Fisher IM Supplement: Using the HART Tri-Loop Converter with FIELDVUE Digital Valve Controllers Manuals & Guides

Instruction Manual Supplement
D103267X012
FIELDVUE Digital Valve Controllers
February 2020
Using the HARTR Tri‐Loop™ HART‐to‐Analog
Signal Converter with Fisher
FIELDVUE™ Digital
Valve Controllers
Tri‐Loop Signal Converter Operation with FIELDVUE Digital Valve Controllers
The Rosemount™ 333U (alarm high) and 333D (alarm low) HART Tri‐Loop HART‐to‐Analog Signal Converter is used to read values from the digital valve controller and present them as 4 to 20 mA signals accessible to AI channels on traditional host systems. This device accepts a HART burst command 3 from a smart instrument and converts it into up to three 4 to 20 mA analog output signals. The output signals then can be read by a control system's analog input channels. Refer to the appropriate HART Field Device Specification instruction manual supplement for command 3 variables (see Related Fisher Documents on page 2).
Figure 1 shows a typical installation of the Tri‐Loop signal converter with a digital valve controller.
The Tri‐Loop signal converter may be used with the following FIELDVUE digital valve controllers:
D DVC6200 or DVC6000 HW2 digital valve controllers
Note
Burst mode communication is not supported with HART 7 in firmware revisions 2-6.
D DVC2000 digital valve controllers
D DVC6000 digital valve controllers
The Tri‐Loop signal converter outputs will go to their fail state when any of the following occur:
D there is a loss of burst mode communication from the smart instrument or
D there is a device malfunction reported by the smart instrument.
Loss of power to channel 1 will cause all channels to go to no output. Loss of power to either channel 2 or 3 will not affect the remaining channels.
When in its fail state, a 333U signal converter generates a current of 21.75 mA or greater. A 333D generates a fail state current which is less than 3.75 mA.
The Tri‐Loop signal converter is not recommended for FIELDVUE digital valve controller in split-range applications.
www.Fisher.com
FIELDVUE Digital Valve Controllers
February 2020
Instruction Manual Supplement
D103267X102
Installation Considerations
The Tri‐Loop HART‐to‐analog signal converter design allows three different din‐rail mounting options:
D Asymmetrical 32mm G rail
D Symmetrical 35 x 7.5 mm top hat rail
D Symmetrical 35 x 15 mm top hat rail
As shown in figure 1, the signal converter must be installed on the safe side of an Intrinsic Safety (IS) barrier. It is approved for FM and CSA ordinary location, and bears the CE marking to indicate compliance with applicable EC directives. It is not approved nor designed for nuclear‐qualified applications.
Figure 1 also shows a HART filter as a convenient connection point for the two additional connections to the loop wires. The necessity of a HART filter depends upon the control system; the Tri‐Loop signal converter does not add a requirement for a filter. If a filter is required, the HF340 din rail mount filter provides a convenient method for connecting field wiring between the control system, the signal converter and the digital valve controller. If no filter is required, the HF341 is available without filter action (straight‐through).
Related Fisher Documents
DVC6200 and DVC6200 SIS
D DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012
D HART Field Device Specification for DVC6200 Digital Valve Controller (D103639X012
D DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012
D HART Field Device Specification for DVC6000 and DVC6200 HW1 Digital Valve Controller (D103649X012
D DVC6200 SIS Digital Valve Controller Instruction Manual (D103557X012
D HART Field Device Specification for DVC6200 SIS Digital Valve Controller (D103638X012
DVC6000 HW2
D DVC6005 Series Remove Mount Digital Valve Controller Quick Start Guide (D103784X012)
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103785X012
D HART Field Device Specification for DVC6000 HW2 Digital Valve Controller (D103782X012
DVC2000
D DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)
D DVC2000 Digital Valve Controller Instruction Manual (D103176X012
D HART Field Device Specification for DVC2000 Digital Valve Controller (D103783X012
)
)
)
)
)
)
)
)
)
)
Miscellaneous
D HF340 Filter Instruction Manual (D102796X012)
2
Instruction Manual Supplement
FIELDVUE Digital Valve Controllers
D103267X012
DVC6000 (Supported)
D DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)
D HART Field Device Specification for DVC6000 and DVC6200 HW1 Digital Valve Controller (D103649X012
February 2020
)
Documents are available from your Emerson sales office
or at Fisher.com.
Figure 1. Example HART Tri‐Loop HART‐to‐Analog Signal Converter Installation with a FIELDVUE DVC6200 Digital Valve Controller
CHANNEL 1 MUST BE
POWERED FOR THE
TRI‐LOOP TO OPERATE
EACH TRI‐LOOP
CHANNEL RECEIVES
POWER FROM
CONTROL ROOM
CONTROL ROOM
VALVE TRAVEL
CHANNEL 2 CONFIGURED OUTPUT (OPTIONAL)
CHANNEL 3 CONFIGURED OUTPUT (OPTIONAL)
BURST INPUT
HART COMMUNICATION CONNECTION
FIELD INSTRUMENT CONNECTION
HAZARDOUS AREANON‐HAZARDOUS AREA
ANALOG OUTPUT
CONTROLLING
DIGITAL VALVE
CONTROLLER
CONTROL SYSTEM CONNECTION
FISHER HF340 HART FILTER
USE AN HF340 IF FILTER ACTION IS REQUIRED. USE AN HF341 IF NO FILTER ACTION IS REQUIRED.
+
+
INTRINSIC SAFETY
BARRIER
IF REQUIRED
BY APPLICATION
W9713
FIELDVUE DIGITAL VALVE CONTROLLER IN BURST MODE (COMMAND 3)
3
FIELDVUE Digital Valve Controllers
(1)
February 2020
Instruction Manual Supplement
D103267X102
Tri‐Loop Signal Converter Configuration From Fisher
The Tri‐Loop HART‐to‐analog signal converter ships from Fisher pre‐configured with one of the choices listed in table
1. As shown in the table the unit is available with either a high or low fail state. The channel 1 variable is always travel and the channel 2 variable is always travel target. Channel 3 is disabled, but can be configured by the user, using a Trex Device Communicator, a 475 Field Communicator, or AMS Suite: Intelligent Device Manager.
Table 1. Tri‐Loop HART‐to‐Analog Signal Converter Configuration Choices
CHANNEL
TRI‐LOOP MODEL FAIL STATE
333D Low 333U High
1. Configurations of channels are preset, but can be changed with the HART or Field Communicator, or AMS Device Manager.
The burst message from FIELDVUE digital valve controllers configured for fail‐open actuators associates 0% travel with an open valve. Therefore, channel 1 of the Tri‐Loop should be configured to provide a 20 mA output when the valve is open and a 4 mA output when the valve is closed (range is 100 to 0 rather than 0 to 100).
1
(Travel)
0 to 100% 0 to 100% Disabled
2
(Travel Target)
3
(Not Configured)
Power Source
Each output channel on the signal converter connects to a separate control system analog input channel. Each channel operates on a terminal voltage of 11 to 42.4 VDC. The signal converter is powered from the channel 1 power source.
Enabling Burst Mode
For a FIELDVUE digital valve controller to communicate with the Tri‐Loop signal converter, the burst mode must be enabled. You can use a Field Communicator, ValveLink software, or AMS Device Manager to enable burst mode in the digital valve controller.
Note
The path to access Burst varies depending on the DD revision of the digital valve controller. Refer to the appropriate instruction manual to verify path.
Note
HART devices connected to an instrument which is actively using burst mode communication may experience some HART communication errors. You should not be concerned unless the errors do not clear after a few moments or if they disrupt ValveLink software configuration, calibration, or diagnostic activities. If a disruption occurs, disable burst mode during these activities and turn it back on when completed.
4
Instruction Manual Supplement
(1)
D103267X012
FIELDVUE Digital Valve Controllers
February 2020
Once burst mode is enabled, the digital valve controller will continue to burst HART command 3 until the burst mode is disabled. Even if instrument power is lost, the instrument will continue to burst command 3 when power is restored.
Troubleshooting
Refer to table 2 for Tri‐Loop diagnostic status messages.
To reach the Diagnostic Status menu using the Trex communicator or the Field Communicator, select Diagnostics/Service, Test Device, and Status (fast key sequence 1‐1‐1).
Other Tri‐Loop parameters can be access using the Trex communicator, Field Communicator or AMS Device Manager. Refer to figure 2 for the menu tree, and table 3 for the fast‐key sequence.
Table 2. Tri‐Loop Diagnostic Status Messages
Error Message Interpretation
CH1 Burst mode variable 'Not a Number' CH2 Burst mode variable 'Not a Number' CH3 Burst mode variable 'Not a Number' CH1 Burst mode variable at saturation CH2 Burst mode variable at saturation CH3 Burst mode variable at saturation
Burst mode message is invalid Parity or checksum error with burst message
Burst mode message timeout Tri‐Loop not receiving burst command “3”
Non‐volatile memory checksum error Internal problem with the Tri‐Loop
Field device reporting failure “Device Malfunction” status from the digital valve controller CH1 Channel output is fixed CH2 Channel output is fixed CH3 Channel output is fixed CH1 Burst mode message units error CH2 Burst mode message units error CH3 Burst mode message units error
1. “ON” = error is in effect. “OFF” = error is not active.
Not applicable to the digital valve controller (always “off”)
Channel commanded into “Output fixed” mode
Channel's units do no match digital valve controllers units
5
FIELDVUE Digital Valve Controllers
February 2020
Figure 2. Menu Tree for the Tri‐Loop Signal Converter
Instruction Manual Supplement
D103267X102
Online Menu
1DEVICE SETUP
1DIAGNOSTICS / SERVICE
2BASIC SETUP
1 TEST DEVICE
2 LOOP TEST
3CALIBRATION
4 D/A TRIM
1Tag
2CONFIGURE CHANNELS
3DEVICE INFORMATION
1Status 2Reset
1CH1 2CH2 3CH3
1CONFIGURE CHANNELS
2RECALL FACTORY TRIM
1CH1 2CH2 3CH3
1CONFIGURE CH1 2CONFIGURE CH2 3CONFIGURE CH3
1Model 2Dev ID 3Tag 4Date 5Descriptor 6Message 7Final Asmbly Num
8REVISION #'s
14mA 220mA 3Other 4End
1CONFIGURE CH1 2CONFIGURE CH2 3CONFIGURE CH3
1CH1 2CH2 3CH3 4All
1Burst Variable 2Units 3LRV 4URV 5Enabled
1Universal Rev 2Fld Dev Rev 3Software Rev
1Burst Variable 2Units 3LRV 4URV 5Enabled
3DETAILED SETUP
4REVIEW
1OUTPUT CONDITION
2DEVICE
INFORMATION
Model Manufacturer Dev ID Tag Descriptor Message Date Final Asmbly Num Universal Rev Fld Dev Rev Software Rev Poll Addr Num Req Preams
1ANALOG OUTPUT
2HART OUTPUT
1Model 2Dev ID 3Tag 4Date 5Descriptor 6Message 7Final Asmbly Num
8REVISION #'s
1 LOOP TEST
2 D/A TRIM
3 SCALED D/A TRIM
1Poll Addr 2Num Req Preams 3Num Rsp Preams
1Universal Rev 2Fld Dev Rev 3Software Rev
1CH1 2CH2 3CH3
1CH1 2CH2 3CH3
1CH1 2CH2 3CH3
14mA 220mA 3Other 4End
1Proceed 2Change
6
Instruction Manual Supplement
D103267X012
FIELDVUE Digital Valve Controllers
February 2020
Table 3. Fast‐Key Sequence for the Tri‐Loop Signal Converter
Function Fast‐Key Sequence Function Fast‐Key Sequence
20 mA (Loop Test) 1‐2‐1‐2 Final Asmbly Num (Detailed Setup) 3‐2‐7 20 mA (Output Condition) 3‐1‐1‐1‐1‐2 Fld Dev Rev (Basic Setup) 2‐3‐8-2 4 mA (Loop Test) 1‐2‐1‐1 Fld Dev Rev (Detailed Setup) 3‐2‐8‐2 4 mA (Output Condition) 3‐1‐1‐1‐1‐1 LRV (Calibration) 1‐3‐1‐1‐3 All (Calibration) 1‐3‐2‐4 LRV (Configure Channels) 2‐2‐1‐3 Burst Variable (Calibration) 1‐3‐1‐1‐1 Message (Basic Setup) 2‐3‐6 Burst Variable (Configure Channels) 2‐2‐1‐1 Message (Detailed Setup) 3‐2‐6 CH1 (Calibration) 1‐3‐2‐1 Model (Basic Setup) 2‐3‐1 CH1 (D/A TRIM) 1‐4‐1 Model (Detailed Setup) 3‐2‐1 CH1 (Output Condition) 3‐1‐1‐2‐1 Num Req Preams 3‐1‐2‐2 CH2 (Calibration) 1‐3‐2‐2 Num Rsp Preams 3‐1‐2‐3 CH2 (D/A TRIM) 1‐4‐2 Other (Loop Test) 1‐2‐1‐3 CH2 (Output Condition) 3‐1‐1‐2‐2 Other (Output Condition) 3‐1‐1‐1‐1‐3 CH3 (Calibration) 1‐3‐2‐3 Poll Addr 3‐1‐2‐1 CH3 (D/A TRIM) 1‐4‐3 Proceed (Scaled D/A Trim) 3‐1‐1‐3‐1‐1 CH3 (Output Condition) 3‐1‐1‐2‐3 Reset 1‐1‐2 Change (Scaled D/A Trim) 3‐1‐1‐3‐1‐2 Software Rev (Basic Setup) 2‐3‐8‐3 Date (Basic Setup) 2‐3‐4 Software Rev (Detailed Setup) 3‐2‐8‐3 Date (Detailed Setup) 3‐2‐4 Status 1‐1‐1 Descriptor (Basic Setup) 2‐3‐5 Tag 2‐1 Descriptor (Detailed Setup) 3‐2‐5 Tag (Basic Setup) 2‐3‐3 Dev ID (Basic Setup) 2‐3‐2 Tag (Detailed Setup) 3‐2‐3 Dev ID (Detailed Setup) 3‐2‐2 Units (Calibration) 1‐3‐1‐1‐2 Enabled (Calibration) 1‐3‐1‐1‐5 Units (Configure Channels) 2‐2‐1‐2 Enabled (Configure Channels) 2‐2‐1‐5 Universal Rev (Basic Setup) 2‐3‐8‐1 End (Loop Test) 1‐2‐1‐4 Universal Rev (Detailed Setup) 3‐2‐8‐1 End (Output Condition) 3‐1‐1‐1‐1‐4 URV (Calibration) 1‐3‐1‐1‐4 Final Asmbly Num (Basic Setup) 2‐3‐7 URV (Configure Channels) 2‐2‐1‐4
Related Rosemount Documents
For more information on the Tri‐Loop HART‐to‐analog signal converter, refer to the following Rosemount documents, available from the Rosemount Measurement division:
D Model 333 HART Tri‐Loop HART‐to‐Analog Signal Converter product manual (00809‐0100‐4754
D Model 333 HART Tri‐Loop HART‐to‐Analog Signal Converter product data sheet (00813‐0100‐4754
D AMS Trex Device Communicator User Guide
D 475 Field Communicator User's Manual
Documents are available from your Emerson sales office or at Emerson.com.
)
)
7
FIELDVUE Digital Valve Controllers
February 2020
Instruction Manual Supplement
D103267X102
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, Tri-Loop, Rosemount, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
8
E 2006, 2020 Fisher Controls International LLC. All rights reserved.
Loading...