Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
TB5
ALARM TRBL SUPV
MS-9600 Control Panel
Document 51530 Rev A0 February 1, 2001
Note: Cut TBL jumper on 4XTMF/4XTM
module to send alarm/trouble signal from
the same pair of terminals.
Sprinkler Supervisory Signal
Alarm/Trouble Signal
4XTMF
R1
3.3K
0.5w
R2
3.3K
0.5w
RP-3.3K
10
UL Listed
5
6
7
8
9
KELTRON
TTM-RPS
95M3158
1
2
3
4
TIP
EARTH
RING
TELEPHONE LINE
ings for exact terminal locations to prevent severe
module damage!
ignations of Keltron modules are not shown in ac-
tual order. Follow Keltron manual and module mark-
For reasons of wiring diagram clarity, terminal des-
CAUTION!
EARTH
RING
TIP
TB3
(24 VDC,
Non-Resettable)
* Note: For more information,
refer to Keltron manual.
1
2
3
4
5
6
KELTRON*
95M3083
TRM-RP
UL Listed
10
7
8
9
with Keltron RCVR/XMTR
POWER
SUPPY
TO
*
STATION
TO CENTRAL
Wiring Diagram
51530 Revision A
February 1, 2001
MS-9600
ECN 01-053