These brief operating instructions show you how to configure the measuring device quickly and
easily:
Safety instructionsPage 7
▼
InstallationPage 13
▼
WiringPage 47
▼
Display and operating elementsPage 61
▼
Commissioning with “QUICK SETUP”Page 83 ff.
You can commission the measuring device quickly and easily, using the special “Quick
Setup” menu. It enables to configure important basic functions using the local display, for
example display language, measured variables, units engineering, type of signal, etc.
The following adjustments can be made separately as necessary:
– Empty-pipe/full-pipe adjustment for empty pipe detection (EPD)
– Configuration of relay contacts (NC or NO contact)
– Configuration of current outputs (active/passive), etc.
▼
Application-specific QUICK SETUPsPage 84 ff.
In “Quick Setup” mode you have the option of launching other, application-specific Quick
Setups, for instance the menu for measuring pulsating
Customer-specific configurationPage 65 ff.
Complex measuring operations necessitate additional functions that you can configure as
necessary with the aid of the function matrix, and customize to suit the process parameters.
flow.
▼
!
All functions are described in detail, as is the function matrix itself, in the “Description of
Device Functions” manual, which is a separate part of this Operating Instruction.
▼
Data storagePage 92 ff.
The configuration of the transmitter can be stored on the integrated T-DAT data storage
device.
!Note!
For time-saving commissioning, the settings stored in the T-DAT can be transmitted:
– For equivalent measuring points (equivalent configuration)
– In the event of device/board replacement.
▼
More detailed configurationPage 97 ff.
The inputs and outputs can be modified on convertible boards by configuring the current
inputs and outputs and relay contacts. The F-CHIP module gives the user the added option
of using software packages for diagnosis, concentration measurement and viscosity.
Note!
Always start trouble-shooting with the checklist on Page 105, if faults occur after commissioning or
during operation. The routine takes you directly to the cause of the problem and the appropriate
remedial measures.
2Endress+Hauser
Proline Promag 53“QUICK SETUP” for commissioning
“QUICK SETUP” for commissioning
!
Note!
More detailed information on running Quick Setup menus, especially for devices without a local
display, can be found on Page 85 ff.
ENDRESS+HAUSER
+
E
ESC
HOME-POSITION
Selection
System units
Selection
Output type
➀
Configure another unit?
➁
➂
+
Quick Setup
+
E
VolumeMassQuit
0402
Unit
Volume Flow
3001
Unit
Totalizer
Current OutputFreq.-/ Pulse Output
4000
Assign
Current
4001
Current
Span
4002
Value
0_4 mA
4003
Value
20 mA
Measuring
4004
Mode
4005
Time
Constant
4006
Failsafe
Mode
B
E
+
Language
1002
QS
Commission
2000
Defaults
0420
Unit
Density
0700
Value
Density
0400
Unit
Mass flow
3001
Unit
Totalizer
Operation
4200
Mode
FrequencyPulse
4201
Assign
Frequency
4203
End
Value Freq.
4204
Value
F low
Value
F high
Measuring
4205
4206
Measuring
Mode
Output
Mode
4207
Output
Signal
Time
4208
Failsafe
Constant
4209
Failsafe
Mode
NOYES
Assign
Pulse
Pulse
Value
Pulse
Width
Signal
Mode
Quit
4221
4222
4223
4225
4226
4227
➃
Inquiry: another
Quick Setup?
Configure another Output?
Autom. Configuration of Display?
Automatic parameterization
Pulsating Flow
Carrying out the
Quick Setup
Pulsating Flow
YES
of the display
Batching
Carrying out the
Quick Setup
Batching
➅
NOYES
NO
➄
NO
F06-53xxxxxx-19-xx-xx-en-000
Fig. 1:QUICK SETUP “Commissioning”
Endress+Hauser3
“QUICK SETUP” for commissioningProline Promag 53
!
Note!
• The display returns to the cell SETUP COMMISSIONING (1002) if you press the ESC key
combination during parameter interrogation. The stored parameters remain valid.
• The “Commissioning” Quick Setup must be carried out before one of the Quick Setups explained
below is run.
m Only units not yet configured in the current Setup are offered for selection in each cycle.
The unit for mass, volume and corrected volume is derived from the corresponding flow unit.
n The “YES” option remains visible until all the units have been configured.
“NO” is the only option displayed when no further units are available.
o Only the outputs not yet configured in the current Setup are offered for selection in
each cycle.
p The “YES” option remains visible until all the outputs have been parameterized.
“NO” is the only option displayed when no further outputs are available.
q The “automatic parameterization of the display” option contains the following
basic settings/factory settings:
YES: Main line = Mass flow; Additional line = Totalizer 1;
Information line = Operating/system conditions
NO: The existing (selected) settings remain.
r The QUICK SETUP BATCHING is only available when the optional software package
The measuring device described in this Operating Manual is to be used only for measuring the flow
rate of conductive fluids in closed pipes. A minimum conductivity of 20 µS/cm is required for
measuring demineralized water. Most fluids can be metered, provided they have a minimum conductivity of 5 µS/cm, for example:
• acids, alkalis, pastes, mashes, pulps,
• drinking water, wastewater, sewage sludge,
• milk, beer, wine, mineral water, yogurt, molasses, etc.
Resulting from incorrect use or from use other than that designated the operational safety of the
measuring devices can be suspended. The manufacturer accepts no liability for damages being
produced from this.
1.2Installation, commissioning and operation
Note the following points:
• Installation, connection to the electricity supply, commissioning and maintenance of the device
must be carried out by trained, qualified specialists authorized to perform such work by the facility's owner-operator. The specialist must have read and understood this Operating Manual and
must follow the instructions it contains.
• The device must be operated by persons authorized and trained by the facility's owner-operator.
Strict compliance with the instructions in the Operating Manual is mandatory.
• Endress+Hauser will be happy to assist in clarifying the chemical resistance properties of parts
wetted by special fluids, including fluids used for cleaning.
• If welding work is performed on the piping system, do not ground the welding appliance through
the Promag flowmeter.
• The installer must ensure that the measuring system is correctly wired in accordance with the
wiring diagrams. The transmitter must be grounded, unless the power supply is galvanically insulated.
• Invariably, local regulations governing the opening and repair of electrical devices apply.
1.3Operational safety
Note the following points:
• Measuring systems for use in hazardous environments are accompanied by separate “Ex documentation”, which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. The
symbol on the front of this supplementary Ex documentation indicates the approval and the
certification body ( 0 Europe, 2 USA, 1 Canada).
• The measuring device complies with the general safety requirements in accordance with
EN 61010, the EMC requirements of EN 61326/A1, and NAMUR recommendation NE 21.
• Depending on the application, the seals of the process connections of the Promag H sensor require
periodic replacement.
• The manufacturer reserves the right to modify technical data without prior notice.
Your Endress+Hauser distributor will supply you with current information and updates to this
Operating Manual.
Endress+Hauser7
1 Safety instructionsProline Promag 53
1.4Return
The following procedures must be carried out before a flowmeter requiring repair or calibration, for
example, is returned to Endress+Hauser:
• Always enclose a duly completed “Declaration of contamination” form. Only then can
Endress+Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per
EN 91/155/EEC.
• Remove all residues. Pay special attention to the grooves for seals and crevices which could contain residues. This is particularly important if the substance is hazardous to health, e.g. flammable,
toxic, caustic, carcinogenic, etc.
!
#
#
Note!
You will find a preprinted “Declaration of contamination” form at the back of this manual.
Warning!
• Do not return a measuring deviceif you are not absolutely certain that all traces of hazardous substances have been removed, e.g. substances which have penetrated crevices or diffused through
plastic.
• Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be
charged to the owner-operator.
1.5Notes on safety conventions and icons
The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the
factory in a condition in which they are safe to operate. The devices comply with the applicable
standards and regulations in accordance with EN 61010 “Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures”. They can, however, be a
source of danger if used incorrectly or for other than the designated use.
Consequently, always pay particular attention to the safety instructions indicated in this Operating
Manual by the following icons:
Warning!
“Warning” indicates an action or procedure which, if not performed correctly, can result in injury
or a safety hazard. Comply strictly with the instructions and proceed with care.
Caution!
"
!
8Endress+Hauser
“Caution” indicates an action or procedure which, if not performed correctly, can result in incorrect
operation or destruction of the device. Comply strictly with the instructions.
Note!
“Note” indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.
Proline Promag 532 Identification
2Identification
2.1Device designation
The “Promag 53” flow measuring system consists of the following components:
• Promag 53 transmitter
• Promag W, Promag P or Promag H sensor
In the compact version, transmitter and sensor form a single mechanical unit; in the remote version
they are installed separately.
2.1.1Nameplate of the transmitter
6
7
PROMAG 53
1
Ser.No.:
TAG No .:
2
3
4
53P1H-XXXXXXXXXXXX
12345678901
ABCDEFGHJKLMNPQRST
16-62VDC/20-55VAC
50-60Hz
EPD/MSU
I-OUT (HART), f-OUT
RELAY, STATUS-IN, I-IN
15VA/W
IP67 / NEMA/Type 4XOrder Code:
5
i
-20°C (-4°F) <Tamb<+60°C (+140°F)
Pat. UK EP 541 878 EP 618 680
Pat. UK 2 084 740 EP 219 725 EP 521 169
Pat. US 5,323,156 5,479,007
Pat. US 4,382,387 4,704,908 5,351,554
F06-53xxxxxx-18-06-xx-xx-000
Fig. 2:Nameplate specifications for the “Promag 53” transmitter (example)
1Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits.
2Power supply / frequency: 16…62 V DC / 20…55 V AC / 50…60 Hz
Power consumption: 15 VA / W
3Additional functions and software:
– EPD/MSU: with Empty Pipe Detection
– ECC: with Electrode Cleaning Circuitry
4Outputs / inputs:
I-OUT (HART): with current output (HART)
f-OUT: with pulse/frequency output
RELAY: with relay output
STATUS-IN: with status input (auxiliary input)
I-IN: with current input
5Reserved for information on special products
6Ambient temperature range
7Degree of protection
Endress+Hauser9
2 IdentificationProline Promag 53
2.1.2Nameplate of the sensor
PROMAG P
1
2
3
4
5
Order Code:
Ser.No.:
TAG N o.:
K-factor:
DN100 DIN EN PN16/
Materials:
TMmax.:
EPD/MSÜ, R/B
6
7
8
-20°C (-4°F)<Tamb<+60°C (+140°F)NEMA/Type4X
XXP1H-XXXXXXXXXXXX
12345678901
ABCDEFGHJKLMNPQRST
0.5328/ 5-
PFA / 1.4435
150°C/300°F
9
10
Pat. US 4,382,387 4,704,908 5,540,103
11
F06-xxxxxxxx-18-05-xx-xx-000
Fig. 3:Nameplate specifications for the “Promag” sensor (example)
1Ordering code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits.
2Calibration factor: 0.5328; zero point:
3Nominal diameter: DN 100
Pressure rating: EN (DIN) PN 16 bar
4TMmax +150 °C (max. fluid temperature)
5Materials:
– Lining: PFA
– Measuring electrodes: stainless steel 1.4435
6Additional information (examples):
– EPD/MSU: with Empty Pipe Detection electrode
– R/B: with reference electrode
7Reserved for information on special products
8Ambient temperature range
9Degree of protection
10Reserved for additional information on device version (approvals, certificates)
11Flow direction
−5
10Endress+Hauser
Proline Promag 532 Identification
2.1.3Nameplate, connections
A:
See operating manual
Betriebsanleitung beachten
Observer manuel d'instruction
Fig. 4:Nameplate specifications for Proline transmitter (example)
1Serial number
2Possible configuration of current output
3Possible configuration of relay contacts
4Terminal assignment, cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
5Signals present at inputs and outputs, possible configuration and terminal assignment (20...27),
see also “Electrical values of inputs/outputs”
6Version of device software currently installed
7Installed communication type, e.g.: HART, PROFIBUS PA, etc.
8Information on current communication software (Device Revision and Device Description), e.g.:
Dev. 01 / DD 01 for HART
9Date of installation
10Current updates to data specified in points 6 to 9
A0000963
2.2CE mark, declaration of conformity
The devices are designed to meet state-of-the-art safety requirements in accordance with sound
engineering practice. They have been tested and left the factory in a condition in which they are
safe to operate. The devices comply with the applicable standards and regulations in accordance
with EN 61010 “Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures” and with the EMC reqiurements of EN 61326/A1.
The measuring system described in this Operating Manual is therefore in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device
by affixing to it the CE mark.
Endress+Hauser11
2 IdentificationProline Promag 53
2.3Registered trademarks
KALREZ ®, VITON
®
are registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
®
is a registered trademark of Ladish & Co., Inc., Kenosha, USA
®
HART
is a registered trademark of HART Communication Foundation, Austin, USA
HistoROM™, S-DAT
Fieldcheck
®
, Applicator
®
, T-DAT®, F-CHIP®, ToF Tool - Fieldtool® Package,
®
are registered trademarks of Endress+Hauser Flowtec AG, Reinach, CH
12Endress+Hauser
Proline Promag 533 Installation
3Installation
3.1Incoming acceptance, transport and storage
3.1.1Incoming acceptance
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.
3.1.2Transport
The following instructions apply to unpacking and to transporting the device to its final location:
• Transport the devices in the containers in which they are delivered.
• Do not remove the protective plates or caps on the process connections until the device is ready
to install. This is particularly important in the case of sensors with PTFE linings.
Special notes on flanged devices
"
#
Caution!
• The wooden covers mounted on the flanges before the device leaves the factory protect the linings
on the flanges during storage and transportation. Do not remove these covers until immediately before the device is installed in the pipe.
• Do not lift flanged devices by the transmitter housing, or the connection housing in the case of
the remote version.
Transporting flanged devices (DN ≤ 300):
Use webbing slings slung round the two process connections (Fig. 5). Do not use chains, as they
could damage the housing.
Warning!
Risk of injury if the measuring device slips. The center of gravity of the assembled measuring device
might be higher than the points around which the slings are slung.
At all times, therefore, make sure that the device does not unexpectedly turn around its axis or slip.
F06-xxxxxxxx-22-00-00-xx-000
Fig. 5:Transporting transmitters with DN ≤300
Endress+Hauser13
3 InstallationProline Promag 53
Transporting flanged devices (DN ≥ 350):
Use only the metal eyes on the flanges for transporting the device, lifting it and positioning the
sensor in the piping.
Caution!
"
Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing. This
would buckle the casing and damage the internal magnetic coils.
F06-5xFxxxxx-22-xx-xx-xx-001
Fig. 6:Transporting sensors with DN ≥350
3.1.3Storage
Note the following points:
• Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
• The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors.
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
• Choose a storage location where moisture does not collect in the measuring device. This will help
prevent fungus and bacteria infestation which can damage the liner.
• Do not remove the protective plates or caps on the process connections until you are ready to
install the device. This is particularly important in the case of sensors with PTFE linings.
14Endress+Hauser
Proline Promag 533 Installation
3.2Installation conditions
3.2.1Dimensions
All the dimensions and lengths of the sensor and transmitter are provided in the separate
documentation “Technical Information”
3.2.2Mounting location
Correct measuring is possible only if the pipe is full. Avoid the following locations:
• Highest point of a pipeline. Risk of air accumulating
• Directly upstream a free pipe outlet in a vertical pipeline.
F06-5xxxxxxx-11-00-00-xx-000
Fig. 7:Location
Installation of pumps
Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and
the consequent risk of damage to the lining of the measuring tube. Information on the lining's resistance to partial vacuum can be found on → Page 132.
It might be necessary to install pulse dampers in systems incorporating reciprocating, diaphragm or
peristaltic pumps. Information on the measuring system's resistance to vibration and shock can be
found on → Page 129.
F06-5xxxxxxx-11-00-00-xx-001
Fig. 8:Installation of pumps
Endress+Hauser15
3 InstallationProline Promag 53
Partially filled pipes
Partially filled pipes with gradients necessitate a drain-type configuration. The Empty Pipe Detection
function (see Page 93) offers additional protection by detecting empty or partially filled pipes.
Caution!
"
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain.
It is advisable to install a cleaning valve.
F06-5xxxxxxx-11-00-00-xx-002
Fig. 9:Installation in partially filled pipe
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes longer than 5 meters. This
precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring
tube. These measures also prevent the system losing prime, which could cause air inclusions.
Information on the lining's resistance to partial vacuum can be found on Page 132.
F06-5xxxxxxx-11-00-00-xx-003
Fig. 10:Measures for installation in a down pipe (a = vent valve; b = siphon)
16Endress+Hauser
Proline Promag 533 Installation
3.2.3Orientation
An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring tube. Promag, nevertheless, supplies a range of functions and accessories for correct measuring
of problematic fluids:
• Electrode Cleaning Circuit (ECC) for applications with accretive fluids, e.g. electrically conductive deposits → “Description of Device Functions” manual.
• Empty Pipe Detection (EPD) ensures the detection of partially filled measuring tubes, e.g. in the
case of degassing fluids or varying process pressures (see Page 93)
• Exchangeable Measuring Electrodes for abrasive fluids (see Page 120)
Vertical orientation
This is the ideal orientation for self-emptying piping systems and for use in conjunction with Empty
Pipe Detection.
"
F06-5xxxxxxx-11-00-00-Nxx-004
Fig. 11:Vertical orientation
Horizontal orientation
The measuring electrode plane should be horizontal. This prevents brief insulation of the two
electrodes by entrained air bubbles.
Caution!
Empty Pipe Detection functions correctly with the measuring device installed horizontally only
when the transmitter housing is facing upward (Fig. 12). Otherwise there is no guarantee that
Empty Pipe Detection will respond if the measuring tube is only partially filled or empty.
F06-5xxxxxxx-11-00-xx-xx-000
Fig. 12:Horizontal orientation
1EPD electrode for the detection of empty pipes (not with Promag H, DN 2…4)
2Measurement electrodes for the signal acquisition
3Reference electrode for the potential equalisation (not with Promag H)
Endress+Hauser17
3 InstallationProline Promag 53
Inlet and outlet runs
If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. Compliance
with the following requirements for the inlet and outlet runs is necessary in order to ensure measuring accuracy.
• Inlet run ≥ 5 x DN
•Outlet run ≥ 2 x DN
"
F06-5xxxxxxx-11-00-00-xx-005
Fig. 13:Inlet and outlet runs
3.2.4Vibrations
Secure the piping and the sensor if vibration is severe.
Caution!
It is advisable to install sensor and transmitter separately if vibration is excessively severe. Information on resistance to vibration and shock can be found on → Page 129.
> 10 m
F06-5xxxxxxx-11-00-00-xx-006
Fig. 14:Measures to prevent vibration of the measuring device
18Endress+Hauser
Proline Promag 533 Installation
3.2.5Foundations, supports
If the nominal diameter is DN ≥ 350, mount the transmitter on a foundation of adequate loadbearing strength.
Caution!
"
Risk of damage. Do not support the weight of the sensor on the metal casing: the casing would
buckle and damage the internal magnetic coils.
Fig. 15:Correct support for large nominal diameters (DN ≥ 350)
F06-5xFxxxxx-11-05-xx-xx-000
Endress+Hauser19
3 InstallationProline Promag 53
3.2.6Adapters
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in largerdiameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very
slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by
cross-section reduction:
!
Note!
The nomogram applies to fluids of viscosity similar to water.
1.Calculate the ratio of the diameters d/D.
2.From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
[mbar]
100
8 m/s
7 m/s
6 m/s
max. 8°
10
d
D
1
5 m/s
4 m/s
3 m/s
2 m/s
1 m/s
!
0.5
0.60.70.80.9
d / D
F06-5xxxxxxx-05-05-xx-xx-000
Fig. 16:Pressure loss due to adapters
3.2.7Nominal diameter and flow rate
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum velocity of flow is 2…3 m/s. The velocity of flow (v), moreover, has to be matched to the
physical properties of the fluid:
• v < 2 m/s: for abrasive fluids such as potter's clay, lime milk, ore slurry, etc.
• v > 2 m/s: for fluids producing build-up such as wastewater sludge, etc.
Note!
Flow velocity can be increased, if necessary, by reducing the nominal diameter of the sensor
(see Section 3.2.6).
20Endress+Hauser
Proline Promag 533 Installation
Promag W
Flow rate characteristic values - Promag W (SI units)
Nominal
diameter
Recommended
flow rate
min./max. full scale value
[mm][inch]
(v ~ 0.3 or 10 m/s)
251"9…300 dm
321 1/4"15…500 dm
401 1/2"25…700 dm
502"35…1100 dm
652 1/2"60…2000 dm
803"90…3000 dm
1004"145…4700 dm
1255"220…7500 dm
1506"20…600 m
2008"35…1100 m
25010"55…1700 m
30012"80…2400 m
35014"110…3300 m
40016"140…4200 m
45018"180…5400 m
50020"220…6600 m
60024"310…9600 m
70028"420…13500 m
–30"480…15000 m
80032"550…18000 m
90036"690…22500 m
100040"850…28000 m
−42"950…30000 m
120048"1250…40000 m
–54"1550…50000 m
1400–1700…55000 m
−60"1950…60000 m
1600–2200…70000 m
−66"2500…80000 m
180072"2800…90000 m
−78"3300…100000 m
2000–3400…110000 m
Factory settings
Full scale value
(v ~ 2.5 m/s)
3
/min75 dm3/min0.50 dm
3
/min125 dm3/min1.00 dm
3
/min200 dm3/min1.50 dm
3
/min300 dm3/min2.50 dm
3
/min500 dm3/min5.00 dm
3
/min750 dm3/min5.00 dm
3
/min1200 dm3/min10.00 dm
3
/min1850 dm3/min15.00 dm
3
/h150 m3/h0.025 m
3
/h300 m3/h0.05 m
3
/h500 m3/h0.05 m
3
/h750 m3/h0.10 m
3
/h1000 m3/h0.10 m
3
/h1200 m3/h0.15 m
3
/h1500 m3/h0.25 m
3
/h2000 m3/h0.25 m
3
/h2500 m3/h0.30 m
3
/h3500 m3/h0.50 m
3
/h4000 m3/h0.50 m
3
/h4500 m3/h0.75 m
3
/h6000 m3/h0.75 m
3
/h7000 m3/h1.00 m
3
/h8000 m3/h1.00 m
3
/h10000 m3/h1.50 m
3
/h13000 m3/h1.50 m
3
/h14000 m3/h2.00 m
3
/h16000 m3/h2.00 m
3
/h18000 m3/h2.50 m
3
/h20500 m3/h2.50 m
3
/h23000 m3/h3.00 m
3
/h28500 m3/h3.50 m
3
/h28500 m3/h3.50 m
Pulse value
(~ 2 pulse/s)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Low flow cutoff
(v ~ 0.04 m/s)
1dm3/min
2dm3/min
3dm3/min
5dm3/min
8dm3/min
12 dm3/min
20 dm3/min
30 dm3/min
2.5 m3/h
5.0 m3/h
7.5 m3/h
10 m3/h
15 m3/h
20 m3/h
25 m3/h
30 m3/h
40 m3/h
50 m3/h
60 m3/h
75 m3/h
100 m3/h
125 m3/h
125 m3/h
150 m3/h
200 m3/h
225 m3/h
250 m3/h
300 m3/h
325 m3/h
350 m3/h
450 m3/h
450 m3/h
Endress+Hauser21
3 InstallationProline Promag 53
Flow rate characteristic values - Promag W (US units)
In order to ensure measuring accuracy, comply with the following instructions when installing the
remote version:
• Secure the cable run or route the cable in a conduit. Movement of the cable can falsify the
measuring signal, particularly if the fluid conductivity is low.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalisation between sensor and transmitter, if necessary.
• The permissible cable length Lmax depends on the fluid conductivity (Fig. 17).
A minimum conductivity of 20 µS/cm is required for measuring demineralized water.
[ S/cm]µ
200
L
max
Fig. 17:Permissible cable length for the remote version
Gray shaded area = permissible range
Lmax = length of connecting cable in [m]
Medium conductivity in [
µ
S/cm]
100
5
10100200
L
max
[m]
F06-xxxxxxxx-05-xx-xx-xx-006
Endress+Hauser25
3 InstallationProline Promag 53
3.3Installation instruction
3.3.1Installing the Promag W sensor
!
Note!
Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
The sensor is designed for installation between the two piping flanges:
• Observe in any case the necessary screw tightening torques on Page 28 ff.
• The mounting of additional ground disks is described on Page 27.
F06-5xFxxxxx-17-05-xx-xx-000
Fig. 18:Installing the Promag W sensor
Seals
Comply with the following instructions when installing seals:
• Hard rubber lining → additional seals are always necessary!
• Polyurethane lining → additional seals are recommended
• For DIN flanges, use only seals acc. to DIN EN 1514-1.
• Make sure that the seals do not protrude into the piping cross-section.
"
Caution!
Risk of short circuit! Do not use electrically conductive sealing compound such as graphite.
An electrically conductive layer could form on the inside of the measuring tube and short-circuit the
measuring signal.
Ground cable (DN 15…2000)
If necessary, the special ground cable for potential equalisation can be ordered as an accessory
(see Page 101). Detailled assembly instructions → Page 57 ff.
26Endress+Hauser
Proline Promag 533 Installation
Assembly with ground disks (DN 25…300)
Depending on the application, e.g. with lined or ungrounded pipes (see Page 56 ff.), it may be
necessary to mount ground disks between the sensor and the pipe flange for potential equalisation.
Ground disks can be ordered separately as an accessory from Endress+Hauser (see Page 101).
Caution!
"
• In this case, when using ground disks (including seals) the total fitting length increases!
All the dimensions are provided in the separate documentation “Technical Information”.
• Hard rubber lining → install additional seals between the sensor and ground disk and between
the ground disk and pipe flange.
• Polyurethane lining → only install additional seals between the ground disk and pipe flange.
1.Place the ground disk and additional seal(s) between the instrument and the pipe flange
(Fig. 19).
2.Insert the bolts through the flange holes. Tighten the nuts so that they are still loose.
3.Now rotate the ground disk as shown in Fig. 19 until the handle strikes the bolts. This will
center the ground disk automatically.
4.Now tighten the bolts to the required torque (see Page 28 ff.)
5.Connect the ground disk to ground → Page 58.
Fig. 19:Assembly with ground disks (Promag W, DN 25…300)
F06-5xFxxxxx-17-05-xx-xx-001
Endress+Hauser27
3 InstallationProline Promag 53
Screw tightening torques (Promag W)
Note the following points:
• The tightening torques listed below are for lubricated threads only.
• Always tighten threaded fasteners uniformly and in diagonally opposite sequence.
• Overtightening the fasteners will deform the sealing faces or damage the seals.
• The tightening torques listed below apply only to pipes not subjected to tensile stress.
Promag W
Nominal diameter
[mm][bar]Hard rubberPolyurethane
25PN 404 x M 12−15
32PN 404 x M 16−24
40PN 404 x M 16−31
50PN 404 x M 16−40
65 *PN 168 x M 163227
65PN 408 x M 163227
80PN 168 x M 164034
80PN 408 x M 164034
100PN 168 x M 164336
100PN 408 x M 205950
125PN 168 x M 165648
125PN 408 x M 248371
150PN 168 x M 207463
150PN 408 x M 2410488
200PN 108 x M 2010691
200PN 1612 x M 207061
200PN 2512 x M 2410492
250PN 1012 x M 208271
250PN 1612 x M 249885
250PN 2512 x M 27150134
300PN 1012 x M 209481
300PN 1612 x M 24134118
300PN 2516 x M 27153138
350PN 1016 x M 20112118
350PN 1616 x M 24152165
350PN 2516 x M 30227252
400PN 1016 x M 24151167
400PN 1616 x M 27193215
400PN 2516 x M 33289326
450PN 1020 x M 24153133
450PN 1620 x M 27198196
450PN 2520 x M 33256253
500PN 1020 x M 24155171
500PN 1620 x M 30275300
500PN 2520 x M 33317360
EN (DIN)
Pressure rating
Threaded fastenersMax. tightening torque [Nm]
28Endress+Hauser
Proline Promag 533 Installation
Promag W
Nominal diameter
[mm][bar]Hard rubberPolyurethane
600PN 1020 x M 27206219
600 *PN 1620 x M 33415443
600PN 2520 x M 36431516
700PN 1024 x M 27246246
700PN 1624 x M 33278318
700PN 2524 x M 39449507
800PN 1024 x M 30331316
800PN 1624 x M 36369385
800PN 2524 x M 45664721
900PN 1028 x M 30316307
900PN 1628 x M 36353398
900PN 2528 x M 45690716
1000PN 1028 x M 33402405
1000PN 1628 x M 39502518
1000PN 2528 x M 52970971
1200PN 632 x M 30319299
1200PN 1032 x M 36564568
1200PN 1632 x M 45701753
1400PN 636 x M 33430398
1400PN 1036 x M 39654618
1400PN 1636 x M 45729762
1600PN 640 x M 33440417
1600PN 1040 x M 45946893
1600PN 1640 x M 5210071100
1800PN 644 x M 36547521
1800PN 1044 x M 45961895
1800PN 1644 x M 5211081003
2000PN 648 x M 39629605
2000PN 1048 x M 4510471092
2000PN 1648 x M 5613241261
* Designed acc. to EN 1092-1 (not to DIN 2501)
EN (DIN)
Pressure rating
Threaded fastenersMax. tightening torque [Nm]
Endress+Hauser29
3 InstallationProline Promag 53
Promag W
Nominal diameter
[mm][inch]Hard rubberPolyurethane
70028"Class D28 x 1 1/4"247292
75030"Class D28 x 1 1/4287302
80032"Class D28 x 1 1/2"394422
90036"Class D32 x 1 1/2"419430
100040"Class D36 x 1 1/2"420477
105042"Class D36 x 1 1/2"528518
120048"Class D44 x 1 1/2"552531
135054"Class D44 x 1 3/4"730633
150060"Class D52 x 1 3/4"758832
165066"Class D52 x 1 3/4"946955
180072"Class D60 x 1 3/4"9751087
200078"Class D64 x 2"853786
Promag W
Nominal diameter
[mm][inch][lbs]Hard rubberPolyurethane
251"Class 1504 x 1/2"−7
251"Class 3004 x 5/8"−8
401 1/2"Class 1504 x 1/2"−10
401 1/2"Class 3004 x 3/4"−15
502"Class 1504 x 5/8"−22
502"Class 3008 x 5/8"−11
803"Class 1504 x 5/8"6043
803"Class 3008 x 3/4"3826
1004"Class 1508 x 5/8"4231
1004"Class 3008 x 3/4"5840
1506"Class 1508 x 3/4"7959
1506"Class 30012 x 3/4"7051
2008"Class 1508 x 3/4"10780
25010"Class 15012 x 7/8"10175
30012"Class 15012 x 7/8"133103
35014"Class 15012 x 1"135158
40016"Class 15016 x 1"128150
45018"Class 15016 x 1 1/8"204234
50020"Class 15020 x 1 1/8"183217
60024"Class 15020 x 1 1/4"268307
AWWA
Pressure rating
ANSI
Pressure rating
Threaded fastenersMax. tightening torque [Nm]
Threaded fastenersMax. tightening torque [Nm]
30Endress+Hauser
Loading...
+ 116 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.