Emerson Liebert XDCF User Manual

Precision Cooling For Business-Critical Continuity™
Liebert® XDCF
User Manual–10kW / 2.8 Tons / 34,000 BTUh

SAVE THESE INSTRUCTIONS

CAUTION
!
Risk of piping and component rupture. May cause injury or equipment damage. Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of
piping. Do not close valves without follow recommended procedures for repair, maintenance and replacement of components. Installing pressure relief valves in field piping that may become isolated by service valves.

Fluorinated Greenhouse Gas Requirements—European Union

Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation also requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
TABLE OF CONTENTS
IMPORTANT SAFETY GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER
1.0 LIEBERT XDCF COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE . . . . . . . .1
2.0 GENERAL PRODUCT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Parts Included With Liebert XDCF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4 Product/System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5.1 Unit Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.6 Unpacking the Liebert XDCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6.1 Recyclable Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0 MECHANICAL CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Mounting Lower Liebert XDCF Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.3.1 Preparing the Lower Module for Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.3.2 Attaching Lower Liebert XDCF Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Attaching Upper Liebert XDCF Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.4.1 Preparing the Upper Module for Attachment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.4.2 Attaching Upper Liebert XDCF Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.0 PIPING CONNECTIONS AND PIPING ACCESS POINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.1 European Union Fluorinated Greenhouse Gas Requirements . . . . . . . . . . . . . . . . . . . . . . . 13
5.2 Connection Methods and Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2.1 Header System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3 Recommended Piping Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4 Connecting Liebert XD Flex Pipes to Liebert XDCF Modules. . . . . . . . . . . . . . . . . . . . . . . . 14
5.5 Connecting a Liebert XDCF with Liebert XD Flex Pipe to an Operational Liebert
XD System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.6 Disconnecting a Liebert XDCF With Liebert XD Flex Pipe From a Liebert XD System . . . 16
5.7 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.0 CHECKLIST FOR PROPER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.1 Fluorinated Greenhouse Gas Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
i
FIGURES
Figure 1 Liebert XDCF component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 3 Liebert XDCF hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 4 Unpacking the Liebert XDCF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5 Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Liebert XDCF unit mounting locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 7 Lower Liebert XDCF attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 8 Locator hole for lower unit stud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 9 Liebert XD Flex Pipe support panel attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Upper Liebert XDCF attachment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11 Attaching Liebert XD Flex Pipe retainers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12 Liebert XDCF supply and return piping access points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 13 Liebert XD prefabricated piping assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 14 Detail view of Liebert XD Flex Pipe and prefabricated piping port. . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 15 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe . . . . . . . . . . 16
Figure 16 Profile view of the Liebert XD system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 17 Piping mains without Liebert XDCF and Liebert XD Flex Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TABLES
Table 1 Branch piping sizes for refrigerant loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 2 Liebert XDCF specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
ii
Liebert XDCF Component Locations and Model Number Nomenclature

1.0 LIEBERT XDCF COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE

Figure 1 Liebert XDCF component locations

Mounting Bracket
Insulation Strip
Gasket along edge of deflector panel not shown for clarity
Top Deflector Panel (2 pieces)
Return Port Connection
Serial Ta g
Coil
Supply Port Connection
Bottom Deflector Panel 2 pieces)
Gasket along edge of deflector panel not shown for clarity
Front Grille
Positioning Stud
1

Figure 2 Model number nomenclature

Example: XD-CF10-BP—0
Liebert XDCF Component Locations and Model Number Nomenclature
XD 10 B 0
Liebert Xtreme
heat density system
CF
Module for
BladeFrame EX
P
Model Size Revision
T = Top
B = Bottom
P = Coupling
- = Domestic Packaging E = Export Packaging
level
2

2.0 GENERAL PRODUCT INFORMATION

The Liebert XDCF™ is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room.
Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts and needs no electricity.
The Liebert XDCF system consists of:
• Liebert XDCF modules—upper and lower models are available
• Liebert XD Flex Pipe (optional)—connects Liebert XDCF units to supply and return piping (ships with Liebert XDCF)
• Liebert XD Piping—delivers R-134a refrigerant through flexible piping
• Liebert XDP or Liebert XDC—supplies R-134a refrigerant to Liebert XDCF modules (see Liebert XDP or Liebert XDC user manual for required chiller or drycooler)
Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX the BladeFrame cabinet is exhausted through the Liebert XDCF, which absorbs the heat. The cooled air passes into the room and the heat is carried away by the Liebert XDCF’s R-134a refrigerant.

2.1 References

This document must be used together with site-specific documentation and documentation for other parts of the system.
General product information
cabinet. Heated air from

2.2 Parts Included With Liebert XDCF

• Installation manual (this document)
• Liebert XDCF module
• Mounting kit parts with the following items:
Lower Module Upper Module
Part Qty Part Qty
Lower mounting bracket 1 Top unit mounting angle 1
Top deflector panel (two-pieces)
Liebert XD Flex Pipe retainers 3 Liebert XD Flex Pipe retainers 3
10-32 screws 3 10-32 screws 2
10-32 nut 2 10-32 nut 1
Liebert XD Flex Pipe support panel 1

2.3 Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either rubber or plastic.
NOTE
The vapor barrier is the single most important requirement for maintaining environmental control in the conditioned space.
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site. Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.
1 Bottom deflector panel
(two-pieces)
1
3

2.4 Product/System Description

Upper and lower modules may be mounted on the rear of the Egenera BladeFrame. Each module, when attached to a fully loaded BladeFrame EX rack, has a nominal cooling capacity of 10kW (2.8 tons; 34,000 BTUh). Performance is based on:
• Entering fluid temperature—55°F (12.8°C) and
• Dew point—50°F (10°C) or lower.
The complete system consists of Liebert XDCF modules, piping and Liebert XDP or Liebert XDC (see Figure 3 below.

Figure 3 Liebert XDCF hydraulic diagram

General product information
To Chiller, Condenser or Drycooler
To Chiller, Condenser or Drycooler
Liebert XDC
or
Liebert XDP
Liebert XDC
or
Liebert XDP

2.5 Equipment Inspection

Upon arrival of the unit, and before unpacking it, verify that the labeled equipment matches the bill of lading. Inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your sales representative.
Pumped
Refrigerant
Pumped
Refrigerant
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Supply Lines
Return Lines
* Liebert XDCF, XDH, XDO or XDV
CAUTION
!
Risk of sudden refrigerant discharge! Can cause loss of charge and minor injury. Each Liebert XDCF unit is shipped with a full charge of R-134a refrigerant under pressure.
Do not remove the pipe caps or plugs before the unit is attached to an Egenera BladeFrame and ready for connection to Liebert XD Piping.
Supply and return fittings on the Liebert XDCF are one-shot connections. Do not disconnect one-shot connections after they have been connected. Disconnection will release pressurized R-134a refrigerant from the Liebert XDCF.

2.5.1 Unit Handling

When unpacking and handling the unit, exercise extra care to prevent damage.
If multiple Liebert XDCF units are delivered, they will be shipped on a pallet. A pallet jack will be required to move these units to the installation location. When using a pallet jack, ensure that it has the size and length needed for safe handling of the pallet.
4

2.6 Unpacking the Liebert XDCF

The unit is shipped in a protective package. Do not remove the packaging from the Liebert XDCF before it is at the installation location.
• When unpacking and handling the Liebert XDCF, care should be taken to prevent damaging the coils.
• Remove outer packaging when ready to install the Liebert XDCF.
• Do not use unit piping to lift or move the Liebert XDCF.

2.6.1 Recyclable Packaging

All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
CAUTION
!
Risk of sharp edges, splinters and exposed fasteners! Can cause personal injury! Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.
NOTICE
Risk of unit damage if improperly stored. Keep the unit indoors and protected from dampness, freezing temperatures and contact damage.
Figure 4 Unpacking the Liebert XDCF
General product information
R
3
Unit Ref.
1
3
1
5
2
Coil End Mounting Assembly
2
Notes
Area indicated on Item #3 (foam insert) is to be used
1. for hardware kit and/or unit manuals for shipping to customer. Coil end mounting assembly is to be wrapped in P/N 123783P1
2. (bubble) and placed into Item #2 (corrugated insert), only when