Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly disseminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air
velocity require more frequent maintenance. A maintenance
agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be performed by authorized professional life safety system installers
only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
2MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft®
and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc.
MS-9600LS Series Manual — P/N 52646:B8 11/20/20153
Page 4
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a
specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
4MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
1.2: Features and Options ...................................................................................................................................12
1.3.1: Current Availability...........................................................................................................................16
1.4: Controls and Indicators................................................................................................................................16
1.9: Getting Started .............................................................................................................................................24
2.2: Power ...........................................................................................................................................................30
2.2.1: AC Power and Earth Ground Connection .........................................................................................30
2.2.2: Battery Power ....................................................................................................................................30
2.2.3: Special Application DC Power Output Connection ..........................................................................31
2.6: Optional Modules and Devices....................................................................................................................35
3.1: Programming Data Entry .............................................................................................................................64
3.2: User Programming .......................................................................................................................................65
3.5: Programming and Passwords.......................................................................................................................66
3.6.2: Point Program ....................................................................................................................................68
3.6.3: Zone Setup .........................................................................................................................................87
Zone 97, 98 and 99 ...............................................................................................................................88
Zones Installed......................................................................................................................................88
Zones Enabled ......................................................................................................................................89
Zones Disabled .....................................................................................................................................89
Zone Type.............................................................................................................................................89
Zones Available....................................................................................................................................90
Zone Message .......................................................................................................................................90
3.6.5: System Setup .....................................................................................................................................91
3.6.7: History .............................................................................................................................................101
Erase History ......................................................................................................................................102
3.6.12: Program Check ..............................................................................................................................118
3.7.1: Disable Point ...................................................................................................................................119
3.7.2: History .............................................................................................................................................120
3.7.3: Program Check ................................................................................................................................121
3.7.5: System .............................................................................................................................................122
3.7.6: Zone Setup.......................................................................................................................................123
Zones Installed....................................................................................................................................124
Zones Enabled ....................................................................................................................................124
Zones Disabled ...................................................................................................................................124
Zone Type...........................................................................................................................................124
Zones Available..................................................................................................................................125
Zone Message.....................................................................................................................................125
4.1: Panel Control Buttons................................................................................................................................127
4.2: LED Indicators...........................................................................................................................................127
4.3: Normal Operation ......................................................................................................................................128
4.7: Process Monitor Operation ........................................................................................................................132
4.9: Medical Alert Condition Operation ...........................................................................................................132
4.10: Mass Notification Operation....................................................................................................................133
4.11: Programmed Zone Operation...................................................................................................................133
4.21: Special System Timers.............................................................................................................................136
4.23: Read Status ..............................................................................................................................................138
4.23.1: System Point..................................................................................................................................138
4.23.2: Zones .............................................................................................................................................139
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 7
Page 8
Table of Contents
4.23.8: Program Check ..............................................................................................................................141
4.23.9: History ...........................................................................................................................................141
4.23.11: Phone Line ...................................................................................................................................142
4.23.12: Central Station .............................................................................................................................143
4.23.13: Service Terminal..........................................................................................................................143
5.3.2: How to Use Table 5.3 on page 148 to Calculate System Current Draw .........................................147
5.4: Calculating the Battery Size.......................................................................................................................149
Appendix F: HVAC Control ..................................................................................................170
F.1: Control Module Operation .........................................................................................................................170
Appendix G: Canadian Applications................................................................................... 172
Index ......................................................................................................................................174
MS-9600LS Series & MS-9600UDLS Series Fire Alarm Control Panels........................... 181
8MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and System
UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems
Note: MS-9600LSE/MS-9600UDLSE is not ULC listed for Canadian applications
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
FM Approved to ANSI/UL 864
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control
Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested
for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local
Authority Having Jurisdiction (AHJ).
MS-9600LS Series Manual — P/N 52646:B8 11/20/20159
Page 10
+
B
A
T
T
E
R
Y
-
LCD DISPLAY
K
E
Y
P
A
D
I
/
F
O
P
T
D
A
C
T
J
3
J
2
T
B2
T
B
3
J
P
3
J
P
2
SW1
JP5
JP6
J
1
7
J16
J
6
J8
J
7
J
1
0
J1
1
R
E
M
O
V
E
T
O
D
I
S
A
B
L
E
L
O
C
A
L
C
H
A
R
G
E
R
D
I
S
A
B
L
E
G
N
D
F
L
T
S
LC OP
T
4
X
T
M
F
O
P
T
B
D
TB4
T
B
4
J
P
8
T
B
5
TB6
TB7
DB9
F
T
B
8
2
1
4
3
6
5
+
+
+
B
+
B
+
B
+
B
+
B
-
B
-
B
-
B-1
1
A
+
A
+
A
-
A
-
shiel
d
-
-
-
-
NO NC C
NC NO C N
O NC C
5 4 3 2 1
9 8 7 6
T
X
RCV
D
T
R
5 4 3
2 1
25 24 23 22 21 20 19 18 17 16
15 14
9 8 7 613 12 11 10
+
-
I
N
+
O
U
T
+
I
N
-
O
U
T
-
B
+
B
-
BA
+
A
-
A
NC NO C
+
+++
+
+
+
+
+
+
+
+
+
+
+
+++
T
X
R
C
V
DTR
G
N
D
GND
B+B-B
+
B
-
332
2
4
4
TB1
J
1
9600udleslayout.wmf
PS2 Keyboard Interface
Flash Memory Load Enable Switch
UP is normal position for switch
DOWN position allows loading of
factory software upgrades
Connector for Optional 2nd
Signaling Line Circuit
Connector for Optional
Onboard DACT-UD
Battery
24 VDC, 26 Amp Hour maximum
(supervised, nonpower-limited)
Auxiliary
Trouble Inputs
#1 2
To disable ground fault detection,
remove jumper/shunt from JP2.
Remove JP3 jumper to disable the FACP
battery charger when using external charger.
JP8- Install NACKEY board in proper
orientation to configure NACs 4
StyleY or 2 Style Z circuits
Connectors for 4XTMF Option Module
Cut this jumper to enable
Supervisory relay when
4XMTF is installed.
Cut this jumper to supervise
the 4XMTF when installed
(see J10 & J11)
(*Factory default relay programming
as shown on circuit board)
circuit number
ELRs 4.7K,
1/2W
NAC #1 NAC #3 NAC #4 NAC #2
Notification Applicance Circuits
Power-limited, supervised circuits
NAC #1, #2, #3, & #4, Style Y (Class B)
3.0 amps max per circuit
JP8 configured for Class B
using NACKEY card
(factory default configuration)
SLC Loop
(Supervised Power-limited)
Refer to the SLC Wring
Manual for detailed
information on wiring
addressable devices for
Style 4, 6, and 7
TERM
(EIA-485)
to LCD-80F
EIA-232 to printer or
personal computer
Power-limited
for EDP-listed equipment
or personal computer with
FACP Upload/Downlad
Utility. 50 foot maximum
within same room.
OR
2 Programmable Relays &
1 Fixed Trouble Relay
(nonsupervised)
Contact Ratings:
2.0 amps @ 30VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts show in normal condi-
tion (AC power with no alarm,
trouble, or supervisory activity).
A fail-safe trouble relay switches
to the NO position during
trouble conditions and
under loss all power.
ACN/ANN-BUS
(EIA-485)
to annunciators
(power-limited,
supervised)
Red
White
Green
Black
Alarm*
NO NC C
Trouble Supervisory*
NO NC C NO NC C
Notification Appliance Circuits
Special Application Power
Power-limited, supervised circuits
NAC #1 & #2 Style Z (Class A)
3.0 amps max per circuit
JP8 configured for Class A
using NACKEY card
(See Style Y illustrated
near right edge of board)
NAC #1 NAC #2
Special Application Power
DC Power Outputs (24 VDC)
Power-limited, nonsupervised circuits
Supervise with a power supervision
relay EOLR-1
Nonresettable Power #2 - 24 VDC
filtered, power-limited, (1.5 amps
maximum) Supervision required.
Suitable for powering annunciators.
Nonresettable Power #1 - 24 VDC
filtered, power-limited, (1.5 amps
maximum) Supervision required.
Suitable for powering annunciators.
Resettable Power - 24 VDC filtered,
power-limited, (1.5 amps maximum)
to smoke detectors.
Supervision required.
Important: Removing Ground
Fault Disable jumper JP2 voids
UL/NFPA Style/Class
identification for circuits.
Remove jumper JP2 only with
AHJ (Authority Having
Jurisdiction) approval
Basic System Connections
10MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 11
Peripheral Devices and Their Documents:
-
+
-
+
JP1
JP3
SW1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR
DELAY
TENS
ONES
CUT FOR
240VAC
GND FLT
DISABLE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
1
5
1
5
A- B- A+ B+
NC NO C
0
439
2615781213151410
11043926
1
5
7812
13
151410
11
J1
J2
J3
PH1
PH2
TB1
TBL
J1
J2
7 6 5 1
POWER LIMITED
Sw1
P1
P2
P3
P4
110
11 20
21 30 31
40
1 2
3 4
5
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
Alarm
Silenced
Earth
Fault
ZONE 1
ALM
TBL
SUP
1
ZONE 6
ALM
TBL
SUP
6
NAC 1
Fault
Battery
Fault
ZONE 2
ALM
TBL
SUP
2
ZONE 7
ALM
TBL
SUP
7
NAC2
Fault
Charger
Fault
ZONE 3
ALM
TBL
SUP
3
ZONE 8
ALM
TBL
SUP
8
FIRE ALARM ANNUNCIATOR
NAC 4
Fault
ZONE 5
ALM
TBL
SUP5ALM
TBL
SUP
NAC 3
Fault
Disabled
ZONE 4
ALM
TBL
SUP
4
ZONE 9
ALM
TBL
SUP
9
T11
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5
F
R
O
M
AP
P
HONE
PSTN
TO AP
OUT NC OUT
NO
INP
UT
T
AMPER GND
+12/24V
P4CN2P5
P
6
P
7P8P9P10P11P1
2
MS-9600LS
ADDRESSABLE
FIRE ALARM CONTROL PANEL
by Honeywell
Addressable Devices and SLC Wiring
Doc. # 51309
CHG-120F Charger
Doc. # 50888
SLC Loop
Battery Connector TB2
9600LSperi.wmf
CHG-75 Charger
Doc. # 51315
DACT-UD2
Communicator
Doc. # 53037
J2 Connector
ANN (EIA-485) TB6
ANN-(R)LED
LED Display
Doc. #53032
ANN-I/O
LED Driver
Doc. #151416
ANN-RLY
Form-C Relay Card
Doc. #53033
ANN-S/PG
Printer Driver
Doc. #151417
ANN-80
Text Annunciator
Doc. #52749
4XTMF
Reverse Polarity
module
J10, J11 Connectors
IPDACT
Internet Communicator
Doc. # 53109
Audio Control for ECC-50/100 Emergency Command Center Doc. #LS10001-000FL-E
or ACC-25/50(ZS/T) Audio-Command-Center Doc. #51889
MS-9600LS Series Manual — P/N 52646:B8 11/20/201511
Page 12
Section 1: Product Description
The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable FACPs
(Fire Alarm Control Panels) with an extensive list of powerful features. The combination of
Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS or MS9600UDLS FACP, offer the latest in fire protection technology. The FLPS-7 power supply is a separate board while all other electronics are contained on a single main circuit board. Both boards are
mounted to a chassis and housed in a metal cabinet, providing a complete fire control system for
most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and
remote upload/download software and remote power expansion.
The MS-9600UDLS includes a factory installed DACT-UD2 Digital Alarm Communicator Transmitter. Refer to “DACT-UD2 Installation” on page 36 and to the DACT-UD2 Manual Document
#53037, which is supplied with the FACP, for DACT wiring and programming information. The
DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. It also allows remote programming or interrogation of the control
panel using the PS-Tools Upload/Download utility via the public switched telephone network.
Local programming and interrogation is also possible for the MS-9600UDLS using the PS-Tools
and the USB port J4 on the DACT-UD2. The MS-9600LS can be programmed and interrogated
locally using the serial port at TB7. Any personal computer with Windows® XP or greater and
compatible modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history
file, walktest data, current status and system voltages.
The MS-9600LSC is a ULC approved Canadian version of the FACP which offers the same features as the MS-9600LS, but is supplied standard with a DP-9692 dress panel. Refer to “Canadian
Option” on page 100 for a full description.
The MS-9600LSE and MS-9600UDLSE offer the same features as the MS-9600LS and MS9600UDLS but allow connection to 220/240 VAC input.
NOTE: Unless otherwise specified, the terms FACP, MS-9600LS and MS-9600UDLS are used
in this manual to refer to all versions of the FACPs.
1.1 Inventory
When the FACP shipment is received, check to make certain that all parts have been included in the
shipment. The FACP shipment should consist of one of each of the following:
•main circuit board with display
•FLPS-7 Power Supply
•chassis (with main circuit board and power supply mounted)
•backbox with door and dress panel
•plastic bag containing screws, cables, key, etc.
•manual
1.2 Features and Options
•Automated activation of the ECC-50/100 Emergency Command Center
•ECC-FFT Firefighter Telephone option
•LiteSpeed™ polling protocol for faster SLC response time
12MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 13
Features and OptionsProduct Description
•SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire or
3,000 ft (900 m) with untwisted, unshielded wire
•Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
•Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
requirements
•318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor
modules)
•99 software zones
•Up to four onboard NACs (Notification Appliance Circuits):
four Style Y (Class B) or two Style Z (Class A)
•Additional NAC capability using control modules
•7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm
•Two programmable relay outputs and one fixed trouble relay
•Real-time clock/calendar with daylight savings time control
•History file with 1,000 event capacity
•Advanced fire technology features:
• Automatic drift compensation
• Maintenance alert
• Detector sensitivity test capability (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification
•Waterflow selection per module point
•Alarm verification selection per detector point
•Walktest, silent or audible
•PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
•New ANN-BUS Annunciators/Modules (ACS annunciators cannot be used when ANN-BUS
annunciators/modules are connected)
• ANN-80 Remote Liquid Crystal Display point annunciator
• ANN-I/O LED Driver Module
• ANN-LED Alarm, Trouble, Supervisory Annunciator (minimum of one required for
Canadian applications)
• ANN-RLED Alarm Annunciator
• ANN-S/PG Serial/Parallel Printer Module
• ANN-RLY Form-C Relay Module
• Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
•Legacy ACS/Term Annunciators: (ANN-BUS annunciator/modules cannot be used when
ACS/Term annunciators are connected)
• ACM Series-LED Zone Annunciators
• LDM Graphic Annunciator Series
• LCD-80F Liquid Crystal Display point annunciator (LCD-80FC for Canadian applications)
• ACM-8RF Relay Module
•Silence inhibit timer option per NAC
•Autosilence timer option per NAC
•Continuous, March Time, Temporal or California code for main circuit board NACs with twostage capability
MS-9600LS Series Manual — P/N 52646:B8 11/20/201513
Page 14
Product DescriptionSpecifications
•Selectable strobe synchronization per NAC
•Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, legacy ACS
annunciators or ANN-80 Remote annunciator
•Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
•Password and key-protected nonvolatile memory
•User programmable password
•Fully programmable from local keypad or keyboard or local PC
•Compatible with Fire•Lite’s newer series addressable devices (LiteSpeed and CLIP Mode) Refer to SLC Wiring Manual for listing of all compatible addressable devices
•Compatible with legacy Fire•Lite’s 300 Series devices (CLIP Mode only) - Refer to SLC
Wiring Manual for listing of all compatible addressable devices
•Optional DACT-UD2 Digital Alarm Communicator Transmitter, reports up to 99 zones or 636
points (all devices) to a UL listed Central Station. The DACT-UD2 is supplied standard with
the MS-9600UDLS/E
•Optional PS-Tools programming utility for local or remote Upload/Download of programming
and data (available for download at www.firelite.com)
•Optional DP-9692 dress panel (required for Canadian applications)
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
Maximum Battery Size: 26 Amp Hour
Minimum Battery Size: 12 Amp Hour
(FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 18 Amp Hour up
to 26 Amp Hour batteries, use BB26 Battery Box)
For greater than 26 Amp Hour up to 75 Amp Hour batteries, use the CHG-75 Battery Charger and
BB26 or BB-55F Battery Box. For greater than 75 Amp Hour up to 120 Amp Hour batteries, use
the CHG-120F Battery Charger and BB-55F Battery Box.
Jumper JP3, on the FACP main circuit board, must be removed to disable the FACP battery charger when using the CHG-75 or CHG-120F.
Communication Loop - (Standard) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 168
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited
Refer to SLC Wiring Manual for wiring information
2
) with 600 V insulation
NOTE: When installing SLC wiring in conduit, each loop must be installed in separate conduit.
14MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 15
SpecificationsProduct Description
Notification Appliance Circuits - TB4
Special Application power
Power-limited circuitry, supervised
NAC wiring requirements, refer to “NAC Wiring” on page 169
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 3.0 amps special application (see Figure 1.1 on page 16)
Maximum signaling current per circuit: 300 mA regulated
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for NACs
Refer to Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB1 & TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.5 on page 31 for information on power-limited wiring for relay circuits
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) TB3, Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 1.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit, nonsupervised
Refer to Device Compatibility Document for listed compatible devices
Nonresettable Special Application Power #1 (24 VDC Nominal) TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
Nonresettable Special Application Power #2 (24 VDC Nominal) TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1)
Power-limited circuit, nonsupervised
EIA-485 (ACS/ANN-BUS) - TB6
ACS/ANN annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)
Supervised, power-limited.
EIA-232 Serial - TB7
Local serial PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)
Non-supervised, power-limited.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201515
Page 16
Product DescriptionControls and Indicators
1
2
3
4
5
6
7
8
1
2
3
4
5
6
TB4
TB3
Figure 1.1 Current Availability
powerdist9600ls2.wmf
*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby. Each
circuit is capable of delivering the full 1.5 amps individually.
Refer to the battery calculations section for additional information.
1.5 amps max
per circuit
1.5 amps max
per circuit
1.5 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
Standby
1.5 Amps Max*
per panel
Resettable Special
Application Power
for 4-wire smoke detectors
Alarm
7 Amps Max
per panel
Resettable Special
Application Power
Power #1
Resettable Special
Application Power
Power #2
NAC 1
Style Y or Z
NAC 2
Style Y or Z
NAC 3
Style Y only
NAC 4
Style Y only
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 020102
1.3.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the
total current available from the FACP power supply.
1.4 Controls and Indicators
16MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high
viewing angle LCD display. The display includes a long life
LED backlight that remains illuminated. If AC power is lost and
the system is not in alarm, the LED backlight will turn off to
conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•AC Power (green)
•Fire Alarm (red)
•Supervisory (yellow)
•Trouble (yellow)
•Maintenance/presignal (yellow)
Page 17
CircuitsProduct Description
Figure 1.2 Membrane/Display Panel
9600kypd.wmf
•Alarm Silenced signals (yellow)
•Disabled (yellow)
•Battery fault (yellow)
•Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•Acknowledge/Step
•Alarm Silence
•Drill
•Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
•1st Event key
•Clear key
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
1.5 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is available by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops,
configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor
(initiating device) and control (output device) modules. Refer to the SLC Wiring Manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum
MS-9600LS Series Manual — P/N 52646:B8 11/20/201517
Page 18
Product DescriptionComponents
ms-9600LS.wmf
NAC (Notification Appliance Circuits)
Up to four NACs are provided with various programmable features:
•four Style Y (Class B) NACs
OR
•two Style Z (Class A) NACs
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe
relay monitors system trouble and the two programmable relays are factory default programmed for
system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5
amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations:
•fire alarm
•trouble
•supervisory
•supervisory auto-resettable
•DACT communication failure
•process monitor
•process monitor auto-resettable
•hazard alert
•medical alert
•AC loss
Auxiliary Trouble Inputs
Auxiliary Trouble Inputs can be connected to trouble bus outputs from auxiliary equipment, such as
power supplies or normally-open dry contacts of a trouble relay to allow monitoring by the FACP.
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board. The circuit
board is delivered mounted to a chassis which must be mounted to the backbox. Refer to the circuit
board illustration on Page 10.
FLPS-7 Power Supply
The FLPS-7 Power Supply is provided as a separate module which is delivered mounted to a chassis which must be mounted to the backbox and connected to the main circuit board.
Cabinet
The FACP cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp Hour).
Ample knockouts are provided for system wiring. Also available is an
optional dress panel DP-9692, which mounts to the inside of the cabinet
(required by ULC for Canadian applications).
Batteries
Batteries must be sealed lead acid type. The FACP cabinet provides space for two batteries (up to
18 Amp Hour). Batteries larger than 18 Amp Hour up to 26 Amp Hour require use of the BB-26 or
similar UL listed battery cabinet. The CHG-75 can be used for charging 26 to 75 AH batteries and
18MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 19
ComponentsProduct Description
the BB-26 can be used for housing the batteries. The CHG-120F can be used for charging 26 to 120
AH batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling
Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to
an SLC address that is set in the detector head using built-in rotary decimal switches with the ability to select up to 159 addresses. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or
LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series
devices. If a mix of old and new series devices are installed on the same loop, that loop must be
programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of compatible addressable detectors.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond
to an address with built-in rotary switches with the ability to select up to 159 addresses (a tab on the
address switch must be broken off to use addresses 100-159). A blinking LED on a monitor module indicates communication between the module and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or
LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series
devices. If a mix of old and new series devices are installed on the same loop, the loop must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved
notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9600LS
FACP. The FACP must be configured for CLIP Mode operation if the control panel is installed in
an existing system with 300 Series devices. The address of 300 Series devices cannot be set above
99. Refer to the SLC Wiring Manual for a complete list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly P/N R-47K
The 47 KΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-300,
MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 KΩ End-of-Line Resistor assembly
is used to supervise the MMF-302 module circuit. The resistors are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay (P/N: EOLR-1) is used to supervise the power
to 4-wire smoke detectors and notification appliances.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201519
Page 20
Product DescriptionOptional Modules
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR,
which is supplied with each module and fire alarm control panel, is mounted to the ELR plate.
Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control
module circuit.
1.7 Optional Modules
The FACP main circuit board includes option module connectors for the following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the
module is used to select an option which allows the reverse polarity circuit to open with a system
trouble condition if no alarm condition exists. The module plugs into connectors J10 and J11
which are located near the top left of the main circuit board. When the 4XTMF module is installed,
Jumper JP6, on the main circuit board, must be cut to allow supervision of the module.
SLC-2LS Expander Module
The SLC-2LS Expander Module allows expansion of the FACP from one SLC circuit to two SLC
circuits. The module plugs into connector J3 which is located in the lower right corner of the main
circuit board. The wiring for the second SLC connects to terminals located on the expander module.
DACT-UD2 Digital Alarm Communicator/Transmitter
The DACT-UD2 is used to transmit system status to UL-listed Central Station receivers via the
public switched telephone network. All circuitry and connectors are contained on a compact module which plugs into connector J2, which is located near the bottom center of the main circuit
board.
The MS-9600UDLS/E is provided with a factory installed DACT-UD2. Refer to “DACT-UD2
Installation” on page 36 and to the DACT-UD2 manual, which is included with the FACP, for
DACT-UD2 wiring and programming information.
IPDACT - Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to
allow FACP status communication to a Central Station via the internet. No telephone lines are
required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT converts the standard DACT phone communication to a protocol that can be transmitted and received
via the internet. It also checks connectivity between the FACP and Central Station. Refer to the
IPDACT Product Installation Document P/N 53109 for additional information.
1.8 Accessories
1.8.1 PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly
from most IBM compatible computers (PC), running Windows™ XP or newer. FACP program
files can also be created and stored on the PC and then downloaded later to the control panel. The
P/N: PK-CD Kit includes the FACP Windows-based Programming Utility software on CD-ROM
with on-line help file. A standard USB cable with male-A to male-B connectors, which must be
purchased separately, is required by the MS-9600UDLS for local connection of the PC to the USB
port J4 on the DACT-UD2. The MS-9600LS requires connection to the Serial Port on FACP connector TB7. Remote programming requires that the PC have a 2400 baud or faster modem.
20MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 21
AccessoriesProduct Description
dp9600.wmf
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to the DACT-UD2 manual). Remote interrogation of panel programming,
history logs, detector status, etc., is possible without enabling the remote download option.
1.8.2 Dress Panel: DP-9692
A DP-9692 dress panel is available for the FACP (required for Canadian installations). The dress
panel restricts access to the system wiring while allowing access to the key panel.
The MS-9600LSC has received ULC approval. ULC approval is contingent on the proper installation of the dress panel which is provided with the FACP
1.8.3 TR-CE Trim Ring
An optional TR-CE trim ring is available for semi-flush mounting the FACP backbox.
1.8.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery
Charger. The battery box is red and is provided with knockouts.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one
100 AH battery. When the CHG-120 is mounted in the BB-55F, two 26 AH or one 60 AH battery
may also be housed in the battery box.
1.8.5 Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9600LS FACP.
The FACP battery charger must be disabled when using the CHG-75. The charger and up to 26 AH
batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to
the CHG-75 Manual for additional information.
CHG-120 Battery Charger
The CHG-120 is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled when using the CHG-120. The batteries and charger can be
housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple
BB-55Fs are required. Refer to the CHG-120 Manual for additional information.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201521
Page 22
Product DescriptionAccessories
1.8.6 ECC-50/100
The ECC-50/100 is a single channel, 50 watt, 25 V
may be used for fire applications, mass notification applications, or both. Automatic activation of
the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via the ACS/ANNBUS
serial communications link from the FACP.
1.8.7 ECC-FFT
An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and
remote telephone handsets. The ECC-FFT’s keypad provides indications of phone activation and
corresponding trouble conditions.
1.8.8 W-GATE Wireless Gateway
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9600LS. It is powered by the SLC loop or by a regulated, external
24VDC UL-listed power supply. Available wireless devices include a photo detector, a photo/heat
detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor module. For
details about wireless devices, system setup, and operation, see the SWIFT™ Smart Wireless Integrated Fire Technology Instruction Manual.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
, emergency voice evacuation panel that
RMS
1.8.9 ANN-BUS Annunciators/Devices
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due
to incompatible serial communication protocols.
A variety of optional devices can be connected to the FACP EIA-485 ANN-BUS communication
circuit. Compatible devices include:
The ANN-80(-W) Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It
mimics the display on the control panel and will annunciate device type, point alarm, trouble or
supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP.
The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication
between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires,
from either the host FACP or remote UL-listed, filtered, power supply.
22MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 23
AccessoriesProduct Description
!
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled
through the FACP software. Refer to “ANN-BUS Options” on page 106 for a description of this
feature and programming information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two minutes without any buttons being pressed on the annunciator, a trouble indication will be annunciated.
ANN-S/PG Serial/Parallel Interface Installation
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting.
ANN-I/O LED Driver Module*
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs
The module is provided with a plastic enclosure for mounting inside the annunciator or accessory
box.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-LED Annunciator Module*
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or
addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or
addressable points. Multiple ANN-(R)LED modules may be used for full system coverage.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
1.8.10 Legacy ACS Annunciators
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due
to incompatible serial communication protocols.
ACM Series LED Zone Type Annunciators
The ACM Series Annunciators remotely display alarm and trouble status as well as system status.
For more detailed information, refer to the appropriate annunciator manual. Following is a list of
annunciators which can be used with the FACP.
•ACM-16ATF - Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power
LED and a local piezo sounder. *In Canada, this module must be used to annunciate the fire
alarm input points/zones only.
•AEM-16ATF - Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs. *In Canada, this module must be used to annunciate the fire
alarm input points/zones only.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201523
Page 24
Product DescriptionGetting Started
•ACM-32A - Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In
addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It
also has a switch for local piezo silence. *In Canada, this module must be used to annunciate
the fire alarm input points/zones only.
•AEM-32AF - Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs.
*In Canada, this module must be used to annunciate the fire alarm input points/zones only.
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that is capable of
displaying English language text. Tactile switches provide remote system Acknowledge, Silence,
Drill and Reset functions. A keyswitch allows enabling/disabling of the tactile switches. Communications between the control panel and the annunciator is accomplished over a serial interface
employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be connected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote
UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to
the LCD-80F manual.
The LCD-80F is not for use in Canadian applications.
LCD-80FC Remote Fire Annunciator (for use in Canadian applications)
The LCD-80FC is identical to the LCD-80F except for the tactile switches and keyswitch. There is
no keyswitch, and tactile switches are provided for local silence and lamp test only. No remote system functions can be performed from the LCD-80FC annunciator.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F
expander modules, are used to provide an interface to a custom graphic LED annunciator.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS-9600LS/MS9600UDLS on-line:
•Install Backbox, Power Supply and Main Circuit Board (refer to “Mounting” on page 26).
•Address and Install Intelligent Devices (refer to the SLC Wiring Manual).
•Enter Autoprogramming (refer to “Autoprogram” on page 67).
•Resolve Programming Conflicts.
•Go to Point Program to Enter Specific Data (refer to “Point Program” on page 68). Use the
right and left arrow keys to navigate between devices.
24MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 25
Notes
MS-9600LS Series Manual — P/N 52646:B8 11/20/201525
Page 26
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using key slots and
two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of
the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided
for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box.
All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting
The circuit board contains static-sensitive components. Always ground yourself with a proper
wrist strap before handling any boards so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies.
•Mark and predrill holes in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.2 on page 28.
•Install center top fastener in the wall with the screw head protruding.
•Place backbox over the top screw, level, and secure.
•Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
•Install remaining fasteners and tighten.
•Attach solid earth ground wire to grounding stud as indicated in Figure 2.1.
•When the location is dry and free of construction dust, install the main circuit board chassis by
positioning the two mounting tab holes on the top of the chassis over the mounting studs in the
top of the backbox and sliding the mounting tabs at the bottom of the chassis into the mounting
slots in the bottom of the backbox as illustrated below.
•Secure the chassis to the mounting studs with the supplied nuts.
Section 2: Installation
26MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 27
MountingInstallation
126#1
st
EVENT
ABC
DEF
JKL
MNO
TUVWXY
-/.
CLR
9
ESC
ENTER
RECALL
ACK/STEP
ALARMSILENCE
DRILL
HOLD 2 SEC
RESET
MODE
Figure 2.1 FACP Main Circuit Board Installation
9600lsbrdinbox.wmf
grounding stud:
attach solid earth
ground wire (refer to
“AC Power and
Earth Ground
Connection” on
page 30)
FACP Backbox
Main Circuit Board on Chassis
mounting studs
mounting slots
mounting tabs
mounting tab holes
MS-9600LS Series Manual — P/N 52646:B8 11/20/201527
Page 28
InstallationMounting
3.37 cm
1.325“
3.37 cm
4.13 cm
4.1 cm
1.625“ (4.128 cm)
1.625“
16.65“ (42.29 cm)
2.00“
4.128 cm
1.00“ (2.54 cm)
1.30“
3.30 cm
13.23 cm
5.207“
12.00“ (30.48 cm)
2.325“ (5.91 cm)
1.625“
4.13 cm
1.625“
1.325“
2.00“
2.00“
2.00“
2.00“
2.00“
5.1 cm
2.00“
16.0“
40.64 cm
5.207“
13.23 cm
29.95 cm
11. 79 2“
4.45cm
1.75“
4.45cm
1.75“
17.83cm
7.02“
2.00“
16.00“ (40.64 cm)
4.1cm
1.625“
12.13cm
4.775"
38.1 cm
15.00“
7.0 cm
2.75“
1.25“ (3.2 cm)
15.0“
38.1 cm
4.535“
11. 52 c m
12.13 cm
4.775“
6.0“
15.24 cm
48.37cm
19.0“
Figure 2.2 FACP Cabinet Mounting
9050udencl.wmf
Semi-Flush Mounting
Do not recess box
more than 3.875” into
wall to avoid covering
venting holes on top of
box.
Hinge Slot for
optional Dress Panel
Hinge Slot for
optional Dress Panel
Semi-flush
mounting
hole
Mounting
slots for
optional
Trim Ring
28MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 29
MountingInstallation
= 19.26" (48.92 cm)
= 19.0" (48.26 cm)
5.325"
(13.526 cm)
= 16.821" (42.73 cm)
= 16.65" (42.29 cm)
= 5.207" (13.23 cm)
Figure 2.3 FACP Cabinet Dimensions
9600cabnew.wmf
Door
Backbox
Left Side
Door
Backbox
Bottom
Right Side
Top
Depth
Depth =
MS-9600LS Series Manual — P/N 52646:B8 11/20/201529
Page 30
InstallationPower
!
Hot L1
Neut L2
EARTH
120 VAC
tb1.wmf
Interconnect
Cable
!
2.2 Power
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED
EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR
INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
2.2.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for
the MS-9600LS(C) and MS-9600UDLS or 240 VAC, 50 Hz, 1.5 amps
for the MS-9600LSE and MS-9600UDLSE. Overcurrent protection for
this circuit must comply with Article 760 of the National Electrical
Code (NEC) and/or local codes. Use 14 AWG (2.00 mm
wire with 600 volt insulation rating. Make certain that the AC mains
circuit breaker is off
before wiring any connections between the mains
and the control panel. Connect wiring from the AC mains to TB1 on
the FLPS-7 Power Supply, being careful to observe proper connections.
Illustration depicts connection of 120 VAC to TB1. Note that the FLPS-7 Power Supply is connected to the main circuit board by a cable connected to J1. Ensure that this cable is connected.
2
) or larger
Connect a wire from the grounding stud in the cabinet to a known solid earth ground (refer to Figure 2.1 on page 27). This connection is vital for maintaining the control panel’s immunity to
unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the
panel only after the system is completely installed and visually checked. Note that AC power must
be applied to the panel before installing the battery interconnect cable (refer to the following section).
2.2.2 Battery Power
Before connecting the batteries to the FACP, make certain that
the interconnect cable between the batteries is not
Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to TB2 on the main circuit board.
Refer “Power Supply Calculations” on page 146, for calculation
of the correct battery rating.
WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK
IMMEDIATE MEDICAL ATTENTION.
connected.
30MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 31
RelaysInstallation
Figure 2.4 Special Application Power Outputs - 24 VDC
1 2 3 4 5 6
Power-limited Resettable Power
1.5 amperes max., 24 VDC nominal
filtered, resettable power can be drawn
from TB3 Terminals 1(+) and 2(-)
Power-limited Nonresettable Power #1
1.5 amperes max., 24 VDC nominal
filtered, nonresettable power can be
drawn from TB3 Terminals 3(+) and 4(-)
Power-limited Nonresettable Power #2
1.5 amperes max. , 24 VDC nominal
filtered, nonresettable power can be drawn
from TB3 Terminals 5(+) and 6(-)
9600tb3.wmf
NC
NONONCC
C
NO
NC C
Figure 2.5 Relay Terminals
Relay contacts shown with power applied to panel
and no active troubles, alarms or supervisories
TB5
Note that the relays labeled as Alarm
Relay (Relay 1) and Supervisory Relay
(Relay 3) reflect the factory default
programming for these relays which are
programmable.
The relay labeled Trouble Relay (Relay 2)
is fixed and cannot be changed. It is a failsafe relay which will transfer on any trouble
or total power failure.
9600reyp2.wmf
TB1
ALARM
RELAY
TROUBLE
RELAY
SUPV
RELAY
2.2.3 Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited.
2.3 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
The Alarm and Supervisory silk-screen labels reflect the factory default programming for the two
programmable relays.
2.4 Notification Appliance Circuits
Note that relay connections must be power-limited. Refer to Power-limited wiring requirements.
The control panel provides four Style Y/Class B or two Style Z/Class A NACs (Notification Appliance Circuits). Each circuit is capable of 3.0 amps of current. Total system current in alarm cannot
exceed 7.0 amps (refer to “Calculating the System Current Draw” on page 146). Use UL listed 24
VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device
Compatibility Document for a listing of compatible notification appliances. The NACs, which are
located on the main circuit board, may be expanded via the FCPS Series field charger/power supplies.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201531
Page 32
InstallationNotification Appliance Circuits
J10
J11
4XTMF OPT BD
JP8
CLASS A
CLASS B
NACKEY -PCA
NACKEY -PCA
Figure 2.6 NAC Configuration Using NACKEY
NACKEY Card
JP8
Top edge of FACP
Main Circuit Board
• Style Z (Class A) - install NACKEY into JP8
with Class A pointing down toward circuit board
as illustrated to the right.
• Style Y (Class B) - install NACKEY into JP8
with Class B pointing down toward circuit board .
NACKEY must be inserted with text side facing
in toward center of main circuit board and key
into key-slot as illustrated to the right. It is keyed
to prevent incorrect insertion.
TB4
If the 4XTMF Option Module is to be installed in
connectors J10 and J11, the NACKEY card must be
carefully separated at the scored mark and only the
required half installed into JP8. This will allow room
for the 4XTMF module.
scored mark
4XTMF Module connectors
NACKEY card slot
Key
Key-slot
connectors for 4XTMF option module
The following sections describe the configuration and wiring of Style Y and Style Z Notification
Appliance Circuits on the FACP main circuit board. The NACs are configured for Style Y (Class
B) from the factory. Refer to “Configuring NACs” on page 32 for information on changing the
NAC configuration to Style Z (Class A) and preparing the NACKEY configuration card located in
JP8, when installing a 4XTMF Transmitter Module.
2.4.1 Configuring NACs
The Notification Appliance Circuits on the main circuit board are configured for Style Y or Style Z
by properly orienting the NACKEY card in JP8 which is located at the top of the main circuit board
near the NAC Terminal TB4. The default configuration is for Style Y (Class B). Refer to Figure
2.6 for information on installing the NACKEY card.
32MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 33
Notification Appliance CircuitsInstallation
Figure 2.7 NAC Style Y (Class B) Wiring
4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7K ohm, ½ watt P/N:71252 UL-listed
Polarized Bells
Polarized Bells
Polarized Horns
Polarized Horns
Polarized Strobes
Notification Appliance Circuit
polarity shown in alarm state
Dummy Load all unused circuit
TB4
9600nacy.wmf
Polarized Strobes
circuit number
NAC 1
NAC 3
NAC 4
NAC 2
2 Style Z (Class A) Notification Appliance
Circuits, supervised and power-limited
Polarized Bell
Polarized Horn
Polarized Horn
Notification Appliance Circuit
polarity shown in alarm state
Polarized Bell
Polarized StrobePolarized Strobe
Figure 2.8 NAC Style Z (Class A) Wiring
9600nacz.wmf
NAC 1NAC 2
2.4.2 Style Y (Class B) NAC Wiring
2.4.3 Style Z (Class A) NAC Wiring
MS-9600LS Series Manual — P/N 52646:B8 11/20/201533
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the FACP is shown below.
34MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 35
Optional Modules and DevicesInstallation
!
Figure 2.10 Keypad/Display Removal
Keypad/Display Mounting
Screw Access Hole
Keypad/Display Mounting
Screw Access Holes
96dact1.wmf
standoff
screwscrew
screw
standoff
screw
screw
screw
2.6 Optional Modules and Devices
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
FACP Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to
replace the keypad/display, access the auxiliary trouble bus connectors at J16 and J17 or install the
DACT-UD2 option module on J2, the Keypad/Display can be removed by inserting a Phillips
screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and
loosening the three mounting screws. Note that it is not necessary to disconnect the cables between
the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift
the Keypad/Display and rest the unit at the bottom of the main circuit board.
NOTE: When installing the DACT-UD2, the main motherboard must be removed from the
chassis. Unplug the power supply cable from J1 before proceeding.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201535
Page 36
InstallationOptional Modules and Devices
!
Figure 2.11 DACT-UD2 Module
SEC
Secondary Phone Line
J5 Connector (located on
back of module) plugs into J2
on FACP main circuit board
PRI
Primary Phone Line
DIALX.wmf
J4
USB Port
2.6.1 DACT-UD2 Installation
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
The DACT-UD2 Digital Alarm Communicator/Transmitter, which is supplied standard with the
MS-9600UDLS/E, transmits system status to UL listed Central Station receivers via the public
switched telephone network. It is capable of reporting up to 99 software zones or up to 636
addressable points. Two modular phone jacks, labeled PRI for Primary phone line and SEC for
Secondary phone line, allow easy connection of two independent telephone lines to the DACTUD2. The following functions have been incorporated into the DACT-UD2:
•Line Seizure - takes control of phone lines disconnecting any premises phones
•Off/On Hook - performs on and off-hook status to the phone lines
•Listen for dial tone - 440 hertz tone typical in most networks
•Dialing Central Station(s) number - default is Touch-Tone®, programmable to rotary
•For tone burst or touchtone type formats: determine proper ‘Acknowledge’ and ‘Kissoff’
tone(s) - the frequency and time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly
•Communicate in the following formats:
• Ademco Contact ID
•SIA
The DACT-UD2 module plugs into connector J2 on the FACP main circuit board.
36MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 37
Optional Modules and DevicesInstallation
Figure 2.12 DACT-UD2 J1 Connector to FACP J2 Connector
J5
J2
Standoff 3
Standoff 2
Standoff 1
J1 Connector located on
back of DACT-UD2 module
96dialx2.wmf
The following steps must be followed when installing the DACT-UD2 module:
1.Remove all power (AC and DC) from FACP before proceeding with installation
2.Remove all main circuit board mounting screws (6 locations) and the 4XTMF module
standoffs (2 locations), unplug the power supply cable from J1 and lift the main circuit board
assembly off the chassis (refer to Figure 2.10)
3.Remove the Keypad/Display from the main circuit board as described in the beginning of this
section
4.Remove and discard the Keypad/Display support standoff that presently occupies DACT-UD2
standoff location #3 (refer to Figure 2.12)
5.Install the supplied DACT-UD2 female/female standoffs in the three locations shown in Figure
2.12 and secure with the three supplied screws, inserted from the bottom side of the main
circuit board. Be sure to tighten them fully.
6.Carefully plug connector J5 on back of the DACT-UD2 module into connector J2 on the FACP
main circuit board, being careful not to bend any pins
7.Align the mounting holes in the DACT-UD2 module with the newly installed standoffs on the
FACP main circuit board
Secure the module to the standoffs on the main circuit board w ith two of the screws sup plied with the DACT-UD2 and the sup plied male/female stando ff which becomes the new Ke ypad/Display support in that location ( see Figure 2.13)
NOTE: It is important that the supplied hardware be used to secure the module in order to help
protect against electrical transients.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201537
Page 38
InstallationOptional Modules and Devices
Figure 2.13 DACT-UD2 Installation on Standoffs
Mounting Screw
male/female standoff
96dialx3.wmf
Mounting Screw
8.Reinstall Keypad/Display on the main circuit board by positioning the unit over the
appropriate standoffs and securing with screws which were loosened in step 3
9.Remount the main circuit board assembly to the chassis using screws and standoffs in their
original locations. Plug in the power supply cable at J1 on the main circuit board
10. Make certain to program the control panel for DACT-UD2 operation
11. Refer to the Telephone Requirement and Warnings section of the DACT-UD2 Installation and
Programming Manual Document #53037, before proceeding with this step. Connect the
premises primary and secondary phone lines to the DACT-UD2 as illustrated in Figure 2.14
and test the system for correct operation
38MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 39
Optional Modules and DevicesInstallation
Figure 2.14 Wiring Phone Jacks
Green Wire
Red Wire
Green Wire
Red Wire
Tip
Ring
Ring
Tip
Ring
Tip
Tip
Ring
To premises phones
To premises phones
Secondary Lines
Incoming Telco
Phone Lines
Primary Lines
Incoming Telco Phone
Lines
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
Primary Phone Line PRI
Secondary Phone Line SEC
Male Plug
Connectors
Female
Connectors
7 foot cable
(MCBL-7)
order separately
DACT-UD2
CAUTION: It is critical that the
DACT-UD2 be located as the first
device on the incoming telephone
circuit to properly function
9600jacj.wmf
2.6.2 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
MS-9600LS Series Manual — P/N 52646:B8 11/20/201539
Note: 4XTMF Module is not suitable for transmitting reverse
polarity supervisory signal.
* Wiring from these terminals
can exit the protected
premises. Dummy load
terminals 6 and 7 (4.7KΩ, ¼
watt resistor) if Municipal Box
is not connected.
Disconnect LED
4xtmfl.wmf
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after
the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate
the Disconnect condition.
The following steps must be followed when installing the 4XTMF module:
1.Remove all power (AC and DC) from the FACP before installing 4XTMF
2.Cut jumper JP6 on the main circuit board to allow the control panel to supervise the 4XTMF
module
3.The NACKEY Card must be separated at the score mark to allow connection of the 4XTMF
module (refer to Figure 2.6 on page 32 for complete information)
4.Carefully plug the connectors on the 4XTMF module into connectors J10 and J11 on the FACP
main circuit board, being careful not to bend any pins
5.Secure 4XTMF module to standoffs with supplied screws.
6.Reapply power to the FACP
7.For proper 4XTMF operation, the output relays must be programmed for the factory default
settings as shown on the PC board silkscreen: Alarm Relay, Trouble Relay and Supervisory
Relay
40MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 41
Optional Modules and DevicesInstallation
Figure 2.16 4XTMF Connectors to FACP Connectors
J10 & J11 Connectors
Cut Jumper JP6
Standoff
Standoff
4XTMF
FACP
9604xtm1.wmf
8.When the installation has been complete, enable the 4XTMF module by sliding the disconnect
switch to the left
9.Test system for proper operation
NOTE: Jumper JP5 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. The supervisory relay must be
programmed as shown on the main circuit board silk-screen (TB5, Terminals 4, 5 & 6).
Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP5 in will prevent generation of a trouble if the supervisory contact opens
2.6.3 Auxiliary Trouble Input (J16 & J17)
Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the FACP main circuit board,
can be used to monitor for trouble conditions on auxiliary equipment such as power supplies. J16
and/or J17 can be connected to any open collector trouble output on the auxiliary equipment. The
control panel will indicate a trouble condition if a trouble is sensed at the Auxiliary Trouble Inputs.
If the 4XTMF Module is installed and FACP jumper JP6 has been cut to supervise it, Auxiliary
Trouble Input 1 (J17) will monitor the 4XTMF for trouble conditions.
2.6.4 SLC-2LS Expander Module
The optional SLC-2LS Expander Module provides a second SLC loop for the FACP control panel.
This allows connection of an additional 318 addressable devices, bringing the total to 636 addressable devices which can be connected to the FACP. Refer to the SLC Wiring Manual for information on connecting devices to the SLC.
IMPORTANT! When SLC wiring is run in conduit, each SLC loop must be installed in separate
conduit.
The following steps must be followed when installing the SLC-2LS Expander Module:
1.Remove all power (AC and DC) from the FACP before installing the SLC-2LS module
2.Remove four screws from main FACP motherboard, from locations indicated in following
illustration, and replace with four supplied metal standoffs
MS-9600LS Series Manual — P/N 52646:B8 11/20/201541
Page 42
InstallationOptional Modules and Devices
Figure 2.17 SLC-2LS Expander Module Installation
SLC-2LS Expander Module
FACP
SLC Loop 2
Shield B
Shield A
SLC A-
SLC BSLC A+
SLC B+
SLC Loop 1
Shield B
Shield A
SLC A-
SLC BSLC A+
SLC B+
96optslc.wmf
Remove four screws and replace
with four supplied metal standoffs
3.Carefully plug connector J3 on the SLC-2LS module into connector J3 on the
MS-9600LS/MS-9600UDLS main circuit board, being careful not to bend any pins
4.Secure the SLC-2LS Expander Module to the four standoffs installed in step 2 with the four
supplied screws (or the screws removed in step 2)
5.Connect the SLC wiring and devices to TB8 on the SLC Expander Module. Refer to the SLC
Wiring Manual for wiring information
6.Reapply power to the control panel
7.Program the addressable devices connected to the SLC-2LS Expander Module as detailed in
“Master Programming Level” on page 67
8.Test the system for proper operation
2.6.5 Printer/PC
A serial printer or a PC (personal computer) may be connected to TB7 Terminals 1 - 4 on the FACP.
The printer can be used to provide a hard-copy printout of real-time events, history file and walktest
data. An IBM compatible PC can be connected to provide local FACP programming capabilities
using the PS-Tools programming utility. Installation of either device requires panel programming
to allow the FACP to communicate with the device.
A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel
Interface Module. Refer to “ANN-S/PG Serial/Parallel Interface Installation” on page 23 for
42MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 43
Optional Modules and DevicesInstallation
!
RS-232 PC/PRINTER
B+ A+ B- A- B A
1 COMM 2
ACS
SHIELD
SLCSLC
XMT RCV DTR GRND
T
B
7
T
B
6
T
B
8
RCV
DTR
GRND
TX
5 4 3 2 1
9 8 7 6
Figure 2.18 Serial Printer and Computer Connections
PRT/PK-CABLE
9600tb7a.wmf
Red
White
Green
Black
installation details. Refer to “ANN-BUS Options” on page 106 for programming information.
CAUTION:POSSIBLE EQUIPMENT DAMAGE
DO NOT CONNECT A PRINTER OR PC TO THE FACP IF A GROUND FAULT (ZERO IMPEDANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT.
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.
Installation
Remote printers and PCs require separate primary power. Also required is the PRT/PK-CABLE
which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-CABLE to TB7 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC
serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25
adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines.
Apply
power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may occur on the FACP, dependent on the printer or PC being used, due to this connection. For this reason, it is important that there be no preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming. Refer to
“Printer/PC” on page 116.
Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about printer setup.
Set the printer’s options as listed in the following table:
COMMUNICATION SETUP
AUTOMATIC CARRIAGE RETURNNO
PC Configuration
The Windows-based PK-CD Programming Utility Kit contains a CD-ROM with on-line help file.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201543
BUFFER:LARGE
DATA BITS:7
PARITY:EVEN
STOP BIT:1 STOP
BAUD RATE:2400/4800/9600
AUTOMATIC LINE FEEDNO
DTRREADY
Page 44
InstallationOptional Modules and Devices
!
2.6.6 ANN-BUS Annunciators/Devices
NOTE: Refer to “Canadian Applications” on page 172 for specific Canadian requirements.
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.
ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum
wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus.
The total worst case current draw is calculated by adding the individual worst case currents for each
module. The individual worst case values are shown in the following table:
1 Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If
current draw exceeds 0.5 amps, refer to “Powering ANN-BUS Devices from
Auxiliary Power Supply” on page 46.
Worst Case Current Draw
1
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance the
modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line
drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges,
capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula
used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case Current
Draw (amps)
0.1001,852 ft.4,688 ft.* 6,000 ft.*6,000 ft.
0.200926 ft.2,344 ft.3,731 ft.5,906 ft.
0.300617 ft.1,563 ft.2,488 ft.3,937 ft.
0.400463 ft.1,172 ft.1,866 ft.2,953 ft.
0.500370 ft.938 ft.1,493 ft.2,362 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
Table 2.1 Wiring Distances
44MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 45
Optional Modules and DevicesInstallation
The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (feet)
(6,000 feet maximum)
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire GaugeOhms per 1,000 feet (Rpu)
2216.2
186.4
164.02
142.54
Total Worst Case Current Draw (amps)
=
Maximum Resistance (Ohms)
6.0 volts
Rpu
*500
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wire GaugeMaximum Wire Length
18312 feet
16497 feet
14787 feet
121,250 feet
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
Figure 2.19 illustrates the wiring between the FACP and ANN-BUS devices.
Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.20 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as
the FCPS-24FS6/8, when the total ANN-BUS power requirement exceeds the capability of the
FACP’s DC Power Output circuit.
46MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 47
Optional Modules and DevicesInstallation
ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled “ANN-BUS Options” on page 106).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.
Address
not validOFFOFFOFFOFFOFF
01OFFOFFOFFOFFON
02OFFOFFOFFONOFF
03OFFOFFOFFONON
04OFFOFFONOFFOFF
05OFFOFFONOFFON
06OFFOFFONONOFF
07OFFOFFONONON
08OFFONOFFOFFOFF
1 Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
Switch 5
1
Switch 4Switch 3Switch 2Switch 1
ANN-80 Remote Fire Annunciator
Specifications
•Operating Voltage Range: 18 VDC to 28 VDC
•Current Consumption @ 24 VDC nominal (filtered and nonresettable):
• Normal/Standby (no activity): 37.0 mA
• Trouble: 39.0 mA
• Alarm: 40.0 mA
• AC Fail ( not backlit): 15.0 mA
•For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to Figure 2.21 on page 48):
1.Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise.
2.Push in the snap latch located on the right side of the unit while pulling the cover open.
3.To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut.
4.Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201547
Page 48
InstallationOptional Modules and Devices
Key switch shown in OFF/Locked position
Press in latch
and
Pull annunciator
cover open
Annunciator cover
with LCD display
Annunciator backplate
Figure 2.21 ANN-80
ann80_iso.wmf
ann80kitmount.wmf
Annunciator mounted on
surface wedge from the
ANN-SB80KIT
Annunciator mounted on stacked
surface wedge and backbox from
the ANN-SB80KIT
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box.
Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and
mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit
comes with a surface backbox and surface wedge for angled viewing. The two pieces can be used
separately or can be stacked together.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator
to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has
been mounted.
48MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 49
Optional Modules and DevicesInstallation
wiring channel
wires
TB1
ann-80boxinside.wmf
TB1
B A (+) (-)
4 3 2 1
TB3
JP5
TB4
JP8
TB5
TB6
TB1
+ - + - + -
A B
+ -
Figure 2.22 ANN-80 Wiring to FACP
FACP
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS
9600lstoann80.wmf
ANN-BUS/
ACS BUS
Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1.Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1.
2.Remove appropriate amount of wire insulation.
3.Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B.
4.If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals
3 & 4. Make certain to connect A to A and B to B.
5.Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+).
Make certain to observe proper polarity.
6.If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity.
7.After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201549
Page 50
InstallationOptional Modules and Devices
(-)
(+)
A
B
TB3
JP5
TB4
JP8
TB5
TB6
TB1
+ - + - + -+ -
A B
Figure 2.23 ANN-S/PG Connection to FACP
ANN-S/PG Module
FACP
Cable Connectors for
connection to printer
Parallel
Serial
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS/
ACS BUS
9600lstospg.wmf
The following table shows the ANN-80 connections to the FACP
FACPANN-80 (TB1)
Terminal GND (-) on TB3Terminal 1 (-)
Terminal PWR (+)TB3Terminal 2 (+)
Terminal ACS on TB6Terminal 3 (A)
Terminal ACS on TB6Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must added to the system via FACP programming. Refer to the programming section titled “ANNBUS Options” on page 106 in this manual for detailed programming information. Select the LCD
option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of a ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-80 at the FACP.
If the Keyswitch on the TISANN-80 is left in the unlocked position for more than 2 minutes, a trouble condition will be indicated at the FACP.
ANN-S/PG Serial/Parallel Interface Installation
Proceed with the installation as described in the following:
1.Ensure that all power (AC and DC) has been removed from the FACP.
2.Connect the ANN-S/PG to the FACP as illustrated in Figure 2.23.
3.Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
4.Select the address and configuration options for the ANN-S/PG module as described in the
to the module.
Programming section of this manual (refer to “ANN-BUS Options” on page 106).
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to “Auto-Configure” on page 114).
50MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 51
Optional Modules and DevicesInstallation
5.Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 2.23). Only
one printer can be connected.
Specifications
•Operating Voltage: 24 VDC
•Current (Alarm and Standby): 45 mA
•Ambient Temperature: 32
o
F to 120oF (0oC to 49oC)
•Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•Mounting: Surface
•Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•For indoor use in a dry location only
PRN-7 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-7 prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section
contains information on connecting a printer to the control panel and setting the printer options.
Connecting a PRN-7 Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The
building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-9 cable.
One end of the cable will plug into the DB-9 connector on the PRN-7 printer and the other end
plugs into the serial connector on the ANN-S/PG module.
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
OptionSettingOptionSetting
FontHS DraftCPI10CPI
LPI6 LPISkip0.5
ESC CharacterESCEmulateLQ-2550
Bidirectional CopyONI/O
CG-TABGraphic Buffer64K
CountryE-US ASCIISerial
Auto CROFF Baud9600 or 2400
Color OptionNot Installed Format7 Bit, Even, 1 Stop
Formien ProtocolXON/XOFF
Lines6LPI=60Character SetStandard
StandardExec 10.5SI.ZeroOn
BarcodeOffAuto LFOn
BarcodeUnsecured
Table 2.2 PRN-7 Setup Options
MS-9600LS Series Manual — P/N 52646:B8 11/20/201551
Page 52
InstallationOptional Modules and Devices
PRN 6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs
into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANNS/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer
cable. Connect either a serial or parallel printer, but not both at the same time.
Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
OptionSettingOptionSetting
FontHS DraftCPI10CPI
LPI6 LPISkip0.5
ESC CharacterESCEmulateEpson FX-850
Bidirectional CopyONI/O
CG-TABGraphic Buffer40K
CountryE-US ASCIISerial
Auto CROFF Baud9600 or 2400
Color OptionNot Installed Format7 Bit, Even, 1 Stop
Formien ProtocolXON/XOFF
Lines6LPI=60Character SetStandard
StandardExec 10.5SI.ZeroOn
Auto LFOn
PAPER
BIN 112/72”
BIN 212/72”
SINGLE12/72”
PUSH TRA12/72”
PULL TRA12/72”
PAP ROLL12/72”
Table 2.3 PRN-6F Setup Options
ANN-I/O LED Driver Module
The following sections describe hardware installation. Refer to the section titled “ANN-BUS
Options” on page 106 for programming information.
52MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 53
Optional Modules and DevicesInstallation
ANN-BUS (ID#)
Address DIP
switch
ANN-BUS Connector
Terminals not used (future)
ann-IObrd2.wmf
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
Figure 2.24 ANN-I/O Board Layout
11011
20
21
30
31
40
ANN-I/O Board Layout
Figure 2.24 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.
Specifications
•Max. ANN-BUS Voltage: 28 VDC
•Max. Current:
• Alarm: 200 mA
• Standby: 35 mA
• Each LED: 10 mA
•Operating Temperature: 32
o
F to 120oF (0oC to 49oC)
•For indoor use in a dry location only
MS-9600LS Series Manual — P/N 52646:B8 11/20/201553
Page 54
InstallationOptional Modules and Devices
P1
P2
P3
P4
1 2
3
4
5
TB3
JP5
TB4
JP8
TB5
TB6
TB1
+ - + - + -
+ -
A B
Figure 2.25 ANN-I/O Connection to FACP
ANN-I/O Module
FACP
ANN-BUS and power wiring are
supervised and power-limited
9600lstoannio2.wmf
ANN-BUS/
ACS BUS
24 VDC
nonresettable
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
LED Out
LED Power
Not Used
1
10
1120213031
40
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.25. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer
to the section titled “ANN-I/O Options” on page 107.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so
that there is approximately 10 mA of current for each LED. No series resistors are required. Refer
to the programming section titled “ANN-I/O Options” on page 107 of this manual.
The LEDs are wired as illustrated in Figure 2.26. Note that the illustration depicts only connectors
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
54MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 55
Optional Modules and DevicesInstallation
Figure 2.26 ANN-I/O Board Layout
annI-ioleds2.wmf
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED Power
no connection
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
LED11
LED12
LED13
LED14
LED15
LED16
LED17
LED18
LED19
LED20
LED Power
no connection
P1
P2
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
Cathode
LEDs
Anode
Cathode
LEDs
Anode
Figure 2.27 ANN-LEDs (shown in possible stacked configuration)
ann-ledistacked.wmf
ANN-LED Annunciator Module
Specifications
•Max. ANN-BUS Voltage: 24 VDC
MS-9600LS Series Manual — P/N 52646:B8 11/20/201555
Page 56
InstallationOptional Modules and Devices
ann-led.wmf
Figure 2.28 Exploded View of ANN-LED
•Max. Current:
• Alarm: 68 mA
• Standby: 28 mA
•Operating Temperature: 32
o
F to 120o F (0o C to 49o C)
•For indoor use in a dry location only
Mounting/Installation
Refer to the documentation supplied with the ANN-LED module for mounting information.
56MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 57
Optional Modules and DevicesInstallation
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB3
JP5
TB4
JP8
TB5
TB6
TB1
+ - + - + -+ -
A B
Figure 2.29 ANN-LED Connection to FACP
FACP
ANN-LED
ANN-BUS/
ACS BUS
+24 VDC
-24 VDC
9600lstoled.wmf
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS (ID#)
Address DIP switch
ANN-LED Board Layout and Connection to FACP
Figure 2.29 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-RLY Annunciator Module
Specifications
•Operating Voltage: 24 VDC
•Max. Current:
•Alarm: 75 mA
•Standby: 15 mA
•Relay Contact Ratings
•2 amps @ 30 VDC (resistive)
•0.5 amps @ 30 VAC (resistive)
•Operating Temperature: 32
•For indoor use in a dry location only
o
F to 120o F (0o C to 49o C)
MS-9600LS Series Manual — P/N 52646:B8 11/20/201557
Page 58
InstallationOptional Modules and Devices
mounting holes
mounting hooks through
mounting slots
grounding wire
ANN-RLY
ANN-MBRLY
mounting bracket
mounting holes
mounting holes
FACP Backbox Installation
using ANN-MBRLY mounting bracket
FACP Chassis Installation
mounting holes
mounting holes
ANN-RLY on
ANN-MBRLY
mounting bracket
ROME Series Installation
using ANN-MBRLY mounting bracket
Figure 2.30 ANN-RLY Mounting Options
ann-rlyinchassis.wmf
ann_mbriyincab3.wmf
rome-relay-plate3.wmf
Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside
the ROME Series enclosure. Refer to the ANN-RLY Installation Document #53033 for instructions
on chassis mounting or to the ROME Series Installation Document #53530 for mounting in the separate backbox.
58MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 59
Optional Modules and DevicesInstallation
Figure 2.31 ANN-RLY Board Layout and Connection to FACP
FACP
ANN-RLY
ANN-BUS
+24 VDC-24 VDC
Ground Wire
attaches to chassis
(see documentation
supplied with module)
9600lstorly.wmf
ANN-BUS (ID#)
Address DIP switch
!
ANN-RLY Board Layout and Connection to FACP
Figure 2.31 illustrates the ANN-RLY board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.6.7 Automatic Audio Panel Control
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY WIRING.
The FACP annunciator bus serves as the “FACP Data Bus” to the ECC-50/100 audio system. User
programming is required to set up the operation of the audio system. To set up the annunciator bus,
refer to Section 2.6.6 on page 44. The annunciator protocol, ANN-Bus or legacy ACS-Bus, must
be selected and enabled. Note that only one of the protocols may be enabled in the system.
When using the ACS-Bus protocol, ACS address 01 must be enabled in the FACP programming.
When using the ANN-Bus protocol, the FACP will automatically detect the audio system connection during annunciator “auto-configuration”. No ANN-Bus address selection is necessary at the
FACP.
Once the FACP can communicate with the audio system, FACP zones Z33 through Z56 become
automatically dedicated as output zones for speaker circuits 1 through 24 respectively. FACP zone
Z32 is dedicated to turn on all speaker circuits. FACP programming allows association between
MS-9600LS Series Manual — P/N 52646:B8 11/20/201559
Page 60
InstallationOptional Modules and Devices
Figure 2.32 FACP Connection to ECC-50/100 Series Audio Panel
FACP
ECC-50/100
to other ACS/ANN
devices
A B
ANN
ACS
9600ecc.wmf
any addressable SLC input device (module, detectors) with any of the speaker circuits. In addition
1 of 14 (1 of 5 using the legacy ACC panel) can be generated over the selected speaker circuit. Any
fault in the ECC-50/100 audio system is sent to the FACP via the FACP Data Bus and is indicated
as an annunciator fault on the FACP display. A fault at the ACC-25/50ZS Series panel will cause
the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault.
For speaker circuit mapping and audio message assignment, refer to “Zone Message” on page 125.
Also, refer to “Programmed Activation by FACP” in chapter 3 of the ECC-50/100 Instruction Man-ual (Doc. LS10001-000FL-E) or Appendix D, “Programmed Activation by FACP” in the ACC25/50ZS Series Instruction Manual (Doc. 51889).
Connect the ECC-50/100 panel’s FACP Data Bus at TB13 to TB9 on the FACP.
60MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 61
Optional Modules and DevicesInstallation
A (+)B (-)
FACP
ACC-ZPMK
on ACC-25/50ZS Series
Figure 2.33 FACP Connection to ACC-25/50ZS Series Audio Panel
ANN-BUS
acczpmtoms9600udls.wmf
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of communication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals
2 & 3 of the ACC-ZPMK module on the audio panel.
2.6.8 ACS Annunciators
Legacy ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.
Legacy ACM Series Annunciators
ACM and AFM Series Annunciators provide visual indications of FACP status in remote locations.
Refer to the appropriate annunciator manual for information on installation, wiring and operation.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201561
Page 62
InstallationOptional Modules and Devices
- + A B
+ -
FACP
ECC-FFT
Figure 2.34 ECC-FFT Connections
96tofft.wmf
XmtRcvDtrGndIn+In-Out+Out-
+ -
B+ A+ B- A- A B
Slc Slc Slc Slc Shield
TB7
TB8
TB6
W-GATE
mounting plate
out to next
SLC device
MS-9600LS
Figure 2.35 W-GATE SLC Connection
96towg.wmf
2.6.9 ECC-FFT Firefighter Telephone
The ECC-FFT connects from TB3 (non-resettable aux power) on the FACP to the DC Power input
on the ECC-FFT board.
2.6.10 W-GATE Wireless Gateway
The W-GATE connects to the FACP’s SLC connection at TB8. The W-GATE can be powered by
either the SLC or an external 24 VDC power source. Refer to the SWIFT™ Smart Wireless Integrated Fire Technology Manual for more information.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
62MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 63
Notes
MS-9600LS Series Manual — P/N 52646:B8 11/20/201563
Page 64
Section 3: Programming
3.1 Programming Data Entry
Programming can be accomplished using the FACP keypad or by connecting an optional standard
computer keyboard. The keyboard can be connected to the PS-2 connector J7 on the control panel
main circuit board.
Local or remote programming and editing can also be accomplished using the DACT-UD2 Digital
Alarm Communicator/Transmitter which is optional for the MS-9600LS and supplied standard
with the MS-9600UDLS. Refer to the DACT-UD2 Manual P/N 53037 for detailed information.
The information presented in this section refers to programming the FACP via the onboard keypad.
If an optional computer keyboard is connected to the FACP main circuit board, the following table
describes the keyboard keys which correspond to the onboard keypad keys.
Keypad KeysComputer Keyboard Keys
1st EventHome
CLRDelete
ESCEsc
RECALLInsert
**
##
A - ZA - Z
0 - 90 - 9
(on QZ key)Space bar
——
//
••
ENTEREnter
ACK/STEPF1
SILENCEF2
DRILLF3
RESETF4
64MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 65
User ProgrammingProgramming
SYSTEM ALL NORMAL
10:00A 010807
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
3.2 User Programming
The FACP is completely field programmable and requires no special software skills. While programming the FACP, the fire protection capabilities of the control panel are
ming mode will time-out following 10 minutes of inactivity.
Site-specific programming may be accomplished in three ways:
•Autoprogramming Feature - This is a convenient method for quickly bringing the FACP
addressable SLC devices on-line without the necessity of programming each device
individually. Refer to “Autoprogram” on page 67 for a detailed description of
Autoprogramming
•Manual programming or editing, using the FACP keypad or a PC keyboard
•Remote Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and modem. For programs requiring a large
amount of data entry, this method may be preferred. A PK-CD programming CD-ROM can be
ordered for this purpose
•Local Programming and Editing Feature - allows creation and editing of site-specific custom
programs using a Windows-based computer and the DACT-UD2 USB connection on the
MS-9600UDLS or Serial Port connection on TB7 of the MS-9600LS. For programs requiring
a large amount of data entry, this method may be preferred. A PK-CD programming CD-ROM
can be ordered for this purpose
enabled. Program-
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
Read Status mode can be entered while the panel is in any
mode of operation. If an alarm or supervisory event exists at the panel, the event must be cleared before entering Programming mode. To
access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status feature which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to “Read Status” on page 138 for a
detailed description of this feature.
Pressing 2 will select user Programming which may only be accomplished by an authorized person.
After pressing 2, a screen will prompt for a password. After entering the correct password, the user
may select from a list of programming options.
Pressing 3 will select Remote Download which allows the user to enable the remote programming
option. Refer to the DACT-UD2 manual P/N 53037.
Exit Programming or Read Status
The programmer can exit Read Status or Programming mode by repeatedly pressing the keypad
ESC (Escape) key until the display reads System All Normal. Ten minutes of inactivity will also
cause the FACP to exit Programming mode. Note that the data which is entered during Program-
ming mode is not
saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key.
If the Reset key is pressed or power is lost before exiting Programming mode, all data which was
just entered will be lost.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201565
Page 66
ProgrammingInitial Power-up
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 020410
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
User Programming Levels
There are two user programming levels:
•User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
•User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If
the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and
the following trouble message will be displayed.
3.4 Programming Screens Description
The main options available when the Enter key is pressed are: Read Status, Programming Mode.
Each option has multiple functions or features which may be chosen. To view all of the choices, it
is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to
“Master Programming Level” on page 67, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in
the upper right corner of the screen being viewed. The programmer can then press the keypad Up
or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
3.5 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in nonvolatile memory. The factory set passwords can be changed by the user as described in “Password
Change” on page 117. If an invalid password is entered, the blinking cursor will return to the first
password character position. To exit Programming or Read Status mode at any time, press the ESC
(Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order
to store the program data entered during this mode. If the Reset key is pressed or power is lost
before exiting Programming mode, the data just entered will not be saved.
To access user Programming mode, press the Enter or Mode key. The LCD will display the following:
66MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 67
Master Programming LevelProgramming
PROGRAMMING
ENTER PASSWORD
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #2
Programming Screen #3
Programming Screen #4
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
To enter the user Programming mode, press 2. The display will read as follows:
Entering the Master
If the Maintenance
level password (default 00000) will cause the following screen to appear:
level password (default 11111) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear:
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated
below while pressing the ‘up’ arrow key will display the previous screen.
3.6.1 Autoprogram
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which
prompts the control panel to poll all devices installed on one or both SLC loops. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as
quickly as possible. The first time the system is powered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default
values for newly installed devices.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201567
Page 68
ProgrammingMaster Programming Level
AUTOPROGRAM
1=LOOP 1
2=LOOP 2
3=ALL LOOPS
Autoprogram Loop Select Screen
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
# OF DET LOOP2 000
# OF MON LOOP2 000
# OF CON LOOP2 000
Autoprogram Result Screen #1
Autoprogram Result Screen #2
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
POINT PROGRAM
SELECT LOOP
1=LOOP 1
2=LOOP 2
Point Program Screen #1
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
When Autoprogram is selected, the programmer is given the option of autoprogramming all loops,
only loop 1 or only loop 2. The following will be displayed on the LCD:
After selecting one of the Autoprogram options, the control panel will begin autoprogramming the
system by communicating with each addressable device installed on one or both loops. While autoprogramming, the panel will display the following:
When Autoprogramming is completed, the control panel will display the type and quantity of each
device installed on the SLC loop(s) similar to the following display:
In the preceding example, the first display indicates that Loop 1 has 55 addressable detectors, 35
monitor modules and 30 control modules installed. The second display indicates that Loop 2 has
no devices installed.
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop,
delete an existing device from a loop or change the programming for an existing device. Pressing
2, while viewing Programming Screen #1, will select the Point Program option and display the following screen:
The programmer selects the desired SLC loop by pressing 1 or 2 in Point Program Screen #1,
which causes the panel to display the following screen:
Detector Programming
68MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Pressing 1, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable detector. The following screen will be displayed by the
control panel:
Page 69
Master Programming LevelProgramming
ADD DETECTOR
ENTER DETECTOR#
Add Detector Screen
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
ADD DETECTOR
DETECTOR# 005
IS ADDED
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
DELETE DETECTOR
ENTER DETECTOR#
Delete Detector Screen
DELETE DETECTOR
DETECTOR# 005
IS DELETED
EDIT DETECTOR
ENTER POINT ADDRESS
Edit Detector Screen
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the
programmer to add a new detector address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
Press the down arrow key to view additional choices. Press the number corresponding to the
desired selection to program that type to the newly added detector.
When the type has been selected, the following screen will be displayed:
The programmer can continue adding detectors by pressing the ESC or left arrow key which will
return the display to the Add Detector Screen.
Delete Detector
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete a specific detector:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005. When the last digit is keyed-in, the following screen
will be displayed:
The programmer can continue deleting detectors by pressing the ESC or left arrow key which will
return the display to the Delete Detector Screen.
Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3 in
the Detector Screen. The following screen will be displayed:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201569
Page 70
ProgrammingMaster Programming Level
NO DETECTOR
INSTALLED
Edit Detector Screen #1
TROUBL SMOKE(PHOTO)
ZNNN
1D017
Edit Detector Screen #1
NORMAL SMOKE (PHOTO)
ZNNN
V 1D017
Edit Detector Screen #1
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 017.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen
showing information about a device that is
installed with a lower address, closest to the selected
address, will be displayed.
If no
detectors have been installed on the loop, the following will be displayed:
If the selected address has been added to programming, device summary screens will be displayed.
These screens allow the programmer to view all device settings at a single glance. Pressing the left
or right arrow keys will allow the programmer to rapidly view the devices at the previous or next
address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed
on the SLC or has a communication fault but the address is programmed in the system, the following screen will be displayed:
If the selected address has been added to programming and a detector (such as a photoelectric
detector) with the selected address is physically installed on the SLC and is communicating with
the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to
view the Edit Detector screens.
In the preceding example:
• Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
• ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 099)
• V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)
• 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop 1, D=Detector
and 017 = Detector Address 017)
70MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 71
Master Programming LevelProgramming
EDIT DETECTOR 1D017
1=ENABLED YES
2=TYPE SMOKE(PHOTO)
3=VERIFICATION OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017
1=WALKTEST NO
2=PAS NO
3=PRE-SIGNAL NO
DETECTOR TYPE
1=SMOKE PHOTO
2=USER DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1
The following examples show the editing of a photoelectric smoke detector with address 017,
located on the first SLC loop:
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the detector will not be polled by the control panel, preventing the detector from reporting
alarms and troubles to the panel. The control panel will display the device type and address which
has been disabled and will turn on the Trouble LED and Disable LED.
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
Screen #2. This will cause the control panel to display the following Detector Type Screens:
Pressing the down arrow key will display additional detector types as indicated in the following
table:
Detector TypeAction When Activated
Smoke PhotoFire Alarm
User-Defined-1same as previous (Smoke Photo)
Smoke IonFire Alarm
User-Defined-2same as previous (Smoke Ion)
Heat DetectFire Alarm
User-Defined-3same as previous (Heat Detect)
Smoke DuctPFire Alarm
User-Defined-4same as previous (Smoke DuctP)
Photo w/HeatFire Alarm
User-Defined-5same as previous (Photo w/Heat)
Duct-SupervSupervisory, latching
User-Defined-6same as previous (Superv DuctP)
Photo-SupervARSupervisory, nonlatching (works only in LiteSpeed)
User-Defined-7same as previous (Photo-SupervAR)
ADAPTFire Alarm
User-Defined-8same as previous (ADAPT)
BeamFire Alarm
User-Defined-9same as previous (Beam)
MS-9600LS Series Manual — P/N 52646:B8 11/20/201571
Page 72
ProgrammingMaster Programming Level
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
While viewing any Detector Type screen, select the type of detector being programmed by pressing
the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and
indicate the selection next to the Type option.
NOTE: If a detector is selected as a SUPERV DUCTP type, it will function like a supervisory point,
not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED
or alarm relay, if smoke is sensed.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica-
tion” on page 137.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable a device for the Walktest feature,
press 1 while viewing the Edit Detector Screen #3 until the display reads Wa l k t e s t Yes. Each press
of the 1 key will cause the display to toggle between Wal k t est Ye s and Wa lktest N o . Refer to “Walktest” on page 137.
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose).
To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display reads
PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and PAS N o .
Refer to “Positive Alarm Sequence” on page 135.
For example, if a detector with address 005 is to be configured for PAS operation:
• Select PAS Yes when editing the detector set to address 005
• Program the desired zone or zones to be activated by this detector, in this example Z001
• Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
• Program an output, such as a control module, for PAS activation by assigning zone Z97 to it.
This control module may be connected to a signaling device used to indicate a PAS
condition (do not use a Notification Appliance Circuit for this purpose)
• Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay timer to some
value
With the preceding program settings, when the detector with address 005 is activated, zone Z97
will cause its associated control module to activate immediately, sounding the connected PAS signaling device. Following the PAS delay time, zone Z001 will cause its associated control module
to activate and the control panel will initiate an alarm condition.
72MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the alarm
relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will
activate. This zone can be programmed to a control module which may be used to activate a
sounder or indicator which the installer designates as a Presignal indication (do not use a Notifica-
tion Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3 while viewing
Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will cause
the display to toggle between Pre-signal Yes and Pre-signal No. Refer to “Presignal” on page 135.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
• Select Pre-signal Yes when editing the detector set to address 005.
• Program the desired zone or zones to be activated by this detector, in this example Z001.
• Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001.
• Program an output, such as a control module, for Pre-signal activation by assigning zone
Z98 to it. This control module may be connected to a signaling device used to indicate a
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose).
• Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-signal delay
timer to some value.
With the preceding program settings, when the detector with address 005 is activated, zone Z98
will cause its associated control module to activate immediately, sounding the connected signaling
device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will
cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Zone Assignment
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while viewing Edit Detector Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zone Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate
through the zones and the CLEAR key can be used to quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause the
following screen to be displayed:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201573
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the detector currently being programmed. When an adjective has been selected, it will appear at the
top of the display as indicated by the asterisks.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the detector currently being programmed. When a noun has been selected, it will appear at the top of the
display as indicated by the asterisks.
74MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit. These descriptors are selected as described in the previous sections.
Page 75
Master Programming LevelProgramming
EDIT DETECTOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Detector Screen #5
DESCRIPTION 1D002
NOUN/ADJECTIVE
Adjective/Noun Screen
Description
The Description selection allows the programmer to enter additional information about the detector
currently being programmed. This information will be displayed as part of the device label on the
display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following screen to be
displayed:
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 2, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Detector Screen #5, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Description, Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position.
•If the zero key is then pressed a second time with no intervening key actions, the entire field is
replaced with the field entered for the previous device programmed
, and the cursor moves to
the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter.
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
•The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1.The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2.With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
3.With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4.Press the right arrow key to advance the zone field.
5.Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201575
Page 76
ProgrammingMaster Programming Level
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
ADD MODULE
ENTER MODULE#
Add Module Screen #1
ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2
ADD MODULE
MODULE# 005
IS ADDED
Add Module Screen #3
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
DELETE MODULE
ENTER MODULE#
Delete Module Screen
DELETE MODULE
MODULE# 005
IS DELETED
Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable module. The following screen will be displayed by the
control panel:
Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the
programmer to add a new module address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
Pressing 1 for Control Module or 2 for Monitor Module will display the following screen:
The programmer can continue adding modules by pressing the ESC or left arrow key which will
return the display to the Add Module Screen #1.
Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the programmer to delete a specific module:
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad,
key in the module address such as 005. When the last digit is keyed in, the following confirmation
that the module has been deleted will be displayed:
76MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 77
Master Programming LevelProgramming
EDIT MODULE
ENTER MODULE ADDRESS
Edit Module Screen
NO MODULE
INSTALLED
Edit Module Screen
TROUBL MONITOR
<ADJ><NOUN>
ZNNN
1M012
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
1M012
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
1M012
Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3 in
the Modules Screen. The following screen will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 012. When the last digit is keyed-in, if the selected address
has not
been added to programming, a screen showing information about a device that is installed
with a lower address, closest to the selected address, will be displayed. If no modules are installed
on the loop, the following screen will be displayed:
If the selected address has been added to programming but a module (such as a monitor module)
with the selected address is not physically installed on the SLC or has a communication fault, the
following screen will be displayed:
If the selected address has been added to programming and a module (such as a monitor module)
with the selected address is physically installed on the SLC and is communicating with the control
panel, the following screen will be displayed:
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Monitor screens. In the preceding example:
• Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled).
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device.
• ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the two digit zone number from 000 - 099).
• 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 012 = Module Address 012).
If the selected address corresponds to a control
module, a screen displaying information about the
control module with the selected address will be displayed as shown in “Edit Module Screen for
Control Modules” on page 83.
If the selected address corresponds to a monitor
module, a screen displaying information about the
module with the selected address will be displayed as illustrated in the following:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201577
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from
reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition and the Disable LED with turn on if any devices are disabled.
Type Monitor
The FACP response to the activation of a user-defined type is the same as most previous standard
types in the list, thus allowing a variety of user-defined types and responses. To select the type of
monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2.
This will cause the control panel to display the following Monitor Type Screens:
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of
the Monitor Type screens, select the type of monitor module being programmed by pressing the
corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which
will show the new type selection.
Table 3.1 lists the Monitor Types and their respective functions.
Monitor module type selection will affect the function of the point as follows:
78MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 79
Master Programming LevelProgramming
Monitor Type Action When Activated
Pull-StationFire Alarm
User-Defined-1same as previous (Pull-Station)
WaterflowFire Alarm Delayed
User-Defined-2same as previous (Waterflow)
MonitorFire Alarm
User-Defined-3same as previous (Monitor)
Futurenot used
Futurenot used
Smoke-Conventional
1
Fire Alarm
User-Defined-5same as previous (Smoke-Conventional)
Heat-ConventionalFire Alarm
User-Defined-6same as previous (Heat-Detector)
Medic-Alert
2
Supervisory, latching
User-Defined-7same as previous (Medic-Alert)
Hazard-Alert
2
Supervisory, latching
User-Defined-8same as previous (Hazard-Alert)
Tornado-Alert
2
Supervisory, latching
User-Defined-9same as previous (Tornado-Alert)
PhoneActive Phone (LCD display only)
User-Defined-10same as previous (Phone)
TamperSupervisory, nonlatching (tracking)
User-Defined-11same as previous (Tamper)
SupervisorySupervisory, latching
User-Defined-12same as previous (Supervisory)
Supervisory-AR
3
Supervisory, nonlatching (tracking)
User-Defined-13same as previous (Supervisory-AR)
HVAC OVRRIDE
4
Switch Supervisory, nonlatching (tracking)
Power-MonitorPower Fault
User-Defined-14same as previous (Power Monitor)
Trouble-MonitorTrouble
User-Defined-15same as previous (Trouble Monitor)
Process-Monitor
2
Piezo
User-Defined 16same as previous (Process-Monitor)
2, 3
Process-Monitor-AR
Piezo, nonlatching (tracking)
User-Defined-17same as previous (Process-Monitor-AR)
MNS EventAllows the Mass Notification System to override FACP programming and turn off
designated active outputs
Futurenot used
Futurenot used
Ack-SwitchActs like panel Acknowledge Key
Sil-SwitchActs like panel Silence Key
Reset-SwitchActs like panel Reset Key
Drill-SwitchActs like panel Drill Key
PAS-BypassPAS Disable
HVAC RESTART
Drill-Switch-AR
4
3
Switch
Drill Switch, nonlatching (tracking)
Table 3.1 Monitor Types
1 Conventional 2-wire smoke detectors may be powered using an external power supply with an
SLC Control Relay Module programmed for Resettable Power operation (refer to note 1 on
page page 84).
2 Combination systems employing these non-fire monitor types require the SLC loop to be
programmed by the installer for Style 4 operation and isolator modules must be employed on
each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC Wiring Manual # 51309.
Fire and non-fire devices must not be used on the same SLC branch.
3 For all entries ending in AR, AR refers to AutoResettable.
4 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module Operation”
on page 170.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201579
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Ye s and Pre-signal No. Refer to “Presignal” on page 135 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Wal ktes t N o. Refer to “Walktest” on page 137 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will
cause the following screen to be displayed:
80MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the monitor module currently being programmed.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the monitor module currently being programmed.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201581
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit.
Page 82
ProgrammingMaster Programming Level
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Monitor Screen #5
DESCRIPTION 1M012
NOUN/ADJECTIVE
Noun/Adjective Screen
Description
The Description selection allows the programmer to enter additional information about the monitor
module currently being programmed. This information will be displayed as part of the device label
on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause the following
screen to be displayed:
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
LCD display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 2, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Monitor Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position.
•If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed
, and the
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter.
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
•The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1.The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2.With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
3.With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4.Press the right arrow key to advance the zone field.
5.Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
82MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 83
Master Programming LevelProgramming
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
EDIT MODULE
ENTER MODULE ADDRESS
Edit Module Screen
NORMAL CONTROL
<ADJ><NOUN>
SW ZNNN
1M002
Edit Control Screen #1
EDIT CONTROL
1=ENABLED YES
2=TYPE CONTROL
3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST YES
2=ZONE ASSIGNMENT
00
Edit Control Screen #3
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Control Screen #4
EDIT CONTROL
1=MNS OVERRIDE NO
Edit Control Screen #5
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by pressing 3 in
the Modules Screen. The following screen will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed
in, if the selected address corresponds to a control module, a screen displaying information about
the control module with the selected address will be displayed as illustrated in the following:
In the preceding example:
•Normal - indicates that the module with the selected address is physically installed on the SLC
and communicating with the control panel (enabled).
•<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device.
•Control - indicates that the selected module is a control module.
•S or * - represents Silenceable (S) or Nonsilenceable (*).
•W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled).
•ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 099).
•1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 002 = Module Address 02).
MS-9600LS Series Manual — P/N 52646:B8 11/20/201583
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Control screens:
Enable/Disable Module
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No
is selected, the module will not be polled by the control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable
LED will turn on if any devices are disabled.
Page 84
ProgrammingMaster Programming Level
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00
Edit Control Screen #3
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type Screens.
Press the down arrow key to view additional screens and selections.
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad number key. The display will return to the Edit
Control Screen #2 and indicate the new type selection.
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board
24 VDC resettable power unless the control relay module is disabled.
The following table contains control module type codes and their functions which are displayed in
the Control Type screens:
Control Type Special Function
Bell CircuitNAC Type - supervised
Horn CircuitNAC Type - supervised
SoundersNAC Type - supervised
RelayIgnore Open Circuit
Strobe CircuitNAC Type - supervised
ControlNAC Type - supervised
Resettable Power
HVAC SHUTDN
1
2
Relay Type - Ignore Open Circuit
Relay Type - Ignore Open Circuit
1 When using a control relay module to supply resettable power to conventional 2-
wire smoke detectors, the MMF-302 monitor module must be set for smokeconventional operation.
2 For HVAC SHUTDN description, refer to “Control Module Operation” on
page 170.
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the
control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature
causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to
toggle between Silenceable Yes and Silenceable No.
Note that nonsilenceable outputs will not
be activated for Fire Drill.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Wal ktes t N o. Refer to “Walktest” on page 137 for additional information.
84MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the control
module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause
the following screen to be displayed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens.
Press the number corresponding to the adjective that is to be used as a descriptor for the location of
the control module currently being programmed.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201585
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press
the number corresponding to the noun that is to be used as a descriptor for the location of the control module currently being programmed.
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which
have been programmed into the control panel using the PS-Tools programming kit.
86MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Description
The Description selection allows the programmer to enter additional information about the control
module currently being programmed. This information will be displayed as part of the device label
on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the following screen to
be displayed:
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional
descriptive information about the device being programmed. This information will appear on the
display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters
from the keypad, repeatedly press the appropriate key until the desired character is displayed in the
first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle
through the characters 1, A, and B. Press the right arrow key to move the cursor one position to the
right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four
times until a blank appears in the desired position. When all characters have been entered, press the
Enter key to store the information. The display will return to the Edit Control Screen #4, displaying
the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position.
•If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter.
, and the
Page 87
Master Programming LevelProgramming
EDIT CONTROL
1=MNS OVERRIDE NO
Edit Control Screen #5
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #2
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE TO ENABLE
Z
Enable Screen
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE TO DISABLE
Z
Disable Screen
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
•The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1.The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2.With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
3.With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
4.Press the right arrow key to advance the zone field.
5.Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
MNS Override
The MNS Override feature, when enabled, allows the ECC-50/100 to override the FACP and turn
off an active control module or prevent the control module from activating during a mass notification event. Pressing 1 while viewing Edit Control Screen #5 will cause the display to change from
the factory default of MNS Override No to MNS Override Yes. Each press of the 1 key will cause
the display to toggle between the two options.
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #1 will access the Zone Setup screens as illustrated
below:
Enable
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.
Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, will display the following screen:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201587
Page 88
ProgrammingMaster Programming Level
SPEC PURPOSE ZONE
1=PAS 97 OFF
2=PRESIGNAL 98 OFF
3=TWO STAGE 99 OFF
Zone 97, 98 and 99 Screen
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONES INSTALLED
00 01 02 03 04 05
Zones Installed Screen
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.
Zone 97, 98 and 99
Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following
screen:
Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the three zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to input and output
devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PA S 9 7 O n . Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any detector will cause Zone 97 to activate. By assigning
Zone 97 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause
the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage Opera-
tion” on page 97 for a description of this feature.
Zones Installed
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
This display will show all of the zones that have been programmed into the control panel. Note that
an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional
zones.
88MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
ZONE TYPE PROG
1=Z00 MONITOR
2=Z01 MONITOR
3=Z02 MONITOR
Zones Installed Screen
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #2
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #3
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
This display will show all of the zones that are enabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:
This display will show all of the zones that are disabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.
Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:
This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201589
Page 90
ProgrammingMaster Programming Level
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable
zone can
be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
zone type to the selected zone. Any signaling devices programmed to the same
To program a waterflow circuit as nonsilenceable
, refer to “System Setup” on page 91.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Station.
Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
Zone Message
Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number
key corresponding to the Zone to be programmed. Screens will be displayed allowing the
programmer to select Audio Messages 1 through 14. When an audio message is selected, the
display will return to the Zone Message screen, showing the message selected for that particular
zone. In the example above, Zone 01 has been programmed for Audio Message 1.
90MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop(s) for NFPA Style 4, 6 or 7 wiring
and to select the protocol for each loop. Pressing 1 while viewing Programming Screen #2 will
cause the following screen to be displayed:
Loop Selection
Press 1 while viewing the Loop Selection Screen to configure Loop1 or 2 to configure Loop 2. The
following screens will appear for each loop.
Page 91
Master Programming LevelProgramming
Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup
Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle the
display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and
Style 6. Note that, when programming the Loop Style, the programmer can only select between
Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop
Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each
addressable device on the loop must have a pair of isolator modules, one on each side.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style
6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset
button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear
the SLC trouble.
Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. Refer to “Wire Requirements” on
page 168 for wire specifications based upon SLC protocol. Two modes of operation are available:
LiteSpeed and CLIP mode. CLIP mode (Classic Loop Interface Protocol) is used for the older legacy addressable devices such as the M300 Series modules and detectors. LiteSpeed mode is used
for newer addressable devices such as the 350 series (or newer) for quicker response times. Note
that the legacy devices can operate only
both modes of operation. Pressing 3 while viewing the Loop Setup Screen will allow the programmer to select between CLIP and LiteSpeed mode. Each press of the 3 key will toggle the setting
between CLIP and LiteSpeed mode.
in CLIP mode while the newer devices are compatible with
Device Addressing
It is important to note that the FACP addressable device capacity is 159 detectors and 159 control/monitor modules per SLC loop. Since older legacy addressable devices cannot be set to
addresses above 099, the newer series devices must be used when addresses 100 to 159 are to be
installed. It is permissible to mix old and new devices in the same panel, however, the FACP must
be programmed for CLIP mode.
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
•Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble
condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and
retransmit the trouble condition to the central station if connected.
•Banner: This option allows the user to change the top line of the LCD display from the blank
factory default readout to a user defined readout when the control panel is in Normal condition.
•Tim e-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
•Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
•NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
•Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201591
SYSTEM SETUP
1=TROUBLE REM OFF
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
FACTORY BANNER
Factory Banner Screen
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER - LINE 2
PRESS ENTER IF OK
User Defined Banner Screen #2
•Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 100).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
•Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.
•MNS Override: This option allows the Mass Notification System to override the FACP’s
specified NACs and control modules.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 91, for a
detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause
the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will
cause the display to toggle between Trouble Rem On and Trouble Rem Off.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
the following to be displayed:
Pressing 1 while viewing the Banner Screen will select the blank factory default banner setting and
display the following screen:
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the
Banner Screen.
Pressing 2 while viewing the Banner Screen will display the following screens :
92MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
These screens allow the programmer to enter a two line custom banner. A flashing cursor will
appear in the bottom left corner of each display. A maximum of 20 characters (including spaces)
can be entered into each screen for a total of two lines with 40 characters. After entering up to 20
characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the
second screen in the same manner or just press Enter if a second banner line is not being entered.
To quickly clear the current banner, press the CLR key.
Page 93
Master Programming LevelProgramming
SYSTEM SETUP
1=TROUBLE REM
2=BANNER
3=TIME-DATE
System Setup Screen #1
TIME AND DATE
1=TIME 10:00 AM
2=DATE 02-04-2010
3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
ENTER TIME
10:00 AM
1=AM 2=PM
Time Screen
ENTER DATE
MONTH DAY YEAR
02-04-2010
Date Screen
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the
desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A, and B. Press the right arrow key to
move the cursor one position to the right and repeat the process to enter the next character. To enter
a space, press the * (QZ) key four times to place a blank in the desired position. When all characters have been entered, press Enter to store the information and return to the Banner Screen.
Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup
Screen #1. The following screen will be displayed:
Time
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be displayed:
A flashing cursor is located toward the top left of the display. Below the cursor is the current time.
To change the time, enter the two-digit hours followed by the two-digit minutes. The cursor will
move one position to the right each time a digit is entered. After the last minutes digit is entered,
the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The
display will then return to the Time-Date Screen which will show the new time entry. If an error is
made while entering a digit, press the CLR key to delete the entire entry and beginning again.
Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed:
A flashing cursor is located toward the top left of the display. Below the cursor is the current date.
To change the date, enter the two-digit month followed by the two-digit day and then the two-digit
year (09 for 2009, 10 for 2010, etc.). The cursor will move one position to the right each time a
digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen
which will show the new date entry. If an error is made while entering a digit, press the CLR key to
delete the entire entry and beginning again.
Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3
while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR.
Select 12HR for 12 hour display or 24HR for 24 hour display.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201593
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
Page 94
ProgrammingMaster Programming Level
TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
DAYLIGHT SAVINGS
1=ENABLED YES
2=START MONTH MAR
3=START WEEK WEEK-2
DAYLIGHT SAVINGS
1=END MONTH NOV
2=END WEEK WEEK-1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
TIMERS
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
TIMERS
1=AC LOSS DELAY 000
Timer Screen #2
TIMERS
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing
1 will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first subscreen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first subscreen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
viewing System Setup Screen #2. The following screen will be displayed:
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
94MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 95
Master Programming LevelProgramming
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
TIMER
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
TIMER
1=AC LOSS DELAY
Timer Screen #2
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
Note that the FACP can be programmed for either PAS or Pre-signal operation, not both. Refer to
“Edit Detector” on page 69 for programming details.
Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any builtin delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2
to display the following:
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss
report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following screen:
A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1.
MS-9600LS Series Manual — P/N 52646:B8 11/20/201595
Page 96
ProgrammingMaster Programming Level
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
NACS
1=NAC 1 3=NAC 3
2=NAC 2 4=NAC 4
NAC Selection Screen
NAC #
1=ENABLED YES
2=TYPE BELL
3=SILENCEABLE YES
NAC Screen #1
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #2
NAC #
1=AUTO SILENCE 00
2=CODING
TEMPORAL
NAC Screen #3
NAC #
1=SYNC TYPE S
2=MNS OVERRIDE NO
NAC Screen #4
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be set by pressing 2 while
viewing System Setup Screen #2. The following screens will be displayed:
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.
The following screens will be displayed for either selection:
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.
Type
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
The following screen will be displayed. Press the down arrow key to view additional screens:
Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type CodeSpecial Function
BellNone
HornNone
StrobeNone
Synced StrobeSynchronized to manufacturer
Strobe Sil SyncSame as Synced Strobe but Silence turns off audible & visual devices
Future UseNone
Future UseNone
Future UseNone
BlankNone
96MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 97
Master Programming LevelProgramming
NAC #
1=AUTO SILENCE
2=CODING
TEMPORAL
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This
will prevent the selected main circuit board NAC from being silenced by pressing the Alarm
Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle
between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the Synced Strobe feature is selected, only the audible devices
will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to
operate. If the Strobe Sil Sync feature is selected, Silence will turn off both audible and visual
devices.
Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. When a time delay is selected, the information will be stored
in memory and the display will return to NAC Screen #2.
Coding
The Coding feature allows the programmer to select the type of output that the main circuit board
notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2
will cause the following displays to appear:
The programmer can select the notification appliance output by pressing the number corresponding
to the desired output. The coding selections are:
•Steady - a continuous output with no coding
•March Time - 120 ppm (pulse-per-minute) output
•California - 10 seconds on and 5 seconds off
•Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
•Two Stage - refer to “Two Stage Operation” on page 97 for description
Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #2, which will display the new coding choice.
•2nd stage output - Temporal coding as described above
MS-9600LS Series Manual — P/N 52646:B8 11/20/201597
Page 98
ProgrammingMaster Programming Level
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
ZONE ASSIGNMENT
Z00 Z Z Z Z
Zone Screen
If Two Stage operation is programmed as the Coding option, the following sequence of events will
occur during an alarm.
1.The on-board NACs which are programmed to General Alarm Zone 0 will activate with a 1st
stage output upon activation of any alarm point.
2.If the activated alarm point is directly mapped to a zone which is programmed to an on-board
NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly
mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage
output.
3.If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not
been pressed,
all NACs presently in 1st stage activation will go to 2nd stage activation.
4.If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation will
remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd
stage activation.
5.If another alarm point is activated and the countdown timer is counting, the alarm point will
have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the
NACs, in which case it will follow the procedure outlined in step 2.
6.If another alarm point is activated and the countdown timer has stopped counting due to the
Acknowledge switch being pressed, the countdown timer will restart and the NACs will
respond as outlined in step 2. NACs already in 2nd stage activation will not be affected.
7.Any control modules assigned to special Zone 99 will be activated either by direct mapping of
an input device programmed to Zone 99 or if the timer counts down to zero and the NAC goes
into 2nd stage coding.
8.Control modules that are programmed to the same zone as the activated input device will not
be delayed for activation.
Zone
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while
viewing NAC Screen #3 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory
default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear
on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this NAC. The cursor moves to the next Z** designation. Continue entering zone assignments
or the remaining zones can be left blank or programmed as general alarm zone Z00. When all
desired changes have been made, press the Enter key to store the zone assignments. The display
will return to the NAC Screen #3 which will show the zone assignments just entered.
Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
NAC for a period of one minute. Pressing 2 while viewing NAC Screen #3 will cause the display
to change from the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2
key will cause the display to toggle between the two options.
98MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Page 99
Master Programming LevelProgramming
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
NAC Screen #4
NAC SYNC TYPE
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
RELAY #
1=TYPE
ALARM
Relay Type Screen
Sync Type
If synchronized strobes were selected as the Type of device installed, the type of synchronization
must be selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following
screen to be displayed:
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock, and 3 will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 3.0 amps. Refer to
the manufacturer’s documentation supplied with the Strobes to determine the maximum current
draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can
be attached to each circuit. Following is a list of the strobes that have been tested with this FACP
and the maximum number that can be connected to each NAC. Make sure that the NAC maximum
current is not exceeded:
• System Sensor: 46 Strobes
• Wheelock: 42 Strobes
• Gentex: 39 Strobes
MNS Override
The MNS Override feature, when enabled, allows the ECC-50/100 to override the FACP and turn
off an active NAC or prevent the NAC from activating during a mass notification event. Pressing 2
while viewing NAC Screen #4 will cause the display to change from the factory default of MNS Override No to MNS Override Yes. Each press of the 2 key will cause the display to toggle between
the two options.
Relays
Pressing 3 while viewing System Setup Screen #2 allows the programmer to configure two of the
main circuit board Form-C relays from the following screen:
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The
following screen will appear for each relay to be programmed:
MS-9600LS Series Manual — P/N 52646:B8 11/20/201599
Page 100
ProgrammingMaster Programming Level
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
Relay Screen #3
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #2
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
Relay Screen #4
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Note the following:
1.AR (AutoResettable) in SUPERVISORY AR and PROCESS MON AR means that a relay with
the Supervisory and/or Process Monitor type code, when activated, will automatically reset
when the corresponding condition is cleared.
2.A relay programmed with the Silenceable Alarm type will activate upon any alarm and
deactivate when the FACP Alarm Silenced LED is illuminated.
Canadian Option
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Canadian requirements. The display will change to Canadian Opt. On. Each press of the 1 key will
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
•The following monitor module type codes are not available:
•monitor
• non-latching supervisory
• non-latching drill
• non-latching process monitor
• process monitor
• hazard
• tornado
• medical alert
•The auto-silence timer is fixed at 20 minutes and cannot be changed.
•Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
100MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.