EVCO EVB1256N9 User Manual

Page 1
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
EVBOX1
Front mounted electrical boards for cold
rooms with single-phase compressor
Installation guide| ENGLISH
page 1 of 88
Page 2
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Important
Read th is document thoroughly before installation and before
use of the device and follow all recommendations; keep this
document with the device for future consultation.
Only use the device in the way described in this document; do
not use the same as a safety device.
Disposal
The device must be disposed of in compliance with local
standards regarding the collection of electric and electronic
equipment.
page 2 of 88
Page 3
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Index
1 INTRODUCTION .............................................. 4
1.1 Introduction ................................................... 4
1.2 Summary table of available models, their main
characteristics and purchase codes .................... 5
2 DESCRIPTION ................................................. 8
2.1 Outward appearance description ....................... 8
2.2 Interior description ........................................ 10
3 DIMENSIONS AND INSTALLATION ................... 13
3.1 Dimensions .................................................. 13
3.2 Installation ................................................... 13
3.3 Installation warnings ..................................... 14
4 ELECTRIC CONNECTION ................................. 15
4.1 Preliminary notes .......................................... 15
4.2 Electric connection for models EVB1204N9 and
EVB1214N9 .................................................. 16
4.3 Electric connection for models EVB1206N9 and
EVB1216N9 .................................................. 17
4.4 Electric connection for models EVB1226N9 and
EVB1236N9 .................................................. 18
4.5 Electric connection for models EVB1246N9 and
EVB1256N9 .................................................. 19
4.6 Electric connection for models with magneto-
thermal switch or differential magneto-thermal
circuit breaker (example for EVB1256N9D) ....... 20
4.7 Insertion of the RS-485 MODBUS port termination
resistor ........................................................ 21
4.8 Connection of the RS-485 network cable screen to
GND ............................................................ 21
4.9 Warnings for the electric connection ................ 21
5 FIRST USE .................................................... 22
5.1 First use ....................................................... 22
6 USER INTERFACE .......................................... 24
6.1 Preliminary notes .......................................... 24
6.2 Device switch-on/off in manual mode .............. 24
6.3 The display ................................................... 24
6.4 Displaying the magnitude detected by an analogue
input ........................................................... 24
6.5 "Rapid cooling" function enabling/disabling ....... 25
6.6 Defrosting manual activation .......................... 26
6.7 Turning on/off of room lights manually (only if the
parameter u1 and/or parameter u11 is set at 0) 26
6.8 Turning the demister heating elements on/off
manually (only if the parameter u1 and/or
parameter u11 is set at 1) .............................. 26
6.9 Turning on/off of the auxiliary output manually
(only if the parameter u1 and/or parameter u11 is
set at 2) ....................................................... 27
6.10 Keyboard locking/unlocking ............................ 27
6.11 Silencing the buzzer ...................................... 28
7 OPERATION WITH LOW OR HIGH RELATIVE
HUMIDITY PERCENTAGES (ONLY IF THE F0
PARAMETER IS SET TO 5) .............................. 29
7.1 Preliminary notes .......................................... 29
7.2 Manual activation of the low and high relative
humidity percentages operating mode ............. 29
7.3 Learning the current operating mode ............... 29
8 “ENERGY SAVING” FUNCTION ......................... 30
8.1 Preliminary notes .......................................... 30
9 “CPT” FUNCTION (CALCULATED PRODUCT
TEMPERATURE) ............................................. 30
9.1 Preliminary notes .......................................... 30
10 “HACCP” FUNCTION ....................................... 30
10.1 Preliminary notes .......................................... 30
10.2 Display of HACCP alarm in formation ................. 31
10.3 Cancelling the HACCP alarm list ....................... 32
11 COMPRESSOR OPERATING HOURS COUNT ........ 33
11.1 Preliminary notes .......................................... 33
11.2 Display of Compressor Operation Hours ............ 33
11.3 Cancelling the compressor operation hours ....... 34
12 SETTINGS .................................................... 35
12.1 Setting the date, time and day of the week (only
in the models with clock) ................................ 35
12.2 Setting the working set point .......................... 36
12.3 Setting the configuration parameters ............... 36
12.4 Restoring the Manufacturer’s Settings .............. 37
12.5 List of configuration parameters ...................... 38
13 WARNING LIGHTS AND DIRECTIONS ............... 73
13.1 Signals ......................................................... 73
13.2 Signal Descriptions/Explanations ..................... 75
14 ALARMS ....................................................... 76
14.1 Alarms ......................................................... 76
15 ERRORS ....................................................... 79
15.1 Errors .......................................................... 79
16 ACCESSORIES ............................................... 81
16.1 Non opto-isolated RS-485/USB serial interface
AVIF20SUXI .................................................. 81
16.2 Data recorder EVUSBREC01 ............................ 81
16.3 USB cover for panel installation 0812000002 .... 81
16.4 0810500018/0810500020 connection cable ...... 82
17 TECHNICAL DATA .......................................... 83
17.1 Technical data ............................................... 83
page 3 of 88
Page 4
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
1 INTRODUCTION
1.1 Introduction
EVBOX1 is a line of front mounted electrical boards for the
management of cold rooms with single-phase compressor.
The user interface comprises a large custom display (with
decimal point and function icons), six keys, and has a
guaranteed IP65 protection grade front part.
The boards are equipped with two 30A res. @ 250 VAC relays
for the direct control of high power compressors and
defrosting elements, with no need for remote control switches.
They can operate in conditions of both low and high relative
humidity percentages, have an adaptive management of the
defrost function, and can implement energy-saving strategies.
Some models are also equipped with a magneto-thermal
switch or different ial magneto-thermal circuit breaker, a clock
(to save the HACCP alarms), management of defrosting
elements and have an integrated driver for unipolar stepper
electronic expansion valves.
The unit is designed to be wall mounted, with bolts and
fastening screws.
page 4 of 88
Page 5
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
1.2 Summary table of available models, their main characteristics and purchase
codes
The following table contains a description of the available models.
Available models
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
The following table shows the main characteristics of the devices.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
Power supply
115... 230 VAC • • • • • • • •
Analogue inputs
room temperature (PTC/NTC) • • • • • • • •
evaporator temperature (PTC/NTC) • • • • • • • •
auxiliary temperature (PTC/NTC) (1) • • • • • • • •
Vapour pressure (4-20 mA)
evaporation temperature (PTC/NTC) • •
Digital inputs (for NA/NC contact)
door micro switch • • • • • • • •
multifunction • • • • • • • •
multifunction 2 • • • • • • • •
Digital inputs (electromechanical relays; A res. @ 250 VAC)
compressor 30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
defrosting 30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
evaporator fan 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
room light 16 A 16 A 16 A 16 A 16 A 16 A
load 4 (default to room light) (2) 8 A 8 A
page 5 of 88
Page 6
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
load 5 (default to condenser fan) (3) 8 A 8 A 8 A 8 A 8 A 8 A
load 6 (default to alarm ) (3) 8 A 8 A 8 A 8 A 8 A 8 A
Communication ports
RS-485 MODBUS for other EVCO products • • • • • • • •
Other characteristics
clock • • • •
alarm buzzer • • • • • • • •
three-phase defrost elements management • •
integrated driver for unipolar stepper electronic expansion valves.
operation at low and high relative humidity percentages • • • • • • • •
overheated condenser alarm management • • • • • • • •
defrosting adaptive management • • • • • • • •
"HACCP" function • • • •
"energy saving" function • • • • • • • •
"rapid cooling" function • • • • • • • •
Notes
(1)
can be set through a configuration parameter to condenser temperature, critical temperature, evaporator 2 temperature or
CPT temperature parameter.
(2)
can be set through a configuration parameter to room light, demister heating elements, auxiliary, alarms, door resistors,
neutral area operation resistors, condenser fan, compressor 2, defrosting 2 evaporator fan 2, pump down valve, on/stand-
by or man in cold room
(3) can be set through a configuration parameter to demister heating elements, auxiliary, alarms, door resistors, neutral area
operation resistors, condenser fan, compressor 2, defrosting 2 evaporator fan 2, pump down valve, on/stand-by or man in
cold room
Available options
In some models, there is a magneto-thermal switch or differential magneto-thermal circuit breaker.
Check that the switch is available for the device; contact the EVCO distribution network.
For additional information, please read chapter "TECHNICAL DATA",
page 6 of 88
Page 7
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
The following table shows the purchase codes.
Available models
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
Add "M" for the magneto-thermal switch or "D" for the differential magneto-thermal circuit breaker.
For additional models, please contact the EVCO distribution network
page 7 of 88
Page 8
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
2 DESCRIPTION
2.1 Outward appearance description
The following drawing shows the outward appearance of the devices.
The following table shows the meaning of the parts of the front of the devices
PART MEANING
1 access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
2 screws fastening the front shell to the back shell
3 tab fastening the front shell to the back shell
4 handle of the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
5 handle to remove the cover of the screws fastening the front shell to the back shell
6 cover of the screws fastening the front shell to the back shell
7 on/off key, hereinafter also "ON/STAND-BY" key
8 manual defrosting key, hereinafter also "DEFROSTING" key
9 auxiliary functions key, hereinafter also "AUXILIARY" key
10 display
11 increase key, hereinafter also "UP" key
page 8 of 88
Page 9
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
12 settings key, hereinafter also "SET" key
13 decrease key, hereinafter also "DOWN" key
14 seal
15 if present, magneto-thermal switch or differential magneto-thermal circuit breaker
16 front shell
17 back shell
For additional information, please refer to the following chapters.
page 9 of 88
Page 10
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
2.2 Interior description
To access the interior of the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in
paragraph 2.1 “Outward appearance description"):
1.
Open the access door of the magneto-thermal switch or differential magneto-thermal circuit breaker (1) using the relevant
handle (4) and loosen the two screws fastening the front shell to the back shell (2) with a screwdriver.
2.
Remove the cover of the two screws fastening the front shell to the back shell (6) using the relevant handle (5) and loosen
the two screws fastening the front shell to the back shell (2) with a screwdriver.
Lift the front shell (16) using the assembly tabs fastening the front shell to the back shell (3) as a pivot.
3.
The following drawing shows the inner appearance of the devices.
page 10 of 88
Page 11
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
The following table shows the meaning of the parts inside the devices
PART MEANING
3 tab fastening the front shell to the back shell
4 handle of the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker
5 handle to remove the cover of the screws fastening the front shell to the back shell
15 if present, magneto-thermal switch or differential magneto-thermal circuit breaker
18 K3 digital output (evaporator fan)
19 K2 digital output (defrosting)
20 K1 digital output (compressor)
21 device power supply
22 if present, driver for unipolar stepper electronic expansion valves connected to a removable male only screw terminal board
23 if present, driver for unipolar stepper electronic expansion valves connected with male only JST connector
24 BUS RS-485 polarisation jumper
25 RS-485 MODBUS port
26 RS-485 MODBUS port termination resistor insertion jumper
27 digital inputs (micro port, multifunction 1 and mult ifunction 2)
analogue inputs 1 and 2 (room temperature and evaporator temperature) and analogue input 3 (can be set through a
28
configuration parameter to condenser temperature, critical temperature, evaporator 2 temperature or CPT temperature)
29 if present, analogue inputs 4 and 5 (evaporation temperature and vapour pressure)
in the EVB1204N9 and EVB1214N9 models, K4 digital output (can be set through a configuration parameter to room light,
demister heating elements, auxiliary, alarms, door resistors, neutral area operation resistors, condenser fan, compressor 2,
defrosting 2, evaporator fan 2, pump down valve, on/stand-by or man in cold room; manufacturer default is room light).
30
in the remaining models, K6 digital output (can be set through a configuration parameter to de mister heating elements,
auxiliary, alarms, door resistors, neutral area operation resistors, condenser fan, compressor 2, defrosting 2, evaporator
fan 2, pump down valve, on/stand-by or man in cold room; manufacturer default is alarm).
page 11 of 88
Page 12
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
if present, K5 digital output (can be set through a configuration parameter to demister heating elements, auxiliary, alarms,
31
door resistors, neutral area operation resistors, condenser fan, compressor 2, defrosting 2, evaporator fan 2, pump down
valve, on/stand-by or man in cold room; manufacturer default is condenser fan).
32 if present, digital output 4 (room light)
33 seal
34 drilling lead for wall installation
35 ground terminal
36 raised profile
37 seal
For additional information, please refer to the following chapters.
page 12 of 88
Page 13
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
3 DIMENSIONS AND INSTALLATION
3.1 Dimensions
The following drawing shows the measurements of the devices, in mm (in).
3.2 Installation
The unit is designed to be wall mounted, with bolts and fastening screws (not supplied).
To install the devices, proceed as follows (numbers in parentheses refer to the part number shown in the tables in chapter 2
"DESCRIPTION"):
1. Open the access door of the magneto-thermal switch or differential magneto-thermal circuit breaker (1) using the relevant
handle (4) and loosen the two screws fastening the front shell to the back shell (2) with a screwdriver.
remove the cover of the two screws fastening the front shell to the back shell (6) using the relevant handle (5) and loosen
2.
the two screws fastening the front shell to the back shell (2) with a screwdriver.
3.
Lift the front shell (16) using the assembly tabs fastening the front shell to the back shell (3) as a pivot.
4. Drill a hole with a diameter of 5.0 mm (0.196 in) in each of the three drilling leads for wall installation (34).
5.
Drill three 6.0 mm (0.236 in) holes in the wall where the device is to be installed, using the three previously perforated
drilling leads (34) as template.
Insert three bolts in the three holes drilled into the wall.
6.
7.
Insert three seals (37) in three fastening screws.
If the connection wires are to be threaded from the top or the bottom, drill a hole in a flat surface of the back shell (17),
8.1
whose dimensions are adequate for a cable tray (not supplied; the cable tray dimensions must be appropriate to the
number of cables to be laid) and assemble the cable tray.
8.2 If the connection cables are to be installed from the back, drill a hole with dimensions appropriate to the number of cables
to be laid in the raised profile (36) on the back wall of the back shell (17) and apply some silicone on the whole profile.
9.
Fasten the back shell (17) with the three screws and the seals (37) previously inserted in the screws.
make the necessary electric connections; please refer to chapter "ELECTRIC CONNECTION".
10.
Place the front shell (16) on the back shell (17) using the assembly tabs fastening the front shell to the back shell (3) as a
11.
pivot.
12.
Tighten the four screws fastening the front shell to the back shell (2) with a screwdriver, put the fastening screws cover (6)
back on and close the access door to the magneto-thermal switch or differential magneto-thermal circuit breaker (1) with
the handle (4).
page 13 of 88
Page 14
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
3.3 Installation warnings
- make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter
“TECHNICAL DATA”
-
do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful
magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or
shocks
- in compliance with Safety Standards, the device must be installed correctly and in a way to protect against any contact with
electric parts; all parts that ensure protection must be fixed in a way that they cannot be removed without the use of tools.
page 14 of 88
Page 15
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4 ELECTRIC CONNECTION
4.1 Preliminary notes
The magnitude detected by the auxiliary sensor (terminals 5 and 8) can be set through the P4 configuration parameter as follows:
no magnitude (parameter P4 = 0)
-
condenser temperature (parameter P4 = 1)
-
-
critical temperature (parameter P4 = 2) evaporator temperature 2 (parameter P4 = 3)
-
outgoing air temperature (parameter P4 = 4); in this case, the temperature associated with the setting shall be the CPT
-
(Calculated Product Temperature) one
In the EVB1204N9 and EVB1214N9 models the application managed by the K4 digital output (terminals 13, 14 and 15) can be set by
the u11 configuration parameter as follows:
-
room light (parameter u1 = 0, default setting) demister heating elements (parameter u1 = 1)
-
-
auxiliary output (parameter u1 = 2) alarm output (parameter u1 = 3)
-
- door heating elements (parameter u1 = 4)
-
neutral area operating heating elements(parameter u1 = 5) condenser fan (parameter u1 = 6)
-
compressor 2 (parameter u1 = 7)
-
-
defrosting 2 (parameter u1 = 8) evaporator fan 2 (parameter u1 = 9)
-
-
pump down valve (parameter u1 = 10) on/stand-by (parameter u1 = 11)
-
man in cold room exit (parameter u1 = 12).
-
In the remaining models, the application managed by the K5 digital output (terminals 16 and 17) can be set through the u1
configuration parameter and that managed by the K6 digital output (terminals 13, 14 and 15) through the u11 configuration parameter
as follows:
demister heating elements (parameter u1 = 1)
-
auxiliary output (parameter u1 and/or u11 = 2)
-
-
alarm output (parameter u1 and/or u11 = 3, default setting for the K6 digital output door heating elements (parameter u1 and/or u11 = 4)
-
neutral area operating heating elements(parameter u1 and/or u11 = 5)
-
-
condenser fan (parameter u1 and/or u11 = 6, default setting for the K5 digital output) compressor 2 (parameter u1 and/or u11 = 7)
-
defrosting2 (parameter u1 and/or u11 = 8)
-
-
evaporator fan 2 (parameter u1 and/or u11 = 9) pump down valve (parameter u1 and/or u11 = 10)
-
on/stand-by (parameter u1 and/or u11 = 11)
-
-
man in cold room exit (parameter u1 and/or u11 = 12).
Through the RS-485 MODBUS port it is possible to carry out on eof the following actions:
- device configuration, through the Parameters Manager set-up software system
device data recording, through the EVUSBREC01 data recording device
-
device supervision, through the CloudEvolution system monitoring and supervision (via Web) system
-
-
use of the MODBUS slave function through third party devices.
The port must not be used for more than one of these purposes at the same time.
Please see paragraph “Setting the configuration parameters” for the settings of the configuration parameters.
For additional information, please refer to the following paragraphs.
page 15 of 88
Page 16
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.2 Electric connection for models EVB1204N9 and EVB1214N9
The following drawing shows the electric connections for the EVB1204N9 and EVB1214N9 mode ls.
page 16 of 88
Page 17
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.3 Electric connection for models EVB1206N9 and EVB1216N9
The following drawing shows the electric connections for the EVB1206N9 and EVB1216N9 models.
page 17 of 88
Page 18
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.4 Electric connection for models EVB1226N9 and EVB1236N9
The following drawing shows the electric connections for the EVB1226N9 and EVB1236N9 models.
page 18 of 88
Page 19
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.5 Electric connection for models EVB1246N9 and EVB1256N9
The following drawing shows the electric connections for the EVB1246N9 and EVB1256N9 models.
page 19 of 88
Page 20
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.6 Electric connection for models with magneto-thermal switch or differential
magneto-thermal circuit breaker (example for EVB1256N9D)
The following drawing shows the electric connections for models with magneto-thermal switch or differential magneto-thermal circuit
breaker (example EVB1256N9D).
page 20 of 88
Page 21
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
4.7 Insertion of the RS-485 MODBUS port termination resistor
To reduce reflections on the signal transmitted through the cables connecting the devices to a RS-485 network it is necessary to insert
the termination resistor of the first and last elements of the network.
To insert the termination resistor place the jumper as shown in the following drawing.
4.8 Connection of the RS-485 network cable screen to GND
To prevent external disturbances from being interpreted as signals by the RS-485 network, it might be necessary to connect the cable
screen of the RS-485 network to GND
To connect the cable screen to GND, place the jumper as shown in the following drawing.
4.9 Warnings for the electric connection
- do not use electric or pneumatic screwdrivers on the device terminal board
-
if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before powering it make sure that the power supply voltage, the frequency and the operational electric power of the device, correspond with
-
those of the local power supply; see chapter “TECHNICAL DATA”
-
disconnect the device power supply before proceeding with any type of maintenance connect the device to a RS-485 MODBUS network using a twisted pair
-
-
position the power cables as far away as possible from the signal cables for repairs and information regarding the device, contact the EVCO sales network.
-
page 21 of 88
Page 22
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
5 FIRST USE
5.1 First use
Operate as follows:
Install the device as described in chapter "DIMENSIONS AND INSTALLATION" , following in particular the instructions of
1.
paragraph “Installation warnings”.
2.
Make the relevant electric connections f or the device as shown in chapter "ELECTRIC CONNECTION", following in particular
the instructions of paragraph “Warning for the electric connection", without connecting the device or the loads power
supply.
3. Connect the device power supply: this shall launch an internal test.
The test typically takes a few seconds to complete; at the end of the test, the display turns off.
If, at the end of the test, the letters "rtc" flash on the screen and the buzzer sounds intermittently, it will be necessary to
4.
set the date, time and day of the week; please refer to paragraph 12.1 “Setting the date, time and day of the week (only in
the models with clock)”.
5. Configure the device using the procedure described in paragraph “Setting the configuration parameters”,
The following table shows the meaning of the main configuration parameters; the parameters are shown in the order with
which it is best to configure the device.
PARAM. MEANING DEFAULT SETTINGS
temperature probe type
P0
0 = PTC
= NTC
1
1
temperature unit of measurement
P2
P9 pressure transducer minimum setting 5
P10 pressure transducer maximum setting 80
P11
SP work set-point -18,0 °C
r0 working set-point differential 2.0 °C
d0
0 = °C
= °F
1
position of the pressure decimal point 0 = no decimal points
= on the tens digit
1
type of defrosting
0
= electric = by hot gas
1
= via stopping of compressor
2
0
1
0
d3 maximum defrosting duration 30 min
page 22 of 88
Page 23
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
in the EVB1204N9 and EVB1214N9 models, the application is managed through
the K4 digital output
0
= man in cold room exit = demister heating elements
1
= auxiliary output
2
3
= alarm output = door heating elements
4
u1
u1
= neutral area operating heating elements
5
6
= condenser fan = compressor 2
7 8 = defrosting2
9
= evaporator fan 2
= pump down valve
10
= on/stand-by
11
12
= man in cold room exit
in the remaining models, the application is managed by the K5 digital output
= reserved
0
1
= demister heating elements = auxiliary output
2
= alarm output
3
4
= door heating elements = neutral area operating heating elements
5
= condenser fan
6
7
= compressor 2 = defrosting2
8
= evaporator fan 2
9
10
= pump down valve = on/stand-by
11
12
= man in cold room exit
0
5
if present, the application is managed by the K6 digital output
0
= reserved
1
= demister heating elements = auxiliary output
2 3 = alarm output
4
= door heating elements = neutral area operating heating elements
u11
5
= condenser fan
6
7
= compressor 2
8 = defrosting2
= evaporator fan 2
9
10
= pump down valve = on/stand-by
11
= man in cold room exit
12
2
Then, check that the remaining settings are appropriate; refer to paragraph 12.5 “List of configuration parameters”.
Connect the loads power supply
6.
Turn the device on; refer to paragraph "Device switch-on/off in manual mode".
7.
For additional information, please refer to the following paragraphs.
page 23 of 88
Page 24
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
6 USER INTERFACE
6.1 Preliminary notes
Operating Statuses:
-
“on” state (the device is powered and is on: the
regulators can be switched on)
“stand-by” status (the device is powered but is
-
switched off via software: the regulators are
switched off; the possibility to turn the room light
or the auxiliary output on/off manually depends on
parameter u2)
-
the “off” status (the device is not powered).
Hereafter, with the word “start-up” means the passage from
“stand-by” status to “on” status; the word “shutdown” means
the passage from “on” status to “stand-by” status.
When the power is switched back on, the device displays the
status that it was in at the time it was disconnected.
6.2 Device switch-on/off in manual
mode
To turn the device on/off in manual mode, proceed as follows:
Make sure that the keyboard is not locked and that
1.
no procedure is in progress.
2.
Hold the key “ON/STAND-BY” for 2 s.
Using the digital inputs it is also possible to remotely switch
on/off the device.
6.3 The display
If the device is switched on, during normal operation, the
display will show the magnitude established with P5, except
during defrosting, when the device will show the temperature
established with parameter d6.
If the device is switched off, the display will be switched off.
6.4 Displaying the magnitude
Device switch-on/off in manual mode
detected by an analogue input
To display the magnitude detected by an analogue input,
proceed as follows:
1.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
2.
the first label available.
3.
Press and release the key “UP” or “DOWN” to
select a label.
page 24 of 88
Access the procedure to display the quantity detected by an analogue
input
Page 25
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
The following table shows the correspondence between the
labels and the magn itudes disp layed.
LABEL MAGNITUDE
Pb1
Pb2 evaporator temperature
Pb3 auxiliary temperature; see also parameter P4
Pb4 CPT temperature; see also parameter P4
Pb5 if present, vapour pressure
Pb6 if present, evaporation temperature
Press and release the key “SET”.
4.
To exit the procedure:
5. Press and release the key “SET” or do not operate
6.
Press and release the “UP” or “DOWN” key until
Alternatively:
7. Press and release the “ON/STAND-BY” key.
If the evaporator temperature sensor is not present (or if the
P3 parameter is set to 0), the "Pb2" label shall not be
displayed.
If the auxiliary temperature sensor is not present (or if the P4
parameter is set to 0), the "Pb3" label shall not be displayed.
If the magnitude recorded by the auxiliary sensor is not the
outgoing air temperature (or if the P4 parameter is not set to
4) the "Pb4" label shall not be displayed.
room/inflowing air temperature; see also
parameter P4
for 60 sec.
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
6.5 "Rapid cooling" function
Displaying the magnitude detected by an analogue input
enabling/disabling
To enable/disable the "rapid cooling" function, proceed as
follows:
1.
Check that the device is turned on, that the
keypad is not locked, that no procedures are in
progress and that there are no defrosting, dripping
or evaporator fan stop operations in progress.
Keep the "UP" key pressed for 4 s: the
2.
"temperature" LED light shall start flashing.
page 25 of 88
"Rapid cooling" function enabling/disabling
Page 26
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
During the "rapid cooling" function the work set point is
decreased by the temperature set with the r5 parameter; the
function runs for the span of time set with the r6 parameter.
During the "rapid cooling" function the defrosting function is
never activated; if the defrosting interval expires while the
rapid cooling function is in progress, the defrosting shall be
activated at the end of the cooling.
6.6 Defrosting manual activation
To activate the defrosting in manual mode, proceed as follows:
1.
Check that the device is turned on, that the
keypad is not locked, that no procedures are in
progress and that the "rapid cooling" function is
not in progress.
Keep the "DEFROSTING" key pressed for 4 s.
2.
If the evaporator temperature sensor functions as a defrosting
sensor (that is to say,if the P3 parameter is set to 1) and when
the defrosting starts the evaporator temperature exceeds the
value set with the d2 parameter, the defrosting shall not be
activated.
6.7 Turning on/off of room lights
manually (only if the parameter
Defrosting manual activation
u1 and/or parameter u11 is set at
0)
To turn the room light on/off in manual mode, proceed as
follows:
1.
Make sure no procedures are in progress. Press and release the "AUXILIARY" key: the "room
2.
light" LED shall turn on/off.
Through the digital ports it is also possible to turn the room
light on/off from remote; see parameter u2.
If parameter u1 and/or parameter u11 are set to 2 (that is to
say, if the application managed by the K5 and/or K6 outputs is
the auxiliary output), pressing the "AUXILIARY" key for 2 s
shall make the "auxiliary 1" and/or "auxiliary 2" and the
auxiliary output LEDs turn on/off.
6.8 Turning the demister heating
elements on/off manually (only if
Turning on/off of room lights in manual mode
the parameter u1 and/or
parameter u11 is set at 1)
To turn the demister heating elements on, proceed as follows:
Check that the device is turned on and no
1.
procedures are in progress.
Demister heating elements manual activation
page 26 of 88
Page 27
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
2.
Keep the "AUXILIARY" key pressed for 2 s: the
"AUX1" and/or "AUX2" LEDs shall light up and the
heating elements be turned turned on, both for
the length of time set with the parameter u6.
The demister heating elements cannot be turned off in manual
mode (that is to say, before the time set with the parameter
u6 has expired).
6.9 Turning on/off of the auxiliary
output manually (only if the
parameter u1 and/or parameter
u11 is set at 2)
To turn the auxiliary output on/off in manual mode, proceed
as follows:
1.
Make sure that the keyboard is not locked and that
no procedure is in progress.
2.
Keep the "AUXILIARY" key pressed for 2 s: the
"AUX1" and/or "AUX2" LEDs shall turn on/off.
Through the digital ports it is also possible to turn the auxiliary
output on/off from remote; see parameter u2.
If the auxiliary output has been turned on manually, it shall be
possible to turn it off only in the same mode (similarly, if it
was turned on from renote, it shall be possible to turn it off
only from remote); see also parameter u2.
6.10 Keyboard locking/unlocking
To lock the keyboard proceed as follows:
Check that the device is turned on and no
1.
procedures are in progress.
2.
Keep the "DOWN" and "ON/STAND-BY" keys
pressed for 1 s: the word "Loc" shall be displayed
on screen for 1 s.
If the keyboard is locked, the following are not permitted:
-
device switch-on/off in manual mode display of a magnitude recorded by an analogue
-
input (with the procedure described in paragraph
6.4 “Displaying the magn itude detected by an
analogue input”)
activation/deactivation of “rapid cooling” function
-
-
manual activation of defrosting manual switch on/off of the auxiliary output
-
activation of the low or high relative humidity
-
percentage operation mode to learn how it works
Turning on/off of the auxiliary output manually
Keyboard locking
page 27 of 88
Page 28
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
- see information regarding the HACCP alarms
-
cancellation of HACCP alarm list display of compressor operation hours
-
-
cancellation of compressor operation hours set the working set point (with the procedure
-
described in paragraph “Setting the working set
point”).
The operations cause the display of the label “Loc” for 1 s.
To unlock the keyboard:
Hold the “DOWN” key and the “ON/STAND-BY” key
3.
for 1 s: the display will show the message “UnL”
for 1 s.
6.11 Silencing the buzzer
To silence the buzzer, proceed as follows:
Make sure no procedures are in progress.
1.
Press a key (the first pressing of the key will not
2.
cause the effect associated with that key).
If the parameter u1 and/or the parameter u11 is set at 3 (i.e.
the utility managed by the digital output K5 and/or K6 is the
alarm output) and parameter u4 is set at 1, pressing the key
will also cause the deactivation of the output.
If parameter u9 is set at 0, the buzzer will not be activated.
Silencing the buzzer
page 28 of 88
Page 29
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
7 OPERATION WITH LOW OR
HIGH RELATIVE HUMIDITY
PERCENTAGES (ONLY IF THE F0
PARAMETER IS SET TO 5)
7.1 Preliminary notes
During operation with a low relative humidity percentage, the
evaporator fan shall be turned on if the compressor is on, and
shall turn on cyclically if the compressor is off (the F4
parameter determines the duration of the off phase of the fan
and the F5 parameter determines the on phase).
During operation with a high relative humidity percentage, the
evaporator fan is always on.
7.2 Manual activation of the low
and high relative humidity
percentages operating mode
To activate the the low or high relative humidity percentages
operating mode manually, proceed as follows:
1.
Ensure that the device is on, the keypad is not
locked and that no procedure is in progress.
2.
Keep the "SET" and "UP" keys pressed for
4 s: the letters "rhL" (operation with low relative
humidity percentage) or "rhH" (operation with
high relative humidity percentage) shall be
displayed on screen for 10 s.
To restore the normal display before time:
Press any key.
3.
It is also possible to activate the low or high relative humidity
percentage operation mode with the F6 parameter.
If the F0 parameter is not set to 5, pressing the keys shall
make the message "- - -" appear on display for 1 s.
7.3 Learning the current operating
Manual activation of the low and high relative humidity percentages
operating mode
mode
To learn which operating mode is in progress proceed as
follows:
1.
Check that the device is turned on and no
procedures are in progress.
2.
Press and release the "SET" and "UP" keys: the
letters "rhL" (operat ion with low relative humidity
percentage) or "rhH" (operation with high relative
humidity percentage) sha ll be displayed on screen
for 10 s.
page 29 of 88
Learning the current operating mode
Page 30
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
8 “ENERGY SAVING” FUNCTION
8.1 Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door micro switch input (after the
room temperature has reached the work set point) the
“energy saving” function is activated (until the input is
activated again).
During the “energy saving” function, the work set point is
increased by the temperature established with parameter r4
and the evaporator fan is turned on cyclically, provided that
the F0 parameter is set to 1, 2, 3 or 4 (parameter F13
establishes the duration of fan switch off and parameter F14
that of switch on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).
9 “CPT” FUNCTION
(CALCULATED PRODUCT
TEMPERATURE)
9.1 Preliminary notes
If parameter P4 is set at 4, the temperature associated to the
regulation will mainly depend on the temperature detected by
the inlet air probe and that detected by the air outlet probe,
herein called CPT temperature (Calculated Product
Temperature); the room temperature probe shall operate as
an air inlet temperature probe and the auxiliary temperature
probe as an air outlet temperature probe.
The formula for the calculation of the CPT temperature is:
CPT temperature = {[(value established with parameter P7) x
(temperature detected by the inlet air probe)] : 100} +
{[(100 - value established with parameter P7) x (temperature
detected by the outlet air probe)] : 100}.
10 “HACCP” FUNCTION
10.1 Preliminary notes
The device can memorise the following HACCP alarms:
-
minimum temperature alarm (code “AL”) maximum temperature alarm (code “AH”)
-
door micro switch input alarm (code “id”)
-
-
power supply cut-off alarm (code “PF”; only in the
models with clock).
The device can memorise up to 9 alarms, after which the
oldest alarm is overwritten.
The device supplies the following information for every alarm:
- the crit ical value
the date and time at which the alarm occurs (only
-
in the models with clock)
-
the duration of the alarm (from 1 min to 99 hours
and 59 min, partial if the alarm is in progress).
The following table shows the correspondence between the
alarm codes and the relevant critical values.
CODE CRITICAL VALUE
AL
AH
id
PF
Models without clock update the information regarding the
alarms provided the critical value of the new alarm is more
critical than that stored or provided the informat ion has
already been displayed.
If the device is switched off, no alarms will be stored.
The “HACCP” LED provides information regarding the storage
status of the alarms; see paragraph “Signals”.
the minimum room temperature or the minimum
CPT temperature during the alarm
the maximum room temperature or the
maximum CPT temperature during the alarm
the maximum room temperature or maximum
CPT temperature during any alarm of this type;
see also parameter i4
the room temperature or the CPT temperature
when power supply is restored; see also
parameters A10 and A12
page 30 of 88
Page 31
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
10.2 Display of HACCP alarm
information
To begin the procedure:
1.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
2.
the first label available.
3.
Press and release the "UP" or "DOWN" key to
select “LS”.
4.
Press and release the “SET” key:
in the models without a clock the
4.1
display will show one of the codes
included in the table in paragraph
“Preliminary notes”
in the models with a clock the display
4.2
will show one of the codes included in
the table in paragraph “Preliminary
notes” followed by a number; the
higher the number, the less current
the alarm.
If the device does not have any alarms stored, the label “LS”
will not be displayed.
To select an alarm:
5.
Press and release the “UP” key or the “DOWN”
key.
To see information regarding the alarm:
Press and release the “SET” key: the HACCP LED
6.
will stop flashing and remain on permanently and
the display will show, for example, the following
information in succession:
Access the procedure to display information on the HACCP alarms
Selection of information on the HACCP alarms
INFORM. MEANING
8.0 the critical value is 8.0 °C/8 °F
the display is about to show the date and time
StA
y14 the alarm occurred in 2014 (continue...)
n03
d26
h16 the alarm occurred at 16:00 (continue...)
n30 the alarm occurred at 16:30
at which the alarm occurs (only in the models
with clock)
the alarm occurred in the month of March
(continue...)
the alarm occurred on 26 March 2014
(continue...)
Display of information on the HACCP alarms
page 31 of 88
Page 32
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (continue...)
n15 the alarm lasted 1 hour and 15 min
code the alarm selected
the displays each piece of information for 1 s.
To exit the information sequence:
7. Press and release the “ON/STAND-BY”: the display
will show the alarm selected.
To exit the procedure:
8.
Exit the informat ion sequence. Press and release the “UP” or “DOWN” key until
9.
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Alternatively:
10.
Press and release the “ON/STAND-BY” key.
10.3 Cancelling the HACCP alarm list
To cancel the HACCP alarm list proceed as follows:
1.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
2.
the first label available.
3.
Press and release the "UP" or "DOWN" key to
select “rLS”.
4. Press and release the “SET” key.
5. Press and release the “UP” or “DOWN” key within
15 s to set “149”.
6.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “- - -” for 4
sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label “rLS”
will not be displayed.
Access the procedure to cancel information on the HACCP alarms
Cancelling information on the HACCP alarms
page 32 of 88
Page 33
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
11 COMPRESSOR OPERATING
HOURS COUNT
11.1 Preliminary notes
The device can memorise up to 999 comp. operating hours.
The parameter C10 establishes the number of operating hours
is higher than the limit at which the need for maintenance is
signalled.
11.2 Display of Compressor
Operation Hours
To display the compressor operation hours, proceed as
follows:
Make sure that the keyboard is not locked and that
1.
no procedure is in progress.
2. Hold the key “DOWN” for 1 s: the display will show
the first label available.
3.
Press and release the "UP" or "DOWN" key to
select a label.
The following table shows the correspondence between the
labels and the relevant meaning.
Access the procedure to display the compressor operation hours
LABEL MEANING
CH1 Compressor operation Hours
CH2 Compressor 2 operation Hours
Press and release the “SET” key.
4.
To exit the procedure:
Press and release the “SET” key or do not operate
5.
for 60 sec.
6.
Press and release the “UP” or “DOWN” key until
the display shows the magnitude established with
parameter P5 or do not operate for 60 sec.
Alternatively:
Press and release the “ON/STAND-BY” key.
7.
If the compressor 2 is not present (or if the u1 and/or u11
parameter is not set to 7), the "CH2" labe l shall not be
displayed.
Display the compressor operation hours
page 33 of 88
Page 34
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
11.3 Cancelling the compressor
operation hours
To cancel the compressor operation hours, proceed as follows:
1.
Make sure that the keyboard is not locked and that
no procedure is in progress.
Hold the key “DOWN” for 1 s: the display will show
2.
the first label available.
3.
Press and release the "UP" or "DOWN" key to
select “rCH”.
4.
Press and release the “SET” key. Press and release the “UP” or “DOWN” key within
5.
15 s to set “149”.
6.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “- - -” for 4
sec and the “alarm” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label “rCH”
will not be displayed.
Access the procedure to cancel the compressor operation hours
Cancelling the compressor operation hours
page 34 of 88
Page 35
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
12 SETTINGS
12.1 Setting the date, time and day
of the week (only in the models
with clock)
The date can be set in the day-month-year format; the time in
the hours-minutes format (24 h).
To access the procedure:
1. Make sure that the keyboard is not locked and that
no procedure is in progress.
2.
Hold the key “DOWN” for 1 s: the display will show
the first label available.
3.
Press and release the "UP" or "DOWN" key to
select “rtc”.
To set the year:
Press and release the “SET” key: the display will
4.
show “y” followed by the last two numbers of the
year and the “clock” LED light shall flash.
5. Press and release the “UP” or “DOWN” key within
15 sec.
To set the month:
Press and release the “SET” key when setting the
6.
year: the display will show “n” followed by the
number of the month.
7. Press and release the “UP” or “DOWN” key within
15 sec.
To set the day:
8.
Press and release the “SET” key when setting the
month: the display will show “d” followed by the
number of the day.
9. Press and release the “UP” or “DOWN” key within
15 sec.
To set the hour:
Press and release the “SET” key when setting the
10.
day: the display will show “h” followed by the
number of the hour.
Press and release the “UP” or “DOWN” key within
11.
15 sec.
To set the minute:
12. Press and release the “SET” key when setting the
hour: the display will show “n” followed by the
number of the minute.
13.
Press and release the “UP” or “DOWN” key within
15 sec.
To set the day of the week:
Press and release the “SET” key when setting the
14.
minute: the display will show the first label
available.
Access the procedure for setting the date, time and day of the week
Setting the year
Setting the day
Setting the minute
page 35 of 88
Page 36
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
15. Press and release the key or the key within
15 sec to set:
- Mon” (Monday)
- tuE” (Tuesday)
- UEd” (Wednesday)
- thu” (Thursday)
- Fri” (Friday)
- SAt” (Saturday)
- Sun” (Sunday).
16.
Press and release the “SET”: the "clock" LED shall
turn off, and then the device shall exit the
procedure.
To exit the procedure before the operation is complete:
17.
Do not operate for 60 sec (any changes will be
saved).
12.2 Setting the working set point
To set the working set point, proceed as follows:
1. Make sure that the keyboard is not locked and that
no procedure is in progress.
2.
Press and release the “SET” key: the “compressor”
LED will flash.
Press and release the “UP” or “DOWN” key within
3.
15 sec; see also parameters r1, r2 and r3.
4.
Press and release the “SET” key or do not operate
for 15 sec: the “compressor” LED will switch off
after which, the device will exit the procedure.
To exit the procedure before the operation is complete:
5.
Do not operate for 15 sec (any changes will be
saved).
The working set point can also be set via parameter SP.
12.3 Setting the configuration
Setting the working set point
parameters
To access the procedure:
1.
Make sure no procedures are in progress. Hold the “UP” and “DOWN” key for 4 s: the display
2.
will show “PA”.
3.
Press and release the “SET” key. Press and release the “UP” or “DOWN” key within
4.
15 s to set “-19”.
5.
Press and release the “SET” key and do not
operate for 15 s.
Hold the “UP” and “DOWN” key for 4 s: the display
6.
will show “SP”.
Access the procedure to set the configuration parameters
page 36 of 88
Page 37
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
To select a parameter:
7.
Press and release the “UP” key or the “DOWN”
key.
To set a parameter:
Press and release the “SET” key.
8.
9.
Press and release the “UP” or “DOWN” key within
15 sec.
Press and release the “SET” key and do not
10.
operate for 15 s.
To exit the procedure:
11.
Press and release the “UP” and “DOWN” key for 4
s or do not operate for 60 s (any changes will be
saved).
After setting the parameters, suspend power supply flow to
the device.
Access the procedure to set the configuration parameters
12.4 Restoring the Manufacturer’s
Settings
To restore the manufacturer's settings, proceed as follows:
Make sure no procedures are in progress.
1.
2.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “PA”.
Press and release the “SET” key.
3.
4.
Press and release the “UP” or “DOWN” key within
15 s to set “149”.
Press and release the “SET” key and do not
5.
operate for 15 s.
6.
Hold the “UP” and “DOWN” key for 4 s: the display
will show “dEF”.
7.
Press and release the “SET” key. Press and release the “UP” or “DOWN” key within
8.
15 s to set “1”.
9.
Press and release the “SET” or do not operate for
15 sec: the display will show a flashing “dEF” for 4
sec, after which the device will exit the procedure
10. Cut the device power supply off.
To exit the procedure in advance:
11. Hold the “UP” and “DOWN” key for 4 s during the
procedure (i.e. before setting “1”: Restore will not
be performed).
Make sure that the manufacturer’s settings are appropriate
(see paragraph 12.5 “List of configuration parameters”.
Setting a parameter
Restoring the Manufacturer’s Settings
page 37 of 88
Page 38
P0 0 1 - - - - 1 1 1 1 1 1 1 1
CA5 -25.0 25.0 °C/°F (1)
CA4 -250 250
points/10
(4)
CA3 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 auxiliary temperature offset (see P4)
CA2 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 evaporator temperature offset
CA1 -25.0 25.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
PARAM. MIN. MAX. M.U.
SP r1 r2 °C/°F (1) -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 -18.0 Working set-point; see also r0
PARAM. MIN. MAX. M.U.
The following table shows the meaning of the configuration parameters of the devices.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
12.5 List of configuration parameters
avail.
not
avail.
not
avail.
not
avail.
not
page 38 of 88
avail.
not
avail.
not
0.0 0.0 evaporation temperature offset
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
0 0 vapour pressure offset
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
temperature probe type
0 = PTC
1
= NTC
if P4 = 0, 1, 2 o 3, room temperature offset
if P4 = 4, inlet air temperature offset
MEASUREMENT INPUTS
EVB1256N9
WORKING SETPOINT
Page 39
P5 0 4 - - - - 0 0 0 0 0 0 0 0
P4 0 4 - - - - 3 3 3 3 3 3 3 3
P3 0 2 - - - - 1 1 1 1 1 1 1 1
P2 0 1 - - - - 0 0 0 0 0 0 0 0
P1 0 1 - - - - 1 1 1 1 1 1 1 1
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 39 of 88
degree Celsius decimal point
temperature unit of measurement (2)
evaporator temperature probe function
magnitude displayed during normal operation
4
= temperature recorded by the auxiliary probe (see
= inlet air temperature (only if P4 = 4 )
P4)
= working set-point 2 = evaporator temperature
if P4 = 4, CPT temperature
= if P4 = 0, 1, 2 or 3, room temperature
the CPT (Calculated Product Temperature) one;
see also P7
0
1
3
3
4
= evaporator 2 temperature
= outlet air temperature; in this case the
temperature associated with the setting shall be
2
= critical temperature
1
= condenser temperature
0 = probe absent
2
= probe for evaporator fan thermostating
magnitude recorded by the auxiliary temperature probe
0
= probe absent 1 = defrosting probe and probe for evaporator fan
thermostating
0 = degree Celsius
1
= degree Fahrenheit
1
= YES
Page 40
r2 r1 99.0 °C/°F (1) 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 maximum working set-point
r1 -99.0 r2 °C/°F (1) -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 -50.0 minimum working set-point
r0 0,1 (5) 15.0 °C/°F (1) 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
PARAM. MIN. MAX. M.U.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
P11 0 1 - - - -
P10 P9 999
P9 -999 P10
P8 0 250 s/10 5 5 5 5 5 5 5 5 delay displaying temperature variation
P7 0 100 % 50 50 50 50 50 50 50 50
points/10
(4)
avail.
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
page 40 of 88
EVB1226N9
EVB1236N9
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
points/10
(4)
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
avail.
not
EVB1246N9
EVB1256N9
if u1 and/or u11 7, working set-point differential; see
also r12 (6)
if u1 and/or u11 = 7, proportional band; see also r12 (7)
MAIN REGULATOR
1 1
position of the pressure decimal point
0 = no decimal points
1
= on the tens digit
80 80 pressure transducer maximum setting
5 5 pressure transducer minimum setting
percentage of the temperature detected by the inlet air
for the calculation of the CPT temperature (only ifP4 = 4)
(3)
Page 41
C2 0 240 min 3 3 3 3 3 3 3 3 minimum compressor switch-off duration (9)
C1 0 240 min 5 5 5 5 5 5 5 5
C0 0 240 min 0 0 0 0 0 0 0 0
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
r12 0 1 - - - - 1 1 1 1 1 1 1 1
r6 0 240 min 30 30 30 30 30 30 30 30 duration of “rapid cooling” function; see also r5
r5 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
r4 0.0 99.0 °C/°F (1) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
r3 0 1 - - - - 0 0 0 0 0 0 0 0
EVB1216N9
page 41 of 88
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
locking of working set-point setting (using the procedure
described in paragraph”Setting the working set point”)
working set point increase during the “energy saving"
working set-point decrease during the “rapid cooling”
1
type of r0
delay in switching on of compressor after the device
minimum time between two consecutive compressor
start-ups; also delay in compressor start-up after
conclusion of room temperature/inlet air probe error
(code “Pr1”) (9) (10)
switches on (8)
COMPRESSOR PROTECTION SYSTEM
0 = asymmetric
= symmetric
function; see also r6
function; see also i5, i10, i15, H01... H14
1
= YES
Page 42
C11 0 240 s 3 3 3 3 3 3 3 3
C10 0 999 hx10 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
C8 0 15 min 1 1 1 1 1 1 1 1 blocked compressor alarm delay (code CSd”) (12)
C7 0.0 199 °C/°F (1) 90.0 90.0 90.0 90.0 90.0 90.0 90.0 90.0
C6 0.0 199 °C/°F (1) 80.0 80.0 80.0 80.0 80.0 80.0 80.0 80.0
C5 0 240 min 10 10 10 10 10 10 10 10
C4 0 240 min 10 10 10 10 10 10 10 10
C3 0 240 s 0 0 0 0 0 0 0 0 minimum duration of compressor switch on time
page 42 of 88
(11)
condenser temperature is higher than that at which the
condenser temperature above which the blocked
number of operating hours is higher than the limit at
which the need for maintenance is signalled
minimum time interval between the switching on of two
different compressors (only if u1 and/or u11 = 7)
0
= function absent
compressor alarm is activated (code “CSd”)
condenser overheating alarm is activated (code “COH”)
duration of compressor switch on time during a room
temperature/inlet air probe error (code “Pr1”); see also
C6
duration of compressor switch off time during a room
temperature/inlet air probe error (code “Pr1”); see also
C5
Page 43
C14 0 1 - - - - 0 0 0 0 0 0 0 0
C13 0 10 - - - - 1 1 1 1 1 1 1 1
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
C12 0 10 - - - - 2 2 2 2 2 2 2 2
page 43 of 88
1 = FROM DIGITAL INPUT - the compressor and the
pump down valve shall be switched on at the
same time due to the setting; the pump down
valve shall be turned off due to the setting and
the compressor afterwards and as a consequence
of the activation of the multifunction or
multifunction 2 input (only if i5 or
i15 = 6); see also u3
the valve switch-off
to the setting; the pump down valve shall be
turned off due to the setting and the compressor
after the expiration of the u3 time interval from
type of pump down (only if u1 and/or u11 = 10)
0 = TIMED - the compressor and the pump down
valve shall be switched on at the same time due
the number of switch-ons of the two compressors ; see
also C12 (only if u1 and/or u11 = 7)
incidence of the switch-ons of the compressor on the
choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
the number of switch-ons of the two compressors ; see
also C13 (only if u1 and/or u11 = 7)
incidence of the number of compressor operation hours
on the choice of compressor to be switched on/off when
attempting to balance the number of operation hours and
Page 44
d3 0 99 min 30 30 30 30 30 30 30 30
d2 -99 99.0
°C/°F
(1)
d1 0 2 - - - - 0 0 0 0 0 0 0 0
d0 0 99 h 8 8 8 8 8 8 8 8
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
PARAM. MIN. MAX. M.U.
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
page 44 of 88
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
if P3 = 0 o 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0
= defrosting will not be activated
d3
temperature at end of defrosting (only if P3 = 1); see also
evaporator fan activity will depend on parameter
F2
2
= VIA STOPPING OF COMPRESSOR - during
defrosting the compressor will remain switched off
and the defrosting output will remain deactivated;
on parameter F2
1
= BY HOT GAS - during defrosting the compressor
will be switched on and the defrosting output will
be activated; evaporator fan activity will depend
activated; evaporator fan activity will depend on
parameter F2
type of defrosting
0
= ELECTRIC - during defrosting the compressor will
remain off and the defrosting output will be
d8 = 3, maximum defrost interval
if d8 = 0, 1 or 2, defrosting interval (13)
0 = interval defrosting will never be activated
DEFROSTING
Page 45
d7 0 15 min 2 2 2 2 2 2 2 2
d6 0 2 - - - - 1 1 1 1 1 1 1 1
d5 0 99 min 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
d4 0 1 - - - - 0 0 0 0 0 0 0 0
page 45 of 88
during dripping the compressor will remain switched off
and the defrosting output will remain deactivated; if d16
= 0, evaporator fan activity will depend on parameter F2;
if d16 0, the evaporator fan will remain switched off)
2 = indication “dEF” (16)
+ t”; if on activation of defrosting, the room
temperature or CPT temperature is above “work
set point + t”, at maximum the room temperature
or CPT temperature on activation of defrosting
(14) (15)
1
temperature displayed during defrosting (only if P5 = 0)
0
= room temperature or CPT temperature
= if on activation of defrosting, the room
temperature or CPT temperature is below the
“work set point + t”, at maximum “ work set point
switched on (8)
if d4 = 0, minimum time between switching on of device
and activation of defrosting (8)
if d4 = 1, delay in activation of defrosting after device is
1
= YES
defrosting when device is switched on (only if d8 = 0, 1, 2
or 3) (8)
Page 46
d11 0 1 - - - - 0 0 0 0 0 0 0 0
d9 -99 99.0
°C/°F
(1)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
d8 0 4 - - - - 0 0 0 0 0 0 0 0
page 46 of 88
temperature has remained below the temperature
2 = AT INTERVALS - FOR EVAPORATOR TEMPERATURE
- defrosting will be activated when the evaporator
1 = AT INTERVALS - FOR COMPRESSOR SWITCH-ON -
defrosting will be activated once the compressor
has altogether been switched on for time d0
d0
defrosting activation methods
0
= AT INTERVALS - defrosting will be activated once
the device has altogether been running for time
1
= YES
absence of an evaporator temperature probe (code “Pr2”)
visible in models EVB1204N9, EVB1206N9,
4
= IN REAL TIME - defrosting will be activated at the
times established in parameters Hd1... Hd6 (not
evaporator temperature; see also d18, d19, d20
and d22 (17)
defrosting alarm switches off once maximum time limit
has been reached (code “dFd”; only if P3 = 1 and in
evaporator temperature is higher than that at which the
defrost interval counter is suspended (only if d8 = 2)
EVB1226N9 and EVB1246N9)
3
= ADAPTABLE - defrosting will be activated at
intervals, whose duration will each time depend
on the duration of compressor switch-ons and the
d9 for a total time of d0 (17)
Page 47
d20 0 500 min 180 180 180 180 180 180 180 180
d19 0.0 40.0
°C/°F
(1)
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
d18 0 999 min 40 40 40 40 40 40 40 40
d16 0 99 min 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
d15 0 99 min 0 0 0 0 0 0 0 0
page 47 of 88
minimum time that the compressor must be switched on
predripping duration (during predripping the compressor
will remain switched off, the defrosting output will be
minimum consecutive time the compressor must be
switched on such as to provoke the defrost activation
0
= defrosting will never be activated due to the effect
of this condition
(only if d8 = 3)
average, or “evaporator temperatures average - d19”)
activated (relative to the evaporator temperatures
evaporator temperature above which the defrost is
0
= defrosting will never be activated due to the effect
of this condition
defrosting interval (only if d8 = 3; defrosting will be
activated when the compressor has been on totally, with
the evaporator temperature below that of d22, for time
d18)
activated and the evaporator fan will remain switched off)
before defrosting can be activated (only if d1 = 1) (18)
Page 48
d26 0 99 h 6 6 6 6 6 6 6 6
d25 0 1 - - - - 0 0 0 0 0 0 0 0
d22 0.0 10.0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
d21 0 500 min 200 200 200 200 200 200 200 200
page 48 of 88
minimum consecutive time the compressor must be
switched on after the insturment switches on (on
condition that the difference “cell temperature - working
setpoint” is higher than 10 °C/20 °F) and after function
Overcooling is activated such as to provoke the defrost
activation
enabling of the outlet air temperature probe as defrosting
probe during the evaporator temperature probe error
defrosting interval for effect of enabling of outlet air
temperature probe like defrosting probe during evaporator
temperature probe error (code “Pr2”; only if P4 = 4), if
d25 = 1 (13)
0
= defrosting will never be activated due to the effect
of this condition
(code “Pr2”; only if P4 = 4); see also d26 (19)
average + d22”) (only if d8 = 3)
evaporator temperature above which the time d18 count
is paused (relating to the average of evaporator
temperatures, that is to say, "evaporator temperatures
0
= the defrost will never be activated because the
compressor has been switched on
Page 49
A6 0 240 min 120 120 120 120 120 120 120 120
A5 0 2 - - - - 1 1 1 1 1 1 1 1
A4 -99.0 99.0
A2 0 2 - - - - 1 1 1 1 1 1 1 1
A1 -99.0 99.0
A0 0 1 - - - - 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
PARAM. MIN. MAX. M.U.
°C/°F
(1)
10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
page 49 of 88
(1)
-10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0 -10.0
°C/°F
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
delay in maximum temperature alarm (code “AH”) after
the device is switched on (8)
2
= absolute (that is A4)
point + A4”; consider A1 without sign)
type of maximum temperature alarm (code “AH”)
0
= alarm absent 1 = relative to working set-p oint (that is “working set-
temperature higher than that at which the maximum
temperature alarm is activated (code “AH”); see also A5
and A11
2
= absolute (that is A1)
point - A1”; consider A1 without sign)
type of minimum temperature alarm (code “AL”)
0
= alarm absent 1 = relative to working set-p oint (that is “working set-
temperature below that at which the minimum
temperature alarm is activated (code “AL”); see also A0,
A2 and A11
1
= evaporator temperature (20)
0
= room temperature or CPT temperature
temperature associated with the minimum temperature
alarm (code “AL”)
TEMPERATURE ALARMS
Page 50
avail.
A12 0 2 - - - -
not
1
A11 0.1 (5) 15.0
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 differential of parameters A1 and A4
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
A10 0 240 min 1
A9 0 240 min 15 15 15 15 15 15 15 15
A8 0 240 min 15 15 15 15 15 15 15 15
A7 0 240 min 15 15 15 15 15 15 15 15 temperature alarm delay (code AL” and code “AH”)
avail.
not
1
page 50 of 88
and by the “HACCP” LED
avail.
not
1
avail.
not
1
1
2
= alarm will be signalled by the “PF” code, buzzer
(as long as cut-off duration exceeds time A10)
buzzer and the “HACCP” LED
type of power supply cut-off alarm signal (code “PF”)
0
= alarm will be signalled by the “HACCP” LED
= alarm will be signalled by the “PF” code, the
avail.
avail.
avail.
to be memorised (code “PF”)
not
1
not
1
not
1
duration of a power cut such to cause the power cut alarm
delay in maximum temperature alarm (code “AH”)
following the deactivation of the door micro switch input
(22)
delay in maximum temperature alarm (code “AH”) from
the conclusion of evaporator fan standstill (21)
Page 51
F2 0 2 - - - - 0 0 0 0 0 0 0 0
F1 -99.0 99.0
°C/°F
(1)
F0 0 5 - - - - 1 1 1 1 1 1 1 1
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
PARAM. MIN. MAX. M.U.
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
page 51 of 88
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
evaporator temperature above the limit at which the
evaporator fan is switched off (only if F0 = 3 o 4); see
2
= depending on F0
recommended)
evaporator fan activity during defrosting and dripping
0
= switched off 1 = switched on (setting parameter d7 to 0 is
also F8
5 = depending on F6; see also F9
dependent on F1 if the compressor is switched on;
see also F9, F13, F14 and i10 (25) (27)
3
4
= depending on F1; see also F9, F13, F14 and i10
= switched off if the compressor is switched off,
F14 and i10 (24)
(25) (26)
evaporator fan activity during normal operation
0
= switched off 1 = switched on; see also F13, F14 and i10 (23) 2 = in parallel with the compressor; see also F9, F13,
EVAPORATOR FAN AND CONDENSER FAN
Page 52
F7 -99.0 99.0
°C/°F
(1)
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
F6 0 1 - - - - 0 0 0 0 0 0 0 0
F5 0 240 s 10 10 10 10 10 10 10 10
F4 0 240 s 60 60 60 60 60 60 60 60
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
F3 0 15 min 0 0 0 0 0 0 0 0
page 52 of 88
evaporator temperature below which the evaporator fan is
restarted (in respect to the working set point, that is to
say “working set-point + F7”); see also F3
1
= high relative humidity (dur ing operation in high
relative humidity conditions the evaporator fan
shall function in parallel with the compressor; see
also F4 and F5)
relative humidity conditions the evaporator fan
shall be switched on)
operation in low or high relative humidity conditions (only
if F0 = 5) (28)
0
= low relative humidity (during operation in low
duration of evaporator fan activation during operation in
low relative humidity conditions with the compressor
switched off; see also F4 (only if F0 = 5)
duration of evaporator fan deactivation during operation
in low re lative humidity conditions with the compressor
switched off; see also F5 (only if F0 = 5)
remain deactivated and the evaporator fan will remain
switched off)
compressor can be switched on, the defrosting output will
maximum duration of evaporator fan deactivation; see
also F7 (during evaporator fan deactivation the
Page 53
F14 0 240 sx10 30 30 30 30 30 30 30 30
F13 0 240 sx10 30 30 30 30 30 30 30 30
F12 0 240 s 30 30 30 30 30 30 30 30
F11 0.0 99.0
F9 0 240 s 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
F8 0.1 (5) 15.0
°C/°F
(1)
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
page 53 of 88
°C/°F
(1)
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 F1 differential
duration of evaporator fan switch on during “energy
saving” function, see also F13, i10, H01... H14 (only if F0
= 1, 2, 3 or 4)
= 1, 2, 3 or 4)
temperature of the condenser above which the condenser
fan is switched on (“F11 + 2,0 °C/4 °F, only if u1 and/or
u11 = 6) (29) (30)
delay in the switchin g off of evaporator fan following the
switching off of the compressor (only if F0 = 2, 4 and 5)
delay in the switching off of condenser fan following the
switching off of the compressor (only if u1 and/or u11 =
6)
duration of evaporator fan switch off during “energy
saving” function, see also F14, i10, H01... H14 (only if F0
Page 54
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
EVB1216N9
page 54 of 88
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
DIGITAL INPUTS
Page 55
i0 0 5 - - - - 3 3 3 3 3 3 3 3
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 55 of 88
5
= SWITCH-OFF OF THE EVAPORATOR FAN AND
SWITCH ON OF ROOM LIGHT - the evaporator fan
will be switched off (at maximum for time i3 or
until the input is deactivated) and the room light
shall be switched on (in the EVB1204N9 and
EVB1214N9 models only if
u1 = 0; the light shall be switch ed off after 10 s
from input deactivation)
EVB1214N9 models only if
u1 = 0; the light shall be switch ed off after 10 s
from input deactivation) (31)
will be switched off (at maximum for time i3 or
until the input is deactivated) and the room light
shall be switched on (in the EVB1204N9 and
4
= SWITCH-OFF OF THE COMPRESSOR AND
be switched off after 10 s from input deactivation)
EVAPORATOR FAN AND SWITCH ON OF ROOM
LIGHT - the compressor and the evaporator fan
3 = SWITCH ON OF ROOM LIGHT - the room light
shall be switched on (in the EVB1204N9 and
EVB1214N9 models only if u1 = 0; the light shall
2
= SWITCH-OFF OF THE EVAPORATOR FAN - the
evaporator fan will be switched off (at maximum
for time i3 or until the input is deactivated)
EVAPORATOR FAN - the compressor and the
evaporator fan will be switched off (at maximum
for time i3 or until the input is deactivated) (31)
1
= SWITCH-OFF OF THE COMPRESSOR AND
effect caused by the activation of the door micro input;
see also i4 (0 = no effect)
Page 56
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
i4 0 1 - - - - 0 0 0 0 0 0 0 0
i3 -1 120 min 15 15 15 15 15 15 15 15
i2 -1 120 min 30 30 30 30 30 30 30 30
i1 0 1 - - - - 0 0 0 0 0 0 0 0
page 56 of 88
1
type of door micro switch input contact
1
= YES
delay in signalling of door micro switch input alarm (code
id”)
maximum duration of the effect caused by the activation
of the door micro switch input on the compressor and the
storage of door micro switch input alarm (code “id”) (32)
evaporator
-1
= the alarm will not be signalled
0 = normally open (active input with closed contact)
= normally closed (act ive input with open contact)
Page 57
i5 0 9 - - - - 7 7 7 7 7 7 7 7
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 57 of 88
5 = SWITCHING OFF THE DEVICE - the device will be
switched off (until the input is deactivated)
4
= SWITCHING ON THE AUXILIARY OUTPUT - the
auxiliary output will be switched on (only if u1
and/or u11 = 2, until the input is deactivated)
deactivated and the device is switched off and re-
started or until the power supply is interrupted);
see also i7 and i9
switched on (only if u1 and/or u11 = 6), the
display will show the flashing code “iSd” and the
buzzer will be activated (until the input is
has been activated the number of times
established with parameter i8 the regulators will
be switched off, the condenser fan will be
u1 and/or u11 = 6), the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated): when the input
3
= ACTIVATION OF THE MAXIMUM PRESSURE
(until the input is deactivated)
SWITCH ALARM - the compressor will be switched
off, the condenser fan will be switched on (only if
2
= ACTIVATION OF MULTIFUNCTION INPUT ALARM -
running; see also r4
once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated
the “energy saving” function will be activated (just
with effect on the compressor, until the input is
deactivated), provided the "rapid cooling" is not
effect caused buy the activat ion of the mult ifunction input
(33)
0
= no effect 1 = ACTIVATION OF “ENERGY SAVING” FUNCTION -
Page 58
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
i7 0 120 min 0 0 0 0 0 0 0 0
i6 0 1 - - - - 0 0 0 0 0 0 0 0
i5 0 9 - - - - 7 7 7 7 7 7 7 7
page 58 of 88
1
type of multifunction input contact
if i5 and/or i15 = 2, mult ifunction input alarm delay (code
iA”)
if i5 and/or i15 = 3, delay in compressor switching on
after the deactivation of the multifunction input (34)
0 = normally open (active input with closed contact)
= normally closed (act ive input with open contact)
activated (until the input is deactivated)
flashing code “MiC” and the buzzer will be
9
= MAN IN COLD ROOM ALARM ACTIVATION - the
man in cold room output shall be turned on (only
if u1 and/or u11 = 12), the display will show the
code “C2t” and the buzzer will be activated (until
the input is deactivated)
8
= COMPRESSOR 2 THERMAL PROTECTION - the
be activated (until the input is deactivated)
compressor 2 will be switched off (only if u1
and/or u11 = 7), the display will show the flashing
show the flashing code “C1t” and the buzzer will
compressor will be switched off, the display will
7
= COMPRESSOR THERMAL PROTECTION - the
6
= ACTIVATION OF THE MINIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the display will show the flashing code “LP”
and the buzzer will be activated (until the input is
deactivated); if u1 and/or u11 = 10, the
compressor will be switched off after the pump
down valve has switched off (also look at C14 and
i17)
Page 59
i14 0 240 - - - - 32 32 32 32 32 32 32 32
i13 0 240 - - - - 180 180 180 180 180 180 180 180
i10 0 999 min 0 0 0 0 0 0 0 0
i9 1 999 min 240 240 240 240 240 240 240 240
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
i8 0 15 - - - - 0 0 0 0 0 0 0 0
page 59 of 88
time that must pass in absence of door micro switch input
activations (after the room temperature or COT
temperature has reached the working set-point) for the
“energy saving” function to be activated (this impacts the
evaporator fan only if F0 = 1, 2, 3 or 4); see also r4, HE2
and H01... H14
number of door switch input activations such as to
provoke the defrost activation
minimum duration of the door switch input activation such
as to provoke the defrost activation
0
= defrosting will never be activated due to the effect
of this condition
0
= defrosting will never be activated due to the effect
of this condition
0
= the function will never be activated due to the
effect of this condition
time that must pass in absence of multifunction in put
alarms (code “iA”) so that the alarm counter is reset (only
i5 and/or i15 = 3)
0 = function disabled
number of multifunction input alarms (code “iA”) such to
cause a pressure switch alarm (code “iSd”) (only if i5
and/or i15 = 3)
Page 60
i15 0 9 - - - - 9 9 9 9 9 9 9 9
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 60 of 88
5 = SWITCHING OFF THE DEVICE - the device will be
switched off (until the input is deactivated)
4
= SWITCHING ON THE AUXILIARY OUTPUT - the
auxiliary output will be switched on (only if u1
and/or u11 = 2, until the input is deactivated)
deactivated and the device is switched off and re-
started or until the power supply is interrupted);
see also i7 and i9
switched on (only if u1 and/or u11 = 6), the
display will show the flashing code “iSd” and the
buzzer will be activated (until the input is
has been activated the number of times
established with parameter i8 the regulators will
be switched off, the condenser fan will be
u1 and/or u11 = 6), the display will show the
flashing code “iA” and the buzzer will be activated
(until the input is deactivated): when the input
3
= ACTIVATION OF THE MAXIMUM PRESSURE
(until the input is deactivated)
SWITCH ALARM - the compressor will be switched
off, the condenser fan will be switched on(only if
2
= ACTIVATION OF MULTIFUNCTION INPUT ALARM -
once time i7 has passed the display will show the
flashing code “iA” and the buzzer will be activated
is not running; see also r4
the “energy saving” function will be activated (just
with effect on the compressor, until the input is
deactivated), provided the "rapid cooling" function
effect caused buy the activat ion of the mult ifunction input
2 (33)
0
= no effect 1 = ACTIVATION OF “ENERGY SAVING” FUNCTION -
Page 61
i17 0 240 s 30 30 30 30 30 30 30 30
i16 0 1 - - - - 0 0 0 0 0 0 0 0
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
i15 0 9 - - - - 9 9 9 9 9 9 9 9
page 61 of 88
1
type of multifunction 2 input contact
minimum pressure switch alarm delay after the
compressor switches on (code “LP”)
0 = normally open (active input with closed contact)
= normally closed (act ive input with open contact)
activated (until the input is deactivated)
flashing code “MiC” and the buzzer will be
9 = MAN IN COLD ROOM ALARM ACTIVATION - the
u11 = 7), the display will show the flashing code
C2t” and the buzzer will be activated (until the
input is deactivated)
man in cold room output shall be turned on (only
if u1 and/or u11 = 12), the display will show the
8
= COMPRESSOR 2 THERMAL PROTECTION - the
be activated (until the input is deactivated)
compressor will 2 be switched off (only if u1
and/or
show the flashing code “C1t” and the buzzer will
compressor will be switched off, the display will
7
= COMPRESSOR THERMAL PROTECTION - the
and the buzzer will be activated (until the input is
deactivated); if u1 and/or u11 = 10, the
compressor will be switched off after the switching
off of the pump down valve (also look at C14 and
i17)
6
= ACTIVATION OF THE MINIMUM PRESSURE
SWITCH ALARM - the compressor will be switched
off, the display will show the flashing code “LP”
Page 62
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
EVB1216N9
page 62 of 88
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
DIGITAL OUTPUTS
Page 63
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
u1 0 12 - - - - 0 0
avail.
not
avail.
not
page 63 of 88
11
12
= MAN IN COLD ROOM - in this ca se parameters i5
will assume significance (42)
and i15 will assume significance of
10
= PUMP DOWN VALVE - in this case parameters
= ON/STAND-BY - in this case “ON/STAND-BY” key
C14 and u3 will assume significance of
and F (39) will assume significance of
8 = DEFROSTING 2 - in this case parameters P4 and d
9
= EVAPORATOR FAN 2 - in this case parameters P4
(38) will assume significance
7
= COMPRESSOR 2 - in this case, parameters r0,
r12, C11, C12 and C13 (37) will assume
significance of
avail.
not
avail.
not
avail.
not
avail.
not
6
= CONDENSER FAN - in this case parameters P4,
F11 and F12 will be activated
OPERATION - in this case parameter u7 will be
activated
5
= HEATING ELEMENTS FOR NEUTRAL AREA
4
= DOOR HEATING ELEMENTS - in this case
be activated
parameter u5 will be activated
3 = ALARM OUTPUTS - in this case parameter u4 will
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
1
= DEMISTER HEATING ELEMENTS - in this case the
“AUXILIARY” key and parameter u6 will be
activated
operation controlled by digital output K4 (35) (36)
0
= ROOM LIGHT - in this case the “AUXILIARY” key
and parameters i0 and u2 will be activated
Page 64
u1 0 12 - - - -
avail.
not
avail.
not
6 6 6 6 6 6
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
page 64 of 88
12
11
10
= PUMP DOWN VALVE - in this case, parameters
= ON/STAND-BY - in this case “ON/STAND-BY” key
= MAN IN COLD ROOM - in this case, parameters i5
will assume significance (42)
and i15 will assume significance of
C14 and u3 will assume significance of
and F (39) will assume significance of
8 = DEFROSTING 2 - in this case parameters P4 and d
9
= EVAPORATOR FAN 2 - in this case parameters P4
(38) will assume significance
7
6
= CONDENSER FAN - in this case parameters P4,
= COMPRESSOR 2 - in this case, parameters r0,
r12, C11, C12 and C13 (37) will assume
significance of
F11 and F12 will be activated
5
= HEATING ELEMENTS FOR NEUTRAL AREA
OPERATION - in this case parameter u7 will be
activated
parameter u5 will be activated
4
= DOOR HEATING ELEMENTS - in this case
3 = ALARM OUTPUTS - in this case parameter u4 will
be activated
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
“AUXILIARY” key and parameter u6 will be
activated
application managed by the K5 digital output (35) (36)
0
= reserved 1 = DEMISTER HEATING ELEMENTS - in this case the
Page 65
u7 -99.0 99.0
u6 1 120 min 5 5 5 5 5 5 5 5
u5 -99.0 99.0
u4 0 1 - - - - 1 1 1 1 1 1 1 1
u3 0 240 s 10 10 10 10 10 10 10 10
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
u2 0 1 - - - - 0 0 0 0 0 0 0 0
°C/°F
(1)
-5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
page 65 of 88
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
duration of demister heating elements activation (in
models EVB1204N9 and EVB1214N9 only if u1 = 1, in the
neutral area value (relative to the work set-point, i.e.
“work set-point + u7) (in models EVB1204N9 and
EVB1214N9 only if u1 = 5, in the remaining models only if
u1 and/or u11 = 5) (41)
remaining models only if u1 an d/or u11 = 1)
u1 = 4, in the remaining models only if u1 and u11 = 4).
room temperature or CPT temperature below which the
door heating elements are turned on ("u5 - 2.0°C/4°F in
models EVB1204N9 and EVB1214N9 only if
1
= YES
enabling of alarm output deactivation with the silencing of
the buzzer (in models EVB1204N9 and EVB1214N9 only if
u1 = 3, in the remaining models only if u1 and/or u11 =
3)
switch-off and compressor switch-off
if C14 = 0 compressor switch-off delay after pump down
valve switch-off
if C14 = 1 maximum delay between pump down valve
1
= YES
activation of room light switch on/off (in models
EVB1204N9 and EVB1214N9 only if u1 = 0) or of the
auxiliary output (in models EVB1204N9 and EVB1214N9
only if u1 = 2, in the remaining models only if u1 and/or
u11 = 2) in manual mode with the device turned off (40).
Page 66
u11 0 12 - - - -
avail.
not
avail.
not
3 3 3 3 3 3
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
u9 0 1 - - - - 1 1 1 1 1 1 1 1
page 66 of 88
12
11
10
= PUMP DOWN VALVE - in this case, parameters
= ON/STAND-BY - in this case “ON/STAND-BY” key
= MAN IN COLD ROOM - in this case, parameters i5
will assume significance (42)
and i15 will assume significance of
C14 and u3 will assume significance of
and F (39) will assume significance of
8
9
= EVAPORATOR FAN 2 - in this case parameters P4
d (38) will assume significance
7
6
= CONDENSER FAN - in this case parameters P4,
= COMPRESSOR 2 - in this case, parameters r0,
= DEFROSTING 2 - in this case, parameters P4 and
r12, C11, C12 e C13 (37) will assume significance
F11 and F12 will be activated
5
= HEATING ELEMENTS FOR NEUTRAL AREA
OPERATION - in this case parameter u7 will be
activated
parameter u5 will be activated
4
= DOOR HEATING ELEMENTS - in this case
3 = ALARM OUTPUTS - in this case parameter u4 will
be activated
2 = AUXILIARY OUTPUT - in this case the “AUXILIARY”
key and parameters i5, i15 and u2 will be
activated
“AUXILIARY” key and parameter u6 will be
activated
application managed by the K6 digital output (35) (36)
0
= reserved 1 = DEMISTER HEATING ELEMENTS - in this case the
1
= YES
buzzer activation
Page 67
H05 0 23 h
H04 0 24 h
H03 0 23 h
H02 0 24 h
H01 0 23 h
HE2 0 999 min 0 0 0 0 0 0 0 0
PARAM. MIN. MAX. M.U.
Hr0 0 1 - - - -
PARAM. MIN. MAX. M.U.
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
avail.
not
0
avail.
not
0
page 67 of 88
avail.
not
0
avail.
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
avail.
0
avail.
0
avail.
0
avail.
avail.
not
not
not
not
not
0
avail.
not
0
avail.
not
0
avail.
not
EVB1204N9
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
avail.
not
EVB1204N9
1
avail.
1
avail.
1
avail.
not
not
not
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
0
activation time of the “energy saving” function every
Wednesday; see also r4, F13, F14 and H06
0
duration of the “energy saving” function every Tuesday;
see also H03
0
activation time of the “energy saving” function every
Tuesday; see also r4, F13, F14 and H04
0
duration of the “energy saving” function every Monday;
see also H01
0
Monday; see alsor4, F13, F14 and H02
EVB1256N9
maximum duration of the “energy saving” function
activated due to the effect of absence of door micro
switch input activation; see also i10
activation time of the “energy saving” function every
0
= the function will last until the input is activated
ENERGY SAVING
1
1
= YES
clock activation, together with the functions that require it
EVB1256N9
CLOCK
Page 68
H14 0 24 h
H13 0 23 h
H12 0 24 h
H11 0 23 h
H10 0 24 h
H09 0 23 h
H08 0 24 h
H07 0 23 h
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
H06 0 24 h
avail.
not
0
avail.
not
0
page 68 of 88
avail.
not
0
avail.
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
avail.
0
avail.
0
avail.
0
avail.
avail.
not
not
0
avail.
not
not
0
avail.
not
not
0
avail.
not
not
avail.
0
avail.
0
avail.
0
avail.
avail.
not
not
0
avail.
not
not
0
avail.
not
not
0
avail.
not
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
avail.
not
0
avail.
not
0
avail.
not
0
avail.
not
0
duration of the “energy saving” function every Sunday;
see also H13
0
activation time of the “energy saving” function every
Sunday; see also r4, F13, F14 and H14
0
duration of the “energy saving” function every Saturday;
see also H11
0
activation time of the “energy saving” function every
Saturday; see also r4, F13, F14 and H12
0
duration of the “energy saving” function every Friday; see
also H09
0
activation time of the “energy saving” function every
Friday; see also r4, F13, F14 and H10
0
duration of the “energy saving” function every Thursday;
see also H07
0
activation time of the “energy saving” function every
Thursday; see also r4, F13, F14 and H08
0
duration of the “energy saving” function every
Wednesday; see also H05
Page 69
Hd6 h0 h-- h
Hd5 h0 h-- h
Hd4 h0 h-- h
Hd3 h0 h-- h
Hd2 h0 h-- h
Hd1 h0 h-- h
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
PARAM. MIN. MAX. M.U.
avail.
not
h--
avail.
not
h--
page 69 of 88
avail.
not
h--
avail.
not
avail.
not
h--
avail.
not
h--
avail.
not
h--
avail.
not
avail.
not
h--
avail.
not
h--
avail.
not
h--
avail.
not
avail.
not
h--
avail.
not
h--
avail.
not
h--
avail.
not
avail.
not
h--
avail.
not
h--
avail.
not
h--
avail.
not
avail.
not
EVB1204N9
h--
avail.
h--
avail.
h--
avail.
not
not
not
EVB1214N9
EVB1206N9
EVB1216N9
EVB1226N9
EVB1236N9
EVB1246N9
h--
time of activation of sixth daily defrosting (only if d8 = 4)
h--
= the sixth defrosting will not be activated
h--
time of activation of fifth daily defrosting (only if d8 = 4)
h--
= the fifth defrosting will not be activated
h--
time of activation of fourth daily defrosting (only if d8 =
4)
h--
= the fourth defrosting will not be activated
h--
time of activation of third daily defrosting (only if d8 = 4)
h--
= the third defrosting will not be activated
h--
time of activation of second daily defrosting (only if d8 =
4)
h--
= the second defrosting will not be activated
h--
h--
time of activation of first daily defrosting (only if d8 = 4)
EVB1256N9
DEFROSTING IN REAL TIME
= the first defrosting will not be activated
Page 70
(6)
if parameter r12 is set to 0, the compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0" and will be switched off when the
temperature falls below the working set-point; if parameter r12 is set to 1, the compressor will be switched on when the room temperature or CPT temperature is above the “working set-point
+ r0/2” and will be switched off when the temperature falls below the "working set-point - r0/2”
CPT temperature = {[(P7) x (temperature detected by the inlet air probe)] + [(100 - P7) x (temperature detected by the outlet air probe)] : 100}
(5)
Properly set the parameters corresponding to the regulators after setting parameter P2
The formula for the calculation of the CPT temperature is:
the parameter is a dimensional and is expressed in tenths (for instance, 1 = 0.1 bar, 10 = 1 bar, etc...); the position of the decimal point depends on parameter P11 .
the value depends on parameter P2 (0,1 °C or 1 °F)
Notes:
(1)
the unit of measurement depends on P2
LP 0 2 - - - 2 2 2 2 2 2 2 2
Lb 0 3 - - - - 2 2 2 2 2 2 2 2
LA 1 247 - - - - 247 247 247 247 247 247 247 247 device address
PARAM. MIN. MAX. M.U.
EVB1204N9
EVB1214N9
EVB1206N9
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
(2)
(3)
(4)
EVB1216N9
page 70 of 88
EVB1226N9
EVB1236N9
EVB1246N9
EVB1256N9
baud rate
parity
0
= none (no parity) 1 = odd 2 = even
0
= 2.400 baud 1 = 4.800 baud 2 = 9.600 baud 3 = 19.200 baud
RS-485 MODBUS
Page 71
(28)
the parameter can be changed also by implementing the procedure described in paragraph “Setting the configuration parameters”
(27)
parameters F13 and F14 have effect when the compressor is on and the temperature of the evaporator is below the temperature established with parameter F1
(26)
parameters F13 and F14 have effect when the evaporator temperature is below the temperature established with parameter F1
(25)
if parameter P3 is set at 0, the device will function as if parameter F0 were set at 2
(24)
parameters F13 and F14 have effect when the compressor is on
(23)
parameters F13 and F14 have effect when the compressor is off
(22)
during activation of the door microswitch input, the maximum temperature alarm is absent, provided the alarm was signaled after the activation of the input
(21)
during defrosting and dripping and when the evaporator fan is stopped, the temperature alarms are absent, provided that these were signalled after the activation of defrosting
(20)
if parameter P3 is set at 0, the device will function as if parameter A0 were set at 0 but it will not store the alarm
(19)
if parameter C1 is set at 0, the delay after the end of the room temperature/inlet air proble error will be 2 min
the parameter differential is 2,0 °C/4 °F
if when the device is switched on, the condenser temperature is already above that established in parameter C7, then parameter C8 will not have effect
the device memorises the defrosting interval count every 30 minutes; the setting of parameters d0 and d26 has effect from the conclusion of the previous defrosting interval or the activation of
the display restores normal operation when, on conclusion of evaporator fan standstill, the room temperature or CPT temperature drops below that which has blocked the display (or if a
the value of t depends on parameter r12 (r0 if r12 = 0, r0/2 if r12 = 1)
if parameter P3 is set at 0 or 2, the device will function as if parameter d8 were set at 0
if when defrosting is activated, the operating duration of the compressor is less than the time established with parameter d5, the compressor will remain on for the amount of time necessary to
if parameter d8 is set at 2 or 3, the device will operate as if the parameter as been set at 0 and defrosting will be activated when the device has been on totally for the time established with
defrosting in manual mode
complete defrosting
parameter d26
temperature alarm occurs)
the choice of which compressor to switch on/off depends on parameters C12 and C13
the parameter has effect even after an interruption in the power supply that occurs while the device is switched on
the time established with the parameter is counted even when the device is switched off
"working set-point - r0/2"
- a compressor will be switched on when the room temperature or CPT temperature is above the working set-point and another when the temperature is above the "working set-point
- a compressor will be switched off when the room temperature or CPT temperature falls below the "working set-point + r0/2" and another when the temperature is below the
+ r0/2"
- a compressor will be switched off when the room temperature or CPT temperature falls below the "working set-point + r0/2" and another when the temperature is below the
if parameter r12 is set to 1:
working set-point
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16) the display restores normal operation on conclusion of evaporator fan standstill (or if a temperature alarm occurs)
(17)
(18)
(7)
- a compressor will be switched on when the room temperature or CPT temperature is above the "working set-point + r0/2" and another when the temperature is above the "working
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
if parameter r12 is set to 0:
set-point + r0"
page 71 of 88
Page 72
(42)
the switching on of the device shall switch on the application and the switching off of the device shall switch off the application.
(39)
it is suggested to set parameter P4 at 3 (the evaporator temperature probe shall be associated with the evaporator fan and the evaporator 2 temperature probe shall be associated with the
(38) if parameter d8 is set at 2 or 3, the setting shall have no effect and the device shall operate as if the parameter were set at 0; it is suggested to set parameter P4 at 3 (the evaporator
the device stores the alarm once the time established in parameter i2 has expired; if parameter i2 is set at -1, the device will not store the alarm
if the parameter i5 i0 and parameter i15 are set at the same value, the effect will be caused by the activation of at least one of the inputs (until both inputs are deactivated)
make sure that the time established with parameter i7 is less than that established with parameter i9
to avoid damaging the unit connected to the instrument, set the parameter setting when the device is switched off
the compressor is off
temperature probe shall be associated with defrosting and the evaporator 2 temperature probe shall be associated with defrosting 2)
on the compressor
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
(29) if parameter P4 is set at 0, 2, 3 or 4, the condenser fan will function in parallel with the compressor
(41) the heating elements are switched on when the room temperature of the cabinet or the CPY temperature drops below the “work set-point + u7” and are switched off when the temperature rises
(40)
if parameter u2 is set at 0, switching off the device may cause the room light and/or the auxiliary output to switch off (the next time the instrument is switched on the unit connected will remain
evaporator 2 fan)
switched off); if parameter u2 is set at 1, switching off the device will not cause the room light or the auxiliary output to switch off (the next time the instrument is switched on the unit
connected will remain switched on)
above the “work set-point + u7 + 2 °C/°F”
(30) the condenser fan is on on condition that the compressor is on and is off when the temperature of the condenser drops below the temperature established with parameter F11 on condition that
(31) the compressor is switched off 10 sec after the activation of the input; if the input is activated during defrosting or when the evaporator fan is deactivated, the activation will not have any effect
(32)
(33)
(34)
(35)
(36) make sure that parameter u1 is not set at 1 when parameter u11 is set at 2 (and vice versa)
(37) if parameter d8 is set at 3, the setting shall have no effect and the device shall operate as if the parameter were set at 0
page 72 of 88
Page 73
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
13 WARNING LIGHTS AND DIRECTIONS
13.1 Signals
The following table shows the meaning of the LED warning lights of the device.
LED MEANING
Compressor LED light
If the LED is on:
-
the compressor is on
If the LED is flashing:
-
the working set point is in the process of being set (via the procedure described in paragraph ”Setting the
working set point”
a compressor protection will be in progress; see parameters C0, C1, C2, C11 and i7
-
Defrost LED
If the LED is on:
defrosting is in progress
-
predripping will be in progress; se e parameter d16
-
If the LED is flashing:
-
defrosting will be requested but a compressor protection will be in progress; see the parameters C0, C1 and
C2
-
dripping will be in progress; see parameter d7 the refrigerant fluid heating will be in progress; see parameter d15
-
Evaporator fan LED light
If the LED is on:
-
the evaporator fan will be on
If the LED is flashing:
-
evaporator fan standstill will be in progress; see parameter F3
room light LED
If the LED is on:
-
the room light has been turned on manually (only if the parameter u1 and/or parameter u11 is set at 0)
If the LED is flashing:
the room light has been turned from a digital input ; see parameter i0 (only if the parameter u1 and/or
-
parameter u11 is set at 0)
page 73 of 88
Page 74
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Auxiliary LED 1 and Auxiliary LED 2
If the LED is on:
-
the demister heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at
1)
-
the auxiliary output will have been switched on in manual mode (only if the parameter u1 and/or parameter
u11 is set at 2)
the door heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at 4)
-
-
the neutral area operating heating elements will be activated (only if the parameter u1 and/or parameter
u11 is set at 5)
AUX1
and
AUX2
the condenser fan will be on (only if the parameter u1 and/or parameter u11 is set at 6)
-
-
compressor 2 will be on (only if the parameter u1 and/or parameter u11 is set at 7) the defrosting output 2 will be on (only if the parameter u1 and/or parameter u11 is set at 8)
-
evaporator 2 fan will be on (only if the parameter u1 and/or parameter u11 is set at 9)
-
-
the pump down valve will be on (only if the parameter u1 and/or parameter u11 is set at 10) the on/stand-by output will be on (only if the parameter u1 and/or parameter u11 is set at 11)
-
the man in cold room output will be on (only if the parameter u1 and/or parameter u11 is set at 12)
-
If the LED is flashing:
- compressor 2 protection will be in progress; see parameters C0, C1, C2, C11 and i7
- evaporator fan 2 standstill will be in progress; see parameter F3
-
the auxiliary out put will have been switched on from a digital input; see parameters i5 and i15 (only if the
parameter u1 and/or parameter u11 is set at 2)
HACCP
Clock LED light
If the LED is on:
-
the value displayed shall be a time
If the LED is flashing:
the date, time and day of the week are being set
-
temperature LED light
If the LED is on:
-
the value displayed shall be a temperature
If the LED is flashing:
- the “rapid cooling” function is in progress; see parameters r5 and r6
pressure LED light
If the LED is on:
-
the value displayed shall be a pressure
HACCP LED light
If the LED is on:
- not all the information on the HACCP alarms has been displayed
If the LED is flashing:
-
if it is flashing, the device has saved at least one new HACCP alarm
Energy saving LED light
If the LED is on:
the “energy saving” function is in progress
-
page 74 of 88
Page 75
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Alarm LED light
If the LED is on:
-
an alarm is in progress
If the LED is flashing:
-
compressor maintenance is required; see parameter C10
13.2 Signal Descriptions/Explanations
The following table shows the meaning of the signal codes of the device.
CODE MEANING
the keyboard is blocked; see paragraph 6.10 “Keyboard locking/unlocking”
Loc
- - - - The operation requested is not available
-
-
the work set point is blocked; see parameter r3
page 75 of 88
Page 76
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
14 ALARMS
14.1 Alarms
The following table shows the meaning of the alarm codes of the device.
CODE MEANING
Minimum alarm temperatures (HACCP alarms)
Solutions:
-
AL
AH
check the temperature associated to the alarm; see parameters A0, A1 and A2
Main consequences:
-
if parameter A0 is set at 0, the device will store the alarm the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Maximum temperature alarm (HACCP alarms)
Solutions:
check the room temperature or CPT temperature; see parameters A4 and A5
-
Main consequences:
-
the device will memorise the alarm the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
id
PF
iA
Door micro switch input alarm (HACCP alarms)
Solutions:
-
check the causes of the activation of the input; see parameters i0 and i1
Main consequences:
the effect established with the parameter i0
-
-
if parameter i4 is set at 1, the device will store the alarm, provided parameter i2 is not set at -1 the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Power supply cut-off alarm (HACCP alarm)
Solutions:
check the causes triggering the power supply cut-off; see parameters A10 and A12
-
-
press a key to restore normal display
Main consequences: Main consequences:
if the interruption lasts longer than the time established with parameter A10, the device will store the alarm
-
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Multifunction and Multifunction 2 input a larm
Solutions:
- check the causes of the activation of the input; see parameters i5, i6, i15 and i16
Main consequences:
the effect established with the parameters i5 and i15
-
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
page 76 of 88
Page 77
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Maximum pressure switch alarm
Solutions:
-
check the cause s of the activation of the input; see parameters i5, i6, i7, i8, i9, i15 and i16
iSd
LP
C1t
switch off and re-start the device or suspend the power supply
-
Main consequences:
-
the regulators will switch off the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Minimum pressure switch alarm
Solutions:
check the causes of the activation of the input; see parameters i5, i6, i15, i16 and i17
-
Main consequences:
- the compressor will be switched off
- the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Compressor thermal protection alarm
Solutions:
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
-
Main consequences:
-
the compressor will be switched off if parameter u1 and/or parameter u11 is set at 7 (or in case of operation with two compressors), the device
-
shall operate exactly as it would with only one compressor (compressor 2)
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
C2t
MiC
COH
Compressor 2 thermal protection alarm
Solutions:
-
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
Main consequences:
-
compressor 2 will be switched off (only if the parameter u1 and/or parameter u11 is set at 7) the device shall operate exactly as it would with only one compressor (compressor 1)
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Man in Cold room alarm
Solutions:
-
check the causes of the activation of the input; see parameters i5, i6, i15 and i16
Main consequences:
-
the man in cold room output will be switched on (only if the parameter u1 and/or parameter u11 is set at
12)
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Condenser overheated alarm
Solutions:
-
check the condenser temperature; see parameter C6
Main consequences:
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
-
the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)
page 77 of 88
Page 78
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Compressor shut down alarm.
Solutions:
check the condenser temperature; see parameter C7
-
-
switch the device off and back on again: if when the device is switched back on, the temperature of the
CSd
dFd
Pd
Main consequences:
the compressor and the evaporator fan will be switched off
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
-
the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)
Defrosting alarm switched off because maximum time has been reached
Solutions:
check the integrity of the evaporator temperature probe; see parametersd2, d3 and d11
-
- press a key to restore normal display
Main consequences:
-
the device will continue to operate normally
Pump down alarm (from digital input) finished for maximum duration
Solutions:
- check the integrity of the sensor switching off the compressor
Main consequences:
-
the device will continue to operate normally
condenser is still higher than that established in parameter C7, disconnect the power supply and clean the
condenser
When the cause of the alarm disappears, the device restores normal operation, except for the following alarms:
-
the power supply interruption alarm (code “PF”) which requires the pressing of a key maximum pressure switch alarm (code “iSd”) which requires the switching off of the device or the temporary suspension of
-
the power supply
-
compressor blocked by condenser temperature alarm (code “CSd”) which requires the switching off of the device or the
temporary suspension of the power supply
- defrosting alarm switched off because maximum time has been reached (code “dFd”) which requires the pressing of a key.
page 78 of 88
Page 79
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
15 ERRORS
15.1 Errors
The following table shows the meaning of the error codes of the device.
CODE MEANING
room temperature/inlet air temperature probes error
Solutions:
- check that the probe is the PTC or NTC type; see parameter P0
check the device-probe connection
-
-
check room/inlet air temperature
Main consequences:
compressor activity will depend on parameters C4 and C5
-
Pr1
-
the defroster will not be activated
- the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
the door heating elements will be switched off (only and provided parameter u1 and/or parameter u11 is set
-
at 4)
-
the neutral area operating heating elements will be deactivated (only if parameter u1 and/or parameter u11
is set at 5)
-
if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the outlet air
temperature probe
Pr2
Pr3
Evaporator temperature probe error
Solutions:
-
the same as the preceding case but with respect to the evaporator temperature probe
Main consequences:
if parameter P3 is set at 1, the defrosting period will last for the amount of time set with parameter 3
-
-
if parameter P3 is set at 1and parameter d8 is set at 2 or to 3, the device will operate as if parameter d8
were set at 0
if parameter F0 is set at 3 or 4, the device will operate as if the parameter were set at 2
-
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Auxiliary temperature probe error
Solutions:
-
the same as in the previous example, but with regard to the auxiliary temperature probe
Main consequences:
if parameter P4 is set at 1:
-
- condenser overheated alarm (code “COH”) will never be activated
- he compressor blocked alarm (code “CSd”) will never be activated
- the condenser fan will operate parallel to the compressor (only if parameter u1 and/or
parameter u11 is set at 6)
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3) if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the inlet air
-
temperature probe
page 79 of 88
Page 80
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Vapour pressure probe error
Solutions:
-
check that the probe is the 4-20 mA type check the device-probe connection
Pr4
Pr5
rtc
-
check the vapour pressure
-
Main consequences:
-
the electronic expansion valve will be closed the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
Evaporation temperature probe error
Solutions:
check that the probe is the PTC or NTC type; see parameter P0
-
check the device-probe connection
-
-
check room/inlet air temperature
Main consequences:
- the electronic expansion valve will be closed
- the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Clock error
Solutions:
set the date, time and day of the week
-
Main consequences:
-
if parameter d8 is set at 4, the device will operate as if it were set at 0
-
the “HACCP” function will not provide information regarding the date and hour in which the alarm was
signalled
the “energy saving” function n real time function will not be activated in real time
-
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
When the cause of the error disappears, the device restores normal operation, except for clock error (“rtc” code), which requires the
date, time and day of the week set.
page 80 of 88
Page 81
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
16 ACCESSORIES
16.1 Non opto-isolated RS-485/USB serial interface EVIF20SUXI
16.1.1 Preliminary notes
The interface makes it possible to connect the device to the Parameters Manager set-up software system.
16.2 Data recorder EVUSBREC01
16.2.1 Preliminary notes
The device records the board data and their download (via USB in a CSV file format).
16.3 USB cover for panel installation 0812000002
16.3.1 Preliminary notes
Through the cover it is possible to make the USB-type communication port more accessible for EVUSBREC01 data recording.
To connect the cover to the devise it is necessary to use also the 0810500018 or 0810500020 connection cable (to be ordered
separately).
page 81 of 88
Page 82
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
16.4 0810500018/0810500020 connection cable
16.4.1 Preliminary notes
The cables can be used to connect the USB cover for panel installation 0812000002 to the EVUSBREC01 data recorder.
The 0810500018 cable is 2.0 m long; the 0810500020 cable is 0.5 m long.
page 82 of 88
Page 83
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
17 TECHNICAL DATA
17.1 Technical data
Purpose of the command device: operating command device.
Construction of the command device: built-in electronic device.
Container: grey self-extinguishing.
Heat and fire protection class: D.
Dimensions:
Method of mounting the command device: wall mounted, with bolts and fastening screws.
Shell protection grade: IP65.
Connection method:
262.0 x 179.0 x 95.6 mm (10.314 x 7.047 x 3.763 in;
L x H x D).
-
screw in terminal b oards 7.5 mm pitch (0.295 in) for
wires up to 4 mm² (0.0062 in²): power supply and
digital outputs
- screw in terminal boards 5.0 mm pitch (0.196 in) for
wires up to 2.5 mm² (0.0038 in²): analogue inputs,
digital inputs and RS-485 MODBUS port
- screw in removable terminal board, male only
3.5 mm pitch (0.137 in) for wires up to 1.5 mm²
(0.0028 in²) or JST male only 6-way connector 2.5
mm pitch (0.098 in): driver for unipolar stepper
electronic expansion valves.
The maximum lengths of the connection cables are:
-
power supply: 100 m (328 ft) analogue inputs: 100 m (328 ft)
-
transducers power supply: 100 m (328 ft)
-
-
digital inputs: 100 m (328 ft) digital outputs: 100 m (328 ft)
-
-
RS-485 MODBUS port: 1,000 m (3,280 ft); please
refer also to the MODBUS specifications and
implementation guides available at
http://www.modbus.org/specs.php
driver for unipolar stepper electronic expansion
-
valves: 3 m (9.842 ft)
from 0 to 45 °C (from 32 to 113 °F) the models with differential
Operating temperature:
Storage temperature: from -25 to 70 °C (from -13 to 158 °F).
magneto-thermal circuit breaker and with remote control switch
for three-phase defrost elements management, from 0 to 50 °C
(from 32 to 122 °F) otherwise.
page 83 of 88
Page 84
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
Humidity for use: from 10 to 90 % relative humidity without condensate.
Command device pollution situation: 2.
Height at which it is used: from 0 to 2,000 m (from 0 to 6,591 ft).
Height at which it can be transported: from 0 to 3,048 m (from 0 to 10,000 ft).
-
RoHS 2011/65/CE
Environmental standards:
EMC standards:
WEEE 2012/19/EU
-
-
REACH (CE) regulation n. 1907/2006.
-
EN 60730-1 IEC 60730-1.
-
Power supply:
Magneto-thermal switch:
Differential magneto-thermal circuit breaker:
Remote control switch for three-phase defrost elements
management:
Control device grounding method: with ground terminal
Rated impulse voltage: 4 KV.
Overvoltage category: III.
Class and structure of software: A.
115... 230 VAC (+10 %, -15 %), 50/60 Hz (±3 Hz), 35 VA max.
non insulated, supplied by a class 2 circuit.
according to model (230 VAC, In 16 A, Icn 4.500 A, unipolar +
neutral, for wires up to 25 mm² (0.0387 in²).
according to model (230 VAC, In 16 A, Icn 4.500 A, Id 300 mA,
unipolar + neutral, for wires up to 25 mm² (0.0387 in²).
according to model (230 VAC, Ie 9 A, Ui 690 V, Uimp 6 KV, Ith
20 A, 2,2 KW in AC3 at 230 VAC with ta 55 °C, three poles +
neutral, for wires up to 25 mm² (0,0387 in²).
lock:
according to model (SuperCap)
SuperCap autonomy without power supply: 24 h with SuperCap
fully charged.
SuperCap recharging time: 2 min (the SuperCap is recharged
through the device power supply).
Drift: 30 s/month at 25 °C (77 °F).
page 84 of 88
Page 85
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
according to model, up to 5 inputs:
-
3 configurable via configuration parameter for OTC
or NTC probes (room temperature, evaporator
temperature and evaporation temperature)
- 1 configurable via configuration parameter for PTC
or NTC probes (configurable via configuration
parameter for condenser temperature, critical
temperature, evaporator 2 temperature or CPT
temperature)
-
1 for 4-20 mA transducers (vapour pressure).
4-20 mA transducers power supply: 12 DC (+50 %, -25 %),
120 mA max.
Analogue inputs PTC (990 @ 25 °C, 77 °F)
KTY 81-121.
from -50 to 150 °C (from -58 to 302
°F).
±0,5 % of scale end.
0,1 °C (1 °F).
100 ms.
none.
Analogue inputs
Type of sensor:
Measurement field:
Precision:
Resolution :
Conversion time:
Protection:
Digital inputs:
Analogue inputs NTC (10 K @ 25 °C, 77 °F)
Type of sensor:
Measurement field:
Precision:
Resolution :
Conversion time:
Protection:
Analogue inputs 4-20 mA
Input resistance:
Precision:
Resolution :
Conversion time:
Protection:
ß3435.
from -50 to 120 °C (from -58 to 248
°F).
±0,5 % of scale end.
0,1 °C (1 °F).
100 ms.
none.
200 .
±0,5 % of scale end.
0.01 mA. 100 ms.
none; maximum allowable current
at each input is 25 mA.
3 inputs, configurable via configuration parameter for NA or NC
contact (micro port, multifunction 1 and multifunction 2)
Digital inputs at 5 VDC mA (clean contact)
Power:
none.
Protection:
none.
Displays: custom 3 digit display with decimal point and function icon.
page 85 of 88
Page 86
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
according to model, up to 6 outputs:
-
2 SPST electromechanical relays with 30 A res. @
250 VAC (compressor and defrosting)
2 SPST electromechanical relays with 16 A res. @
-
250 VAC (evaporator fan and room light)
-
1 SPST electromechanical relay with 8 A res. @ 250
VAC (configurable through a configuration parameter
for demister heating elements, auxiliary, alarms,
door resistors, neutral area operation resistors,
condenser fan, compressor 2, defrosting 2,
evaporator fan 2, pump down valve, on/stand-by or
Digital outputs:
-
1 SPDT electromechanical relay with 8 A res. @ 250
The maximum load current allowed is 16 A.
The device guarantees double insulation between each connector
of the digital outputs and the other parts of the device.
man in cold room; for manufacturer default for the
condenser fan).
VAC (configurable through a configuration parameter
for demister heating elements, auxiliary, alarms,
door resistors, neutral area operation resistors,
condenser fan, compressor 2, defrosting 2,
evaporator fan 2, pump down valve, on/stand-by or
man in cold room; for manufacturer default for the
condenser fan).
Driver for unipolar stepper electronic expansion valves. 12 VDC, 260 mA max.
Type 1 or Type 2 actions: Type 1.
Complementary features of Type 1 or Type 2 actions: C.
Communication port: 1 door RS-485 with MODBUS slave communication protocol.
Signal buzzer and alarm: incorporated.
page 86 of 88
Page 87
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
EVBOX1
Front mounted electrical boards for cold rooms with
single-phase compressor
Installation guide ver. 1.2
PT - 25/14
This document is exc lusive property of EVCO; EVCO does not
assume any liability regarding possible errors stated.
The customer (manufacturer, installer or final user) assumes
all liability regarding configuration of the device.
EVCO does not take any responsibility about damages coming
by the non-observance of additional information.
EVCO reserves the right to make any change without prejudice
the basic safety and operating features.
page 87 of 88
Page 88
EVCO S.p.A. EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124
EVCO S.p.A.
Via Feltre 81, 32036 Sedico Belluno ITALY
Phone 0437/8422 | Fax 0437/83648
info@evco.it | www.evco.it
page 88 of 88
Loading...