Fluke 1750, 1750/B, 1750-TF Case Studies

Instant power replay
solves a breaker trip
Testing Functions Case Study
Measuring tools: Fluke 1750 Power Recorder
After experiencing some nui­sance tripping of breakers in the subpanel feeding the second floor of this industrial building, we installed a Fluke 1750 Power Recorder at the subpanel to gather information about power usage.
For several weeks, we expe­rienced no circuit breaker trips, and the recorded data from the 1750 showed excellent quality power delivery.
The next week, using the cur­rent event detector with a 20 A threshold to match the single phase branch feeds, we dis­covered that there were several events where current exceeded the breaker trip rating. While there were no tripped breakers during the week, it was clear that something was overloading the circuit to the point where a breaker trip was likely to happen.
A search of the facility found an employee who had moved a Tenny temperature chamber into a lab area and was using it to perform elevated tempera­ture tests on some products. The
Application Note
chamber was on wheels and was plugged into a standard 120 V, 20 A branch outlet.
The power recorder captured the operation of the temperature chamber and its effect on the power at the sub-panel.
Data analysis
The current event view shows several events outside the 20 A breaker tolerance curve. The lon­gest event is shown in Figure 1.
The event exhibits a double initial current surge, followed by a sustained current over 20 amps. Although the circuit breaker did not trip during this event, its rating was exceeded and it would be likely to trip occasionally under similar con­ditions. These conditions are frequent during use of the tem­perature chamber, as can be seen in the graph above, where this event is immediately fol­lowed by another similar event whose beginning can be seen at the right side.
Operator: Michael Gipe, Fluke Power Electronics Engineer
Tests conducted: Power quality event recording
From the Fluke Digital Library @ www.fluke.com/library
Figure 1. Current event view, top level events
Zooming into the initial region of the event in Figure 2, we see the turn-on loads of the temper­ature chamber’s dual compres­sor system. The first compressor turns on with a large initial surge, followed by the second­ary compressor surge. This load profile clearly identifies the tem­perature chamber as the cause of the overload.
Temperature chamber peak current is 49.7 amps. In Figure 3, the sustained load is near 25 amps.
We can zoom in further, in Figure 4, to see even more detailed resolution of this ini­tial current surge. Note that the phase A voltage sags during this current surge, but the voltage drop is small, indicating that the power feed at the sub-panel is very stiff, and can accommodate substantial demand.
Conclusion
The power feed to the second floor is robust. The nuisance tripping is most certainly due to temporary overload of a standard 20 amp appliance branch circuit from using an industrial tempera­ture chamber on the circuit. The temperature chamber should be connected to a dedicated branch circuit, sized to meet the require­ments of the chamber, minimum 20 amps.
Figure 2. Compressor activity
Figure 3. Load evaluation
Figure 4. Interpreting voltage drop
2 Fluke Corporation Instant power replay solves a breaker trip
Fluke. Keeping your world up and running.
Fluke Corporation PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2007 Fluke Corporation. Specifications subject to change without notice. Printed in U.S.A. 11/2007 3185343 A-EN-N Rev A
®
Loading...