Flowserve CPM Supply Tank User Manual

Flow Solutions Division
CPM Seal Support Reservoir Assembly
Installation Instructions
Introduction
This manual covers the installation and operation of the CPM Seal Support Reservoir for dual non-pressurized (API Plan 52/ANSI Plan
7352) and dual pressurized seals (API Plan 53/ANSI Plan 7353). The following instructions describe the appropriate system, buffer/barrier fluids, installation, start-up, and maintenance.
Reservoir
The standard CPM Seal Support Reservoir is designed in accordance with ASME Code Section VIII, Division 1. All tanks are welded in accor­dance with ASME Code Section IX. Tanks include inlet, outlet, vent and fill along with two mounting lugs as minimum connections.
Sealing System Description
CPM Seal Support Reservoir can be used as reservoirs for dual pressur­ized Inside, dual pressurized inside/outside or dual non-pressurized Flowserve Seal designs. The sealing system produced is defined as being either a thermal convection system or a forced circulation system.
Support System Descriptions
An API Plan 53/ANSI 7353 is a pressurized dual seal system which is used in services where no process leakage to atmosphere is tolerated. The system consists of dual mechanical seals with a barrier fluid be­tween them. The barrier fluid in the supply tank is pressurized to a higher pressure (normally 25 psig [1.7 bar]) than the seal chamber maximum 160 psig [11 bar]). Primary (inboard) seal leakage will be barrier fluid into the product. Minimal leakage is customary.
An API Plan 53/ANSI Plan 7353 is usually chosen over an API Plan 52/ ASNI Plan 7352 for dirty, abrasive, or polymerizing products which would either damage the seal faces or cause problems with the barrier fluid system if an API Plan 52/ANSI Plan 7352 is used. Two conditions to consider when incorporating API Plan 52/ANSI Plan 7352; first, there will always be some leakage of barrier fluid into the product. Normally, this leakage will be minute, and the leakage rate can be monitored via the
2
© Copyright 2004 Flowserve Corporation
visual water flow indicator. However, when using API Plan 53/ANSI Plan 7353 the product must be able to accommodate a small amount of contamination from the barrier fluid. Secondly, an API Plan 53/ANSI Plan 7353 system is dependent on having the supply tank pressure main­tained at the proper level. If the supply tank pressure drops below seal chamber pressure, seal leakage direction will be reversed and the barrier fluid will be contaminated with the process fluid. The flush plan will then become an API Plan 52/ANSI Plan 7352.
An Induced Circulation System is essentially the same as the thermal convection system except for the addition of a circulating device in the seal cavity which provides for positive flow in the system. The addition of a circulating device provides for positive flow of buffer fluid shown in Figure 1. To maximize dual seal cooling add cooling coils inside the reservoir as a means of removing heat.
Dual Pressuzied Inside Seal with Induced Circulation through CPM Seal Support Reservoir with Cooling Coil
Figure 1
Plan 53/ANSI Plan 7353
vertical porting
outlet
end view
inlet
seal
tangential
or
porting
seal
end view
outlet
inlet
vent valve
pressure
gage
level gage
cooling out
visual water flow indicator
water pressure regulator and inlet port
304SS, 2 gallon reservoir
cooling in
drain
3
Loading...
+ 5 hidden pages