Fire-Lite MS-9200UDLSC User Manual

Addressable Fire Alarm Control Panel
MS-9200UDLS
MS-9200UDLSE
MS-9200UDLSC
Document 52750 4/14/2014 Rev:
P/N 52750:H ECN 14-226
H
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warn ing of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association S tandard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http: // www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States governme nt) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment l
is
ted for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dus t, dirt, or hig h air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthl y or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only . Adequate written reco rds of all inspecti ons should be kept.
Limit-D-1-2013
2 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™, Lite-Connect™, and SWIFT™ are trademarks; and Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Table of Contents

Section 1: Product Description .............................................................................................13
1.1: Features and Options ...................................................................................................................................13
1.2: Specifications...............................................................................................................................................15
1.3: Controls and Indicators................................................................................................................................17
1.4: Digital Alarm Communicator/Transmitter ..................................................................................................18
1.5: Components.................................................................................................................................................18
1.5.1: Intelligent Addressable Detectors: Newer Series ..............................................................................19
1.5.2: Intelligent Addressable Modules: Newer Series ...............................................................................19
1.5.3: 300 Series Intelligent Addressable Devices ......................................................................................20
1.5.4: Addressable Device Accessories.......................................................................................................20
End-of-Line Resistor Assembly...........................................................................................................20
Power Supervision Relay .....................................................................................................................20
EOL-C(R/W) Mounting Plate ..............................................................................................................20
1.6: Optional Modules ........................................................................................................................................20
1.7: Accessories ..................................................................................................................................................20
1.7.1: PS-Tools Programming Utility..........................................................................................................20
1.7.2: DP-9692 Dress Panel.........................................................................................................................21
1.7.3: Trim Ring ..........................................................................................................................................21
1.7.4: Multi-Module Mounting Bracket ......................................................................................................21
1.7.5: Battery Box........................................................................................................................................21
BB-26 ...................................................................................................................................................21
BB-55F.................................................................................................................................................21
1.7.6: Battery Charger..................................................................................................................................22
CHG-75 Battery Charger.................................................................................. ....................................22
CHG-120F Battery Charger .................................................................................................................22
1.7.7: IPDACT Internet Protocol DACT.....................................................................................................22
1.7.8: ECC-50/100.......................................................................................................................................22
1.7.9: ECC-FFT...........................................................................................................................................22
1.7.10: ANN-BUS Annunciators/Modules..................................................................................................22
Guidelines.....................................................................................................................
Remote Fire Annunciator ......................................................................................................23
-80
ANN
ANN-S/PG Serial/Parallel Interface Module .......................................................................................23
ANN-I/O LED Driver Module.............................................................................................................23
ANN-LED Annunciator Module..........................................................................................................24
ANN-RLY Annunciator Module..........................................................................................................24
ANN-LC Lite-Connect Module ...........................................................................................................24
1.7.11: Legacy ACS Series LED Zone Type Annunciators........................................................................24
LCD-80F/LCD-80FC Remote Fire Annunciator/Indicator..................................................................24
LDM Series Lamp Driver Modules (Graphic Annunciator)................................................................25
Legacy ACM-8RF Relay Control Module...........................................................................................25
1.8: Getting Started.............................................................................................................................................25
1.9: Telephone Requirements and Warnings.......................................................................................................25
1.9.1: Telephone Circuitry...........................................................................................................................25
1.9.2: Digital Communicator.......................................................................................................................26
1.9.3: Telephone Company Rights and Warnings.......................................................................................26
1.9.4: For Canadian Applications..............................................................................................................27
........................22
Section 2: Installation.............................................................................................................28
2.1: Mounting the Backbox ................................................................................................................................28
2.2: Mounting Optional Transformer/Remounting Chassis................................................................................29
2.3: Power...........................................................................................................................................................32
2.3.1: AC Power and Earth Ground Connection.........................................................................................32
2.3.2: Battery Power....................................................................................................................................33
2.3.3: Special Application DC Power Output Connection..........................................................................33
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 5
Table of Contents
2.4: Relays...........................................................................................................................................................33
2.5: Notification Appliance Circuits...................................................................................................................34
2.5.1: Style Y (Class B) NAC Wiring .........................................................................................................34
2.5.2: Style Z (Class A) NAC Wiring with ZNAC-92 Converter ...............................................................35
2.6: Remote Synchronization Output ..................................................................................................................35
2.7: UL Power-limited Wiring Requirements.....................................................................................................36
2.8: Digital Communicator .................................................................................................................................38
2.8.1: Ferrite Clamp Installation..................................................................................................................39
2.9: Optional Module Installation.......................................................................................................................39
2.9.1: 4XTMF Transmitter Module Installation..........................................................................................39
2.9.2: ANN-BUS Annunciators/Modules....................................................................................................42
ANN-BUS Wiring................................................................................................................................42
ANN-BUS Device Addressing.............................................................................................................45
ANN-80 Remote Fire Annunciator ......................................................................................................46
ANN-S/PG Serial/Parallel Interface Module........................................................................................49
ANN-I/O LED Driver Module .............................................................................................................52
ANN-LED Annunciator Module..........................................................................................................54
ANN-RLY Annunciator Module..........................................................................................................56
ANN-LC Lite-Connect Module............................................................................................................58
2.9.3: Printer ................................................................................................................................................59
Installation ............................................................................................................................................60
Printer Configuration............................................................................................................................60
2.9.4: ECC-FFT Firefighter Telephone .......................................................................................................61
2.10: Automatic Audio Panel Control.......................................... .......................................................................61
Section 3: Programming........................................................................................................63
3.1: Programming Data Entry.............................................................................................................................63
3.2: User Programming.......................................................................................................................................64
3.3: Initial Power-up............................................................................................................................................65
3.4: Programming Screens Description ..............................................................................................................65
3.5: Programming and Passwords.......................................................................................................................65
3.6: Master Programming Level .........................................................................................................................66
3.6.1: Autoprogram......................................................................................................................................66
3.6.2: Point Program....................................................................................................................................67
Detector Programming..........................................................................................................................67
Enable/Disable Detector.......................................................................................................................70
Type......................................................................................................................................................70
Verification...........................................................................................................................................70
Walktest................................................................................................................................................71
PAS.......................................................................................................................................................71
Pre-signal..............................................................................................................................................71
Zone Assignment..................................................................................................................................72
Noun/Adjective.....................................................................................................................................72
Description............................................................................................................................................74
Recall/Increment Function....................................................................................................................74
Module Programming...........................................................................................................................75
Enable/Disable Module ........................................................................................................................77
Type Monitor........................................................................................................................................77
Pre-signal..............................................................................................................................................79
Walktest................................................................................................................................................79
Zone Assignment..................................................................................................................................79
Noun/Adjective.....................................................................................................................................79
Description............................................................................................................................................81
Recall/Increment Function....................................................................................................................81
Enable/Disable Module ........................................................................................................................82
Type......................................................................................................................................................83
Silenceable............................................................................................................................................83
6 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Table of Contents
Walktest................................................................................................................................................83
Zone Assignment..................................................................................................................................84
Noun/Adjective.....................................................................................................................................84
Description ...........................................................................................................................................86
Recall/Increment Function ...................................................................................................................86
MNS Override.................................................................................................. ....................................86
3.6.3: Zone Setup.........................................................................................................................................87
Enable...................................................................................................................................................87
Disable..................................................................................................................................................87
Zone 97, 98 and 99...............................................................................................................................87
Zones Installed......................................................................................................................................88
Zones Enabled......................................................................................................................................88
Zones Disabled.....................................................................................................................................88
Zone Type.............................................................................................................................................89
Zones Available....................................................................................................................................89
Zone Message.......................................................................................................................................90
3.6.4: Loop Setup.........................................................................................................................................90
Style......................................................................................................................................................90
Loop Protocol.......................................................................................................................................90
Device Addressing........................... .................................. ...................................................................91
3.6.5: System Setup .....................................................................................................................................91
Trouble Reminder.................................................................................................................................92
Banner...................................................................................................................................................92
Time-Date.............................................................................................................................................93
Timers...................................................................................................................................................94
NAC (Notification Appliance Circuit).................................................................................................96
Relays.................................................................................................................................................100
Canadian Option.................................................................................................................................100
Waterflow Silenceable........................................................................................................................101
MNS Override.................................................................................................. ..................................101
Lite-Connect.......................................................................................................................................101
3.6.6: Verify Loop .....................................................................................................................................102
3.6.7: History.............................................................................................................................................102
View Events................................ .................................. ......................................................................102
Erase History................................... .................................. .................................................................103
3.6.8: Walktest...........................................................................................................................................103
3.6.9: Option Modules..............................................................................................................................104
Annunciators.......................................................................................................................................105
ANN-I/O Options...............................................................................................................................108
Onboard DACT.................................................................... ..............................................................118
Central Station Primary and Secondary Phone Numbers...................................................................120
Test Time Interval .................................................. .................................. .........................
....................................................................................................................................121
Account Code
.
.................120
24 Hour Test Time..............................................................................................................................121
Phone Number....................................................................................................................................121
Communication Format......................................................................................................................121
Event Codes........................................................................................................................................122
Ademco Contact ID & SIA Formats..................................................................................................122
Report Style........................................................................................................................................124
Printer/PC...........................................................................................................................................125
3.6.10: Password Change......................................... .................................. ................................................125
3.6.11: Clear Program............................................................ ....................................................................126
3.6.12: Program Check.................................... .................................. ........................................................126
3.7: Maintenance Programming Level..............................................................................................................127
3.7.1: Disable Point ...................................................................................................................................128
3.7.2: History.............................................................................................................................................128
3.7.3: Program Check................................................................................................................................129
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 7
Table of Contents
3.7.4: Walktest...........................................................................................................................................130
3.7.5: System..............................................................................................................................................131
3.7.6: Zone Setup.......................................................................................................................................131
Section 4: Operating Instructions.......................................................................................133
4.1: Panel Control Buttons................................................................................................................................133
4.1.1: Acknowledge/Step...........................................................................................................................133
4.1.2: Alarm Silence ..................................................................................................................................133
4.1.3: Drill/Hold 2 Sec...............................................................................................................................133
4.1.4: Reset ................................................................................................................................................133
4.2: LED Indicators...........................................................................................................................................133
4.3: Normal Operation ......................................................................................................................................134
4.4: Trouble Operation......................................................................................................................................135
4.5: Alarm Operation ........................................................................................................................................136
4.6: Supervisory Operation ...............................................................................................................................137
4.7: Process Monitor Operation ........................................................................................................................138
4.8: Hazard/Tornado Condition Operation........................................................................................................138
4.9: Medical Alert Condition Operation ...........................................................................................................139
4.10: Mass Notification Operation.............................. .................................. ....................................................139
4.11: NAC Operation........................................................................................................................................139
4.12: Programmed Zone Operation...................................................................................................................140
4.13: Disable/Enable Operation............................... .................................. .......................................................140
4.14: Waterflow Circuits Operation..................................................................................................................140
4.15: Detector Functions........................................................ ...........................................................................140
4.16: Time Functions: Real-Time Clock...........................................................................................................141
4.17: Synchronized NAC Operation.................................................................................................................141
4.18: Coded Operation............................... .................................. .....................................................................141
4.19: Presignal..................................................... ..............................................................................................141
4.20: Positive Alarm Sequence.........................................................................................................................142
4.21: Special System Timers....................................................................................... ......................................142
4.21.1: Silence Inhibit Timer.............................................................. .......................................................142
4.21.2: Autosilence Timer ............................. ................................................................. ...........................143
4.21.3: Trouble Reminder............................................ .................................. ............................................143
4.21.4: Waterflow Retard Timer.................................. .................................. ............................................143
4.21.5: Alarm Verification (None or One Minute)....................................................................................143
4.22: Walktest............................................................................ ........................................................................144
4.23: Read Status.................................................................... ...........................................................................144
4.23.1: System Point.............................. ................................................................. ...................................145
4.23.2: Zones........................................................................................................ ......................................146
4.23.3: Power............................................................... ..............................................................................146
4.23.4: Trouble Reminder............................................ .................................. ............................................147
4.23.5: Timers.............................................................. ..............................................................................147
4.23.6: NAC............................................................................. ..................................................................147
4.23.7: Relays ............................. ................................................................. ..............................................147
4.23.8: Program Check ............................................................ .................................. ................................148
4.23.9: History ........................................................ .................................. .................................................148
..................148
4.23.10: Annunciators...........................................................................................................
4.23.11: Phone Line...................................................................................................................................149
4.23.12: Central Station .............................................................................................................................149
4.23.13: Service Terminal..........................................................................................................................150
4.23.14: Printer/PC ....................................................................................................................................150
4.23.15: Print..............................................................................................................................................150
Chamber Value.............................................................. .....................................................................151
Drift Compensation .......................................................... .................................. ................................151
Maintenance Alert ..............................................................................................................................151
4.23.16: Time-Date....................................................................................................................................152
...
8 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Table of Contents
Section 5: Central Station Communications......................................................................153
5.1: Transmittal Priorities.................................................................................................................................154
Section 6: Remote Site Upload/Download..........................................................................156
6.1: Remote Download .....................................................................................................................................156
6.2: Transferring a Program..............................................................................................................................157
6.2.1: Security Features .............................................................................................................................157
Secret Code Verification ....................................................................................................................157
Time-out at Control Panel.................................................................. ................................................158
Error Checking ...................................................................................................................................158
Central Station Data Protection..........................................................................................................158
Section 7: Power Supply Calculations................................................................................159
7.1: Overview....................................................................................................................................................159
7.2: Calculating the AC Branch Circuit............................................................................................................159
7.3: Calculating the System Current Load ........................................................................................................159
7.3.1: Overview .........................................................................................................................................159
7.3.2: How to Calculate System Current Load..........................................................................................160
7.4: Calculating the Battery Size ......................................................................................................................162
7.4.1: NFPA Battery Requirements...........................................................................................................162
7.4.2: Selecting and Locating Batteries.....................................................................................................162
Appendix A: Software Zones...............................................................................................163
A.1: Correlations...............................................................................................................................................163
Appendix B: Default Programming.....................................................................................169
Appendix C: NFPA Standard-Specific Requirements .......................................................170
C.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................174
C.2: MBT-1 Municipal Box Trip - Silenceable ................................................................................................175
Appendix D: FACP with Keltron..........................................................................................176
Appendix E: Wire Requirements.........................................................................................177
E.1: NAC Wiring..............................................................................................................................................179
Appendix F: HVAC Control..................................................................................................180
F.1: Control Module Operation.........................................................................................................................180
F.1.1: HVAC SHUTDN .............................................................. .................................. ............................180
F.2: Monitor Module Operation........................................................................................................................180
F.2.1: HVAC RESTART.................................... ................................................................. ......................180
F.2.2: HVAC OVRRIDE...................................... ................................................................. ....................181
Appendix G: Ademco Contact ID Format Event Code Descriptions................................182
G.1: Transmission Format Between DACT and Receiver................................................................................ 182
G.2: Ademco Contact ID Typical Printout........................................................................................................182
Appendix H: Central Station Points....................................................................................187
Appendix I: Canadian Application.......................................................................................189
Index.......................................................................................................................................192
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309 ECC-50/100 Manual Document #LS10001-000FL-E ECC-FFT Manual Document #LS10031-000FL-E ACS Series Annunciators Document #51480 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 LDM Series Lamp Driver Modules Document #50055 LCD-80F Remote Fire Annunciator Document #50055 ACM-8RF Relay Control Module Document #50362 IPDACT Communicator/Transmitter Document #53109 ANN-80 Product Installation Document Document #52749 ANN-(R)LED Product Installation Doc. Document #50055 ANN-I/O Product Installation Document Document #151416 ANN-RLY Product Installation Document Document #50055 ANN-S/PG Product Installation Document Document #151417 ANN-LC Product Installation Document Document #LS1015 8-000FL-E ACC-25/50(ZS/T) Manual Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
10 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
+ 24V -
NON-RST
POWER
+ 24V -
RST
POWER
REMOTE PWR
SUPPLY SYNC
+ -
1B+ 3B+ 3B- 1B-
2B+ 4B+ 4B- 2B-
NO NC C NO NC C NC NO C
TB5
TB3
TB7
TB2
TB1 TB4
TB9
TB8
TB6
TB1
0
J10
321
JP4
123
JP6
JP7
J14
HOT
NEUT
E
A
R
T
H
TB11
J11
TRANSFORMER 1
TRANSFORMER 2
JP5
- +
BATTERY
J9
J8
J3
PH1
5
PRI. PHONE LINESEC. PHONE
LINE
PH16J12
MINI DIN
KEYBOARD CONN.
SW1J5J6
JP3
JP2
LCD DISPLAY
KEYPAD
I/F
J1
J4
4XTM
Xmt Rcv Dtr Gnd
A B
In+ In- Out+ Out-
+ -
A B
B+ A+ B- A- A B
Slc Slc Slc Slc Shield
++
+
+
++
++
++
+
+
J7
D
B
9
F
5 4 3 2 1
9 8 7 6
R
C
V
TB8
G
N
D
DTR
X
M
T
TB8
5 4 3 2 1
25 24 23 22 21 20 19 18 17 16 15 14
9 8 7 613 12 11 10
RCVDTRGNDXM
T
C
A
U
T
I
O
N
!
H
I
G
H
V
O
L
T
A
G
E
Supervisory* Alarm*
Trouble
2 Programmable Relays &
Fixed Trouble Relay
Non-supervised relay contacts
Contact rating:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in
normal condition (AC power
with no alarm, trouble, or
supervisory activity)
AC Fail Safe Trouble relay
switches to the NO position
during trouble conditions and
under loss of all power.
(*Factory default relay
programming)
Convert NAC circuits
from Style Y (Class B)
to Style Z (Class A)
with the ZNAC-92
converter module.
Cut this jumper
to enable
Supervisory
relay when
4XTMF is
installed
Auxiliary
Trouble
Input
Cut this jumper to supervise
the 4XTMF when installed
(see J5 & J6)
Flash Memory Load Enable
Switch: UP is normal
position for switch, DOWN
position allows to factory
software upgrades
USB Port J12 for local
programming using a
personal computer and
PS-Toolsutilty
To disable ground fault
detection, remove
jumper/shunt from JP7.
Important! Removing
Ground Fault Disable
Jumper JP7 voids
UL/NFPA Style/Class
identifications for
circuits. Remove
jumper JP7 only with
the approval of the AHJ
(Authority Having
Jurisdiction).
Configure TB1, Terminals
1&2 (JP4) and 3&4 (JP6) as
Resettable or Nonresettable
Power.
Resettable Power- jumper
pins 2&3.
Nonresettable Power-
jumper pins 1&2.
Jumpers are installed at the
factory as shown.
Transformer 2 Connector
Transformer 1 Connector
AC Power
(Supervised,
Nonpower-Limited)
120 VAC, 60 Hx, 2.0 amps
220/240 VAC, 50 Hz, 1.2 amps
Cut this jumper to disable
the FACP battery charger
when using an external
battery charger
Battery
24 VDC, supervised,
nonpower-limited,
18 AH maximum
Off-board piezo
sounder- J8
(Canadian
Applications
only)
PS2 Keyboard Interface
DACT Phone LIne Jacks
(Nonpower-Limited)
OR
TERM
(EIA-485)
to LCD-80F
OR
Secondary
ANN-BUS
to Annunciators
(power-limited,
supervised)
Primary
ACS/ANN-BUS
to Annunciators
(power-limited,
supervised)
SLC Loop
(supervised)
TB8 (option to DB-25)
NAC #1 NAC #3 NAC #2NAC #4
Notification Applicance Circuits
NAC #1, #2, #3, & #4 Style Y (Class B)
(Supervised, Power-Limited) (Speci al
application) 2.5 amps max. per circuit
Special Application DC Power Outputs (24 VDC)
Nonsupervised, Power-Limited circuits
Supervise with a power supervision relay EOLR-1
Nonresettable Power suitable for powering
annunciators; Resettable Power suitable for
powering smoke detectors.
EIA-232
to printer or
personal computer
(nonsupervised)
For EDP-listed
equipment or personal
computer with FACP
Upload/Download
Utility.
50 foot maximum
within same room.
ELRs, 4.7K, 1/2W
(for Style Y wiring)
OR
Resettable or Nonresettable Power
Jumper selectable by JP6, 24 VDC filtered,
power-limited (1.0 amp maximum).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP4, 24 VDC filtered,
power-limited (1.0 amp maximum).
Supervision required.
Remote Synchronization Output
Supervised, Power-Limited circuits
24 VDC filtered (0.35 amp maximum),
Requires a 4.7 Kohm End-of-Line Resistor
{
{
{
2
1
+ -
2
1
4
3
Basic System Connections
9200udlsbrd.wmf
+ - + -
Red
White
Green
Black
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 11
Peripheral Devices and Their Documents:
Addressable Devices and SLC Wiring Doc. #51309
CHG-120F Charger
Doc. #50888
ANN-BUS - TB9/TB8
SLC Loop - TB10
Battery Connector - J9
9200udLSannperi.wmf
ANN-80(C)
LCD Text
Annunciator/Indicator
Doc. #52749
ANN-I/O
LED Driver
Doc. #151416
ANN-S/PG
Printer Driver
Doc. #151417
CHG-75 Charger
Doc. # 51315
ANN-(R)LED
LED Display
Doc. #53032
ANN-RLY
10 Form-C
Relay Card
Doc. #53033
4XTMF
Reverse Polarity Module
J5 & J6
ANN Audio Control for ECC-50/100 Doc. #LS10001-000FL-E or ACC-25/50(ZS/T) Doc. #51889
IPDACT
Internet
Communicator
Doc. #53109
PH15 & PH16 Telephone Connections
ANN-LC
Lite-Connect module
Doc. #LS10158-000FL-E
12 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Section 1: Product Description

The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technolog y. The power supply and all electronics are con­tained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software and remote power expan­sion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone net­work. Local programming and interrogation is also possible using the PS-Tools and the USB port (J12) on the FACP. Any personal computer with WINDOWS modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Service Term i­nal. This allows download of the entire program or upload of the entire program, history file, w alk­test data, current status and system voltages.
NOTE: MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS/C (120 VAC versions) and the MS-9200UDLSE (240 VAC version) FACPs.
®
XP or greater, and compatible
Inventory
When MS-9200UDLS shipment is received, check that all parts have been included in shipment. The MS-9200UDLS shipment consists of one of each of the following:
main circuit board with displaybackbox with doorplastic bag containing screws, cables, key, etc.manual

1.1 Features and Options

Automated activation of the ECC-50/100 Emergency Command Center
ECC-FFT Firefighter Telephone option
LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire (refer to “Wire Requirements” on page 177)
Built-in DACT (Digital Alarm Communicator/Transmitter)
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
198 addressable device capacity (99 detectors and 99 control/relay/monitor modu les)
99 software zones
Four (4) Style Y (Class B) NACs (Notification Appliance Circuits) with the option to convert to four (4) Style Z (Class A) circuits - special application power
3.0 amps total 24 VDC output circuit current, expandable to 6.0 amps with optional transformer
T wo programmable relay outputs and one fixed trouble relay
Synchronization output for remote power supply applications (special application)
Built-in Programmer
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 13
Product Description Features and Options
Telephone Line Active LEDs
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
Programmable Make/Break Ratio
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensitivity test capability (NFPA 72 compliant)Automatic device type-code verificationPoint trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pr e-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two­stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, ACS annunciators or ANN-80 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program and data
Compatible with Fire-Lite’s newer series devices in LiteSpeed and CLIP mode (refer to SLC Wiring Manual for a list of compatible addressable devices)
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional ZNAC-92 Class A converter module for NACs
ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators are used):
ANN-80 Remote AnnunciatorANN-80C Remote Indicator (Canadian Applications)ANN-I/O LED DriverANN-S/PG Printer ModuleANN-RLY Form-C Relay ModuleANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for
Canada and emergency signaling)
14 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Specifications Product Description
ANN-RLED Annunciator Module annunciates alarms only
ANN-LC Lite-Connect Module
Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are used):
ACS Series-LED Zone AnnunciatorsLDM Graphic Annunciator SeriesLCD-80F Liquid Crystal Display point annunciatorLCD-80FC Remote Fire Indicator (Canadian applications)ACM-8RF Relay Module

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB11
MS-9200UDLS: 120 VAC, 60 Hz, 2.0 amps MS-9200UDLSE: 220/240 VAC, 50 Hz, 1.2 amps Wire size: minimum 14 AWG (2.00 mm
Battery (Sealed Lead Acid Only) - J9
2
) with 600 V insulation
Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.4 amps Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. The BB-26 Battery Box holds two 26 Amp Hour batteries and the CHG-75. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box). Minimum Battery Size: 7 Amp Hour Note: Jumper JP5, on the FACP main circuit board, must be cut to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum Maximum length - refer to “Wire Requirements” on page 17 7) Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Four (4) Style Y (Class B) NAC circuits, which can be converted to four (4) Style Z (Class A) circuits with optional ZNAC-92 converter module Special Application full-wave rectified power Power-limited circuitry NAC wiring requirements refer to “NAC Wiring” on page 179 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 17) End-of-Line Resistor: 4.7 k, ½ watt (P/N 71252 UL listed) required for each circuit Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.7 on page 33 for information on power-limited relay circuit wiring
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 15
Product Description Specifications
Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB1, Terminals 1 (+) & 2 (-)
Factory-set as nonresettable, suitable for powering annunciators Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 20mV
RMS
Total DC current available is up to 1.0 amp (see Figure 1.1 on page 17) Power-limited circuit
Resettable or Nonresettable Special Application Power (24 VDC Nominal) - TB1, Terminals 3 (+) & 4 (-)
Factory-set as resettable, suitable for powering four-wire smoke detectors Jumper selectable (JP6) for conversion to nonresettable power output Maximum ripple voltage: 20 mV
RMS
Total DC current available is up to 1.0 amp (see Figure 1.1) Power-limited circuit Refer to the Device Compatibility Document for listed compatible devices
Remote Sync Output - TB2
Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 350 mA End-of-Line Resistor: 4.7K Output linked to NAC 1 control Supervised and power-limited circuit
EIA-485 (TERM) or EIA-232 Serial or ANN-BUS2 - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (In +), 2 (In -), 3 (Out +), 4 (Out -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (DTR) 4 (Ground) EIA-485 ANN Ancillary indicator connections: Terminal 3 (“A” data), 4 (“B” data) Annunciators require non-resettable power
EIA-485 ACS or ANN-BUS1 - TB9
ACS/ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) Annunciators require non-resettable power
16 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Controls and Indicators Product Description
Figure 1.1 Current Availability
powerdist9200ud2.wmf
Refer to the battery calculations section for additional information.
6.0 amps with optional second XRM-24B(E) transformer.
3.0 amps max. with only standard transformer installed.
Standby
2.0 amps max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable or Nonresettable Power
NAC #1
NAC #3
NAC #2
NAC #4
1.0 amp max
per circuit
1.0 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
6.0 amps max
per panel
0.35 amp max
per circuit
Remote
Synchronization
Output
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 012102
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP.

1.3 Controls and Indicators

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 17
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Product Description Digital Alarm Communicator/Transmitter
Figure 1.2 Membrane/Display Panel
9600kypd.wmf
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi­tions.

1.4 Digital Alarm Communicator/Transmitter

T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the fol­lowing functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA DCS 8SIA DCS 20
®
, programmable to rotary

1.5 Components

Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main cir­cuit board.
18 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Components Product Description
Standard XRM-24B(E)
Optional XRM-24B(E)
xrm-24s.wmf
Battery Cable P/N 75287
9200batt.wmf
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Transformer Assembly
One 100VA transformer is provided standard with the panel (3.0 amps maximum for output circuits). An optional 100 VA transformer XRM-24B (XRM-24BE for the MS­9200UDLSE) is available to provide maximum system and accessory power (6.0 amps total). Note that the XRM-24B and XRM-24BE are only suitable for use with MS­9200UDLS(E) with a main circuit board assembly number 9200UDLS-PCX
Rev Y, where “X” and “Y” can be any
letter or number. This circuit board can also be identified by using the software revision of #9200UDV4.0 (meaning version 4.0) or later.
Batteries
The MS-9200UDLS cabinet provides space for two bat­teries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG­75 or CHG-120F and a UL listed battery box such as the BB-26 or BB-55F. Batteries must be ordered separately.

1.5.1 Intelligent Addressable Detectors: Newer Series

Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wir­ing and operation). This allows the control panel to continually process the information to deter­mine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maxi­mum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indi­cates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors.

1.5.2 Intelligent Addressable Modules: Newer Series

The newer series of Control Modules and Monitor Modules provide an interface between the con­trol panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel.
These devices (i.e., MMF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wir-
ing Manual for a list of compatible addressable modules. Refer to the Device Compatibility Docu­ment for a list of approved conventional notification and initiating devices.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 19
Product Description Optional Modules

1.5.3 300 Series Intelligent Addressable Devices

Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS­9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices.

1.5.4 Addressable Device Accessories

End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module documenta­tion for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke detectors and notification appliances.
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit.

1.6 Optional Modules

The MS-9200UDLS main circuit board includes option module connectors for the following modules:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervision of the module.
ZNAC-92 Class A Converter Module
The ZNAC-92 is an optional Class A conversion module which mounts to connector J14 on the upper left side of the MS-9200UDLS circuit board. This module allows the MS-9200UDLS to sup­port four (4) Style Z (Class A) Notification Appliance Circuits.

1.7 Accessories

1.7.1 PS-Tools Programming Utility

The PS-Tools Programming Utility can be used to locally or remotely program the FACP from most IBM compatible computers (PC), running Windows files can also be created and stored on the PC for future download to the contro l panel. The PK-CD Kit includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J12 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
®
XP (or newer). The FACP program
20 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Accessories Product Description
dp9200udls.cdr
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Site Upload/Download” on page 156). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.

1.7.2 DP-9692 Dress Panel

An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Cana­dian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox.

1.7.3 Trim Ring

An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring adds 1.5” of wall coverage around the backbox, concealing hardware and providing a finished appearance for a semi-flush mounted panel.

1.7.4 Multi-Module Mounting Bracket

An addressable Multi-Module can be installed inside the FACP backbox using the MULTIMOD-BRKT module mounting bracket. Refer to the MULTIMOD-BRKT Installation Document P/N 53547 for additional information.

1.7.5 Battery Box

BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH bat teries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 21
Product Description Accessories
!

1.7.6 Battery Charger

CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.

1.7.7 IPDACT Internet Protocol DACT

The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to allow FACP status communication to a Central Station via the internet. No telephone lines are required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT con­verts the standard DACT phone communication to a protocol that can be transmitted and received via the internet. It also checks connectivity between the FACP and Central Station. The IPDACT can be mounted inside the FACP cabinet, while still maintaining space for two 18 amp hour batter­ies, using the IPBRKT moutning bracket. Refer to the IPDACT Product Installation Document P/N 53109 for additional information.

1.7.8 ECC-50/100

The ECC-50/100 is a single channel, 50 watt, 25 V may be used for fire applications, mass notification applications, or both. Automatic activation of the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via the ACS/ANN BUS serial communications link from the MS-9200UDLS FACP. Not for use in Canadian applications.
RMS

1.7.9 ECC-FFT

An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The ECC-FFT’s keypad provides indications of phone activation and corresponding trouble conditions. Not for use in Canadian applications.

1.7.10 ANN-BUS Annunciators/Modules

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING.
Guidelines
The legacy ACS annunciators may not be used on connector TB9 if new ANN-BUS annunciators are being used on the primary ANN-BUS (connector TB9) due to incompatible serial communication protocols.
, emergency voice evacuation panel that
22 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Accessories Product Description
A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA-
485) terminals on TB9. A secondary communication circuit for these devices is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the following:
– ANN-80 LCD Annunciator – ANN-80C LCD Indicator (Canadian Applications) – ANN-S/PG Serial/Parallel Printer Interface Module – ANN-I/O LED Driver Module – ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs) – ANN-RLED Annunciator Module (red alarm LEDs only) – ANN-RLY Relay Module (can be mounted in the supplied FACP chassis) – ANN-LC Lite-Connect Module (secondary ANN-BUS only)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in the system.
The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB8) simultaneously.
The panel is capable of operating the ACS-BUS (connector TB9) and the secondary ANN-BUS (connector TB8) simultaneously.
The secondary ANN-BUS (on connector TB8) does not support legacy ACS annunciators.
The secondary ANN-BUS can be configured to support either terminal mode annunciators, printer/PC devices, or ANN-BUS devices.
Only one audio system (ECC-50/100 or ACC-25/50) may be connected to the ANN-BUS.
ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervi­sory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely perform­ing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employ­ing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled through the FACP software. Refer to “ANN-80 Options” on page 117 for a description of this fea­ture and programming information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two min­utes without any buttons being pressed on the annunciator, a trouble indication will be annunciated. The ANN-80C (for Canadian applications) does not provide FACP control for Acknowledge, Reset, Silence, or Drill.
ANN-S/PG Serial/Parallel Interface Module
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting.
ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 23
Product Description Accessories
!
ANN-LED Annunciator Module
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general sys­tem faults and input zones/points when used with a compatible FACP. The ANN-LED module pro­vides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full sy stem coverage.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat­ible FACP.
ANN-LC Lite-Connect Module
The ANN-LC module provides a multi-FACP system where a single communicator and phone line for Alarm, Supervisory, and Trouble reporting to a central station are shared using fiber-optic cables. Each FACP requires its own ANN-LC. The FACP/ANN-LC pair are referred to as a node on the fiber circuit. Each node requires a unique node address. The node communicates with other nodes via fiber-optic media from one ANN-LC to the next.

1.7.11 Legacy ACS Series LED Zone Type Annunciators

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used on the primary ANN-BUS connector (TB9) due to incompatible serial communication protocols. Refer to “Guidelines” on page 22 for rules governing the use of various annunciator types.
The legacy ACS Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the MS-9200UDLS.
*
ACM-16ATF
Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder.
AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs
and 16 yellow trouble LEDs
*
ACM-32AF
Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence.
AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs * In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power, or an activated output.
LCD-80F/LCD-80FC Remote Fire Annunciator/Indicator
The LCD-80F/LCD-80FC annunciator/Indicator is an 80-character backlit LCD remote fire annun­ciator/indicator that is capable of displaying English language text. Communications between the control panel and the annunciator is accomplished over a serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F/LCD-80FC annunciators/indicators may be con­nected to the EIA-485 circuit. The annunciators/indicators may be powered from the host FACP or a remote UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to the LCD-80F and LCD-80FC manuals.
24 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Getting Started Product Description
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator.
Legacy ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. The ACM-8RF mounts in the lower right corner of the FACP backbox using the ACM-8RF-BRKT mounting bracket, also allowing space for batteries.

1.8 Getting Started

The following is a brief summary of the minimal steps involved in bringing an MS-9200UDLS on­line:
Install Backbox and Main Circuit Board (refer to “Mounting the Backbox” on page 28)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to “Autoprogram” on page 66)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to “Point Program” on page 67). Use the right and left arrow keys to navigate between devices.

1.9 Telephone Requirements and Warnings

1.9.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 25
Product Description Telephone Requirements and Warnings

1.9.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL11B9200UDLS Ringer Equivalence: 1.1B
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, com­puter modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to “Digital Communicator” on page 38 for an illustration of the proper installation of this equipment.
Important! The DACT must not
be used to dial a phone number that is call-forwarded .

1.9.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
26 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Telephone Requirements and Warnings Product Description

1.9.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements docu­ment(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des­ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equip­ment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician. “The Ringer Equivalence Number
of the maximum number of terminals allowed to be connected to a telephone interface. the termi­nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emis­sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
(REN) assigned to each terminal device provides an indication
10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: Ringer Equivalence Number (REN): 1.3B Load Number: 2
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 27

Section 2: Installation

!
Figure 2.1 MS-9200UDLS Chassis Removal
Backbox
Main Circuit Board on chassis
mounting studs
9200udcchassisinbox.wmf
grounding stud
mounting slots
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting the Backbox

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
1. Mark and predrill hole in the wall for the center top keyhole mounting bol t us ing the dimen­sions illustrated in Figure 2.3 on page 30.
2. Install center top fastener in the wall with the screw head protruding.
3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower mounting holes. Note: Outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
5. Install remaining fasteners and tighten.
28 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Mounting Optional Transformer/Remounting Chassis Installation
Figure 2.2 MS-9200UDLS Main Board/Chassis Installation
Standard XRM-24B(E) Transformer
Mounting Slot
Mounting Studs
Optional XRM-24B(E) Transformer Installation
Remove screw and spacer from chassis.
Slide top flange of XRM-24B(E) into slot at top left of chassis. Slide bottom flange of XRM-24B(E) onto transformer mounting stud.
Secure with spacer and screw.
Optional XRM-24B(E) Transformer mounting location

2.2 Mounting Optional Transformer/Remounting Chassis

One XRM-24B(E) transformer is supplied standard with the control panel. An optional second XRM-24B(E) transformer can be ordered and installed to provide maximum system power. Note that the XRM-24B and XRM-24BE are only suitable for use with MS-9200UDLS(E) with a main circuit board assembly number 9200UDLS-PCX number. Install the trans fo rm e rs in the locations indicated in the following illustration.
1. The standard transformer is premounted to the chassis. If the optional second transformer has been ordered, mount it to the chassis as illustrated below. The chassis does not need to be removed to install the optional transformer.
2. When the location is dry and free of construction dust, install the chassis/transformer/circuit board assembly.
3. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting hole tabs over the studs with nuts located in the upper portion of the backbox.
4. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down.
5. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a 3/8” nut driver or socket.
6. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the chassis and secure with the supplied screws.
7. Connect the Standard XRM-24B(E) Transformer plug to Transformer 1 Connector J10 on the FACP main circuit board
8. Connect the Optional XRM-24B(E) Transformer plug to Transformer 2 Connector J11 on the FACP main circuit board.
9. Complete the installation as detailed in the following sections.
Rev Y, where “X” and “Y” can be any letter or
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 29
Installation Mounting Optional Transformer/Remounting Chassis
Figure 2.3 MS-9200UDLS Cabinet Mounting
9050udencl.cdr
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
Hinge Slot for optional Dress Panel
Hinge Slot for optional Dress Panel
Semi-flush mounting hole
Mounting slots for optional Trim Ring
30 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Loading...
+ 170 hidden pages