Fluke i3000s Flex Series, i2000 Flex, i3000s 24 Flex, i3000s 36 Flex Instruction Sheet

i3000s/i2000 Flex
AC Current Probe
Instruction Sheet
Introduction
The i3000s 24 Flex, i3000s 36 Flex, and i2000 Flex AC Current Probes (hereafter referred to as “the Probe”) are used with oscilloscopes, digital multimeters, recorders or data loggers. The i3000s probes can be used to measure AC current up to 3000 A. The i2000 can be used to measure AC current up to 2000 A. The flexible measuring head allows current measurements on conductors that are hard to reach or inaccessible using typical clamp-on current probes.
The Probes provide a low-voltage (3 V AC for i3000s models, and 2 V AC for i2000) output that is proportional to the current being measured. The Probes provide full-scale direct readings for 30 A, 300 A, and 3000 A when using the i3000s models, and 20 A, 200 A, and 2000 A when using the i2000.
Symbols
The following table shows the symbols used on the product and/or in this manual.
®
Symbol Description
Do not dispose of this product as unsorted municipal
~
W
T
-
P
>
PN 2560447 March 2006
©2006 Fluke Corporation. All rights reserved.
waste. Contact Fluke or a qualified recycler for disposal.
Important Information. Refer to the manual.
Double/Reinforced insulation.
Do not apply around or remove from the HAZARDOUS LIVE conductors.
Complies with the relevant European standards.
Conforms to Underwriters’ Laboratory, Inc.
Safety Instructions
In this instruction sheet, a Warning identifies conditions and actions that pose hazard(s) to the user. A Caution identifies conditions and actions that may damage the calibrator or the test instruments.
WX Warning
To avoid electric shock or personal injury:
Use the Probes only if qualified.
Use caution during installation and use of
the Probe; high voltages and currents may be present in circuit under test.
Have maintenance performed by only
qualified service personnel.
Protect the probe against water and
humidity.
Wear protective clothing and gloves as
required.
Do not install this product on live
conductors. Always de-energize the circuit under test before installing the flexible measuring head.
Always inspect the electronics unit,
connecting cable, and flexible measuring head for damage before using the Probe.
Do not use the Probe if damaged.
Always connect Probe to display device
before installing the flexible measuring head.
Never change batteries while measurement
head is installed on conductor.
Never connect or disconnect the external
power supply while the measurement head is installed on a conductor.
Use only the provided original or specified
accessories.
Use the Current Probe only as specified in
the operating instructions; otherwise the current probe’s safety features may not protect you.
Adhere to local and national safety codes.
Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
CAT III equipment is designed to protect
against the transients in the equipment in fixed equipment installations, such as distribution panels, feeders and short branch circuits, and the lighting systems in large buildings.
Specifications
Electrical Characteristics
Measuring ranges
i3000s (24 and 36 Flex)
i2000 Flex
Output sensitivity 100 mV/10 mV/1 mV per A
Accuracy (at 25 ºC) ±1 % of range (45 – 65 Hz) Frequency range
i3000s (24 and 36 Flex) i2000 Flex
Phase error < ±1° (45 – 65 Hz),
Linearity ±0.2 % of reading from
Position sensitivity ±2 % of range with cable
External field ±1 % of range with cable
Minimum load
Noise
30 A/300 A/3000 A AC, switch selectable 20 A/200 A/2000 A AC, switch selectable
(AC coupled)
10 Hz to 50 kHz (-3 dB) 10 Hz to 20 kHz (-1 dB)
±10° (at 20 kHz)
10 %
- 100 % of range
>25 mm (1") from the coupling
>200 mm (8 in) from the head
100 ke for specified accuracy
8 mV RMS (0.3 % of range) in 30 A range
2 mV RMS (0.1 % of range) in 300 A and 3000 A