Fire-Lite MS-9050UDC User Manual

Addressable Fire Alarm Control Panel
MS-9050UD
MS-9050UDC
MS-9050UDE
Document 52413 4/14/2014 Rev:
P/N 52413:G ECN 14-226
G
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warn ing of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association S tandard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http: // www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States governme nt) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment l
is
ted for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dus t, dirt, or hig h air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthl y or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only . Adequate written reco rds of all inspecti ons should be kept.
Limit-D-1-2013
2 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™, Lite-Connect™, and SWIFT™ are trademarks; and Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
MS-9050 Series Manual — P/N 52413:G 4/14/2014 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 MS-9050 Series Manual — P/N 52413:G 4/14/2014

Table of Contents

Section 1: Product Description .............................................................................................12
1.1: Features and Options ...................................................................................................................................12
1.2: Specifications...............................................................................................................................................14
1.3: Controls and Indicators................................................................................................................................15
1.4: Circuits.........................................................................................................................................................16
1.5: Digital Alarm Communicator/Transmitter ..................................................................................................17
1.6: Components.................................................................................................................................................17
1.6.1: Intelligent Addressable Detectors: Newer Series ..............................................................................18
1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................18
1.6.3: 300 Series Intelligent Addressable Devices ......................................................................................18
1.6.4: Device Accessories............................................................................................................................18
1.7: Optional Modules and Accessories .............................................................................................................19
1.8: Getting Started.............................................................................................................................................21
1.9: Telephone Requirements and Warnings.......................................................................................................21
1.9.1: Telephone Circuitry...........................................................................................................................21
1.9.2: Digital Communicator.......................................................................................................................21
1.9.3: Telephone Company Rights and Warnings.......................................................................................22
1.9.4: For Canadian Applications................................................................................................................22
Section 2: Installation.............................................................................................................24
2.1: Mounting the Backbox ................................................................................................................................24
2.2: Mounting the Chassis/Transformer/Main Circuit Board.............................................................................25
2.3: Power...........................................................................................................................................................28
2.3.1: AC Power and Earth Ground Connection.........................................................................................28
2.3.2: Battery Power....................................................................................................................................28
2.4: Relays ..........................................................................................................................................................29
2.5: Notification Appliance Circuits...................................................................................................................30
2.5.1: Configuring NACs.............................................................................................................................30
2.6: UL Power-limited Wiring Requirements.....................................................................................................31
2.7: Digital Communicator.................................................................................................................................32
2.8: Optional Modules/Accessories Installation.................................................................................................33
2.8.1: 4XTMF Transmitter Module Installation..........................................................................................33
2.8.2: ANN-SEC Option Card.....................................................................................................................35
2.9: ANN-BUS Devices......................................................................................................................................36
Guidelines.............................................................................................................................................36
2.9.1: ANN-BUS Wiring.............................................................................................................................36
Calculating Wiring Distance for ANN-BUS Modules.........................................................................37
Wiring Configuration ................................................ .................................. .........................................39
Powering ANN-BUS Devices from Auxiliary Power Supply .............................................................39
2.9.2: ANN-BUS Device Addressing ..........................................................................................................40
2.9.3: ANN-80(C) Remote Fire Annunciator/Indicator ..............................................................................40
Specifications .......................................................................................................................................40
Installation............................................................................................................................................41
Opening/Closing Annunciator..............................................................................................................41
Mounting ..............................................................................................................................................41
Wiring ANN-80 to FACP................................................................................. ....................................42
2.9.4: ANN-S/PG Serial/Parallel Interface Module ....................................................................................43
Specifications .......................................................................................................................................44
PRN-6F Printer Installation..................................................................................................................44
2.9.5: ANN-I/O LED Driver Module..........................................................................................................45
ANN-I/O Board Layout........................................................................................................................46
Specifications .......................................................................................................................................46
ANN-I/O Connection to FACP............................................................................................................47
ANN-I/O Module LED Wiring............................................................................................................47
MS-9050 Series Manual — P/N 52413:G 4/14/2014 5
Table of Contents
2.9.6: ANN-LED Annunciator Module.......................................................................................................49
Specifications........................................................................................................................................49
Mounting and Installation.....................................................................................................................49
ANN-LED Board Layout and Connection to FACP............................................................................50
2.9.7: ANN-RLY Relay Module..................................................................................................................50
Specifications........................................................................................................................................50
Mounting and Installation.....................................................................................................................51
ANN-RLY Board Layout and Connection to FACP............................................................................52
2.9.8: ANN-LC Lite-Connect Module .........................................................................................................52
Specifications........................................................................................................................................52
Installation ............................................................................................................................................52
Mounting ..............................................................................................................................................52
Wiring the ANN-LC to the MS-9050UD.............................................................................................53
Section 3: Programming........................................................................................................55
3.1: Programming Data Entry.............................................................................................................................55
3.2: User Programming.......................................................................................................................................56
3.3: Initial Power-up............................................................................................................................................57
3.4: Programming Screens Description ..............................................................................................................57
3.5: Programming and Passwords.......................................................................................................................57
3.6: Master Programming Level .........................................................................................................................58
3.6.1: Autoprogram......................................................................................................................................58
3.6.2: Point Program....................................................................................................................................59
Detector Programming..........................................................................................................................59
Module Programming...........................................................................................................................66
3.6.3: Zone Setup.........................................................................................................................................78
Enable...................................................................................................................................................78
Disable..................................................................................................................................................78
Zone 17, 18, and 19 ..............................................................................................................................78
Zones Installed......................................................................................................................................79
Zones Enabled ......................................................................................................................................79
Zones Disabled .....................................................................................................................................79
Zone Type.............................................................................................................................................79
Zones Available....................................................................................................................................80
3.6.4: Loop Setup.........................................................................................................................................81
Style......................................................................................................................................................81
Loop Protocol .......................................................................................................................................81
3.6.5: System Setup .....................................................................................................................................81
Trouble Reminder.................................................................................................................................82
Banner...................................................................................................................................................82
Time-Date.............................................................................................................................................83
Timers...................................................................................................................................................84
NAC (Notification Appliance Circuit).................................................................................................86
Relays ...................................................................................................................................................90
Canadian Option...................................................................................................................................91
Waterflow Silenceable..........................................................................................................................91
Lite-Connect.........................................................................................................................................91
3.6.6: Verify Loop .......................................................................................................................................93
3.6.7: History ...............................................................................................................................................93
View Events.......................................................................................... ................................................94
Erase History ........................................................... .................................. ...........................................94
3.6.8: Walktest.............................................................................................................................................94
3.6.9: Option Modules ................................................................................................................................95
ANN-BUS.............................................................................................................................................96
Onboard DACT ............................................................................................ ......................................106
3.6.10: Password Change.................................. .................................. ....................................
3.6.11: Clear
Program
................................................................. ................................. ..............................118
...................118
6 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Table of Contents
3.6.12: Program Check.................................... .................................. .................................. ......................119
3.7: Maintenance Programming Level..............................................................................................................119
3.7.1: Disable Point ...................................................................................................................................120
3.7.2: History.............................................................................................................................................120
3.7.3: Program Check................................................................................................................................121
3.7.4: Walktest...........................................................................................................................................122
3.7.5: System .............................................................................................................................................123
3.7.6: Zone Setup.......................................................................................................................................124
Section 4: Operating Instructions.......................................................................................126
4.1: Panel Control Buttons................................................................................................................................126
4.1.1: Acknowledge/Step...........................................................................................................................126
4.1.2: Alarm Silence..................................................................................................................................126
4.1.3: Drill/Hold 2 Sec...............................................................................................................................126
4.1.4: Reset ................................................................................................................................................126
4.2: Status Indicators and LEDs........................................................................................................................126
4.3: Normal Operation......................................................................................................................................127
4.4: Trouble Operation......................................................................................................................................128
4.5: Alarm Operation........................................................................................................................................129
4.6: Supervisory Operation...............................................................................................................................130
4.7: Process Monitor Operation........................................................................................................................130
4.8: Hazard/Tornado Condition Operation .......................................................................................................131
4.9: Medical Alert Condition Operation...........................................................................................................131
4.10: NAC Operation..................................................................................... ...................................................132
4.11: Programmed Zone Operation...................................................................................................................132
4.12: Disable/Enable Operation................................................................................... .....................................132
4.13: Waterflow Circuits Operation..................................................................................................................132
4.14: Detector Functions................................... .................................. .................................. ............................132
4.15: Time Functions: Real-Time Clock...........................................................................................................133
4.16: Synchronized NAC Operation.................................................................................................................133
4.17: Coded Operation................................................................................... ...................................................133
4.18: Presignal ........................................................... .................................. .....................................................134
4.19: Positive Alarm Sequence.........................................................................................................................134
4.20: Special System Timers............................................................... .................................. ............................135
4.20.1: Silence Inhibit Timer................................................................................... ..................................135
4.20.2: Autosilence Timer ................................................ .................................. .......................................135
4.20.3: Trouble Reminder........................................................................................ ..................................135
4.20.4: Waterflow Retard Timer.............................................................................. ..................................135
4.20.5: Alarm Verification (None or One Minute)....................................................................................135
4.21: Walktest ...................................................... .................................. ...........................................................136
4.22: Read Status ....................................................... .................................. .....................................................136
4.22.1: System Point.................................................................................. ................................................137
4.22.2: Zones .......................................................................................... ...................................................138
4.22.3: Power..................................................................................... ........................................................138
4.22.4: Trouble Reminder........................................................................................ ..................................139
4.22.5: Timers....................................... ................................. .................................. ..................................139
4.22.6: NAC........................................................ .................................. .....................................................139
4.22.7: Relays .............................................................................. .................................. . ...........................139
4.22.8: Program Check.................................... .................................. .................................. ......................140
4.22.9: History................................ .................................. .................................. .......................................140
4.22.10: ANN-BUS ...............................................................................................................
ne...................................................................................................................................141
4.22.11: Phone L
i
4.22.12: Central Station.............................................................................................................................141
4.22.13: Service Terminal..........................................................................................................................141
4.22.14: Print .............................................................................................................................................142
4.22.15: Time-Date....................................................................................................................................143
....................140
MS-9050 Series Manual — P/N 52413:G 4/14/2014 7
Table of Contents
Section 5: Central Station Communications......................................................................145
5.1: Transmittal Priorities..................................................................................................................................148
Section 6: Local/Remote Site Upload/Download...............................................................150
6.1: Remote Download .....................................................................................................................................150
6.2: Transferring a Program..............................................................................................................................151
6.3: Security Features........................................................................................................................................151
Section 7: Power Supply Calculations ...............................................................................153
7.1: Overview....................................................................................................................................................153
7.2: Calculating the AC Branch Circuit............................................................................................................153
7.3: Calculating the System Current Draw .......................................................................................................154
7.3.1: Overview..........................................................................................................................................154
7.3.2: How to Use Table 7.3 to Calculate System Current Draw..............................................................154
7.4: Calculating the Battery Size.......................................................................................................................156
7.4.1: NFPA Battery Requirements............................. .................................. ............................................156
7.4.2: Selecting and Locating Batteries .....................................................................................................156
Appendix A: Software Zones...............................................................................................157
A.1: Correlations...............................................................................................................................................157
Appendix B: Default Programming.....................................................................................162
Appendix C: NFPA Standard-Specific Requirements.......................................................164
C.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................168
C.2: MBT-1 Municipal Box Trip - Silenceable.................................................................................................169
Appendix D: FACP with Keltron..........................................................................................170
Appendix E: Wire Requirements.........................................................................................171
E.1: NAC Wiring...............................................................................................................................................172
Appendix F: HVAC Control..................................................................................................173
F.1: Control Module Operation .........................................................................................................................173
F.1.1: HVAC SHUTDN............................................. .................................. ..............................................173
F.2: Monitor Module Operation ........................................................................................................................173
F.2.1: HVAC RESTART.............................................................. .................................. ...........................173
F.2.2: HVAC OVRRIDE...................................................... .................................. ...................................174
Appendix G: Ademco Contact ID Format Event Code Descriptions ...............................175
G.1: Transmission Format Between DACT and Receiver................................................................................175
G.2: Ademco Contact ID Typical Printout........................................................................................................175
Appendix H: Canadian Application.....................................................................................181
H.1: ANN-LED Annunciator Installation for Canadian Applications..............................................................181
H.2: AC Power Connections for Canadian Applications..................................................................................184
Index ......................................................................................................................................185
8 MS-9050 Series Manual — P/N 52413:G 4/14/2014
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and System
CAN/ULC - S524-01 Standard for Installation of Fire Alarm System CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 ANN-80(C) Product Installation Doc. Document #52749 ANN-(R)LED Product Installation Doc. Document #53032 ANN-I/O Product Installation Doc. Document #151416 ANN-RLY Product Installation Doc. Document #53033 ANN-S/PG Product Installation Doc. Document #151417 ANN-LC Product Installation Doc. Document #LS10158-000FL-E
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9050 Series Manual — P/N 52413:G 4/14/2014 9
J
1
3
C
A
U
T
I
O
N
!
H
I
G
H
V
O
L
T
A
G
E
9050udlayout.wmf
For specific UL wiring
information, refer to
“UL Power-limited
Wiring Requirements”
on page 31.
E
IA-232 to
perso
nal computer
personal co
mputer with
FACP Upload/Download
utility, 50 foot maximum
within sa
me room,
(Nonsupervised, Power
-
limited, Class 2 Circuit)
A
N
N
-
B
U
S
(
E
I
A
-
4
8
5
)
f
o
r
A
n
n
u
n
c
i
a
t
o
r
C
o
n
n
e
c
t
i
o
n
(
P
o
w
e
r
-
l
i
m
i
t
e
d
,
C
l
a
s
s
2
,
S
u
p
e
r
v
i
s
e
d
)
A
la
r
m
*
N
O
N
C
C
T
r
o
u
b
le
N
O
N
C
C
S
u
p
e
r
v
is
o
r
y
*
N
O
N
C
C
2 Programmable Relays
& 1
Fixed Trouble Relay
Nonsupervised Contact Ratings:
2.0 am
ps @ 30 VDC (resistive)
0.5 amp @ 30 VAC
(resistive)
Contac
ts shown below in normal
condition (AC power
with no alarm,
trouble, or supervisory activity).
A Fail Safe Trouble
relay switches to the
NO posi
tion during
trouble conditions andunder loss of all power.
(*Factory default rel
ay programming)
SLC Loop
Refer t
o the SLC Wiring
Manual for detail
ed
information on wiring
addre
ssable devices for
Style 4, 6, and
7.
(Power-limited, Class 2,
Sup
ervised Circuit)
Notification Ap
pliance Circuits
Special Applicati
on Power
NAC #1 show
n Style Y (Class B) (Power-limited, Cl
ass 2, Supervised)
NAC #2 shown Style Z (C
lass A) (Power-limited, Class 2, Supe
rvised)
2.5 amps max. per circuit. Total av
ailable current is 2.5 amps.
N
A
C
#
1
N
A
C
#
2
E
L
R
-
4
.
7
,
½
W
Transformer
Connector
Nonpower-limited
Supervised
Battery
24 VDC, nonpower-limited,
supervised, 18 Amp Hour max.
PS2 Keyboard Interface
DACT Phone Line Jacks
(nonpower-limited, supervised)
K
I
S
S
O
F
F
P
R
I
M
A
R
Y
A
C
T
I
V
E
S
E
C
O
N
D
A
R
Y
A
C
T
I
V
E
PHONE LINE
SECONDARY PRIMARY
PHONE LINE
F
L
A
S
H
M
E
M
O
R
Y
L
O
A
D
E
N
A
B
L
E
S
W
I
T
C
H
R
e
m
o
v
e
t
h
i
s
j
u
m
p
e
r
t
o
e
n
a
b
l
e
s
u
p
e
r
v
i
s
o
r
y
r
e
l
a
y
w
h
e
n
4
X
T
M
F
i
s
i
n
s
t
a
l
l
e
d
.
L
C
D
D
I
S
P
L
A
Y
4
X
T
M
F
C
u
t
J
P
2
8
t
o
S
u
p
e
r
v
i
s
e
4
X
T
M
F
T
o
d
i
s
a
b
l
e
g
r
o
u
n
d
f
a
u
l
t
d
e
t
e
c
t
i
o
n
,
r
e
m
o
v
e
j
u
m
p
e
r
/
s
h
u
n
t
f
r
o
m
J
P
1
A
N
N
-
S
E
C
O
p
t
i
o
n
C
a
r
d
c
o
n
n
e
c
t
o
r
C
h
a
r
g
e
r
D
i
s
a
b
l
e
J
u
m
p
e
r
(
c
u
t
t
o
d
i
s
a
b
l
e
F
A
C
P
o
n
b
o
a
r
d
b
a
t
t
e
r
y
c
h
a
r
g
e
r
)
BASIC SYSTEM CONNECTIONS
w
h
i
t
e
r
e
d
g
r
e
e
n
b
l
a
c
k
10 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Peripheral Devices
-
+
-
+
JP1
JP3
SW1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR DELAY
TENS
ONES
CUT FOR 240VAC
GND FLT DISABLE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
1
5
1
5
A- B- A+ B+
NC NO C
043
92615
78121315141011043
92615
7
8
12
13
15
14
10
11
TB1
TBL
J1
J2
7 6 5 1
POWER LIMITED
Sw1
P1 P2
P3
P4
110
11 20
21 30 31
40
1 2 3 4 5
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
Alarm
Silenced
Earth Fault
ZONE 1
ALM
TBL
SUP
1
ZONE 6
ALM
TBL
SUP
6
NAC 1
Fault
Battery
Fault
ZONE 2
ALM
TBL
SUP
2
ZONE 7
ALM
TBL
SUP
7
NAC2
Fault
Charger
Fault
ZONE 3
ALM
TBL
SUP
3
ZONE 8
ALM
TBL
SUP
8
FIRE ALARM ANNUNCIATOR
NAC 4
Fault
ZONE 5
ALM
TBL
SUP5ALM
TBL
SUP
NAC 3
Fault
Disabled
ZONE 4
ALM
TBL
SUP
4
ZONE 9
ALM
TBL
SUP
9
T11 T10 T9 T8 T7 T6
T1 T2 T3 T4 T5
FROM AP PHONE
PSTN TO AP OUT NC OUT NO
I
NPUT TAMPER GND +12/2
4
V
P4CN2P5P6P7P8P9P10P11P1
2
CHG-120F Charger
Doc. #50888
CHG-75 Charger
Doc. #51315
Addressable Devices and SLC Wiring
Doc. #51309
SLC Loop
Battery Connector
ANN-BUS
ANN-80(C)
LCD Text
Annunciator/
Indicator
Doc. #52749
ANN-I/O
LED Driver
Doc. #151416
ANN-S/PG
Printer Driver
Doc. #151417
9050UDper2i.wmf
ANN-RLY
10 Form-C
Relay Card
Doc. #53033
ANN-(R)LED
LED Display
Doc. #53032
4XTMF Municipal Box Transmitter
RS-232
Local PC
IPDACT Internet Protocol Communicator Doc. #53109
PH1 & PH2
Telephone
ANN-LC
Lite-Connect Module
Doc. #LS10158-000FL-E
MS-9050 Series Manual — P/N 52413:G 4/14/2014 11

Section 1: Product Description

The MS-9050UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applica­tions. Availa ble accessories include local and remote upload/download software, remote annuncia­tors and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone net­work. Any personal computer with Windows of 2400 baud or faster and Upload/Download software kit PK-CD, containing PS-Tools, may serve as a Service T erminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
The MS-9050UDC is a ULC-approved Canadian version of the FACP which offers the same fea­tures as the MS-9050UD, but is supplied standard with a dress panel and one built-in ANN-LED annunciator. Refer to“Canadian Option” on page 91 for a full descriptio n.
The MS-9050UDE offers the same features as the MS-9050UD but allows connection to 220/240 VAC power.
®
XP or newer, and compatible modem with a speed
NOTE: Unless otherwise specified, the terms FACP and MS-9050UD are used in this manual to refer to all versions of the FACPs.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been included in the shipment. The MS-9050UD shipment should consis t of one of each of the fo llow­ing:
main circuit board with displaychassis with transformerbackbox with doorplastic bag containing screws, cables, key, etc.manual

1.1 Features and Options

Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
50 addressable device capacity (any combination of addressable detectors and addressable control/relay/monitor modules totaling 50)
20 software zones
Two onboard NACs (Notification Appliance Circuits) which can be configured as Style Y (Class B) or Style Z (Class A) circuits
2.5 amps total output power
Two programmable relays and one fixed trouble relay
Built-in Programmer
Telephone Line Active LEDs
12 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Features and Options Product Description
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
EIA-232 PC interface for local upload/download
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 500 event capacity
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensitivity test capability (NFPA 72 compliant)Automatic device type-code verificationPoint trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) per addressab le detecto r and Pre-si gnal per poin t (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two­stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
SLC operates up to 10,000 ft. (3,000 m) with twisted, unshielded fire wire
Compatible with Fire-Lite addressable devices (refer to the SLC Wiring Manual)
Compatible with legacy Fire-Lite 300 Series addressable devices (refer to the SLC Wiring Manual)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional ANN-I/O LED Driver module
Optional ANN-S/PG printer interface module
Optional ANN-80 remote LCD annunciator
Optional ANN-80C remote LCD indicator (for Canadian applications)
Optional ANN-LED Annunciator Module annunciates alarm, trouble and supervisory
Optional ANN-RLED Annunciator Module annunciates alarms only
Optional ANN-RLY Form-C Relay Module
Optional ANN-LC Lite-Connect Module
Optional Dress Panel DP-51050 (a modified dress panel with the ANN-LED is included standard with the MS-9050UDC)
Optional PRN-6F Serial Printer (requires ANN-S/PG module)
Optional PK-CD (contains PS-Tools) for local/remote upload/download of programming and data
MS-9050 Series Manual — P/N 52413:G 4/14/2014 13
Product Description Specifications

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections. For wire specifications, refer to “Wire Requirements” on page 171.
AC Power - Transformer Connection
MS-9050UD: 120 VAC, 60 Hz, 3.0 amps MS-9050UDE: 240 VAC, 50 Hz, 1.5 amps Wire size: minimum 14 AWG (2.00 mm Nonpower-limited, supervised
Battery (Lead Acid Only) - J1
Maximum Charging Circuit: Normal Flat Charge - 27.4 VDC @ 4.3 amps peak inrush current tapering to a maximum of 2.8 amps of continuous charging current. Maximum Battery Charger Capacity: 18 Amp Hour, (FACP cabinet holds maximum of two 18 Amp Hour batteries) For greater than 18 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Bat­tery Charger and BB-26 or BB-55F Battery Box, respectively. Jumper JP30 on the FACP main circuit board, must be removed to disable the FACP battery char­ger when using an external battery charger . Minimum Battery: 7 Amp Hour Nonpower-limited, supervised
2
) with 600 V insulation
SLC Communication Loop - TB2
24 VDC nominal, 27.6 VDC maximum Maximum length is 10,000 ft. (3,000 m) total twisted, unshielded fire wire Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Loop manual for wiring information
Notification Appliance Circuits/Special Application (Auxiliary) Power - TB1
Terminal Block provides connections for up to two NACs, Style Y (Class B) or Style Z (Class A) Special Application power Power-limited, supervised circuitry For wire specifications, refer to “NAC Wiring” on page 172. Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps for NACs, 1.0 amp for auxiliary power and door holders End-of-Line Resistor: 4.7 K, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to the Fire-Lite Device Compatibility Document for listed compatible devices
A circuit programmed for door holders or auxiliary power does not support notification appli­ances.
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays, nonpower-limited, nonsupervised Refer to Figure 2.5 on page 29 for information on power-limited relay circuit wiring
EIA-232 - TB3
EIA-232 PC applications connections: Terminal 5 (Receive), 6 (Transmit), 7 (DTR), 8 (Ground) Power-limited, supervised
14 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Controls and Indicators Product Description
TB3
TB1 TB1
TB1
55 66
77 88
NAC #1
NAC #2
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
2.5 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
ANN-SEC
Option Card
0.5 amp max
per circuit
Figure 1.1 Current Availability
powerdis9050.wmf
Refer to the battery calculations section for additional information.
Nonresettable/
Resettable Power
#1
#2
1.0 amp max
per circuit
1.0 amp max
per circuit
OR
SYSTEM ALL NORMAL
10:00A 092105
Special Application Primary ANN-BUS Power - TB3
Nominal Operating Voltage: 24 VDC Maximum Current (Terminals 1 & 2): 500 mA Power-limited, supervised
Special Application Secondary ANN-BUS Power - ANN-SEC - TB1
Nominal Operating Voltage: 24 VDC Maximum Current (Terminals 1 & 2): 500 mA Power-limited, supervised
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP.

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
MS-9050 Series Manual — P/N 52413:G 4/14/2014 15
Product Description Circuits
Figure 1.2 Membrane/Display Panel
9050udkypd.cdr
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Alarm Silenced signals (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silenced
Drill (Manual Evacuate)
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi­tions.

1.4 Circuits

SLC Communication Loop
One SLC loop is provided on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Charger - 24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits) - Two NACs configurable for Style Y (Class B) or Style Z (Class A), are provided with various programmable features.
16 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Digital Alarm Communicator/Transmitter Product Description
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following oper­ations:
fire alarm
silenceable alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
•AC loss

1.5 Digital Alarm Communicator/Transmitter

T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the fol­lowing functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types
4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID

1.6 Components

Main Circuit Board
®
, programmable to rotary
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main cir­cuit board. The circuit board is delivered mounted to a chassis in the MS-9050UD backbox (refer to circuit board illustration on page 10).
MS-9050 Series Manual — P/N 52413:G 4/14/2014 17
Product Description Components
MS_9050UD.wmf
Battery Cable P/N 75203
9200batt.cdr
Cabinet
The MS-9050UD backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel, which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Batteries
The MS-9050UD cabinet provides space for two bat­teries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120F and a UL listed battery box such as the BB-55F. Batteries must be ordered sepa­rately.

1.6.1 Intelligent Addressable Detectors: Newer Series

Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on addressable devices, device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector . Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel. Refer to the Fire-Lite Device Compatibility Document for a list of approved conventional detectors.

1.6.2 Intelligent Addressable Modules: Newer Series

The newer series of Control Modules and Monitor Modules provide an interface between the con­trol panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. A blinking LED on a monitor module indicates com­munication between the module and the control panel. These devices can also be used when installed on older systems. Refer to the SLC Wiring Manual for information on addressable
devices. Refer to the Fire-Lite Device Compatibility Document for a list of approved conventional notification and initiating devices.

1.6.3 300 Series Intelligent Addressable Devices

Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9050UD FACP. Refer to the SLC Wiring Manual for device information.

1.6.4 Device Accessories

End-of-Line Resistor Assembly
Refer to the SLC Wiring Manual for device information. The 47 K End-of-Line Resistor assem­bly (P/N: R-47K) is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 K End-of-Line Resistor assembly is used to supervise the MMF-302 module circuit. The End-of-Line resistors are included with each module.
Power Supervision Relay
18 MS-9050 Series Manual — P/N 52413:G 4/14/2014
The UL-listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke detectors and notification appliances.
Optional Modules and Accessories Product Description
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit.

1.7 Optional Modules and Accessories

The MS-9050UD main circuit board includes option module connectors for the following module:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J8 and J9 which are located near the top center of the main circuit board. When the 4XTMF module is installed, Jumper JP28, on the main circuit board, must be cut to allow supervision of the module.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display and provides remote RESET, SILENCE, ACKNOWLEDGE, and DRILL.
ANN-80C LCD Indicator (Canadian applications)
The ANN-80C is a remote LCD indicator which mimics the information displayed on the FACP LCD display but does not allow remote control of the FACP.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. An ANN-LED module is installed in the dress panel for the Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for Cana­dian applications requiring remote annunciation.
ANN-LC Lite-Connect Module
The ANN-LC provides a multi-FACP system where a single communicator and phone line for Alarm, Trouble, and Supervisory reporting to a central station is shared using fiber-optic cables.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. The Canadian version is supplied standard with a modified dress panel.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cab­inet.
MS-9050 Series Manual — P/N 52413:G 4/14/2014 19
Product Description Optional Modules and Accessories
Battery Boxes
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box, which is red and is provided with knockouts, was designed specifically to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 26 AH bat teries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program an MS-9050UD directly from most IBM compatible personal computers (PC), running Windows
®
XP (or newer). MS-9050UD program files can also be created and stored on the PC and then downloaded to the control panel. The part number PK-CD Kit includes the Windows-based Programming Utility soft­ware on CD-ROM with online help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately, is required for local connection of the PC to the RS-232 (PC/Printer) termi­nals at TB3 of the MS-9050UD main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Download” on page 150). Remote interrogation of panel pro ­gramming, history logs, detector status, etc., is possible without enabling the remote download option.
Battery Chargers
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP bat­tery charger must be disabled, by removing jumper JP30, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the F ACP. The FACP battery charger must be disabled, by removing jumper JP30, when using the CHG-120F. The bat­teries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batter­ies greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for addi-
tional information.
IPDACT, IPDACT-2, IPDACT-2UD - IP Communicator
The IPDACT, IPDACT-2, and IPDACT-2UD are a compact, Internet Protocol Communicators designed to allow FACP status communication to a Central Station via the internet. No telephone lines are required when using any IPDACT. Using Contact ID protocol from the FACP, any IPDACT converts the standard DACT phone communication to a protocol that can be transmitted and received via the internet. It also checks connectivity between the FACP and Central Station.
Refer to the IPDACT Series Product Installation Document P/N 53109 for additional information.
20 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Getting Started Product Description

1.8 Getting Started

The following is a brief summary of the minimal steps involved in bringing an MS-9050UD on­line:
Install Backbox and Main Circuit Board (refer to “Mounting the Backbox” on page 24).
Address and Install Intelligent Devices (refer to the SLC Wiring Manual).
Enter Autoprogramming (refer to“Autoprogram” on page 58).
Resolve Programming Conflicts.
Go to Point Program to Enter Specific Data (refer to“Point Program” on page 59). Use the
right and left arrow keys to navigate between devices.

1.9 Telephone Requirements and Warnings

1.9.1 Telephone Circuitry

AC Ringer Equivalence Number (REN) = 03B DC Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.9.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-9050UD FCC Registration Number: US:1W6AL03B9050UD AC Ringer Equivalence: 0.3B DC Ringer Equivalence: 0.0B
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identi­fier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the tele­phone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, com­puter modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these
MS-9050 Series Manual — P/N 52413:G 4/14/2014 21
Product Description Telephone Requirements and Warnings
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to“Digital Communicator” on page 32 for an illustration of the proper installation of this equipment.
Important! The DACT must not
be used to dial a phone number that is call-forwarded.

1.9.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be pro vid ed except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equip­ment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.

1.9.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements docu­ment(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des­ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equip­ment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.
CAUTION
22 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Telephone Requirements and Warnings Product Description
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termi­nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emis­sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-9050UD Ringer Equivalence Number (REN): 0.3B
MS-9050 Series Manual — P/N 52413:G 4/14/2014 23

Section 2: Installation

Figure 2.1 Chassis Removal
Backbox
FACP Main Circuit Board on Chassis
mounting studs
9050udbdUnmn.cdr
mounting slots
mounting tabs
mounting tab holes
Ground Stud
backbox stud mounting hole
backbox stud mounting hole
backbox stud mounting holes
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting the Backbox

The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.3 on page 26.
Install center top fastener in the wall with the screw head protruding.Place backbox over the top screw, level, and secure.Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
Install remaining fasteners and tighten.
24 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Mounting the Chassis/Transformer/Main Circuit Board Installation
Figure 2.2 Main Circuit Board/Chassis Installation
Backbox
FACP Main Circuit Board on Chassis
mounting studs
9050udbdmn.cdr
mounting slots
mounting tabs
mounting tab holes
Ground Stud
Transformer is mounted to the back of the chassis in the lower left corner.

2.2 Mounting the Chassis/Transformer/Main Circuit Board

One transformer is supplied standard with the control panel. Install the transformer and chassis in the location indicated in the following illustration.
1. When the location is dry and free of construction dust, install the chassis/transformer/circuit
board assembly.
2. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the
backbox, then position the two mounting hole tabs over the studs with nuts located in the upper portion of the backbox.
3. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by
pressing the chassis down.
4. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and
to ensure proper grounding, use a 3/8” nut driver or socket.
5. If the main circuit board is not already attached to the chassis, install it by positioning the ten
mounting holes over the studs on the chassis and secure with the supplied screws.
6. Ensure the transformer plug is connected to Connector J2 on the FACP main circuit board
7. Complete the installation as detailed in the following sections.
MS-9050 Series Manual — P/N 52413:G 4/14/2014 25
Installation Mounting the Chassis/Transformer/Main Circuit Board
Figure 2.3 FACP Cabinet Mounting
9050udencl.wmf
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
Hinge Slot for optional Dress Panel
Hinge Slot for optional Dress Panel
Mounting slots for optional Trim Ring
Semi-Flush mounting hole
26 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Mounting the Chassis/Transformer/Main Circuit Board Installation
Figure 2.4 FACP Cabinet Dimensions
9050udcab2.wmf
Left Side
Right Side
Bottom
Door
Door Backbox
Backbox
Depth =
Depth
Top
MS-9050 Series Manual — P/N 52413:G 4/14/2014 27
Installation Power
!
Interconnect Cable
!

2.3 Power

WARNING: RISK OF DAMAGE AND ELECTRICAL SHOCK
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.

2.3.1 AC Power and Earth Ground Connection

Primary power required for the MS-9050UD/C FACP is 120 VAC, 60 Hz, 3.0 amps or 240 VAC, 50 Hz, 1.5 amps for the MS-9050UDE. Overcurrent protection for this circuit must comply with Arti­cle 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 mm larger wire with 600 volt insulation rating. Make certain that the AC main circuit breaker is off before wiring any connections between the mains and the control panel. Connect wiring from the AC mains to the Transformer on the FACP, being careful to observe proper connections.
Connect the AC ground wire to the Ground Stud located in the left side of the backbox. Refer to Figure 2.2 on page 25 and the illustration below for location of the stud. If installing an optional ANN-LC, ensure that the ground for the AC mains cable is installed first, closest to the backbox. This connection is vital for maintaining the control panel’s immunity to unwanted transients gener­ated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before
installing the battery interconnect cable (refer to the following section).
2
) or
For AC connections to the MS-9050UDC, refer to“AC Power Connections for Canadian Applica­tions” on page 184.

2.3.2 Battery Power

Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is com­pletely installed. Observe polarity when connecting the batter­ies. Connect the battery cable to J1 on the main circuit board. Refer to“Power Supply Calculations” on page 153, for calcula­tion of the correct battery rating.
WARNING: BATTERIES CONTAIN SULFURIC ACID
BATTERIES CONTAIN SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
28 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Relays Installation
AC Connection to
Transformer leads:
HOT
NEUTRAL
Battery Connection
to J1 on FACP
Ground Stud
9050udpowr.cdr
Figure 2.5 Relay Terminals
Relay contacts shown with power applied to panel
and no active troubles, alarms or supervisories
Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail­safe relay which will transfer on any trouble or total power failure.
9050udrely.wmf

2.4 Relays

The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be nonpower-limited. Refer to UL Power-limited wiring require­ments.
MS-9050 Series Manual — P/N 52413:G 4/14/2014 29
Installation Notification Appliance Circuits
TB1
B+ B- B-B+
A+ A-
A+
A-
NAC1
NAC2
-
+
B +
B
-
1
4
A+A
-
23
+
+
B +
B
-
A+A
-
+
+
+
5
6
7
8
Figure 2.6 NAC Wiring
Style Y (Class B) Notification Appliance Circuits, supervised and power-limited -
4.7 K, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized HornsPolarized Horns
Polarized Strobes
Notification Appliance Circuit polarity shown in alarm state
Dummy Load all unused circuits with a 4.7 K, ½ watt resistor across the B+ & B­terminals or wire jumpers between A+ & B+ and A- & B-.
9050udnac.wmf
Polarized Strobes
terminal number
NAC 1
NAC 2
Style Z (Class A) Notification Appliance Circuits, supervised and power-limited
Polarized Bells

2.5 Notification Appliance Circuits

The control panel provides two NACs (Notification Appliance Circuits) Style Y (Class B) or Style Z (Class A). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 2.5 amps (refer to “Calculating the System Current Draw” on page 154). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Fire-Lite Device Compatibility Document for a listing of compatible notification appli­ances. The NACs, which are located on the main circuit board, may be expanded via the Fire-Lite FCPS Series field charger/power supplies.
NACs can also be configured for auxiliary power. If set for auxiliary power (door holder, resettable power, non-resettable power) do not connect notification appliances. Refer to Section 1.2, “Speci­fications” for power capability.
The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the FACP main circuit board.

2.5.1 Configuring NACs

The Notification Appliance Circuits are configured for Style Y (Class B) or Style Z (Class A) by properly wiring the NAC devices to TB1 on the main circuit board as illustrated below.
30 MS-9050 Series Manual — P/N 52413:G 4/14/2014
Loading...
+ 162 hidden pages