Furuno 10n, etr6 User Manual

Page 1
NETWORK SOUNDER
ETR-6/10N
Page 2
(
C
9-52, Ashihara-cho, Nishinomiya, Japan
Telephone: 0798-65-2111 Telefax: 0798-65-4200
All rights reserved.
Printed in Japan
FIRST EDITION : MAR. 2001
PUB. No. OME-20240
MIMA)
ETR-6/10N
Page 3

SAFETY INSTRUCTIONS

WARNING
ELECTRICAL SHOCK HAZARD
Do not open the equipment unless totally familiar with electrical circuits and service manual.
Only qualified personnel should work inside the equipment.
Turn off the power at the switchboard before beginning the installation.
Fire or electrical shock can result if the power is left on.
Do not install the equipment where it may get wet from rain or water splash.
Water in the equipment can result in fire, electrical shock or equipment damage.
WARNING
Install the transducer according to the installation instructions.
Failure to install the transducer correctly may result in water leakage and damage to the ship's hull.
Be sure no water leaks in at the trans­ducer mounting location.
Water leakage can sink the vessel. Also, confirm that the transducer will not loosen by ship's vibration. The installer of the equipment is solely responsible for the proper installation of the equipment. FURUNO will assume no responsibility for any damage associated with improper installation.
Be sure that the power supply is compatible with the voltage rating of the equipment.
Connection of an incorrect power supply can cause fire or equipment damage. The voltage rating of the equipment appears on the label above the power connector.
i
Page 4
CAUTION
Ground the equipment to prevent mutual interference.
Observe the following compass safe distances to prevent interference to a magnetic compass:
Standard compass
Network Sounder
0.80 m 0.55 m
Do not allow warm water or any liquid other than seawater or freshwater to contact the transducer.
Damage to the transducer may result.
Do not install the transducer where noise or air bubbles is present.
Performance will be affected.
Turn off the power at the switchboard
when will not be used for a long period.
Turn off the power at the switchboard
or detach the power cable from the connector to turn off the equipment when trouble occurs.
Steering
compass
CAUTION
The transducer cable must be handled carefully, following the guidelines below.
Keep fuels and oils away from the
cable.
Locate the cable where it will not be damaged.
The cable sheath is made of chloro­ phrene or polychloride vinyl, which
is easily by damaged plastic solvents such as toulene. Locate the cable well away from plastic solvents.
Use the correct fuse.
Use of a wrong fuse can cause fire or equipment damage.
A warning label is attached to the equip­ment. Do not remove the label. If the label is missing or illegible, contact a FURUNO agent or dealer.
WARNING
To avoid electrical shock, do not remove cover. No user-serviceable parts inside.
Name: Warning Label (1) Type: 86-003-1011-0 Code No.: 100-236-230
ii
Page 5

TABLE OF CONTENTS

SAFETY INSTRUCTIONS.................................................................................. i
SYSTEM CONFIGURATION............................................................................ iv
EQUIPMENT LISTS .......................................................................................... v
1. MOUNTING ................................................................................................... 1
1.1 Network Sounder....................................................................................................... 1
1.2 Thru-hull Mount Transducer 520-5PSD, 520-5MSD.................................................. 2
1.3 Transom Mount Transducer 520-5PWD,
Optional Transom Mount Triducer 520ST-PWD........................................................ 5
1.4 Inside-hull Mount Transducer 520-5PSD, 520-5MSD................................................7
1.5 Optional Water Temp erature/Speed Sensors............................................................ 9
1.6 Optional Water Temp erature Sensors..................................................................... 10
1.7 Optional Triducer 524ST-M S D................................................................................ 12
2. WIRING........................................................................................................ 13
2.1 Wiring...................................................................................................................... 13
2.2 Optional Sensors..................................................................................................... 15
2.3 Optional 50 kHz and 200 kHz T ransducers.............................................................. 17
3. INITIAL SETTINGS ..................................................................................... 18
3.1 Selecting the Transmission Power........................................................................... 18
3.2 Replacing the Fuse................................................................................................. 19
3.3 LED Lamp............................................................................................................... 19
SPECIFICATIONS....................................................................................... SP-1
PACKING LISTS ........................................................................................... A-1
OUTLINE DRAWINGS .................................................................................. D-1
INTERCONNECTION DIAGRAM...................................................................S-1
SCHEMATIC DIAGRAM.................................................................................S-2
iii
Page 6

SYSTEM CONFIGURATION

Network Sounder
ETR-6/10N
NAVnet series
Radar
Plotter
NAVnet series
Rectifier
PR-62
Ship's Mains
12-24 VDC
HUB*
Distribution Box
MB-1000
Radar
Plotter
Radar
Plotter
Radar
Plotter
1 kW
100/110/220/230 V AC , 1φ, 50/60 Hz
*: HUB may be connected to 3 sets of NAVnet radar or plotter.
: Standard : Option : External Equipment
iv
Transducer 520-5PSD 520-5PWD 520-5MSD
Triducer 525ST-MSD 525ST-PWD 524ST-MSD 520ST-PWD
Water temperature/ speed sensor ST-02MSB ST-02PSB
Water temperature sensor T-02MTB T-02MSB T-03MSB
Transducer 50B-6/6B/6G 50B-62M 50B-9B 50B-92M
50/200-1T
50/200-12M
Transducer 200B-5/5S
Page 7

EQUIPMENT LISTS

Standard supply
No. Name Type Code No. Qty Remarks 1 Network Sounder ETR-6/10N - 1 2 Spare Parts SP02-04301 - 1 set 3 Installation
Materials
CP02-06800 000-027-897 MJ-A3SPF0013-035 (3 A)
MJ-A6SPF0014-050 (5 m)
1 set
CP02-06810 000-027-898
+Tapping screw MJ-A3SPF0013-035 (3 A) +Tapping screw
v
Page 8
Optional supply
No. Name Type Code No. Remarks 1 Distribution
Box
2 Cable Assy.
3 Inside Hull
Kit S
4 Triducer
5 Transducer
7 Temperature
Sensor
8 Cable Assy. 02S4147 000-141-082 10P-10, 6P
9 Rectifier PR-62
MB-1000 000-040-809 For 1 kW
02S4089 000-133-622 10P-8P,
For MB-1000 MJ-A6SPF0014-010 000-144-421 6P-6P, 1 m, For NAVnet MJ-A6SPF0014-050 000-144-422 6P-6P, 5 m, For NAVnet MJ-A6SPF0014-100 000-144-423 6P-6P, 10 m, For NAVnet MJ-A6SPF0014-200 000-144-424 6P-6P, 20 m, For NAVnet MJ-A6SPF0014-300 000-144-425 6P-6P, 30 m, For NAVnet MJ-A6SRMD/TM11AP8-005 000-144-463 For HUB 22S0191 000-802-598
524ST-MSD 000-015-224 520ST-PWD 000-015-128 525ST-MSD 000-144-528 525ST-PWD 000-144-526 520-5PSD 000-015-204 520-5PWD 000-015-126 520-5MSD 000-015-127 50B-6 000-015-042 10 m, For 1 kW 50B-6B
50B-6G 000-015-016 10 m 50B-9B 000-015-065 15 m, For 1 kW 50B-62M 000-015-251 For 1 kW 50B-92M 000-015-252 For 1 kW 200B-5 000-015-027 10 m, For 1 kW 200B-5S 000-015-029 10 m, For 1 kW 50/200-1T 000-015-170 10 m, For 1 kW 50/200-12M 000-015-171 10 m ST-02MSB 000-137-986 6 ST Sensor ST-02PSB 000-137-987 T-02MTB 000-040-026 T-02MSB 000-040-040 T-03MSB 000-040-027
000-015-043 15 m, For 1 kW 000-015-018 30 m, For 1 kW 000-015-255 40 m, For 1 kW
Speed/Temperature sensor
For the water
temperature/speed sensor
000-013-484 100 VAC 000-013-485 110 VAC 000-013-486 220 VAC 000-013-487 230 VAC
vi
Page 9

1. MOUNTING

1.1 Network Sounder

Mounting considerations
The network sounder can be installed on the deck or on the bulkhead. When selecting a mounting location for t he network sounder, keep the following in mind:
The temperature and humidity should be moderate and stable.
Locate the unit away from exhaust pipes and vents.
The mounting location should be well ventilated.
Mount the unit where shock and vibration are minimal.
• Keep the unit away from electromagnetic field-generating equipment such as motors and generators.
• Leave slack in cables for maintenance and servicing ease.
• A magnetic compass will be affected if the network sounder placed too close to the magnetic compass. Observe the following compass safe distances to prevent disturbance to the magnetic compass:
a) Standard com pass: 0. 80 m eters b) Steering compass: 0.55 meters
Mounting procedure
Fasten the network sounder to the mounting location with four tapping screws (4 x 16).
Note: Do not install the equipment where it may get wet from rain or water splash.
Waterproof level is IPX2 (IEC 60529).
Tapping screw (4x16)
Figure 1-1 Mounting the network sounder
1
Page 10

1.2 Thru-hull Mount Transducer 520-5PSD, 520-5MSD

Transducer mounting location
This type of mounting provides the best performance of all, since the transducer protrudes from the hull and the effect of air bubbles and turbulence near the hull skin is reduced. When the boat has a keel, the transducer should be at least 30 cm away from it. Typical thru-hull mountings are shown in the figure on the next page.
The performance of this sounder is directly related to the mounting location of the transducer, especially for high-speed cruising. The installation should be planned in advance, keeping the standard cable length (8 m) and the following factors in mind:
• Air bubbles and turbulence caused by movem ent of the boat seriously degrade the sounding capability of the transducer. The transducer should, therefore, be located in a position where water flow is the smoothest. Noise from the propellers also adversely affects performance and the transducer should not be m ounted nearby. The lifting strakes are notorious for creating acoustic noise, and these must be avoided by keeping the transducer inboard of them.
• The transducer must always remain submerged, even when the boat is rolling, pitching or up on a plane at high speed.
• A practical choice would be somewhere between 1/3 and 1/2 of the boat’s length from the stern. For planing hulls, a practical location is generally rather far ast ern, so that the transducer is always in water regardless of the planing attitude.
Transducer outline drawings
120
30
22
68
520-5PSD
All dimensions in millimeters
120
28
68
520-5MSD
24
Ship's bow
87
Figure 1-2 Dimensions of transducers 520-5PSD, 520-5MSD
2
Page 11
Acceptable transducer mounting locations
Deep-V hull
* Position 1/2 to 1/3 length of the hull from stern. * 15 to 30 cm from center line (inside first lifting strakes).
Figure 1-3 Transducer mounting location on deep-V hull
High speed V-planing hull
* Within the wetted bottom area * Deadrise angle within 15
°
Figure 1-4 Transducer mounting location on high speed V-planing hull
Typical thru-hull mount transducer installations
Flat washer
Rubber
Fairing block
Hull bottom
Deep-V Hull
Figure 1-5 Typical thru-hull mount transducer installations
washer
Flat Hull
Hull bottom
3
Page 12
Procedure for installing the thru-hull mount transducer
1. With the boat hauled out of the water, mark the location selected for mounting the transducer on the bottom of the hull.
2. If the hull is not level within 15° in any direction, fairing blocks made out of teak should be used between the transducer and hull, both inside and outside, to keep the transducer face parallel with the water line. Fabricate the fairing block as shown below and make the entire surface as smooth as possible to provide an undisturbed flow of water around the transducer.
The fairing block should be smaller than t he transducer itself to provide a channel to
divert turbulent water around the sides of the transducer rather than over its face.
Hole for stuffing tube
Upper half
BOW
Lower half
Saw along slope of hull.
Figure 1-6 Construction of fairing block
3. Drill a hole just large enough t o pass the threaded stuffing tube of the transducer through the hull, making sure it is drilled vertically.
4. Apply a sufficient amount of high quality caulking compound to the top surface of the transducer, around the threads of the st uffing tube and inside the m ounting hole (and fairing blocks if used) to ensure watertight mount ing.
5. Mount the transducer and fairing blocks and tighten the locking nuts. Be sure that the transducer is properly oriented and its working face is parallel to the water line.
Note: Do not over-stress the stuffing t ube and locking nuts through excessive tightening,
since the wood block will swell when the boat is placed in the water. It is suggested that the nut be tightened lightly at installat ion and retightened several days after the boat has been launched.
4
Page 13

1.3 Transom Mount Transducer 520-5PWD, Optional Transom Mount Triducer 520ST-PWD

This type of mounting is very commonly employed for outboard motor boats. Do not use this method on an inboard mot or boat because turbulence is created by the propeller ahead of the transducer.
There are two methods of installation: flush with hull (for flat hulls) and projecting from hull (for deep V-hulls).
Flat Hull
Figure 1-7 Transom mount transducer mounting locations
Deep V -hull
Installing the transom mount transducer flush with hull (for flat hulls)
A suitable mounting location is at least 50 cm away from the engine and where the water flow is smooth.
1. Drill four pilot holes in the mounting location.
2. Attach the t r ansducer to the bracket with tapping screws (supplied).
3. Adjust t he t r ansducer position so the transducer faces right to the seabed.
Note: If necessary, to improve water flow and minimize air bubbles staying on the
transducer face, incline the transducer about 5° at the rear. This may require a certain amount of experimentation for fine tuning at high cruising speeds.
4. Fill the gap between the wedge front of the transducer and transom with epoxy material
to eliminate any air spaces.
5
Page 14
M5x20
Tape
Figure 1-8 Transom mount transducer, mounting flush with hull
Installing the transom mount transducer projecting from hull (for deep-V hulls)
This method is em ployed on deep-V hulls and provides good perf ormance because the effects of air bubbles are minimal. Install the tr ansducer parallel with water surface; not flush with hull. If the boat is placed on a trailer care must be taken not to dam age the transducer when the boat is hauled out of the water and put on the trailer.
M5x20
M5x20
No.2
Figure 1-9 Transom mount transducer, projecting from hull
M5x14
Transducer preparation
Before putting the boat in water, wipe the face of the transducer thoroughly with a detergent liquid soap. This will lessen the time necessary for the transducer to have good contact with the water. Otherwise the time required for com plete “saturation” will be lengthened and performance will be reduced.
Note: Do not paint the transducer. Performance will be affected.
6
Page 15

1.4 Inside-hull Mount Transducer 520-5PSD, 520-5MSD

Necessary tools
You will need the following tools:
• Sandpaper (#100)
• Silicone sealant
• Silicone grease
Remarks on installation
• Turn off the engine and anchor the boat while installing the equipment.
• Install the transducer in the engine room.
Selecting the mounting location
Keep the following points in mind when selecting a mounting location:
• The mounting location should be where the hull is of single-hull thickness and is void of
air or flotation mat erials ot her than solid fiberglass between the transducer face and the water.
• Do not place the transducer over hull struts or ribs which run under the hull.
• Avoid a location where the rising angle of the hull exceeds 15°, to minimize the effect of
the boat’s rolling.
• You will finalize the mounting location through some trial and error. The procedure for
this is shown later.
Center line
50cm
50cm
Figure 1-10 Inside-hull transducer mounting location
1/2
15cm 15cm
1/3
Mounting location for transducer
7
Page 16
Attaching the inside-hull mount transducer
1. Clean the transducer face to remove any foreign material. Lightly roughen the transducer face with #100 sandpaper. Also, roughen the inside of the hull where the transducer is to be mounted.
2. Warm the silicone sealant t o 40°C before usage to soften it. Coat t he transducer face and mounting location with silicone sealant.
Transducer face
Silicone sealant
Figure 1-11 Coating the transducer face with silicone sealant
3. Press the transducer firmly down on the hull and gently twist it back and forth to remove any air which may be trapped in the silicone sealant.
Squeeze out air bubbles.
Silicone sealant
Hull
Figure 1-12 Attaching transducer to hull with silicone sealant
8
Page 17

1.5 Optional Water Temperature/Speed Sensors

Through-hull mount water temperature/speed sensor ST-02MSB, ST-02PSB
Select a suitable mounting location considering the following:
• Select a mid-boat flat position. The sensor does not have to be installed perfectly perpendicular. The sensor must not be damaged in dry-docking operation.
• Select a place apart from equipment generating heat.
• Select a place in the forward direction viewing from the drain hole, t o allow for circulation of cooling water.
• Select a place free fr om vibration.
1. Dry-dock the boat.
2. Make a hole of approx. 51 mm in diamet er.
3. Unfast en locknut and remove the sensor section.
4. Apply high-grade sealant to the flange of the sensor.
5. Pass the sensor casing through the hole.
6. Face the notch on the sensor toward boat’s bow and tighten the flange.
7. Set the sensor section to the sensor casing and tighten the locknut.
8. Launch the boat and check for water leakage around the sensor.
Locknut
Face "notch" toward bow.
Flange nut
Coat with silicone sealant.
Figure 1-13 Water temperature/speed sensor ST-02MSB, ST-02PSB
Brim
51
φ77
123
9
Page 18

1.6 Optional Water Temperature Sensors

Transom mount water temperature sensor T-02MTB
• Fix the cable at a convenient location with cable clamp.
• When the cable is led in through the transom board, make a hole of approx. 17 mm in diameter to pass the connector. After passing the cable, fill the hole with a sealing compound.
D>50cm
Figure 1-14 How to install transom mount water temperature sensor T-02MTB
D
M5x20
Mount sensor flush with hull bottom.
10
Page 19
Thru-hull mount water temperature sensor T-02MSB, T-03MSB
Select a suitable mounting location considering the following points:
• Select a mid-boat flat position. The sensor does not have to be inst alled perfectly perpendicular. However, the location should not be such that the transducer may be damaged when the boat is dry-docked.
• Locate away from equipment which gives off heat.
• Locate away from drain pipes.
• Select a location where vibration is minimal.
T-02MSB T-03MSB
Sensor Holder
Sensor cable
Locknut Washer Gasket
Locknut
Locknut
φ21 mm
Coat with sealant.
Mounting procedure
1. Drill a hole of 21 mm in diameter in the mounting location.
2. Pass the sensor cable through the hole.
3. Pass gasket, washer and locknut onto cable in that order.
4. Coat the sensor flange with high quality sealant and then fasten the sensor with the locknut. (Torque: max. 59N·m)
5. Launch the boat to check for water leakage around the sensor.
Washer
Gasket
φ25 mm
Coat with sealant.
Plate thickness
Holder Guide
within 25 mm
Mounting procedure
1. Drill a hole of 25 mm in diameter in the mounting location.
2. Coat holder guide with high quality sealant, and pass gasket, washer and locknut onto holder guide in that order and then tighten the locknut.
3. Set the sensor holder to the holder guide from inside the boat and then tighten the locknut.
4. Launch the boat to check for water leakage around the sensor.
Figure 1-15 Assembling thru-hull water temperature sensor T-02MSB, T-03MSB
11
Page 20

1.7 Optional Triducer 524ST-MSD

The triducer is designed for thru-hull m ounting.
Mounting considerations
When selecting a mounting location keep the following points in m ind:
• Air bubbles and turbulence caused by movement of the boat seriously degrade the sounding capability of the transducer. The transducer should, therefore, be located in a position where water flow is the smoothest. Noise from the propellers also adversely affects performance and the transducer should not be mounted nearby. The lifting strakes are notorious for creating acoustic noise, and these must be avoided by keeping the transducer inboard of them.
• The transducer must always remain submerged, even when the boat is rolling, pitching or up on a plane at high speed.
• A practical choice would be somewhere between 1/3 and 1/2 of the boat’s length fr om the stern. For planing hulls, a practical location is generally rather far ast ern, so that the transducer is always in water regardless of the planing attitude.
φ79 mm
133 mm
2.00"-12 UN threads
φ51 mm
27 mm
Figure 1-16 Dimensions of triducer 524ST-MSD
140 mm
7 mm
12
Page 21

2. WIRING

2.1 Wiring

All wiring is terminated at the network sounder.
Network sounder
Ground terminal
NAVnet equipment or HUB
Ground
WhiteBlack
Shield
Transducer
Figure 2-1 Network sounder
Battery
Power cable
Connect the power cable to the power connector. Connect the leads to the battery (12-24 VDC); white to plus (+) terminal and black to minus (-) term inal.
Cable connector
Power cable w/fuse (3A)
Lead wire
Black
White
Shield
BATTERY
Figure 2-2 Connecting the power cable to the battery
13
Page 22
Transducer, optional triducer
Connect the transducer cable to the XDR connector.
Ground
Connect the ground wire (2.0sq) to ship's ground to prevent interference to the picture. Shorten the ground wire as much as possible. For FRP vessels, install a ground plate that measures about 20 cm by 30 cm on the outside of the hull bottom to provide a ground point.
CAUTION
Ground the equipment to prevent mutual interference.
Note: Use a "closed" lug to make the ground connection at the net work sounder. Do not
use an "open-type" lug (
).
14
Page 23

2.2 Optional Sensors

Water temperature sensor
Connect the water temperature sensor (option) or water temperature/speed sensor (option) to the XDR port with the converter connector (Type: 02S4147, Code No.: 000-141-082, option).
MJ-A6SRMD
MJ-A10SPF
Temperature sensor
MJ-A10SRMD
Transducer
SHIELD TEMP TEMP0V NC NC NC
NC NC NC NC NC NC NC XDR+ XDR SHIELD XDR-
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
10
1 4 7 3 2 5 6 8 9
10
Figure 2-3 Connection of water temperature speed sensor
SPD TEMP TEMP0V SHIELD +V NC NC XDR+ XDR SHIELD XDR-
XDR port on the ETR-6/10N
Connection of water temperature/speed sensor
MJ-A6SRMD
Temperature/ speed sensor
Transducer
SHIELD TEMP TEMP0V/SPD0V SPD +V NC
MJ-A10SRMD
NC NC NC NC NC NC NC XDR+ XDR SHIELD XDR-
Figure 2-4 Connection of water temperature/speed sensor
1 2 3 4 5 6
1 2 3 4 5 6 7 8 9
10
MJ-A10SPF
4 7 3 1 2 5 6 8 9
10
TEMP TEMP0V SPD0V/ SHIELD SPD +V NC NC XDR+ XDR SHIELD XDR-
XDR port on the ETR-6/10N
15
Page 24
Connect to XDR port at network sounder
MJ-A10SPF
MJ-A6SRMD MJ-A10SRMD
Tape connector with self-vulcanizing tape and then vinyl tape to waterproof connector. Bind tape end with cable tie.
Water temp., water temp/speed sensor connector
Transducer connector
Figure 2-5 Connection of transducer, water temperature sensor,
water temperature/speed sensor
16
Page 25

2.3 Optional 50 kHz and 200 kHz Transducers

To connect optional transducer 50B-6, 50B-6B, 50B-6G, 50B-62M, 50B-9B, 50B-92M, 200B-5, 200B-5S, 50/200-1T or 50/200-12M, the optional Distribution Box (MB-1000, code no. 000-040-809) is required. Additionally, a cable assembly (02S4089, code no. 000-133-622) is required to connect to the network sounder. Fasten the cable from the Distribution Box to the XDR connector on the network sounder.
Jumper block setting
TRANSDUCER
50B-6/6B/6G 50B-62M 50B-9B 50B-92M
50kHz
200kHz
SHIELD
RED RED
BLK
BLK
TB2
1 2 3 4 5
02P6168
J2 J1
3 2 1
TB1
WHT
BLK
200B-5/5S
50/200-1T
or
50/200-12M
(SHIELD)
(RED)
(BLU)
(GRN)
(BLK)
TB2
1 2 3 4 5
TB1
1 2 3
Figure 2-6 Distributor MB-1000
Distribution Box (Type: MB-1000, Code No.: 000-040-809)
J2: Full power output J1: Reduced output
Shield
To network sounder (cable is fitted with 8P connector. 8P-10P converter connector is re­quired.)
(BLK)
(SHIELD)
(WHT)
Name Type Code No. Qty Remarks
Distribution Box
MB-1000 000-040-805
1 Cable w/8P connector supplied for
connection to network sounder Crimp-on Lug FV1.25-3 Red 000-538-113 6 Cord Lock NC-1 000-516-650 1 For use with separate transducer
Fabrication of transducer cable
Fabricate the transducer cable as illustrated below to connect it to the Distr ibution Box.
Vinyl Sheath
Crimp-on lug FV1.25-3, Red
Clamp here.
Figure 2-7 Fabrication of transducer cable
Tape
Vinyl Tube
Shield
17
Page 26

3. INITIAL SETTINGS

WARNING
ELECTRICAL SHOCK HAZARD
Do not open the equipment unless totally familiar with electrical circuits and service manual.
Only qualified personnel should work inside the equipment.

3.1 Selecting the Transmission Power

The default transmission power is 600 W. If you install the 1 kW transducer, change the jumper connector to #3-4 f r om #1-2 on J12 as follows:.
1. Detach the power cable from the connector.
2. Open the cover of the ETR-6/10N.
3. Remove the jumper connector on J12 by using long-nose pliers.
4. Insert it t o #3-4 pins of the J12 for 1 kW transducer. Note: Do not insert the jumper connector upside down.
5. Close the cover.
NET
03P9284
J800
J6
1-2 3-4
J3
J12
02P6294
Fuse (4A)
J2
J1
Figure 3-1 Location of parts inside ETR-6/10N
J12 #1-2: for 600 W (Default) #3-4: for 1 kW
18
Page 27

3.2 Replacing the Fuse

The 3 A fuse in the snap-in fuse holder on the power cable protects the equipment from equipment fault and reverse polarity of the ship’s mains. If the f use blows find out the cause before replacing it. If t he fuse blows again after replacement, contact a F URUNO agent or dealer for advice. If the LED lamp on the front panel does not light, t he 4 A fuse inside the network sounder may have blown. In the case, contact a FURUNO agent or dealer for advice.
CAUTION
Use the correct fuse.
Use of a wrong fuse can cause fire or equipment damage.

3.3 LED Lamp

The green LED lamp on the front panel lights or flashes according to equipment st ats. When a radar or plott er is OFF, or the network sounder is not connected to a radar or plotter, the LED lamp flashes for 3 minutes and then lights cont inuously. When a radar or plotter is ON, the LED lamp flashes continuously.
LED lamp Lighting (after flashing 3 minutes): A radar or plotter is OFF or the net cable is disconnected or damaged.
Flashing: The network sounder works with a radar or plotter.
Figure 3-2 LED lamp
19
Page 28
SPECIFICATIONS OF THE NETWORK SOUNDER
ETR-6/10N
1. GENERAL
1.1. Output Power 600 W/ 1 kW rms nominal, 1 kW requires optional MB-1000
1.2. TX Frequency 50 kHz or 200 kHz, 50/200 kHz exchangeable
1.3. Amplifier type Log amplifier
1.4. Network protocol Ethernet 10BASE-T
1.5. Depth Range and Pulse Repetition Rate
Range (m)
2 1500
5 1500
10 750
40 375
100 150
200 75
400 41
1200 12
2. POWER SUPPLY
2.1. Main Unit 12-24 VDC: 1.0-0.5 A, 12.0 VA max. (at 1 kW output)
Stand-by: 1.0 VA or less
3. ENVIRONMENTAL CONDITION
3.1. Ambient Temperature -15°C to +55°C
PRR /min.
3.2. Relative Humidity 95% at 40°C
3.3. Water proofing IPX2
3.4. Vibration IEC 60945
4. COATING COLOR
4.1. Main Unit N3.0
SP - 1
E2024S01A.doc
Page 29
Page 30
Page 31
Page 32
Page 33
Loading...