Fire-Lite MS-9600LS, MS-9600LSE, MS-9600UDLS, MS-9600UDLSE, MS-9600LSC User Manual

Addressable Fire Alarm Control Panel
MS-9600LS/MS-9600LSE
MS-9600UDLS/MS-9600UDLSE
MS-9600LSC
Document 52646 11/20/2015 Rev:
P/N 52646:B8 ECN 15-642
B8
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication meth­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
2 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015

Table of Contents

Section 1: Product Description .............................................................................................12
1.1: Inventory......................................................................................................................................................12
1.2: Features and Options ...................................................................................................................................12
1.3: Specifications...............................................................................................................................................14
1.3.1: Current Availability...........................................................................................................................16
1.4: Controls and Indicators................................................................................................................................16
1.5: Circuits.........................................................................................................................................................17
1.6: Components .................................................................................................................................................18
1.6.1: Intelligent Addressable Detectors: Newer Series ..............................................................................19
1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19
1.6.3: 300 Series Intelligent Addressable Devices ......................................................................................19
1.6.4: Addressable Device Accessories.......................................................................................................19
1.7: Optional Modules ........................................................................................................................................20
1.8: Accessories ..................................................................................................................................................20
1.8.1: PS-Tools Programming Utility..........................................................................................................20
1.8.2: Dress Panel: DP-9692........................................................................................................................21
1.8.3: TR-CE Trim Ring..............................................................................................................................21
1.8.4: Battery Box........................................................................................................................................21
1.8.5: Battery Charger..................................................................................................................................21
CHG-75 Battery Charger......................................................................................................................21
CHG-120 Battery Charger....................................................................................................................21
1.8.6: ECC-50/100.......................................................................................................................................22
1.8.7: ECC-FFT ...........................................................................................................................................22
1.8.8: W-GATE Wireless Gateway .............................................................................................................22
1.8.9: ANN-BUS Annunciators/Devices.....................................................................................................22
ANN-80 Remote Fire Annunciator ......................................................................................................22
ANN-S/PG Serial/Parallel Interface Installation..................................................................................23
ANN-I/O LED Driver Module* ...........................................................................................................23
ANN-LED Annunciator Module*........................................................................................................23
ANN-RLY Annunciator Module..........................................................................................................23
1.8.10: Legacy ACS Annunciators ..............................................................................................................23
1.9: Getting Started .............................................................................................................................................24
Section 2: Installation.............................................................................................................26
2.1: Mounting......................................................................................................................................................26
2.2: Power ...........................................................................................................................................................30
2.2.1: AC Power and Earth Ground Connection .........................................................................................30
2.2.2: Battery Power ....................................................................................................................................30
2.2.3: Special Application DC Power Output Connection ..........................................................................31
2.3: Relays ..........................................................................................................................................................31
2.4: Notification Appliance Circuits...................................................................................................................31
2.4.1: Configuring NACs.............................................................................................................................32
2.4.2: Style Y (Class B) NAC Wiring .........................................................................................................33
2.4.3: Style Z (Class A) NAC Wiring..........................................................................................................33
2.5: Power-limited Wiring Requirements...........................................................................................................34
2.6: Optional Modules and Devices....................................................................................................................35
2.6.1: DACT-UD2 Installation ...................................................................................................................36
2.6.2: 4XTMF Transmitter Module Installation ..........................................................................................39
2.6.3: Auxiliary Trouble Input (J16 & J17) .................................................................................................41
2.6.4: SLC-2LS Expander Module ..............................................................................................................41
2.6.5: Printer/PC ..........................................................................................................................................42
2.6.6: ANN-BUS Annunciators/Devices.....................................................................................................44
ANN-BUS Wiring ................................................................................................................................44
ANN-BUS Device Addressing.............................................................................................................47
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 5
Table of Contents
ANN-80 Remote Fire Annunciator ......................................................................................................47
ANN-S/PG Serial/Parallel Interface Installation ..................................................................................50
PRN-7 Printer Installation ....................................................................................................................51
ANN-I/O LED Driver Module .............................................................................................................52
ANN-LED Annunciator Module ..........................................................................................................55
ANN-RLY Annunciator Module..........................................................................................................57
2.6.7: Automatic Audio Panel Control ........................................................................................................59
2.6.8: ACS Annunciators .............................................................................................................................61
Legacy ACM-8RF Relay Control Module ...........................................................................................61
Legacy ACM Series Annunciators .......................................................................................................61
2.6.9: ECC-FFT Firefighter Telephone .......................................................................................................62
2.6.10: W-GATE Wireless Gateway ...........................................................................................................62
Section 3: Programming ........................................................................................................ 64
3.1: Programming Data Entry .............................................................................................................................64
3.2: User Programming .......................................................................................................................................65
3.3: Initial Power-up............................................................................................................................................66
3.4: Programming Screens Description ..............................................................................................................66
3.5: Programming and Passwords.......................................................................................................................66
3.6: Master Programming Level .........................................................................................................................67
3.6.1: Autoprogram......................................................................................................................................67
3.6.2: Point Program ....................................................................................................................................68
Detector Programming..........................................................................................................................68
Module Programming...........................................................................................................................76
MNS Override ......................................................................................................................................87
3.6.3: Zone Setup .........................................................................................................................................87
Enable ...................................................................................................................................................87
Disable ..................................................................................................................................................87
Zone 97, 98 and 99 ...............................................................................................................................88
Zones Installed......................................................................................................................................88
Zones Enabled ......................................................................................................................................89
Zones Disabled .....................................................................................................................................89
Zone Type.............................................................................................................................................89
Zones Available....................................................................................................................................90
Zone Message .......................................................................................................................................90
3.6.4: Loop Setup.........................................................................................................................................90
Loop Selection ......................................................................................................................................90
Loop Protocol .......................................................................................................................................91
3.6.5: System Setup .....................................................................................................................................91
Trouble Reminder.................................................................................................................................92
Banner...................................................................................................................................................92
Time-Date.............................................................................................................................................93
Timers...................................................................................................................................................94
NAC (Notification Appliance Circuit) .................................................................................................96
Relays ...................................................................................................................................................99
Canadian Option .................................................................................................................................100
Waterflow Silenceable........................................................................................................................101
MNS Override ....................................................................................................................................101
3.6.6: Verify Loops....................................................................................................................................101
3.6.7: History .............................................................................................................................................101
View Events....................................................................................................................
Erase History ......................................................................................................................................102
3.6.8: Walktest ...........................................................................................................................................102
3.6.9: Option Modules ..............................................................................................................................103
Annunciators.......................................................................................................................................104
On Board DACT.................................................................................................................................116
Printer/PC ...........................................................................................................................................116
....................102
6 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Table of Contents
3.6.10: Password Change...........................................................................................................................117
3.6.11: Clear Program................................................................................................................................117
3.6.12: Program Check ..............................................................................................................................118
3.7: Maintenance Programming Level..............................................................................................................119
3.7.1: Disable Point ...................................................................................................................................119
3.7.2: History .............................................................................................................................................120
3.7.3: Program Check ................................................................................................................................121
3.7.4: Walktest...........................................................................................................................................122
3.7.5: System .............................................................................................................................................122
3.7.6: Zone Setup.......................................................................................................................................123
Zones Installed....................................................................................................................................124
Zones Enabled ....................................................................................................................................124
Zones Disabled ...................................................................................................................................124
Zone Type...........................................................................................................................................124
Zones Available..................................................................................................................................125
Zone Message.....................................................................................................................................125
Section 4: Operating Instructions .......................................................................................127
4.1: Panel Control Buttons................................................................................................................................127
4.1.1: Acknowledge/Step...........................................................................................................................127
4.1.2: Alarm Silence ..................................................................................................................................127
4.1.3: Drill/Hold 2 Sec...............................................................................................................................127
4.1.4: Reset ................................................................................................................................................127
4.2: LED Indicators...........................................................................................................................................127
4.3: Normal Operation ......................................................................................................................................128
4.4: Trouble Operation......................................................................................................................................129
4.5: Alarm Operation ........................................................................................................................................130
4.6: Supervisory Operation ...............................................................................................................................131
4.7: Process Monitor Operation ........................................................................................................................132
4.8: Hazard Condition Operation......................................................................................................................132
4.9: Medical Alert Condition Operation ...........................................................................................................132
4.10: Mass Notification Operation....................................................................................................................133
4.11: Programmed Zone Operation...................................................................................................................133
4.12: Disable/Enable Operation........................................................................................................................133
4.13: Waterflow Circuits Operation..................................................................................................................133
4.14: Detector Functions...................................................................................................................................133
4.15: Time Functions: Real-Time Clock...........................................................................................................134
4.16: NAC Operation ........................................................................................................................................134
4.17: Synchronized NAC Operation .................................................................................................................134
4.18: Coded Operation......................................................................................................................................135
4.19: Presignal ..................................................................................................................................................135
4.20: Positive Alarm Sequence.........................................................................................................................135
4.21: Special System Timers.............................................................................................................................136
4.21.1: Silence Inhibit Timer.....................................................................................................................136
4.21.2: Autosilence Timer .........................................................................................................................136
4.21.3: Trouble Reminder..........................................................................................................................136
4.21.4: Waterflow Retard Timer................................................................................................................137
4.21.5: Alarm Verification.........................................................................................................................137
4.22: Walktest ...................................................................................................................................................137
4.23: Read Status ..............................................................................................................................................138
4.23.1: System Point..................................................................................................................................138
4.23.2: Zones .............................................................................................................................................139
4.23.3: Power.............................................................................................................................................140
4.23.4: Trouble Reminder..........................................................................................................................140
4.23.5: Timers............................................................................................................................................140
4.23.6: NAC...............................................................................................................................................140
4.23.7: Relays ............................................................................................................................................141
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 7
Table of Contents
4.23.8: Program Check ..............................................................................................................................141
4.23.9: History ...........................................................................................................................................141
4.23.10: Annunciators................................................................................................................................142
4.23.11: Phone Line ...................................................................................................................................142
4.23.12: Central Station .............................................................................................................................143
4.23.13: Service Terminal..........................................................................................................................143
4.23.14: Printer/PC ....................................................................................................................................143
4.23.15: Print..............................................................................................................................................144
4.23.16: Time-Date ....................................................................................................................................145
Section 5: Power Supply Calculations ............................................................................... 146
5.1: Overview....................................................................................................................................................146
5.2: Calculating the AC Branch Circuit ............................................................................................................146
5.3: Calculating the System Current Draw .......................................................................................................146
5.3.1: Overview..........................................................................................................................................146
5.3.2: How to Use Table 5.3 on page 148 to Calculate System Current Draw .........................................147
5.4: Calculating the Battery Size.......................................................................................................................149
5.4.1: NFPA Battery Requirements ...........................................................................................................149
5.4.2: Selecting and Locating Batteries .....................................................................................................149
Appendix A: Software Zones............................................................................................... 150
A.1: Correlations...............................................................................................................................................150
Appendix B: Default Programming .....................................................................................158
Appendix C: NFPA Standard-Specific Requirements ....................................................... 159
C.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................165
C.2: MBT-1 Municipal Box Trip - Silenceable.................................................................................................166
Appendix D: FACP with Keltron ..........................................................................................167
Appendix E: Wire Requirements .........................................................................................168
E.1: NAC Wiring...............................................................................................................................................169
Appendix F: HVAC Control ..................................................................................................170
F.1: Control Module Operation .........................................................................................................................170
F.1.1: HVAC SHUTDN.............................................................................................................................170
F.2: Monitor Module Operation ........................................................................................................................170
F.2.1: HVAC RESTART ...........................................................................................................................170
F.2.2: HVAC OVRRIDE ...........................................................................................................................171
Appendix G: Canadian Applications................................................................................... 172
Index ......................................................................................................................................174
MS-9600LS Series & MS-9600UDLS Series Fire Alarm Control Panels........................... 181
8 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems ANSI/UL 864, Control Units and Accessories for Fire Alarm Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and System UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems Note: MS-9600LSE/MS-9600UDLSE is not ULC listed for Canadian applications
This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
FM Approved to ANSI/UL 864 Other:
EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309 ACS Series Annunciators Document #51480 411UD Communicator/Transmitter Document #50759 411UDAC Communicator/Transmitter Document #51073 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 LDM Series Lamp Driver Modules Document #50055 LCD-80F Remote Fire Annunciator Document #51338 ACM-8RF Relay Control Module Document #50362 DACT-UD2 Manual Document #53037 IDACT Communicator/Transmitter Document #53109 ANN-80 Installation Document Document #52749 ANN-(R)LED Installation Document Document #53032 ANN-I/O Installation Document Document #151416 ANN-RLY Installation Document Document #53033 ANN-S/PG Installation Document Document #151417 ECC-50/100 Manual Document #LS10001-000FL-E ECC-FFT Manual Document #LS10031-000FL-E Wireless Gateway Manual Document #LS10036-000FL-E ACC-25/50(ZS/T) Manual Document #51889
This product has been certified to comply with the requirements in the ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 9th Edition. Operation of this product with products not tested for ANSI/UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 9
+
B
A
T
T
E
R
Y
-
LCD DISPLAY
K
E
Y
P
A
D
I
/
F
O
P
T
D
A
C
T
J
3
J
2
T
B2
T
B
3
J
P
3
J
P
2
SW1
JP5
JP6
J
1
7
J16
J
6
J8
J
7
J
1
0
J1
1
R
E
M
O
V
E
T
O
D
I
S
A
B
L
E
L
O
C
A
L
C
H
A
R
G
E
R
D
I
S
A
B
L
E
G
N
D
F
L
T
S
LC OP
T
4
X
T
M
F
O
P
T
B
D
TB4
T
B
4
J
P
8
T
B
5
TB6
TB7
DB9
F
T
B
8
2
1
4
3
6
5
+
+
+
B
+
B
+
B
+
B
+
B
-
B
-
B
-
B-1
1
A
+
A
+
A
-
A
-
shiel
d
-
-
-
-
NO NC C
NC NO C N
O NC C
5 4 3 2 1
9 8 7 6
T
X
RCV
D
T
R
5 4 3
2 1
25 24 23 22 21 20 19 18 17 16
15 14
9 8 7 613 12 11 10
+
-
I
N
+
O
U
T
+
I
N
-
O
U
T
-
B
+
B
-
BA
+
A
-
A
NC NO C
+
+++
+
+
+
+
+
+
+
+
+
+
+
+++
T
X
R
C
V
DTR
G
N
D
GND
B+B-B
+
B
-
332
2
4
4
TB1
J
1
9600udleslayout.wmf
PS2 Keyboard Interface
Flash Memory Load Enable Switch
UP is normal position for switch
DOWN position allows loading of
factory software upgrades
Connector for Optional 2nd
Signaling Line Circuit
Connector for Optional
Onboard DACT-UD
Battery
24 VDC, 26 Amp Hour maximum
(supervised, nonpower-limited)
Auxiliary
Trouble Inputs
#1 2
To disable ground fault detection,
remove jumper/shunt from JP2.
Remove JP3 jumper to disable the FACP
battery charger when using external charger.
JP8- Install NACKEY board in proper
orientation to configure NACs 4
StyleY or 2 Style Z circuits
Connectors for 4XTMF Option Module
Cut this jumper to enable
Supervisory relay when
4XMTF is installed.
Cut this jumper to supervise
the 4XMTF when installed
(see J10 & J11)
(*Factory default relay programming
as shown on circuit board)
circuit number
ELRs 4.7K,
1/2W
NAC #1 NAC #3 NAC #4 NAC #2
Notification Applicance Circuits
Power-limited, supervised circuits
NAC #1, #2, #3, & #4, Style Y (Class B)
3.0 amps max per circuit JP8 configured for Class B
using NACKEY card
(factory default configuration)
SLC Loop
(Supervised Power-limited)
Refer to the SLC Wring
Manual for detailed
information on wiring
addressable devices for
Style 4, 6, and 7
TERM
(EIA-485)
to LCD-80F
EIA-232 to printer or
personal computer
Power-limited
for EDP-listed equipment
or personal computer with
FACP Upload/Downlad
Utility. 50 foot maximum
within same room.
OR
2 Programmable Relays &
1 Fixed Trouble Relay
(nonsupervised)
Contact Ratings:
2.0 amps @ 30VDC (resistive)
0.5 amp @ 30 VAC (resistive) Contacts show in normal condi-
tion (AC power with no alarm,
trouble, or supervisory activity).
A fail-safe trouble relay switches
to the NO position during
trouble conditions and
under loss all power.
ACN/ANN-BUS
(EIA-485)
to annunciators
(power-limited,
supervised)
Red
White
Green
Black
Alarm*
NO NC C
Trouble Supervisory*
NO NC C NO NC C
Notification Appliance Circuits
Special Application Power
Power-limited, supervised circuits
NAC #1 & #2 Style Z (Class A)
3.0 amps max per circuit JP8 configured for Class A
using NACKEY card
(See Style Y illustrated
near right edge of board)
NAC #1 NAC #2
Special Application Power
DC Power Outputs (24 VDC)
Power-limited, nonsupervised circuits
Supervise with a power supervision
relay EOLR-1
Nonresettable Power #2 - 24 VDC
filtered, power-limited, (1.5 amps
maximum) Supervision required.
Suitable for powering annunciators.
Nonresettable Power #1 - 24 VDC
filtered, power-limited, (1.5 amps
maximum) Supervision required.
Suitable for powering annunciators.
Resettable Power - 24 VDC filtered,
power-limited, (1.5 amps maximum)
to smoke detectors.
Supervision required.
Important: Removing Ground
Fault Disable jumper JP2 voids
UL/NFPA Style/Class
identification for circuits.
Remove jumper JP2 only with
AHJ (Authority Having
Jurisdiction) approval
Basic System Connections
10 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Peripheral Devices and Their Documents:
-
+
-
+
JP1
JP3
SW1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR DELAY
TENS
ONES
CUT FOR 240VAC
GND FLT DISABLE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
1 5
1 5
A- B- A+ B+
NC NO C
0
439
2615781213151410
11043926
1
5
7812
13
151410
11
J1
J2
J3
PH1
PH2
TB1
TBL
J1
J2
7 6 5 1
POWER LIMITED
Sw1
P1
P2
P3
P4
110
11 20
21 30 31
40
1 2
3 4
5
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
Alarm
Silenced
Earth Fault
ZONE 1
ALM
TBL
SUP
1
ZONE 6
ALM
TBL
SUP
6
NAC 1
Fault
Battery
Fault
ZONE 2
ALM
TBL
SUP
2
ZONE 7
ALM
TBL
SUP
7
NAC2
Fault
Charger
Fault
ZONE 3
ALM
TBL
SUP
3
ZONE 8
ALM
TBL
SUP
8
FIRE ALARM ANNUNCIATOR
NAC 4
Fault
ZONE 5
ALM
TBL
SUP5ALM
TBL
SUP
NAC 3
Fault
Disabled
ZONE 4
ALM
TBL
SUP
4
ZONE 9
ALM
TBL
SUP
9
T11 T10 T9 T8 T7 T6
T1 T2 T3 T4 T5
F
R
O
M
AP
P
HONE
PSTN
TO AP
OUT NC OUT
NO
INP
UT
T
AMPER GND
+12/24V
P4CN2P5
P
6
P
7P8P9P10P11P1
2
MS-9600LS
ADDRESSABLE
FIRE ALARM CONTROL PANEL
by Honeywell
Addressable Devices and SLC Wiring
Doc. # 51309
CHG-120F Charger
Doc. # 50888
SLC Loop
Battery Connector TB2
9600LSperi.wmf
CHG-75 Charger
Doc. # 51315
DACT-UD2 Communicator Doc. # 53037
J2 Connector
ANN (EIA-485) TB6
ANN-(R)LED
LED Display
Doc. #53032
ANN-I/O
LED Driver
Doc. #151416
ANN-RLY
Form-C Relay Card
Doc. #53033
ANN-S/PG
Printer Driver
Doc. #151417
ANN-80
Text Annunciator
Doc. #52749
4XTMF Reverse Polarity module
J10, J11 Connectors
IPDACT Internet Communicator Doc. # 53109
Audio Control for ECC-50/100 Emergency Command Center Doc. #LS10001-000FL-E or ACC-25/50(ZS/T) Audio-Command-Center Doc. #51889
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 11

Section 1: Product Description

The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable FACPs (Fire Alarm Control Panels) with an extensive list of powerful features. The combination of Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS or MS­9600UDLS FACP, offer the latest in fire protection technology. The FLPS-7 power supply is a sep­arate board while all other electronics are contained on a single main circuit board. Both boards are mounted to a chassis and housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for spe­cial functions. Available accessories include LED, graphic and LCD annunciators, reverse polar­ity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and remote upload/download software and remote power expansion.
The MS-9600UDLS includes a factory installed DACT-UD2 Digital Alarm Communicator Trans­mitter. Refer to “DACT-UD2 Installation” on page 36 and to the DACT-UD2 Manual Document #53037, which is supplied with the FACP, for DACT wiring and programming information. The DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone network. Local programming and interrogation is also possible for the MS-9600UDLS using the PS-Tools and the USB port J4 on the DACT-UD2. The MS-9600LS can be programmed and interrogated locally using the serial port at TB7. Any personal computer with Windows® XP or greater and compatible modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Ser­vice Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages.
The MS-9600LSC is a ULC approved Canadian version of the FACP which offers the same fea­tures as the MS-9600LS, but is supplied standard with a DP-9692 dress panel. Refer to “Canadian Option” on page 100 for a full description.
The MS-9600LSE and MS-9600UDLSE offer the same features as the MS-9600LS and MS­9600UDLS but allow connection to 220/240 VAC input.
NOTE: Unless otherwise specified, the terms FACP, MS-9600LS and MS-9600UDLS are used in this manual to refer to all versions of the FACPs.

1.1 Inventory

When the FACP shipment is received, check to make certain that all parts have been included in the shipment. The FACP shipment should consist of one of each of the following:
main circuit board with display
FLPS-7 Power Supply
chassis (with main circuit board and power supply mounted)
backbox with door and dress panel
plastic bag containing screws, cables, key, etc.
manual

1.2 Features and Options

Automated activation of the ECC-50/100 Emergency Command Center
ECC-FFT Firefighter Telephone option
LiteSpeed™ polling protocol for faster SLC response time
12 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Features and Options Product Description
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire or 3,000 ft (900 m) with untwisted, unshielded wire
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7 requirements
318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor modules)
99 software zones
Up to four onboard NACs (Notification Appliance Circuits): four Style Y (Class B) or two Style Z (Class A)
Additional NAC capability using control modules
7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm
Two programmable relay outputs and one fixed trouble relay
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
• Automatic drift compensation
• Maintenance alert
• Detector sensitivity test capability (NFPA 72 compliant)
• Automatic device type-code verification
• Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
New ANN-BUS Annunciators/Modules (ACS annunciators cannot be used when ANN-BUS annunciators/modules are connected)
• ANN-80 Remote Liquid Crystal Display point annunciator
• ANN-I/O LED Driver Module
• ANN-LED Alarm, Trouble, Supervisory Annunciator (minimum of one required for
Canadian applications)
• ANN-RLED Alarm Annunciator
• ANN-S/PG Serial/Parallel Printer Module
• ANN-RLY Form-C Relay Module
• Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
Legacy ACS/Term Annunciators: (ANN-BUS annunciator/modules cannot be used when ACS/Term annunciators are connected)
• ACM Series-LED Zone Annunciators
• LDM Graphic Annunciator Series
• LCD-80F Liquid Crystal Display point annunciator (LCD-80FC for Canadian applications)
• ACM-8RF Relay Module
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two­stage capability
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 13
Product Description Specifications
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, legacy ACS annunciators or ANN-80 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or keyboard or local PC
Compatible with Fire•Lite’s newer series addressable devices (LiteSpeed and CLIP Mode) ­Refer to SLC Wiring Manual for listing of all compatible addressable devices
Compatible with legacy Fire•Lite’s 300 Series devices (CLIP Mode only) - Refer to SLC Wiring Manual for listing of all compatible addressable devices
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional DACT-UD2 Digital Alarm Communicator Transmitter, reports up to 99 zones or 636 points (all devices) to a UL listed Central Station. The DACT-UD2 is supplied standard with the MS-9600UDLS/E
Optional PS-Tools programming utility for local or remote Upload/Download of programming and data (available for download at www.firelite.com)
Optional DP-9692 dress panel (required for Canadian applications)

1.3 Specifications

AC Power - TB1 of Power Supply Board
MS-9600LS(C) & MS-9600UDLS: 120 VAC, 50/60 Hz, 3.0 amps (L1=Hot, L2=Neutral) MS-9600LSE & MS-9600UDLSE: 240 VAC, 50 Hz, 1.5 amps (L1=Hot Leg 1, L2=Hot Leg 2) Wire size: minimum 14 AWG (2.00 mm
Battery (Sealed Lead Acid Only) - TB2
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp Maximum Battery Size: 26 Amp Hour Minimum Battery Size: 12 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 18 Amp Hour up to 26 Amp Hour batteries, use BB26 Battery Box) For greater than 26 Amp Hour up to 75 Amp Hour batteries, use the CHG-75 Battery Charger and BB26 or BB-55F Battery Box. For greater than 75 Amp Hour up to 120 Amp Hour batteries, use the CHG-120F Battery Charger and BB-55F Battery Box.
Jumper JP3, on the FACP main circuit board, must be removed to disable the FACP battery char­ger when using the CHG-75 or CHG-120F.
Communication Loop - (Standard) TB8 and (Optional SLC Expander Module) J3
24 VDC nominal, 27.6 VDC maximum Maximum length - refer to “Wire Requirements” on page 168 Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited Refer to SLC Wiring Manual for wiring information
2
) with 600 V insulation
NOTE: When installing SLC wiring in conduit, each loop must be installed in separate conduit.
14 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Specifications Product Description
Notification Appliance Circuits - TB4
Special Application power Power-limited circuitry, supervised NAC wiring requirements, refer to “NAC Wiring” on page 169 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 3.0 amps special application (see Figure 1.1 on page 16) Maximum signaling current per circuit: 300 mA regulated End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for NACs Refer to Device Compatibility Document for listed compatible devices
Two Programmable and One Fixed Output Relay - TB1 & TB5
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.5 on page 31 for information on power-limited wiring for relay circuits
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) ­TB3, Terminals 1 (+) & 2 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 1.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit, nonsupervised Refer to Device Compatibility Document for listed compatible devices
Nonresettable Special Application Power #1 (24 VDC Nominal) ­TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1) Power-limited circuit, nonsupervised
Nonresettable Special Application Power #2 (24 VDC Nominal) ­TB3, Terminals 5 (+) & 6 (-)
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 1.5 amps (see Figure 1.1) Power-limited circuit, nonsupervised
EIA-485 (ACS/ANN-BUS) - TB6
ACS/ANN annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -) Supervised, power-limited.
EIA-232 Serial - TB7
Local serial PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground) Non-supervised, power-limited.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 15
Product Description Controls and Indicators
1
2
3
4
5
6
7
8
1
2
3
4
5
6
TB4
TB3
Figure 1.1 Current Availability
powerdist9600ls2.wmf
*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby. Each circuit is capable of delivering the full 1.5 amps individually.
Refer to the battery calculations section for additional information.
1.5 amps max
per circuit
1.5 amps max
per circuit
1.5 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
Standby
1.5 Amps Max*
per panel
Resettable Special Application Power
for 4-wire smoke detectors
Alarm
7 Amps Max
per panel
Resettable Special Application Power
Power #1
Resettable Special Application Power
Power #2
NAC 1
Style Y or Z
NAC 2
Style Y or Z
NAC 3
Style Y only
NAC 4
Style Y only
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 020102

1.3.1 Current Availability

The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP power supply.

1.4 Controls and Indicators

16 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
Circuits Product Description
Figure 1.2 Membrane/Display Panel
9600kypd.wmf
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi­tions.

1.5 Circuits

SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is avail­able by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops, configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring Manual for infor­mation on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Special Application Power
24 VDC Battery Charger (up to 26 AH batteries)
• 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 17
Product Description Components
ms-9600LS.wmf
NAC (Notification Appliance Circuits)
Up to four NACs are provided with various programmable features:
four Style Y (Class B) NACs OR
two Style Z (Class A) NACs
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following oper­ations:
fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
•AC loss
Auxiliary Trouble Inputs
Auxiliary Trouble Inputs can be connected to trouble bus outputs from auxiliary equipment, such as power supplies or normally-open dry contacts of a trouble relay to allow monitoring by the FACP.

1.6 Components

Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring inter­face connectors. Optional modules plug in and are mounted to the main circuit board. The circuit board is delivered mounted to a chassis which must be mounted to the backbox. Refer to the circuit board illustration on Page 10.
FLPS-7 Power Supply
The FLPS-7 Power Supply is provided as a separate module which is delivered mounted to a chas­sis which must be mounted to the backbox and connected to the main circuit board.
Cabinet
The FACP cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel DP-9692, which mounts to the inside of the cabinet (required by ULC for Canadian applications).
Batteries
Batteries must be sealed lead acid type. The FACP cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour up to 26 Amp Hour require use of the BB-26 or similar UL listed battery cabinet. The CHG-75 can be used for charging 26 to 75 AH batteries and
18 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Components Product Description
the BB-26 can be used for housing the batteries. The CHG-120F can be used for charging 26 to 120 AH batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered sep­arately.

1.6.1 Intelligent Addressable Detectors: Newer Series

Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wir­ing and operation). This allows the control panel to continually process the information to deter­mine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches with the abil­ity to select up to 159 addresses. Note that a blinking LED on an intelligent detector indicates com­munication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, that loop must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of com­patible addressable detectors.

1.6.2 Intelligent Addressable Modules: Newer Series

The newer series of Control Modules and Monitor Modules provide an interface between the con­trol panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches with the ability to select up to 159 addresses (a tab on the address switch must be broken off to use addresses 100-159). A blinking LED on a monitor mod­ule indicates communication between the module and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the loop must be pro­grammed to operate in CLIP mode. Refer to the SLC Wiring Manual for a complete list of compat­ible addressable modules. Refer to the Device Compatibility Document for a list of approved
notification and initiating devices.

1.6.3 300 Series Intelligent Addressable Devices

Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9600LS FACP. The FACP must be configured for CLIP Mode operation if the control panel is installed in an existing system with 300 Series devices. The address of 300 Series devices cannot be set above
99. Refer to the SLC Wiring Manual for a complete list of compatible addressable devices.

1.6.4 Addressable Device Accessories

End-of-Line Resistor Assembly P/N R-47K
The 47 KΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 KΩ End-of-Line Resistor assembly is used to supervise the MMF-302 module circuit. The resistors are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay (P/N: EOLR-1) is used to supervise the power to 4-wire smoke detectors and notification appliances.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 19
Product Description Optional Modules
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control module circuit.

1.7 Optional Modules

The FACP main circuit board includes option module connectors for the following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J10 and J11 which are located near the top left of the main circuit board. When the 4XTMF module is installed, Jumper JP6, on the main circuit board, must be cut to allow supervision of the module.
SLC-2LS Expander Module
The SLC-2LS Expander Module allows expansion of the FACP from one SLC circuit to two SLC circuits. The module plugs into connector J3 which is located in the lower right corner of the main circuit board. The wiring for the second SLC connects to terminals located on the expander mod­ule.
DACT-UD2 Digital Alarm Communicator/Transmitter
The DACT-UD2 is used to transmit system status to UL-listed Central Station receivers via the public switched telephone network. All circuitry and connectors are contained on a compact mod­ule which plugs into connector J2, which is located near the bottom center of the main circuit board.
The MS-9600UDLS/E is provided with a factory installed DACT-UD2. Refer to “DACT-UD2 Installation” on page 36 and to the DACT-UD2 manual, which is included with the FACP, for DACT-UD2 wiring and programming information.
IPDACT - Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to allow FACP status communication to a Central Station via the internet. No telephone lines are required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT con­verts the standard DACT phone communication to a protocol that can be transmitted and received via the internet. It also checks connectivity between the FACP and Central Station. Refer to the IPDACT Product Installation Document P/N 53109 for additional information.

1.8 Accessories

1.8.1 PS-Tools Programming Utility

The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible computers (PC), running Windows™ XP or newer. FACP program files can also be created and stored on the PC and then downloaded later to the control panel. The P/N: PK-CD Kit includes the FACP Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required by the MS-9600UDLS for local connection of the PC to the USB port J4 on the DACT-UD2. The MS-9600LS requires connection to the Serial Port on FACP con­nector TB7. Remote programming requires that the PC have a 2400 baud or faster modem.
20 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Accessories Product Description
dp9600.wmf
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to the DACT-UD2 manual). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.

1.8.2 Dress Panel: DP-9692

A DP-9692 dress panel is available for the FACP (required for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel.
The MS-9600LSC has received ULC approval. ULC approval is contingent on the proper installa­tion of the dress panel which is provided with the FACP

1.8.3 TR-CE Trim Ring

An optional TR-CE trim ring is available for semi-flush mounting the FACP backbox.

1.8.4 Battery Box

BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box is red and is provided with knockouts.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120 is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.

1.8.5 Battery Charger

CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9600LS FACP. The FACP battery charger must be disabled when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120 Battery Charger
The CHG-120 is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled when using the CHG-120. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120 Manual for additional information.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 21
Product Description Accessories

1.8.6 ECC-50/100

The ECC-50/100 is a single channel, 50 watt, 25 V may be used for fire applications, mass notification applications, or both. Automatic activation of the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via the ACS/ANNBUS serial communications link from the FACP.

1.8.7 ECC-FFT

An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The ECC-FFT’s keypad provides indications of phone activation and corresponding trouble conditions.

1.8.8 W-GATE Wireless Gateway

The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the MS-9600LS. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply. Available wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor module. For details about wireless devices, system setup, and operation, see the SWIFT™ Smart Wireless Integrated Fire Technology Instruction Manual.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission (FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be legally used outside the USA.
, emergency voice evacuation panel that
RMS

1.8.9 ANN-BUS Annunciators/Devices

The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due to incompatible serial communication protocols.
A variety of optional devices can be connected to the FACP EIA-485 ANN-BUS communication circuit. Compatible devices include:
ANN-80 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
ANN-RLED Annunciator Module (red alarm LEDs only)
ANN-RLY Relay Module
ANN-80 Remote Fire Annunciator
The ANN-80(-W) Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervi­sory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely perform­ing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employ­ing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
22 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Accessories Product Description
!
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled through the FACP software. Refer to “ANN-BUS Options” on page 106 for a description of this feature and programming information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two min­utes without any buttons being pressed on the annunciator, a trouble indication will be annunciated.
ANN-S/PG Serial/Parallel Interface Installation
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting.
ANN-I/O LED Driver Module*
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs The module is provided with a plastic enclosure for mounting inside the annunciator or accessory box.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi­sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-LED Annunciator Module*
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general sys­tem faults and input zones/points when used with a compatible FACP. The ANN-LED module pro­vides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full system coverage.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi­sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.

1.8.10 Legacy ACS Annunciators

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due to incompatible serial communication protocols.
ACM Series LED Zone Type Annunciators
The ACM Series Annunciators remotely display alarm and trouble status as well as system status. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the FACP.
ACM-16ATF - Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. *In Canada, this module must be used to annunciate the fire alarm input points/zones only.
AEM-16ATF - Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. *In Canada, this module must be used to annunciate the fire alarm input points/zones only.
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 23
Product Description Getting Started
ACM-32A - Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. *In Canada, this module must be used to annunciate the fire alarm input points/zones only.
AEM-32AF - Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs. *In Canada, this module must be used to annunciate the fire alarm input points/zones only.
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that is capable of displaying English language text. Tactile switches provide remote system Acknowledge, Silence, Drill and Reset functions. A keyswitch allows enabling/disabling of the tactile switches. Commu­nications between the control panel and the annunciator is accomplished over a serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be con­nected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to the LCD-80F manual.
The LCD-80F is not for use in Canadian applications.
LCD-80FC Remote Fire Annunciator (for use in Canadian applications)
The LCD-80FC is identical to the LCD-80F except for the tactile switches and keyswitch. There is no keyswitch, and tactile switches are provided for local silence and lamp test only. No remote sys­tem functions can be performed from the LCD-80FC annunciator.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator.

1.9 Getting Started

The following is a brief summary of the minimal steps involved in bringing an MS-9600LS/MS­9600UDLS on-line:
Install Backbox, Power Supply and Main Circuit Board (refer to “Mounting” on page 26).
Address and Install Intelligent Devices (refer to the SLC Wiring Manual).
Enter Autoprogramming (refer to “Autoprogram” on page 67).
Resolve Programming Conflicts.
Go to Point Program to Enter Specific Data (refer to “Point Program” on page 68). Use the right and left arrow keys to navigate between devices.
24 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Notes
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 25
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting

The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies.
Mark and predrill holes in the wall for the center top keyhole mounting bolt using the dimen­sions illustrated in Figure 2.2 on page 28.
Install center top fastener in the wall with the screw head protruding.
Place backbox over the top screw, level, and secure.
Mark and drill the left and right upper and lower mounting holes. Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
Install remaining fasteners and tighten.
Attach solid earth ground wire to grounding stud as indicated in Figure 2.1.
When the location is dry and free of construction dust, install the main circuit board chassis by positioning the two mounting tab holes on the top of the chassis over the mounting studs in the top of the backbox and sliding the mounting tabs at the bottom of the chassis into the mounting slots in the bottom of the backbox as illustrated below.
Secure the chassis to the mounting studs with the supplied nuts.

Section 2: Installation

26 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Mounting Installation
126#1
st
EVENT
ABC
DEF
JKL
MNO
TUV WXY
-/.
CLR
9
ESC
ENTER
RECALL
ACK/STEP
ALARM SILENCE
DRILL
HOLD 2 SEC
RESET
MODE
Figure 2.1 FACP Main Circuit Board Installation
9600lsbrdinbox.wmf
grounding stud:
attach solid earth
ground wire (refer to
“AC Power and
Earth Ground
Connection” on
page 30)
FACP Backbox
Main Circuit Board on Chassis
mounting studs
mounting slots
mounting tabs
mounting tab holes
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 27
Installation Mounting
3.37 cm
1.325“
3.37 cm
4.13 cm
4.1 cm
1.625“ (4.128 cm)
1.625“
16.65“ (42.29 cm)
2.00“
4.128 cm
1.00“ (2.54 cm)
1.30“
3.30 cm
13.23 cm
5.207“
12.00“ (30.48 cm)
2.325“ (5.91 cm)
1.625“
4.13 cm
1.625“
1.325“
2.00“
2.00“
2.00“
2.00“
2.00“
5.1 cm
2.00“
16.0“
40.64 cm
5.207“
13.23 cm
29.95 cm
11. 79 2“
4.45cm
1.75“
4.45cm
1.75“
17.83cm
7.02“
2.00“
16.00“ (40.64 cm)
4.1cm
1.625“
12.13cm
4.775"
38.1 cm
15.00“
7.0 cm
2.75“
1.25“ (3.2 cm)
15.0“
38.1 cm
4.535“
11. 52 c m
12.13 cm
4.775“
6.0“
15.24 cm
48.37cm
19.0“
Figure 2.2 FACP Cabinet Mounting
9050udencl.wmf
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering
venting holes on top of
box.
Hinge Slot for optional Dress Panel
Hinge Slot for optional Dress Panel
Semi-flush mounting hole
Mounting slots for optional Trim Ring
28 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Mounting Installation
= 19.26" (48.92 cm)
= 19.0" (48.26 cm)
5.325" (13.526 cm)
= 16.821" (42.73 cm) = 16.65" (42.29 cm)
= 5.207" (13.23 cm)
Figure 2.3 FACP Cabinet Dimensions
9600cabnew.wmf
Door Backbox
Left Side
Door
Backbox
Bottom
Right Side
Top
Depth
Depth =
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 29
Installation Power
!
Hot L1
Neut L2
EARTH
120 VAC
tb1.wmf
Interconnect Cable
!

2.2 Power

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DIS­CONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.

2.2.1 AC Power and Earth Ground Connection

Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9600LS(C) and MS-9600UDLS or 240 VAC, 50 Hz, 1.5 amps for the MS-9600LSE and MS-9600UDLSE. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 mm wire with 600 volt insulation rating. Make certain that the AC mains circuit breaker is off
before wiring any connections between the mains and the control panel. Connect wiring from the AC mains to TB1 on the FLPS-7 Power Supply, being careful to observe proper connections. Illustration depicts connection of 120 VAC to TB1. Note that the FLPS-7 Power Supply is con­nected to the main circuit board by a cable connected to J1. Ensure that this cable is connected.
2
) or larger
Connect a wire from the grounding stud in the cabinet to a known solid earth ground (refer to Fig­ure 2.1 on page 27). This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must
be applied to the panel before installing the battery interconnect cable (refer to the following sec­tion).

2.2.2 Battery Power

Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not Do not connect the interconnect cable until the system is com­pletely installed. Observe polarity when connecting the batter­ies. Connect the battery cable to TB2 on the main circuit board. Refer “Power Supply Calculations” on page 146, for calculation of the correct battery rating.
WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
connected.
30 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Loading...
+ 154 hidden pages