Tri‐Loop Signal Converter Operation with FIELDVUE Digital Valve
Controllers
The Rosemount™ 333U (alarm high) and 333D (alarm low) HART Tri‐Loop HART‐to‐Analog Signal Converter is used to
read values from the digital valve controller and present them as 4 to 20 mA signals accessible to AI channels on
traditional host systems. This device accepts a HART burst command 3 from a smart instrument and converts it into up
to three 4 to 20 mA analog output signals. The output signals then can be read by a control system's analog input
channels. Refer to the appropriate HART Field Device Specification instruction manual supplement for command 3
variables (see Related Fisher Documents on page 2).
Figure 1 shows a typical installation of the Tri‐Loop signal converter with a digital valve controller.
The Tri‐Loop signal converter may be used with the following FIELDVUE digital valve controllers:
D DVC6200 or DVC6000 HW2 digital valve controllers
Note
Burst mode communication is not supported with HART 7 in firmware revisions 2-6.
D DVC2000 digital valve controllers
D DVC6000 digital valve controllers
The Tri‐Loop signal converter outputs will go to their fail state when any of the following occur:
D there is a loss of burst mode communication from the smart instrument or
D there is a device malfunction reported by the smart instrument.
Loss of power to channel 1 will cause all channels to go to no output. Loss of power to either channel 2 or 3 will not
affect the remaining channels.
When in its fail state, a 333U signal converter generates a current of 21.75 mA or greater. A 333D generates a fail state
current which is less than 3.75 mA.
The Tri‐Loop signal converter is not recommended for FIELDVUE digital valve controller in split-range applications.
www.Fisher.com
FIELDVUE Digital Valve Controllers
February 2020
Instruction Manual Supplement
D103267X102
Installation Considerations
The Tri‐Loop HART‐to‐analog signal converter design allows three different din‐rail mounting options:
D Asymmetrical 32mm G rail
D Symmetrical 35 x 7.5 mm top hat rail
D Symmetrical 35 x 15 mm top hat rail
As shown in figure 1, the signal converter must be installed on the safe side of an Intrinsic Safety (IS) barrier. It is
approved for FM and CSA ordinary location, and bears the CE marking to indicate compliance with applicable EC
directives. It is not approved nor designed for nuclear‐qualified applications.
Figure 1 also shows a HART filter as a convenient connection point for the two additional connections to the loop
wires. The necessity of a HART filter depends upon the control system; the Tri‐Loop signal converter does not add a
requirement for a filter. If a filter is required, the HF340 din rail mount filter provides a convenient method for
connecting field wiring between the control system, the signal converter and the digital valve controller. If no filter is
required, the HF341 is available without filter action (straight‐through).
Related Fisher Documents
DVC6200 and DVC6200 SIS
D DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012
D HART Field Device Specification for DVC6200 Digital Valve Controller (D103639X012
D DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012
D HART Field Device Specification for DVC6000 and DVC6200 HW1 Digital Valve Controller (D103649X012
D DVC6200 SIS Digital Valve Controller Instruction Manual (D103557X012
D HART Field Device Specification for DVC6200 SIS Digital Valve Controller (D103638X012
DVC6000 HW2
D DVC6005 Series Remove Mount Digital Valve Controller Quick Start Guide (D103784X012)
D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103785X012
D HART Field Device Specification for DVC6000 HW2 Digital Valve Controller (D103782X012
DVC2000
D DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)
D DVC2000 Digital Valve Controller Instruction Manual (D103176X012
D HART Field Device Specification for DVC2000 Digital Valve Controller (D103783X012
)
)
)
)
)
)
)
)
)
)
Miscellaneous
D HF340 Filter Instruction Manual (D102796X012)
2
Instruction Manual Supplement
FIELDVUE Digital Valve Controllers
D103267X012
DVC6000 (Supported)
D DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)
D HART Field Device Specification for DVC6000 and DVC6200 HW1 Digital Valve Controller (D103649X012
February 2020
)
Documents are available from your Emerson sales office
or at Fisher.com.
Figure 1. Example HART Tri‐Loop HART‐to‐Analog Signal Converter Installation with a FIELDVUE DVC6200 Digital
Valve Controller
CHANNEL 1 MUST BE
POWERED FOR THE
TRI‐LOOP TO OPERATE
EACH TRI‐LOOP
CHANNEL RECEIVES
POWER FROM
CONTROL ROOM
CONTROL ROOM
VALVE TRAVEL
CHANNEL 2 CONFIGURED OUTPUT (OPTIONAL)
CHANNEL 3 CONFIGURED OUTPUT
(OPTIONAL)
BURST INPUT
HART
COMMUNICATION
CONNECTION
FIELD
INSTRUMENT
CONNECTION
HAZARDOUS AREANON‐HAZARDOUS AREA
ANALOG OUTPUT
CONTROLLING
DIGITAL VALVE
CONTROLLER
CONTROL
SYSTEM
CONNECTION
FISHER HF340 HART FILTER
USE AN HF340 IF FILTER
ACTION IS REQUIRED. USE AN HF341
IF NO FILTER ACTION IS REQUIRED.
−
+
−
+
INTRINSIC SAFETY
BARRIER
IF REQUIRED
BY APPLICATION
W9713
FIELDVUE DIGITAL
VALVE CONTROLLER
IN BURST MODE
(COMMAND 3)
3
FIELDVUE Digital Valve Controllers
(1)
February 2020
Instruction Manual Supplement
D103267X102
Tri‐Loop Signal Converter Configuration From Fisher
The Tri‐Loop HART‐to‐analog signal converter ships from Fisher pre‐configured with one of the choices listed in table
1. As shown in the table the unit is available with either a high or low fail state. The channel 1 variable is always travel
and the channel 2 variable is always travel target. Channel 3 is disabled, but can be configured by the user, using a Trex
Device Communicator, a 475 Field Communicator, or AMS Suite: Intelligent Device Manager.
Table 1. Tri‐Loop HART‐to‐Analog Signal Converter Configuration Choices
CHANNEL
TRI‐LOOP MODELFAIL STATE
333DLow
333UHigh
1. Configurations of channels are preset, but can be changed with the HART or Field Communicator, or AMS Device Manager.
The burst message from FIELDVUE digital valve controllers configured for fail‐open actuators associates 0% travel with
an open valve. Therefore, channel 1 of the Tri‐Loop should be configured to provide a 20 mA output when the valve is
open and a 4 mA output when the valve is closed (range is 100 to 0 rather than 0 to 100).
1
(Travel)
0 to 100%0 to 100%Disabled
2
(Travel Target)
3
(Not Configured)
Power Source
Each output channel on the signal converter connects to a separate control system analog input channel. Each channel
operates on a terminal voltage of 11 to 42.4 VDC. The signal converter is powered from the channel 1 power source.
Enabling Burst Mode
For a FIELDVUE digital valve controller to communicate with the Tri‐Loop signal converter, the burst mode must be
enabled. You can use a Field Communicator, ValveLink software, or AMS Device Manager to enable burst mode in the
digital valve controller.
Note
The path to access Burst varies depending on the DD revision of the digital valve controller. Refer to the appropriate instruction
manual to verify path.
Note
HART devices connected to an instrument which is actively using burst mode communication may experience some HART
communication errors. You should not be concerned unless the errors do not clear after a few moments or if they disrupt ValveLink
software configuration, calibration, or diagnostic activities. If a disruption occurs, disable burst mode during these activities and
turn it back on when completed.
4
Instruction Manual Supplement
(1)
D103267X012
FIELDVUE Digital Valve Controllers
February 2020
Once burst mode is enabled, the digital valve controller will continue to burst HART command 3 until the burst mode
is disabled. Even if instrument power is lost, the instrument will continue to burst command 3 when power is restored.
Troubleshooting
Refer to table 2 for Tri‐Loop diagnostic status messages.
To reach the Diagnostic Status menu using the Trex communicator or the Field Communicator, select
Diagnostics/Service, Test Device, and Status (fast key sequence 1‐1‐1).
Other Tri‐Loop parameters can be access using the Trex communicator, Field Communicator or AMS Device Manager.
Refer to figure 2 for the menu tree, and table 3 for the fast‐key sequence.
Table 2. Tri‐Loop Diagnostic Status Messages
Error MessageInterpretation
CH1 Burst mode variable 'Not a Number'
CH2 Burst mode variable 'Not a Number'
CH3 Burst mode variable 'Not a Number'
CH1 Burst mode variable at saturation
CH2 Burst mode variable at saturation
CH3 Burst mode variable at saturation
Burst mode message is invalidParity or checksum error with burst message
Burst mode message timeoutTri‐Loop not receiving burst command “3”
Non‐volatile memory checksum errorInternal problem with the Tri‐Loop
Field device reporting failure“Device Malfunction” status from the digital valve controller
CH1 Channel output is fixed
CH2 Channel output is fixed
CH3 Channel output is fixed
CH1 Burst mode message units error
CH2 Burst mode message units error
CH3 Burst mode message units error
1. “ON” = error is in effect. “OFF” = error is not active.
Not applicable to the digital valve controller (always “off”)
Channel commanded into “Output fixed” mode
Channel's units do no match digital valve controllers units
5
FIELDVUE Digital Valve Controllers
February 2020
Figure 2. Menu Tree for the Tri‐Loop Signal Converter
Instruction Manual Supplement
D103267X102
Online Menu
1DEVICE SETUP
1DIAGNOSTICS /
SERVICE
2BASIC SETUP
1 TEST DEVICE
2 LOOP TEST
3CALIBRATION
4 D/A TRIM
1Tag
2CONFIGURE
CHANNELS
3DEVICE
INFORMATION
1Status
2Reset
1CH1
2CH2
3CH3
1CONFIGURE
CHANNELS
2RECALL FACTORY
TRIM
1CH1
2CH2
3CH3
1CONFIGURE CH1
2CONFIGURE CH2
3CONFIGURE CH3
1Model
2Dev ID
3Tag
4Date
5Descriptor
6Message
7Final Asmbly Num
8REVISION #'s
14mA
220mA
3Other
4End
1CONFIGURE CH1
2CONFIGURE CH2
3CONFIGURE CH3
1CH1
2CH2
3CH3
4All
1Burst Variable
2Units
3LRV
4URV
5Enabled
1Universal Rev
2Fld Dev Rev
3Software Rev
1Burst Variable
2Units
3LRV
4URV
5Enabled
3DETAILED SETUP
4REVIEW
1OUTPUT
CONDITION
2DEVICE
INFORMATION
Model
Manufacturer
Dev ID
Tag
Descriptor
Message
Date
Final Asmbly Num
Universal Rev
Fld Dev Rev
Software Rev
Poll Addr
Num Req Preams
1ANALOG
OUTPUT
2HART OUTPUT
1Model
2Dev ID
3Tag
4Date
5Descriptor
6Message
7Final Asmbly Num
8REVISION #'s
1 LOOP TEST
2 D/A TRIM
3 SCALED D/A TRIM
1Poll Addr
2Num Req Preams
3Num Rsp Preams
1Universal Rev
2Fld Dev Rev
3Software Rev
1CH1
2CH2
3CH3
1CH1
2CH2
3CH3
1CH1
2CH2
3CH3
14mA
220mA
3Other
4End
1Proceed
2Change
6
Instruction Manual Supplement
D103267X012
FIELDVUE Digital Valve Controllers
February 2020
Table 3. Fast‐Key Sequence for the Tri‐Loop Signal Converter
20 mA (Loop Test)1‐2‐1‐2Final Asmbly Num (Detailed Setup)3‐2‐7
20 mA (Output Condition)3‐1‐1‐1‐1‐2Fld Dev Rev (Basic Setup)2‐3‐8-2
4 mA (Loop Test)1‐2‐1‐1Fld Dev Rev (Detailed Setup)3‐2‐8‐2
4 mA (Output Condition)3‐1‐1‐1‐1‐1LRV (Calibration)1‐3‐1‐1‐3
All (Calibration)1‐3‐2‐4LRV (Configure Channels)2‐2‐1‐3
Burst Variable (Calibration)1‐3‐1‐1‐1Message (Basic Setup)2‐3‐6
Burst Variable (Configure Channels)2‐2‐1‐1Message (Detailed Setup)3‐2‐6
CH1 (Calibration)1‐3‐2‐1Model (Basic Setup)2‐3‐1
CH1 (D/A TRIM)1‐4‐1Model (Detailed Setup)3‐2‐1
CH1 (Output Condition)3‐1‐1‐2‐1Num Req Preams3‐1‐2‐2
CH2 (Calibration)1‐3‐2‐2Num Rsp Preams3‐1‐2‐3
CH2 (D/A TRIM)1‐4‐2Other (Loop Test)1‐2‐1‐3
CH2 (Output Condition)3‐1‐1‐2‐2Other (Output Condition)3‐1‐1‐1‐1‐3
CH3 (Calibration)1‐3‐2‐3Poll Addr3‐1‐2‐1
CH3 (D/A TRIM)1‐4‐3Proceed (Scaled D/A Trim)3‐1‐1‐3‐1‐1
CH3 (Output Condition)3‐1‐1‐2‐3Reset1‐1‐2
Change (Scaled D/A Trim)3‐1‐1‐3‐1‐2Software Rev (Basic Setup)2‐3‐8‐3
Date (Basic Setup)2‐3‐4Software Rev (Detailed Setup)3‐2‐8‐3
Date (Detailed Setup)3‐2‐4Status1‐1‐1
Descriptor (Basic Setup)2‐3‐5Tag2‐1
Descriptor (Detailed Setup)3‐2‐5Tag (Basic Setup)2‐3‐3
Dev ID (Basic Setup)2‐3‐2Tag (Detailed Setup)3‐2‐3
Dev ID (Detailed Setup)3‐2‐2Units (Calibration)1‐3‐1‐1‐2
Enabled (Calibration)1‐3‐1‐1‐5Units (Configure Channels)2‐2‐1‐2
Enabled (Configure Channels)2‐2‐1‐5Universal Rev (Basic Setup)2‐3‐8‐1
End (Loop Test)1‐2‐1‐4Universal Rev (Detailed Setup)3‐2‐8‐1
End (Output Condition)3‐1‐1‐1‐1‐4URV (Calibration)1‐3‐1‐1‐4
Final Asmbly Num (Basic Setup)2‐3‐7URV (Configure Channels)2‐2‐1‐4
Related Rosemount Documents
For more information on the Tri‐Loop HART‐to‐analog signal converter, refer to the following Rosemount documents,
available from the Rosemount Measurement division:
D Model 333 HART Tri‐Loop HART‐to‐Analog Signal Converter product manual (00809‐0100‐4754
D Model 333 HART Tri‐Loop HART‐to‐Analog Signal Converter product data sheet (00813‐0100‐4754
D AMS Trex Device Communicator User Guide
D 475 Field Communicator User's Manual
Documents are available from your Emerson sales office or at Emerson.com.
)
)
7
FIELDVUE Digital Valve Controllers
February 2020
Instruction Manual Supplement
D103267X102
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, Tri-Loop, Rosemount, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of
Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a
registered trademark of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
8
E 2006, 2020 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.