EMERSON LPS61, LPS62, LPS63, LPS64, LPS65 Service Manual

...
Page 1
Rev. 05.27.08
LPS60 Series
1 of 3
Embedded Power for Business-Critical Continuity
LPS60 Series
60 Watts
Special Features
• 3" x 5" footprint
•Remote sense
• Built in EMI filter
• Low output ripple
• Adjustable output voltage
• Overload protection
• 110 KHz switching frequency
• LPX60 enclosure kit available
Total Power: 60 - 80 Watts Input Voltage: 85 - 264 Vac
120 - 300Vdc
# of Outputs: Single
Electrical Specifications
Safety
Input
Input ra nge: 85 - 264 Vac (wide range)
120 - 300 Vdc
Frequency: 47-440 Hz
Inrush current: <18A peak @ 115 Vac, <36 A peak @230 Vac,
cold start @ 25 °C
Input current: 1.5 A max. (RMS) @ 115 Vac
Efficiency: 70% typical at full load
EMI filter: FCC Class B conducted; CISPR22 Class B conducted; EN55022
Class B conducted; VDE0878PT3 Class B conducted
Safety ground leakage current:
<0.5 mA @ 50/60 Hz; 264 Vac input
Output
Maximum power: 60 W for convection; 80 W with 30 CFM forced air Adjustment range -5, +10% minimum
Hold-up time 20 ms @ 60 W load, 115 Vac nominal line
Overload protection Short circuit protection on all outputs.
Case overload protected @ 110-145% above peak rating
Overvoltage protection 5 V output; 5.7 - 6.7 Vdc. Other outputs 10% to 25%
above nominal output
Remote sense Compensates for 0.5 V lead drop min. Will operate without
remote sense connected. Reverse connection protected.
VDE 0805/EN60950 (IEC950)
11774-3336-1255 (LC #86665)
UL UL1950
E132002
CSA CSA 22.2-234 Level 3
LR53982C
NEMKO EN 60950/EMKO-TUE
P95100123 (74-sec) 203
CB Certificate and report
1521, 1522, 1523, 1524
CE Mark (LVD)
Page 2
Mechanical Drawing
Rev. 05.27.08
LPS60 Series
2 of 3
Operating temperature:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C, -20 °C startup
Storage temperature: -40°C to +85 °C Electromagnetic susceptibility:
designed to meet IEC801, -2, -3, -4, -5, -6, Level 3
Humidity: Operating; non-condensing 5% to 95% RH
Vibration:
Three orthogonal axes, sweep at 1 cot/min, 5 min. dwell at four major resonances 0.75 G peak 5 Hz to 500 Hz, operational
Temperature coefficient ±0.04% per °C
MTBF demonstrated
>550,000 hours at full load and 25 °C ambient conditions
Environmental Specifications
0.22" (5.6)
GND
M1
3.00"
(76.2)
2.55"
(64.8)
SK 1
1
N
3
L
SK201
Output
Power
(Watts)
M2
+
_
SK 2
1 2 3 4 5 6
80W
60W
40W
20W
0W
0°C
10°C 20°C 30°C 40°C 50°C 60°C 70°C
Remote Sense
Connector
Voltage Adj. Pot
Power Derating Curve
30 CFM Forced Air Cooling
Natural
Convection
Cooling
TA – Ambient Temperature – °C
40W
30W
0.22" (5.6)
1.69"
(42.9)
0.12" (3)
4.56"
(115.8)
0.15" (4)
DIA (4 places)
5.00" (127)
Page 3
Rev. 05.27.08
LPS60 Series
3 of 3
Embedded Power for Business-Critical Continuity
Ordering Information
Model
Number
Output
Voltage
Minimum
Load
Maximum Load
with Convection
Cooling
Maximum Load
with 30CFM
forced Air
Peak
Load
1
Regulation
2
Ripple
P/P (PARD)
3
LPS61 3.3 V 2 A 12 A 16 A 18 A ±2% 33 mV
LPS62 5 V 0 A 12 A 16 A 18 A ±2% 50 mV
LPS63 12 V 0 A 5 A 6.7 A 7.5 A ±2% 120 mV
LPS64 15 V 0 A 4 A 5.3 A 6 A ±2% 150 mV
LPS65 24 V 0 A 2.5 A 3.3 A 3.8 A ±2% 240 mV
LPS68 48 V 0 A 1.3 A 1.7 A 1.9 A ±2% 480 mV
1. Peak current lasting <30 seconds with a maximum 10% duty cycle.
2 . At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3 . Peak-to-peak with 20 MHz bandwidth and 10 μF (tantalum capacitor) in parallel with a 0.1 μF capacitor at rated
line voltage and load ranges.
Pin Assignments
Connector LPS61 LPS62 LPS63 LPS64 LPS65 LPS68
SK1-1 Neutral Neutral Neutral Neutral Neutral Neutral SK1-3 Line Line Line Line Line Line
SK2-1 3.3 V 5 V +12 V +15 V +24 V 48 V SK2- 2 3.3 V 5 V +12 V +15 V +24 V 48 V SK2- 3 3.3 V 5 V +12 V +15 V +24 V 48 V SK2-4 Common Common Common Common Com mon Common SK2-5 Common Common Common Common Com mon Common SK2-6 Common Common Common Common Com mon Common SK201-1 +Sense +Sense +Sense +Sense +Sense +Sense SK201-2 -Sense -Sense -Sense -Sense -Sense -Sense
Mating Connectors
AC Input:
Molex 09-50-8031 (USA) Not required for (-T) option 09-91-0300 (UK) PINS: 08-58-0111
DC Outputs:
Molex 09-50-8061 (USA) Not required for (-T) option 09-91-0600 (UK) PINS: 08-58-0113
Remote Sense:
Molex 22-01-2025 PINS: 08-52-0113
Astec Connector Kit #70-841-006, includes all of the above
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±0.02" (±0.5mm)
3. Mounting holes M1 and M2 should be grounded for EMI purposes.
4. Mounting hole M1 is safety ground connection.
5. Specifications are for convection rating at factory settings at 115 Vac input, 25°C unless otherwise stated.
6. Warranty: 2 year
7. Weight: 0.75lbs/0.34kg
Americas
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 (760) 930 4600 Facsimile: +1 (760) 930 0698
Europe (UK)
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
www.powerconversion.com
techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.
EmersonNetworkPower. com
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls Precision Cooling Racks & Integrated Cabinets
Services
Surge Protection
Emerson Network Power.
The global leader in enabling business-critical continuity.
AC Power
Connectivity
DC Power