This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the
unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death.
Disconnect all local and remote electric power supplies and wear protective equipment per
NFPA 70E before working within electric control enclosure. Failure to comply can cause
serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off
mode. Some internal components require and receive power even during the Unit Off mode of
Liebert iCOM control.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
WARNING
Risk of unit falling over. Can cause property damage, injury or death.
The XDP is top-heavy. Use extreme caution and care when moving and installing this unit.
CAUTION
Risk of piping and component rupture. Can cause injury or equipment damage.
System is pressurized. Relieve pressure through access valve before working on unit.Closing
service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do
not close valves without following recommended procedures for repair, maintenance and
replacement of components. Install pressure relief valves in field piping that may become
isolated by service valves. System is pressurized. Relieve pressure through access valve
before working on unit
NOTE
This document is intended to be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Before any action that could cause a disturbance in the XD system’s cooling function is begun,
the facility manager MUST be informed. In addition, after the action is taken and the work is
finished, the facility manager MUST be informed.
NOTICE
Risk of leaking chilled water lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe
property damage and loss of critical data center equipment. Do not locate unit directly above
any equipment that could sustain water damage. Emerson Network Power recommends
installing monitored leak detection equipment for the unit and supply and return lines.
1
Page 8
Figure 1Model number nomenclature
R
Pump
Redundancy
XDP160–*
Pumping
unit
Revision
level
Liebert
X-treme heat
Density system
160kW
nominal
capacity
Place holder
Example: XDP160RA– –4
A
A = 460V-3ph-60Hz
(voltage-phase-frequency)
C = 208V-3ph-60Hz
M = 380/415-3ph-50Hz
–
Place holder
2
Page 9
1.0PRODUCT DESCRIPTION
Liebert XDP Unit
Control Valve
Liebert XD Cooling Modules
Heat Exchanger
Receiver
Pumps
Chilled Water
1.1General Product Information
1.1.1Product/System Description
Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system
and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant
to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP is rated
for 160kW (546,000BTU/H) of cooling.
The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control
valve, receiver, controls, valves and piping.
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the
refrigerant being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are
automatic.
Figure 2Liebert XDP components
Product Description
1.1.2Minimum Load
1.2Equipment Inspection
The Liebert XDP's minimum recommended operating load is 30% of system nominal capacity. The
Liebert XDP160 is rated for 160kW (546,000BTU/H) of cooling, therefore the system's minimum
recommended load is 48kW (163,800BTU/H). Loading below this value can unfavorably affect system
operation. Consult the factory for any loading below this recommendation.
To achieve the minimum recommended load, the capacity of all connected modules must total at least
48kW (163,800BTU/H). See
Table 1Number of Liebert XD cooling modules required to achieve at least 48kW
(163,800
BTU/H) load
Number of Liebert XD
cooling modules required
to achieve at least 48kW
(163,800BTU/H) load
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be
immediately reported to the carrier and a damage claim filed with a copy sent to Emerson and to your
sales representative.
Table 1.
Liebert XD Module Type
XDCF10XDV8XDV10XDO16XDO20XDH20XDH32XDR20
56533323
3
Page 10
1.3Equipment Handling
!
!
WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this
unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified
rating organization. See Table 15 for unit weights. Unit weights are specified in section 9.0
Personnel should be properly trained and certified to move and rig equipment
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
1.3.1Handling the Liebert XDP While it is on Skid and Packaged
• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In
either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6"
(152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care
must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift
point of the unit.
Product Description
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard
doorway. Any attempt to move the unit, while skidded, through a standard doorway will
cause damage to the unit and to the building.
NOTICE
Risk of damage from forklift. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to
prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures
and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that
the straps are not tightened to a point of damaging panels.
1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and
side packaging planks.
2. Remove and set aside filter dryer kit.
3. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The
bag may remain in place for dust and panel protection or removed for immediate unit installation.
4. Remove the bag from the unit when ready to remove the skid for installation.
Figure 3Unpacking the Liebert XDP
Product Description
1.3.3Removing the Unit from the Skid Using a Forklift
1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be
equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without
damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
5
Page 12
Figure 4Use a forklift to remove the Liebert XDP from the skid
Fit the forklift tines under the Liebert XDP.
Move the forklift forward
until the tines are fully
under the unit.
The forklift tines
must be equally
spaced on either
side of the center of
gravity indicator.
1.3.4Removing the Unit from the Skid using Rigging
1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally
spaced on either side of the center of gravity indicator. Refer to
2. Place slings under the unit using spaces provided between the skid deck boards.
Product Description
Figure 5.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer
packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two
horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the
unit.
7. Remove the skid from under the unit.
6
Page 13
Figure 5Removing the unit from the skid using rigging
Equally
Spaced
Equally
Spaced
Center of
Gravity
Symbols
Spreader
Bars
Lag
Bolts
Bracket
If rigging will be used
to transport the
Liebert XDP, place one
or two horizontal
straps around the unit
and the vertical staps
about this height.
Cushioning material
not shown for clarity.
Product Description
1.3.5Moving the Liebert XDP Using Piano Jacks
1. Elevate the Liebert XDP with a lifting mechanism, such as a forklift or rigging.
2. Position one piano jack at each end of the Liebert XDP.
3. Lower the unit to a height suitable for placing it on the piano jacks.
4. Put protective material between the Liebert XDP and the piano jacks and straps.
5. Secure the Liebert XDP to the piano jacks.
6. Release the the Liebert XDP from the straps securing it to the lifting mechanism and move the
mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
7
Page 14
Figure 6Securing the Liebert XDP to piano jacks
Using a forklift to put a
Liebert XDP on piano jacks
Using rigging to put a
Liebert XDP on piano jacks
Liebert XDP Secured
to piano jacks
Product Description
1.3.6Removing the Unit from the Piano Jacks
1. Lower the Liebert XDP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert XDP off one piano jack with a pry bar or similar device, taking care not
to damage the unit’s cabinet.
4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert XDP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
8
Page 15
2.0INSTALLATION
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN001598
Pg. 2, Rev. 7
D
Unit Base
E
Unit Base
F
Height
of Unit
11"
(279mm)
5"
(127mm)
1" (25mm)
2-3/8"
(60mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.
2.1Mechanical Considerations
2.1.1Positioning the Liebert XDP
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at
least 3
For additional technical information, refer to the System Design and Configuration Document for the
Liebert XD
www.liebert.com, as well as from your local Emerson representative.
Figure 7Dimensions
feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
™
System, SL-16655. The document is available in electronic format at Liebert’s Web site,
To first cooling module
or bypass flow controller **
Installation
Close this
valve during
normal
operation
A - Return from Liebert XD
Cooling Modules
17-1/4"
(438mm)
10" (254mm)
19"
(483mm)
16-1/8"
(409.6mm)
Install replaceable filter dryer assembly
in liquid supply line B.
* Orientation
determined
by installer.
B - Supply to Liebert XD Cooling Modules
Emerson recommends field-installation
of shutoff valves at these points to permit
isolating the Liebert XDP for maintenance
Dimensions are
approximate
and subject to change
without notice.
* Allow 8" (204mm) clearance for filter replacement.
** To ensure ensure all refrigerant flow is filtered,
install the filter dryer assembly between the discharge
line of the Liebert XDP and the first bypass flow controlle
or the first Liebert XD cooling module.
D - Chilled Water Return
To Chilled Water Source
Table 3Unit piping outlet connection sizes, inches, OD Cu
ModelPipe Connection Point
50/60 HzABCD
XDP1602-1/8 1-1/8 2-5/8 2-5/8
2.2Electrical Considerations
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated
on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring
regulations.
Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 11
and make sure that the phases are correctly connected.
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit.
C - Chilled Water Supply
From Chilled Water Source
10
DPN001598
Pg. 3, Rev. 7
Page 17
!
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment
damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp
edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.
2.2.1Connecting High-Voltage Cables
1. Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 9). Open the front doors
and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 9Front view of Liebert XDP and electrical enclosure
Enclosure Cover Latch
Hazardous Volatge
Enclosure Cover
Installation
2. Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 10).
11
Page 18
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
XDP Input Power
Knockout
Enclosure Cover
Not Shown for Clarity
Customer
Power
Connection
Ground
Lug
Fused
Disconnect
Fuse
Blocks
Fuse
Block
Power Block
Pump
Contactors
Transformer 2
(Supplied on 460V
Units Only)
Transformer 6
Transformer 1
Installation
Figure 11 High voltage connections—60Hz
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see
Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper
phasing.
4. Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of
the enclosure.
12
Page 19
Figure 12 High voltage connections—50Hz
Busbar
Customer Power
Connection
Pump Circuit
Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Transformer 6
Fuse Blocks
Liebert XD Module Condensate
Connections (optional; depends
on features supplied with
Liebert XD Module)
User Interface Wiring
Temperature/Humidity
Sensor Wiring
Alternate Knockout
for Temperature/Humidity
Sensor Wiring
Enclosure Cover Not Shown for Clarity
2.2.2Extra Low Voltage (ELV) Connections
Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this
equipment (refer to
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 13).
Installation
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage
13
Page 20
Figure 14 Connecting the remote temperature/humidity sensors
P66
Cooling Module
P3P1
See Note 8
Liebert XD
P66 P67
See
Note 4
CAN
Cable
See Note 4
P66P64
P67
CAN Ground
Coupler
Termination
Plug
See Note 8
P2P4
CAN Iso
Adapter
P67
CAN Ground
Coupler
See Note 5
P66
P66
Cooling Module
See Note 5
P67
Liebert XD
Installation
P67
Unit Display
(Rear View)
See
Note 9
Red Crossover
Ethernet Cable
T1 Unit Control
Crossover Coupler
See Note 6
See Note 3
E5
P67
Not
Used
P63
P64
P61
Liebert IntelliSlot 1
P1
P2
Liebert IntelliSlot
Power Supply
Liebert IntelliSlot 2
Ribbon
Cables
P65
P3
Cable A
77
See
Note 2
Cable B
78
P65
P18
Liebert iCOM Microprocessor
and I/O Board
P40
P8
P32
1. See unit electrical schematic, installation and user manuals.
2. Cables “A” and “B” provided with each unit. Only one is used as follows:
Liebert IntelliSlot-based communications - Cable “A” is preconnected to P65
on microprocessor and input/output board and P65 on Liebert IntelliSlot
power supply non-Liebert IntelliSlot-based communications - Vable “B” is
pre-connected to Terminals 77 and 78 but must be exchanged with Cable “A”
at P65 on the microprocessor and input/output board.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect ground coupling on end of cable connected
to Sensor “A” or Sensor “B.”
302211
Rev. 2
Remote T/H Sensor BRemote T/H Sensor A
See Note 7
T6 Isolation
Transformer
24VAC Nominal
Transformer
P41
P13
P11
P7
P12
1
2
3
P66
P78
OFF ON
SW
2
21436
5
P68
P43
P4
E4
E3
E2
E1
TB1
P54
P51
E1
P24
Control
Fuse
Board
P45
P4
See Table for
Plug Assignments
P34
P33
P35
P36
P22 P38 P39 P53 P52
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug
the red cable from P64 on the microprocessor and input/output board
and connect to one side of the crossover coupler. The first customer
connection point is to P64 on the microprocessor and input/output board.
The second customer connection point is to the other side of the crossover
coupler. This connects the microprocessor and input/output board and
display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the
Liebert XD cooling module and which connects to P2 on CAN Iso.
8. Field-install cables with factory-installed ferrite beads (when provided,
typical two places). Each cable must make three passes through the ferrite
bead. Locate the ferrite bead on top of the electric box. See instruction
sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). Cable passes through
ferrite bead three times
14
Page 21
2.2.3DIP Switch and Jumper Settings for Remote Sensors
P68
135
246
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A”REMOTE T/H SENSOR “B”
SW1SW1
OFF
ON
OFF
ON
Jumper
on 1-2
1
2
3
P78
DIP
Switches
ON
1
3
4
9
10
OFF
2
5
6
7
8
Jumpers
on 1-2, 5-6
OFF ON
1
2
3
4
5
6
7
8
9
10
DIP
Switches
ON
None
OFF
1
2
3
4
5
6
7
8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
DIP
Switches
ON
1
5
OFF
2
3
4
6
7
8
DIP
Switches
ON
2
5
OFF
1
3
4
6
7
8
SW3
1
2
3
4
5
6
7
8
OFF ON
P3
321
Jumper
on 2-3
P3
321
Jumper
on 2-3
302211
Rev. 2
302211
Rev. 2
Te rm i n at i on
Plug
Liebert iCOM
Microprocessor
& I/O Board
Customer
Connection
Points
Crossover
Coupler
Red Crossover
Ethernet Cable
Straight Through
Ethernet Cables
U2U Networking Switch
(Field Supplied)
Unit Display (Rear View)
Not
Used
P64
P66
P64
P66P67
To / From Other
Networked Units
CAN Cable
See Note 1
P65
E5
P61
P63
P11 P13
P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U)
networking. Unplug the red cable from P64 on the
microprocessor and I/O board and connect to one side
of the crossover coupler. The first customer connection
point is to P64 on the microprocessor and I/O board.
The second customer connection point is to the other
side of the crossover coupler. This connects the
microprocessor and I/O board and display to the
private U2U network.
The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See
Figure 15.
Figure 15 DIP switch and jumper settings
Installation
Figure 16 Unit-to-unit networking connections
15
Page 22
2.3Field Connections—Optional for All Units
1
1
2
P67
P64 P66 P67
To Remote T/H Sensor A
Termination Plug
To P66 on Liebert iCOM
Control Board
To P64 on Liebert iCOM
Control Board
Red Ethernet Cable
To Liebert XD Cooling
Module(s) and Remote
T/H Sensor B
To Optional
External
Connections
UNIT DISPLAY (Rear View)
Factory-Wired
Temperature Sensor
Control wiring must be Class 2 and installed in
accordance with the National Electrical Code (NEC).
Requires shielded cable.
NOTES:
DPN001598
Pg. 6, Rev. 7
Do Not
Use
• Connect field wiring from the optional Liebert XD cooling module condensation detection circuit
to terminal strip locations COMM. (24) and H2O (51).
• Connect optional field wiring from remote devices to remote alarm device, common alarm outputs,
site monitor and remote shutdown, if applicable. See terminal strip descriptions in
Figure 17 Liebert XDP extra low voltage field connections points
Installation
Figure 17.
16
Page 23
2.4Remote Sensor Installation—Proper Placement
Placement of the two remote temperature/humidity sensors is critical to effective cooling of the
conditioned space.
The remote sensors must be installed in areas where conditions are representative of the space
conditioned by the Liebert XDP. Emerson recommends installing the sensors in different areas near
the cooling modules served by the Liebert XDP. If the return air side of the primary air mover, such
as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one
sensor could be placed there. Emerson suggests placing the other sensor on the wall opposite the heat
load area (see
Do not install the sensors where ambient air might cause false readings, for example, near unsealed
doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable;
each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM input/output board inside
the Liebert XDP. Secure the ring terminal on the cable shield to the electric box adjacent to P67
(see
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the
ring terminal on the cable shield to the grounding screw adjacent to P67.
Figure 18 for guidance).
Figure 14).
Installation
Figure 18 Suggested remote sensor placement
17
Page 24
3.0PIPING
3.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection
systems in the European Community market and operating with fluorinated greenhouse gases (fgas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (Fgas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the
atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not
entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to
recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.
3.2Connection Sizes
The copper pipe connections on the Liebert XDP are:
Building Chilled Water Supply2-5/8" OD
Building Chilled Water Return2-5/8" OD
Refrigerant Supply1-1/8" OD
Refrigerant Return2-1/8" OD
Piping
3.2.1Recommended Pipe Size
Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to
site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions must be minimized to get good fluid flow.
Table 4Supply, return pipe sizes for refrigerant loop
Pipe FunctionSize / Equivalent Pipe Length
Liebert XDP supply line, from Liebert XDP supply
to farthest Liebert XD cooling module
Liebert XDP return line, from farthest Liebert XD cooling
module to Liebert XDP return
From any model Liebert XDO/Liebert XDH supply
to supply line of Liebert XDP
From any model Liebert XDO/Liebert XDH return
to return line of Liebert XDP
From any model Liebert XDV/Liebert XDCF supply
to supply line of Liebert XDP
From any model Liebert XDV/Liebert XDCF return
to return line of Liebert XDP
1-1/8" OD for lengths up to 60 feet
1-3/8" OD for lengths over 60 but less than 175 feet
2-1/8" OD for lengths up to 60 feet
2-5/8" OD for lengths over 60 but less than 175 feet
1/2" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 25 feet
7/8" OD for lengths up to 10 feet
1-1/8" OD for lengths over 10 but less than 25 feet
1/2" OD for lengths up to 10 feet
5/8" OD for lengths over 10 but less than 35 feet
5/8" OD for lengths up to 10 feet
7/8" OD for lengths over 10 but less than 35 feet
18
Page 25
3.3Liebert XDP Interconnection with Liebert XD Cooling Modules
Liebert XD
Cooling
Module
Liebert XD
Cooling
Module
Liebert XD
Cooling
Module
Liebert XD
Cooling
Module
Liebert X D
Cooling
Module
Liebert XDP
SLOPE—The main supply and return lines to and
from the Liebert XDP must be sloped downward
toward the Liebert XDP at a rate of 1-2" per 20 feet
(25.4-51mm per 6m) of pipe run.
All supply and return
mains must be level
with or above the
top of all Liebert XD
modules
All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe.
The Liebert XDP may be connected to Liebert XD cooling modules with either Liebert’s XD
prefabricated piping assembly or with rigid, off-the-shelf piping. In either setup, piping for the Liebert
XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling
modules are connected in parallel between main return and supply pipes going to and from the
Liebert XDP/Liebert XDC.
Liebert’s XD System Design Manual, SL-16655, available at Liebert’s Web site: www.liebert.com. The
guidelines provided for pipe size must be strictly followed. Failure to size the main lines
and connection lines adequately may result in reduced cooling capacity. The critical aspects
of pipe sizing are related to refrigerant volume and pressure drop. Each must be minimized.
Figure 19 Liebert XD system diagram
Figure 19 represents a typical configuration. For piping details, refer to
Piping
3.4Piping Installation Methods
The assembly and connection means used for piping in the Liebert XD system are similar to those
used for conventional refrigeration systems. All piping should be installed with high-temperature
brazed joints. Soft soldering is not recommended.
During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and
scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping
supports, leak testing, dehydration and charging. Failure to use good system practices may result in
damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice
refrigeration piping.
Insulate all piping lines to prevent condensation in applications where the dew point approaches the
R-134a refrigerant temperature.
Emerson recommends venting the pressure relief valve for the R-134a outside the conditioned space
where it is open to the atmosphere. The R-134a side relief valve is inside the Liebert XDP unit at the
top of the receiver.
3.4.1Piping Installation—R-134a Pumped Circuit
Emerson recommends venting the relief pressure valve of the Liebert XDP (located at the top of the
receiver) outside of the conditioned space where it is open to the atmosphere.
19
Page 26
3.4.2Piping Mains
7/8
"
(22mm) ID
4"(102mm)
All refrigeration piping mains connected to the Liebert XD cooling module, both supply and return,
should be installed with a downward pitch toward the Liebert XDP of 1-2" for every 20 feet
(25.4-51mm per 6m) of pipe run.
Install a 20-40 mesh strainer on the chilled water supply to the Liebert XDP. The strainer is required
to prevent particles in the chilled water from entering the Liebert XDP’s heat exchanger. The
maximum distance from the strainer to the Liebert XDP is 10 feet (3m).
NOTICE
Risk of particles in chilled water. Can cause equipment damage and reduced cooling.
Failure to install a strainer in the supply line to the Liebert XDP can result in damage to the
unit’s heat exchanger.
3.4.3Bypass Flow Controller
Three bypass flow controllers are required to ensure that the Liebert XDP pumps operate within the
optimum range. These devices are added to the field piping and simulate the flow of additional cooling
modules.
Each bypass flow controller must be installed with one shutoff valve to allow the controller to be
disabled when cooling modules are added to a Liebert XD system.
Bypass flow controllers should be connected between the main supply and the main return lines of the
field piping. The connection points to the main supply and return lines should be in a convenient and
accessible location between the Liebert XDP/Liebert XDC and the first Liebert XD module in the
circuit. See
Figures 20 and 21 for piping details of the bypass flow controller.
Piping
Refer to Table 5 to determine the number of bypass flow controllers that must be open to provide
proper refrigerant flow based on the total nominal cooling capacity of the cooling modules in each
Liebert XD system.
Table 5Bypass flow controllers for a Liebert XDP-based system
7/8" R efri gerant Grade
Full Port Ball Valve
Field-Supplied and Field-Installed
Supply
Main
Bypass Flow Controll er
(Field-Installed)
Flow Direction
Filter D ryer
Assembly
Liebert XD
Cooling
Module #1
Liebert XD
Cooling
Module #2
Coolant
Supply
Coolant
Return
Liebert
XDP
Bypass Flow
Controllers
Figure 22 Bypass flow controller piping
Piping
3.5Piping Details—Shutoff/Isolation Valves
Isolation valves must be installed on the Liebert XDP’s refrigerant circuit to permit maintenance on
the unit (see
Figure 23).
21
Page 28
Figure 23 General piping details
Liebert
XDP A
Liebert
XDP B
Return
Supply
Return
Supply
Floor
Building Chilled Water Supply
Building Chilled Water Return
Isolation
valves
Isolation
valves
Emerson recommends
field-installation of shutoff
valves at these points to
permit isolating the
Liebert XDP for
maintenance.
Piping
3.5.1Evacuation and Leak Check—R-134a Pumped Circuit
1. Open all service valves, including those outside the Liebert XDP.
2. Attach a jumper hose from one of the Schrader valve fittings on a pump outlet before the check
valve to a Schrader valve fittings after the check valve.
3. Place 150psig (1034kPa; 10.34 bars) of dry nitrogen with a tracer of R-134a in the system.
NOTICE
Risk of overpressurization. Can cause equipment damage.
Do not exceed 150 psig (1034 kPa; 10.34 bars) in the R-134a circuit.
4. Check the system for leaks with a suitable leak finder on the pumps’ suctions lines.
5. After completion of the leak testing, release the test pressure (per local code) and connect to
vacuum pump(s) at the Schrader valves.
6. After pulling a deep vacuum for four hours, check the vacuum level and, if it has not changed,
3.5.2Insulation
break the vacuum with dry nitrogen.
7. Pull a second vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.
NOTE
Do not insulate piping before checking it for leaks. Insulating pipes before checking them for
leaks would prevent easy detection of leaks.
Insulate all piping between the Liebert XDP and its connected cooling modules to prevent
condensation where the piping passes through non-conditioned areas.
22
Page 29
3.6Filling the Pumped Circuit—R-134a
Using a refrigerant pump or cylinder heater pads will speed the charging process.
1. Connect a charging manifold to the service port of the receiver outlet valve or to the suction and
discharge side of the pump.
2. Purge the hoses.
3. Calculate the amount of R-134a refrigerant needed to charge the system, using the values in
Tables 6, 7, 8 and 9; for assistance, refer to 3.6.1 - Calculating Refrigerant Charge—
Example. The section includes a worksheet to calculate system refrigerant charge requirements.
4. Weigh in the calculated charge.
5. After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium.
Observe the refrigerant level through the sight glasses of the receiver. The level should be above
the second sight glass at a minimum when the Liebert XDP is off.
6. If the refrigerant level is improper, the charge must be adjusted.
If the level is too high or too low, recalculate the required charge and reduce or increase the
amount as needed to reach the proper level.
NOTE
All lengths in Tables 6, 7 and 8 are actual pipe lengths, not equivalent pipe lengths.
NOTE
System refrigerant volume calculations derived from Tables 6, 7, 8 and 9 are based on a fully
loaded system. Additional charge may be required for lightly loaded systems.
Piping
Table 6System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert
Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert
XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant
required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF,
Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20
Liebert XDV8 cooling modules.
___ 1. Unpack and check received material.
___ 2. Position the Liebert XDP and secure it to the floor.
___ 3. Wire high voltage connections.
___ 4. Wire low voltage connections.
___ 5. Connect the building chilled water piping to the Liebert XDP.44Connect the Liebert XD
cooling module piping to the Liebert XDP with slope.
___ 6. Check the system for leaks.
___ 7. Hold a vacuum on the system.
___ 8. Charge the system with refrigerant.
___ 9. Make sure that all piping has proper insulation.
Piping
25
Page 32
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Liquid Crystal
Display screen
Keypad
LED Status Indicators
(top LED is red or flashing
red; bottom LED is green
or amber)
ESC
?
On/Off Key
Escape KeyDown Arrow Key
Up Arrow Key
Left Arrow KeyRight Arrow KeyEnter Key
Alarm Key
Help Key
LEDs
(see Table 12 for
meanings)
4.0LIEBERTICOM CONTROL—FIRMWARE VERSION XP1.00.010.STD
4.1Liebert iCOM Components and Functions
The Liebert iCOM controller layout is shown in Figure 24; the keyboard functions are defined in
Table 12.
Figure 24 Liebert iCOM display components
26
Page 33
Table 12Keyboard icons and functions
?
ESC
IconKey NameFunction
On/Off KeyControls the operational state of the cooling unit.
Alarm KeySilences an alarm.
Help KeyAccesses integrated Help menus.
ESCape KeyReturns to the previous display view.
Enter KeyConfirms all selections and selects icons or text.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Increase Key
(Up Arrow)
Decrease Key
(Down Arrow)
Left and Right
Arrow Keys
Upper LED
Lower LED
Moves upward in a menu or increases the value of a selected parameter.
Moves downward in a menu or reduces the value of a selected parameter.
Navigates through text and sections of the display.
Blinking Red—Active, unacknowledged alarm exists
Solid Red—Active, acknowledged alarm exists
Amber—Power is available to the unit; unit is NOT operating
Green—Unit is operating with no alarms
4.2Display Lamp Indicators
• The Green lamp will be On only when the Liebert XDP is On and running with no alarms.
• The Red lamp will be On if the unit is On and running with an active alarm, or if the unit is shut
down because of an alarm.
• The Red lamp will flash while an alarm is being annunciated. The Red lamp will stop flashing and
the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
• The Amber lamp will be On if the Liebert XDP has been shut down at the I/O switch or if the unit
has been shut down by an alarm condition.
27
Page 34
Liebert iCOM Control—Firmware Version XP1.00.010.STD
press : for next/prev unit for unit /system view
press : for menu; ESC for prev screen ; ? for help
08/2011
Liebert
XDP
57°F
50.0°F set
CFC: 30%
28.02.2012 15 :03UNIT ON
Sensor A
Room Data
Date and
Time
Pump Operation
represented by animated
refrigerant lines
Next Scheduled
Maintenance
Alarm/Event
History
Navigation
Prompts
Unit
Name
Sensor B
Room Data
Unit Status
Refrigerant
Tem per atu re
Available only
with Liebert XD
Smart Modules
4.3Navigating Through the Liebert iCOM Display
Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The
Liebert iCOM’s home screen is shown in
Figure 25 Liebert iCOM default home screen
Figure 25.
4.3.1Accessing Menus and Settings
Viewing Data
No password is required to view data or settings.
To view data:
1. From the home screen, press the Enter key to view the User Menu (see Figure 29).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view.
4. Once that icon is highlighted, press Enter again to open that menu.
• If a password is required, see 4.3.3 - Entering the Password.
• If a menu has more than one screen, the Liebert iCOM display will have text at the top similar to this: (page 1 of 2).
5. Press Enter to select the first line of data.
6. Use the Up and Down arrow keys to scroll to the desired data point.
7. Press ESC to move back to higher level menus.
28
Page 35
4.3.2Cooling Module Overview
UNIT 1
OFF 9/2013100%
212°F
Max XD Supply
Air Temp
Liebert XDP
AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01AA01
(01) 8/2 /2012 08 :33 R ST General Alarm
(01) 8/2 /2012 08 :20 ACK HIGH CHILLED WATER TEMP
8/4 /2012 14 :13 :54ALARM OFF
? for help
for next/previous unit
for system view
ESC
for previous screen
for menu
°F 70 72 74 76 75 73 74 71 77 72
The Liebert iCOM will display an overview of all connected cooling modules. It does not display a
system view, which would include units other than the cooling modules.
NOTE
The Liebert iCOM control screens display a setting to select a system view, but the Liebert XDP
does not support a system view.
To display an overview of all connected cooling modules:
1. At the default home screen on the Liebert iCOM, press the down arrow. This will display the first
10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.
Figure 26 Cooling module overview, first 10 modules
Liebert iCOM Control—Firmware Version XP1.00.010.STD
2. Press the down arrow button again to display the next 10 modules’ outlet temperature and
capacity levels.
3. Press ESC to return to the default home screen.
29
Page 36
4.3.3Entering the Password
SETPOINTS
to change parameter
to confirm
to select parameter
for next/pr evious unit
then
PASSWORD (Actual Level 0)
Min Room Temperature Setpoint
After highlighting the Password command line, press
Enter again to highlight the first digit. Use the Up and
Down arrow keys to change the first digit. Move to the
next digit in the Password with the right arrow.
Most settings in the Liebert iCOM are protected by a factory-set password, 1490. To enter the
password:
1. From the home screen, press the Enter key to view the User Menu (see Figure 29).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press Enter to highlight the Password line.
6. With the Password line highlighted, press Enter to highlight the first digit in the password
7. Enter the password, 1490.
Use the Up and Down arrow keys to select a numeral for the first digit of the password.
Move to the next digit of the password with the Right arrow key.
Select the numerals for all four digits with the same process.
8. After all four digits of the password have been entered, press the Enter key.
NOTE
Do not press the ESC key or the Liebert iCOM will move to the previous screen and the
password must be re-entered before changes may be made.
Figure 27 Entering the password
Liebert iCOM Control—Firmware Version XP1.00.010.STD
30
Page 37
Liebert iCOM Control—Firmware Version XP1.00.010.STD
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit
then
Language
Date
Time
Temperature Indication
Display Contrast
Buzzer Frequency
Backlite Off after
Screen
Highlight the
setting to be
changed by
pressing Enter.
4.4Changing Liebert iCOM’s Display Settings
No password is required to change the way Liebert iCOM displays data. The Display Setup controls
how the unit shows data, such as temperature, date and time.
To change the display settings:
1. From the home screen, press the Enter key to view the User Menu (see Figure 29).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the Display Setup icon.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press the Enter key to select the first setting.
Either change that setting or navigate to another setting with the Up and Down arrow keys.
6. Once the desired setting is highlighted, press the Enter key to access that parameter’s display
setting options.
7. Use the Up and Down arrow keys to make changes.
8. Press the Enter key to accept the changes.
9. Press the ESC key twice to return to Liebert iCOM’s user menu.
Figure 28 Display setup screen
4.5Changing Operational Settings
Changes to the Liebert XDP’s operation settings in the Set Alarms and Setpoints menus require a
password.
1. From the home screen, press the Enter key to view the User Menu (see Figure 29).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
If a password is required, see 4.3.3 - Entering the Password.
5. After entering the password, use the Up and Down arrow keys to scroll to and highlight the
operational setting to be changed.
6. Press Enter to highlight the values for that setting.
7. Use the Up and Down arrow keys to change the value.
8. Press Enter to accept the change. (The value will no longer be highlighted.)
9. Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)
10. Press ESC again to move to previous screens.
31
Page 38
Liebert iCOM Control—Firmware Version XP1.00.010.STD
°C / °F
% RH
SET
EVENT
LOG
SET
ALARMS
!
ACTIVE
ALARMS
1 2
39
6
SET
1234h
XDIO
4.6Graphical Data Record
The Graphical Data Record charts the average temperature from Sensors A and B and the supply
refrigerant temperature.
The temperature scales can be changed to expand or compress the data.
The time scale also can be altered to any of several selectable values.
NOTE
Changing the time scale eliminates all previous graphical data and the unit will begin
recording new data.
4.7Liebert iCOM User Menu Icons and Legend
Figure 29 Liebert iCOM User Menu icons
Setpoints
View and change
operational
setpoints
Sensor Data
Shows readings
of sensors; View
Only
Spare Parts List
Contains spare
parts available on
site
Active Alarms
Lists all current
alarms; View Only
Event Log
Lists last 400
events and
alarms
View Only
Display Setup
Change settings
for display:
language and
time
Graphic Data Record
Displays average
temperature from
Sensors A and B, the
average dew point from
Sensors A and B, the
supply refrigerant
temperature and the
supply refrigerant control
point graphs; Data is
View Only; Display scale
is adjustable
Total Run Hours
Records the run time of
all components and
allows setting of limits on
run time; View Only
View Network
Shows status of
all connected
units; View Only
Smart Modules
Displays
readings for the
individual smart
modules; View
Only
Set Alarms
Allows user to
change settings for
alarms
Service Contacts
Contains key
contact information
for service
NOTE
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
32
Page 39
Figure 30 Liebert XDP User Menu screen
EVENT
LOG
°C / °F
% RH
SET
SET
12
39
6
SET
ALARMS
!
ACTIVE
ALARMS
1234
h
USER MENUS
ESC
to unselect
to change level
to open requested menu
to navigate
XDIO
Liebert iCOM Control—Firmware Version XP1.00.010.STD
33
Page 40
4.8Liebert iCOM User Menu Screens
SETPOINTS
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0)
Min Room Temperature Setpoint
User menus report general cooling unit operations and status. User menu screens employ a coding
that begins with “U” and is followed by parameters and information, such as settings. Gaining access
to some User menu screens requires entering a password; the User Menu password is 1490.
Check www.liebert.com for the latest Liebert iCOM user manual updates, SL-18835.
Figure 31 Setpoints screen
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to
maintain. If the temperature falls below this point, the unit will raise the refrigerant temperature to
reduce the amount of cooling.
The setting is intended to keep the room temperature above the setpoint. Without a proper setpoint,
the Liebert XDP can lower the room temperature too much, depending on the room dew point and
load. This setpoint will reduce the cooling to keep the room temperature above this desired
temperature.
NOTE
This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool
as much as possible. If the Liebert XDP is able to cool the room to this setpoint, it will reduce its
cooling action to try to keep the room temperature at or above this setpoint.
The default setting is 60°F (15.6°C). The range is 50-80°F (10-27°C).
For optimal cooling performance, the minimum temperature setpoint should be 1-2° below the
expected temperature at the remote sensors, which may affect placement of the remote sensors. If the
minimum temperature setpoint is set above the typical remote temperature sensor reading, it will
reduce the Liebert XD cooling output and, in extreme cases, cause erratic Liebert XD performance.
Spare Parts
Spare Parts—The spare parts lists contains a detailed description and part number that can be used
to order parts for the unit. These part numbers are specific to each model and option installed on the
unit.
Event Log
Event Log—The event log displays all events and actions that have been generated by the unit.
When multiple units are networked you will see the event log of the whole system. Each event shows
the unit that generated the alarm, time and date stamp, a description and the event type.
34
Page 41
Figure 32 Set Alarms screen
SET ALARMS (page 1 of 1)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
PASSWORD (Actual Level 0)
High Room Air Temperature
Low Room Air Temperature
High Room Dewpoint
High Refrigerant Temperature
High Room Air Temperature—Sets the threshold where a high room temperature alarm will
occur, based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur,
based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on
the calculated values from either remote Sensor A or remote Sensor B. The range for the high room
dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold where a high refrigerant temperature alarm
will occur based on the actual reading from the supply refrigerant sensor. The supply refrigerant
temperature is from the Liebert XDP to the modules. The range for the high supply refrigerant
temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold where a high chilled water temperature
alarm will occur based on the actual reading from the supply chilled water sensor. The range for the
high chilled water temperature is from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Sensor A Temperature62.8°F
Sensor A Humidity42.20%
Sensor A Dew Point39.4°F
Sensor B Temperature71.2°F
Sensor B Humidity29.60°%
Sensor B Dew Point37.8°F
Supply Refrigerant Temperature55.0°F
Supply Chilled Water Temperature55.0°F
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor A.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor B.
Supply Refrigerant Temperature—Displays the actual supply refrigerant temperature from the
Liebert XDP to the modules.
Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature
to the Liebert XDP.
Daily High Temperature07:49 :5772°F
Daily Low Temperature07:11 :3064°F
Daily High Humidity11:31:4645%
Daily Low Humidity07:56 :1834%
Daily High Dew Point07:47 :2645°F
Daily Low Dew Point08:02:2037°F
Daily High Refrigerant Temp13:01:2569°F
Daily Low R efrigerant Temp13:01 :1169°F
Daily High CW Temp14:01:3355°F
Daily Low CW Temp14:01 :4555°F
Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A
or remote Sensor B.
Daily High Dew Point—Shows the highest dew point in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Dew Point—Shows the lowest dew point in a 24 hour period for either remote Sensor A
or remote Sensor B.
Daily High Refrigerant Temperature—Shows the highest supply refrigerant temperature in a
rolling 24 hour period from the Liebert XDP to the modules.
Daily Low Refrigerant Temperature—Shows the lowest supply refrigerant temperature in a
rolling 24 hour period from the Liebert XDP to the modules.
Daily High Chilled Water Temperature—Shows the highest chilled water supply temperature
being delivered to the Liebert XDP in a rolling 24 hour period.
Daily Low Chilled Water Temperature—Shows the lowest chilled water return temperature
being delivered to the Liebert XDP in a rolling 24 hour period.
37
Page 44
Figure 35 Display Setup screen
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit
then
Language
Date
Time
Temperature Indication
Display Contrast
Buzzer Frequency
Backlite Off after
Screen
Language—Sets the language on the display. Changing this setting changes all menu parameters to
the selected language.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Date—Sets the internal date of the unit. If this unit is connected to other units with the unit-to-unit
network connection, each unit will reflect the last date set.
Time—Sets the internal time of the unit. If this unit is connected to other units with the unit-to-unit
network connection each unit will reflect the last time set.
Temperature Indication—Selects the actual and setpoint temperature scale. Selecting C will set
the unit to display in Celsius and F will set the unit to display in Fahrenheit.
Display Contrast—Changes the contrast of the display to adjust for different viewing angles, low
light and bright light conditions. As the display ages, the contrast may require adjustment for
viewing.
Buzzer Frequency—Changes the audible noise frequency of the built-in buzzer. The buzzer will
sound when its frequency is being adjusted, easing selection of a frequency easily detected when an
alarm occurs.
Backlite Off After—Controls how long the back-light remains active when the display is unused.
When the buttons on the front display have not been pressed for the time selected in this parameter,
the back-light will turn Off, extending the life of the display and saving energy.
Screen—Controls the screen layout. The Liebert XDP has one view, Unit View.
Display Colors—Selects the background color. Inverted sets the display to show white font with
blue background and Normal sets a white background with blue font.
Date Format—Date format changes the month, day and year arrangement shown on the front
display and on event time stamps.
Model / CapacityXDV8SK8KW
Left Fan StatusON
Right Fan StatusON
ONLINE
65°F
NODE 81 AZ81
57°F
92°F
66°F
XDV
Module Node ID—The location within the CANbus. Each module’s ID is factory-set to 80 and is
automatically changed during setup; requires no user action.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Module Labels—A four-character label consisting of two letters and two numerals. This is the standard
nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be
denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or
both labels can be used and are entered using the Module Setup found in the Service menu (S910).
Module Status—Indicates whether the smart module is connected to the CANbus.
Figure 37 Liebert XDV Smart Module Status screen
U905—Displays the temperature of the air entering the Liebert XDV.
U908—Displays the temperature of the air leaving the right and left fan of the Liebert XDV.
U911—Displays the module type and calculated local module capacity; possible module types are
XDV8SK, XDV8SS, XDV8ST, XDV10SK, XDV10SS and XDV10ST.
U912—Displays the left fan status; possible values are ON and OFF.
U913—Displays the right fan status; possible values are ON, OFF and ON ECON. ON ECON
indicates that only one fan is On.
39
Page 46
Liebert iCOM Control—Firmware Version XP1.00.010.STD
The parameter shows the actual hours Pump 1 and Pump 2 have operated and the maximum time
Pump 1 can operate before the next maintenance.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
4.9Liebert iCOM Service Menu Icons and Legend
Figure 41 Liebert iCOM Service Menu icons
Setpoints
View and change
operational
setpoints
Sensor
Calibration/Setup
Setup and calibrate
sensors for site
NOTE
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
Unit Diary
Shows all program
changes and
maintenance
performed,
Network
Setup or alter
network setting.
41
Maintenance/
Wellness
Settings
Shows all mainte-
nance records, cal-
culates next
maintenance date
Options Setup
Enter specific
settings for various
options
Diagnostics/
Service Mode
Enter Diagnostics/
Service Mode for
troubleshooting
and repair
Smart Module
Setup of alarms
and events. Set
temperature limits
for supply and
return sensors.
Label smart
modules, view
firmware version
Set Alarms
Change settings for
alarms
Service Contacts
Contains key
contact information
for service
Page 48
Figure 42 Liebert XDP Service Menu screen
SERVICE MENUS
to select parameter
to change level
to open requested menu
ESC
to unselect
to navigate
+
WELLNESS
SET
ALARMS
SERVIC E
+/-
NETWORK
SET
UP
XDIO
°C / °F
% RH
SET
SETPOINTS
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Min R oom Temperature Setpoint
Temperature Control Type
Temperature Proportional Band
Temperature Integration Tiime
Temperature Derivative
Dewpoint Margin
Minimum Control Point
Min Percent Cooling Setpoint
Liebert iCOM Control—Firmware Version XP1.00.010.STD
4.10Liebert iCOM Service Menu Screens
Service menus allow customized settings for site operations. Service Menu screens employ a coding
that begins with “S” and is followed by parameters and information, such as settings. Gaining access
to most Service Menus requires entering a password; the Service Menu password is 5010; see
Entering the Password for assistance.
The Liebert iCOM control firmware is being updated constantly. As a result, the Service Menu
parameters in this manual may be slightly different from what is shown on a cooling unit’s display.
Check
Figure 43 Setpoints screen
www.liebert.com for the latest Liebert iCOM user manual updates.
4.3.3 -
42
Page 49
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to
maintain. If the temperature falls below this point, unit will raise the refrigerant temperature to
reduce the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting
is 60°F (15.6°C).
NOTE
This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool
as much as possible. If the Liebert XDP is able to cool the room to this setpoint, it will reduce its
cooling action to try to keep the room temperature at or above this setpoint.
Temperature Control Type—Selects the type of control the system will use to activate cooling. The
Liebert iCOM control has three temperature control types: Proportional, PI and Intelligent. The
factory default is Intelligent.
Proportional—If Proportional Control is selected, the percent cooling requirement is
determined by the difference between the air temperature sensor reading and the temperature
setpoint. As the air temperature rises above the temperature setpoint, the percent cooling
required increases proportionally (from 0 to 100%) over half the programmable temperature
proportional band. The percent heating requirement (0 to 100%) is determined the same way
when the air temperature falls below the setpoint.
PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two
individual terms, proportional and integral. The proportional term is calculated in a manner
similar to the previously described Proportional control. The integral term (sometimes called
reset action) is calculated by measuring how much and for how long the air temperature has been
above or below the setpoint. If the actual air temperature is above the setpoint, the percent
requirement is slowly but continuously increased until the total is sufficient to bring the return
room air back to the setpoint.
Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the
setpoint. The percent temperature adjustment required is calculated based on logic that is
programmed into the control. These rules simulate the actions that would be taken by a human
operator manually controlling the system.
Temperature Proportional Band—Adjusts the activation points of compressors or rate of change
based on the actual sensor values deviation from setpoint. The smaller this number the faster the
compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short
cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8 to
54.0°F (1.0 to 30.0°C). The factory default setting is 7.0°F (3.9°C).
Temperature Integration Time—Temperature integration takes into consideration the amount of
time the actual temperature has deviated from the setpoint. The larger this deviation is the longer
the unit will wait before corrective action is taken to achieve the setpoint. This parameter is
adjustable from 0 to 15 minutes. The factory default is 0.
Temperature Derivative Time—Monitors the rate of change and will reduce or increase the
amount of corrective action based on the actual temperature increasing or decreasing toward the
temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.
Dewpoint Margin—Selects the difference between the room dew point and the refrigerant
temperature control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory
default setting is 4.0°F (2.2°C).
Minimum Control Point—Sets the minimum supply refrigerant temperature the Liebert XDP will
maintain. This parameter is adjustable from 40 to 80°F (4.4 to 27.0°C). The factory default is 55°F
(12.8°C).
Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal
operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go
below this value. The parameter is adjustable from 5 to 30%. The factory default is 15%.
43
Page 50
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Basic Settings (page 1 of 7)
SYSTEM
PASSWORD (Actual Level 0)????
Maintenance Frequency Per Year1
Max Bonus0
Max Penalty0
Last Maintenance08/25/2011
Service EngineerNOBODY
Confirm PMNo
Calculated Next Maintenance08/2014
Figure 44 Maintenance—Basic Settings screen, page 1 of 7
Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year
time span.
Max Bonus—Increases the time until the next required maintenance. Service personnel should
assign a bonus when a service visit finds all components working optimally.
Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign
a penalty when a service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the
date of the last visit.
Service Engineer—Provides a label for the service representative to list either the company name
or representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance
and resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the
last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty
or bonus set in the Liebert iCOM control.
44
Page 51
Liebert iCOM Control—Firmware Version XP1.00.010.STD
PASSW ORD (Actual Level 0 )????
Number of Starts31
Run Hours453hrs
Average Run Time876min
Starts per Day Best1
Starts per Day Worst24
Number of Alarms1
Actual Bonus0
Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7
Number of Starts—Shows the number of starts for the unit’s Pump 1.
Run Hours—Shows the number of run hours for the unit’s Pump 1.
Average Run Time—Shows the average run time of the unit’s Pump 1.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1.
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will
always take the value from the worst component for the next maintenance indication.
45
Page 52
Liebert iCOM Control—Firmware Version XP1.00.010.STD
PASSW ORD (Actual Level 0)????
Number of Starts2
Run Hours0hrs
Average Run Time0min
Starts per Day Best1
Starts per Day Worst24
Number of Alarms1
Actual Bonus0
Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7
Number of Starts—Shows the number of starts for the unit’s Pump 2.
Run Hours—Shows the number of run hours for the unit’s Pump 2.
Average Run Time—Shows the average run time of the unit’s Pump 2.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2.
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will
always take the value from the worst component for the next maintenance indication.
Figure 47 Maintenance screens, pages 4 through 7
Pages 4 through 7 apply only to the Liebert XDC. No Liebert XDP parameters are present.
46
Page 53
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Figure 48 Diagnostics/Service Mode screen, page 1 of 6
Page 1 applies to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 49 Diagnostics/Service Mode screen, page 2 of 6
Manual Mode—Used to place the Liebert iCOM control in manual mode. This is the initial setting
necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each
service menu item shows the current status of each parameter.
Pump 1—Starts the unit’s Pump 1.
Pump 2—Starts the unit’s Pump 2.
3P Start Active/Complete—Displays if the startup routine is active, and if it is completed.
3P Actuator Input Request—Shows the % call for cooling.
3P Actuator Position—Sets the position of the actuator 0-100% in manual mode.
3P Actuator Open—Opens the 3P actuator when set to ON in manual mode.
3P Actuator Close—Closes the 3P actuator when set to ON in manual mode
Valve Feedback—Opens the valve % in manual mode.
47
Page 54
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Manual Mode Control TypeFull
Manual Deviation12%
Analog Output R amp 130%
Analog Output R amp 20%
Analog Output R amp 360%
Analog Output R amp 458%
Alarm RelayOff
Warning RelayOff
Figure 50 Diagnostics/Service Mode screen, page 3 of 6
Page 3 applies to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 51 Diagnostics/Service Mode screen, page 4 of 6
Manual Mode Control Type—Not currently used.
Manual Deviation—Not currently used.
Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory
default for the Liebert XDP is the Valve % Open.
Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory
default for the Liebert XDP is the Call for Cooling.
Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory
default for the Liebert XDP is the CW Temp.
Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory
default for the Liebert XDP is the refrigerant temperature.
Alarm Relay—Used to activate the Liebert iCOM’s common alarm relay output.
Warning Relay—Used to activate the Liebert iCOM’s warning relay output.
48
Page 55
Liebert iCOM Control—Firmware Version XP1.00.010.STD
PASSW ORD (Actual Level 0 )????
High Room Air Temperature88.0°F
Low Room Air Temperature55.0°F
High Room D ew point65.0°F
High Refrigerant Temperature80.0°F
High Chilled W ater Temperature60.0°F
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The
range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range
for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the
high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm.
The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the
default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply refrigerant temperature alarm is
from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).
Customer Input 1—Selects the device and operation of the customer input. Each event reflects a
different alarm and possible action to the unit. Selectable options are:
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Call Service
C-Input
Water
Smoke
Customer Input 1 active when—Selects whether the Customer Input 1 input is normally closed or
normally open.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning
occurs.
Reset Disabled Alarms—Resets disabled events.
The Set Alarm Screens (Figure 56 through 60) permit setting the operation of an active alarm. Each
event can be enabled or disabled and can be set to operate as an alarm, warning or message. The
delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
51
Page 58
Figure 56 Set Alarms screen, page 3 of 7
SET ALARMS (page 3 of 7)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
HIGH TEMP SENSOR A
LOW TEMP SENSOR A
HIGH TEMP SENSOR B
LOW TEMP SENSOR B
HIGH DEWPOINT
SENSOR A FAILURE
SENSOR B FAILURE
HIGH CHILLED WATER TEMP
SUPPLY CW SENSOR FAILURE
Liebert iCOM Control—Firmware Version XP1.00.010.STD
HIGH TEMP SENSOR A—Enables or disables the High Temperature Sensor A event, which occurs
when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR A—Enables or disables the Low Temperature Sensor A event, which occurs when
the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH TEMP SENSOR B—Enables or disables the High Temperature Sensor B event, which occurs
when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is
reported as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR B—Enables or disables the Low Temperature Sensor B event, which occurs
when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
HIGH DEWPOINT—Enables or disables the High Dewpoint event, which occurs when the
calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
SENSOR A FAILURE—Enables or disables the Sensor A Failure event, which occurs when the
control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
SENSOR B FAILURE—Enables or disables the Sensor B Failure event, which occurs when the
control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
HIGH CHILLED WATER TEMP—Enables or disables the High Chilled Water Temp event, which
occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint.
Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control
waits before reporting the event.
SUPPLY CW SENSOR FAILURE—Enables or disables the Supply CW Sensor Failure Failure
event, which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
52
Page 59
Figure 57 Set Alarms screen, page 4 of 7
SET ALARMS (page 4 of 7)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
HIGH REFRIGERANT TEMP
LOW REFRIGERANT TEMP
SUPPLY REFRIGERANT SENSOR
LOSS OF FLOW PUMP 1
LOSS OF FLOW PUMP 2
PUMP SHORT CYCLE
Liebert iCOM Control—Firmware Version XP1.00.010.STD
HIGH REFRIGERANT TEMP—Enables or disables the High Refrigerant Temp event, which
occurs when the reading from supply refrigerant temperature sensor is above the user-specified
alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how
long the control waits before reporting the event.
LOW REFRIGERANT TEMP—Enables or disables the Low Refrigerant Temp event, which occurs
when the reading from supply refrigerant temperature sensor is below the user-specified alarm
setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the
control waits before reporting the event.
SUPPLY REFRIGERANT SENSOR—Enables or disables the Supply Refrigerant Sensor event,
which occurs when the control no longer senses a signal from the Supply Refrigerant Sensor. Sets how
the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when
Pump 1 is commanded to run and the differential pressure switch does not sense differential
pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the
control waits before reporting the event.
LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when
Pump 2 is commanded to run and the differential pressure switch does not sense differential
pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the
control waits before reporting the event.
PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow
is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs
when the chilled water control valve has been commanded by the control to open or close and no
change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning
or a message. Specifies how long the control waits before reporting the event.
CONDENSATION DETECTED
FAN FAILURE
CUSTOMER INPUT 1
SMOKE DETECTED
WATER UNDER FLOOR
UNIT X DISCONNECTED
WORKING HRS EXCEEDED
CALL SERVICE
LOSS OF POWER
Pages 5 and 6 apply to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 59 Set Alarms screen, page 7 of 7
Liebert iCOM Control—Firmware Version XP1.00.010.STD
occurs when water is detected at a Liebert XD cooling module. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
FAN FAILURE—Enables or disables the Fan Failure event, which occurs when a fan failure occurs
at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message.
Specifies how long the control waits before reporting the event.
CUSTOMER INPUT 1—Enables or disables the Customer Input 1 event, which occurs when 24VAC
is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies
how long the control waits before reporting the event.
SMOKE DETECTED—Enables or disables the Smoke Detected event, which occurs when the
Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
CONDENSATION DETECTED—Enables or disables the Condensation Detected event, which
54
Page 61
WATER UNDER FLOOR—Enables or disables the Water Under Floor event, which occurs when
SENSOR CALIBRATION/SETUP (page 1 of 3)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Temperature Sensor A
Calibrated Temperature Sensor A
Humidity Sensor A
Calibrated Humidity Sensor A
Temperature Sensor B
Calibrated Temperature Sensor B
Humidity Sensor B
Calibrated Humidity Sensor B
the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets
how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits
before reporting the event.
UNIT X DISCONNECTED—Not currently used.
WORKING HOURS EXCEEDED—Enables or disables the Working Hrs Exceeded event, which
occurs when a component has exceeded the user-specified limit. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
CALL SERVICE—Enables or disables the Call Service event, which occurs when the Customer
Input 1 is configured for “Call Service” and 24VAC is applied to the input. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOSS OF POWER—Enables or disables the Loss of Power event, which occurs when the unit is On
and operational and the 24VAC power to the control is lost. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Figure 60 Sensor Calibration/Setup screen, page 1 of 3
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Temperature Sensor A—Adjusts the temperature reading from the actual remote CAN Temp
Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other
sensors in the room.
Calibrated Temperature Sensor A—Displays the adjusted temperature value of the remote CAN
Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus
the offset Temperature Sensor A.
Humidity Sensor A—Adjusts the humidity reading from the actual remote CAN Temp Humidity
sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in
the room.
Calibrated Humidity Sensor A—Displays the adjusted humidity value of the remote CAN Temp
Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the
offset Humidity Sensor A.
Temperature Sensor B—Adjusts the temperature reading from the actual remote CAN Temp
Humidity sensor designated as Sensor B to compensate for any error of the sensor or to match other
sensors in the room.
Calibrated Temperature Sensor B—Displays the adjusted temperature value of the remote CAN
Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus
the offset Temperature Sensor B.
55
Page 62
Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as
Sensor B to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp
Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the
offset Humidity Sensor B.
Figure 61 Sensor Calibration/Setup screen, page 2 of 3
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Supply Refrigerant Sensor—Adjusts the temperature reading from the actual supply refrigerant
sensor to compensate for any error of the sensor.
Calibrated Supply Refrigerant Sensor—Displays the adjusted temperature value of the supply
refrigerant sensor. This value is the actual sensor reading plus or minus the offset Supply Refrigerant
Sensor.
Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled
water sensor to compensate for any error of the sensor.
Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled
water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water
Sensor.
Figure 62 Sensor Calibration/Setup screen, page 3 of 3
56
Page 63
Liebert iCOM Control—Firmware Version XP1.00.010.STD
SYSTEM/NETWORK SETUP (page 1 of 2)SYSTEM
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Number of Connected Units
Supply Refrigerant Sensor 0%—Allows the sensor reading to be calibrated at the lowest reading of
the sensor. This calibration changes the start point of the sensor reading.
Supply Refrigerant Sensor 100%—Allows the sensor reading to be calibrated at the highest
reading of the sensor. This calibration changes the end point of the sensor reading.
Figure 63 System/Network Setup screen—System, page 1 of 2
Number of Connected Units—Shows the number of displays connected. This is always 1.
Configuration Safe—Saves or loads configuration settings for the display that have been modified
from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM
Service Tool. Selecting Save will write the settings to the internal storage file and selecting Load will
write the settings from the internal storage file to the application software. The internal file is
updated automatically every 12 hours.
Network Safe—Saves or loads network settings for the display that have been modified from the
factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service
Tool. Selecting Save will write the settings to the internal storage file and selecting Load will write
the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM display.
57
Page 64
Liebert iCOM Control—Firmware Version XP1.00.010.STD
SYSTEM/NETWORK SETUP (page 2 of 2)SYSTEM
Attention: any changes done on these parameters
must be followed by a 'Save+Reboot ' command .
PASSW ORD (Actual Level 0 )
IP Address
Netmask
Gateway
MAC
U2U Protocol
U2U Address
U2U Group
Figure 64 System/Network Setup screen—System, page 2 of 2
IP Address—Contains the network address of the display. This address must be unique on the
network. The factory default is 192.168.254.003.
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A network point that acts as an entrance to another network. The factory default is
0.000.000.000.
MAC—A unique hardware identifier for the Ethernet device. The following parameters (U2U
Protocol, U2U Address and U2U Group) are for displaying other networked Liebert XDPs. The
Liebert XDP does not perform Teamwork Operations.
U2U Protocol—This is always set to GBP.
U2U Address—A unique identifier for each display on the network. Display addresses range from 33
to 64. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Used to create zones or groups within a U2U network. Once a group number is
selected, the display will see only other devices with the same group number. The group number can
be changed to view other devices in different groups. Not currently used.
Bootloader Variables—Indicates the bootloader has changed since it was last loaded. This
parameter should only be activated by an authorized service person.
58
Page 65
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Figure 65 System/Network Setup screen—Unit, page 1 of 2
Monitoring Address—Sets the address used by the Liebert IntelliSlot® cards. This is set to 3 at the
factory and should not be changed.
Unit Name—Identifies the unit from the local or remote display. This label will show at the top right
of every screen that has monitoring or configuration of that unit
Configuration Safe—Saves or loads configuration settings for the control board that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and
selecting “Load” will write the settings from the internal storage file to the application software. The
internal file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the control board that have been modified from
the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM
Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load”
will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM.
59
Page 66
Liebert iCOM Control—Firmware Version XP1.00.010.STD
SYSTEM/NETWORK SETUP (page 2 of 2)
Attention: any changes done on these parameters
must be followed by a 'Save+Reboot ' command .
PASSW ORD (Actual Level 0 )
Monitoring Protocol
IP Address
Netmask
Gateway
MAC
U2U Protocol
U2U Address
U2U Group
Bootloader Variables
Static RAM
Figure 66 System/Network Setup screen—Unit, page 2 of 2
Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default which will
provide communications to the Liebert IntelliSlot housing. IGMnet will activate the 77/78 terminals
for communication to the Liebert SiteLink(-E). Liebert Hironet is only used on Liebert HPM units.
IP Address—Contains the network address of the display. This address must be unique to every
other device on the network. The factory default is 192.168.254.003.
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A gateway is a network point that acts as an entrance to another network. The factory
default is 0.000.000.000.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other
Liebert XDPs that are networked. The Liebert XDP does not perform Teamwork Operations.
U2U Protocol—Always set to GBP.
U2U Address—Unique identifier for each display on the network. Display addresses range from 1 to
32. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Creates zones or groups within a U2U network. Once a group number is selected the
display will only see other devices with the same group number. The group number can be changed to
view other devices in different groups. Not currently used.
Bootloader Variables—Indicates if there has been a change to the boot loader since it was last
loaded. This parameter should only be activated by authorized service personnel.
Static RAM—Allows service personnel to clear and reboot the RAM of the control board. Only
Emerson service personnel should perform this function.
60
Page 67
Figure 67 Options Setup screen, page 1 of 2
OPTIONS SETUP (page 1 of 2)
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Autorestart Enabled
Single Unit Auto Restart
Unit Start Sequence D elay
Control Delay Time
Pump Start Time Delay
Pump Wait Time Delay
Pump Off Time Delay
Autorestart Enabled—Restarts the unit after a power cycle when set to Yes. When this parameter
is set to No, the unit will not restart after a power cycle.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Single Unit Auto Restart—Sets a time delay for the unit to restart when the Auto Restart Enabled
is set to Yes. The delay begins once the boot process has completed. This parameter allows units to be
staggered On to reduce the amount of simultaneous power consumption after a loss of power.
Unit Start Sequence Delay—Not currently used.
Control Delay Time—Not currently used.
Pump Start Time Delay—Sets a time delay to ensure that refrigerant begins flowing when the
pump starts. If refrigerant does not begin flowing before the user-set delay expires, the pump will be
turned Off.
Pump Wait Time Delay—Sets the pump wait time delay to prevent the pump from continuing to
run when refrigerant is not flowing. If a pump is running normally and refrigerant flow is lost, the
pump will stay On for the specified time trying to re-establish refrigerant flow. If refrigerant flow
resumes during the specified interval, the pump will continue operating. If the wait time expires and
refrigerant flow has not resumed, the pump will shut down.
Pump Off Time Delay—Sets the length of time a pump will remain off when refrigerant flow is
interrupted or stops. After the time delay has expired, the control will try to restart the pump.
Lead Pump—Sets which pump is the active pump. It can be set to PUMP 1 or PUMP 2. The control
will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF FLOW
condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time delay
has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.
Pump Short Cycle Delay—Sets the time to lock Off the unit if it is unable to establish refrigerant
flow within this set amount of time.
61
Page 68
Figure 68 Options Setup screen, page 2 of 2
OPTIONS SETUP (page 2 of 2)
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0 )
Valve Start Open
Valve Start TD
3P Actuator Runtime
3P Actuator Direction
Unit Off Valve % Open
PASSW ORD (Actual Level 0 )
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
Valve Start Open—Sets position of the valve when the unit starts.
Liebert iCOM Control—Firmware Version XP1.00.010.STD
Valve Start TD—Sets a time interval for the unit to complete startup and enter into normal
operation.
3P Actuator Runtime—If Valve Control is selected for “Time” then this parameter sets the travel
time of the valve to determine the full open and closed position of the valve. This parameter is set at
the factory, based on the valve manufacturer’s specifications.
3P Actuator Direction—Sets if the valve is a “Direct” or “Reverse” acting valve.
Unit Off Valve % Open—Sets the valve position when the unit is Off.
Figure 69 Module Setup screen, page 1 of 20
62
Page 69
Liebert iCOM Control—Firmware Version XP1.00.010.STD
MODULE SETUP (page 1 of 20)UNIT 01
PASSW ORD (Actual Level 0 )
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
This screen selects the operation of an active alarm for each smart module. Each event can be enabled
or disabled and can be set to operate as an alarm, a warning or a message. The delay is the time the
control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer/front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Fan Control Type—Sets the fan control mode. Values can be OFF, ON, ON ALL and TEMP CNTL.
Disable Local Button—Disables the push button on the front of the smart module. To disable the
push button, set the parameter to YES. To re-enable the push button, set the parameter to NO.
Flash LED at Module—Flashes the LED on the smart module when set to Yes.
Set Module Label—A four-character label consisting of two letters and two numerals. This is the
standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location
can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list.
Either or both labels can be used and are entered using this screen.
Supply Air Temp Limit—Sets the high and low supply air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Return Air Temp Limit—Sets the high and low return air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Firmware Version—Displays the firmware version installed on the smart module.
Figure 70 Module Setup screen, page 1 of 20
63
Page 70
5.0STARTTHE LIEBERT XDP WITH LIEBERTICOM
!
5.1Checklist for Liebert XDP Startup
CAUTION
Risk of piping and component rupture. May cause equipment damage or injury.
Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of
piping. Do not close valves without following recommended procedures for repair,
maintenance and replacement of components. Install pressure relief valves in field piping
that may become isolated by service valves.
NOTE
The Liebert XDP160 requires a minimum load of 48kW (163,800BTU/H) before the system can
be commissioned. This load can be supplied by actual user load in racks, by independent load
banks or by the “Load Bank Testing” service of Emerson Network Power Liebert Services. To
achieve the minimum load requirements, the capacity of all connected modules must total at
least 48kW (163,800BTU/H). See
NOTE
Before any action that could cause a disturbance in the Liebert XD system’s cooling function is
begun, the facility manager MUST be informed. In addition, after the action is taken and the
work is finished, the facility manager MUST be informed
1. Verify that bypass flow controllers were installed (if applicable), see Table 5.
2. Verify that the minimum load level of 48kW (163,800BTU/H) is present.
3. Check all isolation ball valves in the Liebert XDP and Liebert XD cooling module and verify that
all are open.
4. Check rotation of the Liebert XDP’s pumps.
On 460V units only—Hold the rotation device provided against the pump housing at the
inspection screw prior to energizing the pumps. Counterclockwise indicates proper rotation;
clockwise indicates incorrect rotation.
On 208V and 400V units only, view the LED indicator on the pump. Green indicates proper
rotation; Green and Red indicate incorrect rotation.
Table 13Liebert XDP pump light indicator—208V and 400V units
Indicator Lights
Green Red
OffOff
OnOffThe electricity supply has been switched On. Normal operation.
OnOn
The electricity supply has been switched Off or the pump has
been cut out by the thermal switch.
The electricity supply has been switched On. The direction of
rotation is wrong.
Table 1.
Description
Start the Liebert XDP with Liebert iCOM
5. Check rotation of fans on Liebert XD cooling module units.
6. Verify that air is being discharged into the cold aisle.
7. Confirm that the total calculated refrigerant R-134a amount has been properly charged into the
system (see
8. Confirm that the remote temperature/humidity sensors provided have been installed in optimal
locations (see
The Liebert XDP system is now ready to be turned ON.
5.2Starting the Liebert XDP with Liebert iCOM Controller
Operation above sight glass #3 can
make the system operate erratically
and reduce cooling capacity. Reduce
charge to recommended level.
Recommended operating level
Acceptable operating level
Operation below sight glass #1 may
cause loss of flow or cooling. Add
charge to reach recommended level.
For lightly loaded systems,
the recommended operating
level is sight glass #2.
Sight Glasses 1, 2 & 3
The Liebert XDP is started, stopped and controlled through the Liebert iCOM controller. Figure 24
shows the Liebert iCOM keypad.
1. Turn the Liebert XDP On with the user interface (I/O button). The factory-setting defaults
Liebert XD module fans to On. When the Liebert XDP is turned On, the Liebert XD modules’ fans
will turn On. Allow the system to attempt to start for at least 2 minutes.
If the Liebert XDP pump cannot maintain flow and continues to switch over due to starting
difficulties, refer to
2. If constant flow is established, wait until the Liebert XDP has been operating for 10-15 minutes,
then verify that the refrigerant level in the receiver sight glass is between the second and third
level (see
Figure 71). Add or remove charge, if necessary.
3. Check pressure differential functionality:
The Liebert XDP system should be On. If it is Off:
a. Turn the Liebert XDP On via user interface (I/O button). The factory-setting defaults Liebert
XD module fans to On. When the Liebert XDP is turned On, the Liebert XD modules’ fans will
turn On.
If no “Loss of Flow” alarm is present—This suggests that there is flow. Test the pressure
differential by closing the ball valve on either the suction line or discharge line to stop the
flow.
This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has
opened on low pressure (below 6 psi; 41kPa; 0.41 bars).
If a “Loss of Flow” alarm is present—This suggests that there is no flow. Verify that this
is correctly annunciated by looking at the sight glass in the receiver. If a true no-flow condi
tion exists, the level will not move.
However, if there is flow, but the differential reading is faulty, the level will slowly
drop, indicating flow, while the loss of flow alarm is annunciated.
Check the pressure differential physically by making sure that the electrical connections are
properly connected. Then check the pressure differential electrically by making sure that the
unit has 24VAC across it.
7.0 - Troubleshooting. After remedying the problem, proceed to Step 2.
Start the Liebert XDP with Liebert iCOM
-
Figure 71 System R-134a liquid level at 160kW load
65
Page 72
6.0ALARM DESCRIPTIONSAND SOLUTIONS
6.1Alarm Descriptions
NOTE
Alarms must be acknowledged before they can be reset. To acknowledge or silence an alarm,
press the ALARM key one time. This will silence the alarm; the red LED will remain
illuminated until the alarm is reset.
CALL SERVICE—Activated when Customer Input 1 is configured for “Call Service” and 24VAC is
applied to the input. This alarm is reset when the 24VAC is removed.
CONDENSATION DETECTED (optional)—Activated when water is detected at a cooling module.
A 24VAC signal is applied to the condensation input on the control board using a pair of twisted wires
or the alarm is sent via CANbus communication. When this alarm is active, the control will raise its
refrigerant control point by 4°F (2.2°C). This alarm will reset when the alarms is acknowledged and
the signal stops being sent from CANbus or condensation input. The alarm can also be reset by
cycling the power. The main power must be cycled to remove the 4°F (2.2°C) offset.
CONTROL VALVE FAILURE—Activated when the chilled water control valve has been
commanded to open or close by the control and no change is detected by the valve position signal. The
alarm is reset when the main power is cycled.
CUSTOMER INPUT 1—Activated when a 24VAC signal is applied to the customer alarm input on
the control board. This alarm will reset when the 24VAC signal stops being sent from the customer
alarm input. WATER UNDER FLOOR, SMOKE DETECTED, CALL SERVICE, and COMP LOCK
PD are possible designations for this alarm; they are set with the Unit Code.
FAN FAILURE (optional)—Activated when a 24VAC signal is applied to the fan failure input on
the control board using a twisted pair of wires or the alarm is sent via CANbus communication. This
alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or
fan failure input. The alarm can also be reset by cycling the power.
HIGH CW TEMP—Activated when the Supply CW sensor reads the chilled water temperature
above the user-specified alarm setpoint. This alarm will reset when the reading from the refrigerant
temperature sensor drops 5°F (2.8°C) below the user-specified setpoint and the alarm has been
acknowledged.
HIGH DEW POINT—Activates when the calculated dew point at either Sensor A or B exceeds the
user-specified alarm setpoint. The alarm will reset when the calculated room dew point from both
Sensor A and Sensor B is 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.
HIGH REFRIGERANT TEMP—Activated when the refrigerant temperature sensor reads the
refrigerant temperature above the user-specified alarm setpoint. This alarm will reset when the
reading from the refrigerant temperature sensor drops 2°F (1.1°C) below the user-specified setpoint
and the alarm has been acknowledged.
HIGH TEMP SENSOR A—Activated when the reading from Sensor A is above the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the
setpoint and the alarm has been acknowledged.
HIGH TEMP SENSOR B—Activated when the reading from Sensor A is above the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the
setpoint and the alarm has been acknowledged.
LOSS OF FLOW PUMP 1—Activated when Pump 1 is commanded to run and the differential
pressure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting
to start Pump 1 three times, the Liebert XDP will automatically switch to the other pump to establish
flow. This alarm will reset when flow has been established on Pump 1 and the alarm has been
acknowledged.
LOSS OF FLOW PUMP 2—Activated when Pump 2 is commanded to run and the differential
pressure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting
to start Pump 2 three times, the Liebert XDP will automatically switch to the other pump to establish
flow. This alarm will reset when flow has been established on Pump 2 and the alarm has been
acknowledged.
Alarm Descriptions and Solutions
66
Page 73
Alarm Descriptions and Solutions
LOW MEMORY—Activated when the control board is low in memory resources. This alarm rests
automatically as soon as memory consumption falls below the threshold.
LOW REFRIGERANT TEMP—Activated when the supply refrigerant temperature sensor
temperature reading drops below the higher of the two calculated dew points, assuming that neither
Sensor A or Sensor B has a sensor failure alarm. This alarm will reset when the refrigerant
temperature sensor reads the refrigerant temperature above both of the two calculated dew points
and the alarm has been acknowledged. This alarm can lock the unit Off. If this occurs, the main
power must be cycled, or the Low Refrig Temp Alarm Code in the Service Diagnostics menu must be
reset to 0.
LOW TEMP SENSOR A—Activated when the reading from Sensor A drops below the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A rises 2°F (1.1°C) above the
setpoint and the alarm has been acknowledged.
LOW TEMP SENSOR B—Activated when the reading from Sensor B drops below the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor B rises 2°F (1.1°C) above the
setpoint and the alarm has been acknowledged.
NODEX CONDENSATION DETEC—Activated when condensation is detected on a smart module
at CAN node ID X, where X is a value ranging from 81 to 100. This alarm resets when condensate is
no longer detected. The main power must be cycled off to remove the 4°F (2.2°C) offset value.
NODEX FAN FAILURE—Activated when a fan failure occurs on a smart module at CAN node ID X,
where X is a value ranging from 81 to 100. The alarm will rest when the fan returns to normal
operation.
NODEX LOCAL SHUT DOWN—Activated when a smart module at CAN node ID X, where X is a
value ranging from 81 to 100, has been shut down by an external signal. This alarm will reset when
the remote shutdown input is deactivated.
NODEX RETURNAIR TEMPLIMT—Activated when the return air temperature (entering air
temperature to the module) exceeds the user-specified return air temperature range on a smart
module at CAN node ID X, where X is a value ranging from 81 to 100. This alarm will reset when the
return air temperature return to with the user-specified range.
NODEX SENSOR FAILURE—Activated when a smart module at CAN node ID X, where X is a
value ranging from 81 to 100, stops receiving a signal from one or more of its supply air, return air, or
refrigerant temperature sensors. This alarm will reset when signals are detected from the module’s
sensors.
NODEX SUPPLYAIR TEMPLIMT—Activated when the supply air temperature (temperature of
the air leaving the module) exceeds the user-specified supply air temperature range on a smart
module at CAN node ID X, where X is a value ranging from 81 to 100. This alarm will reset when the
return air temperature return to with the user-specified range.
PUMP SHORT CYCLE—Activated when the Liebert XDP is trying to establish flow (differential
pressure) and is unable to do so. The Liebert XDP will attempt three times to establish flow on a
pump before trying the other pump. The control will keep cycling three times on one pump, then three
times on the other pump until it is able to establish flow (differential pressure). If this cycling occurs
for 30 minutes and the Liebert XDP still does not establish flow, a PUMP SHORT CYCLE alarm will
be present. This alarm will shut down the Liebert XDP. To reset this alarm, the main power must be
cycled.
RAM/BATTERY FAIL—Activated when the RAM backup battery or the RAM itself has failed. This
requires a hardware replacement.
SENSOR A FAILURE—Activated when the controls no longer senses a signal from Sensor A. This
alarm will reset when the signal is returned and the alarms has been acknowledged.
SENSOR B FAILURE— Activated when the controls no longer senses a signal from Sensor B. This
alarm will reset when the signal is returned and the alarm has been acknowledged.
67
Page 74
SMOKE DETECTED—Activated when the Customer Input 1 is configured for “Smoke” and 24VAC
is applied to the input. This alarm is reset when the 24VAC is removed.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
SUPPLY CW SENSOR FAILURE—Activated when the control no longer senses a signal from the
Supply CW sensor. This alarm will reset when the signal is returned.
SUPPLY REFRIGERANT SENSOR FAILURE—Activated when the control no longer senses a
signal from the supply refrigerant sensor. This alarm will reset when the signal is returned.
UNIT CODE MISSING—Activated when a valid unit code has not been entered and saved. To reset,
enter valid unit code, save and execute.
WATER UNDER FLOOR—Activated when Customer Input 1 is configured for “Water Alarm” and
24VAC is applied to the input. This alarm is reset when the 24VAC is removed.
6.2Warning Descriptions
LOSS OF POWER—Activated when the unit is On and operational and 24VAC power to the control
is lost. This alarm will be emitted when power is restored to the control. The Liebert XDP will restart
at a user-defined time delay after power is restored. Once activated, the alarm will remain activated
for 30 minutes.
PUMP 1 HRS EXCEED—Activated when the Pump 1 Actual Hours exceeds the user-specified limit.
To reset, Actual Hours must be reset to 0.
Alarm Descriptions and Solutions
PUMP 2 HRS EXCEED—Activated when the Pump 2 Actual Hours exceeds the user-specified limit.
To reset, Actual Hours must be reset to 0.
6.3System Shutdown Causes
Unit Is Off By Refrig Sens Fail
The control has lost its signal from the refrigerant temperature sensor. The control has no way of
controlling the refrigerant temperature, so the unit is shut off. Main power (disconnect switch) must be
turned Off, then back On to clear this alarm.
Unit Is Off By High CW Temp
The entering chilled water temperature is too high to keep the refrigerant pump(s) running normally. If
a HIGH CW TEMP alarm occurs and the refrigerant pump loses flow (differential pressure), then the
Liebert XDP will go into a pre-chill mode. The Liebert XDP can attempt to start again only if the
entering chilled water temperature drops below the HIGH CW TEMP setpoint.
Unit Is Off By Pump Short Cycle
The control was unable to get a pump started upon startup or after a loss of differential pressure. The
control looks at the SHORT CYCLE time delay. If it cannot establish differential pressure within that
amount of time, the unit is shut down. Main power (disconnect switch) must be turned Off, then back
On to clear this alarm.
Unit Is Off By Low Refrig Temp
The control was unable to raise the refrigerant temperature to the calculated refrigerant temperature
control point. The unit is shut down because if the control cannot raise the refrigerant temperature to
the calculated refrigerant temperature control point, water may condense on the refrigerant piping and
receiving coils. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
68
Page 75
7.0TROUBLESHOOTING
Table 14Troubleshooting the Liebert XDP
SymptomPossible CauseCheck or Remedy
No main powerCheck L1, L2 and L3 for rated voltage.
Overloads trippedAllow pump to cool. Check amp draw.
Tripped circuit breakerCheck circuit breaker to pump(s).
Incorrect phase wiringSee Table 13.
No chilled water
Isolation valve(s) on pump suction
and/or discharge is closed.
Supply chilled water is too high
Liebert XD cooling modules are Off
Low Refrigerant Temperature
(high dew point)
Pressure switch not making contact
Not enough chargeSee 5.1 - Checklist for Liebert XDP Startup.
Chilled water valve not closing
completely.
Cavitation due to vapor in pump
Worn motor bearingsReplace pump
Pump is rotating in reverseSee Table 13.
Low refrigerant temperature
Loss of power
Clogged filter dryer and/or impellerClean out debris
Leak in system - loss of charge
Low chilled water temperature alarm
and loss of flow Pump X alarm
Supply refrigerant sensor failure
alarm
Debris or other contaminants in
refrigerant
Motor operates but valve won't open
No 24 VAC power to motorCheck for 24 VAC between P52-1 and P52-4.
No signal from controlCheck 24 VAC at P22-1 (close) or P22-3 (open).
Motor not operating
Check and verify that there is supply chilled water to the
Liebert XDP.
Open all isolation valves completely during normal operation.
Check and verify that the chilled water temperature setpoint is
at 50°F (10°C) or lower and that there is flow on the chilled
water side.
Check Liebert XD cooling modules to make sure that they are
On prior to starting the Liebert XDP.
Check alarm(s) history on Liebert XDP. The Liebert XDP was
operating below the dew point for a significant amount of time.
Check humidity in conditioned space, lower humidity if
necessary to allow Liebert XDP to operate at a lower
temperature. (Disconnect must be switched to Off then back
On to allow Liebert XDP to reset itself).
Check both differential pressure settings. If not within 6 psi, ± 1
psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then manually
change accordingly.
Wait at least 10 minutes before calibrating. Access the
Advanced Menu>Factory Settings>Calibrate Actuator.
Contact Liebert Services for assistance, 1-800-543-2778.
Check for adequate charge in system, refer to the User's
Manual. 5.1 - Checklist for Liebert XDP Startup
1. Check humidity of the room along with the location of
remote sensors. Make sure that the sensors are not in a cold
area where there is insufficient air flow for accurate,
representative readings.
2. Chilled Water temperature is too cold.
3. Load is too light.
When power is restored, the Liebert XDP will automatically
restart.
Check the entire system for leaks with a refrigerant sniffer.
Repair as necessary.
Check supply chilled water temperature.
Check wiring.
Call service.
Replace.
Check linkage for adjustment and be sure that it is tight on the
valve.
Unplug P22 from the board. Jumper P22-5 to P52-4 for
grounding, then jumper P22-1 to P52-1 to drive close. Remove
jumper to close and then jumper P22-3 to P52-1 to drive open.
If motor fails to work, replace it.
Troubleshooting
69
Page 76
Table 14Troubleshooting the Liebert XDP (continued)
SymptomPossible CauseCheck or Remedy
Motor Burnout
Main 24VAC Fuse Trips
Unstable Pump
Operation
Room Becomes
Too Warm
Reduced Chilled Water
Flow Rate
Increased Refrigerant
Temperature
Check control panel for welded
contactor contacts or welded
overload contacts
Shorts or loose connectionsCheck the wiring connections of the 24 VAC circuit.
Faulty circuit boardReplace the circuit board.
R-134a pump loop overcharged
R-134a pump loop undercharged
Filter dryer clogged
Liebert XDP is Off
High dew point
Liebert XD cooling modules are Off
Minimum room temperature setpoint
is too high
Temperature/humidity sensors
incorrectly placed
Clogged strainerClean or replace strainer
Fouled heat exchanger (no strainer
installed)
Clogged strainerClean or replace strainer
Fouled heat exchanger (no strainer
installed)
Troubleshooting
Replace defective components.
While pump is running R-134a receiver level must be within
recommended levels (see
See Clogged Filter Dryer and/or Impeller symptom and
remedy.
Check status of the Liebert XDP at the user interface. Turn
system On at I/O button if system is Off.
Check temperature and relative humidity (RH) of room. Lower
RH setpoint if necessary to lower dew point. At normal room
temperature of 68°F (20°C), the RH should be set to 50% or
lower.
Check Liebert XD cooling modules to make sure that they are
On before starting the Liebert XDP.
Check the setpoint in the User Setpoints menu (see
Figure 43).
Place the sensor on the return air side of the primary air mover
(eg., Liebert DS). Do not install the sensor near unsealed
doors, windows or similar areas.
Replace heat exchanger and install 20-40 mess strainer
Replace heat exchanger and install 20-40 mess strainer
Figure 71).
70
Page 77
8.0MAINTENANCE
The Liebert XD system components require little maintenance when proper fluid levels are
maintained and proper startup and operation procedures are followed. The following tasks should be
performed at the intervals stated:
1. Clean or replace chilled water strainer annually. Adjust accordingly based on purity of chilled
water.
2. Check sight glass level of receiver every 4-6 weeks. During normal operation, the level should be
at or above the second sight glass.
3. Check system for leaks every 4-6 weeks.
8.1Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection
systems in the European Community market and operating with fluorinated greenhouse gases (fgas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (Fgas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the
atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not
entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to
recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
Maintenance
71
Page 78
9.0SPECIFICATIONS
Table 15Liebert XDP160 specifications
ModelsXDP160RC--4XDP160RA--4XDP160RM--4
Cooling Capacity, Nominal
Minimum Load30% of nominal system capacity or 48kW (163,800BTU/H)
Il Produttore dichiara che, se munito di marchio CE, il prodotto è conforme alle direttive dell'Unione
europea:
The Manufacturer hereby declares that this product, when bearing the CE mark, conforms to the
European Union directives:
Der Hersteller erklärt hiermit, dass das vorliegende Produkt, sollte es die CE-Kennzeichnung tragen, den
folgenden Richtlinien der Europäischen Union entspricht:
Le fabricant déclare par la présente que ce produit, portant la marque CE, est conforme aux directives
de l'Union européenne :
El fabricante declara por la presente que si este producto lleva el marcado CE es conforme con las
directivas de la Unión Europea:
O fabricante declara por este meio que este produto, quando ostenta a marca CE, está em
conformidade com as directivas da União Europeia:
Tillverkaren tillkännager härmed att den här produkten, när den är CE-märkt, överensstämmer med
EU:s direktiv:
De fabrikant verklaart hierbij dat dit product, indien het van de CE-markering is voorzien, conform de
EU-richtlijnen is:
Valmistaja vakuuttaa täten, että mikäli tuotteessa on CE-merkintä, se täyttää seuraavien EU-direktiivien
vaatimukset:
Produsenten erklærer herved at dette produktet, når det er CE-merket, er i samsvar med EU-direktiver:
Producenten erklærer hermed, at dette produkt overholder EU's direktiver, når det bærer CE-mærket:
Ο Κατασκευαστής δηλώνει ότι το προϊόν αυτό, το οποίο φέρει σήμανση CE, είναι σύμμορφο με τις
οδηγίες της Ε.Ε.:
2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC
Page 80
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity
™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
™
Compromise
by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.