Fisher IM Supplement: Using OPC for Accessing Fisher FIELDVUE Digital Valve Controller Data Manuals & Guides

Instruction Manual Supplement
D104429X012
Digital Valve Controllers and OPC Servers
April 2019
Using OPC™ for Accessing Fisher™ FIELDVUE
Digital Valve Controller Data
Introduction
Object Linking and Embedding (OLE) for Process Control (OPC) is a technology designed to bridge Windows®-based applications and process control hardware. It is an open standard communications protocol that permits a consistent method of accessing data from digital field devices. This method remains the same regardless of the type and source of data.
This document provides guidance for data gathering via OPC of parameters from FIELDVUE digital valve controllers.
Note
A third party OPC client is required to request and read the data from the OPC Server.
Emerson OPC Servers
An OPC Server is a licensable feature with both AMS Device Manager and the 1410 and 1420 WirelessHART™ Gateways. The OPC Server allows an OPC client application to access HART (and with AMS Device Manager, F device data in near real-time. Live device information through OPC is not supported from PROFIBUS devices.
OUNDATION™ Fieldbus)
References
D HART Field Device Specification for DVC6200 Digital Valve Controller (D103639X012)
D HART Field Device Specification for DVC6000 HW2 Digital Valve Controller (D103782X012
D HART Field Device Specification for DVC6000 and DVC6200 HW1 Digital Valve Controller (D103649X012
D HART Field Device Specification for DVC2000 Digital Valve Controller (D103783X012
D HART Field Device Specification for DVC5000 Digital Valve Controller (Retired) (D103266X012
)
)
)
)
www.Fisher.com
Digital Valve Controllers and OPC Servers
/
April 2019
Instruction Manual Supplement
D104429X012
Rosemount™ 14x0 WirelessHART Gateway / THUM WirelessHART Adapter
With a WirelessHART Gateway, the information available via OPC from FIELDVUE digital valve controllers is obtained
through the two HART
messages configured in the THUM WirelessHART adapter used for routine polling of the field device. The OPC Server can only serve up parameter data and cannot provide detailed device alert information, so the best choices for the two THUM commands to the FIELDVUE instrument should be to gather as many device parameters as possible. See Appendix A for proper configuration of the THUM WirelessHART adapter for optimum OPC data gathering from FIELDVUE digital valve controllers. See Appendix B for information on the configuration of OPC parameters in the Rosemount WirelessHART Gateway.
Refer to table 1 for information available via the Gateway OPC Server.
Table 1. Information Available Via the Gateway OPC Server
Digital Valve Controller ID by Variable Number ID by Parameter Label ID by Dynamic Variable Possible Unit Codes
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
DVC6200 HW2 only
All except DVC6200 HW2
ALL
ALL
0 0_UNITS
2 2_UNITS
4 4_UNITS
5 5_UNITS
6 6_UNITS
8 8_UNITS
9 9_UNITS
10 10_UNITS
1 1_UNITS
211 211_UNITS
245 245_UNITS
ANALOG_INPUT ANALOG_INPUT_UNITS
PRESSURE_PORT_A PRESSURE_PORT_A_UNITS
DRIVE_SIGNAL DRIVE_SIGNAL_UNITS
PRESSURE_PORT_B PRESSURE_PORT_B_UNITS
TRAVEL_SETPOINT TRAVEL_SETPOINT_UNITS
SUPPLY_PRESSURE SUPPLY_PRESSURE_UNITS
IMPLIED_VALVE_POSITION IMPLIED_VALVE_POSITION_UNITSSVSV_UNITS
PRIMARY_FEEDBACK PRIMARY_FEEDBACK_UNITS
INTERNAL_TEMPERATURE INTERNAL_TEMPERATURE_UNITS
TEMPERATURE TEMPERATURE_UNITS
CURRENT CURRENT_UNITS
DEVICE_MALFUNCTION MORE_STATUS_AVAILABLE
PV PV_UNITS
TV TV_UNITS
57
6, 7, 10, 12
57
6, 7, 10, 12
QV QV_UNITS
32, 33
39
39, 57
6, 7, 10, 12
57
57
32, 33
true / false true
false
Units Code Meaning
6 psi
7 Bar 10 kg/cm² 12 kPa 32 °C 33 °F 39 mA 57 %
2
Instruction Manual Supplement
D104429X012
Digital Valve Controllers and OPC Servers
April 2019
AMS Device Manager OPC Server
The information available via the AMS Device Manager OPC Server, shown in table 2, is obtained from FIELDVUE digital valve controllers via the definitions in the DD file and include information from both device variables, proprietary variables, and (for the DVC6200 HW2 device only) Spec Sheet information as configured in the instrument (see table 3).
Table 2. Information Available Via AMS Device Manager OPC Server
Digital Valve Controller
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
DVC6200 HW2 only
All except DVC6200 HW2
ALL
ALL ALL ALL ALL ALL ALL ALL ALL ALL DVC6200 HW2 DVC6200 HW2 DVC6000 / DVC6200 DVC6000 / DVC6200 ALL
ID by Variable
Number
0 0_UNITS
2 2_UNITS
4 4_UNITS
5 5_UNITS
6 6_UNITS
8 8_UNITS
9 9_UNITS
10 10_UNITS
1 1_UNITS
211 211_UNITS
245 245_UNITS
DEVICE_STATUS CYCYLE_COUNTER TVL_ACCUM DEVICE_SPECIFIC_STATUS_0 (“XMTR_DEVICE_STATUS” for older Digital Valve Controllers) DEVICE_SPECIFIC_STATUS_1 DEVICE_SPECIFIC_STATUS_2 DEVICE_SPECIFIC_STATUS_3 DEVICE_SPECIFIC_STATUS_4 DEVICE_SPECIFIC_STATUS_5 MAX_RECORDED_TEMP MIN_RECORDED_TEMP NUMBER_OF_POWER_UPS RUN_TIME (number of 18 hour increments) TAG LONG_TAG INST_SERIAL_NUM VALVE_SERIAL_NUM ZERO_POWER_CONDITION
ANALOG_INPUT ANALOG_INPUT_UNITS
PRESSURE_PORT_A PRESSURE_PORT_A_UNITS
DRIVE_SIGNAL DRIVE_SIGNAL_UNITS
PRESSURE_PORT_B PRESSURE_PORT_B_UNITS
TRAVEL_SETPOINT TRAVEL_SETPOINT_UNITS
SUPPLY_PRESSURE SUPPLY_PRESSURE_UNITS
IMPLIED_VALVE_POSITION IMPLIED_VALVE_POSITION_UNITS
PRIMARY_FEEDBACK PRIMARY_FEEDBACK_UNITS
INTERNAL_TEMPERATURE INTERNAL_TEMPERATURE_UNITS
TEMPERATURE TEMPERATURE_UNITS
CURRENT CURRENT_UNITS
ID by Parameter Label
ID by Dynamic
Variable
PV PV_UNITS
TV TV_UNITS
SV SV_UNITS
QV QV_UNITS
Possible Unit
Codes
39, 57
6, 7, 10, 12
57
6, 7, 10, 12
57
6, 7, 10, 12
57
57
32, 33
32, 33
39
true / false (value) (value (string) (string) (string) (string) (string) (string) (value) (value) (value) (value) (string) (string) (string)
open / close
Units Code Meaning
6 psi
7 Bar 10 kg/cm² 12 kPa 32 °C 33 °F 39 mA 57 %
3
Digital Valve Controllers and OPC Servers
Instruction Manual Supplement
April 2019
Table 3. DVC6200 Spec Sheet Information Available Via AMS Device Manager OPC Server
Digital Valve Controller Spec Sheet Information
DVC6200 HW2 spec_actuator_air
spec_actuator_effective_area spec_actuator_lever_arm_length spec_actuator_lower_bench_set spec_actuator_manufacturer spec_actuator_model spec_actuator_nominal_supply spec_actuator_size spec_actuator_spring_rate spec_actuator_upper_bench_set spec_area_units spec_breakout_torque spec_dynamic_torque spec_length_units spec_lever_style spec_LSVC spec_LSVO spec_position_xmtr spec_quick_release spec_sheet_version spec_solenoid_valve spec_spring_rate_units spec_torque_units spec_travel_units spec_trim_flow_direction spec_trim_flow_tendsto spec_trim_leak_class spec_trim_port_diameter spec_trim_port_type spec_trim_push_downto spec_trim_seat_type spec_trim_unbal_area spec_valve_actual_travel spec_valve_class spec_valve_inlet_pressure spec_valve_manufacturer spec_valve_models spec_valve_outlet_pressure spec_valve_packing_type spec_valve_rated_travel spec_valve_size spec_valve_stem_diameter
D104429X012
4
Instruction Manual Supplement
D104429X012
Digital Valve Controllers and OPC Servers
April 2019
Appendix A
Configuration of a THUM Wireless Adapter for Optimum OPC Data Coverage
1. Scope
This procedure is the site infrastructure guide for setting up a WirelessHART network of FIELDVUE digital valve controllers for use as a read-only data gathering for OPC data in table 1 provided by Rosemount Smart Wireless Gateway.
2. Emerson Wireless HART Equipment
The following Emerson WirelessHART equipment is required to provide wireless HART communication connectivity:
D A WirelessHART 775 THUM Adapter installed on every FIELDVUE digital valve controller.
D One or more Smart WirelessHART Gateway 1410 (25 device tags) or 1420 (100 device tags) with the Dual Ethernet
connect (Option 2) and the D2, D4, or D6 Data Protocol option that includes support of the OPC data protocol.
D Proper physical placement and sufficient number of wireless devices to support a robust field WirelessHART mesh
network.
Note
AMS Device Manager software and ValveLink SNAP-ON for AMS are NOT required for the OPC data transfer from the Gateway. AMS Device Manager or another DD-based handheld configuration tool is required to configure the THUM WirelessHART adapter
as described below along with the necessary network credentials to join the WirelessHART network
Figure 1. Data Transfer
.
5
Digital Valve Controllers and OPC Servers
April 2019
Instruction Manual Supplement
3. Wireless Network Configuration
D Wire the Wireless 775 THUM Adapter to the FIELDVUE instrument as shown in figure 2.
d THUM adapter’s Yellow wire attached to digital valve controller’s “LOOP +” terminal.
d THUM adapter’s White wire attached to digital valve controller’s “LOOP –“ terminal.
d THUM adapter’s Green wire attached to the Ground terminal on digital valve controller.
d THUM adapter’s Red wire attached to 4-20 mA “Loop +” source.
d THUM adapter’s Black wire attached to 4-20 mA “Loop –“ source.
Note
A 250-ohm resistor is NOT used when wiring a 775 THUM adapter to a FIELDVUE digital valve controller.
Figure 2. THUM Adapter Wiring
D104429X012
THUM ADAPTER
GREEN
RED
BLACK
WHITE
YELLOW
WIRED DEVICE
GROUND
LOOP -
LOOP +
4-20 mA LOOP +
4-20 mA LOOP -
SPLICE CONNECTOR
6
Instruction Manual Supplement
D104429X012
Digital Valve Controllers and OPC Servers
4. Configuration of Wireless 775 THUM Adapter
D Using AMS Device Manager, configure the Wireless 775 THUM Adapter as follows:
d OTHER Tab:
H 775 THUM’s HART address to desired address “3” through “63”
H 775 THUM’s HART Master Type:
D “Primary” if control system is non-HART communicating
D “Secondary” if control system is HART-communicating
April 2019
7
Digital Valve Controllers and OPC Servers
April 2019
d WIRED DEVICE Tab:
Instruction Manual Supplement
D104429X012
Choice for Voltage Drop:
“Variable Voltage Drop”
Choice for Primary Information Type:
“PV, SV, TV, and QV”
8
Instruction Manual Supplement
D104429X012
Choice for Secondary Information Type:
“Process Variables”
Digital Valve Controllers and OPC Servers
April 2019
Choice for Transmitter Variables:
“DVC5000, DVC2000, DVC6200/DVC6000 HW1: Variables 4, 5, 8, and 211
DVC6200 HW2: Variables 1, 4, 5, and 8
9
Digital Valve Controllers and OPC Servers
April 2019
d WIRELESS Tab:
Instruction Manual Supplement
D104429X012
Configure Advanced Update Rate:
Message 1 - THUM Specific Information: “All Variables and Status”: 60 seconds
Message 2 - Primary Information: “PV, SV, TV, and QV”: 8 seconds
Message 3 - Secondary Information: “Process Variables”: 16 seconds
10
Instruction Manual Supplement
D104429X012
Digital Valve Controllers and OPC Servers
April 2019
Appendix B
Configuration of OPC Parameters in the Rosemount WirelessHART Gateway
1. Scope
This procedure is the site infrastructure guide for setting up a OPC Mapping on a Rosemount Smart 1410 or 1420 Wireless Gateway.
2. Procedure for Mapping New OPC Parameters
1 . Select “Add New Entry”.
2 . In the blank pop-up box, enter the parameter you wish mapped in the format “hart_tag.parameter”. See the list
below for available parameters.
3 . Repeat steps 1 & 2 for all desired parameters.
4 . Select “Submit” to accept the new mappings.
11
Digital Valve Controllers and OPC Servers
April 2019
Available Parameter Labels
Paramter Label Paramter Label
hart_tag.0 hart_tag.DEVICE_TYPE hart_tag.0_UNITS hart_tag.DRIVE_SIGNAL hart_tag.1 hart_tag.DRIVE_SIGNAL_UNITS hart_tag.10 hart_tag.IMPLIED_VALVE_POSITION hart_tag.10_UNITS hart_tag.IMPLIED_VALVE_POSITION_UNITS hart_tag.1_UNITS hart_tag.INTERNAL_TEMPERATURE hart_tag.2 hart_tag.INTERNAL_TEMPERATURE_UNITS hart_tag.245 hart_tag.MORE_STATUS_AVAILABLE hart_tag.245_UNITS hart_tag.PRESSURE_PORT_A hart_tag.2_UNITS hart_tag.PRESSURE_PORT_A_UNITS hart_tag.4 hart_tag.PRESSURE_PORT_B hart_tag.4_UNITS hart_tag.PRESSURE_PORT_B_UNITS hart_tag.5 hart_tag.PRIMARY_FEEDBACK hart_tag.5_UNITS hart_tag.PRIMARY_FEEDBACK_UNITS hart_tag.6 hart_tag.PRIMARY_FEEDBACK hart_tag.6_UNITS hart_tag.PRIMARY_FEEDBACK_UNITS hart_tag.8 hart_tag.PV hart_tag.8_UNITS hart_tag.QV hart_tag.9 hart_tag.QV_UNITS hart_tag.9_UNITS hart_tag.STATUS_CODE hart_tag.ANALOG_INPUT hart_tag.SUPPLY_PRESSURE hart_tag.ANALOG_INPUT_UNITS hart_tag.SUPPLY_PRESSURE_UNITS hart_tag.CURRENT hart_tag.SV hart_tag.CURRENT_UNITS hart_tag.SV_UNITS hart_tag.DEVICE_MALFUNCTION hart_tag.TRAVEL_SETPOINT hart_tag.CURRENT_UNITS hart_tag.TRAVEL_SETPOINT_UNITS hart_tag.DEVICE_MALFUNCTION hart_tag.TV
hart_tag.TV_UNITS
Instruction Manual Supplement
D104429X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and Rosemount are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. FOUNDATION Fieldbus is a trademark of FieldComm Group. HART and WirelessHARTare registered trademarks of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
12
E 2019 Fisher Controls International LLC. All rights reserved.
Loading...