Fire-Lite ECC-50-100E User Manual

Emergency Command Center
ECC-50/100
ECC-50/100E
Instruction Manual
Document LS10001-000FL-E 4/10/2013 Rev:
P/N LS10001-000FL-E:A ECN 13-186
A
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warn ing of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the National Fire Protection Asso ciation Standard 72 (NFPA 72), manufa cturer's recommendati ons, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http://www.systemsensor.com/ appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or pro tection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a vari ety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have be
en prope
rly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dus t, dirt, or hig h air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthl y or as required by National and/or local fire codes and should be per­formed by authorized professional life saftety system installers only . Adequate written reco rds of all inspecti ons should be kept.
Limit-D-1-2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2013 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013

Table of Contents

Section 1: Product Description .............................................................................................12
1.1: Product Features ..........................................................................................................................................12
1.2: Input/Output Circuit Specifications .............................................................................................................13
1.2.1: ECC-50/100 Main Control Board .....................................................................................................13
1.2.2: Display Board....................................................................................................................................18
1.2.3: ECC-CE6 Circuit Expander Module .................................................................................................19
1.3: Controls and Indicators................................................................................................................................20
1.3.1: Push-Button Controls ........................................................................................................................20
1.3.2: LED Indicators (visible with door closed) ........................................................................................21
1.3.3: LED Indicators (visible with door and dress panel open) .................................................................21
1.4: Components .................................................................................................................................................21
1.5: Optional Equipment.....................................................................................................................................23
Section 2: Installation.............................................................................................................25
2.1: Mounting Options........................................................................................................................................25
2.2: Backbox Installation ....................................................................................................................................25
Removing the Dress Panel....................................................................................................................25
Removing the Chassis Assembly .........................................................................................................26
Mounting the Backbox .........................................................................................................................27
2.3: Operating Power ..........................................................................................................................................30
2.3.1: AC Power and Earth Ground Connection .........................................................................................30
2.3.2: Secondary Power Source (Batteries) .................................................................................................31
2.4: Auxiliary DC Power Output Connections ...................................................................................................32
2.5: Input/Initiating Circuits ...............................................................................................................................32
2.5.1: CMD Inputs .......................................................................................................................................32
2.5.2: External Audio Input .........................................................................................................................33
2.5.3: NAC Follower Input..........................................................................................................................34
2.5.4: Night Ring .........................................................................................................................................34
2.6: Output Circuits.............................................................................................................................................35
2.6.1: Relays ................................................................................................................................................35
MNS Active Relay - TB1 .....................................................................................................................35
Trouble Relay - TB2.............................................................................................................................35
AC Power Loss Relay - TB3................................................................................................................35
2.6.2: Speaker Circuits.................................................................................................................................36
2.6.3: Notification Appliance Circuit ..........................................................................................................37
2.6.4: Speaker Volume Control ...................................................................................................................38
2.6.5: FACP Data Bus .................................................................................................................................39
ACS Mode Wiring................................................................................................................................40
2.7: ECC-LOC Local Operator Console.............................................................................................................41
2.8: ECC-RPU Remote Page Unit ......................................................................................................................43
2.9: ECC-RM Remote Microphone ....................................................................................................................45
2.10: ECC-50/125DA Distributed Audio Amplifier...........................................................................................46
2.11: Shielding for External Device Wiring .......................................................................................................46
2.12: UL Power-limited Wiring Requirements...................................................................................................48
2.13: Installation of Option Modules..................................................................................................................49
2.13.1: ECC-CE6 Circuit Expander Module ...............................................................................................49
2.13.2: Audio Amplifier Module (ECC-50W-25/70V) ...............................................................................49
Installation ............................................................................................................................................49
Power and Control Cables....................................................................................................................51
Configuration........................................................................................................................................51
...
ECC-50/100 Configurations with ECC-50W-25/70V.......
2.13.3: 70.7 V
2.14: Addressing External Data Bus Devices.....................................................................................................54
Transformer (ECC-XRM-70V) ....................................................................................54
RMS
................................................................52
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 5
Table of Contents
Section 3: Programming........................................................................................................58
3.1: Main Menu - User Programming.................................................................................................................59
3.1.1: Password Options ..............................................................................................................................59
3.1.2: General/NAC Options .......................................................................................................................60
General Options....................................................................................................................................60
NAC Options ........................................................................................................................................61
Console Control....................................................................................................................................62
3.1.3: Address Assignment ..........................................................................................................................62
Remote Microphone / Operator Console Address Assignments ..........................................................62
Speaker Circuit Address Assignment ...................................................................................................63
3.1.4: Message Buttons................................................................................................................................64
Message Buttons...................................................................................................................................64
CMD Input Style ..................................................................................................................................64
3.1.5: Date / Time ........................................................................................................................................65
3.1.6: Send to Panel .....................................................................................................................................65
3.2: Main Menu - Utilities...................................................................................................................................65
3.2.1: Message Recording............................................................................................................................66
3.2.2: USB File Options...............................................................................................................................66
3.3: Main Menu - Informational .........................................................................................................................67
3.3.1: Informational .....................................................................................................................................68
Speaker Circuit Buttons........................................................................................................................68
Version Information..............................................................................................................................69
History Information ..............................................................................................................................69
3.4: Recording Custom Messages.......................................................................................................................70
3.4.1: Message Record Mode ......................................................................................................................70
3.4.2: External Audio Input .........................................................................................................................70
Recording with External Audio - Example ..........................................................................................71
3.4.3: Microphone........................................................................................................................................72
Recording with Microphone - Example ...............................................................................................72
3.4.4: Erasing a User Message.....................................................................................................................73
3.4.5: Audio Programming Utility Software ...............................................................................................73
Writing a Message to the Panel ............................................................................................................74
Reading a Message from the Panel.......................................................................................................74
Moving a Message to a Different Slot..................................................................................................74
3.5: Programmed Activation by FACP ...............................................................................................................75
3.5.1: MS-9600(UD)LS and MS-9200UDLS..............................................................................................75
FACP Programming .............................................................................................................................76
FACP Message Assignment - Speaker Specific...................................................................................76
FACP Message Assignment - Zone Specific........................................................................................77
FACP Programming Menus .........................................................................................................
........78
Section 4: Operating Instructions.........................................................................................82
4.1: Main Control Panel Keypad Labels.............................................................................................................82
4.2: ECC-50/100 Switch Functions ....................................................................................................................82
4.3: LED Indicators.............................................................................................................................................83
4.4: Operation......................................................................................................................................................85
4.4.1: Paging from the Microphone .............................................................................................................85
4.4.2: Manual Message Control...................................................................................................................85
4.4.3: Fire Alarm Response, System Configured for Fire Only ..................................................................86
4.4.4: Fire Alarm Restoral, System Configured for Fire Only ....................................................................86
4.4.5: Manual Activation .............................................................................................................................86
4.4.6: Manual Activation Restoral...............................................................................................................87
4.4.7: Alarm/Alert Response, System Configured for Mass Notification Only ..........................................87
4.4.8: Alarm/Alert Restoral, System Configured for Mass Notification Only ............................................87
4.4.9: Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with Fire Priority ..88
4.4.10: Alarm/Alert Restoral, System Configured for Combo Fire/Mass Notification with Fire Priority..88
4.4.11: Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with Mass Notifica-
6 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Table of Contents
tion Priority..................................................................................................................................................88
4.4.12: Alarm/Alert Restoral, System Configured for Combo Fire/Mass Notification with Mass Notification
Priority .........................................................................................................................................................89
4.4.13: Trouble Condition Response ...........................................................................................................89
4.4.14: Trouble Condition Restoral .............................................................................................................90
4.4.15: External Audio Input Operation ......................................................................................................91
Section 5: Getting Started ......................................................................................................92
5.1: System Requiring up to 50 Watts of Audio Power......................................................................................92
5.2: System Requiring Up to 100 Watts of Audio Power...................................................................................92
5.3: System Requiring Greater Than 100 Watts of Audio Power.......................................................................92
Section 6: Power Supply Calculations..................................................................................93
6.1: Overview......................................................................................................................................................93
6.2: Calculating the AC Branch Circuit..............................................................................................................93
6.3: Calculating the System Current Draw .........................................................................................................93
6.3.1: Overview ...........................................................................................................................................93
6.3.2: How to use Table 6.2 to calculate system current draws...................................................................94
6.4: Calculating the Battery Size ........................................................................................................................95
6.4.1: NFPA Battery Requirements.............................................................................................................95
6.4.2: Selecting and Locating Batteries .......................................................................................................95
Appendix A: Digital Voice Messages....................................................................................96
Appendix B: Wiring Requirements........................................................................................98
Index.......................................................................................................................................103
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 7
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Underwriters Laboratories
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards: NFPA 72 National Fire Alarm Code Note: Audible signal appliances used in public mode applications, are required to have
minimum sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA at the minimum hearing distance from the audible appliance. To ensure that the appliance is clearly heard, the audible appliance sound level must be at least 15 dBA above the average ambient sound level or 5 dBA above the maximum sound level with a duration of at least 60 seconds, depending on which level is greater, with the sound level being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1711 Amplifiers for Fire Protective Signaling Systems UL 2572 Communication and Control Units for Mass Notification Systems
Other:
NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents:
Fire•Lite Device Compatibility Document Document #15384 ECC-50/125DA Manual Document #LS10027-000FL-E ECC-FFT Manual Document #LS10031-000FL-E ECC-LOC Installation Document Document #LS10028-000FL-E ECC-RPU Installation Document Document #LS10030-000FL-E ECC-RM Installation Document Document #LS10029-000FL-E ECC-CE6 Installation Document Document #LS10033-000FL-E ECC-CE4 Installation Document Document #LS10002-000FL-E ECC-50W-25/70V Installation Document Document #LS10035-000FL-E ECC-XRM-70V Installation Document Document #LS10032-000FL-E MS-9200UDLS Series Manual Document #52750 MS-9600(UD)LS Technical Manual Document #52646
8 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
FIRE SYSTEM ACTIVE
SYSTEM CONTROL
ALL CALL
1 2 3 4 5 6 7 8
9 10 11 12
13
18 19 20 21 22 23 24
16 17
14 15
LITFI®AL
by Honeywell
FIRE SYSTEM ACTIVE
SYSTEM CONTROL
ALL CALL
1 2 3 4 5 6 7 8 9 10 11 12
13
18 19 20 21 22 23 24
16 17
14 15
LITFI®AL
by Honeywell
Speaker Circuits
TB20 & TB21
internal options
ECC-50W-25/70V
optional amplifier
ECC-CE6
circuit expander
ECC-50DA
50W remote amplifier
ECC-RPU
remote page unit
ECC-RM
remote microphone
remote
consoles
distributed
audio
ECC-125DA
125W remote amplifier
ECC-LOC
local operator console
CHG-120F
charger
CHG-75
charger
external battery
charger - J7
TB4 TB12 TB22
Figure 1.1 Peripheral Devices
eccperi.wmf
NAC Circuit
TB19
visual only
ECC-FFT
firefighter telephone
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 9
+
+
+
J12
TB15
J9
RTZM
DISPLAY
C
A
U
T
I
O
N
!
H
I
G
H
V
O
L
T
A
G
E
ecc50layo.wmf
AC Power
(Supervised,
Nonpower-Limited)
120 VAC, 60 Hz, 3.5 ampsor230 VAC, 50 Hz, 2.0 amps
Special Application DC Power Output (24 VDC)
Supervised, Power-Limited (Class 2) circuit
Supervise with a power supervision relay EOLR-1
Nonresettable Power suitable for powering control
modules and power supervision relays.
NAC Follower Input
Supervised, Power-
Limited (Class 2)
circuits
24 VDC filtered (10
mA maximum),
Requires a 4.7 Kohm
End-of-Line Resistor
AC Loss, MNS Active, &
Fixed Trouble Relay
Non-supervised relay contacts
Contact rating:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in
normal condition (AC power
with no alarm, trouble, or
supervisory activity)
AC Fail Safe Trouble relay
switches to the NO position
during trouble conditions and
under loss of all power.
Flash Memory Load Enable
Switch: UP is normal
position for switch, DOWN
position allows for factory
software upgrades
Ethernet Port J2/
for local programming
using a personal
computer and web-
based utility
Battery
24 VDC, supervised,
Non-power-limited,
26 AH maximum
Notification
Appliance Circuit
Style Y (Class B) or
Style Z (Class A)
Supervised, Power-
Limited (Class 2)
(Special
application) 2.0
amps max.
Regulated power:
200mA max.
ELR, 4.7K, 1/2W
(for Style Y wiring)
Optional 50W Amplifier
connectors
Optional 70V
Transformer connector
Optional CE6 Circuit
Expander Connector
Display Board
connector
Speaker Volume Control Override
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
(Special application) 0.25 amps max.
4.7K ELR, 1/2W required for Style Y
(Class B) wiring
Primary/Secondary Speaker Circuits
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
50W integrated output power. Use of
secondary circuit requires optional
ECC-50W-25/70V amplifier
15K ELR, 1W required for Style Y
(Class B) wiring
CMD1 & CMD2 Command Input Circuits
Trigger by contact closure or NAC reverse
polarity (ELR required)
alarm polarity shown.
CMD3 - CMD8 Command Input Circuits
Trigger by contact closure (ELR required)
alarm polarity shown.
(inputs only)
Night Ring Input
Trigger by contact closure
External Operator Interface Power
Supervised, Power-Limited
(Class 2) circuit
24 VDC Nonresettable Power for
external operator interface components.
External Data Bus
Supervised, Power-Limited
(Class 2) data connections to
external operator interface
components
FACP Data Bus
Supervised, Power-Limited
circuit dedicated as FACP
serial bus connection
External Audio Riser
Style Y (Class B) or Style Z (Class A)
Supervised, Power-Limited (Class 2)
audio connection to external operator
interface components
Speaker
Voltage
Switch
To disable
ground fault
detection,
remove
jumper/shunt
from JS2.
Basic System Connections - Main Control Board (Section 1.2.1)
Cut jumper to use
external charger
Backup
amplifier
test switch
USB-A Port J1/
for local program
download
10 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
TB5- External Audio Input/
Audio Riser
SW1- Dipswitch for
BUS addressing
ON
JP5 ­isolation/ground when powered by source other than main control board
J2- Connection to
main control board
P2- Microphone
connector
J1- USB connector -
connection to a PC for
downloading messages
Refer to Section 3.4.5
on page 73.
Basic System Connections - Display Board (Section 1.2.2)
disp.wmf
SW2- Distributed Audio Switch set to UP position if any ECC-50/125DAs are installed in the system. Default is the DOWN position.
TB1-
Aux Trouble Input 1
TB2- Aux Trouble Input 2
TB3- Data Bus/Power Input
TB4- Data Bus/Power Output
JP2 - External Data
Bus termination
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 11

Section 1: Product Description

The Fire•Lite Emergency Command Center ECC-50/100 is a single channel, 50 watt, 25 V emergency voice evacuation panel that may be used for fire applications, mass notification applica­tions, or both. The ECC-50/100 comes standard with one speaker circuit. The panel provides the ability to record fourteen field programmable messages (up to 60 seconds each) with an integral microphone or from an external audio source. An integral power supply with battery charger sup­plies operational power. A 50 watt audio amplifier is built into each panel. An optional second 50 watt amplifier (ECC-50W-25/70V) is also available for backup purposes or to provide an additional 50 watts. The backup amplifier is available in either 25 volts or 70 volts depending on which appli­cation is necessary.
Automatic activation of the ECC-50/100 by an FACP is possible via eight Command Input Circuits (CMD) or via the ACS/ANN Bus serial communications link from the MS-9600(UD)LS and MS-9200UDLS FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP Notification Appliance Circuit reverse polarity or by closure of a supervised normally open contact and six Command Input Circuits activate on contact closure. CMD 1 and CMD 2 provide terminals for NAC input and output to allow installation of the audio panel anywhere along the NAC circuit being used to activate it.
If the message generator fails, the system automatically reverts to a backup tone generator.
Power is fed independently down the other. Full output power of 50 watts per amplifier is generated while in a low battery con­dition. Power is not diminished when the optional 70 V is amplified utilizing modern integrated circuits as opposed to transformer technology. This pro­vides for very low signal distortion for crystal clear audio.
to each amplifier so that a short circuit in one amplifier will not shut
transformer module is installed. Audio
RMS
RMS
,
Primary applications for the audio panels include protecting structures such as military facilities, restaurants, schools, auditoriums, places of worship, buildings with occupancies over 50, etc. The ECC-50/100 is designed to interface directly to addressable or conventional (CMD inputs 1-8) fire alarm control panels or can be used with the ECC-50/125DA panel to distribute audio in systems that require more than 100 watts.

1.1 Product Features

Modular design for maximum system flexibility and easy expansion
Removable terminal blocks for ease of servicing and module replacement
50 watts of 25 V
2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols:
– System Sensor
– Wheelock
–Gentex
Optional 70.7 V speaker wiring continues to be supervised in standby, alarm and when background music is playing with this optional transformer installed)
Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification
Appliance Circuits (reverse polarity) or contact closures
– CMD3-CMD8 are activated by contact closures
Speaker Circuits
– single Style Y (Class B) or Style Z (Class A) speaker circuit
RMS
audio power (expandable to 100 watts)
RMS
conversion transformer available for the primary amplifier (note that
12 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Input/Output Circuit Specifications Product Description
– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-
25/70V Audio Amplifier installed)
– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-
25/70V and ECC-CE6 installed)
ECC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. Compatible FACPs include the MS-9600(UD)LS and MS-9200UDLS.
Integral supervised microphone
Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time
Up to 14 recorded messages
14 prerecorded messages for fire, emergency, and weather alerts
Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio input
External Audio Input can be used for background music
Up to 60 second message duration for all messages
Integral tone generators field selectable for multiple tone types
Powered by integral AC power supply or batteries during AC fail
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
Piezo sounder for local trouble
100 event history log
Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
500 mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable FACPs and End-of-Line power supervision relays
System Status LEDs (refer to “Controls and Indicators” on page 20)
Integral Dress Panel
Optional TR-CE semi-flush trim ring
Any combination of up to eight (8) of:
– Optional ECC-RM Remote Microphone (includes cabinet).
– Optional ECC-RPU Remote Page Unit (includes cabinet)
– Optional ECC-LOC (includes cabinet)
Optional ECC-CE6 Circuit Expander
Optional ECC-50W-25V amplifier, 50 watts, 25 volts
Optional ECC-50W-70V amplifier, 50 watts, 70 volts
Optional ECC-50DA distributed amplifier, 50 watts
Optional ECC-125DA distributed amplifier, 125 watts

1.2 Input/Output Circuit Specifications

1.2.1 ECC-50/100 Main Control Board

AC Power - TB15
ECC-50/100: 120 VAC, 60 Hz, 3.5 amps (HOT, NEU) ECC-50/100E: 240 VAC, 50 Hz, 2.0 amps (HOT=HotLeg1, NEU=HotLeg2) Wire size: minimum #14 AWG (2.00mm
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 13
2
) with 600 V insulation.
Product Description Input/Output Circuit Specifications
Battery (lead acid only) - J7
Maximum Charging Circuit: Normal Flat Charge - 27.3V @ 2.8 amps Maximum Charger Capacity: 26 Amp Hour battery. (ECC cabinet holds max. 18 Amp Hour Bat­tery. Minimum Battery Size: 12 Amp Hour
MNS Active Relay - TB1
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),
Form-C Trouble Relay - TB2
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).
AC Loss Relay - TB3
Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive),
NAC Output - TB19, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)
One (1) Style Y (Class B) or Style Z (Class A) circuit Power-limited circuitry (Class 2), supervised Nominal operating voltage: 24 VDC Maximum signaling current for special application power: 2.0 amps Maximum signaling current for regulated power: 200mA Current limit: fuseless, electronic, power-limited Maximum wiring impedance: 1 End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style Y (Class B) operation
Refer to the Device Compatibility Document for listed compatible devices.
NAC Follower - TB18, Terminals 3 (IN+), 4 (IN-), 1 (OUT+) & 2 (OUT-)
Connections for FACP NAC synchronization trigger signal Output terminals: pass-through to other system components Trigger input voltage: 9 to 32 VDC, 24 VDC rated Input current draw in Alarm condition: 10 mA at rated voltage
Special Application Power (Aux. Power) - TB17 Terminals 1(+) & 2(-)
Up to 500 mA @ 24 VDC of special application power is available for powering addressable mod­ules and associated End-of-Line power supervision relays.
Power-limited (Class 2) circuitry. Refer to the Device Compatibility Document for a list of compat-
ible devices.
Speaker Volume Control Override - TB23, Terminals 1 (B+), 2 (A+), 3 (A-), & 4 (B-)
Style Y (Class B) or Style Z (Class A) circuit Special Application power Power-limited (Class 2) circuitry, supervised Nominal operating voltage: 24 VDC Maximum signaling current: 0.25 amps Current limit: fuseless, electronic, power-limited End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style Y (Class B) operation
Speaker Circuits
Primary Speaker Circuit - TB20, Terminals 1(+) & 2(-) Style Y (Class B), 4(+) & 5(-) Style Z
(Class A), 3 Shield (Standby and Alarm Polarity Shown) on main control board
Secondary Speaker Circuit (with optional amplifier only) - TB21, Terminals 1(+) & 2(-)
Style Y (Class B), 4(+) & 5(-) Style Z (Class A), 3 Shield (Standby and Alarm Polarity Shown) on main control board
14 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Input/Output Circuit Specifications Product Description
Power-limited (Class 2) circuitry Operation: Circuit can be wired Style Y (Class B) or Style Z (Class A) Normal Operating Voltage: 25 V (70.7 V
@ 700 mA max. with maximum Load Impedance of 100operation possible by plug-
RMS
@ 2 amps max. and maximum Load Impedance of 12.5
RMS
ging optional ECC-XRM-70V conversion transformer into J12 of the main control board). Output Power: 50 watts (5 watts when background music is employed); Frequency Range: 800 - 2,800 Hz Maximum total capacitance for each speaker circuit: 250 µF. End-of-Line Resistor required for Style Y circuit: 15 K, 1 watt (P/N: ELR-15K)
Command Input Circuits (alarm polarities shown)
CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices downstream; provides internal trouble relay rated at 3.0 amps maximum
CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices downstream
CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for contact closure only
CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for contact closure only
CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for contact closure only
CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for contact closure only
CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for contact closure only
CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for contact closure only
Power-limited (Class 2) and supervised circuitry Normal Operating Voltage Range: 10.5 VDC - 29 VDC; Maximum Voltage: 29 VDC NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mA maximum. Contact Closure Operation Current (requires 4.7K, ½ watt End-of-Line Resistor P/N 27072): 6.6 mA maximum Maximum Wiring Impedance CMD1 - CMD8 (Contact Closure Operation): 200 Maximum Input Impedance:
• CMD1 & CMD2 (Reverse Polarity Operation): 20K
• CMD1 - CMD8 (Contact Closure Operation): 4.75K
Night Ring Input - TB16, Terminals 1 (+) & 2 (-)
Contact closure input Isolated, nonsupervised Operation current: 3.8 mA, maximum Maximum wiring impedance: 30K Minimum isolation withstand voltage: 1500 V
RMS
External Operator Interface Power Output - TB24, Terminals 1 (PWR, +) & 2 (GND, -)
Non-resettable power for external operator interface components Power-limited (Class 2) circuitry, Supervised Nominal operating voltage: 24 VDC Maximum output current: 0.80 amps Current limit: fuseless, electronic, power-limited circuitry
External Data Bus (EIA-485) - TB12, Terminals 2 (B), 3 (A) , 4 (BRTN), 5 (ARTN), & 1(SHLD)
Data connections for external operator interface components Redundant transceiver circuitry for Class A operability Power-limited (Class 2) circuitry, supervised Maximum wiring impedance: 13.2
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 15
Product Description Input/Output Circuit Specifications
FACP Data Bus (EIA-485) - TB13, Terminals 1 (B IN), 2 (A IN), 3 (B OUT), & 4 (A OUT)
Dedicated connection to FACP serial bus Output terminals: pass-through to other system components Isolated, supervised Minimum isolation withstand voltage: 1500 V
RMS
Maximum wiring impedance: 40 (ANN-BUS)/26 (ACS BUS)
External Audio Riser TB22, Termina ls 1 (OUT+), 2 (OUT-), 4 (IN+), 5 (IN-), & 3 (SHLD)
Style Y (Class B) or Style Z (Class A) audio connections to external operator interface components Power-limited (Class 2) circuitry, supervised Audio signal level: 3.85 V
, maximum
RMS
Frequency range: 800 - 2,800 Hz Frequency range (ECC-50/125DA): 800 Hz - 2.8 KHz
NOTE: Zero impedance to ground will cause a ground fault.
16 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Input/Output Circuit Specifications Product Description
TB20
TB21
TB19
TB24
TB23
TB17
Primary 50W Speaker Circuit
3.3 amps max.
Secondary 50W Speaker Circuit- Optional Amplifier Installed
3.3 amps max.
NAC Circuit
2.0 amps max.
Aux. Power
0.5 amp max.
Speaker Volume Control Override
0.25 amp max.
External Operator Interface Power
0.8 amp max.
Standby
2.0 amps max.
(includes background
music) with external
charger. Refer to
Section 6.
Alarm
7.5 amps max.
Figure 1.2 Current Availability - 100 Watt System
Current Availability
The following figures illustrate the maximum current possible for each panel output circuit and the total output current available from the power supply. Refer to Section 6, “Power Supply Calcula­tions” for additional current draw by option cards that must be considered when determining total standby and alarm currents.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 17
Product Description Input/Output Circuit Specifications
TB20
TB19
TB17
TB23
TB24
Primary 50W Speaker Circuit
3.3 amps max.
NAC Circuit
2.0 amps max.
Aux. Power
0.5 amp max.
Speaker Volume Control Override
0.25 amp max.
External Operator Interface Power
0.8 amp max.
Standby
2.0 amps max.
(includes background
music) with external
charger. Refer to
Section 6.
Alarm
7.5 amps max.
Figure 1.3 Current Availability - 50 Watt System

1.2.2 Display Board

External Audio Input - TB5, Terminals 1(-), 2 (+)
Input Impedance: 8.5K, nominal @ 1 KHz Input Voltage: 700 mV Input Current: 0.1 mA, maximum @ 700 mV Background Music Input Voltage: 225mV
NOTE: Some laptops/personal computers only provide an audio output for headphones. It may be necessary to adjust the headphone output level for proper recording of voice messages.
maximum
RMS
maximum
RMS,
18 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Input/Output Circuit Specifications Product Description

1.2.3 ECC-CE6 Circuit Expander Module

Power-limited (Class 2) circuitry Up to six (6) circuits on the ECC-CE6 can be wired as Style Y (Class B) or Style Z (Class A). Normal Operating Voltage for Speaker Circuits: 25 V Impedance of 12.5
@ 2 amps max. and maximum Load
RMS
(70.0 V
@ 700 mA max. with maximum Load Impedance of 100operation possible for
RMS
the primary circuit by plugging optional ECC-XRM-70V conversion transformer into J12 of the main control board. The same operation is possible for the optional 50W amplifier by selecting the ECC-50W-70V model.)
Speaker circuit wiring is supervised during standby, background music, and alarm. Output Power: 50 watts total; Frequency Range: 800 - 2,800 Hz
Maximum total capacitance: 250 µF. (Note that the total
capacitance for the speaker outputs must
not exceed the maximum of 250 µF).
End-of-Line Resistor required for Style Y (Class B) speaker circuit: 15 K, 1 watt (P/N: ELR-15K) TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides programmed speaker control
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 19
Product Description Controls and Indicators
FIRE SYSTEM ACTIVE
SYSTEM
CONTROL
ALL
CALL
1
2 3 4 5 6 7 8
9 10 11 12
13
18 19 20
21
22
23
24
16
17
14 15
ecckyd.wmf
Figure 1.4 ECC-50/100 Keypad
SPEAKER
ZONE 1
SPEAKER
ZONE 2
SPEAKER
ZONE 3
SPEAKER
ZONE 4
SPEAKER
ZONE 5
SPEAKER
ZONE 6
SPEAKER
ZONE 7
SPEAKER
ZONE 8
SPEAKER
ZONE 9
SPEAKER
ZONE 10
SPEAKER
ZONE 11
SPEAKER
ZONE 12
SPEAKER
ZONE 13
SPEAKER
ZONE 14
SPEAKER
ZONE 15
SPEAKER
ZONE 16
SPEAKER
ZONE 17
SPEAKER
ZONE 18
SPEAKER
ZONE 19
SPEAKER
ZONE 20
SPEAKER
ZONE 21
SPEAKER
ZONE 22
SPEAKER
ZONE 23
SPEAKER
ZONE 24
MESSAGE 1
MESSAGE 2
MESSAGE 3
MESSAGE 4
MESSAGE 5
MESSAGE 6
MESSAGE 7
MESSAGE 8
DIST. AMP 1 DIST. AMP 2 DIST. AMP 3 DIST. AMP 4 DIST. AMP 5 DIST. AMP 6 DIST. AMP 7 DIST. AMP 8
DIAGNOSTIC
REMOTE AMPS
TROUBLE SILENCE
AC POWER GROUND FAULT CHARGER FAULT BATTERY FAULT DATA BUS FAULT NAC FAULT NAC ACTIVE SYSTEM TROUBLE
AUDIO RISER FAULT
LOC 1 LOC 2 RPU 1 RPU 2 RPU 3
RM 1 RM 2 RM 3
CONSOLE LAMP TEST
MAIN CONSOLE
MNS
CONTROL
OK TO PAGE
MICROPHONE TROUBLE
green green
yellow
yellow
red
green
green
yellow
Note: Console assignments are shown here as an example only.

1.3 Controls and Indicators

1.3.1 Push-Button Controls

•All Call
MNS Control
System Control
Speaker Select 1-24
Message Select 1-8
Diagnostic Select
Trouble Silence
•Console Lamp Test
20 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Components Product Description

1.3.2 LED Indicators (visible with door closed)

Fire System Active (green)
MNS Control (green)
System Control (green)
System in Use (green)
Speaker Zone 1-24 Active (green)
Speaker Zone 1-24 Fault (yellow)
OK to Page (green)
Microphone Trouble (yellow)
Message 1-8 Active (red)
Message 1-8 Fault (yellow)
Remote Amplifier 1-8 Fault (yellow)
LOC/RPU/RM 1-8 Fault (yellow)
LOC/RPU/RM 1-8 Active (green)
Main Console Fault (yellow)
AC Power (green)
Ground Fault (yellow)
Charger Fault (yellow)
Battery Fault (yellow)
Data Bus Fault (yellow)
NAC Fault (yellow)
NAC Active (green)
System Trouble (yellow)
Audio Riser Fault (yellow)

1.3.3 LED Indicators (visible with door and dress panel open)

Speaker Volume Control Fault (yellow)
Option Card Fault (yellow)
Amplifier Over Current Fault (yellow)

1.4 Components

Main Control Board
The ECC-50/100 main control board contains the system's CPU, power supply, battery charger, other primary components and wiring interface components. One 50W amplifier is integrated into the main control board.
Display Board
The display board contains the user interface along with tone generators, digital message recorder/generator, integral microphone input, and preamplifier.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 21
Product Description Components
FIRE SYSTEM ACTIVE
SYSTEM CONTROL
ALL
CALL
1 2 3 4 5 6 7 8 9
10
11
12
13
18 19 20 21 22 23 24
16 17
14 15
LIT
FI®AL
by Honeywell
Figure 1.5 Cabinet
eccfront.wmf
Figure 1.6 Dress Panel
ecc_dp.wmf
Cabinet
The cabinet is red with an attractive navy blue front overlay. A clear window allows viewing of the display board, status LEDs and location of microphone. The backbox measures 16.65" x 19.0" x
5.2" D (42.29cm x 48.26cm x 13.23cm) and provides space for two 12AH or two 18AH batteries.
Batteries
The cabinet provides space for up to 18 Amp Hour batteries (charged by integral Power Sup­ply/Battery Charger) with all options installed.
Dress Panel
The Dress Panel is supplied standard with the system. It mounts to the cabinet with two supplied screws. The Dress Panel protects the user from high voltages and circuit boards from accidental
damage.
Trim Ring
An optional TR-CE trim ring is available for semi-flush mounting of the audio panel.
22 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Optional Equipment Product Description

1.5 Optional Equipment

ECC-50W-25/70V Audio Amplifier Modules
An optional second audio amplifier can be plugged into connectors J10 & J11 located in the upper right of the main control board in the ECC-50/100. This amplifier also provides 50 watts of power
RMS
or 70 V
at 25 V to 100 watts (providing dual 50 watt speaker circuits) or it can be used as a backup amplifier. The output is power-limited (Class 2) and speaker circuit connections to it are provided on the main control board and optional speaker circuit expander module. The circuit can be wired for Style Y (Class B) or Style Z (Class A) operation.
LEDs are provided to indicate Amplifier Supervision (green indicates amplifier is functional) and Circuit Trouble (yellow indicates field wiring fault or amplifier fault). The LEDs are only visible with the panel door open.
ECC-CE6 Circuit Expander Module
This optional module plugs into connector P1 in the upper middle of the main control board. The ECC-CE6 adds three primary speaker circuits to the ECC-50/100. The ECC-CE6 adds three sec­ondary circuits to the system when the ECC-50W-25/70V Audio Amplifier Module is also installed.
, depending on the model, and can therefore be used to expand system power
RMS
ECC-XRM-70V Transformer 70.7 V
RMS
This optional module plugs into connector J12 of the main control board and provides conversion for the integral audio amplifier from 25 V
to 70.7 V
RMS
at full rated 50 watts output power.
RMS
ECC-FFT Fire Fighter Telephone
The ECC-FFT has a telephone handset and user interface that allows an operator to communicate with remotely located telephone handsets in a building. It is housed in its own cabinet with key lock. It requires an external operator interface power connection (24 volts DC) from the ECC­50/100 main console or it may be powered from an external 24 VDC power supply such as HP300ULX. The ECC-FFT provides supervision, annunciation, and control for the local handset and for up to 24 remote telephone handsets. It provides indications of phone activation and corre-
sponding trouble conditions. Refer to the ECC-FFT Fire Fighter Telephone manual.
ECC-50DA Distributed (Remote) Audio
The ECC-50DA is a 50-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus connection and an external audio riser connection from the ECC­50/100 main console. The unit comes standard with 4 speaker circuits. An option card, ECC-CE4, provides 4 more speaker circuits for a total of 8. Speaker circuits are activated/de-activated manu­ally or automatically by the ECC-50/100 main console. The unit is capable of either 25 V
70.7 V
operation. Refer to the ECC-50/125DA Distributed Audio manual.
RMS
RMS
or
ECC-125DA Distributed (Remote) Audio
The ECC-125DA is a 125-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus connection and an external audio riser connection from the ECC­50/100 main console. The unit comes standard with four (4) speaker circuits. An option card, ECC­CE4, provides 4 more speaker circuits for a total of eight (8). Speaker circuits are activated/de-acti­vated manually or automatically by the ECC-50/100 main console. The unit is capable of 25 V
RMS
operation. Refer to the ECC-50/125DA Distributed Audio manual.
NOTE: Any combination of up to eight audio boosters comprised of ECC-50DA and ECC-125DA can be used in the system. Their external data bus addresses must be unique and must be sequential. Addresses are set via dipswitches on each unit's PC board. Refer to Section 2.14 on page 54.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 23
Product Description Optional Equipment
ECC-RM Remote Microphone
The ECC-RM has a hand held microphone and is housed in its own cabinet with keyed lock. It requires an external data bus connection, an external audio riser connection, and an external opera­tor interface power connection (24 volts DC) from the ECC-50/100 main console. ALL CALL pag­ing can be broadcast over the speaker circuits by depressing the microphone's push-to-talk switch. Not for use in UL2572 Mass Notification applications.
ECC-RPU Remote Page Unit
The ECC-RPU has a hand held microphone and 8 message buttons. It is housed in its own cabinet with a keyed lock or thumb lock (requires AHJ approval). It also has a 9th button that will activate an MMF-300 monitor module mounted inside the cabinet. This may be used for HVAC shutdown applications when the monitor module is connected to the FACP SLC polling loop. The remote page unit requires an external data bus connection, an external audio riser connection, and an exter­nal operator interface power connection (24 volts DC) from the ECC-50/100 main console. ALL CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to­talk switch. ALL CALL broadcast of a stored message can be done by pressing a message button. The message buttons operate in the same fashion as the message buttons on the ECC-50/100 main console. Not for use in UL2572 Mass Notification applications.
ECC-LOC Local Operator Console
The ECC-LOC has a complete operator interface like the ECC-50/100 main console and is housed in its own cabinet with a keyed lock or thumb lock (requires AHJ approval). The local operator console requires an external data bus connection, an external audio riser connection, and an exter­nal operator interface power connection (24 volts DC) from the ECC-50/100 main console.
NOTE: Any combination of up to eight remote consoles comprised of ECC-RM(s), ECC-RPU(s), and ECC-LOC(s) can be used in the system. Their external data bus addresses must be set via dipswitches on each unit's PC board. Refer to Section 2.14 on page 54.
24 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013

Section 2: Installation

!

2.1 Mounting Options

The cabinet may be semi-flush or surface mounted. The cabinet mounts using three key slots at the top of the backbox and two additional 0.250" diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. Note that knockouts are also located on the back of the cabinet. All wiring should be in accordance with the National and/or Local codes for fire alarm systems. Refer to Figure 2.4 for knockouts that cannot be used.

2.2 Backbox Installation

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAG­ING TO PROTECT ELECTRONIC ASSEMBLIES.

Removing the Dress Panel

1. Open the door and lift the door off the pin hinges.
2. Loosen the two (2) screws that secure the dress panel to the backbox. Then, lift up to swing the dress panel open.
3. Disconnect the ground wire from the dress panel.
4. Unplug the cable on the display board at J2. This is the connection to the main control board on the chassis.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 25
Installation Backbox Installation
J12
TB15
J9
RTZM
Rev.
ECC-MCB-PCA
loosen screws
disconnect
earth ground
unplug cable
lift up dress panel, pull out, slide down to remove
Figure 2.1 Dress Panel Removal
ecc-dpopn.wmf
remove screws
loosen nuts
chassisinst.wmf
Figure 2.2 Chassis Removal
5. Lift the dress panel up and gently pull the lower hinge out of the backbox. Gently pull down to remove the top hinge. Store the dress panel in a safe place.

Removing the Chassis Assembly

1. If present, remove the two (2) screws which fasten the lower chassis tabs to the backbox. These are for shipping purposes only and do not need to be reinstalled.
2. Loosen the two nuts which secure the top of the chassis with an 11/32” socket.
3. Carefully lift up and remove the chassis assembly from the backbox and store in a safe, clean place. Avoid static discharge which may damage static sensitive components on the board.
26 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Backbox Installation Installation
!
J12
TB15
J9
RTZM
Rev.
ECC-MCB-PCA
Figure 2.3 Chassis Installation
chassistab.wmf

Mounting the Backbox

1. Mark and predrill hole in the wall for the center top keyhole mounting bolt using the dimen­sions illustrated in Figure 2.4 on page 28.
2. Install center top fastener in the wall with the screw head protruding.
3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower mounting holes. Note: Outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
5. Install remaining fasteners and tighten.
6. Carefully reinstall the chassis assembly and dress panel by reversing the steps above. Use appropriate precautions to prevent damage to components due to static discharge. When reinstalling the chassis assembly, be sure that all four (4) tabs are seated properly in the slots of the backbox to avoid possible damage to the unit.
CAUTION: POSSIBLE EQUIPMENT DAMAGE
REINSTALL THE CHASSIS ASSEMBLY CAREFULLY , MAKING SURE TO PROPERLY SEAT THE UNIT TO THE BACKBOX.
7. Draw wires through the respective knockout locations.
An optional Trim Ring (P/N TR-CE) is available for semi-flush mount installations.
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 27
Installation Backbox Installation
Figure 2.4 Cabinet Dimensions & Knockout Locations
9050udencl.wmf
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
Hinge Slot for Dress Panel
Hinge Slot for Dress Panel
Semi-flush mounting hole
Mounting slots for optional Trim Ring
Do not use these knock-outs!
28 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Backbox Installation Installation
FIRE SYSTEM ACTIVE
SYSTEM CONTROL
ALL CALL
1 2 3 4 5 6 7 8
9 10 11 12
13
18 19 20 21 22 23 24
16 17
14 15
LIT
FI
®
AL
by Honeywell
Figure 2.5 ECC-50/100 Backbox Dimensions
ecc-cab.wmf
Left Side
Right Side
Bottom
Door
Door Backbox
Backbox
Depth =
Depth
Top
Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013 29
Installation Operating Power
!
Figure 2.6 Earth Ground Connection
e
c
c
g
n
d
.
w
m
f
grounding stud
keps nuts
Grounding Cable #71073
grounding stud
Equipment Ground

2.3 Operating Power

WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DIS­CONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. BE SURE TO OBSERVE PROPER GROUNDING AND HANDLING PROCEDURES.

2.3.1 AC Power and Earth Ground Connection

Primary power source for the ECC-50/100 is 120 VAC, 60 Hz, 3.5 amps. Primary power source for the ECC-50/100E is 240 VAC, 50 Hz, 2.0 amps. Over-current protection for this circuit must com­ply with Article 760 of the National Electrical Code (NEC) and/or local codes. Make certain that the AC mains circuit breaker is off before making any wiring connections between the mains and the panel. Connect AC mains wiring from the protected premises main breaker box to TB15 of the main control board. Use 14 AWG (2.0 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V insu­lation. No other equipment may be connected to this circuit and it may not contain any power dis­connect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Do not use conduit for the Earth Ground connec­tion since this does not provide reliable protection. Remove the two keps nuts from the grounding stud in the backbox. Connect the incoming earth ground wire to supplied cable #71073 with a wire nut. Position the ring terminal end over the grounding stud. Secure with one of the keps nuts. Place the ring terminal from the other supplied cable to TB15. Refer to Figure 2.6 for the location of the stud. Apply AC power to the panel only after the system is completely installed and visually
checked. Note that AC power must be applied to the panel before installing the battery intercon- nect cable (refer to the following section).
30 Emergency Command Center Manual — P/N LS10001-000FL-E:A 4/10/2013
Loading...
+ 78 hidden pages