Flowserve Circulator User Manual

Experience In Motion
Flowserve Circulator
Instruction,Operation and
Maintenance Manual
Table of Contents
Section
A Installation, Start-up and Maintenance
1. Introduction
3. Start-up
3.4 Pressure control valve adjustment
3.5 Pressure relief valve reset procedure
4. Maintenance
5. Troubleshooting
B Piping and Instrumentation Diagram
C Kit Installation Instruction
1. Pressure switch
2. Accumulator
3. Level switch
4. Heat exchanger
5. Pressure gauge
D Customer Drawings
Section A: Installation, Start-up and Maintenance
2.3 Foundation/placement
1 Introduction
1.1 This manual is a valuable tool covering the circulator you have purchased.
1.2 Do not proceed with installation or operation until you have read and understand this manual.
1.3 Following is a step-by-step approach covering instal­lation, start-up, operation and maintenance of the circulator.
1.4 Familiarize yourself with and refer to the circulator drawing (Section B). Item numbers referred to in this
manual can be found on this drawing. Order specic
drawings can be found in Appendix 1.
1.5 The circulator purchased includes only the kit options shown on these drawings. Additional kits are available as described in Section C.
2.3.1 The foundation (customer steel base or con-
crete pad) for the circulator should be at and level, with anchor bolts set rmly in place.
A foundation weight of not less than 3 times
the weight of the circulator (when lled with barrier uid) is recommended as a minimum
for concrete foundations. Steel baseplates
shall have sufcient rigidity to prevent distort-
ing the circulator after bolt down.
2.3.2 The foundation must be free of all debris prior to placement of the circulator.
2.3.3 The circulator reservoir is fabricated such that the top is level. Gently lower the circulator onto the foundation and check to see if the level is maintained. If required, shim mounting feet level before bolting the circulator down. Mounting bolts should be torqued per manu-
facturer’s specications.
2.4 Interconnecting piping/tubing
2 Installation
2.1 Location
2.1.1 Circulator location and ambient temperature extremes must be taken into account. All inter­ connecting piping/tubing must be thermally
protected to insure a continuous ow of barrier uid.
2.1.2 Shading the circulator from direct sunlight is recommended.
2.1.3 Installation must take place during a time when ambient temperatures are above freezing or
with all uid lines protected from damage.
2.1.4 Follow notes listed on the circulator order drawings, in Appendix 1, covering utility require­ ments and control component points.
2.2 Lifting/uncrating
2.2.1 Remove the crating carefully to avoid damag­ ing components.
2.2.2 The circulator must be lifted only from the bottom or by the lifting lugs when provided. Lift carefully
2
to avoid damaging circulator components.
2.4.1 Definition: Interconnecting piping/tubing is all
uid piping/tubing between the circulator and
the process equipment.
2.4.2 Piping/tubing should be installed to meet local codes or other applicable standards.
2.4.3 The interconnecting piping/tubing system should be sized and constructed to minimize pressure losses and should not be less than the corresponding pipe/tube size and schedule as contained in the circulator (refer to the piping and instrumentation diagram of pipe size, schedule and material).
2.4.4 The interconnecting piping/tubing system, both to and from the seal, should be construct­ ed of similar material as the circulator.
2.4.5 Piping/tubing must not be supported by the circulator.
2.4.6 Before installing, the piping/tubing system should be checked for freedom from contami­ nation. If not completely free of contaminants,
clean and ush the entire interconnecting
piping/tubing system before connecting the cir­ culator. Once you are sure the piping/tubing system is free of contamination, drain the
ushing media and air blow dry.
Do not, under any circumstances, use the circulator to flush the interconnecting piping/tubing. Using the cir­culator to flush the interconnecting piping/tubing will void the warranty. The circulator is flushed clean and sealed at the factory.
It is the customer’s responsibility to familiarize them-
selves with the instrumentation and controls mounted on the circulator. The customer’s supplied control panel shall at minimum provide the functions listed and as described on the circulator drawings.
2.4.7 Connections to circulator: A teon paste pipe
sealant is recommended and should be applied no closer than two threads from the end of the
tting to avoid contamination.
2.4.7.1 Do not remove plugs from ports until
you are ready to make a nal connec-
tion.
2.4.7.2 Refer to the circulator drawings in Section B for connections to be made.
3 Start-up Operation
3.1 Initial start-up
3.1.1 Check all eld connections in piping/tubing to
see that the joints are tight. Also check and tighten circulator fasteners, which may have become loose during transit.
3.1.2 Verify the correct barrier uid type with the seal manufacturer before lling. Fill the reservoir to the top of the level gauge through the ller port
provided.
3.1.3 The pump/motor assembly does not require alignment.
3.1.4 Before connecting the motor power source. Disengage the pump/motor coupling. Connect the motor power source. Jog the motor (3-5 seconds) to check rotation against the rotation arrows. Reconnect the pump/motor coupling. Replace the coupling guard cover plate.
3.2 All instruments must be tied into the customer’s control panel to operate the main process equip­ment. Functions listed on the circulator drawings are the minimum requirements necessary to insure proper operation. The manufacturer may place more stringent requirements on sequencing of the main process equipment. It is recommended the customer contact the seal manufacturer to obtain a list of all operational sequences and interlocks to insure safe
and efcient operation.
3.3 This circulator is equipped with a Pressure Relief Valve (PRV-1) and a Pressure Control Valve (PCV-1). The pressure relief valve on the right end of the mani­fold is factory set at and should never be adjusted. The pressure contol valve on the left end of the mani­fold is factory set and will need adjustment to meet the requirements of the application. The pressure control valve can be adjusted using the following procedure and referring to the manufacturers service manual in Appendix 2 of this manual.
3.4 Pressure control valve adjustment
The pressure control valve located on the left end of the manifold is factory set at 200 psig (1379 kPa) and will need adjustment to meet the requirements of the application. Follow these steps to adjust the pressure control valve.
3.4.1 The uid temperature in the circulator must be
at the normal operating temperature to achieve the correct pressure setting.
3.4.2 To prevent accidental over pressurization of the seal, connect the seal supply port directly to the seal return port, bypassing the seal. This will protect the seal from high pressures during valve adjustment.
3.4.3 Completely open the pressure control valve on the left end of the manifold.
3.4.4 Start the circulator and allow to run long enough to remove any air from the system. All
uid ow should be through the pressure con-
trol valve, through the heat exchanger and back into the reservoir.
3.4.5 Slowly close the pressure control valve on the left end of the manifold until the desired system pressure is achieved.
3.4.6 Shut down the circulator and return any piping
to its original, normal operating conguration.
The pressure control valve is now set to the proper pressure.
3
3.5 Pressure relief valve reset procedure
4.2 Service of suction strainers
The pressure relief valve on the right end of the mani­fold is factory set at 450 psig (3103 kPa) and should not require adjustment. If however, the relief valve setting
has become suspect or the seal requires a lower setting, follow these steps to reset the pressure relief valve. Do not
exceed 450 psig (3103 kPa).
3.5.1 To prevent accidental over pressurization of the seal, connect the seal supply port directly to the seal return port. This will protect the seal from high pressures during valve adjust ­ ment.
3.5.2 Completely close the pressure control valve on the left end of the manifold.
3.5.3 Completely open the pressure relief valve on the right end of the manifold.
3.5.4 Start the circulator and allow to run long enough to remove any air from the system. All
uid ow should be through the pressure relief
valve and into the reservoir.
To service the suction strainer, the circulator pump must be shut off. Make sure the circulator motor cannot be auto started. Remove top plate of reservoir. Strainers should be checked and cleaned every 12 months.
4.3 Customer electrical
It is the customer’s responsibility to provide a control panel to properly operate the circulator.
4.4 Pressure lter
4.4.1 Caution: Do not attempt to open any lines,
loosen ttings or remove lter canister unless
all pressure gauges read zero pressure. Be sure that instrument isolation valves are open to gauges. Always wear safety goggles with side shields when performing mainte- nance or making adjustments to the system.
4.4.2 After 8 hours of initial start-up or sooner
per clogging indicator, the lter element
should be changed.
3.5.5 Carefully close the pressure relief valve on the right end of the manifold until the desired pres­ sure is maintained in the system.
3.5.6 Shut down the circulator. The pressure relief valve is now set at and will not need further adjustment. Higher adjustment of the pressure relief valve may cause damage to the pump.
3.5.7 Once the pressure relief valve is set, reset the pressure control valve setting. Refer to the previous section of this document.
4 Maintenance
Caution: Do not attempt to work on this system unless you have on safety glasses with side shields and you have completely read and understand this service manual.
4.4.3 Change element every time the clogging indi-
cator on the lter is in the red service lter
position.
4.5 Questions
Do not hesitate to contact your Flowserve representative with any questions you have concerning the installation, operation or maintenance of the circulator.
4.1 Electrical/power input
Shut down all electrical power to the circulator prior to
attempting maintenance.
4
Loading...
+ 8 hidden pages