Frymaster, a member of the Commercial Food Equipment Service Association, recommends
using CFESA Certified Technicians.
24-Hour Service Hotline 1-800-551-8633
Price: $10.00
819-5712
11-01
Please read all sections of this manual and retain for future reference.
NOTICE
This appliance is intended for professional use only and is to be operated by qualified
personnel only. A Dean Factory Authorized Service Center (FASC) or other qualified
professional should perform installation, maintenance, and repairs. Installation, maintenance,
or repairs by unqualified personnel may void the manufacturer’s warranty. See Chapter 1 of
this manual for definitions of qualified personnel.
NOTICE
This equipment must be installed in accordance with the appropriate national and local codes of
the country and/or region in which the appliance is installed.
NOTICE
Drawings and photos used in this manual are intended to illustrate operational, cleaning and
technical procedures and may not conform to onsite management operational procedures.
NOTICE TO OWNERS OF UNITS EQUIPPED WITH COMPUTERS
U.S.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: 1) This device may not cause harmful interference, and 2) This device must accept
any interference received, including interference that may cause undesired operation. While
this device is a verified Class A device, it has been shown to meet Class B limits.
Canada
This digital apparatus does not exceed the Class A or B limits for radio noise emissions as set
out by the ICES-003 standard of the Canadian Department of Communications.
Cet appareil numerique n’emet pas de bruits radioelectriques depassany les limites de classe A
et B prescrites dans la norme NMB-003 edictee par le Ministre des Communications du Canada.
DANGER
Improper installation, adjustment, maintenance or service, and unauthorized alterations or
modifications can cause property damage, injury, or death. Read the installation, operating and
service instructions thoroughly before installing or servicing this equipment. Only qualified
service personnel may convert this appliance to use a gas other than that for which it was
originally configured. See Chapter 1 of this manual for definition of qualified service personnel.
DANGER
Adequate means must be provided to limit the movement of this appliance without depending
upon the gas line connection. Single fryers equipped with legs must be stabilized by installing
anchor straps. All fryers equipped with casters must be stabilized by installing restraining
chains. If a flexible gas line is used, an additional restraining cable must be connected at all
times when the fryer is in use.
DANGER
The front ledge of the fryer is not a step. Do not stand on the fryer. Serious injury can result
from slips or contact with the hot oil.
DANGER
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any
other appliance.
DANGER
Instructions to be followed in the event the operator smells gas or otherwise detects a gas leak
must be posted in a prominent location. This information can be obtained from the local gas
company or gas supplier.
DANGER
The crumb tray in fryers equipped with a filter system must be emptied into a fireproof container
at the end of frying operations each day. Some food particles can spontaneously combust if left
soaking in certain shortening material. Additional information can be obtained in the filtration
manual included with the system.
WARNING
No structural material on the fryer should be altered or removed to accommodate placement of
the fryer under a hood. Questions? Call the Dean Service Hotline at 1-800-551-8633.
WARNING
Do not bang fry baskets or other utensils on the fryer’s joiner strip. The strip is present to seal
the joint between the frypot. Banging fry baskets on the strip to dislodge shortening will distort
the strip, adversely affecting its fit. It is designed for a tight fit and should only be removed for
cleaning.
IMPORTANT
Safe and satisfactory operation of Dean equipment depends upon its proper installation.
Installation MUST conform with local codes, or in the absence of local codes, to European
Community (CE) Standards.
NOTICE
The Commonwealth of Massachusetts requires any and all gas products to be installed by a
licensed plumber or pipe fitter.
KSCF18G Cool Zone Gas Fryers
INSTALLATION & OPERATION MANUAL
TABLE OF CONTENTS
Page #
1. INTRODUCTION 1-1
2. IMPORTANT INFORMATION 2-1
3. INSTALLATION INSTRUCTIONS 3-1
4. DAILY OPERATION 4-1
5. FILTRATION 5-1
6. PREVENTATIVE MAINTENANCE 6-1
7. TROUBLESHOOTING 7-1
8. PARTS LIST 8-1
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 1: INTRODUCTION
1.1 Applicability and Validity
The KSCF18G Cool Zone Series gas model family has been approved by the European Union
(EU) for sale and installation in the following EU countries: AT, BE, KE, KD, ES, FI, FR, GB,
IE, IT, LU, NL, NO, PT and SE.
This manual is applicable to and valid for all KSCF18G gas units sold in English-speaking
countries, including those in the European Union. Where conflicts exist between instructions
and information in this manual and local or national codes of the country in which the
equipment is installed, installation and operation shall comply with those codes.
This appliance is only for professional use and shall be used by qualified personnel as defined
in Section 1.7.
1.2 After Purchase
In order to improve service, have the following chart filled in by the Frymaster Authorized Service
Technician who installed this equipment.
Authorized Service
Technician/FASC
Address
Telephone/Fax
Model Number
Serial Number
Gas Type
1.3 Ordering Parts
Customers may order parts directly from their local factory authorized service center. For this
address and phone number, contact your factory authorized service center or call the Frymaster
Service Hotline phone number, 1-800-551-8633.
To speed up your order, provide the model number, serial number, gas type, part needed, item part
number (if known), and quantity needed.
1-1
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 1: INTRODUCTION
1.4 Service Information
Call the Frymaster Service Hotline, 1-800-551-8633, for the location of your nearest factory
authorized service center. To assist you more efficiently, always provide the service technician with
the model number, gas type, serial number, and the nature of the problem.
1.5 Computer Information
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC rules. While this device is a verified Class A device, it has been
shown to meet the Class B limits. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of
the equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
The user is cautioned that any changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
If necessary, the user should consult the dealer or an experienced radio and television technician for
additional suggestions.
The user may find the following booklet prepared by the Federal Communications Commission
helpful: "How to Identify and Resolve Radio-TV Interference Problems". This booklet is available
from the U.S. Government Printing Office, Washington, DC 20402, Stock No. 004-000-00345-4.
1.6 Safety Information
Before attempting to operate your unit, read the instructions in this manual thoroughly.
Throughout this manual, you will find notations enclosed in double-bordered boxes similar to the
ones below.
CAUTION
CAUTION boxes contain information about actions or conditions that may cause or result in a
malfunction of your system.
WARNING
WARNING boxes contain information about actions or conditions that may cause or result in
damage to your system, and which may cause your system to malfunction.
1-2
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 1: INTRODUCTION
1.6 Safety Information (cont.)
DANGER
DANGER boxes contain information about actions or conditions that may cause or result in injury
to personnel, and which may cause damage to your system and/or cause your system to malfunction.
1.7 Service Personnel
1.7.1 Definitions
A. Qualified and/or Authorized Operating Personnel
1. Qualified/authorized operating personnel are those who have carefully read the information
in this manual and have familiarized themselves with the equipment functions, or have had
previous experience with the operation of equipment covered in this manual.
B. Qualified Installation Personnel
1. Qualified/authorized personnel are those who have carefully read the information in this
manual and have familiarized themselves with the equipment functions, or who have had
previous experience with the operation of the equipment covered in this manual.
C. Qualified Service Personnel
1. Qualified service personnel are those who are familiar with Frymaster equipment and have
been authorized by Frymaster to perform service on Frymaster equipment. All authorized
service personnel are required to be equipped with a complete set of service parts manuals
and stock a minimum amount of parts for Frymaster equipment. A list of Frymaster Factory
Authorized Service Centers (FASCs) was included with the fryer when shipped from the
factory. Failure to use qualified service personnel will void the Frymaster warranty on your equipment.
1-3
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 2: IMPORTANT INFORMATION
2.1 Receiving and Unpacking Equipment
A. Check that the container is upright. Use an outward prying motion - no hammering - to
remove the carton. Unpack the fryer carefully and remove all accessories from the carton.
Do not discard or misplace these, as they will be needed.
B. After unpacking, immediately check the equipment for visible signs of shipping damage. If
damage has occurred, contact the carrier and file the appropriate freight claims. Do not
contact the factory. Shipping damage responsibility is between the carrier and the dealer.
If your equipment arrives damaged:
1. File claim for damages immediately, regardless of extent of damage.
2. Visible loss or damage: Be sure this is noted on the freight bill or express receipt and is
signed by the person making the delivery.
3. Concealed loss or damage: If damage is unnoticed until equipment is unpacked, notify
freight company or carrier immediately, and file a concealed damage claim. This should
be done within fifteen (15) days of date of delivery. Be sure to retain container for
inspection.
NOTE: Frymaster Does Not Assume Responsibility for Damage or Loss Incurred in Transit.
C. Frying systems with built-in filtration: Take off the filter support brace and remove the
filter pan from the cabinet.
D. Remove all plastic skin from sides, front, and doors of the fryer(s). Failure to do this prior to
initial fryer operation will make it very difficult to remove later.
2.2 General
Upon arrival, inspect the fryer carefully for visible or concealed damage. (See Receiving and
Unpacking Equipment in Section 2.1.)
The Frymaster KSCF18G Cool Zone Series Fryers are energy-efficient, gas-fired units, designcertified by the International Approval Services (AGA/CGA), Gaz de France, NSF International and
manufactured to their basic performance and application specifications.
All units are shipped completely assembled with accessories packed inside the frypots. All units are
adjusted, tested and inspected at the factory before shipment. Sizes, weights and input rates of all
models are listed in this manual.
2-1
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 2: IMPORTANT INFORMATION
2.3 Principles of Operation
The incoming gas flows through orifices and is mixed with air in the burners to create the correct
ratio for proper combustion. The mixture is ignited at the front end of each heat tube by the pilot
light. Internal diffusers slow the flame as it goes through the burner tube. This slower and more
turbulent flame gives much better heat transfer to the walls of the tubes, thereby heating the oil more
efficiently.
2.4 Rating Plate
This is attached to the inside of the front door panel. Information provided includes the model and
serial number of the fryer, BTU/hr (kW/hr) input of the burners, outlet gas pressure in inches W.C.
(mbars) and whether the unit has natural (G20/25) or propane (G31) gas orifices.
2.5 Pre-Installation
DANGER
This appliance is equipped with a three-prong (grounding) plug for your protection
against electrical shock, and must be plugged directly into a properly grounded
three-prong receptacle. Do not cut, remove, or otherwise bypass the grounding
prong on this plug.
A. General: Only licensed personnel should install any gas-fired equipment.
1. A manual gas shut-off valve must be installed in the gas supply line ahead of the fryers for
safety and ease of future service.
2. The Frymaster KSCF18G gas fryers require 120 volts (AC) 60-cycle electrical service for
non-CE installation (U.S./Canada/Mexico) and 230 volts (AC) 50-cycle electrical service
for CE/International installations. Fryers are equipped with a 16-3 SJT grounded flexible
power cord for a direct connection to the power supply. Amperage draw for each unit
depends on the accessories supplied with the unit. See detailed instructions packaged with
the fryer line-up.
DANGER
No structural material on the fryer should be altered or removed to accommodate
placement of the fryer under a hood. Questions? Call the Frymaster Service Hotline
at 1-800-551-8633.
2-2
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 2: IMPORTANT INFORMATION
2.5 Pre-Installation (cont.)
DANGER
This appliance must be installed with sufficient ventilation to prevent the occurrence
of unacceptable concentrations of substances harmful to the health of personnel in
the room in which it is installed.
B. Clearances: The fryer area must be kept free and clear of all combustibles. This unit is design-
certified for the following installations:
1. Commercial installation only (not for household use).
2. Non-combustible floor installation equipped with factory-supplied 6-inch (15-cm)
adjustable legs or 5-inch (13-cm) casters;
3. Combustible construction with a minimum clearance of 6-inches (15-cm) side and 6-inches
(15-cm) rear, and equipped with factory-supplied 6-inch (15-cm) adjustable legs or 5-inch
(13-cm) casters.
C. Installation Standards
1. U.S. installations must meet: 2. Canadian installations must meet:
American National Standard Institute CAN 1-B149 Installation Codes
ANSI Z83.11 Canadian Gas Association
American Gas Association 55 Scarsdale Road
8501 E. Pleasant Valley Road Don Mills, ONT, M3B 2R3
Cleveland, OH 44131
National Electrical Code Canadian Electric Code c22.1, part 1
ANSI/NFPA #70 Canadian Standards Association
American National Standard Institute 178 Rexdale Blvd.
1430 Broadway Rexdale, ONT, M9W 1R3
New York, NY 10018
NFPA Standards #96 and #211
National Fire Protection Association
470 Atlantic Avenue
Boston, MA 02110
3. CE/EXPORT STANDARDS: Fryer installation must conform with local codes, or in the
absence of local codes, to the appropriate national or European Community (CE)
standards.
2-3
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 2: IMPORTANT INFORMATION
2.6 Air Supply and Ventilation
DANGER
Do not connect this appliance to the gas supply before reviewing each step in this
section.
A. Keep the area around the fryer clear to prevent obstruction of combustion and ventilation airflow
as well as for service and maintenance and adhere to the following:
1. Do not connect this fryer to an exhaust duct.
2. Correct installation and adjustment will ensure adequate airflow to the fryer system.
3. A commercial, heavy-duty fryer’s combustion wastes must be vented to the outside of the
building. A deep-fat fryer must be installed under a powered exhaust hood, or an exhaust
fan must be provided in the wall above the unit, as exhaust gas temperatures are
approximately 800-1000°F (427-538°C). Check air movement during installation. Strong
exhaust fans in the exhaust hood or in the overall air conditioning system can produce
slight air drafts in the room, which can cause erratic burner flames and/or improper fryer
operation.
4. Do not place the fryer’s flue outlet directly into the plenum of the hood, as it will affect the
gas combustion of the fryer.
5. Never use the interior of the fryer cabinet for storage or store items on shelving over or
behind the fryer. Exhaust temperatures can exceed 800°F (427ºC) and may damage or
melt items stored in or near the fryer.
6. Adequate distance must be maintained from the flue outlet of the fryer(s) to the lower edge
of the filter bank. Per NFPA Standards No. 96, a minimum of 18-inches (45-cm) should be
maintained between the flue(s) and the lower edge of the exhaust hood filter.
7. Filters and drip troughs should be part of any industrial hood, but consult local codes before
constructing and installing any hood. The duct system, the exhaust hood and the filter
bank must be cleaned on a regular basis and kept free of grease.
B. After the fryer has been positioned under the exhaust hood, ensure the following has been
accomplished:
1. Adequate means must be provided to limit the movement of fryers without depending upon
gas connections. If a flexible gas hose is used, a restraining cable must be connected at all
times when the fryer is in use. The restraining cable and installation instructions are
packed with the flexible hose in the accessories box that was shipped with your unit.
2-4
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 2: IMPORTANT INFORMATION
2.6 Air Supply and Ventilation (cont.)
2. Single unit fryers must be stabilized by installing restraining chains on appliances
equipped with casters or anchor straps on appliances equipped with legs. Follow
instructions shipped with the casters/legs to properly install the chains or straps.
DANGER
Do not attach an apron drain board to a single unit. The appliance may become
unstable, tip over, and cause injury. The appliance area must be free and clear of
combustible material at all times.
2.7 Equipment Installed at High Altitudes
A. The fryer input rating [BTU/hr (kW/hr)] is for elevations up to 2,000 feet (610-m). For
elevations above 2,000 feet (610-m), the rating should be reduced four percent for each
additional 1,000 feet (305-m) above sea level.
B. The correct orifices are installed at the factory if operating altitude is known at time of the
customer’s order.
2.8 Conversion of Units
Pressure:
1 mbar = 10.2 mm water column (mm W.C.) = 0.4 Inch WC
20 mbar = 204 mm W.C. = 8 Inch W.C.
1-Inch W.C. = 25.4 mm W.C. = 2.5 mbar
Heat Input:
1 kW = 3410 BTU/hr
100 BTU/hr = 0.0293 kW
Temperature:
0º Celsius = 32º Fahrenheit
Temperature in degrees Celsius = (Temperature in degrees Fahrenheit (F) – 32) X 0.555
100° Celsius = (212º Fahrenheit – 32) X 0.555
2-5
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.1 Installing the Fryer
Qualified, licensed, and/or authorized installation or service personnel only (as defined in
Section 1.7) should perform the following:
• Installation and service on Frymaster equipment.
• Conversion of this appliance from one gas type to another.
Failure to use qualified, licensed, and/or authorized installation or service personnel to install,
convert to another gas type or otherwise service this equipment will void the Frymaster
warranty and may result in damage to the equipment or injury to personnel.
Where conflicts exist between instructions and information in this manual and local code or
national codes, or regulations, installation and operation shall comply with the codes or
regulations in force in the country in which the equipment is installed.
A. Initial Installation: If installed with legs, do not push against any unit edges to adjust its position.
Use a pallet or lift jack to lift it slightly and place it where it is to be installed.
B. Relocating the Fryer: If relocating a fryer installed with legs, remove all weight from each leg
before moving.
Note: If a leg becomes damaged during movement, contact your service agent for immediate
repair/replacement.
DANGER
Building codes prohibit a fryer with its open tank of hot oil/shortening being installed
beside an open flame of any type, including those of broilers and ranges.
3.2 Leg and Caster Installation
DANGER
Frymaster fryers equipped with legs are for permanent installations. Fryers fitted
with legs must be lifted during movement to avoid damage and possible bodily
injury. For a moveable or portable installation, optional equipment casters must be
used. Questions? Call 1-800-551-8633
A. General
1. Install legs and rear rigid casters near where the fryer is to be used, as neither are secure for
long transit. Unit cannot be curb mounted and must be equipped with the legs and rear rigid
casters provided.
3-1
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.2 Leg and Caster Installation (cont.)
2. When positioning the fryer, gently lower the fryer into position to prevent undue strain to
the legs and internal mounting hardware. Use a pallet or lift jack to lift and position the
fryer if possible. Tilting the fryer may damage the legs.
3. The rigid casters must be installed on the fryer rear channel assembly only.
4. Proceed to Step 3.3, Leveling the Fryer, after legs and rear rigid casters are installed to
ensure the fryer is level before using.
B. Leg and Rigid Caster Installation
1. Remove unit from pallet.
2. Carefully raise unit with forklift, pallet jack, or other steady means.
3. Place one lock washer on each hex head screw.
4. Insert hex head screws with lock washers [1/4-20 threads by ¾" (19-mm) long] through bolt
holes of leg mounting plates and mount to the front channel. Mount rigid casters to the rear
channel following the same procedure. Locknuts have been attached to the topside of the
base mounting plates at the factory to capture hex head screws as they are screwed in.
5. Tighten the bolts to 50 inch-lbs. (5.65 joules) minimum torque.
WARNING
For caster retrofit, the unit must be at room temperature and drained of shortening
before installing the casters.
3.3 Leveling the Fryer
A. Place a carpenter’s spirit level across the top of the fryer and level the unit front-to-back. If the
fryer is off level side to side, a platform or other surface adjustment is needed; there is no side to
side level adjustments on a fryer equipped with caster/leg combinations (If a fryer is equipped
with legs only, side to side level adjustments can be made. If a fryer is equipped with casters
only, no level adjustments to the fryer can be made.). If the fryer is not level, the unit may not
function efficiently, the oil may not drain properly for filtering and in a multi-fryer battery, it
may not match adjacent units.
Legs (Only)
1. Adjust leg height with an adjustable or 1-1/16-inch (27-mm) open-end wrench by turning
the hex bullet on the bottom of the leg.
3-2
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.3 Leveling the Fryer (cont.)
2. The hex bullet is for minor leg height adjustment only. Do not adjust more than 1-inch (25mm).
3. When leveling the unit, the leg body should be held firmly to keep the leg from bending or
rotating while turning the hex bullet foot to the required height.
Rigid Casters (Only)
1. Install the rigid casters on the fryer rear channel only. Legs must be installed on the front
channel.
2. There are no level-adjustments for the rigid casters.
B. If the floor is uneven or has a decided slope, place the fryer on a smooth platform.
C. If the fryer is moved, re-level the fryer following the instructions given in Steps 3.3.A-C.
D. Installing Optional Swivel Casters
1. Install non-locking casters only at the rear of the unit.
2. Locking casters must be installed at the front of the unit. Locking casters allow the fryer to
be "locked" in position for safe operations.
3. Follow the same instructions for leg installations as given above in steps 3.2, B1-5.
Front View
1/4-20 x 3/4 Hex Bolt
:
Rear Side View
Optional Caster-
Rear Only
Optional Caster-
Front Only
Front Channel
or Rear Channel
Front or Rear Leg with
Mounting Plate
Adjust as needed
Front Channel or
Rear Channel
Leg Support Assembly
Washer
1/4-20 Hex Head Locknut
1/4-20 x 3/4 Hex Bolt
Rear Caster—5" Rigid
Leg and Caster (Optional) Mounting Installation
3-3
Front Caster—5" Swivel
w/Brak e
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.3 Leveling the Fryer (cont.)
ANSI Z83.11a-(Latest Edition) requires a fryer be restrained to prevent tipping when installed
in order to avoid the splashing of hot liquid. The means of restraint may be the manner of
installation, such as connection to battery of appliances or installing the fryer in an alcove, or
by separate means, such as adequate ties (chains, straps, etc.). A bracket has been provided on
the fryer back panel for this purpose.
NOTE: The installation must be inspected after it is complete to ensure it meets the intent of
these instructions. The on-site supervisor and/or operator(s) should be informed that the
appliance is installed with restraints. If restraints are removed to move fryer (cleaning
beneath and behind, relocation, etc.), ensure that they are re-installed when fryer is returned
to its permanently installed position.
3.4 Gas Connections
KSCF18G Cool Zone Series gas fryers have obtained CE markings for countries and gas categories
shown below:
Countries Supply Pressures and
Gas (mbar)
G20 20/25 I2E (R) B G20 20
BE Belgium
G31 37 I3P
Appliance
Categories
Countries Supply Pressures and
Gas (mbar)
GR Greece
G31 37 and 50
Appliance
Categories
II2H3P
DE Germany
DK Denmark G20 20 I2H IT Italy G20 20 I2H
ES Spain
FR France
GB Great Britain
G20 20 I2E G20 20
G31 50 I3P
G20 20 G20/G25 20/25
II2H3P LU Luxembourg
G31 37 and 50
G20/G25 20/25 G25 25
II2ESI3P NL
G31 37 and 50
G20 20 G20 20
II2H3P PT Portugal
G31 37
IR Ireland
The
Netherlands
G31 37
G31 50
G31 50
G31 37
II2H3P
II2E3P
II2L3P
II2H3P
The gas supply (service) line must be the same size or greater than the fryer inlet line. KSCF18G
gas fryers are equipped with a 3/4" (22-mm) male inlet. The gas supply line must be sized to
accommodate all gas-fired equipment connected to that gas supply. Consult local gas
companies/suppliers or your local contractor for minimum supply line requirements.
3-4
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.4 Gas Connections (cont.)
Supply Line Specifications
The gas supply lines must be sized as indicated in the chart below, based on the total number of
fryers connected to the main gas supply.
Gas Types Number of Fryers
1 2 to 3 4 or more (*)
Natural Gas 3/4" (22 mm) 1" (28 mm) 1 1/4" (35 mm)
Propane Gas 1/2" (15 mm) 3/4" (22 mm) 1" (28 mm)
(*) When exceeding 18 feet (6 meters) for a configuration of more than four fryers, it is necessary
to provide a 1 1/4" (35 mm) rigid gas connection.
Recommended Gas Supply Line Sizes
DANGER
All connections must be sealed with a joint compound suitable for the gas being
used and all connections must be tested with a solution of soapy water before
lighting any pilots.
Never use matches, candles, or any other ignition source to check for leaks. If gas
odors are detected, shut off the gas supply to the appliance at the main shut-off
valve and immediately contact the local gas company or an authorized service
agency for service.
DANGER
"Dry-firing" your unit will cause damage to the frypot and can cause a fire. Always
ensure that melted shortening, cooking oil or water is in the frypot before firing the
unit.
DANGER
Before connecting new pipe to this appliance, the pipe must be blown out
thoroughly to remove all foreign material. Foreign material in the burner and gas
controls will cause improper and dangerous operation.
3-5
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.4 Gas Connections (cont.)
Rigid Connections
Check any installer-supplied intake pipe(s) visually and clean metal particles or other foreign matter
from the threads before installing into a service line. If the intake pipes are not clear of all foreign
matter, the orifices will clog when gas pressure is applied. When using thread compound on gas
piping, use very small amounts and only on male threads. Use a pipe thread compound that is not
affected by the chemical action of LP gases. DO NOT apply thread compound to the first two pipe
threads—doing so will cause clogging of the burner orifices and control valve.
Manual shut-off valve
This gas service supplier-installed valve must be installed in the gas service line ahead of the fryers
in the gas stream and in a position where it can be reached quickly in the event of an emergency.
Regulating Gas Pressure
The fryer and shut-off valve must be disconnected from the gas supply during any pressure testing of
the system.
External gas regulators are not normally required on this fryer. A safety control valve protects the
fryer against pressure fluctuations. If the incoming pressure is in excess of ½" PSI (3.45 kPa/35
mbar), a step-down regulator will be required.
DANGER
When pressure-testing incoming gas supply lines, disconnect the fryer from the gas
line if the test pressure is 3,45 kPa (½" PSI, 14" W.C.) or greater to avoid damage to
the fryer’s gas piping and gas valve(s).
The fryer and its individual shut-off valve must be disconnected from the gas supply piping system
during any pressure testing of the gas supply system, especially if the test pressures are in excess of
½" PSI (3.45 kPa/35 mbar).
A. Manifold Pressure: Your local service technician should check the manifold pressure with a
manometer.
1. Check the rating plate for manifold gas pressures. Natural gas units normally require 4"
WC, and propane units normally require 11" WC gas pressure.
2. Confirm that the arrow forged into the bottom of the regulator body, which indicates gas
flow direction, is pointed downstream towards the fryers. The air vent cap is also part of the
regulator and should not be removed.
3-6
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.4 Gas Connections (cont.)
3. If a vent line from the gas pressure regulator is used, it should be installed in accordance
with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1-(Latest Edition).
WARNING
Use a diluted soap solution to find potentially dangerous gas leaks when making
new connections.
B. Regulators: Gas regulators can be adjusted in the field, but no adjustments should be made
unless the regulator is out of adjustment, or serious pressure fluctuations are observed.
C. Only qualified service personnel should make adjustments to the regulators.
D. Orifices: The fryer can be ordered to operate on any available gas. The correct combination
gas valve, appropriate burner orifices, and pilot burners are installed at the factory. While
the valve can be adjusted in the field, only qualified service personnel should make any
adjustments with the proper test equipment.
DANGER
If gas odors are detected, the gas supply must be shut off at the main shut-off valve.
The local gas company or FASC should be contacted immediately to rectify the
problem.
E. Flexible Couplings, Connectors and Casters:
1. If the fryer is to be installed with flexible couplings and/or quick-disconnect fittings, the
installer must use a heavy-duty AGA design-certified commercial flexible connector of
at least 3/4" NPT (with suitable strain-relief attachments), in compliance with the
Standard for Connectors for Movable Gas Appliances, ANSI Z21.69-(Latest Edition)
and Addenda Z21.69a-(Latest Edition). Quick disconnect devices must comply with the
Standard for Quick-Disconnect Devices for Use with Gas Fuel, ANSI Z21.41-(Latest
Edition).
2. For an appliance equipped with casters, the installation shall be made with a connector
that complies with the Standard for Connectors for Movable Gas Appliances, ANSI
Z21.69, or Connectors for Moveable Gas Appliances, CAN/CGA-6.16. A quickdisconnect device that complies with the Standard for Quick-Disconnect Devices for Use
with Gas Fuel, ANSI Z21.41, or Quick-Disconnect Devices for Use with Gas Fuel,
CANI-6.9 must be used. Under no circumstances are the connector and the quickdisconnect device, or its associated piping be used to limit fryer movement. A restraining
bracket is provided on the appliance structural back to prevent the unit from moving
from its installed position.
3-7
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.4 Gas Connections (cont.)
WARNING
Do not attach accessories to this fryer unless fryer is secured from tipping.
Personal injury may result.
3. The fryer must be restrained by means independent of the flexible coupling or connector
in order to limit the movement of the fryer. Clips are located on the back panel of the
fryer for the attachment of restraints.
4. If disconnection of the restraint is necessary, this restraint must be reconnected after the
fryer has been returned to its originally installed position.
F. After hook-up, bleed the gas line of air to ensure that the pilot light will ignite quickly and
evenly.
WARNING
Qualified personnel MUST perform any adaptation, modification, or gas conversion,
if required. Failure to use qualified personnel will void the Frymaster warranty.
3.5 Adjustments/Adaptation To Different Gases
A. Proper operation of appliances requires operator to scrupulously inspect the following
adjustments in terms of:
1. Gas inputs and pressures.
2. Voltage and polarities of electrical power supplies.
B. Frymaster gas fryers are manufactured to use the type of gas and pressure specified on the
rating plate. When changing gas, adaptation must be performed by qualified personnel
Failure to use qualified personnel will void the Frymaster warranty.
.
3-8
KSCF18G COOL ZONE SERIES GAS FRYERS
CHAPTER 3: INSTALLATION INSTRUCTIONS
3.6 Gas Inputs
A. Nominal "Qn" Heat Input for the KSCF18G Cool Zone Gas fryer is 25 kW.
B. Inputs for different gases are as follows:
G20
Natural Gas
(Type H)
20 mbar/ 8" WC
G25
Natural Gas
(Type L)
25 mbar/ 10" WC
G31 Propane 37 mbar/ 15" WC
C. Adjustments for different gases are as follows:
ORIFICE SIZE
(# / MM)
#42 / 2,40
#42 / 2,40
#53 / 1,51
GAS TYPE
G20
G25
G31
GAS PRESSURE AT
REGULATOR
MBAR INCH W.C.
10,0
15,0
27,0
4,0
6,0
10,8
BURNER
MARKING
Blue
Blue
Red
PILOT
MARKING
26N
26N
16LP
NOTE: Outlet gas pressure must be adjusted strictly within the above requirements 5 to 10 minutes
after the appliance is operating.
* For controls and adjustments, please refer to "gas valve" illustrations on page 3-11. (Pilot Flame
Adjustment: Turn the pilot adjustment screw clockwise/counter-clockwise until the desired flamevolume is achieved).
3-9
Loading...
+ 49 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.