Instant power replay
solves a breaker trip
Testing Functions
Case Study
Measuring tools: Fluke 1750 Power
Recorder
After experiencing some nuisance tripping of breakers in the
subpanel feeding the second
floor of this industrial building,
we installed a Fluke 1750 Power
Recorder at the subpanel to
gather information about power
usage.
For several weeks, we experienced no circuit breaker trips,
and the recorded data from the
1750 showed excellent quality
power delivery.
The next week, using the current event detector with a 20
A threshold to match the single
phase branch feeds, we discovered that there were several
events where current exceeded
the breaker trip rating. While
there were no tripped breakers
during the week, it was clear
that something was overloading
the circuit to the point where a
breaker trip was likely to happen.
A search of the facility found
an employee who had moved
a Tenny temperature chamber
into a lab area and was using
it to perform elevated temperature tests on some products. The
Application Note
chamber was on wheels and
was plugged into a standard
120 V, 20 A branch outlet.
The power recorder captured
the operation of the temperature
chamber and its effect on the
power at the sub-panel.
Data analysis
The current event view shows
several events outside the 20 A
breaker tolerance curve. The longest event is shown in Figure 1.
The event exhibits a double
initial current surge, followed
by a sustained current over
20 amps. Although the circuit
breaker did not trip during this
event, its rating was exceeded
and it would be likely to trip
occasionally under similar conditions. These conditions are
frequent during use of the temperature chamber, as can be
seen in the graph above, where
this event is immediately followed by another similar event
whose beginning can be seen at
the right side.
Operator: Michael Gipe, Fluke Power
Electronics Engineer
Tests conducted: Power quality
event recording
From the Fluke Digital Library @ www.fluke.com/library
Figure 1. Current event view, top level events
Zooming into the initial region
of the event in Figure 2, we see
the turn-on loads of the temperature chamber’s dual compressor system. The first compressor
turns on with a large initial
surge, followed by the secondary compressor surge. This load
profile clearly identifies the temperature chamber as the cause of
the overload.
Temperature chamber peak
current is 49.7 amps. In Figure 3,
the sustained load is near
25 amps.
We can zoom in further,
in Figure 4, to see even more
detailed resolution of this initial current surge. Note that the
phase A voltage sags during this
current surge, but the voltage
drop is small, indicating that the
power feed at the sub-panel is
very stiff, and can accommodate
substantial demand.
Conclusion
The power feed to the second
floor is robust. The nuisance
tripping is most certainly due to
temporary overload of a standard
20 amp appliance branch circuit
from using an industrial temperature chamber on the circuit. The
temperature chamber should be
connected to a dedicated branch
circuit, sized to meet the requirements of the chamber, minimum
20 amps.
Figure 2. Compressor activity
Figure 3. Load evaluation
Figure 4. Interpreting voltage drop
2 Fluke Corporation Instant power replay solves a breaker trip
Fluke. Keeping your world
up and running.
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2007 Fluke Corporation. Specifications subject
to change without notice. Printed in U.S.A.
11/2007 3185343 A-EN-N Rev A
®