EVCO EVB1256N9D User Manual

EVCO S.p.A.
EVBOX1
Front mounted electrical boards for cold
rooms with single-phase compressor
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Installation guide| ENGLISH
Code 144BOX1E134
page 1 of 92
EVCO S.p.A.
Important
Read this document thoroughly before installation and before
use of the device and follow all recommendations; keep this
document with the device for future consultation.
Only use the device in the way described in this document; do
not use the same as a safety device.
Disposal
The device must be disposed of in compliance with local
standards regarding the collection of electric and electronic
equipment.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 2 of 92
EVCO S.p.A.
Index
1
1.1
1.2
2
2.1
2.2
3
3.1
3.2
3.3
4
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
5
5.1
6
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
INTRODUCTION ............................................... 4
Introduction .................................................... 4
Summary table of available models, their main
characteristics and purchase codes ................... 5
DESCRIPTION ................................................. 8
Outward appearance description ........................ 8
Interior description ........................................ 10
DIMENSIONS AND INSTALLATION ................... 13
Dimensions ................................................... 13
Installation.................................................... 13
Installation warnings ...................................... 14
ELECTRIC CONNECTION ................................. 15
Preliminary notes ........................................... 15
Electric connection for models EVB1204 and
EVB1214....................................................... 16
Electric connection for models EVB1206 and
EVB1216....................................................... 17
Electric connection for models EVB1226 and
EVB1236....................................................... 18
Electric connection for models EVB1246 and
EVB1256....................................................... 19
Electric connection for models with direct loads
connection (example for EVB1216N9XXC) ........ 20
Electric connection for models with magneto-
thermal switch or differential magneto-thermal
circuit breaker (example for EVB1256N9D) ....... 21
Insertion of the RS-485 MODBUS port termination
resistor ......................................................... 22
Connection of the RS-485 network cable screen to
GND ............................................................. 22
Warnings for the electric connection ................. 22
FIRST USE .................................................... 23
First use ....................................................... 23
USER INTERFACE ........................................... 25
Preliminary notes ........................................... 25
Device switch-on/off in manual mode .............. 25
The display ................................................... 25
Displaying the magnitude detected by an
analogue input .............................................. 25
"Rapid cooling" function enabling/disabling ...... 26
Defrosting manual activation ........................... 27
Turning on/off of room lights manually (only if the
parameter u1 and/or parameter u11 is set at 0)
................................................................... 27
Turning the demister heating elements on/off
manually (only if the parameter u1 and/or
parameter u11 is set at 1) .............................. 27
Turning on/off of the auxiliary output manually
(only if the parameter u1 and/or parameter u11
is set at 2) .................................................... 28
Displaying some instant values joined to the
electronic expansion valve (only in models
EVB1246 and EVB1256).................................. 28
Keyboard locking/unlocking ............................. 29
Silencing the buzzer ....................................... 30
7
7.1
7.2
7.3
8
8.1
9
9.1
10
10.1
10.2
10.3
11
11.1
11.2
11.3
12
12.1
12.2
12.3
12.4
12.5
13
13.1
13.2
14
14.1
15
15.1
16
16.1
16.2
16.3
16.4
17
17.1
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
OPERATION WITH LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGES (ONLY IF THE F0
PARAMETER IS SET TO 5) ...............................31
Preliminary notes ...........................................31
Manual activation of the low and high relative
humidity percentages operating mode ..............31
Learning the current operating mode ...............31
“ENERGY SAVING” FUNCTION ..........................32
Preliminary notes ...........................................32
“CPT” FUNCTION (CALCULAT- ED PRODUCT
TEMPERATURE) ..............................................32
Preliminary notes ...........................................32
“HACCP” FUNCTION ........................................32
Preliminary notes ...........................................32
Display of HACCP alarm information ................33
Cancelling the HACCP alarm list .......................34
COMPRESSOR OPERATING HOURS COUNT .......35
Preliminary notes ...........................................35
Display of Compressor Operation Hours ...........35
Cancelling the compressor operation hours .......36
SETTINGS .....................................................37
Setting the date, time and day of the week (only
in the models with clock) ...............................37
Setting the working set point ...........................38
Setting the configuration parameters ...............38
Restoring the Manufacturer’s settings ..............39
List of configuration parameters .......................40
WARNING LIGHTS AND DIRECTIONS ................76
Signals .........................................................76
Signal Descriptions/Explanations ......................78
ALARMS ........................................................79
Alarms ..........................................................79
ERRORS ........................................................82
Errors ...........................................................82
ACCESSORIES ...............................................84
Non opto-isolated RS-485/USB serial interface
EVIF20SUXI...................................................84
Data recorder EVUSBREC01 .............................84
USB cover for panel installation 0812000002 .....84
0810500018/0810500020 connection cable .......85
TECHNICAL DATA ...........................................86
Technical data ...............................................86
page 3 of 92
EVCO S.p.A.
1 INTRODUCTION
1.1 Introduction
EVBOX1 is a line of front mounted electrical boards for the
management of cold rooms with single-phase compressor.
The user interface comprises a large custom display (with
decimal point and function icons), six keys, and has a
guaranteed IP65 protection grade front part.
The boards are equipped with two 30A res. @ 250 VAC relays
for the direct control of high power compressors and
defrosting elements, with no need for remote control switches.
They can operate in conditions of both low and high relative
humidity percentages, have an adaptive management of the
defrost function, and can implement energy-saving strategies.
Some models are also equipped with a magneto-thermal
switch or differential magneto-thermal circuit breaker, a clock
(to save the HACCP alarms), management of defrosting
elements and have an integrated driver for unipolar stepper
electronic expansion valves.
The unit is designed to be wall mounted, with bolts and
fastening screws.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 4 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
1.2 Summary table of available models, their main characteristics and purchase
codes
The following table contains a description of the available models.
Available models
The following table shows the main characteristics of the devices.
Power supply
115... 230 VAC
Analogue inputs
room temperature (PTC/NTC/Pt 1000)
evaporator temperature (PTC/NTC/Pt 1000)
auxiliary temperature (PTC/NTC/Pt 1000) (1)
vapour pressure (4-20 mA)
evaporation temperature (PTC/NTC/Pt 1000)
Digital inputs (for NA/NC contact)
door micro switch
multifunction
multifunction 2
Digital inputs (electromechanical relays; A res. @ 250 VAC)
compressor 30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
defrosting 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
evaporator fan 30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
room light 16 A 16 A 16 A 16 A 16 A 16 A
load 4 (default to room light) (2) 8 A 8 A
page 5 of 92
EVCO S.p.A.
load 5 (default to condenser fan) (3) 8 A 8 A 8 A 8 A 8 A 8 A
load 6 (default to alarm ) (3) 8 A 8 A 8 A 8 A 8 A 8 A
Communication ports
RS-485 MODBUS for other EVCO products
Other characteristics
clock
alarm buzzer
three-phase defrost elements management
integrated driver for unipolar stepper electronic expansion valves.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
operation at low and high relative humidity percentages
overheated condenser alarm management
defrosting adaptive management
"HACCP" function
"energy saving" function
"rapid cooling" function
Notes
(1)
(2)
(3)
Available options
In some models, there is a magneto-thermal switch or differential magneto-thermal circuit breaker.
Check that the switch is available for the device; contact the EVCO distribution network.
For additional information, please read chapter "TECHNICAL DATA",
can be set through a configuration parameter to condenser temperature, critical temperature, evaporator 2 temperature or
CPT temperature parameter.
can be set through a configuration parameter to room light, demister heating elements, auxiliary, alarms, door resistors,
neutral area operation resistors, condenser fan, compressor 2, defrosting 2 evaporator fan 2, pump down valve, on/stand-
by or man in cold room
can be set through a configuration parameter to demister heating elements, auxiliary, alarms, door resistors, neutral area
operation resistors, condenser fan, compressor 2, defrosting 2 evaporator fan 2, pump down valve, on/stand-by or man in
cold room
page 6 of 92
EVCO S.p.A.
The following tables show the purchase codes.
Switchboards for single-phase cold rooms (3)
Notes
(1) with magneto-thermal switch
(2) with differential magneto-thermal circuit breaker
(3) also available in version with direct loads connection (add “XXC” after “9” or “XC” after “M” and “D” to the purchase code).
Switchboards for single-phase cold rooms with three-
phase defrost heater management
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Available models
Add "M" for the magneto-thermal switch or "D" for the differential magneto-thermal circuit breaker.
For additional models, please contact the EVCO distribution network
page 7 of 92
EVCO S.p.A.
2 DESCRIPTION
2.1 Outward appearance description
The following drawing shows the outward appearance of the devices.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
The following table shows the meaning of the parts of the front of the devices
PART MEANING
1 access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
2 screws fastening the front shell to the back shell
3 tab fastening the front shell to the back shell
4 handle of the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
5 handle to remove the cover of the screws fastening the front shell to the back shell
6 cover of the screws fastening the front shell to the back shell
7 on/off key, hereinafter also "ON/STAND-BY" key
8 manual defrosting key, hereinafter also "DEFROSTING" key
9 auxiliary functions key, hereinafter also "AUXILIARY" key
10 display
11 increase key, hereinafter also "UP" key
page 8 of 92
EVCO S.p.A.
For additional information, please refer to the following chapters.
12 settings key, hereinafter also "SET" key
13 decrease key, hereinafter also "DOWN" key
14 seal
15 if present, magneto-thermal switch or differential magneto-thermal circuit breaker
16 front shell
17 back shell
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 9 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
2.2 Interior description
To access the interior of the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in
paragraph 2.1 “Outward appearance description"):
1.
2.
3.
The following drawing shows the inner appearance of the devices.
Open the access door of the magneto-thermal switch or differential magneto-thermal circuit breaker (1) using the relevant
handle (4) and loosen the two screws fastening the front shell to the back shell (2) with a screwdriver.
Remove the cover of the two screws fastening the front shell to the back shell (6) using the relevant handle (5) and loosen
the two screws fastening the front shell to the back shell (2) with a screwdriver.
Lift the front shell (16) using the assembly tabs fastening the front shell to the back shell (3) as a pivot.
page 10 of 92
EVCO S.p.A.
The following table shows the meaning of the parts inside the devices
PART MEANING
3 tab fastening the front shell to the back shell
4 handle of the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
5 handle to remove the cover of the screws fastening the front shell to the back shell
15 if present, magneto-thermal switch or differential magneto-thermal circuit breaker
18 K3 digital output (evaporator fan)
19 K2 digital output (defrosting)
20 K1 digital output (compressor)
21 device power supply
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
22 if present, driver for unipolar stepper electronic expansion valves connected to a removable male only screw terminal board
23 if present, driver for unipolar stepper electronic expansion valves connected with male only JST connector
24 BUS RS-485 polarisation jumper
25 RS-485 MODBUS port
26 RS-485 MODBUS port termination resistor insertion jumper
27 digital inputs (micro port, multifunction 1 and multifunction 2)
analogue inputs 1 and 2 (room temperature and evaporator temperature) and analogue input 3 (can be set through a
28
configuration parameter to condenser temperature, critical temperature, evaporator 2 temperature or CPT temperature)
29 if present, analogue inputs 4 and 5 (evaporation temperature and vapour pressure)
in the EVB1204 and EVB1214 models, K4 digital output (can be set through a configuration parameter to room light,
demister heating elements, auxiliary, alarms, door resistors, neutral area operation resistors, condenser fan, compressor 2,
defrosting 2, evaporator fan 2, pump down valve, on/stand-by or man in cold room; manufacturer default is room light).
30
in the remaining models, K6 digital output (can be set through a configuration parameter to demister heating elements,
auxiliary, alarms, door resistors, neutral area operation resistors, condenser fan, compressor 2, defrosting 2, evaporator
fan 2, pump down valve, on/stand-by or man in cold room; manufacturer default is alarm).
page 11 of 92
EVCO S.p.A.
For additional information, please refer to the following chapters.
if present, K5 digital output (can be set through a configuration parameter to demister heating elements, auxiliary, alarms,
31
door resistors, neutral area operation resistors, condenser fan, compressor 2, defrosting 2, evaporator fan 2, pump down
valve, on/stand-by or man in cold room; manufacturer default is condenser fan).
32 if present, digital output 4 (room light)
33 seal
34 drilling lead for wall installation
35 ground terminal
36 raised profile
37 seal
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 12 of 92
EVCO S.p.A.
3 DIMENSIONS AND INSTALLATION
3.1 Dimensions
The following drawing shows the measurements of the devices, in mm (in).
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
3.2 Installation
The unit is designed to be wall mounted, with bolts and fastening screws (not supplied).
To install the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in chapter 2
"DESCRIPTION"):
1.
2.
3.
4.
5.
6.
7.
8.1
8.2
9.
10.
11.
12.
Open the access door of the magneto-thermal switch or differential magneto-thermal circuit breaker (1) using the relevant
handle (4) and loosen the two screws fastening the front shell to the back shell (2) with a screwdriver.
remove the cover of the two screws fastening the front shell to the back shell (6) using the relevant handle (5) and loosen
the two screws fastening the front shell to the back shell (2) with a screwdriver.
Lift the front shell (16) using the assembly tabs fastening the front shell to the back shell (3) as a pivot.
Drill a hole with a diameter of 5.0 mm (0.196 in) in each of the three drilling leads for wall installation (34).
Drill three 6.0 mm (0.236 in) holes in the wall where the device is to be installed, using the three previously perforated
drilling leads (34) as template.
Insert three bolts in the three holes drilled into the wall.
Insert three seals (37) in three fastening screws.
If the connection wires are to be threaded from the top or the bottom, drill a hole in a flat surface of the back shell (17),
whose dimensions are adequate for a cable tray (not supplied; the cable tray dimensions must be appropriate to the
number of cables to be laid) and assemble the cable tray.
If the connection cables are to be installed from the back, drill a hole with dimensions appropriate to the number of cables
to be laid in the raised profile (36) on the back wall of the back shell (17) and apply some silicone on the whole profile.
Fasten the back shell (17) with the three screws and the seals (37) previously inserted in the screws.
make the necessary electric connections; please refer to chapter "ELECTRIC CONNECTION".
Place the front shell (16) on the back shell (17) using the assembly tabs fastening the front shell to the back shell (3) as a
pivot.
Tighten the four screws fastening the front shell to the back shell (2) with a screwdriver, put the fastening screws cover (6)
back on and close the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker (1) with
the handle (4).
page 13 of 92
EVCO S.p.A.
3.3 Installation warnings
-
-
-
make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter
“TECHNICAL DATA”
do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful
magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or
shocks
in compliance with Safety Standards, the device must be installed correctly and in a way to protect against any contact with
electric parts; all parts that ensure protection must be fixed in a way that they cannot be removed without the use of tools.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 14 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4 ELECTRIC CONNECTION
4.1 Preliminary notes
The magnitude detected by the auxiliary sensor (terminals 5 and 8) can be set through the P4 configuration parameter as follows:
-
-
-
-
-
In the EVB1204 and EVB1214 models the application managed by the K4 digital output (terminals 13, 14 and 15) can be set by the u11
configuration parameter as follows:
-
-
-
-
-
-
-
-
-
-
-
-
-
In the remaining models, the application managed by the K5 digital output, terminals 16 and 17 (K3 in the models with direct load
connection, terminals 20 and 21) can be set through the u1 configuration parameter and that managed by the K6 digital output
(terminals 13, 14 and 15) through the u11 configuration parameter as follows:
-
-
-
-
-
-
-
-
-
-
-
-
Through the RS-485 MODBUS port it is possible to carry out on eof the following actions:
-
-
-
-
The port must not be used for more than one of these purposes at the same time.
Please see paragraph “Setting the configuration parameters” for the settings of the configuration parameters.
For additional information, please refer to the following paragraphs.
no magnitude (parameter P4 = 0)
condenser temperature (parameter P4 = 1)
critical temperature (parameter P4 = 2)
evaporator temperature 2 (parameter P4 = 3)
outgoing air temperature (parameter P4 = 4); in this case, the temperature associated with the setting shall be the CPT
(Calculated Product Temperature) one
room light (parameter u1 = 0, default setting)
demister heating elements (parameter u1 = 1)
auxiliary output (parameter u1 = 2)
alarm output (parameter u1 = 3)
door heating elements (parameter u1 = 4)
neutral area operating heating elements(parameter u1 = 5)
condenser fan (parameter u1 = 6)
compressor 2 (parameter u1 = 7)
defrosting 2 (parameter u1 = 8)
evaporator fan 2 (parameter u1 = 9)
pump down valve (parameter u1 = 10)
on/stand-by (parameter u1 = 11)
man in cold room exit (parameter u1 = 12).
demister heating elements (parameter u1 = 1)
auxiliary output (parameter u1 and/or u11 = 2)
alarm output (parameter u1 and/or u11 = 3, default setting for the K6 digital output
door heating elements (parameter u1 and/or u11 = 4)
neutral area operating heating elements(parameter u1 and/or u11 = 5)
condenser fan (parameter u1 and/or u11 = 6, default setting for the K5 digital output)
compressor 2 (parameter u1 and/or u11 = 7)
defrosting2 (parameter u1 and/or u11 = 8)
evaporator fan 2 (parameter u1 and/or u11 = 9)
pump down valve (parameter u1 and/or u11 = 10)
on/stand-by (parameter u1 and/or u11 = 11)
man in cold room exit (parameter u1 and/or u11 = 12).
device configuration, through the Parameters Manager set-up software system
device data recording, through the EVUSBREC01 data recording device
device supervision, through the CloudEvolution system monitoring and supervision (via Web) system
use of the MODBUS slave function through third party devices.
page 15 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.2 Electric connection for models EVB1204 and EVB1214
The following drawing shows the electric connections for the EVB1204 and EVB1214 models.
page 16 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.3 Electric connection for models EVB1206 and EVB1216
The following drawing shows the electric connections for the EVB1206 and EVB1216 models.
page 17 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.4 Electric connection for models EVB1226 and EVB1236
The following drawing shows the electric connections for the EVB1226 and EVB1236 models.
page 18 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.5 Electric connection for models EVB1246 and EVB1256
The following drawing shows the electric connections for the EVB1246 and EVB1256 models.
page 19 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.6 Electric connection for models with direct loads connection (example for
EVB1216N9XXC)
The following drawing shows the electric connections for models with direct loads connection (example EVB1216N9XXC).
page 20 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.7 Electric connection for models with magneto-thermal switch or differential
magneto-thermal circuit breaker (example for EVB1256N9D)
The following drawing shows the electric connections for models with magneto-thermal switch or differential magneto-thermal circuit
breaker (example EVB1256N9D).
page 21 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
4.8 Insertion of the RS-485 MODBUS port termination resistor
To reduce reflections on the signal transmitted through the cables connecting the devices to a RS-485 network it is necessary to insert
the termination resistor of the first and last elements of the network.
To insert the termination resistor place the jumper as shown in the following drawing.
4.9 Connection of the RS-485 network cable screen to GND
To prevent external disturbances from being interpreted as signals by the RS-485 network, it might be necessary to connect the cable
screen of the RS-485 network to GND
To connect the cable screen to GND, place the jumper as shown in the following drawing.
4.10 Warnings for the electric connection
-
-
-
-
-
-
-
do not use electric or pneumatic screwdrivers on the device terminal board
if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before powering it
make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with
those of the local power supply; see chapter “TECHNICAL DATA”
disconnect the device power supply before proceeding with any type of maintenance
connect the device to a RS-485 MODBUS network using a twisted pair
position the power cables as far away as possible from the signal cables
for repairs and information regarding the device, contact the EVCO sales network.
page 22 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
5 FIRST USE
5.1 First use
Operate as follows:
1.
2.
3.
4.
5.
PARAM. MEANING DEFAULT SETTINGS
Install the device as described in chapter "DIMENSIONS AND INSTALLATION" , following in particular the instructions of
paragraph “Installation warnings”.
Make the relevant electric connections for the device as shown in chapter "ELECTRIC CONNECTION", following in particular
the instructions of paragraph “Warning for the electric connection", without connecting the device or the loads power
supply.
Connect the device power supply: this shall launch an internal test.
The test typically takes a few seconds to complete; at the end of the test, the display turns off.
If, at the end of the test, the letters "rtc" flash on the screen and the buzzer sounds intermittently, it will be necessary to
set the date, time and day of the week; please refer to paragraph 12.1 “Setting the date, time and day of the week (only in
the models with clock)”.
Configure the device using the procedure described in paragraph “Setting the configuration parameters”,
The following table shows the meaning of the main configuration parameters; the parameters are shown in the order with
which it is best to configure the device.
temperature probe type
P0
0 = PTC
1 = NTC
2 = Pt 1000
1
temperature unit of measurement
P2
P9 pressure transducer minimum setting 0.5
P10 pressure transducer maximum setting 7.0
SP work set-point -18,0 °C
r0 working set-point differential 2.0 °C
d0
d3 maximum defrosting duration 30 min
0 = °C
1 = °F
type of defrosting
0 = electric
1 = by hot gas
2 = via stopping of compressor
0
0
page 23 of 92
EVCO S.p.A.
u1
u1
in the EVB1204 and EVB1214 models, the application is managed through the
K4 digital output
0 = man in cold room exit
1 = demister heating elements
2 = auxiliary output
3 = alarm output
4 = door heating elements
5 = neutral area operating heating elements
6 = condenser fan
7 = compressor 2
8 = defrosting2
9 = evaporator fan 2
10 = pump down valve
11 = on/stand-by
12 = man in cold room exit
in the remaining models, the application is managed by the K5 digital output (K3
in the models with direct load connection)
0 = reserved
1 = demister heating elements
2 = auxiliary output
3 = alarm output
4 = door heating elements
5 = neutral area operating heating elements
6 = condenser fan
7 = compressor 2
8 = defrosting2
9 = evaporator fan 2
10 = pump down valve
11 = on/stand-by
12 = man in cold room exit
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
0
6
if present, the application is managed by the K6 digital output
0 = reserved
1 = demister heating elements
2 = auxiliary output
3 = alarm output
4 = door heating elements
u11
6.
7.
For additional information, please refer to the following paragraphs.
5 = neutral area operating heating elements
6 = condenser fan
7 = compressor 2
8 = defrosting2
9 = evaporator fan 2
10 = pump down valve
11 = on/stand-by
12 = man in cold room exit
Then, check that the remaining settings are appropriate; refer to paragraph 12.5 “List of configuration parameters”.
Connect the loads power supply
Turn the device on; refer to paragraph "Device switch-on/off in manual mode".
3
page 24 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
6 USER INTERFACE
6.1 Preliminary notes
Operating Statuses:
-
-
-
Hereafter, with the word “start-up” means the passage from
“stand-by” status to “on” status; the word “shutdown” means
the passage from “on” status to “stand-by” status.
When the power is switched back on, the device displays the
status that it was in at the time it was disconnected.
“on” state (the device is powered and is on: the
regulators can be switched on)
“stand-by” status (the device is powered but is
switched off via software: the regulators are
switched off; the possibility to turn the room light
or the auxiliary output on/off manually depends on
parameter u2)
the “off” status (the device is not powered).
6.2 Device switch-on/off in manual
mode
To turn the device on/off in manual mode, proceed as follows:
1.
2.
Using the digital inputs it is also possible to remotely switch
on/off the device.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “ON/STAND-BY” for 2 s.
6.3 The display
If the device is switched on, during normal operation, the
display will show the magnitude established with P5, except
during defrosting, when the device will show the temperature
established with parameter d6.
If the device is switched off, the display will be switched off.
6.4 Displaying the magnitude
Device switch-on/off in manual mode
detected by an analogue input
To display the magnitude detected by an analogue input,
proceed as follows:
1.
2.
3.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the key “UP” or “DOWN” to
select a label.
page 25 of 92
Access the procedure to display the quantity detected by an analogue
input
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
The following table shows the correspondence between the
labels and the magnitudes displayed.
LABEL MAGNITUDE
Pb1
Pb2 evaporator temperature
Pb3 auxiliary temperature; see also parameter P4
Pb4 if present, vapour pressure
Pb5 if present, evaporation temperature
Pb6 CPT temperature; see also parameter P4
4.
To exit the procedure:
5.
6.
Alternatively:
7.
If the evaporator temperature sensor is not present (or if the
P3 parameter is set to 0), the "Pb2" label shall not be
displayed.
If the auxiliary temperature sensor is not present (or if the P4
parameter is set to 0), the "Pb3" label shall not be displayed.
If the magnitude recorded by the auxiliary sensor is not the
outgoing air temperature (or if the P4 parameter is not set to
4) the "Pb4" label shall not be displayed.
room/inflowing air temperature; see also
parameter P4
Press and release the key “SET”.
Press and release the key “SET” or do not operate
for 60 sec.
Press and release the “UP” or “DOWN” key until
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Press and release the “ON/STAND-BY” key.
6.5 "Rapid cooling" function
Displaying the magnitude detected by an analogue input
enabling/disabling
To enable/disable the "rapid cooling" function, proceed as
follows:
1.
2.
Check that the device is turned on, that the
keypad is not locked, that no procedures are in
progress and that there are no defrosting, dripping
or evaporator fan stop operations in progress.
Keep the "UP" key pressed for 4 s: the
"temperature" LED light shall start flashing.
page 26 of 92
"Rapid cooling" function enabling/disabling
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
During the "rapid cooling" function the work set point is
decreased by the temperature set with the r5 parameter; the
function runs for the span of time set with the r6 parameter.
During the "rapid cooling" function the defrosting function is
never activated; if the defrosting interval expires while the
rapid cooling function is in progress, the defrosting shall be
activated at the end of the cooling.
6.6 Defrosting manual activation
To activate the defrosting in manual mode, proceed as follows:
1.
2.
If the evaporator temperature sensor functions as a defrosting
sensor (that is to say,if the P3 parameter is set to 1) and when
the defrosting starts the evaporator temperature exceeds the
value set with the d2 parameter, the defrosting shall not be
activated.
Check that the device is turned on, that the
keypad is not locked, that no procedures are in
progress and that the "rapid cooling" function is
not in progress.
Keep the "DEFROSTING" key pressed for 4 s.
6.7 Turning on/off of room lights
Defrosting manual activation
manually (only if the parameter
u1 and/or parameter u11 is set
at 0)
To turn the room light on/off in manual mode, proceed as
follows:
1.
2.
Through the digital ports it is also possible to turn the room
light on/off from remote; see parameter u2.
If parameter u1 and/or parameter u11 are set to 2 (that is to
say, if the application managed by the K5 and/or K6 outputs is
the auxiliary output), pressing the "AUXILIARY" key for 2 s
shall make the "auxiliary 1" and/or "auxiliary 2" and the
auxiliary output LEDs turn on/off.
Make sure no procedures are in progress.
Press and release the "AUXILIARY" key: the "room
light" LED shall turn on/off.
6.8 Turning the demister heating
elements on/off manually (only
if the parameter u1 and/or
parameter u11 is set at 1)
To turn the demister heating elements on, proceed as follows:
1.
Check that the device is turned on and no
procedures are in progress.
Turning on/off of room lights in manual mode
Demister heating elements manual activation
page 27 of 92
EVCO S.p.A.
2.
The demister heating elements cannot be turned off in manual
mode (that is to say, before the time set with the parameter
u6 has expired).
Keep the "AUXILIARY" key pressed for 2 s: the
"AUX1" and/or "AUX2" LEDs shall light up and the
heating elements be turned turned on, both for
the length of time set with the parameter u6.
6.9 Turning on/off of the auxiliary
output manually (only if the
parameter u1 and/or
parameter u11 is set at 2)
To turn the auxiliary output on/off in manual mode, proceed
as follows:
1.
2.
Through the digital ports it is also possible to turn the auxiliary
output on/off from remote; see parameter u2.
If the auxiliary output has been turned on manually, it shall be
possible to turn it off only in the same mode (similarly, if it
was turned on from renote, it shall be possible to turn it off
only from remote); see also parameter u2.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Keep the "AUXILIARY" key pressed for 2 s: the
"AUX1" and/or "AUX2" LEDs shall turn on/off.
6.10 Displaying some instant values
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Turning on/off of the auxiliary output manually
joined to the electronic
expansion valve (only in
models EVB1246 and EVB1256)
To display some instant values joined to the electronic
expansion valve, proceed as follows:
1.
2.
3.
select a label.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the key “UP” or “DOWN” to
Access the procedure to display some instant values joined to the
electronic expansion valve
page 28 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
The following table shows the correspondence between the
labels and the magnitudes displayed.
LABEL MAGNITUDE
SH instant superheating
POS percentage (required) valve open
POr percentage (instant) valve open
4.
To exit the procedure:
5.
6.
Alternatively:
7.
Press and release the key “SET”.
Press and release the key “SET” or do not operate
for 60 sec.
Press and release the “UP” or “DOWN” key until
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Press and release the “ON/STAND-BY” key.
6.11 Keyboard locking/unlocking
To lock the keyboard proceed as follows:
1.
2.
If the keyboard is locked, the following are not permitted:
-
-
-
-
-
-
-
-
-
-
Check that the device is turned on and no
procedures are in progress.
Keep the "DOWN" and "ON/STAND-BY" keys
pressed for 1 s: the word "Loc" shall be displayed
on screen for 1 s.
device switch-on/off in manual mode
display of a magnitude recorded by an analogue
input (with the procedure described in paragraph
6.4 “Displaying the magnitude
detected by an analogue input”)
activation/deactivation of “rapid cooling” function
manual activation of defrosting
manual switch on/off of the auxiliary output
activation of the low or high relative humidity
percentage operation mode to learn how it works
see information regarding the HACCP alarms
cancellation of HACCP alarm list
display of compressor operation hours
cancellation of compressor operation hours
Displaying some instant values joined to the electronic expansion valve
Keyboard locking
page 29 of 92
EVCO S.p.A.
-
The operations cause the display of the label “Loc” for 1 s.
To unlock the keyboard:
3.
set the working set point (with the procedure
described in paragraph “Setting the working set
point”).
Hold the “DOWN” key and the “ON/STAND-BY” key
for 1 s: the display will show the message “UnL
for 1 s.
6.12 Silencing the buzzer
To silence the buzzer, proceed as follows:
1.
2.
If the parameter u1 and/or the parameter u11 is set at 3 (i.e.
the utility managed by the digital output K5 and/or K6 is the
alarm output) and parameter u4 is set at 1, pressing the key
will also cause the deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be activated.
Make sure no procedures are in progress.
Press a key (the first pressing of the key will not
cause the effect associated with that key).
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Silencing the buzzer
page 30 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
7 OPERATION WITH LOW OR
HIGH RELATIVE HUMIDITY
PERCENTAGES (ONLY IF THE F0
PARAMETER IS SET TO 5)
7.1 Preliminary notes
During operation with a low relative humidity percentage, the
evaporator fan shall be turned on if the compressor is on, and
shall turn on cyclically if the compressor is off (the F4
parameter determines the duration of the off phase of the fan
and the F5 parameter determines the on phase).
During operation with a high relative humidity percentage, the
evaporator fan is always on.
7.2 Manual activation of the low
and high relative humidity
percentages operating mode
To activate the the low or high relative humidity percentages
operating mode manually, proceed as follows:
1.
2.
To restore the normal display before time:
3.
It is also possible to activate the low or high relative humidity
percentage operation mode with the F6 parameter.
If the F0 parameter is not set to 5, pressing the keys shall
make the message "- - -" appear on display for 1 s.
Ensure that the device is on, the keypad is not
locked and that no procedure is in progress.
Keep the "SET" and "UP" keys pressed for
4 s: the letters "rhL" (operation with low relative
humidity percentage) or "rhH" (operation with
high relative humidity percentage) shall be
displayed on screen for 10 s.
Press any key.
7.3 Learning the current operating
Manual activation of the low and high relative humidity percentages
operating mode
mode
To learn which operating mode is in progress proceed as
follows:
1.
2.
Check that the device is turned on and no
procedures are in progress.
Press and release the "SET" and "UP" keys: the
letters "rhL" (operation with low relative humidity
percentage) or "rhH" (operation with high relative
humidity percentage) shall be displayed on screen
for 10 s.
page 31 of 92
Learning the current operating mode
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
8 “ENERGY SAVING” FUNCTION
8.1 Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
room temperature has reached the work set point) the
“energy saving” function is activated (until the input is
activated again).
During the “energy saving” function, the work set point is
increased by the temperature established with parameter r4
and the evaporator fan is turned on cyclically, provided that
the F0 parameter is set to 1, 2, 3 or 4 (parameter F13
establishes the duration of fan switch off and parameter F14
that of switch on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).
9 “CPT” FUNCTION (CALCULAT-
ED PRODUCT TEMPERATURE)
9.1 Preliminary notes
If parameter P4 is set at 4, the temperature associated to the
regulation will mainly depend on the temperature detected by
the inlet air probe and that detected by the air outlet probe,
herein called CPT temperature (Calculated Product
Temperature); the room temperature probe shall operate as
an air inlet temperature probe and the auxiliary temperature
probe as an air outlet temperature probe.
The formula for the calculation of the CPT temperature is:
CPT temperature = {[(value established with parameter P7) x
(temperature detected by the inlet air probe)] : 100} +
{[(100 - value established with parameter P7) x (temperature
detected by the outlet air probe)] : 100}.
10 “HACCP” FUNCTION
10.1 Preliminary notes
The device can memorise the following HACCP alarms:
-
-
-
-
The device can memorise up to 9 alarms, after which the
oldest alarm is overwritten.
The device supplies the following information for every alarm:
-
-
-
The following table shows the correspondence between the
alarm codes and the relevant critical values.
CODE CRITICAL VALUE
Models without clock update the information regarding the
alarms provided the critical value of the new alarm is more
critical than that stored or provided the information has
already been displayed.
If the device is switched off, no alarms will be stored.
The “HACCP” LED provides information regarding the storage
status of the alarms; see paragraph “Signals”.
minimum temperature alarm (code “AL”)
maximum temperature alarm (code “AH”)
door micro switch input alarm (code “id”)
power supply cut-off alarm (code “PF”; only in the
models with clock).
the critical value
the date and time at which the alarm occurs (only
in the models with clock)
the duration of the alarm (from 1 min to 99 hours
and 59 min, partial if the alarm is in progress).
AL
AH
PF
the minimum room temperature or the minimum
CPT temperature during the alarm
the maximum room temperature or the
maximum CPT temperature during the alarm
the maximum room temperature or maximum
id
CPT temperature during any alarm of this type;
see also parameter i4
the room temperature or the CPT temperature
when power supply is restored; see also
parameters A10 and A12
page 32 of 92
EVCO S.p.A.
10.2 Display of HACCP alarm
information
To begin the procedure:
1.
2.
3.
4.
If the device does not have any alarms stored, the label “LS
will not be displayed.
To select an alarm:
5.
To see information regarding the alarm:
6.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the "UP" or "DOWN" key to
select “LS”.
Press and release the “SET” key:
4.1
4.2
Press and release the “UP” key or the “DOWN”
key.
Press and release the “SET” key: the HACCP LED
will stop flashing and remain on permanently and
the display will show, for example, the following
information in succession:
in the models without a clock the
display will show one of the codes
included in the table in paragraph
“Preliminary notes”
in the models with a clock the display
will show one of the codes included in
the table in paragraph “Preliminary
notes” followed by a number; the
higher the number, the less current
the alarm.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Access the procedure to display information on the HACCP alarms
Selection of information on the HACCP alarms
INFORM. MEANING
8.0 the critical value is 8.0 °C/8 °F
the display is about to show the date and time
StA
y14 the alarm occurred in 2014 (continue...)
n03
d26
h16 the alarm occurred at 16:00 (continue...)
n30 the alarm occurred at 16:30
at which the alarm occurs (only in the models
with clock)
the alarm occurred in the month of March
(continue...)
the alarm occurred on 26 March 2014
(continue...)
Display of information on the HACCP alarms
page 33 of 92
EVCO S.p.A.
the displays each piece of information for 1 s.
To exit the information sequence:
7.
To exit the procedure:
8.
9.
Alternatively:
10.
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (continue...)
n15
code the alarm selected
the alarm lasted 1 hour and 15 min
Press and release the “ON/STAND-BY”: the display
will show the alarm selected.
Exit the information sequence.
Press and release the “UP” or “DOWN” key until
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Press and release the “ON/STAND-BY” key.
10.3 Cancelling the HACCP alarm list
To cancel the HACCP alarm list proceed as follows:
1.
2.
3.
4.
5.
6.
If the device does not have any alarms stored, the label “rLS
will not be displayed.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the "UP" or "DOWN" key to
select “rLS”.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 s to set “149”.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “- - -” for 4
sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Access the procedure to cancel information on the HACCP alarms
Cancelling information on the HACCP alarms
page 34 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
11 COMPRESSOR OPERATING
HOURS COUNT
11.1 Preliminary notes
The device can memorise up to 999 comp. operating hours.
The parameter C10 establishes the number of operating hours
is higher than the limit at which the need for maintenance is
signalled.
11.2 Display of Compressor
Operation Hours
To display the compressor operation hours, proceed as
follows:
1.
2.
3.
The following table shows the correspondence between the
labels and the relevant meaning.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the "UP" or "DOWN" key to
select a label.
Access the procedure to display the compressor operation hours
LABEL MEANING
CH1 Compressor operation Hours
CH2 Compressor 2 operation Hours
4.
To exit the procedure:
5.
6.
Alternatively:
7.
If the compressor 2 is not present (or if the u1 and/or u11
parameter is not set to 7), the "CH2" label shall not be
displayed.
Press and release the “SET” key.
Press and release the “SET” key or do not operate
for 60 sec.
Press and release the “UP” or “DOWN” key until
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Press and release the “ON/STAND-BY” key.
Display the compressor operation hours
page 35 of 92
EVCO S.p.A.
11.3 Cancelling the compressor
operation hours
To cancel the compressor operation hours, proceed as follows:
1.
2.
3.
4.
5.
6.
If the device does not have any alarms stored, the label “rCH
will not be displayed.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the "UP" or "DOWN" key to
select “rCH”.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 s to set “149”.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “- - -” for 4
sec and the “alarm” LED switches off, after which
the device will exit the procedure.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Access the procedure to cancel the compressor operation hours
Cancelling the compressor operation hours
page 36 of 92
EVCO S.p.A.
12 SETTINGS
12.1 Setting the date, time and day
of the week (only in the models
with clock)
The date can be set in the day-month-year format; the time in
the hours-minutes format (24 h).
To access the procedure:
1.
2.
3.
To set the year:
4.
5.
To set the month:
6.
7.
To set the day:
8.
9.
To set the hour:
10.
11.
To set the minute:
12.
13.
To set the day of the week:
14.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
Press and release the "UP" or "DOWN" key to
select “rtc”.
Press and release the “SET” key: the display will
show “y” followed by the last two numbers of the
year and the “clock” LED light shall flash.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key when setting the
year: the display will show “n” followed by the
number of the month.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key when setting the
month: the display will show “d” followed by the
number of the day.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key when setting the
day: the display will show “h” followed by the
number of the hour.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key when setting the
hour: the display will show “n” followed by the
number of the minute.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key when setting the
minute: the display will show the first label
available.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Access the procedure for setting the date, time and day of the week
Setting the year
Setting the day
Setting the minute
page 37 of 92
EVCO S.p.A.
15.
16.
To exit the procedure before the operation is complete:
17.
Press and release the key or the key within 15
sec to set:
-
-
-
-
-
-
-
Press and release the “SET”: the "clock" LED shall
turn off, and then the device shall exit the
procedure.
Do not operate for 60 sec (any changes will be
saved).
Mon” (Monday)
tuE” (Tuesday)
UEd” (Wednesday)
thu” (Thursday)
Fri” (Friday)
SAt” (Saturday)
Sun” (Sunday).
12.2 Setting the working set point
To set the working set point, proceed as follows:
1.
2.
3.
4.
To exit the procedure before the operation is complete:
5.
The working set point can also be set via parameter SP.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Press and release the “SET” key: the “compressor”
LED will flash.
Press and release the “UP” or “DOWN” key within
15 sec; see also parameters r1, r2 and r3.
Press and release the “SET” key or do not operate
for 15 sec: the “compressor” LED will switch off
after which, the device will exit the procedure.
Do not operate for 15 sec (any changes will be
saved).
12.3 Setting the configuration
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Setting the working set point
parameters
To access the procedure:
1.
2.
3.
4.
5.
6.
Make sure no procedures are in progress.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “PA”.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 s to set “-19”.
Press and release the “SET” key and do not
operate for 15 s.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “SP”.
Access the procedure to set the configuration parameters
page 38 of 92
EVCO S.p.A.
To select a parameter:
7.
To set a parameter:
8.
9.
10.
To exit the procedure:
11.
After setting the parameters, suspend power supply flow to
the device.
Press and release the “UP” key or the “DOWN”
key.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key and do not
operate for 15 s.
Press and release the “UP” and “DOWN” key for 4
s or do not operate for 60 s (any changes will be
saved).
12.4 Restoring the Manufacturer’s
settings
To restore the manufacturer's settings, proceed as follows:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
To exit the procedure in advance:
11.
Make sure that the manufacturer’s settings are appropriate
(see paragraph 12.5 “List of configuration parameters”.
Make sure no procedures are in progress.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “PA”.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 s to set “149”.
Press and release the “SET” key and do not
operate for 15 s.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “dEF”.
Press and release the “SET” key.
Press and release the “UP” or “DOWN” key within
15 s to set “1”.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “dEF” for 4
sec, after which the device will exit the procedure
Cut the device power supply off.
Hold the “UP” and “DOWN” key for 4 s during the
procedure (i.e. before setting “1”: Restore will not
be performed).
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Access the procedure to set the configuration parameters
Setting a parameter
Restoring the Manufacturer’s Settings
page 39 of 92
EVCO S.p.A.
12.5 List of configuration parameters
The following table shows the meaning of the configuration parameters of the devices.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
SP r1 r2 °C/°F (1) -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 Working set-point; see also r0
PARAM. MIN. MAX. M.U.
CA1 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
CA2 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 evaporator temperature offset
CA3 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 auxiliary temperature offset (see P4)
CA4 -25.0 25.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0.0 0.0 evaporation temperature offset
WORKING SETPOINT
MEASUREMENT INPUTS
if P4 = 0, 1, 2 o 3, room temperature offset
if P4 = 4, inlet air temperature offset
CA5 -25.0 25.0
P0 0 2 - - - - 1 1 1 1 1 1 1 1
points/10
(4)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
page 40 of 92
not
avail.
0 0 vapour pressure offset
temperature probe type
0 = PTC
1 = NTC
2 = Pt 1000
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
P1 0 1 - - - - 1 1 1 1 1 1 1 1
P2 0 1 - - - - 0 0 0 0 0 0 0 0
P3 0 2 - - - - 1 1 1 1 1 1 1 1
P4 0 4 - - - - 3 3 3 3 3 3 3 3
degree Celsius decimal point
1 = YES
temperature unit of measurement (2)
0 = degree Celsius
1 = degree Fahrenheit
evaporator temperature probe function
0 = probe absent
1 = defrosting probe and probe for evaporator fan
thermostating
2 = probe for evaporator fan thermostating
magnitude recorded by the auxiliary temperature probe
0 = probe absent
1 = condenser temperature
2 = critical temperature
3 = evaporator 2 temperature
4 = outlet air temperature; in this case the
temperature associated with the setting shall be
the CPT (Calculated Product Temperature) one;
see also P7
P5 0 4 - - - - 0 0 0 0 0 0 0 0
page 41 of 92
magnitude displayed during normal operation
0 = if P4 = 0, 1, 2 or 3, room temperature
if P4 = 4, CPT temperature
1 = working set-point
2 = evaporator temperature
3 = temperature recorded by the auxiliary probe (see
P4)
4 = inlet air temperature (only if P4 = 4 )
EVCO S.p.A.
P7 0 100 % 50 50 50 50 50 50 50 50
P8 0 250 s/10 5 5 5 5 5 5 5 5 delay displaying temperature variation
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
percentage of the temperature detected by the inlet air
for the calculation of the CPT temperature (only ifP4 = 4)
(3)
P9 -99.9 99.9
P10 -99.9 99.9
PARAM. MIN. MAX. M.U.
r0 0,1 (5) 15.0 °C/°F (1) 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
r1 -99.0 r2 °C/°F (1) -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 minimum working set-point
r2 r1 99.0 °C/°F (1) 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 maximum working set-point
bar g /
PSI g
bar g /
PSI g
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
-0.5 -0.5 pressure transducer minimum setting
7.0 7.0 pressure transducer maximum setting
MAIN REGULATOR
if u1 and/or u11 7, working set-point differential; see
also r12 (6)
if u1 and/or u11 = 7, proportional band; see also r12 (7)
r3 0 1 - - - - 0 0 0 0 0 0 0 0
page 42 of 92
locking of working set-point setting (using the procedure
described in paragraph”Setting the working set point”)
1 = YES
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
r4 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
r5 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
r6 0 240 min 30 30 30 30 30 30 30 30 duration of “rapid cooling” function; see also r5
r12 0 1 - - - - 1 1 1 1 1 1 1 1
PARAM. MIN. MAX. M.U.
h01 3.0 25.0 °C/°F (1)
h02 10.0 40.0 °C/°F (1)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
6.0 6.0 superheating
15.0 15.0
working set point increase during the “energy saving"
function; see also i5, i10, i15, H01... H14
working set-point decrease during the “rapid cooling”
function; see also r6
type of r0
0 = asymmetric
1 = symmetric
ELECTRONIC EXPANSION VALVE (45)
evaporating temperature above which the high
superheating alarm is activated (code “HSH”) (11)
h03 -70.0 40.0 °C/°F (1)
h04 1.0 99.9 °C/°F (1)
h05 0 999 s
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
page 43 of 92
non
disp.
not
avail.
not
avail.
evaporating temperature below which the low pressure
-70.0 -70.0
40.0 40.0 PID action proportional band
120 120 PID action integral time
modality is activated (the valve is completely open; code
LOP”) (11)
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
h06 0 999 s
h07 1 250 s
h08 -1 100 %
h09 0 100 %
h10 0 45.0
h11 0 250 min
h12 0 1 - - - -
bar g /
PSI g (4)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
non
disp.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
non
disp.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
non
disp.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
non
disp.
30 30 PID action derivative time
5 5 starting delay
-1 -1
0 0
1.0 1.0
3 3
0 0
percentage valve open during the manual operation
-1 = the superheating will be enabled
percentage valve open during the hot gas defrost (during
the pre-dripping and the dripping the valve will be closed,
during the evaporator fan delay the valve opening will be
function of the algorithm of regulation)
evaporating pressure below which the compressor is
switched off during the pump down
high superheating alarm delay (code “HSH”) and
operative low pressure alarm delay (code “LOP”)
enabling the low pressure alarm (code “LP”)
1 = YES
h13 -0.5 45.0
h14 0 250 min
bar g /
PSI g (4)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
page 44 of 92
not
avail.
not
avail.
0.0 0.0
3 3 low pressure alarm delay (code “LP”)
evaporating pressure below which the lower pressure
alarm is activated (code “LP”) (44)
EVCO S.p.A.
h15 0 7 - - - -
h16 0 4 - - - -
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0 0
1 1
kind of refrigerat gas
0 = R-22
1 = R-404A
2 = R-507A
3 = R-744
4 = R-290
5 = R-717
6 = R1270
7 = R-407F
kind of electronic expansion valve
0 = generic valve
1 = Sanhua DPF
2 = Danfoss ETS 6
3 = Sporlan SER U
4 = Sporlan ESX
h17 0 100 %
h18 0 490
h19 0 250
h20 25 999 steps/s
steps x
10 (43)
steps
(43)
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
page 45 of 92
not
avail.
not
avail.
not
avail.
not
avail.
percentage valve open during the evaporating pressure
0 0
100 100
30 30
100 100 step frequency of the generic electronic expansion valve
probe error (code “Pr4”) and/or during the evaporating
temperature probe error (code “Pr5”)
maximum number of operative steps of the generic
electronic expansion valve
maximum number of overdriving steps of the generic
electronic expansion valve
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
C0 0 240 min 0 0 0 0 0 0 0 0
C1 0 240 min 5 5 5 5 5 5 5 5
C2 0 240 min 3 3 3 3 3 3 3 3 minimum compressor switch-off duration (9)
C3 0 240 s 0 0 0 0 0 0 0 0 minimum duration of compressor switch on time
C4 0 240 min 10 10 10 10 10 10 10 10
C5 0 240 min 10 10 10 10 10 10 10 10
COMPRESSOR PROTECTION SYSTEM
delay in switching on of compressor after the device
switches on (8)
minimum time between two consecutive compressor
start-ups; also delay in compressor start-up after
conclusion of room temperature/inlet air probe error
(code “Pr1”) (9) (10)
duration of compressor switch off time during a room
temperature/inlet air probe error (code “Pr1”); see also
C5
duration of compressor switch on time during a room
temperature/inlet air probe error (code “Pr1”); see also
C6
C6 0.0 199 °C/°F (1) 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0
C7 0.0 199 °C/°F (1) 90.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0
page 46 of 92
condenser temperature is higher than that at which the
condenser overheating alarm is activated (code “COH”)
(11)
condenser temperature above which the blocked
compressor alarm is activated (code “CSd”)
EVCO S.p.A.
C8 0 15 min 1 1 1 1 1 1 1 1 blocked compressor alarm delay (code “CSd”) (12)
C10 0 999 hx10 0 0 0 0 0 0 0 0
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
number of operating hours is higher than the limit at
which the need for maintenance is signalled
0 = function absent
C11 0 240 s 3 3 3 3 3 3 3 3
C12 0 10 - - - - 2 2 2 2 2 2 2 2
C13 0 10 - - - - 1 1 1 1 1 1 1 1
minimum time interval between the switching on of two
different compressors (only if u1 and/or u11 = 7)
incidence of the number of compressor operation hours
on the choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C13 (only if u1 and/or u11 = 7)
incidence of the switch-ons of the compressor on the
choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C12 (only if u1 and/or u11 = 7)
page 47 of 92
EVCO S.p.A.
C14 0 2 - - - - 0 0 0 0 0 0 2 2
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
type of pump down
0 = TIMED - the compressor and the pump down
valve (or the electronic expansion valve if
present) shall be switched on at the same time
due to the setting; the pump down valve (or the
electronic expansion valve if present) shall be
turned off due to the setting and the compressor
after the expiration of the u3 time interval from
the valve switch-off (only if u1 and/or u11 = 10)
1 = FROM DIGITAL INPUT - the compressor and the
pump down valve (or the electronic expansion
valve if present) shall be switched on at the same
time due to the setting; the pump down valve
shall be turned off due to the setting and the
compressor afterwards and as a consequence of
the activation of the multifunction or multifunction
2 input (only if i5 or i15 = 6); see also u3 (only if
u1 and/or u11 = 10)
2 = FOR EVAPORATING PRESSURE - (ONLY
AVAILABLE IN MODELS EVB1246 and EVB1256) -
the electronic expansion valve (it will also work as
pump down valve) will be switced-on due to the
setting and the compressor on afterwards; the
electronic expansion valve will be switched off due
to the setting and the compressor on afterwards
and as a consequence of the attainment by the
evaporating pressure of the value set with
parameter h10; see also u3
page 48 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
d0 0 99 h 8 8 8 8 8 8 8 8
d1 0 2 - - - - 0 0 0 0 0 0 0 0
DEFROSTING
if d8 = 0, 1 or 2, defrosting interval (13)
0 = interval defrosting will never be activated
d8 = 3, maximum defrost interval
type of defrosting
0 = ELECTRIC - during defrosting the compressor will
remain off and the defrosting output will be
activated; evaporator fan activity will depend on
parameter F2
1 = BY HOT GAS - during defrosting the compressor
will be switched on and the defrosting output will
be activated; evaporator fan activity will depend
on parameter F2
2 = VIA STOPPING OF COMPRESSOR - during
defrosting the compressor will remain switched off
and the defrosting output will remain deactivated;
evaporator fan activity will depend on parameter
F2
d2 -99 99.0
d3 0 99 min 30 30 30 30 30 30 30 30
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
page 49 of 92
temperature at end of defrosting (only if P3 = 1); see also
d3
if P3 = 0 o 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0 = defrosting will not be activated
EVCO S.p.A.
d4 0 1 - - - - 0 0 0 0 0 0 0 0
d5 0 99 min 0 0 0 0 0 0 0 0
d6 0 2 - - - - 1 1 1 1 1 1 1 1
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
defrosting when device is switched on (only if d8 = 0, 1, 2
or 3) (8)
1 = YES
if d4 = 0, minimum time between switching on of device
and activation of defrosting (8)
if d4 = 1, delay in activation of defrosting after device is
switched on (8)
temperature displayed during defrosting (only if P5 = 0)
0 = room temperature or CPT temperature
1 = if on activation of defrosting, the room
temperature or CPT temperature is below the
“work set point + t”, at maximum “ work set point
+ t”; if on activation of defrosting, the room
temperature or CPT temperature is above “work
set point + t”, at maximum the room temperature
or CPT temperature on activation of defrosting
(14) (15)
2 = indication “dEF” (16)
d7 0 15 min 2 2 2 2 2 2 2 2
page 50 of 92
during dripping the compressor will remain switched off
and the defrosting output will remain deactivated; if d16
= 0, evaporator fan activity will depend on parameter F2;
if d16 0, the evaporator fan will remain switched off)
EVCO S.p.A.
d8 0 4 - - - - 0 0 0 0 0 0 0 0
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
defrosting activation methods
0 = AT INTERVALS - defrosting will be activated once
the device has altogether been running for time
d0
1 = AT INTERVALS - FOR COMPRESSOR SWITCH-ON -
defrosting will be activated once the compressor
has altogether been switched on for time d0
2 = AT INTERVALS - FOR EVAPORATOR TEMPERATURE
- defrosting will be activated when the evaporator
temperature has remained below the temperature
d9 for a total time of d0 (17)
3 = ADAPTABLE - defrosting will be activated at
intervals, whose duration will each time depend
on the duration of compressor switch-ons and the
evaporator temperature; see also d18, d19, d20
and d22 (17)
4 = IN REAL TIME - defrosting will be activated at the
times established in parameters Hd1... Hd6 (not
visible in models EVB1204, EVB1206, EVB1226
and EVB1246)
d9 -99 99.0
d11 0 1 - - - - 0 0 0 0 0 0 0 0
°C/°F
(1)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
page 51 of 92
evaporator temperature is higher than that at which the
defrost interval counter is suspended (only if d8 = 2)
defrosting alarm switches off once maximum time limit
has been reached (code “dFd”; only if P3 = 1 and in
absence of an evaporator temperature probe (code “Pr2”)
1 = YES
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
d15 0 99 min 0 0 0 0 0 0 0 0
d16 0 99 min 0 0 0 0 0 0 0 0
d18 0 999 min 40 40 40 40 40 40 40 40
d19 0.0 40.0
°C/°F
(1)
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
minimum time that the compressor must be switched on
before defrosting can be activated (only if d1 = 1) (18)
predripping duration (during predripping the compressor
will remain switched off, the defrosting output will be
activated and the evaporator fan will remain switched off)
defrosting interval (only if d8 = 3; defrosting will be
activated when the compressor has been on totally, with
the evaporator temperature below that of d22, for time
d18)
0 = defrosting will never be activated due to the effect
of this condition
evaporator temperature above which the defrost is
activated (relative to the evaporator temperatures
average, or “evaporator temperatures average - d19”)
(only if d8 = 3)
d20 0 500 min 180 180 180 180 180 180 180 180
page 52 of 92
minimum consecutive time the compressor must be
switched on such as to provoke the defrost activation
0 = defrosting will never be activated due to the effect
of this condition
EVCO S.p.A.
d21 0 500 min 200 200 200 200 200 200 200 200
d22 0.0 10.0
d25 0 1 - - - - 0 0 0 0 0 0 0 0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
minimum consecutive time the compressor must be
switched on after the insturment switches on (on
condition that the difference “cell temperature - working
setpoint” is higher than 10 °C/20 °F) and after function
Overcooling is activated such as to provoke the defrost
activation
0 = the defrost will never be activated because the
compressor has been switched on
evaporator temperature above which the time d18 count
is paused (relating to the average of evaporator
temperatures, that is to say, "evaporator temperatures
average + d22”) (only if d8 = 3)
enabling of the outlet air temperature probe as defrosting
probe during the evaporator temperature probe error
(code “Pr2”; only if P4 = 4); see also d26 (19)
d26 0 99 h 6 6 6 6 6 6 6 6
page 53 of 92
defrosting interval for effect of enabling of outlet air
temperature probe like defrosting probe during evaporator
temperature probe error (code “Pr2”; only if P4 = 4), if
d25 = 1 (13)
0 = defrosting will never be activated due to the effect
of this condition
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
A0 0 1 - - - - 0 0 0 0 0 0 0 0
A1 -99.0 99.0
A2 0 2 - - - - 1 1 1 1 1 1 1 1
A4 -99.0 99.0
°C/°F
(1)
°C/°F
(1)
-10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
TEMPERATURE ALARMS
temperature associated with the minimum temperature
alarm (code “AL”)
0 = room temperature or CPT temperature
1 = evaporator temperature (20)
temperature below that at which the minimum
temperature alarm is activated (code “AL”); see also A0,
A2 and A11
type of minimum temperature alarm (code “AL”)
0 = alarm absent
1 = relative to working set-point (that is “working set-
point - A1”; consider A1 without sign)
2 = absolute (that is A1)
temperature higher than that at which the maximum
temperature alarm is activated (code “AH”); see also A5
and A11
A5 0 2 - - - - 1 1 1 1 1 1 1 1
A6 0 240 min 120 120 120 120 120 120 120 120
page 54 of 92
type of maximum temperature alarm (code “AH”)
0 = alarm absent
1 = relative to working set-point (that is “working set-
point + A4”; consider A1 without sign)
2 = absolute (that is A4)
delay in maximum temperature alarm (code “AH”) after
the device is switched on (8)
EVCO S.p.A.
A7 0 240 min 15 15 15 15 15 15 15 15 temperature alarm delay (code “AL” and code “AH”)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
A8 0 240 min 15 15 15 15 15 15 15 15
A9 0 240 min 15 15 15 15 15 15 15 15
A10 0 240 min 1
A11 0.1 (5) 15.0
A12 0 2 - - - -
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 differential of parameters A1 and A4
not
avail.
not
avail.
1
not
avail.
1
1
not
avail.
not
avail.
1
1
not
avail.
not
avail.
delay in maximum temperature alarm (code “AH”) from
the conclusion of evaporator fan standstill (21)
delay in maximum temperature alarm (code “AH”)
following the deactivation of the door micro switch input
(22)
duration of a power cut such to cause the power cut alarm
1
to be memorised (code “PF”)
type of power supply cut-off alarm signal (code “PF”)
0 = alarm will be signalled by the “HACCP” LED
1 = alarm will be signalled by the “PF” code, the
1
buzzer and the “HACCP” LED
2 = alarm will be signalled by the “PF” code, buzzer
(as long as cut-off duration exceeds time A10)
and by the “HACCP” LED
page 55 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
F0 0 5 - - - - 1 1 1 1 1 1 1 1
F1 -99.0 99.0
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
EVAPORATOR FAN AND CONDENSER FAN
evaporator fan activity during normal operation
0 = switched off
1 = switched on; see also F13, F14 and i10 (23)
2 = in parallel with the compressor; see also F9, F13,
F14 and i10 (24)
3 = depending on F1; see also F9, F13, F14 and i10
(25) (26)
4 = switched off if the compressor is switched off,
dependent on F1 if the compressor is switched on;
see also F9, F13, F14 and i10 (25) (27)
5 = depending on F6; see also F9
evaporator temperature above the limit at which the
evaporator fan is switched off (only if F0 = 3 o 4); see
also F8
F2 0 2 - - - - 0 0 0 0 0 0 0 0
page 56 of 92
evaporator fan activity during defrosting and dripping
0 = switched off
1 = switched on (setting parameter d7 to 0 is
recommended)
2 = depending on F0
EVCO S.p.A.
F3 0 15 min 0 0 0 0 0 0 0 0
F4 0 240 s 60 60 60 60 60 60 60 60
F5 0 240 s 10 10 10 10 10 10 10 10
F6 0 1 - - - - 0 0 0 0 0 0 0 0
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
maximum duration of evaporator fan deactivation; see
also F7 (during evaporator fan deactivation the
compressor can be switched on, the defrosting output will
remain deactivated and the evaporator fan will remain
switched off)
duration of evaporator fan deactivation during operation
in low relative humidity conditions with the compressor
switched off; see also F5 (only if F0 = 5)
duration of evaporator fan activation during operation in
low relative humidity conditions with the compressor
switched off; see also F4 (only if F0 = 5)
operation in low or high relative humidity conditions (only
if F0 = 5) (28)
0 = low relative humidity (during operation in low
relative humidity conditions the evaporator fan
shall function in parallel with the compressor; see
also F4 and F5)
1 = high relative humidity (during operation in high
relative humidity conditions the evaporator fan
shall be switched on)
F7 -99.0 99.0
°C/°F
(1)
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
page 57 of 92
evaporator temperature below which the evaporator fan is
restarted (in respect to the working set point, that is to
say “working set-point + F7”); see also F3
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
F8 0.1 (5) 15.0
F9 0 240 s 0 0 0 0 0 0 0 0
F11 0.0 99.0
F12 0 240 s 30 30 30 30 30 30 30 30
F13 0 240 sx10 30 30 30 30 30 30 30 30
F14 0 240 sx10 30 30 30 30 30 30 30 30
°C/°F
(1)
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 F1 differential
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
delay in the switching off of evaporator fan following the
switching off of the compressor (only if F0 = 2, 4 and 5)
temperature of the condenser above which the condenser
fan is switched on (“F11 + 2,0 °C/4 °F, only if u1 and/or
u11 = 6) (29) (30)
delay in the switching off of condenser fan following the
switching off of the compressor (only if u1 and/or u11 =
6)
duration of evaporator fan switch off during “energy
saving” function, see also F14, i10, H01... H14 (only if F0
= 1, 2, 3 or 4)
duration of evaporator fan switch on during “energy
saving” function, see also F13, i10, H01... H14 (only if F0
= 1, 2, 3 or 4)
page 58 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
i0 0 5 - - - - 3 3 3 3 3 3 3 3
DIGITAL INPUTS
effect caused by the activation of the door micro input;
see also i4 (0 = no effect)
1 = SWITCH-OFF OF THE COMPRESSOR AND
EVAPORATOR FAN - the compressor and the
evaporator fan will be switched off (at maximum
for time i3 or until the input is deactivated) (31)
2 = SWITCH-OFF OF THE EVAPORATOR FAN - the
evaporator fan will be switched off (at maximum
for time i3 or until the input is deactivated)
3 = SWITCH ON OF ROOM LIGHT - the room light
shall be switched on (in the EVB1204 and
EVB1214 models only if u1 = 0; the light shall be
switched off after 10 s from input deactivation)
4 = SWITCH-OFF OF THE COMPRESSOR AND
EVAPORATOR FAN AND SWITCH ON OF ROOM
LIGHT - the compressor and the evaporator fan
will be switched off (at maximum for time i3 or
until the input is deactivated) and the room light
shall be switched on (in the EVB1204 and
EVB1214 models only if
u1 = 0; the light shall be switched off after 10 s
from input deactivation) (31)
5 = SWITCH-OFF OF THE EVAPORATOR FAN AND
SWITCH ON OF ROOM LIGHT - the evaporator fan
will be switched off (at maximum for time i3 or
until the input is deactivated) and the room light
shall be switched on (in the EVB1204 and
EVB1214 models only if
u1 = 0; the light shall be switched off after 10 s
from input deactivation)
page 59 of 92
EVCO S.p.A.
i1 0 1 - - - - 0 0 0 0 0 0 0 0
i2 -1 120 min 30 30 30 30 30 30 30 30
i3 -1 120 min 15 15 15 15 15 15 15 15
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
type of door micro switch input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
delay in signalling of door micro switch input alarm (code
id”)
-1 = the alarm will not be signalled
maximum duration of the effect caused by the activation
of the door micro switch input on the compressor and the
evaporator
i4 0 1 - - - - 0 0 0 0 0 0 0 0
page 60 of 92
storage of door micro switch input alarm (code “id”) (32)
1 = YES
EVCO S.p.A.
i5 0 9 - - - - 7 7 7 7 7 7 7 7
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
effect caused buy the activation of the multifunction input
(33)
0 = no effect
1 = ACTIVATION OF “ENERGY SAVING” FUNCTION -
the “energy saving” function will be activated (just
with effect on the compressor, until the input is
deactivated), provided the "rapid cooling" is not
running; see also r4
2 = ACTIVATION OF MULTIFUNCTION INPUT ALARM -
once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated)
3 = ACTIVATION OF THE MAXIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the condenser fan will be switched on (only if
u1 and/or u11 = 6), the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated): when the input
has been activated the number of times
established with parameter i8 the regulators will
be switched off, the condenser fan will be
switched on (only if u1 and/or u11 = 6), the
display will show the flashing code “iSd” and the
buzzer will be activated (until the input is
deactivated and the device is switched off and re-
started or until the power supply is interrupted);
see also i7 and i9
4 = SWITCHING ON THE AUXILIARY OUTPUT - the
auxiliary output will be switched on (only if u1
and/or u11 = 2, until the input is deactivated)
5 = SWITCHING OFF THE DEVICE - the device will be
switched off (until the input is deactivated)
page 61 of 92
EVCO S.p.A.
i5 0 9 - - - - 7 7 7 7 7 7 7 7
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
6 = ACTIVATION OF THE MINIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the display will show the flashing code “LP
and the buzzer will be activated (until the input is
deactivated); if u1 and/or u11 = 10, the
compressor will be switched off after the pump
down valve has switched off (also look at C14 and
i17)
7 = COMPRESSOR THERMAL PROTECTION - the
compressor will be switched off, the display will
show the flashing code “C1t” and the buzzer will
be activated (until the input is deactivated)
8 = COMPRESSOR 2 THERMAL PROTECTION - the
compressor 2 will be switched off (only if u1
and/or u11 = 7), the display will show the flashing
code “C2t” and the buzzer will be activated (until
the input is deactivated)
9 = MAN IN COLD ROOM ALARM ACTIVATION - the
man in cold room output shall be turned on (only
if u1 and/or u11 = 12), the display will show the
flashing code “MiC” and the buzzer will be
activated (until the input is deactivated)
i6 0 1 - - - - 0 0 0 0 0 0 0 0
i7 0 120 min 0 0 0 0 0 0 0 0
page 62 of 92
type of multifunction input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
if i5 and/or i15 = 2, multifunction input alarm delay (code
iA”)
if i5 and/or i15 = 3, delay in compressor switching on
after the deactivation of the multifunction input (34)
EVCO S.p.A.
i8 0 15 - - - - 0 0 0 0 0 0 0 0
i9 1 999 min 240 240 240 240 240 240 240 240
i10 0 999 min 0 0 0 0 0 0 0 0
i13 0 240 - - - - 180 180 180 180 180 180 180 180
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
number of multifunction input alarms (code “iA”) such to
cause a pressure switch alarm (code “iSd”) (only if i5
and/or i15 = 3)
0 = function disabled
time that must pass in absence of multifunction input
alarms (code “iA”) so that the alarm counter is reset (only
i5 and/or i15 = 3)
time that must pass in absence of door micro switch input
activations (after the room temperature or COT
temperature has reached the working set-point) for the
“energy saving” function to be activated (this impacts the
evaporator fan only if F0 = 1, 2, 3 or 4); see also r4, HE2
and H01... H14
0 = the function will never be activated due to the
effect of this condition
number of door switch input activations such as to
provoke the defrost activation
0 = defrosting will never be activated due to the effect
of this condition
i14 0 240 - - - - 32 32 32 32 32 32 32 32
page 63 of 92
minimum duration of the door switch input activation such
as to provoke the defrost activation
0 = defrosting will never be activated due to the effect
of this condition
EVCO S.p.A.
i15 0 9 - - - - 9 9 9 9 9 9 9 9
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
effect caused buy the activation of the multifunction input
2 (33)
0 = no effect
1 = ACTIVATION OF “ENERGY SAVING” FUNCTION -
the “energy saving” function will be activated (just
with effect on the compressor, until the input is
deactivated), provided the "rapid cooling" function
is not running; see also r4
2 = ACTIVATION OF MULTIFUNCTION INPUT ALARM -
once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated)
3 = ACTIVATION OF THE MAXIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the condenser fan will be switched on(only if
u1 and/or u11 = 6), the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated): when the input
has been activated the number of times
established with parameter i8 the regulators will
be switched off, the condenser fan will be
switched on (only if u1 and/or u11 = 6), the
display will show the flashing code “iSd” and the
buzzer will be activated (until the input is
deactivated and the device is switched off and re-
started or until the power supply is interrupted);
see also i7 and i9
4 = SWITCHING ON THE AUXILIARY OUTPUT - the
auxiliary output will be switched on (only if u1
and/or u11 = 2, until the input is deactivated)
5 = SWITCHING OFF THE DEVICE - the device will be
switched off (until the input is deactivated)
page 64 of 92
EVCO S.p.A.
i15 0 9 - - - - 9 9 9 9 9 9 9 9
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
6 = ACTIVATION OF THE MINIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the display will show the flashing code “LP
and the buzzer will be activated (until the input is
deactivated); if u1 and/or u11 = 10, the
compressor will be switched off after the switching
off of the pump down valve (also look at C14 and
i17)
7 = COMPRESSOR THERMAL PROTECTION - the
compressor will be switched off, the display will
show the flashing code “C1t” and the buzzer will
be activated (until the input is deactivated)
8 = COMPRESSOR 2 THERMAL PROTECTION - the
compressor will 2 be switched off (only if u1
and/or
u11 = 7), the display will show the flashing code
C2t” and the buzzer will be activated (until the
input is deactivated)
9 = MAN IN COLD ROOM ALARM ACTIVATION - the
man in cold room output shall be turned on (only
if u1 and/or u11 = 12), the display will show the
flashing code “MiC” and the buzzer will be
activated (until the input is deactivated)
i16 0 1 - - - - 0 0 0 0 0 0 0 0
i17 0 240 s 30 30 30 30 30 30 30 30
page 65 of 92
type of multifunction 2 input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
minimum pressure switch alarm delay after the
compressor switches on (code “LP”)
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
u1 0 12 - - - - 0 0
DIGITAL OUTPUTS
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
operation controlled by digital output K4 (35) (36)
0 = ROOM LIGHT - in this case the “AUXILIARY” key
and parameters i0 and u2 will be activated
1 = DEMISTER HEATING ELEMENTS - in this case the
“AUXILIARY” key and parameter u6 will be
activated
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
3 = ALARM OUTPUTS - in this case parameter u4 will
be activated
4 = DOOR HEATING ELEMENTS - in this case
parameter u5 will be activated
5 = HEATING ELEMENTS FOR NEUTRAL AREA
OPERATION - in this case parameter u7 will be
activated
6 = CONDENSER FAN - in this case parameters P4,
F11 and F12 will be activated
7 = COMPRESSOR 2 - in this case, parameters r0,
r12, C11, C12 and C13 (37) will assume
significance of
8 = DEFROSTING 2 - in this case parameters P4 and d
(38) will assume significance
9 = EVAPORATOR FAN 2 - in this case parameters P4
and F (39) will assume significance of
10 = PUMP DOWN VALVE - in this case parameters
C14 and u3 will assume significance of
11 = ON/STAND-BY - in this case “ON/STAND-BY” key
will assume significance (42)
12 = MAN IN COLD ROOM - in this case parameters i5
and i15 will assume significance of
page 66 of 92
EVCO S.p.A.
u1 0 12 - - - -
not
avail.
not
avail.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
6 6 6 6 6 6
application managed by the K5 (K3 in the models with
direct load connection) digital output (35) (36)
0 = reserved
1 = DEMISTER HEATING ELEMENTS - in this case the
“AUXILIARY” key and parameter u6 will be
activated
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
3 = ALARM OUTPUTS - in this case parameter u4 will
be activated
4 = DOOR HEATING ELEMENTS - in this case
parameter u5 will be activated
5 = HEATING ELEMENTS FOR NEUTRAL AREA
OPERATION - in this case parameter u7 will be
activated
6 = CONDENSER FAN - in this case parameters P4,
F11 and F12 will be activated
7 = COMPRESSOR 2 - in this case, parameters r0,
r12, C11, C12 and C13 (37) will assume
significance of
8 = DEFROSTING 2 - in this case parameters P4 and d
(38) will assume significance
9 = EVAPORATOR FAN 2 - in this case parameters P4
and F (39) will assume significance of
10 = PUMP DOWN VALVE - in this case, parameters
C14 and u3 will assume significance of
(RESERVED in models EVB1246 and EVB1256)
11 = ON/STAND-BY - in this case “ON/STAND-BY” key
will assume significance (42)
12 = MAN IN COLD ROOM - in this case, parameters i5
and i15 will assume significance of
page 67 of 92
EVCO S.p.A.
u2 0 1 - - - - 0 0 0 0 0 0 0 0
u3 0 240 s 10 10 10 10 10 10 10 10
u4 0 1 - - - - 1 1 1 1 1 1 1 1
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
activation of room light switch on/off (in models EVB1204
and EVB1214 only if u1 = 0) or of the auxiliary output (in
models EVB1204 and EVB1214 only if u1 = 2, in the
remaining models only if u1 and/or u11 = 2) in manual
mode with the device turned off (40).
1 = YES
if C14 = 0 compressor switch-off delay after pump down
valve switch-off
if C14 = 1 or 2, maximum delay between pump down
valve switch-off and compressor switch-off
enabling of alarm output deactivation with the silencing of
the buzzer (in models EVB1204 and EVB1214 only if u1 =
3, in the remaining models only if u1 and/or u11 = 3)
1 = YES
room temperature or CPT temperature below which the
u5 -99.0 99.0
u6 1 120 min 5 5 5 5 5 5 5 5
u7 -99.0 99.0
°C/°F
(1)
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
-5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
page 68 of 92
door heating elements are turned on ("u5 - 2.0°C/4°F in
models EVB1204 and EVB1214 only if
u1 = 4, in the remaining models only if u1 and u11 = 4).
duration of demister heating elements activation (in
models EVB1204 and EVB1214 only if u1 = 1, in the
remaining models only if u1 and/or u11 = 1)
neutral area value (relative to the work set-point, i.e.
“work set-point + u7) (in models EVB1204 and EVB1214
only if u1 = 5, in the remaining models only if u1 and/or
u11 = 5) (41)
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
u9 0 1 - - - - 1 1 1 1 1 1 1 1
u11 0 12 - - - -
not
avail.
not
avail.
3 3 3 3 3 3
buzzer activation
1 = YES
application managed by the K6 digital output (35) (36)
0 = reserved
1 = DEMISTER HEATING ELEMENTS - in this case the
“AUXILIARY” key and parameter u6 will be
activated
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
3 = ALARM OUTPUTS - in this case parameter u4 will
be activated
4 = DOOR HEATING ELEMENTS - in this case
parameter u5 will be activated
5 = HEATING ELEMENTS FOR NEUTRAL AREA
OPERATION - in this case parameter u7 will be
activated
6 = CONDENSER FAN - in this case parameters P4,
F11 and F12 will be activated
7 = COMPRESSOR 2 - in this case, parameters r0,
r12, C11, C12 e C13 (37) will assume significance
8 = DEFROSTING 2 - in this case, parameters P4 and
d (38) will assume significance
9 = EVAPORATOR FAN 2 - in this case parameters P4
and F (39) will assume significance of
10 = PUMP DOWN VALVE - in this case, parameters
C14 and u3 will assume significance of
(RESERVED in models EVB1246 and EVB1256)
11 = ON/STAND-BY - in this case “ON/STAND-BY” key
will assume significance (42)
12 = MAN IN COLD ROOM - in this case, parameters i5
and i15 will assume significance of
page 69 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
Hr0 0 1 - - - -
PARAM. MIN. MAX. M.U.
HE2 0 999 min 0 0 0 0 0 0 0 0
H01 0 23 h
H02 0 24 h
not
avail.
not
avail.
not
avail.
1
0
0
not
avail.
not
avail.
not
avail.
1
0
0
not
avail.
not
avail.
not
avail.
1
0
0
not
avail.
not
avail.
not
avail.
CLOCK
clock activation, together with the functions that require it
1
1 = YES
ENERGY SAVING
maximum duration of the “energy saving” function
activated due to the effect of absence of door micro
switch input activation; see also i10
0 = the function will last until the input is activated
activation time of the “energy saving” function every
0
Monday; see alsor4, F13, F14 and H02
duration of the “energy saving” function every Monday;
0
see also H01
H03 0 23 h
H04 0 24 h
H05 0 23 h
not
avail.
not
avail.
not
avail.
0
0
0
not
avail.
not
avail.
not
avail.
0
0
0
not
avail.
not
avail.
not
avail.
page 70 of 92
0
0
0
not
avail.
not
avail.
not
avail.
activation time of the “energy saving” function every
0
Tuesday; see also r4, F13, F14 and H04
duration of the “energy saving” function every Tuesday;
0
see also H03
activation time of the “energy saving” function every
0
Wednesday; see also r4, F13, F14 and H06
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
H06 0 24 h
H07 0 23 h
H08 0 24 h
H09 0 23 h
H10 0 24 h
H11 0 23 h
H12 0 24 h
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0
0
0
0
0
0
0
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0
0
0
0
0
0
0
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
0
0
0
0
0
0
0
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
duration of the “energy saving” function every
0
Wednesday; see also H05
activation time of the “energy saving” function every
0
Thursday; see also r4, F13, F14 and H08
duration of the “energy saving” function every Thursday;
0
see also H07
activation time of the “energy saving” function every
0
Friday; see also r4, F13, F14 and H10
duration of the “energy saving” function every Friday; see
0
also H09
activation time of the “energy saving” function every
0
Saturday; see also r4, F13, F14 and H12
duration of the “energy saving” function every Saturday;
0
see also H11
H13 0 23 h
H14 0 24 h
not
avail.
not
avail.
0
0
not
avail.
not
avail.
0
0
not
avail.
not
avail.
page 71 of 92
0
0
not
avail.
not
avail.
activation time of the “energy saving” function every
0
Sunday; see also r4, F13, F14 and H14
duration of the “energy saving” function every Sunday;
0
see also H13
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
Hd1 h0 h-- h
Hd2 h0 h-- h
Hd3 h0 h-- h
Hd4 h0 h-- h
not
avail.
not
avail.
not
avail.
not
avail.
h--
h--
h--
h--
DEFROSTING IN REAL TIME
not
avail.
not
avail.
not
avail.
not
avail.
h--
h--
h--
h--
not
avail.
not
avail.
not
avail.
not
avail.
h--
h--
h--
h--
not
avail.
not
avail.
not
avail.
not
avail.
h--
h--
h--
h--
time of activation of first daily defrosting (only if d8 = 4)
h-- = the first defrosting will not be activated
time of activation of second daily defrosting (only if d8 =
4)
h-- = the second defrosting will not be activated
time of activation of third daily defrosting (only if d8 = 4)
h-- = the third defrosting will not be activated
time of activation of fourth daily defrosting (only if d8 =
4)
h-- = the fourth defrosting will not be activated
Hd5 h0 h-- h
Hd6 h0 h-- h
not
avail.
not
avail.
h--
h--
not
avail.
not
avail.
h--
h--
not
avail.
not
avail.
page 72 of 92
h--
h--
not
avail.
not
avail.
h--
h--
time of activation of fifth daily defrosting (only if d8 = 4)
h-- = the fifth defrosting will not be activated
time of activation of sixth daily defrosting (only if d8 = 4)
h-- = the sixth defrosting will not be activated
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
PARAM. MIN. MAX. M.U.
LA 1 247 - - - - 247 247 247 247 247 247 247 247 device address
Lb 0 3 - - - - 2 2 2 2 2 2 2 2
LP 0 2 - - - 2 2 2 2 2 2 2 2
Notes:
(1)
(2)
(3)
(4)
(5)
(6)
the unit of measurement depends on P2
Properly set the parameters corresponding to the regulators after setting parameter P2
The formula for the calculation of the CPT temperature is:
CPT temperature = {[(P7) x (temperature detected by the inlet air probe)] + [(100 - P7) x (temperature detected by the outlet air probe)] : 100}
the unit of measurement depends on P9 and P10
the value depends on parameter P2 (0,1 °C or 1 °F)
if parameter r12 is set to 0, the compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0" and will be switched off when the
temperature falls below the working set-point; if parameter r12 is set to 1, the compressor will be switched on when the room temperature or CPT temperature is above the “working set-point
+ r0/2” and will be switched off when the temperature falls below the "working set-point - r0/2”
RS-485 MODBUS
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parity
0 = none (no parity)
1 = odd
2 = even
page 73 of 92
EVCO S.p.A.
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16) the display restores normal operation on conclusion of evaporator fan standstill (or if a temperature alarm occurs)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(25)
(26)
(27)
(28)
(29)
if parameter r12 is set to 0:
-
-
if parameter r12 is set to 1:
-
-
the choice of which compressor to switch on/off depends on parameters C12 and C13
the parameter has effect even after an interruption in the power supply that occurs while the device is switched on
the time established with the parameter is counted even when the device is switched off
if parameter C1 is set at 0, the delay after the end of the room temperature/inlet air proble error will be 2 min
the parameter differential is 2,0 °C/4 °F
if when the device is switched on, the condenser temperature is already above that established in parameter C7, then parameter C8 will not have effect
the device memorises the defrosting interval count every 30 minutes; the setting of parameters d0 and d26 has effect from the conclusion of the previous defrosting interval or the activation of
defrosting in manual mode
the display restores normal operation when, on conclusion of evaporator fan standstill, the room temperature or CPT temperature drops below that which has blocked the display (or if a
temperature alarm occurs) the value of t depends on parameter r12 (r0 if r12 = 0, r0/2 if r12 = 1)
if parameter P3 is set at 0 or 2, the device will function as if parameter d8 were set at 0
if when defrosting is activated, the operating duration of the compressor is less than the time established with parameter d5, the compressor will remain on for the amount of time necessary to
complete defrosting
if parameter d8 is set at 2 or 3, the device will operate as if the parameter as been set at 0 and defrosting will be activated when the device has been on totally for the time established with
parameter d26
if parameter P3 is set at 0, the device will function as if parameter A0 were set at 0 but it will not store the alarm
during defrosting and dripping and when the evaporator fan is stopped, the temperature alarms are absent, provided that these were signalled after the activation of defrosting
during activation of the door microswitch input, the maximum temperature alarm is absent, provided the alarm was signaled after the activation of the input
parameters F13 and F14 have effect when the compressor is off
parameters F13 and F14 have effect when the compressor is on
if parameter P3 is set at 0, the device will function as if parameter F0 were set at 2
parameters F13 and F14 have effect when the evaporator temperature is below the temperature established with parameter F1
parameters F13 and F14 have effect when the compressor is on and the temperature of the evaporator is below the temperature established with parameter F1
the parameter can be changed also by implementing the procedure described in paragraph “Setting the configuration parameters”
if parameter P4 is set at 0, 2, 3 or 4, the condenser fan will function in parallel with the compressor
a compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0/2" and another when the temperature is above the "working
set-point + r0"
a compressor will be switched off when the room temperature or CPT temperature falls below the "working set-point + r0/2" and another when the temperature is below the
working set-point
a compressor will be switched on when the room temperature or CPT temperature is above the working set-point and another when the temperature is above the "working set-point
+ r0/2"
a compressor will be switched off when the room temperature or CPT temperature falls below the "working set-point + r0/2" and another when the temperature is below the
"working set-point - r0/2"
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 74 of 92
EVCO S.p.A.
(30) the condenser fan is on on condition that the compressor is on and is off when the temperature of the condenser drops below the temperature established with parameter F11 on condition that
(31) the compressor is switched off 10 sec after the activation of the input; if the input is activated during defrosting or when the evaporator fan is deactivated, the activation will not have any effect
(32)
(33)
(34)
(35)
(36) make sure that parameter u1 is not set at 1 when parameter u11 is set at 2 (and vice versa)
(37) if parameter d8 is set at 3, the setting shall have no effect and the device shall operate as if the parameter were set at 0
(38)
(39)
(40)
(41)
(42)
(43) the parameter is in ten (for example, 1 = 10 steps, 10 = 100 steps, etc.)
(44)
(45) the models integrating the unipolar electronic expansion valves driver do not support the backup module for the valve closure in case of lack of power supply; it is suggested to set parameter u1
the compressor is off
on the compressor
the device stores the alarm once the time established in parameter i2 has expired; if parameter i2 is set at -1, the device will not store the alarm
if the parameter i5 i0 and parameter i15 are set at the same value, the effect will be caused by the activation of at least one of the inputs (until both inputs are deactivated)
make sure that the time established with parameter i7 is less than that established with parameter i9
to avoid damaging the unit connected to the instrument, set the parameter setting when the device is switched off
if parameter d8 is set at 2 or 3, the setting shall have no effect and the device shall operate as if the parameter were set at 0; it is suggested to set parameter P4 at 3 (the evaporator
temperature probe shall be associated with defrosting and the evaporator 2 temperature probe shall be associated with defrosting 2)
it is suggested to set parameter P4 at 3 (the evaporator temperature probe shall be associated with the evaporator fan and the evaporator 2 temperature probe shall be associated with the
evaporator 2 fan)
if parameter u2 is set at 0, switching off the device may cause the room light and/or the auxiliary output to switch off (the next time the instrument is switched on the unit connected will remain
switched off); if parameter u2 is set at 1, switching off the device will not cause the room light or the auxiliary output to switch off (the next time the instrument is switched on the unit
connected will remain switched on)
the heating elements are switched on when the room temperature of the cabinet or the CPY temperature drops below the “work set-point + u7” and are switched off when the temperature rises
above the “work set-point + u7 + 2 °C/°F”
the switching on of the device shall switch on the application and the switching off of the device shall switch off the application
the parameter differential is 2,0 bar g / PSI g
(or u11) to 11 and connect the digital output K5 (or K6) to a solenoid valve.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 75 of 92
EVCO S.p.A.
13 WARNING LIGHTS AND DIRECTIONS
13.1 Signals
The following table shows the meaning of the LED warning lights of the device.
LED MEANING
Compressor LED light
If the LED is on:
-
If the LED is flashing:
-
-
Defrost LED
If the LED is on:
-
-
If the LED is flashing:
-
-
-
the compressor is on
the working set point is in the process of being set (via the procedure described in paragraph ”Setting the
working set point”
a compressor protection will be in progress; see parameters C0, C1, C2, C11 and i7
defrosting is in progress
predripping will be in progress; see parameter d16
defrosting will be requested but a compressor protection will be in progress; see the parameters C0, C1 and
C2
dripping will be in progress; see parameter d7
the refrigerant fluid heating will be in progress; see parameter d15
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Evaporator fan LED light
If the LED is on:
-
If the LED is flashing:
-
room light LED
If the LED is on:
-
If the LED is flashing:
-
the evaporator fan will be on
evaporator fan standstill will be in progress; see parameter F3
the room light has been turned on manually (only if the parameter u1 and/or parameter u11 is set at 0)
the room light has been turned from a digital input ; see parameter i0 (only if the parameter u1 and/or
parameter u11 is set at 0)
page 76 of 92
EVCO S.p.A.
AUX1
and
AUX2
Auxiliary LED 1 and Auxiliary LED 2
If the LED is on:
-
-
-
-
-
-
-
-
-
-
-
If the LED is flashing:
- compressor 2 protection will be in progress; see parameters C0, C1, C2, C11 and i7
- evaporator fan 2 standstill will be in progress; see parameter F3
-
the demister heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at
1)
the auxiliary output will have been switched on in manual mode (only if the parameter u1 and/or parameter
u11 is set at 2)
the door heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at 4)
the neutral area operating heating elements will be activated (only if the parameter u1 and/or parameter
u11 is set at 5)
the condenser fan will be on (only if the parameter u1 and/or parameter u11 is set at 6)
compressor 2 will be on (only if the parameter u1 and/or parameter u11 is set at 7)
the defrosting output 2 will be on (only if the parameter u1 and/or parameter u11 is set at 8)
evaporator 2 fan will be on (only if the parameter u1 and/or parameter u11 is set at 9)
the pump down valve will be on (only if the parameter u1 and/or parameter u11 is set at 10)
the on/stand-by output will be on (only if the parameter u1 and/or parameter u11 is set at 11)
the man in cold room output will be on (only if the parameter u1 and/or parameter u11 is set at 12)
the auxiliary out put will have been switched on from a digital input; see parameters i5 and i15 (only if the
parameter u1 and/or parameter u11 is set at 2)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
HACCP
Clock LED light
If the LED is on:
-
If the LED is flashing:
-
temperature LED light
If the LED is on:
-
If the LED is flashing:
-
pressure LED light
If the LED is on:
-
HACCP LED light
If the LED is on:
-
If the LED is flashing:
-
the value displayed shall be a time
the date, time and day of the week are being set
the value displayed shall be a temperature
the “rapid cooling” function is in progress; see parameters r5 and r6
the value displayed shall be a pressure
not all the information on the HACCP alarms has been displayed
if it is flashing, the device has saved at least one new HACCP alarm
Energy saving LED light
If the LED is on:
-
the “energy saving” function is in progress
page 77 of 92
EVCO S.p.A.
Alarm LED light
If the LED is on:
-
If the LED is flashing:
-
an alarm is in progress
compressor maintenance is required; see parameter C10
13.2 Signal Descriptions/Explanations
The following table shows the meaning of the signal codes of the device.
CODE MEANING
-
Loc
- - - - The operation requested is not available
-
the keyboard is blocked; see paragraph 6.11 “Keyboard locking/unlocking”
the work set point is blocked; see parameter r3
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 78 of 92
EVCO S.p.A.
14 ALARMS
14.1 Alarms
The following table shows the meaning of the alarm codes of the device.
CODE MEANING
Minimum alarm temperatures (HACCP alarms)
Solutions:
-
AL
AH
Main consequences:
-
-
Maximum temperature alarm (HACCP alarms)
Solutions:
-
Main consequences:
-
-
check the temperature associated to the alarm; see parameters A0, A1 and A2
if parameter A0 is set at 0, the device will store the alarm
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the room temperature or CPT temperature; see parameters A4 and A5
the device will memorise the alarm
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
id
PF
iA
Door micro switch input alarm (HACCP alarms)
Solutions:
-
Main consequences:
-
-
-
Power supply cut-off alarm (HACCP alarm)
Solutions:
-
-
Main consequences: Main consequences:
-
-
Multifunction and Multifunction 2 input alarm
Solutions:
-
Main consequences:
-
-
check the causes of the activation of the input; see parameters i0 and i1
the effect established with the parameter i0
if parameter i4 is set at 1, the device will store the alarm, provided parameter i2 is not set at -1
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the causes triggering the power supply cut-off; see parameters A10 and A12
press a key to restore normal display
if the interruption lasts longer than the time established with parameter A10, the device will store the alarm
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
the effect established with the parameters i5 and i15
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
page 79 of 92
EVCO S.p.A.
iSd
LP
HSH
Maximum pressure switch alarm
Solutions:
-
-
Main consequences:
-
-
Minimum pressure switch alarm
Solutions:
- check the evaporating pressure; see parameters h12 and h13
-
Main consequences:
-
-
- the electronic expansion valve will be closed
High superheating alarm alarm
Solutions:
- check the evaporating temperature; see parameters h02
Main consequences:
-
check the causes of the activation of the input; see parameters i5, i6, i7, i8, i9, i15 and i16
switch off and re-start the device or suspend the power supply
the regulators will switch off
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the causes of the activation of the input; see parameters i5, i6, i15, i16 and i17
the compressor will be switched off
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
C1t
C2t
MiC
Compressor thermal protection alarm
Solutions:
-
Main consequences:
-
-
-
Compressor 2 thermal protection alarm
Solutions:
-
Main consequences:
-
-
-
Man in Cold room alarm
Solutions:
-
Main consequences:
-
-
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
the compressor will be switched off
if parameter u1 and/or parameter u11 is set at 7 (or in case of operation with two compressors), the device
shall operate exactly as it would with only one compressor (compressor 2)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
compressor 2 will be switched off (only if the parameter u1 and/or parameter u11 is set at 7)
the device shall operate exactly as it would with only one compressor (compressor 1)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
the man in cold room output will be switched on (only if the parameter u1 and/or parameter u11 is set at
12)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
page 80 of 92
EVCO S.p.A.
COH
CSd
Condenser overheated alarm
Solutions:
-
Main consequences:
-
-
Compressor shut down alarm.
Solutions:
-
-
Main consequences:
-
-
-
check the condenser temperature; see parameter C6
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)
check the condenser temperature; see parameter C7
switch the device off and back on again: if when the device is switched back on, the temperature of the
condenser is still higher than that established in parameter C7, disconnect the power supply and clean the
condenser
the compressor and the evaporator fan will be switched off
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Defrosting alarm switched off because maximum time has been reached
Solutions:
-
dFd
Pd
When the cause of the alarm disappears, the device restores normal operation, except for the following alarms:
-
-
-
-
-
Main consequences:
-
Pump down alarm (from digital input) finished for maximum duration
Solutions:
-
Main consequences:
-
the power supply interruption alarm (code “PF”) which requires the pressing of a key
maximum pressure switch alarm (code “iSd”) which requires the switching off of the device or the temporary suspension of
the power supply
compressor blocked by condenser temperature alarm (code “CSd”) which requires the switching off of the device or the
temporary suspension of the power supply
defrosting alarm switched off because maximum time has been reached (code “dFd”) which requires the pressing of a key.
check the integrity of the evaporator temperature probe; see parametersd2, d3 and d11
press a key to restore normal display
the device will continue to operate normally
check the integrity of the sensor switching off the compressor
the device will continue to operate normally
page 81 of 92
EVCO S.p.A.
15 ERRORS
15.1 Errors
The following table shows the meaning of the error codes of the device.
CODE MEANING
room temperature/inlet air temperature probes error
Solutions:
-
Pr1
-
-
Main consequences:
-
-
-
-
-
-
check that the probe is the PTC, NTC or Pt 1000 type; see parameter P0
check the device-probe connection
check room/inlet air temperature
compressor activity will depend on parameters C4 and C5
the defroster will not be activated
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the door heating elements will be switched off (only and provided parameter u1 and/or parameter u11 is set
at 4)
the neutral area operating heating elements will be deactivated (only if parameter u1 and/or parameter u11
is set at 5)
if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the outlet air
temperature probe
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Pr2
Pr3
Evaporator temperature probe error
Solutions:
-
Main consequences:
-
-
-
-
Auxiliary temperature probe error
Solutions:
-
Main consequences:
-
-
-
the same as the preceding case but with respect to the evaporator temperature probe
if parameter P3 is set at 1, the defrosting period will last for the amount of time set with parameter 3
if parameter P3 is set at 1and parameter d8 is set at 2 or to 3, the device will operate as if parameter d8
were set at 0
if parameter F0 is set at 3 or 4, the device will operate as if the parameter were set at 2
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the same as in the previous example, but with regard to the auxiliary temperature probe
if parameter P4 is set at 1:
-
-
-
parameter u11 is set at 6)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the inlet air
temperature probe
condenser overheated alarm (code “COH”) will never be activated
he compressor blocked alarm (code “CSd”) will never be activated
the condenser fan will operate parallel to the compressor (only if parameter u1 and/or
page 82 of 92
EVCO S.p.A.
Pr5
Pr4
rtc
Vapour pressure probe error
Solutions:
-
-
-
Main consequences:
-
-
Evaporation temperature probe error
Solutions:
-
-
-
Main consequences:
-
-
Clock error
Solutions:
-
Main consequences:
-
-
-
-
check that the probe is the 4-20 mA type
check the device-probe connection
check the vapour pressure
the electronic expansion valve will be open the percentage set with parameter h17
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
check that the probe is the PTC, NTC or Pt 1000 type; see parameter P0
check the device-probe connection
check room/inlet air temperature
the electronic expansion valve will be open the percentage set with parameter h17
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
set the date, time and day of the week
if parameter d8 is set at 4, the device will operate as if it were set at 0
the “HACCP” function will not provide information regarding the date and hour in which the alarm was
signalled
the “energy saving” function n real time function will not be activated in real time
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
When the cause of the error disappears, the device restores normal operation, except for clock error (“rtc” code), which requires the
date, time and day of the week set.
page 83 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
16 ACCESSORIES
16.1 Non opto-isolated RS-485/USB serial interface EVIF20SUXI
16.1.1
The interface makes it possible to connect the device to the Parameters Manager set-up software system.
Preliminary notes
16.2 Data recorder EVUSBREC01
16.2.1
The device records the board data and their download (via USB in a CSV file format).
Preliminary notes
16.3 USB cover for panel installation 0812000002
16.3.1
Through the cover it is possible to make the USB-type communication port more accessible for EVUSBREC01 data recording.
To connect the cover to the devise it is necessary to use also the 0810500018 or 0810500020 connection cable (to be ordered
separately).
Preliminary notes
page 84 of 92
EVCO S.p.A.
16.4 0810500018/0810500020 connection cable
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
16.4.1
The cables can be used to connect the USB cover for panel installation 0812000002 to the EVUSBREC01 data recorder.
The 0810500018 cable is 2.0 m long; the 0810500020 cable is 0.5 m long.
Preliminary notes
page 85 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
17 TECHNICAL DATA
17.1 Technical data
Purpose of the command device: operating command device.
Construction of the command device: built-in electronic device.
Container: grey self-extinguishing.
Heat and fire protection class: D.
Dimensions:
Method of mounting the command device: wall mounted, with bolts and fastening screws.
Shell protection grade: IP65.
Connection method:
262.0 x 179.0 x 95.6 mm (10.314 x 7.047 x 3.763 in;
L x H x D).
-
-
-
The maximum lengths of the connection cables are:
-
-
-
-
-
-
-
screw in terminal boards 6.35 mm pitch (0.25 in) for
wires up to 4 mm² (0.0062 in²): power supply and
digital outputs
screw in terminal boards 5.0 mm pitch (0.196 in) for
wires up to 2.5 mm² (0.0038 in²): analogue inputs,
digital inputs and RS-485 MODBUS port
screw in removable terminal board, male only
3.5 mm pitch (0.137 in) for wires up to 1.5 mm²
(0.0028 in²) or JST male only 6-way connector 2.5
mm pitch (0.098 in): driver for unipolar stepper
electronic expansion valves.
power supply: 100 m (328 ft)
analogue inputs: 100 m (328 ft)
transducers power supply: 100 m (328 ft)
digital inputs: 100 m (328 ft)
digital outputs: 100 m (328 ft)
RS-485 MODBUS port: 1,000 m (3,280 ft); please
refer also to the MODBUS specifications and
implementation guides available at
http://www.modbus.org/specs.php
driver for unipolar stepper electronic expansion
valves: 3 m (9.842 ft)
from 0 to 45 °C (from 32 to 113 °F) the models with differential
Operating temperature:
Storage temperature: from -25 to 70 °C (from -13 to 158 °F).
magneto-thermal circuit breaker and with remote control switch
for three-phase defrost elements management, from 0 to 50 °C
(from 32 to 122 °F) otherwise.
page 86 of 92
EVCO S.p.A.
Humidity for use: from 10 to 90 % relative humidity without condensate.
Command device pollution situation: 2.
Height at which it is used: from 0 to 2,000 m (from 0 to 6,591 ft).
Height at which it can be transported: from 0 to 3,048 m (from 0 to 10,000 ft).
Environmental standards:
EMC standards:
Power supply:
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
-
-
-
-
-
115... 230 VAC (+10 %, -15 %), 50/60 Hz (±3 Hz), 35 VA max.
non insulated, supplied by a class 2 circuit.
The maximum phase current allowed is 16 A.
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH (CE) regulation n. 1907/2006.
EN 60730-1
IEC 60730-1.
Magneto-thermal switch:
Differential magneto-thermal circuit breaker:
Remote control switch for three-phase defrost elements
management:
Control device grounding method: with ground terminal
Rated impulse voltage: 4 KV.
Overvoltage category: III.
Class and structure of software: A.
according to model (230 VAC, In 16 A, Icn 4.500 A, unipolar +
neutral, for wires up to 2,5 mm² (0.0387 in²).
according to model (230 VAC, In 16 A, Icn 4.500 A, Id 300 mA,
unipolar + neutral, for wires up to 2,5 mm² (0.0387 in²).
according to model (230 VAC, Ie 9 A, Ui 690 V, Uimp 6 KV, Ith
20 A, 2,2 KW in AC3 at 230 VAC with ta 55 °C, three poles +
neutral, for wires up to 2,5 mm² (0,0387 in²).
incorporated (with lithium secondary battery).
Real time clock:
Battery autonomy without power supply: 6 months.
Battery recharging time: 24 h (the battery is recharged through
the device power supply).
Drift: ≤ 30 s/month at 25 °C (77 °F).
page 87 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
according to model, up to 5 inputs:
-
-
-
4-20 mA transducers power supply: 12 VDC (±10 %),
30 mA max.
Analogue inputs PTC (990 @ 25 °C, 77 °F)
Type of sensor:
Measurement field: from -50 to 150 °C (from -58 to
Precision:
Resolution :
Protection:
3 configurable via configuration parameter for PTC,
NTC or Pt 1000 probes (room temperature,
evaporator temperature and evaporation
temperature)
1 configurable via configuration parameter for PTC,
NTC or Pt 1000 probes (configurable via
configuration parameter for condenser temperature,
critical temperature, evaporator 2 temperature or
CPT temperature)
1 for 4-20 mA transducers (vapour pressure).
302 °F).
KTY 81-121.
±0,5 % of scale end.
0,1 °C (1 °F).
none.
Analogue inputs
Analogue inputs NTC (10 K @ 25 °C, 77 °F)
Type of sensor:
Measurement field: from -50 to 120 °C (from -58 to
Precision:
Resolution :
Protection:
Analogue inputs Pt 1000 (1 K @ 0 °C, 32 °F)
Measurement field: from -99 to 150 °C (from -99 to
Precision:
Resolution :
Protection:
Analogue inputs 4-20 mA
Input resistance:
Precision:
Resolution :
Protection:
248 °F).
302 °F).
ß3435.
±0,5 % of scale end.
0,1 °C (1 °F).
none.
±0,5 % of scale end.
0,1 °C (1 °F).
none.
≤ 200 .
±0,5 % of scale end.
0.01 mA.
none; maximum allowable current
at each input is 25 mA.
Digital inputs:
3 inputs, configurable via configuration parameter for NA or NC
contact (micro port, multifunction 1 and multifunction 2)
page 88 of 92
EVCO S.p.A.
Displays: custom 3 digit display with decimal point and function icon.
Digital outputs:
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
Digital inputs at 5 VDC mA (clean contact)
Power: none.
Protection:
according to model, up to 6 outputs:
-
-
-
-
The device guarantees reinforced insulation between each
connector of the digital outputs and the other parts of the
device.
2 SPST electromechanical relays with 30 A res. @
250 VAC (compressor and evaporator fan)
2 SPST electromechanical relays with 16 A res. @
250 VAC (defrosting and room light)
1 SPST electromechanical relay with 8 A res. @ 250
VAC (configurable through a configuration parameter
for demister heating elements, auxiliary, alarms,
door resistors, neutral area operation resistors,
condenser fan, compressor 2, defrosting 2,
evaporator fan 2, pump down valve, on/stand-by or
man in cold room; for manufacturer default for the
condenser fan).
1 SPDT electromechanical relay with 8 A res. @ 250
VAC (configurable through a configuration parameter
for demister heating elements, auxiliary, alarms,
door resistors, neutral area operation resistors,
condenser fan, compressor 2, defrosting 2,
evaporator fan 2, pump down valve, on/stand-by or
man in cold room; for manufacturer default for the
condenser fan).
none.
Driver for unipolar stepper electronic expansion valves. 12 VDC, 260 mA max.
Type 1 or Type 2 actions: Type 1.
Complementary features of Type 1 or Type 2 actions: C.
Communication port: 1 door RS-485 with MODBUS slave communication protocol.
Signal buzzer and alarm: incorporated.
page 89 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 90 of 92
EVCO S.p.A.
EVBOX1
Front mounted electrical boards for cold rooms with
single-phase compressor
Installation guide ver. 1.3
PT - 30/14
Code 144BOX1E134
This document is exclusive property of EVCO; EVCO does not
assume any liability regarding possible errors stated.
The customer (manufacturer, installer or final user) assumes
all liability regarding configuration of the device.
EVCO does not take any responsibility about damages coming
by the non-observance of additional information.
EVCO reserves the right to make any change without prejudice
the basic safety and operating features.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
page 91 of 92
EVCO S.p.A.
EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134
EVCO S.p.A.
Via Feltre 81, 32036 Sedico Belluno ITALY
Phone 0437/8422 | Fax 0437/83648
info@evco.it | www.evco.it
page 92 of 92
Loading...