This manual contains important instructions that must be closely followed during installation and
maintenance of this unit to maintain compliance with agency listings. Read all safety and operating
instructions before attempting to operate the XDF. Adhere to all warnings on the unit and in this
manual. Follow all operating and user instructions.
This product is designed for commercial / industrial use only. This product is not intended for use
with life support or other U.S. FDA designated “critical” devices. Maximum loads must not exceed
those shown on the Liebert XDF serial tag.
Operate this product in an indoor environment at an ambient temperature between 35°F and 104°F
(1.6°C to 40°C). Install in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
This product must be connected to and powered by suitable AC supplies, rated in accordance with the
unit’s serial tag. It must be suitably grounded and protected by circuit breakers or fuses.
Power extension cables, if used, must be rated for the load and must not exceed 20 ft. (6.1m) in length.
Liebert recommends using shielded cables for all external communication interfaces.
Ensure that the XDF has proper ventilation. Never block or insert objects into the ventilation holes or
other openings. Maintain a minimum clearance of 36 in. (915mm) in front, behind, on the right side
and above the self-contained, air cooled XDF for proper airflow and service. The water/glycol cooled
XDF requires 36 in. (915mm) clearance in front, behind and on the right side. It does not require top
clearance.
1
1.0GLOSSARYOF SYMBOLS
Hazardous Voltage Present
Note following instructions
Consult user manual for additional information
Indicates weight
Glossary of Symbols
Indicates ground connection
Indicates alternating current
2
Product Description
2.0PRODUCT DESCRIPTION
Congratulations on purchasing a Liebert XDF. The XDF is an integrated equipment cabinet with
built-in cooling and intelligent control to protect mission-critical enterprise systems from extreme
heat. The XDF provides an organized, secure, controlled environment for your sensitive electronic
equipment. The unit is available in a variety of configurations to suit your electronic equipment’s
environmental requirements.
The self-contained, air cooled Liebert XDF is intended for installation in open areas. Installation in
closed-in areas, such as in a closet, alcove or similar space, requires field-supplied ducting, an external booster fan and sufficient makeup air. Contact your local Liebert representative before installing
the XDF in an area that might inhibit heat dissipation.
The water/glycol cooled unit, however may be installed in closed-in areas, subject to clearances of
three feet in the front, rear and right side. See Figure 6. This is possible because heat rejected from
the XDF cabinet is carried away in the coolant.
2.1Operational Overview—Self-Contained, Air Cooled Model
The self-contained, air cooled XDF model employs a compressorized, direct expansion cooling system
rated at 14kW to supply cooling air to rack-mounted equipment. A bank of fans circulates this cooling
air through the electronic equipment in the XDF (see Figure 1). An evaporator coil extracts heat
from the circulating air. That heat is transferred to a condenser at the top of the XDF and exhausted
into the room.
The XDF’s backup ventilation system operates automatically if power fails or if any XDF cooling system component fails.
Figure 1Component location, general operational layout of self-contained, air cooled model
Condenser Coil transfers
heat extracted from
electronic equipment
cabinet to incoming air
Heated Air Exhaust
Condenser Air
Entry Point
iCOM Controller
Rack-Mount Equipment
Compartment (isolated
from external air and top
condenser section)
Condenser Air
Entry Point
Condenser
Coil - 1 of 2
Evaporator Coil
extracts heat from
air circulated through
the rack equipment
compartment
Backup Ventilation
Air Intake
Compressor
Evaporator Fans
circulate cooling air
3
2.2Operational Overview - Water/Glycol Cooled Model
The water/glycol cooled XDF model employs a single-stage cooling system rated at 14kW to supply
cooling air to the rack-mounted equipment. A bank of fans circulates this cooling air through the electronic equipment in the XDF (see Figure 1).
An evaporator coil extracts heat from the circulating air. That heat is transferred to a brazed plate
condenser at the top of the XDF, transferred to the cooling water or glycol solution and is piped out of
the unit.
Coolant is piped through the back of the XDF through supply and return pipes with 1" female NPT
connections (refer to Figure 2 or Figure 6).
The XDF’s backup ventilation system operates automatically if power fails or if any XDF cooling system component fails.
If water is used as the coolant, Liebert recommends employing a closed system connected to an external condensing unit. A closed water supply system protects the XDF from particles and other contaminants that might reduce cooling efficiency and damage the XDF.
Figure 2Component location of water/glycol cooled model
Brazed Plate
Condenser
(behind grille)
Product Description
Coolant Return - in rear
Coolant Supply - in rear
iCOM Controller
Rack-Mount
Equipment
Compartment
(isolated from
external air)
Front of XDF
Evaporator Coil
extracts heat from
air circulated
through
the rack equipment
compartment
Backup Ventilation
Air Intake
Compressor
Evaporator Fans
circulate cooling air
4
Figure 3Component location, rear of XDF
SELF-CONTAINED
AIRCOOLEDMODEL
Condenser air intakes,
perforated grilles
Product Description
Condenser fan
(removable to reduce
height temporarily)
Backup ventilation
damper (air exit)
Service access for
gauges to be inserted
for testing
Three-phase electrical
cord, 10 feet (3m)
Single-phase electrical cord,
10 feet (3m)
WATER/GLYCOL COOLED MODEL
Return Line
(1" female,
NPT)
Casters
Door handle
Rear door
Condensate drain
Stabilizing foot
(one of four)
Supply Line
(1" female, NPT)
Backup ventilation
damper (air exit)
Service access for
gauges to be inserted
for testing
Three-phase electrical
cord, 10 feet (3m)
Single-phase electrical cord,
10 feet (3m)
Door handle
Rear door
Condensate drain
Stabilizing foot
Casters
5
(one of four)
Figure 4Dimensional data, self-contained, air cooled model
34-1/8"
(867mm)
24-1/8"
Control
Side
2-1/2"
(64mm)
(2026mm)
Rack Section
(613mm)
79-3/4"
Product Description
82-1/4"
(2089mm)
36U
2-5/8"
(68mm )
FRONT
Cooling Section
9-5/16" (252mm)
Single -Phase Power Cord
Entrance ; factory-supplied ,
10' (3m) NEMA 5- 15P
3-Phase Power Cord
Entrance ; factory - supplied ,
10' ( 3m) NEMA L21-30P
Capped Service
Gauge Access
LEFT SIDE
24-3/8" to 32-11/32
(620-821mm)
mounting depth
49-1/2” (1257mm)
45-3/4”
(1162mm)
Backup
Ventilation
Air Outlet
4-1/2”
(114mm)
Cover
Plate
DETAIL A
Condensate Drain
Connection
6
Detail
Area
“A”
REAR VIEW
Figure 5Dimensional data, water/glycol cooled model
Rack Section
24-1/8"
(613mm)
79-3/4"
(2026mm)
2-5/8"
(68mm)
Cooling Section
9-5/16" (252mm)
Control
Side
5-1/2”
(139.7mm)
1.88”
(47.6mm)
7”
(177mm)
45-3/4”
(1162mm)
Product Description
6.95”
(176.5mm)
Backup
Ventilation
Air Outlet
FRONT
42U
4-1/2”
(114mm)
Detail
Area
“A”
REAR VIEW
Single -Phase Power Cord
Entrance ; factory-supplied ,
10' (3m) NEMA 5- 15P
3-Phase Power Cord
Entrance ; factory - supplied ,
10' ( 3m) NEMA L21-30P
Capped Service
Gauge Access
LEFT SIDE
24-3/8" to 32-11/32
(620-821mm)
mounting depth
49-1/2” (1257mm)
Cover
Plate
Condensate Drain
Connection
DETAIL A
7
Figure 6Dimensional data, all models—top, bottom and cable entry cutouts
Product Description
4-3/8"
(112mm)
4"
(102mm)
4-1/2"
(114mm)
B
TOP VIEW
A
15"
(381mm)
BOTTOM VIEW
Front
Cable
Entry
Cutouts
4-1/2"
(114mm)
Self-contained, air cooled model shown; water cooled unit
dimensions are identical; water cooled unit does not have
condenser fan.
3.1Standard Components—Self-Contained, Air Cooled and Water/Glycol Cooled
Models
3.1.1Frame
The self-contained, air cooled XDF is 82-1/4 inches (2089mm) tall; the water/glycol cooled unit, 79-3/4
(2026) tall. The self-contained, air cooled XDF has 36U (63 inches) of usable rack height. The
water/glycol cooled XDF has 42U (73-1/2 inches) of usable rack height. Both the self-contained, air
cooled and water/glycol cooled XDF units have a standard EIA rack width of 19 inches (483mm).
The XDF frame consists of heavy-duty, riveted, 12-gauge steel. The unit has fixed front rails and
adjustable rear rails with square holes for installing rack-mount equipment. The front and rear vertical frame members accommodate internal mounting rail options and provide space to route and manage cabling.
Cutouts in the top (front and rear) permit customer cable entry (Figure 6). All units have casters,
stabilizing feet and a grounding lug.
3.1.2Enclosure
The XDF is equipped with seals to maintain a separate air volume inside the equipment compartment.
NOTE
Preventing air infiltration into the XDF will significantly improve overall performance and
reduce the amount of condensate generated. Ensure that all cable entrances are sealed and that
doors are closed securely. Check to ensure that all panels are properly installed; this is
especially important if panels have been removed in the field.
3.1.3Doors
The front and rear doors are framed from sheet metal and are removable. A multi-point latch with
key lock is provided for security. The front door may be either solid sheet metal or have a Plexiglas
window for viewing installed equipment. The rear door is solid, full-height sheet metal.
3.1.4Side Panels
Side panels are constructed of sheet metal and use special fasteners to permit removal for maintenance. Insulation is included to provide improved thermal and sound insulation, as well as to prevent
condensate formation on the outside of the unit.
™
9
3.1.5Environmental Control
The XDF supplies cooling air—68°F to 77°F (20-25°C)—to electronic equipment in the rack-mount
equipment compartment.
In normal operation, six fans at the right front corner of the XDF circulate cooling air through the
equipment compartment. The laterally circulating air absorbs heat generated by the electronic equipment and transfers the heat to an evaporator coil at the right rear of the XDF. The heat is removed
differently in the self-contained, air cooled and water/glycol cooled units.
Heat Removal—Self-Contained, Air Cooled XDF
Heat removed from the self-contained, air cooled XDF cabinet is transferred to condenser coils at the
top of the XDF, in a section separated from the equipment compartment. The condenser fan on top of
the self-contained, air cooled XDF draws ambient air through the condenser coils and exhausts the
heat-laden air into the room.
Heat Removal—Water/Glycol Cooled XDF
The water/glycol cooled XDF transfers the heat captured by the evaporator coil to a brazed plate condenser at the top of the unit, also separate from the equipment compartment. That heat is then carried away by the cooling water or glycol to a condenser or drycooler.
Figure 7Cooling system components—self-contained, air cooled models
XDF Components
Condenser Fan
Condenser Coil
Condenser Air
Intake Vent for
Normal Operation
Backup Ventilation Intake
Vent (exhaust vent is on
rear)
Evaporator Coil (behind
damper) extracts heat
from circulated air
10
RearFront
Figure 8Cooling system components—water cooled models
Brazed Plate
Condenser
XDF Components
Coolant
Return Connection
Coolant
Supply
Connection
Backup Ventilation Intake
Vent (exhaust vent is on
rear)
Evaporator Coil
(behind damper)
extracts heat from circulated air
RearFront
11
3.1.6Control—Liebert’s iCOM Controller
The XDF is equipped with Liebert’s iCOM controller for all programming functions on the XDF. The
menu-driven, 128 x 64 dot matrix graphic display shows the status of the conditioned space, setpoints, alarm status and settings, event histories and the time.
Refer to 10.2 - iCOM Components and Functions and 10.3 - Navigating Through the iCOM Display for details or call 800-543-2778.
Figure 9XDF with iCOM controller
XDF Components
?
ESC
Liebert iCOM controller
12
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.