Endress+Hauser Omnigrad M TR13, Omnigrad TC13 Technical Information

Page 1
TR13 with resistance insert (RTD) TC13 with thermocouple insert (TC)
Application
• Universal range of application
• Measuring range: – Resistance insert (RTD): –200 to 600 °C (–328 to 1 112 °F) – Thermocouple (TC): –40 to 1 100 °C (–40 to 2 012 °F)
• Degree of protection: up to IP 68
Head transmitter
All Endress+Hauser transmitters are available with enhanced accuracy and reliability compared to directly wired sensors. Easy customizing by choosing one of the following outputs and communication protocols:
• Analog output 4 to 20 mA
• HART
®
• PROFIBUS® PA
• FOUNDATION Fieldbus™
Your benefits
• High degree of flexibility thanks to modular design with standard terminal heads as per DIN EN 50446 and customer-specific immersion lengths
• High degree of insert compatibility and design as per DIN 43772
• Extension neck to protect the head transmitter from overheating
• Fast response time with reduced/tapered tip form
• Types of protection for use in hazardous locations: – Intrinsic Safety (Ex ia) – Non-sparking (Ex nA)
Products Solutions Services
Technical Information
Omnigrad M TR13, TC13
Modular thermometer
TI01097T/09/EN/02.13 71226662
Page 2
Omnigrad M TR13, TC13
2
Function and system design
Measuring principle
Resistance thermometer (RTD)
These resistance thermometers use a Pt100 temperature sensor according to IEC 60751. The temperature sensor is a temperature-sensitive platinum resistor with a resistance of 100 Ω at 0 °C (32 °F) and a temperature coefficient α = 0.003851 °C-1.
There are generally two different kinds of platinum resistance thermometers:
Wire wound (WW): Here, a double coil of fine, high-purity platinum wire is located in a ceramic support. This is then sealed top and bottom with a ceramic protective layer. Such resistance thermometers not only facilitate very reproducible measurements but also offer good long-term stability of the resistance/temperature characteristic within temperature ranges up to 600 °C (1 112 °F). This type of sensor is relatively large in size and it is comparatively sensitive to vibrations.
Thin film platinum resistance thermometers (TF): A very thin, ultrapure platinum layer, approx. 1 μm thick, is vaporized in a vacuum on a ceramic substrate and then structured photolithographically. The platinum conductor paths formed in this way create the measuring resistance. Additional covering and passivation layers are applied and reliably protect the thin platinum layer from contamination and oxidation, even at high temperatures.
The primary advantages of thin film temperature sensors over wire wound versions are their smaller sizes and better vibration resistance. A relatively low principle-based deviation of the resistance/ temperature characteristic from the standard characteristic of IEC 60751 can frequently be observed among TF sensors at high temperatures. As a result, the tight limit values of tolerance category A as per IEC 60751 can only be observed with TF sensors at temperatures up to approx. 300 °C (572 °F). For this reason, thin-film sensors are generally only used for temperature measurements in ranges below 400 °C (932 °F).
Thermocouples (TC)
Thermocouples are comparatively simple, robust temperature sensors which use the Seebeck effect for temperature measurement: if two electrical conductors made of different materials are connected at a point, a weak electrical voltage can be measured between the two open conductor ends if the conductors are subjected to a thermal gradient. This voltage is called thermoelectric voltage or electromotive force (emf.). Its magnitude depends on the type of conducting materials and the temperature difference between the "measuring point" (the junction of the two conductors) and the "cold junction" (the open conductor ends). Accordingly, thermocouples primarily only measure differences in temperature. The absolute temperature at the measuring point can be determined from these if the associated temperature at the cold junction is known or is measured separately and compensated for. The material combinations and associated thermoelectric voltage/temperature characteristics of the most common types of thermocouple are standardized in the IEC 60584 and ASTM E230/ANSI MC96.1 standards.
Page 3
Omnigrad M TR13, TC13
3
Measuring system
A
°C
= 20-250V DC/AC
» 50/60Hz
4...20 mA
24V DC / 30 mA
B
C
A0010442
1 Application example
A Mounted thermometer with head transmitter installed. B RIA16 field display unit - The display unit records the analog measuring signal from the head transmitter and
shows this on the display. The LC display shows the current measured value in digital form and as a bar graph indicating a limit value violation. The display unit is looped into the 4 to 20 mA circuit and gets the required energy from there. More information on this can be found in the Technical Information (see "Documentation").
C Active barrier RN221N - The RN221N (24 V DC, 30 mA) active barrier has a galvanically isolated output for
supplying voltage to loop-powered transmitters. The universal power supply works with an input supply voltage of 20 to 250 V DC/AC, 50/60 Hz, which means that it can be used in all international power grids. More information on this can be found in the Technical Information (see "Documentation").
Design
E
1 2
3
4
5
66a 6b
IL
IL
L
10 mm (0.4 in)
7
A0010444
2 Thermometer design
1 Insert with head transmitter mounted (example with 3 mm (0.12 in)) 2 Insert with terminal block mounted (example with 6 mm (0.24 in)) 3 Terminal head 4 Thermowell 5 Process conneciton: flange 6 Various tip shapes - detailed information see chapter "Tip shape": 6a Reduced or tapered for inserts with 3 mm (0.12 in) 6b Straight or tapered for inserts with 6 mm (0.24 in) 7 Jacket (protective sheath) E Extension neck length L Immersion length IL Insertion length
Thermometers from the Omnigrad M TR13 and TC13 series have a modular design. The terminal head is used as a connection module for the mechanical and electrical connection of the insert. The position of the actual thermometer sensor in the insert ensures that it is mechanically protected. The insert can be exchanged and calibrated without interrupting the process. Either ceramic terminal blocks or transmitters can be fitted to the internal base washer.
Page 4
Omnigrad M TR13, TC13
4
Measurement range
RTD: –200 to 600 °C (–328 to 1 112 °F)
• TC: –40 to 1 100 °C (–40 to 2 012 °F)
Performance characteristics
Operating conditions
Ambient temperature
Terminal head Temperature in °C (°F)
Without mounted head transmitter Depends on the terminal head used and the cable gland or fieldbus
connector, see 'Terminal heads' section
With mounted head transmitter –40 to 85 °C (–40 to 185 °F)
With mounted head transmitter and display
–20 to 70 °C (–4 to 158 °F)
Process pressure
The pressure values to which the actual thermowell can be subjected at the various temperatures and maximum permitted flow velocity are illustrated by the figure below. Occasionally, the pressure loading capacity of the process connection can be considerably lower. The maximum allowable process pressure for a specific thermometer is derived from the lower pressure value of the thermowell and process connection.
0
50
100
150
200
150 200 250 300 350 400
P (bar)
0
150 200 250 300 350 400
L (mm)
P (bar)
50
100
150
200
A B
L (in)
6
8
10 12
0
700
2100
2900
P (PSI)
1400
14 166
8
10 12 14 16
0
700
2100
2900
P (PSI)
1400
L (mm)
L (in)
P ~ PN100max.
P ~ PN60max.
A0013494
3 Maximum permitted process pressure for tube diameter
A Medium water T = 50 °C (122 °F) B Medium superheated steam at T = 400 °C (752 °F) L Immersion length P Process pressure ___ Thermowell diameter 9 x 1 mm (0.35 in)
- - - Thermowell diameter 12 x 2.5 mm (0.47 in)
Page 5
Omnigrad M TR13, TC13
5
Note the limitation of the maximum process pressure to the flange pressure ratings indicated in the following table.
Process connection
Standard Max. process pressure
Flange EN1092-1 or ISO
7005-1
Depending on the flange pressure rating PNxx: 20, 40, 50 or 100 bar at
20 °C (68 °F)
ASME B16.5 Depending on the flange pressure rating 150 or 300 psi at
20 °C (68 °F)
JIS B 2220 Depending on the flange pressure rating 20K, 25K or 40K
DIN2526/7 Depending on the flange pressure rating PN40 at 20 °C (68 °F)
Maximum flow velocity
The highest flow velocity tolerated by the thermowell diminishes with increasing immersion length exposed to the stream of the fluid. Detailed information may be taken from the figures below.
100 200 300 400 500
v (m/s)
A
100 200 300 400 500
v (m/s)
B
4
8
12 16 20
4
8
12 16
v (ft/s)
v (ft/s)
L (mm)
0
10
20
30
40
50
60
70
80
90
L (in)
20
0
30
65
100
130
165
200
230
260
295
0
5
10
15
20
25
30
35
40
45
0
15
30
50
65
80
100
115
130
145
L (mm)
L (in)
50
2
50
2
A0008605
4 Flow velocity depending on the immersion length
A Medium water at T = 50 °C (122 °F) B Medium superheated steam at T = 400 °C (752 °F) L Immersion length v Flow velocity ___ Thermowell diameter 9 x 1 mm (0.35 in)
- - - Thermowell diameter 12 x 2.5 mm (0.47 in)
Shock and vibration resistance
RTD: 3G / 10 to 500 Hz according to IEC 60751
• TC: 4G / 2 to 150 Hz according to IEC 60068-2-6
Page 6
Omnigrad M TR13, TC13
6
Accuracy
RTD resistance thermometer as per IEC 60751
Class Max. tolerances (°C) Characteristics
Cl. AA, former 1/3 Cl. B
± (0.1 + 0.0017 · |t|
1)
)
A
AA
-200 -100 0 100 200 300 400 500 600°C
0.5
1.0
1.5
2.0
B
2.5
3.0
- 0.5
- 1.0
- 1.5
- 2.0
- 2.5
- 3.0
B
A
AA
Max. deviation (°C)
Max. deviation (°C)
A0008588-EN
Cl. A ± (0.15 + 0.002 · |t|
1)
)
Cl. B ± (0.3 + 0.005 · |t|
1)
)
Temperature ranges for compliance with the tolerance classes
Wire wound sensor (WW):
Cl. A Cl. AA
–100 to +450
°C
–50 to +250 °C
Thin-film version (TF):
Cl. A Cl. AA
• Standard
• iTHERM
®
StrongSens
–30 to +300 °C
–30 to +300 °C
0 to +150 °C
0 to +200 °C
1) |t| = absolute value °C
In order to obtain the maximum tolerances in °F, the results in °C must be multiplied by a factor of 1.8.
Permissible deviation limits of thermoelectric voltages from the standard characteristic for thermocouples as per IEC 60584 or ASTM E230/ANSI MC96.1:
Standard Type Standard tolerance Special tolerance
IEC 60584 Class Deviation Class Deviation
J (Fe-CuNi) 2 ±2.5 °C (–40 to 333 °C)
±0.0075 |t|
1)
(333 to 750 °C)
1 ±1.5 °C (–40 to 375 °C)
±0.004 |t|
1)
(375 to 750 °C)
K (NiCr-NiAl) 2 ±2.5 °C (–40 to 333 °C)
±0.0075 |t|
1)
(333 to 1 200 °C)
1 ±1.5 °C (–40 to 375 °C)
±0.004 |t|
1)
(375 to 1 000 °C)
1) |t| = absolute value °C
Standard Type Standard tolerance Special tolerance
ASTM E230/ANSI MC96.1
Deviation, the larger respective value applies
J (Fe-CuNi) ±2.2 K or ±0.0075 |t|
1)
(0 to 760
°C) ±1.1 K or ±0.004 |t|
1)
(0 to 760 °C)
K (NiCr-NiAl) ±2.2 K or ±0.02 |t|
1)
(–200 to 0 °C)
±2.2 K or ±0.0075 |t|
1)
(0 to 1 260 °C)
±1.1 K or ±0.004 |t|
1)
(0 to 1 260 °C)
1) |t| = absolute value °C
Page 7
Omnigrad M TR13, TC13
7
Response time
Calculated at an ambient temperature of approx. 23 °C by immersing in running water (0.4 m/s flow rate, 10 K excess temperature):
Complete assembly:
Thermometer type
Diameter t
(x)
Reduced tip Tapered tip Straight tip
Resistance thermometer (measuring probe Pt100, TF/WW)
9 mm (0.35 in) t
50
7.5 s 11 s 18 s
t
90
21 s 37 s 55 s
11 mm (0.43 in) t
50
7.5 s not available 18 s
t
90
21 s not available 55 s
12 mm (0.47 in) t
50
not available 11 s 38 s
t
90
not available 37 s 125 s
Thermo­meter type
Diameter t
(x)
Grounded Ungrounded
Reduced tip
Tapered tip
Straight tip
Reduced tip
Tapered tip
Straight tip
Thermo­couple
9 mm (0.35 in)
t
50
5.5 s 9 s 15 s 6 s 9.5 s 16 s
t
90
13 s 31 s 46 s 14 s 33 s 49 s
11 mm (0.43 in)
t
50
5.5 s not available
15 s 6 s not
available
16 s
t
90
13 s not
available
46 s 14 s not
available
49 s
12 mm (0.47 in)
t
50
not available
8.5 s 32 s not
available
9 s 34 s
t
90
not available
20 s 106 s not
available
22 s 110 s
Response times for insert without transmitter.
Page 8
Omnigrad M TR13, TC13
8
Tested in accordance with IEC 60751 in flowing water (0.4 m/s at 30 °C):
Insert:
Sensor type Diameter ID Response time Thin film (TF)
iTHERM® StrongSens 6 mm (0.24 in) t
50
<3.5 s
t
90
<10 s
TF Sensor
3 mm (0.12 in) t
50
2.5 s
t
90
5.5 s
6 mm (0.24 in) t
50
5 s
t
90
13 s
WW Sensor
3 mm (0.12 in) t
50
2 s
t
90
6 s
6 mm (0.24 in) t
50
4 s
t
90
12 s
Thermocouple (TPC100) grounded
3 mm (0.12 in) t
50
0.8 s
t
90
2 s
6 mm (0.24 in) t
50
2 s
t
90
5 s
Thermocouple (TPC100) ungrounded
3 mm (0.12 in) t
50
1 s
t
90
2.5 s
6 mm (0.24 in) t
50
2.5 s
t
90
7 s
Response time for the sensor assembly without transmitter.
Insulation resistance
RTD: Insulation resistance according to IEC 60751 > 100 MΩ at 25 °C between terminals and sheath material measured with a minimum test voltage of 100 V DC
• TC: Insulation resistance according to IEC 1515 between terminals and sheath material with a test voltage of 500 V DC: – > 1 GΩ at 20 °C – > 5 MΩ at 500 °C
Dielectric strength
Tested at a room temperature for 5 s:
6: ≥1 000 V DC between terminals and insert sheath
• 3: ≥250 V DC between terminals and insert sheath
Self heating
RTD elements are passive resistances that are measured using an external current. This measurement current causes a self-heating effect in the RTD element itself which in turn creates an additional measurement error. In addition to the measurement current, the size of the measurement error is also affected by the temperature conductivity and flow velocity of the process. This self­heating error is negligible when an Endress+Hauser iTEMP® temperature transmitter (very small measurement current) is connected.
Calibration
Endress+Hauser provides comparison temperature calibration from –80
to +1 400 °C (–110 to +2 552 °F) based on the International Temperature Scale (ITS90).
Page 9
Omnigrad M TR13, TC13
9
Calibrations are traceable to national and international standards. The calibration certificate is referenced to the serial number of the thermometer. Only the insert is calibrated.
Insert: ⌀6
mm (0.24 in) and 3 mm (0.12 in)
Minimum insertion length of insert in mm (in)
Temperature range without head transmitter with head transmitter
–80 to –40 °C (–110 to –40 °F) 200 (7.87)
–40 to 0 °C (–40 to 32 °F) 160 (6.3)
0 to 250 °C (32 to 480 °F) 120 (4.72) 150 (5.91)
250 to 550 °C (480 to 1 020 °F) 300 (11.81)
550 to 1 400 °C (1 020 to 2 552 °F) 450 (17.72)
Material
Extension neck, thermowell and insert
The temperatures for continuous operation specified in the following table are only intended as reference values for use of the various materials in air and without any significant compressive load. The maximum operation temperatures are reduced considerably in some cases where abnormal conditions such as high mechanical load occur or in aggressive media.
Material name Short form Recommended max.
temperature for continuous use in air
Properties
Wetted parts
AISI 316L/
1.4404
1.4435
X2CrNiMo17-12-2 X2CrNiMo18-14-3
650 °C (1 202
°F)
1)
• Austenitic, stainless steel
• High corrosion resistance in general
• Particularly high corrosion resistance in chlorine-based and acidic, non­oxidizing atmospheres through the addition of molybdenum (e.g. phosphoric and sulfuric acids, acetic and tartaric acids with a low concentration)
• Increased resistance to intergranular corrosion and pitting
• Compared to 1.4404, 1.4435 has even higher corrosion resistance and a lower delta ferrite content
AISI 316Ti/
1.4571
X6CrNiMoTi17-12-2 700 °C (1 292 °F)
1)
• Properties comparable to AISI316L
• Addition of titanium means increased resistance to intergranular corrosion even after welding
• Broad range of uses in the chemical, petrochemical and oil industries as well as in coal chemistry
• Can only be polished to a limited extent, titanium streaks can form
Inconel600/
2.4816
NiCr15Fe 1 100 °C (2 012 °F) • A nickel/chromium alloy with very
good resistance to aggressive, oxidizing and reducing atmospheres, even at high temperatures
• Resistance to corrosion caused by chlorine gases and chlorinated media as well as many oxidizing mineral and organic acids, sea water etc.
• Corrosion from ultrapure water
• Not to be used in sulfur-containing atmospheres
Page 10
Omnigrad M TR13, TC13
10
Material name Short form Recommended max.
temperature for continuous use in air
Properties
Hastelloy C276/2.4819
NiMo16Cr15W 1 100
°C (2 012 °F) • A nickel-based alloy with good
resistance to oxidizing and reducing atmospheres, even at high temperatures
• Particularly resistant to chlorine gas and chloride as well as to many oxidizing mineral and organic acids
Jacket
PTFE (Teflon) Polytetrafluorethylen 200 °C (392 °F) • Resistant to almost all chemicals
• High temperature stability
PVDF Polyvinylidene fluoride 80 °C (176 °F) • High stability
• A high creepage stability under continuous demand
• Good cold properties
Tantalum - 250 °C (482 °F) • With the exception of hydrofluoric
acid, fluorine and fluorides, tantalum exhibits excellent resistance to most mineral acids and saline solutions
• Prone to oxidation and embrittlement at higher temperatures in air
1) Can be used to a limited extent up to 800 °C (1472 °F) for low compressive loads and in non-corrosive media. Please contact your Endress+Hauser sales team for further information.
Components
Family of temperature transmitters
Thermometers fitted with iTEMP® transmitters are an installation-ready complete solution to improve temperature measurement by significantly increasing accuracy and reliability, when compared to direct wired sensors, as well as reducing both wiring and maintenance costs.
PC programmable head transmitters
They offer a high degree of flexibility, thereby supporting universal application with low inventory storage. The iTEMP® transmitters can be configured quickly and easily at a PC. Endress+Hauser offers free configuration software which can be downloaded from the Endress+Hauser Website. More information can be found in the Technical Information.
HART®
programmable head transmitters
The transmitter is a 2-wire device with one or two measuring inputs and one analog output. The device not only transfers converted signals from resistance thermometers and thermocouples, it also transfers resistance and voltage signals using HART® communication. It can be installed as an intrinsically safe apparatus in Zone 1 hazardous areas and is used for instrumentation in the terminal head (flat face) as per DIN EN 50446. Swift and easy operation, visualization and maintenance by PC using operating software, Simatic PDM or AMS. For more information, see the Technical Information.
PROFIBUS® PA head transmitters
Universally programmable head transmitter with PROFIBUS® PA communication. Conversion of various input signals into digital output signals. High accuracy over the complete ambient temperature range. Swift and easy operation, visualization and maintenance using a PC directly from the control panel, e. g. using operating software, Simatic PDM or AMS. For more information, see the Technical Information.
FOUNDATION Fieldbus™ head transmitters
Universally programmable head transmitter with FOUNDATION Fieldbus™ communication. Conversion of various input signals into digital output signals. High accuracy over the complete ambient temperature range. Swift and easy operation, visualization and maintenance using a PC directly from the control panel, e.g. using operating software such as ControlCare from Endress +Hauser or NI Configurator from National Instruments. For more information, see the Technical Information.
Page 11
Omnigrad M TR13, TC13
11
Advantages of the iTEMP® transmitters:
Dual or single sensor input (optionally for HART® transmitter)
• Unsurpassed reliability, accuracy and long-term stability in critical processes
• Mathematical functions
• Monitoring of the thermometer drift, sensor backup functionality, sensor diagnostic functions
• Sensor-transmitter matching based on Callendar/Van Dusen coefficients
Terminal heads
All terminal heads have an internal shape and size in accordance with DIN EN 50446 flat face and a thermometer connection of M24x1.5, G1/2" or 1/2" NPT thread. All dimensions in mm (in). The cable glands in the diagrams correspond to M20x1.5 connections. Specifications without head transmitter installed. For ambient temperatures with head transmitter installed, see "Operating conditions" section.
TA30A Specification
107.5 (4.23)
68.5 (2.7)
28
(1.1)
78 (3.1)
15.5 (0.6)
A0009820
• Available with one or two cable entries
Protection class: IP66/68 (NEMA Type 4x encl.)
• Temperature: –50 to +150 °C (–58 to +302 °F) without cable gland
• Material: aluminum, polyester powder coated Seals: silicone
• Threaded cable entry: G ½", ½" NPT and M20x1.5;
• Protection armature connection: M24x1.5
• Head color: blue, RAL 5012
• Cap color: gray, RAL 7035
• Weight: 330 g (11.64 oz)
• Ground terminal, internal and external
• With 3-A® symbol
TA30A with display window Specification
107.5 (4.23)
91.6 (3.61)
28
(1.1)
78 (3.1)
15.5 (0.6)
A0009821
• Available with one or two cable entries
Protection class: IP66/68 (NEMA Type 4x encl.)
• Temperature: –50 to +150 °C (–58 to +302 °F) without cable gland
• Material: aluminum, polyester powder coated Seals: silicone
• Threaded cable entry: G ½", ½" NPT and M20x1.5
• Protection armature connection: M24x1.5
• Head color: blue, RAL 5012 Cap color: gray, RAL 7035
• Weight: 420 g (14.81 oz)
• With TID10 display
• Ground terminal, internal and external
• With 3-A® symbol
Page 12
Omnigrad M TR13, TC13
12
TA30D Specification
107.5 (4.23)
110 (4.3)
28
(1.1)
78 (3.1)
15.5 (0.6)
A0009822
• Available with one or two cable entries
Protection class: IP66/68 (NEMA Type 4x encl.)
• Temperature: –50 to +150 °C (–58 to +302 °F) without cable gland
• Material: aluminum, polyester powder coated Seals: silicone
• Threaded cable entry: G ½", ½" NPT and M20x1.5
• Protection armature connection: M24x1.5
• Two head transmitters can be mounted. In the standard version, one transmitter is mounted in the terminal head cover and an additional terminal block is installed directly on the insert.
• Head color: blue, RAL 5012
• Cap color: gray, RAL 7035
• Weight: 390 g (13.75 oz)
• Ground terminal, internal and external
• With 3-A® symbol
TA30P Specification
!83 (3.3)
114 (4.5)
11 (0.43)
68 (2.7)
41.5 (1.63)
A0012930
• Protection class: IP65
Max. temperature: –40 to +120 °C (–40 to +248 °F)
• Material: polyamide (PA), antistatic Seals: silicone
• Threaded cable entry: M20x1.5
• Protection armature connection: M24x1.5
• Head and cap color: black
• Weight: 135 g (4.8 oz)
• Types of protection for use in hazardous locations: Intrinsic Safety (G Ex ia)
• Ground terminal: only internal via auxiliary clamp
TA20B Specification
116 (6.54)
25 (1)
84 (3.3)
73 (2.87)
A0008663
• Protection class: IP65
Max. temperature: 80 ˚C (176 ˚F)
• Material: polyamide (PA)
• Cable entry: M20x1.5
• Head and cap color: black
• Weight: 80 g (2.82 oz)
• 3-A® marked
Page 13
Omnigrad M TR13, TC13
13
TA21E Specification
84 (3.3)
95 (3.9)
57 (2.2)
122 (4.8)
28 (1.1)
A0008669
• Protection class: IP65
Max. temperature: 130 °C (266 °F) silicone, 100 °C (212 °F) rubber seal without cable gland (observe max. permitted temperature of the cable gland!)
• Material: aluminum alloy with polyester or epoxy coating, rubber or silicone seal under the cover
• Cable entry: M20x1.5 or plug M12x1 PA
• Protection armature connection: M24x1.5, G 1/2" or NPT 1/2"
• Head color: blue, RAL 5012
• Cap color: gray, RAL 7035
• Weight: 300 g (10.58 oz)
• 3-A® marked
TA20J Specification
114 (4.49)
119 (4.7)*
28 (1.1)
89 (3.5)
41 (1.61)
64 (2.52)
A0008866
* dimensions with optional display
• Protection class: IP66/IP67
Max. temperature: 70 °C (158 °F)
• Material: 316L (1.4404) stainless steel, rubber seal under the cover (hygienic design)
• 4 digits 7-segments LC display (loop powered with optional4 to 20 mA transmitter)
• Cable entry: 1/2" NPT, M20x1.5 o plug M12x1 PA
• Protection armature connection: M24x1.5 or 1/2" NPT
• Head and cap color: stainless steel, polished
• Weight: 650 g (22.93 oz) with display
• Humidity: 25 to 95 %, no condensation
• 3-A® marked
The programming is executed through 3 keys at the bottom of the display.
TA20R Specification
79 (3.11)
53 (2.1)
54 (2.13)
81 (3.2)
28 (1.1)
!55 (2.17)
A0008667
• Protection class: IP66/67
Max. temperature: 100 °C (212 °F)
• Material: SS 316L (1.4404) stainless steel
• Cable entry: 1/2" NPT, M20x1.5 or plug M12x1 PA
• Head and cap color: stainless steel
• Weight: 550 g (19.4 oz)
• LABS-free
• 3-A® marked
Page 14
Omnigrad M TR13, TC13
14
Maximum ambient temperatures for cable glands and fieldbus connectors
Type Temperature range
Cable gland ½" NPT, M20x1.5 (non Ex) –40 to +100 °C (–40 to +212 °F)
Cable gland M20x1.5 (for dust ignition-proof area) –20 to +95 °C (–4 to +203 °F)
Fieldbus connector (M12x1 PA, 7/8" FF) –40 to +105 °C (–40 to +221 °F)
Design
All dimensions in mm (in).
M4x1
!6 (0.24)
L
E
10 (0.4)
10 (0.4)
75 (3)
!33 (1.3)
!42 (1.65)
!33 (1.3)
!42 (1.65)
!X
!ID
!ID
1 2
3
IL
!X
5 (0.2)
12 (0.47)
4
!33 (1.3)
!44 (1.73)
L
0.5 (0.02)
0.5 (0.02)
!12x11
5
A0010446
5 Dimensions of the Omnigrad M TR13 and TC13
1 Insert with terminal block mounted 2 Insert with head transmitter mounted 3 Insert with flying leads 4 Jacket (PTFE/PVDF) 5 Jacket (Tantalum) E Extension neck length ID Insert diameter IL Total length of insert L Immersion length X Thermowell diameter
Page 15
Omnigrad M TR13, TC13
15
Tip shape
40 (1.6)
35 (1.34)
50 (1.97)
20 (0.8)
40 (1.6)
20
(0.8)
T
R
M
W
5 (0.2)
!6.6 (0.26)
!5.3 (0.21)
!5.3 (0.21)
S
3.2
(0.13)
3 (0.12)
~3.5 (0.14)
6.1 (0.24)
3
(0.12)
3.2 (0.13)
3
(0.12)
7 (0.28)!
1-2.5 (0.04-0.1)
! !11 (0.43)
9 (0.35)
!9 (0.35)
!9 (0.35)
!12 (0.47)
!9 (0.35)
!12 (0.47)
S
6.5 (0.26)!
1-2.5 (0.04-0.1)
!9 (0.35)
S
7 (0.28)!
1-2.5 (0.04-0.1)
!11 (0.43)
S
11 (0.43)!
1-2.5 (0.04-0.1)
!15 (0.59)
S
10 (0.39)!
1-2.5 (0.04-0.1)
!14 (0.55)
A0019347
6 Available thermowell tips (reduced, straight or tapered). Maximum surface roughness Ra ≤ 1.6 μm
(62.9 μin)
Pos. No. Tip shape, L = immersion length Insert diameter
M Reduced, L ≥70 mm (2.76 in) 3 mm (0.12 in)
R Reduced, L ≥50 mm (1.97 in)
1)
3 mm (0.12 in)
S Straight 6 mm (0.24 in)
T Tapered, L ≥70 mm (2.75 in)
1)
3 mm (0.12 in)
W Tapered DIN43772-3G, L ≥90 mm (3.54 in)
1)
6 mm (0.24 in)
1)
not with material Hastelloy® C276/2.4819 and Inconel600
Jacket
For thermowells with straight tip shape and protection tube diameter 11 mm (PTFE/Tantalum) and 12 mm (PVDF) (0.43 and 0.47 in), a jacket in PTFE (Teflon®), PVDF or Tantalum is available. The external diameter of the thermowell stem will be 15 mm (PTFE) and 16 mm (PVDF) (0.6 and 0.63 in), for Tantalum 12 mm (0.47 in). The immersion length L will be slightly higher also because of the different thermal expansion of the thermowell and jacket. The upper part of the jacket is fitted with a disc of the same material that is inserted between the flange and counterflange.
Page 16
Omnigrad M TR13, TC13
16
Insert
Depending on the application different inserts are available for the assembly:
RTD
Selection in order code
A B C F G 2 3 6 7 S T U V
Sensor design; wiring type
1x
Pt100
WW; 3-
wire
2x
Pt100
WW; 3-
wire
1x
Pt100
WW; 4-
wire
2x
Pt100
WW; 3-
wire
1x
Pt100
WW; 4-
wire
1x Pt100 TF; 3-
wire
1x Pt100 TF; 4-
wire
1x Pt100 TF; 3-
wire
1x Pt100 TF; 4-
wire
1x Pt100 TF; 3-
wire
1x Pt100 TF; 4-
wire
1x Pt100 TF; 3-
wire
1x Pt100 TF; 4-
wire
Vibration resistance for the tip of the insert
Vibration resistance up to 3g Increased vibration resistance up to 4g
iTHERM® StrongSens®
vibration
resistance > 60g
Measuring range; accuracy class with temperature range
–200 to 600 °C; cl. A,
–200 to 600 °C
–200 to 600 °C; cl.
AA, 0 to 250 °C
–50 to 400 °C; cl. A, –50 to 250 °C
–50 to 400 °C; cl.
AA, 0 to 150 °C
–50 to 500 °C;
cl. A,
–30 to 300 °C
–50 to 500 °C;
cl. AA,
0 to 200 °C
Insert type TPR100 iTHERM® TS111
Diameter 3 mm (0.12 in) or 6 mm (0.24 in), depending on the selected tip shape 6 mm (0.24 in)
TC
Selection in order code A B E F
Sensor design; material 1x K; INCONEL600 2x K; INCONEL600 1x J; 316L 2x J; 316L
Measuring range according to:
DIN EN 60584 –40 to 1 200
°C –40 to 750 °C
ANSI MC 96.1 0 to 1 250 °C 0 to 750 °C
TC Standard, accuracy IEC 60584-2; class 1
ASTM E230-03; special
Insert type TPC100
Diameter 3 mm (0.12 in) or 6 mm (0.24 in), depending on the selected tip shape
Weight
From 1.5 to 3.5 kg (3.3 to 7.7 lbs)
for standard options.
Page 17
Omnigrad M TR13, TC13
17
Process connection
The following figure shows the basic dimensions of the available flanges.
Flange
L
D
K
d
b
f
A0010471
For detailed information on the flange dimensions refer to the following flange standards:
ANSI/ASME B16.5
• ISO 7005-1
• EN 1092-1
• JIS B 2220 : 2004
The flange material must be the same as of the stem of the thermowell. For this reason, connections are available both in 316L/1.4404 and in 316Ti/1.4571. Models in Hastelloy
®
have flanges in basic material 316L/1.4404 and a disc in Hastelloy® on the surface in contact with the process media. For the specification PVDF/PTFE/Tantalum thermowell an additional jacket with a disc on the upper end will be used. The standard surface finish of the coupling side of flanges ranges from 3.2 to 6.4 µm (Ra). Other types of flanges can be supplied on request.
Spare parts
The thermowell TW13 is available as spare part (→  25)
• The Jacket (TA730) is available as spare part (→  25)
• The gasket set M24x1.5, aramid+NBR (material no. 60001329) is available as spare part
• The RTD insert is available as spare part TPR100 (→  25)
• The iTHERM® StrongSens is available as spare part TS111 (→  25)
• The TC insert is available as spare part TPC100 (→  25) The inserts are made from mineral insulated cable (MgO) with a sheath in AISI316L/1.4404 (RTD)
or Inconel600 (TC).
If spare parts are required, refer to the following equation:
Insertion length IL = E + L + 10 mm (0.4 in)
Page 18
Omnigrad M TR13, TC13
18
Wiring
Wiring diagrams for RTD
Type of sensor connection
Head mounted transmitter TMT18x (single input)
3
5
6
RTD
3
4
5
6
RTD
1
2
3-wire
4-wire
Power supply head transmitter and analog output 4 to 20 mA, or bus connection
(red)
(red)
(red) (red)
(white) (white)
(white)
mA
A0016433-EN
Head mounted transmitter TMT8x (dual input)
-
+
+
1
-
2
7
6
5
4
3
1
2
7
6
5
4
3
Sensor input 2
Sensor input 1
RTD - and 3-wire: 4
RTD 3-wire:
Bus connection
and supply voltage
Display connection
red
white
red
red
red
white
white
(black)
(black)
(yellow)
A0008848-EN
Terminal block mounted
1 x Pt100
1 x Pt100
2 x Pt100
red
red
white
black
4 wires
3 wires 3 wires
white
red
red
black
yellow
red
white
red
white
A0008591-EN
Wiring diagrams for TC
Thermocouple wire colors
As per IEC 60584 As per ASTM E230
• Type J: black (+), white (-)
Type K: green (+), white (-)
• Type J: white (+), red (-)
• Type K: yellow (+), red (-)
Page 19
Omnigrad M TR13, TC13
19
Head mounted transmitter TMT18x (single input)
Head mounted transmitter TMT8x (dual input)
-
+
6
4
1
2
Power supply head transmitter and analog output 4...20 mA or bus connection
A0012698-EN
-
+
+
1
-
2
7
6
5
4
3
1
2
7
6
5
4
3
Sensor input 2
Sensor input 1
Bus connection
and supply voltage
Display connection
TC
TC
A0012699-EN
Terminal block mounted
1 x TC
2 x TC
-
+
-
+
+
-
A0012700
Page 20
Omnigrad M TR13, TC13
20
Installation conditions
Orientation
No restrictions.
Installation instructions
L
A
L
B
C
D
A0010447
7 Installation examples
A-B In pipes with a small cross section the thermowell tip should reach or extend slightly past the center line of
the pipe (=L).
C-D Angled installation.
The immersion length of the thermometer influences the accuracy. If the immersion length is too small then errors in the measurement are caused by heat conduction via the process connection and the container wall. If installing into a pipe then the immersion length should be at least half of the pipe diameter. A further solution could be an angled (tilted) installation (see C and D). When determining the immersion length all thermometer parameters and the process to be measured must be taken into account (e.g. flow velocity, process pressure).
Installation possibilities: Pipes, tanks or other plant components
• Recommended minimum immersion length: 80 to 100 mm (3.15 to 3.94 in) The immersion length should correspond to at least 8 times of the thermowell diameter. Example: Thermowell diameter 12 mm (0.47 in) x 8 = 96 mm (3.8 in). A standard immersion length of 120 mm (4.72 in) is recommended.
• ATEX certification: Always take note of the installation regulations!
Page 21
Omnigrad M TR13, TC13
21
Extension neck length
The extension neck is the part between the process connection and the terminal head. As illustrated in the following diagram, the extension neck length influences the temperature in the terminal head. This temperature must remain within the limit values defined in the "Operating conditions" section.
10
20
30
∆T in K
0
100 125 150 175 20075
mm
400 °C (752 °F)
220 °C (428 °F)
225 250
570 °C (1060 °F)
3 4 5 6 7 8 9 10 in
5
15
25
Extension neck length
Terminal head heating
Process temperature
A0019295-EN
8 Heating of the terminal head consequent to the process temperature. Temperature in terminal head =
ambient temperature 20 °C (68 °F) + ΔT
Page 22
Omnigrad M TR13, TC13
22
Certificates and approvals
CE Mark
The device meets the legal requirements of the EC directives if applicable. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark.
Hazardous area approvals
For further details on the available Ex versions (ATEX, CSA, FM etc.), please contact your nearest Endress+Hauser sales organization. All relevant data for hazardous areas can be found in separate Ex documentation.
Other standards and guidelines
EN 60079: ATEX certification for hazardous areas
• IEC 60529: Degree of protection of housing (IP code)
• IEC 61010-1: Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures.
• IEC 60751: Industrial platinum resistance thermometers
• IEC 60584 and ASTM E230/ANSI MC96.1: Thermocouples
• DIN 43772: Thermowells
• DIN EN 50446: Terminal heads
• IEC 61326-1: Electromagnetic compatibility (EMC requirements)
PED approval
The thermometer complies with paragraph 3.3 of the Pressure Equipment Directive 97/23/CE and is not marked separately.
Material certification
The material certificate 3.1 (according to EN 10204) can be requested separately. The "short form" certificate includes a simplified declaration with no enclosures of documents related to the materials used in the construction of the single sensor and guarantees the traceability of the materials through the identification number of the thermometer. The data related to the origin of the materials can subsequently be requested if necessary.
Test on thermowell
Thermowell pressure tests are carried out in accordance with the specifications in DIN 43772. With regard to thermowells with tapered or reduced tips that do not comply with this standard, these are tested using the pressure of corresponding straight thermowells. Sensors for use in hazardous areas are also always subjected to a comparative pressure during the tests. Tests according to other specifications can be carried out on request. The liquid penetration test verifies that there are no cracks in the welded seams of the thermowell.
Test report and calibration
The "Factory calibration" is carried out according to an internal procedure in a laboratory of Endress +Hauser accredited by the European Accreditation Organization (EA) according to ISO/IEC 17025. A calibration which is performed according to EA guidelines (SIT/Accredia or DKD/DAkks calibration) may be requested separately. The calibration is performed on the replaceable insert of the thermometer. In the case of thermometers without a replaceable insert, the entire thermometer ­from the process connection to the tip of the thermometer - is calibrated.
Ordering information
Detailed ordering information is available from the following sources:
In the Product Configurator on the Endress+Hauser website: www.endress.com → Select country → Instruments → Select device → Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration
Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Page 23
Omnigrad M TR13, TC13
23
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Communication-specific accessories
Configuration kit TXU10 Configuration kit for PC-programmable transmitter with setup software and
interface cable for PC with USB port Order code: TXU10-xx
Commubox FXA195 HART
For intrinsically safe HART communication with FieldCare via the USB interface.
For details, see "Technical Information" TI00404F
Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.
For details, see "Technical Information" TI00405C
HART Loop Converter HMX50
Is used to evaluate and convert dynamic HART process variables to analog current signals or limit values.
For details, see "Technical Information" TI00429F and Operating Instructions BA00371F
Wireless HART adapter SWA70
Is used for the wireless connection of field devices. The WirelessHART adapter can be easily integrated into field devices and existing infrastructures, offers data protection and transmission safety and can be operated in parallel with other wireless networks with minimum cabling complexity.
For details, see Operating Instructions BA061S
Fieldgate FXA320 Gateway for the remote monitoring of connected 4-20 mA measuring devices via a
Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions BA00053S
Fieldgate FXA520 Gateway for the remote diagnostics and remote configuration of connected HART
measuring devices via a Web browser.
For details, see "Technical Information" TI00025S and Operating Instructions BA00051S
Field Xpert SFX100 Compact, flexible and robust industry handheld terminal for remote configuration
and for obtaining measured values via the HART current output (4-20 mA).
For details, see Operating Instructions BA00060S
Service-specific accessories
Accessories Description
Applicator Software for selecting and sizing Endress+Hauser measuring devices:
• Calculation of all the necessary data for identifying the optimum measuring device: e.g. pressure loss, accuracy or process connections.
• Graphic illustration of the calculation results
Administration, documentation and access to all project-related data and parameters over the entire life cycle of a project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• On CD-ROM for local PC installation.
Page 24
Omnigrad M TR13, TC13
24
Konfigurator
+temperature
Software for selecting and configuring the product depending on the measuring task, supported by graphics. Includes a comprehensive knowledge database and calculation tools:
For temperature competence
• Quick and easy design and sizing of temperature measuring points
• Ideal measuring point design and sizing to suit the processes and needs of a wide range of industries
The Konfigurator is available: On request from your Endress+Hauser sales office on a CD-ROM for local PC installation.
W@M Life cycle management for your plant
W@M supports you with a wide range of software applications over the entire process: from planning and procurement, to the installation, commissioning and operation of the measuring devices. All the relevant device information, such as the device status, spare parts and device-specific documentation, is available for every device over the entire life cycle. The application already contains the data of your Endress+Hauser device. Endress +Hauser also takes care of maintaining and updating the data records.
W@M is available:
Via the Internet: www.endress.com/lifecyclemanagement
• On CD-ROM for local PC installation.
FieldCare FDT-based plant asset management tool from Endress+Hauser.
It can configure all smart field units in your system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
For details, see Operating Instructions BA00027S and BA00059S
System components
Accessories Description
Field display unit RIA16 The display unit records the analog measuring signal from the head transmitter
and shows this on the display. The LC display shows the current measured value in digital form and as a bar graph indicating a limit value violation. The display unit is looped into the 4 to 20 mA circuit and gets the required energy from there.
For details, see the "Technical Information" document TI00144R/09/en
RN221N Active barrier with power supply for safe separation of 4-20 mA standard signal
circuits. Offers bidirectional HART transmission.
For details, see "Technical Information" TI00073R and Operating Instructions BA00202R
RNS221 Supply unit for powering two 2-wire measuring devices solely in the non-Ex area.
Bidirectional communication is possible via the HART communication jacks.
For details, see "Technical Information" TI00081R and Brief Operating Instructions KA00110R
Page 25
Omnigrad M TR13, TC13
25
Documentation
Technical Information
iTEMP® Temperature head transmitter – TMT180, PC-programmable, single-channel, Pt100 (TI088R/09/en) – PCP TMT181, PC-programmable, single-channel, RTD, TC, Ω, mV (TI00070R/09/en) – HART® TMT182, single-channel, RTD, TC, Ω, mV (TI078R/09/en) – HART® TMT82, two-channel, RTD, TC, Ω, mV (TI01010T/09/en) – PROFIBUS® PA TMT84, two-channel, RTD, TC, Ω, mV (TI00138R/09/en) – FOUNDATION FieldbusTM TMT85, two-channel, RTD, TC, Ω, mV (TI00134R/09/en)
• Inserts: – Resistance thermometer insert Omniset TPR100 (TI268t/02/en) – Thermocouple insert Omniset TPC100 (TI278t/02/en) – iTHERM® TS111 Insert for installation in thermometers (TI01014T/09/en)
• Thermowell and thermowell oversheats: – Thermowell for temperature sensors Omnigrad M TW13 (TI00264T/02/en) – Thermowell oversheats Omnigrad TA730 (TI233t/02/en)
• Application example: – RN221N Active barrier, for supplying loop-powered transmitters (TI073R/09/en) – RIA16 Field display unit, loop-powered (TI00144R/09/en)
Supplementary ATEX documentation:
• RTD/TC Thermometer Omnigrad TRxx, TCxx, TxCxxx, ATEX II 1GD or II 1/2GD Ex ia IIC T6 to T1 (XA00072R/09/a3)
• Omnigrad TRxx, Omniset TPR100, TET10x, TPC100, TEC10x ATEX II 3GD EEx nA (XA00044r/09/a3)
• Inserts Omniset TPR100, TPC100, ATEX/IECEx Ex ia (XA00100T/09/a3)
Page 26