Flowserve BUSwitch-Profibus-DP User Manual

Automax BUSwitchTM – Profibus-DP
Flowserve Corporation Flow Control Division
Installation, Operating & Maintenance Instructions
Electronic Printed Circuit Board Specifications
Power requirements
XA0231 Profibus-DP
Interface Card
Temperature
Operational
To operate, an external 24 VDC source must be locally
supplied to the interface card.
Storage
- 675 mA max with solenoid activated.
-40 °F to +185 °F
(-40 °C to +85 °C)
-40 °F to +250 °F
(-40 °C to +120 °C)
Principles of Operation
Flowserve’s BUSwitch is a valve automation and control product that uses the Profibus-DP communication protocol to operate and monitor position as well as provide predictive and preventative maintenance functions. In response to a command from the operator, the BUSwitch energizes the appropriate solenoid valve, which shifts a spool valve, directing the pneumatic force to the appropriate actuator port, thereby operating the valve actuator. solenoid coil is mounted internal to the BUSwitch housing to protect it from the environment. A 4-way spool valve is bolted externally to the housing. The fail direction of the actuator can be established based on which set of terminals (open or closed) the solenoid coil is connected to. For dual coil operation, externally mounted solenoid valves must be used as the housing will not accommodate two internal coils. Upon reception of an open or close command, a timer is started whose value is compared to a user-defined setpoint for that particular operation. If this timer value exceeds the setpoint, an alarm is sent back to the control operator to indicate a possible problem exists at the valve. In addition, an odometer counter totals the number of transitions the valve has made, which is then compared to a user-defined limit. If this limit is exceeded an indication is sent back to the control operator. The odometer limit can be reset by the control operator after maintenance has been performed. During operation the valve status (open, closed or in-transit) is continuously available to the control operator. The Profibus-DP Interface Board (XA0231) requires 24 VDC at 175 mA maximum.
For single coil operation, the
765 South 100 East Provo, Utah 84606 www.flowserve.com
24 VDC
Email: actuators@flowserve.com
Phone: 801 373 3028
Facsimile: 801 489 2228
Profibus Information
Manufacturer
Device
GSD File AMAX0867.GSD
Firmware
Revision
Transmission
GSD file supplied on diskette included with every device.
ID 0867 (Hex)
Speed
12 MBaud maximum
Current consumption with a solenoid activated will be the sum of the solenoid current plus 175 mA.
Mechanical Installation
Installation is best performed with Flowserve NAMUR mounting kits. These kits allow direct mounting of the BUSwitch shaft to the actuator pinion without a coupler. The NAMUR mounting kits will work with any actuator conforming to the NAMUR standard for accessory mounting hole locations and pinion dimensions. Simply attach the bracket to actuator and BUSwitch to the bracket with the included fasteners. The BUSwitch shaft features an integral alignment pin that engages the tapped pinion hole. Flowserve also offers a full line of non­NAMUR kits.
Spool and Tubing Configuration
1. For spring return actuators, a 4-way spool valve is provided with port #2 plugged. For double acting actuators, the same valve is provided with no plugs. Make sure the correct spool is selected before installing tubing. (Note: the Flowserve APS2 purge module can be supplied on spring return actuators to purge the spring chamber with supply air.)
2. Make sure all air pressure is removed before installing tubing.
3. Attach tubing according to Figures 1 or 2 below, depending upon application. Attach supply tubing to Port 1 and use 3 and 5 for exhaust.
4. To prolong actuator life use only clean, dry plant air. Lubricated air is not required, although it is recommended, particularly for high cycle applications.
1.13
LML0012-0 8/99 Page 1 of 6
©1999, Flowserve Corporation, Provo, Utah
Flowserve Corporation Flow Control Division
Automax BUSwitchTM – Profibus-DP
765 South 100 East Provo, Utah 84606 www.flowserve.com
Email: actuators@flowserve.com
Phone: 801 373 3028
Facsimile: 801 489 2228
Figure 1
Figure 2
Lubrication
All BUSwitch™ spool valves are pre-lubricated and will operate dry (with no additional lubrication). The use of lubricated air will not interfere with the BUSwitch’s functioning. If air lubrication is used, the oils listed below are popular, easily obtainable, fluids that are recommended for use with the BUSwitch spool valve: Gulf Harmony 47, Mobil DTE Medium, Shell Tellus 29, Texaco Rondo B, Sohivis 47 and Sunnis 921. Many other lubricants are acceptable providing they do not contain detergents that will attack Buna-N or Viton Seals.
Electrical Connections
marked ‘OPEN’ and ‘CLOSE’. External power (24 VDC) is connected to the indicated location.
CAUTION
BE SURE TO OBSERVE CORRECT POLARITY
OF THE EXTERNAL POWER CONNECTIONS
OR DAMAGE TO THE PRINTED CIRCUIT
BOARD WILL OCCUR!
A ‘dry-contact’ device can be connected to the terminals marked ‘EXTERNAL ALARM’, the meaning of which is determined by the customer. Refer to figure three. The data cable connection is made to the locations marked PROFIBUS + B and PROFIBUS – A, observing polarity. If this is the last device on the segment, move the shorting jumpers to the Y position to enable the termination resistor. Refer to figure three for data cable connection locations.
CAUTION
To prevent ignition of hazardous atmospheres,
keep cover bolts tight while circuits are live.
Disconnect supply circuit before opening.
Entry into the BUSwitch housing is made through three ½” NPT conduit entries. All electrical connections (power, data, external alarm, open and close solenoids) are made to captive screw cage terminal strips located on the Profibus-DP Interface board (XA0231). BUSwitch models with an internal pilot valve will have the valve connected to the appropriate circuit board terminals by the factory. For dual solenoid applications, connect the respective solenoids to the terminal strip locations
For hazardous locations, Underwriters Laboratories (UL) and the National Electric Code (NEC) require an approved sealing fitting within eighteen inches of the switch enclosure. Sealing fittings are not required for Division 2 non-incendive applications. Open conduit entries must be closed after installation using a close-up plug approved for hazardous locations. Conduit and plugs must engage a full five threads. Flowserve can provide the sealing fitting with a union and junction box for ‘daisy chain’ wiring applications.
LML0012-0 8/99 Page 2 of 6
©1999, Flowserve Corporation, Provo, Utah
Profibus-DP Interface Card (XA0231)
Figure 3
Loading...
+ 4 hidden pages