Fire-Lite FC-LPS Installation Instruction

The optional FC-LPS Local Playback Speaker Module can be used to
monitor the recorded digital message without transmitting the
message over the system speakers. The FC-LPS is necessary to take
advantage of the Playback feature. The speaker module plugs into
P2 of the main circuit board and is temporarily installed for testing.
Voice Evacuation Control Panel
FC-LPS Local Playback
Speaker Module
Product Installation Drawing
Document 50617 Rev B 5/27/97 ECN 97-215
It is not necessary to remove power when installing the FC-LPS Local Playback Speaker Module.
Temporary Installation of the FC-LPS Local Playback Speaker Module:
1. Remove the main circuit board mounting screw located to the right of power terminal block TB3. Refer to the illustration
below.
2. Install the supplied metal standoff in the mounting hole just vacated in step 1, and screw standoff into place.
3. Position the FC-LPS mounting bracket hole over the standoff and secure with the screw removed in step 1.
4. Plug the FC-LPS Local Playback Speaker Module's polarized connector into connector P2 on the main circuit board. P2 is
located on the bottom right of the main circuit board near the Control/Indicator panel.
permanent connection.
3
Install FC-LPS Speaker Module on metal standoff
FC-LPS
1
Remove the mounting screw from
left center of main circuit board
Main Circuit Board
Voice Evacuation Control Panel
Remove mounting screw from main circuit board and install metal standoff
1,2
2
Install one metal standoff by
screwing into place
Main Circuit Board
Plug Speaker Module Cable into connector P2
3
Install Speaker Module and
secure with screw
Main Circuit Board
Speaker
Module
Loading...