EVCO EV9346J9 User Manual

Evco S.p.A. • Code 1049346E00
EV9346 Digital controller with 6 outputs for electric pizza ovens, with rapid heating function version 3.00
E ENGLISH
1 IMPORTANT
1.1 Important
Read these instructions carefully before installation and use and follow
all recommendations regarding installation and for the electric con-
nection; keep these instructions for future reference.
Standards regarding the collection of electric and electronic
appliances.
1.2 Dimensions and installation
Panel, with supplied screw bracket; dimensions in mm (in).
DIMENS. MINIMUM TYPICAL MAXIMUM
A 92.0 (3.622) 92.0 (3.622) 92.8 (3.653)
B 92.0 (3.622) 92.0 (3.622) 92.8 (3.653)
Installation recommendations:
• the thickness of the panel must not exceed 4,0 mm (0,157 in)
• position the brackets as indicated in the drawing in this paragraph;
moderate the coupling torque
• make sure that the work conditions (temperature of use, humidity,
etc.) lie within the limits indicated in the technical data
• do not install the instrument in proximity of heat sources (resistances,
hot air pipes etc.) appliances with strong magnets (large diffusers etc.),
places subject to direct sunlight, rain, humidity, excessive dust, me-
chanical vibrations or shocks
• in compliance with Safety Standards, the protection against any con-
tact with the electric parts must be ensured via correct installation of
the instrument. All parts that ensure protection must be fixed in a way
such that they cannot be removed without the aid of a tool.
1.3 Electric connection
With reference to the wiring diagram: the serial port is the communi-
cation port with the supervising system (through a serial interface, via
TTL, with MODBUS communication protocol) or with the program-
ming key; the port must not be used for two purposes at the same time.
Recommendations for the electric connection:
• do not operate on the terminal boards using electric or pneumatic
screwdrivers
• if the instrument has been taken from a cold place to a hot one, the
humidity could condense inside. Wait about one hour before apply-
ing power
• make sure that the power supply voltage, frequency and operational
electric power correspond to those of the local power supply
• disconnect the power supply before performing any type of mainte-
nance
• equip the probes with a protection able to insulate them against any
contact with metal parts or use isolated probes
• do not use the instrument as a safety device
• for repairs and information regarding the instrument, contact the
Evco sales network.
2 PRELIMINARY CONSIDERATIONS
2.1 Preliminary considerations
The instrument can be configured to function with 1 measurement
input (default, chamber probe) or with 2 measurement inputs (top
probe and floor probe).
Functioning with 1 measurement input allows to independently set
the power distributed to the top to that distributed to the floor. Func-
tioning with 2 measurement inputs allows to independently set the top
and floor work temperatures.
The utilities managed by the digital outputs (i.e. the K1 relays... K6) are
the following:
RELAY UTILITY MANAGED
K1 top
K2 floor
K3 alarm
K4 chamber light
K5 acoustics
K6 on/stand-by
To set the type of functioning (with 1 measurement input rather than 2)
see paragraph 4.1.
2.2 Management of the utilities
Top.
If functioning with 1 measurement input:
• the output is switched on in cyclical mode, preferably when the top
output is off (the parameter c1 establishes the cycle time. The proce-
dure given in paragraph 4.3 can be used to set the duration of output
switch-on, intended as a percentage of the time established with
parameter c1)
• the cyclical activity is subject to the chamber temperature (chamber
probe), to the work set-point and parameter r0.
If functioning with 2 measurement inputs:
• the output activity depends mainly on the floor temperature (floor
probe), the floor set-point and parameter r0.
Floor.
If functioning with 1 measurement input:
• the output is switched on in cyclical mode, preferably when the top
output is off (the parameter c1 establishes the cycle time. The proce-
dure given in paragraph 4.3 can be used to set the duration of output
switch-on, intended as a percentage of the time established with
parameter c1)
• the cyclical activity is subject to the chamber temperature (chamber
probe), to the work set-point and parameter r0.
If functioning with 2 measurement inputs:
• the output activity depends mainly on the floor temperature (floor
probe), the floor set-point and parameter r6.
Alarm.
The output is activated during a temperature alarm.
Chamber light.
The output is activated in manual mode.
Through the multifunction input it is also possible to activate the output
in remote mode.
Acoustics.
The output is activated during an alarm or an error, with continuous
contribution.
On/Stand-by.
The output is activated during the “on” status (see paragraph 3.1).
3 USER INTERFACE
3.1 Preliminary considerations
The following functioning states exist:
• the “on” state (the instrument is powered and on: the regulators can
be on)
• the “stand-by” state (the instrument is powered but switched off via
software: the regulators are off)
• the “off” state (the instrument is not powered).
Successively, the term “switch-on” means the passage from the stand-by
state to the on state. The term “switch-off” means the passage from the
on state to the stand-by state.
When powered, the instrument re-proposes the state that it was in when
the power supply was disconnected.
3.2 Instrument switch on/off
To pass from the stand-by state to the on state (and vice versa):
• make sure no procedure is in progress
• press for 1s.
Through the on/stand-by input it is also possible to pass from the on
state to the stand-by state in remote mode.
To pass from the on to the stand-by state in remote mode:
• activate the on/stand-by input (the instrument remains in the stand-by
state for the entire duration of input activation).
If the on/stand-by input is active, it will not be allowed to pass from the
stand-by state to the on state by pressing the key.
3.3 The display
If functioning with 1 measurement input, if the instrument is in the on
state:
• the upper part of the display will show the quantity established with
parameter P5:
- if P5 = 0, the display will show the chamber temperature
- if P5 = 1, the display will show the work set-point
• the lower part of the display will show the size established with pa-
rameter P6:
- if P6 = 0, the display will show the chamber temperature
- if P6 = 1, the display will show the work set-point (in this case the “set”
LED will be on).
See also paragraphs 3.4 and 3.6.
If functioning with 2 measurement inputs, if the instrument is in the on
state:
• the upper part of the display will show the size established with pa-
rameter P5:
- if P5 = 0, the display will show the top temperature
- if P5 = 1, the display will show the top set-point
- if P5 = 2, the display will show the floor temperature
- if P5 = 3, the display will show the floor set-point
• the lower part of the display will show the size established with pa-
rameter P6:
- if P6 = 0, the display will show the top temperature
- if P6 = 1, the display will show the top set-point (in this case the “set”
LED and the “1” LED will be on)
- if P6 = 2, the display will show the floor temperature
- if P6 = 3, the display will show the floor set-point (in this case the “set”
LED and the “2” LED will be on).
See also paragraphs 3.4 and 3.6.
If the instrument is in the stand-by state:
• the upper part of the display will be off
• the lower part of the display will be off
• the LED will be on.
3.4 Learning the quantity shown by the upper part of
the display during the on state
• make sure no procedure is in progress
• press and : if functioning with 1 measurement input, the
upper part of the display will show one of the
labels given in the following table for 2 seconds:
LABEL MEANING
Pb chamber temperature
SP work set-point
If functioning with 2 measurement inputs, the upper part of the display
will show one of the labels given in the following table for 2 seconds:
LABEL MEANING
Pb1 temperature of the top
SP1 top set-point
Pb2 temperature of the floor
SP2 floor set-point
3.5 Temporary setting of the quantity shown by the
upper part of the display during the on state
• make sure no procedure is in progress
• press and for 1 s several times: the upper part of the display
will show one of the labels given in the tables in
paragraph 3.4 for 2 secs, after which it will show
the corresponding value.
Any power supply cut-off causes the display of the quantity established
with parameter P5 to be restored.
3.6 Learning the quantity shown by the lower part of
the display during the on state
• make sure no procedure is in progress
• press and : if functioning with 1 measurement input, the
lower part of the display will show one of the
labels given in the following table for 2 seconds:
LABEL MEANING
Pb chamber temperature
SP work set-point
if functioning with 2 measurement inputs, the lower part of the display
will show one of the labels given in the following table for 2 seconds
value of the cooking timer or its count if the timer is active:
LABEL MEANING
Pb1 temperature of the top
SP1 top set-point
Pb2 temperature of the floor
SP2 floor set-point
3.7 Temporary setting of the quantity shown by the
lower part of the display during the on state
• make sure no procedure is in progress
• press and for 1s several times: the lower part of the display
will show one of the labels given in the tables in
paragraph 3.6 for 2 secs, after which it will show
the corresponding value.
Any power supply cut-off causes the display of the quantity established
with parameter P6 to be restored.
3.8 Chamber light switch on/off
• make sure no procedure is in progress
• press
Using the multifunction input, it is also possible to cause the same effect
by pressing the key in remote mode.
3.9 Buzzer silencing
• make sure no procedure is in progress
• press a key (the first time the key is pressed, the associated effect is not
caused).
Pressing the key also causes the deactivation of the acoustic output and
the buzzer output.
Using the multifunction input, it is also possible to deactivate the buzzer,
the acoustic output and the buzzer output in remote mode.
4 SETTINGS
4.1 Setting the type of functioning (with 1 measure-
ment input rather than 2)
To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press and for 4s: the upper part of the display will show
PA
• press : the lower part of the display will show the corresponding
value
• press or within 15s to set “743
• press
• press and for 4s: the upper part of the display will show
Pb”.
To modify the type of functioning:
• press : the lower part of the display will show the corresponding
value.
The meaning of the values is the following:
VALUE MEANING
1 functioning with 1 measurement input (default, chamber
probe)
2 functioning with 2 measurement inputs (top probe and
floor probe)
• press or within 15s
• press
To exit the procedure:
• press and for 4s.
The modification of the type of functioning does not cause
the configuration parameters default value to be restored.
4.2.1 Setting the work set-point (only if functioning with
1 measurement input)
• make sure that the instrument is in on state and that no procedure is
in progress
• press : the lower part of the display will show “SP”, the upper
part the corresponding value and the LED will flash
• press or within 15s; see also parameters r1 and r2
• press 3 times or do not operate for 15s: the LED will switch-
off, after which the instrument will exit the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the work set-point via the SP parameter.
4.2.2 Setting the t op set-point and t he floor s et-point (only
if functioning with 2 measurement inputs)
To modify the top set-point:
• make sure that the instrument is in on state and that no procedure is
in progress
• press : the lower part of the display will show “SP1”, the upper
part the corresponding value and the LED will flash
• press or within 15s; see also parameters r1 and r2
• press 2 times or do not operate for 15s: the LED will switch-
off, after which the instrument will exit the procedure.
To modify the floor set-point:
• press during the modification of the top set-point: the lower part
of the display will show “SP2”, the upper part the corre-
sponding value and the LED will flash
• press or within 15s; see also parameters r7 and r8
• press : the LED will switch-off, after which the instrument
will exit the procedure.
To go back to previous levels:
• press several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the top set-point via parameter SP1 and the floor
set-point via parameter SP2.
4.3 Setting the power distributed to the top and the
power distributed to the floor (only if functioning
with 1 measurement input)
To modify the power distributed to the top:
• press during the modification of the work set-point: the lower
part of the display will show “Po1”, the upper part the
corresponding value and a proportioned number of bars
of the will flash
• press or within 15s; see also parameters c0 and c1
• do not operate for 15s: the LED will switch-off, after which the
instrument will exit the procedure.
To modify the power distributed to the floor:
• press during the modification of the power distributed to the
top: the lower part of the display will show “Po2”, the
upper part the corresponding value and a proportioned
number of bars of the LED will flash
• press or within 15s; see also parameters c0 and c1
• press : the LED will switch-off, after which the instrument will
exit the procedure.
To go back to previous levels:
• press several times during the procedure.
To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the power distributed to the top through param-
eter Po1 and the power distributed to the floor through parameter
Po2.
4.4 Setting the configuration parameters
To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press and for 4s: the upper part of the display will show
PA
• press : the lower part of the display will show the corresponding
value
• press or within 15s to set “-19
• press or do not operate for 15s
• press and for 4s: if functioning with 1 measurement input,
the upper part of the display will show “SP”; if
functioning with 2 measurement inputs, the up-
per part of the display will show “SP1”.
To select a parameter:
• press or
To modify a parameter:
• press : the lower part of the display will show the corresponding
value
• press or within 15s
• press or do not operate for 15s.
To exit the procedure:
• press and for 4s or do not operate for 60s (any modifica-
tions will be saved).
Cut the instrument power supply off after modification of
the parameters.
4.5 Restore the default value of the configuration pa-
rameters
• make sure that the instrument is in stand-by state and that no proce-
dure is in progress
• press and for 4s: the upper part of the display will show
PA
• press : the lower part of the display will show the corresponding
value
• press or within 15s to set “743
• press or do not operate for 15s
• press and for 4s: the upper part of the display will show
Pb
• press or to select “dEF
• press : the lower part of the display will show the corresponding
value
• press or within 15s to set “149
• press or do not operate for 15s: the upper part of the display will
show “dEF” flashing for 4s, after which “dEF” will switch
on
• cut the instrument power supply off.
To exit the procedure in advance:
• press and for 4s during the procedure (i.e. before setting
149”: restore will not be carried out).
Make sure that the default value of the parameters is appro-
priate.
5 RAPID HEATING (only if functioning with 1 meas-
urement input)
5.1 Preliminary considerations
The rapid heating allows to reach the work set-point as quickly as
possible, supplying 100% of the power both to the top and the floor
(i.e. excluding switch-on of the top and floor outputs in a cyclical way
with benefit to switch-on in continuous mode).
When the temperature of the chamber reaches the “work set-point -
temperature established with parameter c3” value, the function is inter-
rupted.
5.2 Rapid heating activation
• causes the event established with parameter c2:
- if c2 = 1, press for 1s (make sure that the instrument is in on state
and that no procedure is in progress)
- if c2 = 2, pass from the stand-by state to the on state
- if c2 = 3, press for 1s (make sure that the instrument is in on state
and that no procedure is in progress) or pass from the stand-by state
to the on state.
If parameter c2 is set at 0, the function cannot be activated.
When the function is in progress the upper part of the display shows
F-F” alternately to the quantity established with parameter P5.
5.3 Interruption of rapid heating in manual mode
• make sure no procedure is in progress
• press for 1s.
6 SIGNALS
6.1 Signals
LED MEANING
top and floor LED
if it is on, the top output and/or the floor output will be on
if it flashes, the modification of the work set-point, the top
set-point and the floor set-point is in progress (with the pro-
cedures indicated in paragraphs 4.2.1 or 4.2.2)
power distributed to the top LED
supplies and indication regarding the power distributed to
the top
if it flashes, the modification of the power distributed to the
top is in progress (with the procedure indicated in para-
graph 4.3)
power distributed to the floor LED
supplies and indication regarding the power distributed to
the floor
if it flashes, the modification of the power distributed to the
floor is in progress (with the procedure indicated in para-
graph 4.3)
°C degrees Celsius LED
if it is on, the unit of measurement of the temperatures will
be degrees Celsius (parameter P2)
°F degrees Fahrenheit LED
if it is on, the unit of measurement of the temperatures will
be degrees Fahrenheit (parameter P2)
on/stand-by LED
if it is on, the instrument is in the stand-by state
set set-point LED
if it is on, the quantity shown by the lower part of the display
will be the work set-point value, the top set-point and the
floor set-point
1 • the quantity displayed by the lower part of the display will
be the top set-point value
• the quantity displayed by the lower part of the display will
be the floor set-point value
7 INDICATIONS
7.1 Indications
INDICAT. MEANING
F-F alternately to the quantity established with parameter P5:
the rapid heating function will be in progress (only if func-
tioning with 1 measurement input)
8 ALARMS
8.1 Alarms
CODE ME ANING
AL chamber temperature alarm (only if functioning with 1
measurement input)
Remedies:
• check the chamber temperature
• see parameters A1 and A3
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be acti-
vated
AL1 top temperature alarm (only if functioning with 2 measure-
ment inputs)
Remedies:
• check the top temperature
• see parameters A1 and A3
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be acti-
vated
AL2 floor temperature alarm (only if functioning with 2 meas-
urement inputs)
Remedies:
• check the floor temperature
• see parameters A5 and A7
Consequences:
• the alarm output will be activated
• the acoustics output and the buzzer output will be acti-
vated
When the causes of the alarm have disappeared, the instrument will go
back to normal functioning.
9 INTERNAL DIAGNOSTICS
9.1 Internal diagnostics
CODE ME ANING
Pr1 If functioning with 1 measurement input:
chamber probe error
Remedies:
• see parameter P0
• check probe integrity
• check the instrument-probe connection
• check the chamber temperature
Main consequences:
• the top output and the floor output will be deactivated
• the acoustics output and the buzzer output will be acti-
vated
If functioning with 2 measurement inputs:
top probe error
Remedies:
• the same as the previous case but relative to the top probe
Main consequences:
• the top output will be deactivated
• the acoustics output and the buzzer output will be acti-
vated
Pr2 floor probe error (only if functioning with 2 measurement
inputs)
Remedies:
• the same as the previous case but relative to the floor probe
Main consequences:
• the floor output will be deactivated
• the acoustics output and the buzzer output will be acti-
vated
When the causes of the alarm have disappeared, the instrument will go
back to normal functioning.
10 TECHNICAL DATA
10.1 Technical data
Container: grey self-extinguishing.
Front panel protection rating: IP 54.
Connections: removable terminal boards (power supply, inputs and
outputs), 6-pole connector (serial port). Temperature of use: from 0 to 55 °C (from 32 to 131 °F,
10 ... 90% relative humidity without condensate).
Power supply: 115 ... 230 VAC, 50/60 Hz, 5 VA (approx) or 24 VAC.
Alarm buzzer: incorporated.
Digital inputs: 2 inputs:
• on/stand-by input in high voltage (230 VAC) with
configurable polarity
• multifunction input, for NO/NC contact (potential-
free contact, 5 V 1 mA).
Range of measurement: from -99 to 800 °C (from -99 to 999 °F) for J thermocouple, from -99 to 999 °C (from -99 to 999 °F) for K thermo-
couple.
Resolution: 1 °C/1 °F.
Digital outputs: 6 relays:
top (relay K1): 8 A res. @ 250 VAC (contact in
exchange)
floor (relay K2): 8 A res. @ 250 VAC (contact in
exchange)
alarm (relay K3): 8 A res. @ 250 VAC (NO
contact)
chamber light (relay K4): 8 A res. @ 250 VAC
(NO contact)
acoustics (relay K5): 8 A res. @ 250 VAC (NO
contact)
on/stand-by (relay K6): 8 A res. @ 250 VAC
(NO contact)
The maximum current accepted on clamp 23 is 10 A.
Other outputs: buzzer output (12 V, max. 20 mA); the output is acti-
vated during alarms and errors, with continuous contribution.
Serial port: port for the communication with the supervising system
(through a serial interface, via TTL, with MODBUS communication
protocol) or with the programming key.
Measurement inputs: can be configured:
• 1 (chamber probe) for J/K thermocouple
if functioning with 1 measurement input
• 2 (top probe and floor probe) for J/K ther-
mocouple if functioning with 2 measure-
ment inputs
11 WORK SET-POINT, POWER DISTRIBUTED AND CONFIGURATION PARAMETERS
11.1 Work set-point
MIN. MAX. U.M. 1 INPUT 2 INPUTS r1 r2 °C/°F (1) 15 0 not visible r1 r2 °C/°F (1) not visible 15 0 r7 r8 °C/°F (1) not visible 15 0
WORK SET-POINT
work set-point
top set-point
floor set-point
11.2 Power distributed
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS
0 1 0 0 % 50 not visible
0 1 0 0 % 50 not visible
POWER DISTRIBUTED
power distributed to the top (percentage of c1); see also c0 and c1
power distributed to the floor (percentage of c1); see also c0 and c1
11.3 Configuration parameters
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS SP r1 r2 °C/°F (1) 15 0 not visible SP1 r1 r2 °C/ °F (1) not visible 15 0 SP2 r7 r8 °C/ °F (1) not visible 15 0
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS
Po1 0 1 00 % 50 not visible
Po2 0 1 00 % 50 not visible
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS CA1 -25/-5025/50 °C/°F (1) 0 0
WORK SET-POINT
work set-point
top set-point
floor set-point
POWER DISTRIBUTED
power distributed to the top (percentage of c1); see also c0 and c1
power distributed to the floor (percentage of c1); see also c0 and c1
MEASUREMENT INPUTS
with 1 measurement input, chamber probe inset; with 2 measurement inputs,
top probe offset
CA2 -25/-5025/50 °C/°F (1) not visible 0
P0 0 1 - - - - 0 0
floor probe offset
type of probe
0=J
1=K
P2 0 1 - - - - 0 0
temperature unit of measurement (2) 0=°C 1=°F
P5 0 (3) - - - - 0 0
quantity shown by the upper part of the display during the on state or during
normal functioning
0 = with 1 measurement input, chamber temperature; with 2 measurement
inputs, top temperature
1 = with 1 measurement input, work set-point; with 2 measurement inputs, top
set-point
2 = temperature of the floor
3 = floor set-point
P6 0 (3) - - - - 1 1
quantity shown by the lower part of the display during the on state or during
normal functioning
0 = with 1 measurement input, chamber temperature; with 2 measurement
inputs, top temperature
1 = with 1 measurement input, work set-point; with 2 measurement inputs, top
set-point
2 = temperature of the floor
3 = floor set-point
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS r0 1 99 °C/°F (1) 5 5
MAIN REGULATOR
with 1 measurement input, work set-point differential; with 2 measurement
inputs, top set-point differential
r1 0 r2 °C/°F (1) 5 0 5 0
with 1 measurement input, minimum work set-point; with 2 measurement in-
puts, top minimum set-point
r2 r1 999 °C/°F (1) 350 350
with 1 measurement input, maximum work set-point; with 2 measurement in-
puts, top maximum set-point
r6 1 99 °C/°F (1) not visible 5 r7 0 r8 °C/°F (1) not visible 50 r8 r7 999 °C/°F (1) not visible 35 0
floor set-point differential
minimum floor set-point
maximum floor set-point
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS
c0 0 2 - - - - 0 not visible
VARIOUS
restraint between the power distributed to the top and power distributed to the floor
0 = no restraint
1 = the modification of the power supplied to an output automatically causes
the supply of the maximum power to the other
2 = the modification of the power supplied to an output causes an automatic
adaptation of the power supplied to the other such to guarantee that the
sum of the two percentages is always 100
c1 1 9 99 s 80 not visible
c2 0 3 - - - - 1 not visible
cycle time for the top output and floor output switch-on, see also Po1 and Po2
event that causes the activation of the rapid heating function
0 = function cannot be activated
1 = press for 1s (make sure that the instrument is in on state and that no
procedure is in progress)
2 = pass from stand-by state to on state
3 = press for 1s (make sure that the instrument is in on state and that no
procedure is in progress) or pass from stand-by state to on state
c3 0 99 °C/°F (1) 1 0 not visible
temperature of the chamber over which the rapid heating function is inter-
rupted (relative to the work set-point i.e. “work set-point - c3”)
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS A1 0 999 °C/°F (1) 0 0
TEMPERATURE ALARMS
with 1 measurement input, temperature of the chamber above which the cham-
ber temperature alarm is activated; with 2 measurement inputs, temperature of
the top above which the top temperature alarm is activated; see also A3 (4)
A2 0 240 min 0 0
with 1 measurement input, chamber temperature alarm delay; with 2 measure-
ment inputs, top temperature alarm delay
A3 0 2 - - - - 0 0
with 1 measurement input, type of chamber temperature alarm delay; with
2 measurement inputs, type of top temperature alarm delay
0 = no alarm
1 = absolute (i.e. A1)
2 = with 1 measurement input, relative to the work set-point (i.e. “work set-point
+ A1”); with 2 measurement inputs, relative to the top set-point (i.e. “top set-
point + A1”)
A4 0 999 °C/°F (1) not visible 0
floor temperature above which the floor temperature alarm is activated, se also
A6 (4)
A5 0 24 0 m in not visible 0
A6 0 2 - - - - not visible 0
floor temperature alarm delay
type of floor temperature alarm
0 = no alarm
1 = absolute (i.e. A4)
2 = relative to the floor set-point (i.e. “floor set-point + A4”)
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS
i1 0 1 - - - - 0 0
DIGITAL INPUTS
on/stand-by input polarity
0 = live input active
1 = non-live input active
i5 0 2 - - - - 0 0
effect caused by the activation of the multifunction input
0 = no effect
1=CHAMBER LIGHT SWITCH-ON/OFF - the activation of the input will cause the
chamber light to switch-on and the successive activation will cause its switch-
off
2=BUZZER, ACOUSTIC OUTPUT AND BUZZER OUTPUT DEACTIVATION - the
activation of the input will cause deactivation of the buzzer, the acoustic
output and the buzzer output (activate the input again to deactivate these
utilities again)
i6 0 1 - - - - 0 0
type of contact of the multifunction input
0 = NO (input active with closed contact)
1 = NC (input active with open contact)
PARAM. MIN. MAX. U.M. 1 INPUT 2 INPUTS
LA 1 247 - - - - 247 247
Lb 0 3 - - - - 2 2
SERIAL NETWORK (MODBUS)
instrument address
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
LP 0 2 - - - - 2 2
parity
0 = none (no parity)
1 = odd
2 = even
(1) the unit of measurement depends on parameter P2
(2) set the parameters relative to the regulators appropriately after modification of parameter P2
(3) the value depends on the type of functioning (1 with 1 measurement input and 3 with 2 measurement inputs) (4) the parameter differential is 10 °C/18 °F.
PT • 35/09
EVCO S.p.A. This document belongs to Evco; unless you are authorized by Evco, you can not publish it.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.
Phone +39-0437-852468 • Fax +39-0437-83648 Evco does not take any responsibility about damages coming by the non-observance of the additional information.
info@evco.it • www.evco.it Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Loading...