Gaylord Command Center (Refer to Figure 3-2-1). If the Command Center is programmed to
fan automatically, then the stop button does not need to be pushed.
When the START WASH button is pushed the following occurs:
1. The exhaust and supply fans shut off.
2. The UV lamps shut off and the green UV System Status Light will shut off.
3. Baffle #1 begins closing forward to the wash position
approximately 45 seconds. Note: Baffle #1 only move to the wash position on Models CG3-UVi
and CG3-UVi-FDL Series. Baffle #1 is fixed on Models CG3-UVi-FDT, CG3-UVi-FDD and CG3-UViND. Refer to pages 1-5 and 1-6 for complete explanation. Important Note: Refer to your
Command Center Technical Manual for specific text displayed while the baffle #1 is moving to
the wash position.
4. After baffle #1 closes to the wash position, the Wash Cycle comes on spraying hot,
detergent injected water, through the spray nozzles washing away the day’s grease, dust
lint accumulation from the baffles, the particulate separator, and gray dust from the UV
and
Module, flushing it
drain system (Refer to Figure 3-6-1). The Wash
programmed in the
equipment, 4 minutes for light /medium duty equipment, 5 minutes for mediumequipment, 7 minutes for heavy-duty equipment and 9 minutes for extra heavy duty
equipment. Important Note: Refer to your Command Center Technical Manual for specific text
displayed while the Ventilator is in a Wash Cycle.
5. Upon completion of the Wash Cycle, the baffle #1 stays in the
exhaust fan is re-started. Closing the baffle saves building energy by not allowing conditioned air
from drafting up the exhaust duct, or in cold climates prevents cold air from coming down the
duct and into the kitchen.
Note 1: If the Ventilator is equipped with a Gaylord Autostart Controller, the exhaust fan will stay on if
the temperature at the sensor mounted in the canopy exceeds 90°F. (Refer to Figure 3-3-1). Once the
temperature drops below 90°F., the fan will continue to run for 15 minutes and then shut off.
Note 2: The Command Center control may be programmed to automatically turn off the exhaust fan at a
specific time. Refer to your Command Center Technical Manual for complete operating instructions.
down to the main gutter which slopes to drain that leads to the building
Command Center. The typical wash times are 3 minutes for light-duty
grease extraction baffles, particulate separator and UV Lamps. The Command Center
to the Technical Manual for your specific model of Command Center for complete
instructions on programming wash times. If you do not have a Technical Manual for your
Sloping Gutter
UV Module
Wash Manifolds
Particulate
Baffle #1 In the
Drain To Building
Figure 3-6-1
Turning Off the Exhaust Fan and Starting the Wash Cycle – Cont.
With Spray Nozzles
Drain System
Wash Cycle
Length of Wash
The length of the Wash Cycle is primarily determined by the type of cooking equipment involved; Light
Duty, Light/Medium, Medium Duty, Heavy Duty, and Extra Heavy Duty as shown Table T-3-7-1.. The
factory recommended wash times are shown on table T-3-7-1however the length of the Wash Cycle to
adequately clean the Ventilator may vary depending on the following:
1. Actual amount of cooking within the hours of fan operation.
2. Type of food product being cooked.
3. Water pressure. Required pressure is 40 psi Min. to 80 psi Max.
4. Water temperature. Required temperature is 140 degrees F. Min. to 180 degrees F. Max.
5. Type of detergent. Refer to page 3-8for recommend detergent.
6. Ratio of detergent to water.
Separator
Wash Position
The wash cycle may be programmed for different times as needed to adequately clean the
illustrated in this manual may not represent the model of Command Center you have. Refer
Command Center, obtain the model number from the nameplate on the Command Center
and contact Gaylord Industries. Refer to page 1-1 for contact information.
FORMULA G-510EF is the only cleaner recommended by Gaylord Industries for use in the wash down
system of The Gaylord Ventilator. FORMULA G-510EF is a concentrated colloid cleaner specially
formulated to remove the daily accumulation of grease inside the Ventilator without damaging the
rubber and synthetic parts of the solenoid valves and the detergent pumping system. FORMULA G510EF is safe for kitchen personnel and has a variety of uses.
FORMULA G-510EF Safety
FORMULA G-510EF is registered with the U.S. EPA’s Design for the Environment Program (DfE)which
seeks to promote the use of institutional cleaners and maintenance products with improved
environmental and human health characteristics.
FORMULA G-510EF for the Ventilator Wash System
Pour FORMULA G-510EF directly into the detergent tank located inside the Wash Control Cabinet (Refer
to Figure 2-11-2). The detergent pump injects the detergent into the Main Feed Line where it dilutes
with the hot water at the proper ratio (Refer to Figure 2-11-2).
FORMULA G-510EF for Cleaning the Ventilator Exterior
Mix one part FORMULA G-510EF to twenty parts water in hand spray bottle. Spray on, let stand for a few
minutes and wipe off.
FORMULA G-510EF for Other Cleaning Jobs
The colloidal action of FORMULA G-510EF makes it a cleaner especially well-suited for use in kitchens.
The colloids break up dirt and grease into millions of tiny particles that constantly repel each other.
These particles cannot recombine or redeposit on a surface and are, therefore, easily washed away.
FORMULA G-510EF contains no harsh chemicals, yet offers outstanding performance on the toughest
cleaning jobs.
Use a mixture of one part FORMULA G-510EF to twenty parts water for:
- VINYL/PLASTIC/WALLS...Removes dirt, grease, food deposits and fingerprints.
- REFRIGERATORS...Removes dirt, spilled milk, blood, mildew and objectionable odors.
- RESTROOMS...Add a disinfectant to clean all fixtures, walls, floors, etc.
Use a mixture of one part FORMULA G-510EF to five parts water for extremely heavy grease build-up,
such as on the floor and on equipment around deep-fryers. Spray on, let set for a few minutes and rinse
or wipe off. For extremely soiled areas, gentle agitation, followed by a soaking period, will result in more
thorough cleaning. DON’T be afraid to experiment with FORMULA G-510EF because it contains no
phosphates, nitrates, enzymes, sulfates, suffocates or silicates.
Loading...
+ 92 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.