Precision Cooling
For Business-Critical Continuity™
Liebert® XDCF
User Manual–10kW / 2.8 Tons / 34,000 BTUh
™
IMPORTANT SAFETY GUIDELINES
SAVE THESE INSTRUCTIONS
CAUTION
!
Risk of piping and component rupture. May cause injury or equipment damage.
Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of
piping. Do not close valves without follow recommended procedures for repair, maintenance
and replacement of components. Installing pressure relief valves in field piping that may
become isolated by service valves.
Fluorinated Greenhouse Gas Requirements—European Union
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in
the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C,
R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits,
among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation also requires operators to use use all measures that are technically feasible and do not
entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas
during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
Liebert XDCF Component Locations and Model Number Nomenclature
1.0LIEBERT XDCF COMPONENT LOCATIONSAND MODEL NUMBER
NOMENCLATURE
Figure 1Liebert XDCF component locations
Mounting
Bracket
Insulation
Strip
Gasket along edge of deflector
panel not shown for clarity
Top Deflector Panel
(2 pieces)
Return Port
Connection
Serial
Ta g
Coil
Supply Port
Connection
Bottom Deflector
Panel 2 pieces)
Gasket along edge of deflector
panel not shown for clarity
Front
Grille
Positioning
Stud
1
Figure 2Model number nomenclature
Example: XD-CF10-BP—0
Liebert XDCF Component Locations and Model Number Nomenclature
XD10B0
Liebert
Xtreme
heat
density
system
CF
Module for
BladeFrame EX
P
Model SizeRevision
T = Top
B = Bottom
P = Coupling
- = Domestic Packaging
E = Export Packaging
—
level
2
2.0GENERALPRODUCTINFORMATION
The Liebert XDCF™ is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets
and equipment without exhausting heat into the room.
Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts
and needs no electricity.
The Liebert XDCF system consists of:
• Liebert XDCF modules—upper and lower models are available
• Liebert XD Flex Pipe (optional)—connects Liebert XDCF units to supply and return piping (ships
with Liebert XDCF)
• Liebert XD Piping—delivers R-134a refrigerant through flexible piping
• Liebert XDP or Liebert XDC—supplies R-134a refrigerant to Liebert XDCF modules
(see Liebert XDP or Liebert XDC user manual for required chiller or drycooler)
Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX
the BladeFrame cabinet is exhausted through the Liebert XDCF, which absorbs the heat. The cooled
air passes into the room and the heat is carried away by the Liebert XDCF’s R-134a refrigerant.
2.1References
This document must be used together with site-specific documentation and documentation for other
parts of the system.
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the
ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either
rubber or plastic.
NOTE
The vapor barrier is the single most important requirement for maintaining environmental
control in the conditioned space.
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly
controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site.
Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.
1 Bottom deflector panel
(two-pieces)
1
3
2.4Product/System Description
Upper and lower modules may be mounted on the rear of the Egenera BladeFrame. Each module,
when attached to a fully loaded BladeFrame EX rack, has a nominal cooling capacity of
10kW (2.8 tons; 34,000 BTUh). Performance is based on:
• Entering fluid temperature—55°F (12.8°C) and
• Dew point—50°F (10°C) or lower.
The complete system consists of Liebert XDCF modules, piping and Liebert XDP or Liebert XDC (see
Figure 3 below.
Figure 3Liebert XDCF hydraulic diagram
General product information
To Chiller,
Condenser
or Drycooler
To Chiller,
Condenser
or Drycooler
Liebert XDC
or
Liebert XDP
Liebert XDC
or
Liebert XDP
2.5Equipment Inspection
Upon arrival of the unit, and before unpacking it, verify that the labeled equipment matches the bill
of lading. Inspect all items for either visible or concealed damage. Damage should be immediately
reported to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your
sales representative.
Pumped
Refrigerant
Pumped
Refrigerant
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Liebert XD
Cooling Module *
Supply
Lines
Return
Lines
* Liebert XDCF,
XDH, XDO or XDV
CAUTION
!
Risk of sudden refrigerant discharge! Can cause loss of charge and minor injury.
Each Liebert XDCF unit is shipped with a full charge of R-134a refrigerant under pressure.
Do not remove the pipe caps or plugs before the unit is attached to an Egenera BladeFrame
and ready for connection to Liebert XD Piping.
Supply and return fittings on the Liebert XDCF are one-shot connections. Do not disconnect
one-shot connections after they have been connected. Disconnection will release pressurized
R-134a refrigerant from the Liebert XDCF.
2.5.1Unit Handling
When unpacking and handling the unit, exercise extra care to prevent damage.
If multiple Liebert XDCF units are delivered, they will be shipped on a pallet. A pallet jack will be
required to move these units to the installation location. When using a pallet jack, ensure that it has
the size and length needed for safe handling of the pallet.
4
2.6Unpacking the Liebert XDCF
The unit is shipped in a protective package. Do not remove the packaging from the Liebert XDCF
before it is at the installation location.
• When unpacking and handling the Liebert XDCF, care should be taken to prevent damaging the
coils.
• Remove outer packaging when ready to install the Liebert XDCF.
• Do not use unit piping to lift or move the Liebert XDCF.
2.6.1Recyclable Packaging
All material used to package this unit is recyclable. Please save for future use or
dispose of the material appropriately.
CAUTION
!
Risk of sharp edges, splinters and exposed fasteners! Can cause personal injury!
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.
NOTICE
Risk of unit damage if improperly stored. Keep the unit indoors and protected from dampness,
freezing temperatures and contact damage.
Figure 4Unpacking the Liebert XDCF
General product information
R
3
Unit Ref.
1
3
1
5
2
Coil End
Mounting Assembly
2
Notes
Area indicated on Item #3 (foam insert) is to be used
1.
for hardware kit and/or unit manuals for shipping to customer.
Coil end mounting assembly is to be wrapped in P/N 123783P1
2.
(bubble) and placed into Item #2 (corrugated insert), only when
packaging a specified bottom-mount unit.
3. Ref: Use P/N S-6060, or equivalent adhesive, to seal the top and
bottom of Item #1 (box) for shipping to the customer.
4. Refer to manufacturing work instructions for any additional
directions regarding packaging of this unit.
4
182713
5
3.0MECHANICAL CONSIDERATIONS
The Liebert XDCF is engineered to fit on the rear of the Egenera BladeFrame enclosure. Figure 5,
below, illustrates the unit’s dimensions and the location of pipes. Figure 6 shows the attachment
positions of each module.
Figure 5Overall dimensions
TIGHTEN FLEX PIPE
TO UNIT WITH THE
SCHRADER VALVE
RETURN
IN TH IS P O S ITIO N
R-134a
ONCE FLEX PIPE CONNECTIONS
ARE MADE TO THE UNIT DO NOT
DISASSEMBLE FROM THE UNIT.
REMOVE CONNECTIONS FROM
CEILING HEADERS BY TURNING
THE SUPPLY VALVE TO THE
OFF POSITION AND THEN TURNING
THE RETURN VALVE TO THE OFF
POSITION THE HEADER
CONNECTIONS MAY BE REMOVED.
TIGHTEN FLEX PIPE
SUPPLY
TO UNIT WITH THE
SCHRADER VALVE
1194311 P1
IN TH IS P O S ITIO N
3-3/4"
(95mm)
7-3/8"
(187mm)
1-5/8"
(41mm)
Mechanical Considerations
3-3/4"
(95mm)
Return
Pipe
13-3/8"
(340mm)
TOP
7/8" (22mm)
30-1/4"
(768mm)
1-5/8"
(41mm)
Upper unit shown;
both upper and
lower units have
same dimensions
Piping is not load-bearing
and should never be used
to lift or move the Liebert
XDCF
DISCHARGE
FRONT
SIDE
EMERSON
NETWORK POWER
TM
Liebert
XD
TM
BACK
RIGHT
SIDE
6
4.0INSTALLATION
4.1References
This document must be used together with site-specific documentation and documentation for other
parts of the system.
4.2Installation Considerations
Liebert XDCF modules must be securely mounted to the rear of the Egenera BladeFrame cabinet. No
cutting or drilling is required to attach the modules; all mounting holes, slots and pins required are
fabricated at the factory.
If only one Liebert XDCF will be attached to an Egenera BladeFrame cabinet, Liebert recommends
using the lower Liebert XDCF module. If both an upper and a lower Liebert XDCF module will be
attached, attach the lower unit first.
Liebert XDCF modules attach beside the power modules on the rear of the Egenera BladeFrame (see
Figure 6).
Figure 6Liebert XDCF unit mounting locations
Installation
7
4.3Mounting Lower Liebert XDCF Module
The lower Liebert XDCF module attaches to the Egenera BladeFrame cabinet with a mounting
bracket, four bolts and a metal stud.
Before the Liebert XDCF is mounted, the mounting bracket and a two-piece deflector panel must be
attached to its top surface and insulation must be applied to the left side.
4.3.1Preparing the Lower Module for Attachment
1. Position the mounting bracket over the two mounting holes. The holes are near the center of the
top of the Liebert XDCF module (see Figure 7).
2. Use two captive panel fasteners to attach the mounting bracket to the top of the Liebert XDCF
module. Tighten the fasteners securely, using a screwdriver, either a blade-type or Phillips.
3. Position the top deflector over the two mounting holes along the front edge of the top of the lower
Liebert XDCF module (see Figure 7). The flanges along the edge should be on the bottom.
4. Use two captive panel fasteners to attach the top deflector to the top of the lower Liebert XDCF
module.Tighten the fasteners securely, using a screwdriver, either a Phillips or a blade-type.
5. Position the second piece of the top deflector along the front edge of the deflector piece attached in
Steps 3 and 4, matching the mounting slots in the two pieces. The flanges along the edge should
be on the bottom.
6. Use two captive panel fasteners to connect the deflector pieces. Tighten the fasteners finger-tight,
leaving them loose enough to slide for good contact with the Egenera BladeFrame cabinet.
Figure 7Lower Liebert XDCF attachments
Slots in front piece
Captive nuts
for mounting
bracket, 2
of deflector permit
proper positioning
FRONT
Installation
Mounting bracket and
top deflector
attached
to unit
FRONT
LEFT
SIDE
Holes for attaching
top deflector
RIGHT SIDE
Positioning Stud
8
4.3.2Attaching Lower Liebert XDCF Module
Liebert XDCF modules mount on the rear of the Egenera BladeFrame cabinet, near the power modules. The cabinet and Liebert XDCF have prefabricated mounting holes and studs to ease mounting.
1. Set the lower Liebert XDCF module on the left side of the ledge on the rear of the Egenera
BladeFrame cabinet. Make sure the positioning stud on the bottom of the Liebert XDCF fits into
the locator hole on the ledge as shown in Figure 8.
Figure 8Locator hole for lower unit stud
Installation
Mounting
stud
for upper
CF unit
Mounting holes
for lower CF unit
Locator hole
for lower CFunit
bottom stud
2. Press the Liebert XDCF against the Egenera BladeFrame cabinet.
3. Insert a panel fastener into the mounting bracket and screw it into the captive panel nut in the
rear of the Egenera BladeFrame cabinet. For the hole locations, see Figure 6. Tighten the
fasteners securely with a screwdriver, either a blade-type or Phillips.
4. Secure the Liebert XDCF to the cabinet by inserting and tightening four screws along the right
side of the Liebert XDCF (see Figure 7).
5. Press the front section of the top deflector against the Egenera cabinet and tighten the panel
fasteners joining the two-piece deflector.
NOTE
If a lower module and an upper module will be attached to the Egenera cabinet, proceed to 4.4 Attaching Upper Liebert XDCF Module.
9
Attaching Liebert XD Flex Pipe Support Panel
Use of only the lower Liebert XDCF module requires attaching a Liebert XD Flex Pipe support panel
and three pipe retainers. The retainers keep the refrigerant pipes behind the Egenera cabinet. If an
upper Liebert XDCF module will be used, the Liebert XD Flex Pipe retainers will be attached to the
upper module.
To attach the Liebert XD Flex Pipe support panel:
1. Position the Liebert XDCF Liebert XD Flex Pipe support panel over the line of four holes above
the right edge of the lower Liebert XDCF module
2. Secure the Liebert XD Flex Pipe support panel to the cabinet by inserting and tightening four
screws on the panel’s flange. Tighten the fasteners securely with a screwdriver, either a Phillips
or a blade-type.
3. Attach the three pipe retainers:
a. Slip the front end of a retainer into a slot on the Liebert XD Flex Pipe support panel.
b. Insert a panel fastener into the retainer and thread it into the captive panel nut.
c.Tighten the fastener securely, using a screwdriver, either a blade-type or Phillips.
d. Repeat Steps a and c for the other retainers.
Figure 9Liebert XD Flex Pipe support panel attachment
Installation
Captive Panel
Fastener
Liebert XD
Flex Pipe
support
panel and
retainers
Lower
CF unit
Captive
Panel
Nut
Liebert XD
Flex Pipe
Support Panel
Liebert XD
Flex Pipe
Retainers
Captive
Panel
Nuts
Captive Panel
Fastener
10
4.4Attaching Upper Liebert XDCF Module
The upper Liebert XDCF module attaches to the Egenera BladeFrame cabinet with a mounting angle
and four bolts.
Before the Liebert XDCF is mounted, the mounting angle and a two-piece deflector panel must be
attached to the bottom of the Liebert XDCF and insulation must be applied to the left side.
4.4.1Preparing the Upper Module for Attachment
1. Position the mounting angle over the two mounting holes. The holes are near the center of the
bottom of the Liebert XDCF module (see Figure 7).
2. Use two captive panel fasteners to attach the mounting angle to the bottom of the Liebert XDCF
module. Tighten the fasteners securely, using a screwdriver, either a blade-type or Phillips.
3. Position the bottom deflector over the two mounting holes along the front edge of the bottom of
the upper Liebert XDCF module (see Figure 10). The flanges along the edge should be on the top
side.
4. Use two captive panel fasteners to attach the bottom deflector to the bottom of the upper Liebert
XDCF module. Tighten the fasteners securely with a screwdriver, either a Phillips or a bladetype.
5. Position the second piece of the bottom deflector along the front edge of the deflector piece
attached in Steps 3 and 4, matching the mounting slots in the two pieces. The flanges along the
edge should be on the top side.
6. Use two captive panel fasteners to connect the deflector pieces. Tighten the fasteners finger-tight,
leaving them loose enough to slide for good contact with the Egenera BladeFrame cabinet.
Figure 10 Upper Liebert XDCF attachment
Installation
Coil
Bottom
Deflector
Bracket
TOP VIEW
7-5/16"
(186mm)
3-9/16"
(90mm)
1-7/16"
(37mm)
Pipe support brackets
not shown for clarity
1-7/16"
(37mm)
Right Side
View
3-9/16"
(90mm)
Captive
panel
fasteners
Gasket not shown
for clarity
Mounting
Angle
11
4.4.2Attaching Upper Liebert XDCF Module
S
The upper Liebert XDCF module mounts on the rear of the Egenera BladeFrame cabinet, above the
lower Liebert XDCF module. The cabinet and Liebert XDCF have prefabricated mounting holes and
studs to ease mounting.
1. Attach the mounting angle to the bottom of the Egenera BladeFrame cabinet with a 10-32 nut
that fits onto the stud on the back of the cabinet, see Figure 6).
2. Hang the upper Liebert XDCF module on the top of the Egenera BladeFrame cabinet, using the
overhanging front edge of the Liebert XDCF. The bottom should rest on the mounting angle
attached in Step 1.
3. Hold the Liebert XDCF against the Egenera cabinet.
4. Insert a panel fastener into the mounting angle and screw it into the captive panel nut in the rear
of the Egenera BladeFrame cabinet. Tighten the fasteners securely with a screwdriver, either a
Phillips or a blade-type.
5. Secure the Liebert XDCF to the cabinet four captive panel fasteners along the right side of the
Liebert XDCF For the hole locations, see Figure 6.
6. Press the front section of the bottom deflector against the Egenera cabinet and tighten the panel
fasteners joining the two-piece deflector.
Liebert XD Flex Pipe retainers must be attached to the upper Liebert Liebert XDCF module to keep
the refrigerant pipes positioned behind the Egenera cabinet.
Installation
To attach the three retainers to the upper Liebert XDCF module:
1. Slip the front end of a Liebert XD Flex Pipe retainer into a slot on the right side of the Liebert
XDCF.
2. Insert a panel fastener into the retainer and thread it into the captive panel nut.
3. Tighten the fastener securely with a screwdriver, either Phillips or a blade-type.
4. Repeat Steps 1 and 3 for the remaining retainers
Refer to site specific drawings for general locations of the piping connections. For Liebert XDCF connection locations, refer also to Figure 12.
5.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas),
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to
recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.
5.2Connection Methods and Points
The assembly and connection means used for piping in the Liebert XD system are the same as those
used in conventional refrigeration systems. Observe all standard practices during installation and
startup to prevent damage and contamination.
Supply piping connection is 1/2" OD copper pipe, and return piping connection is 5/8" OD copper. Both
supply and return fittings are one-shot connections. These fittings contain pressurized R-134a refrigerant inside the Liebert XDCF.
CAUTION
!
Risk of sudden refrigerant discharge! Can cause loss of charge and minor injury!
Do not disconnect one-shot connections after they have been connected. Disconnection will
release pressurized R-134a refrigerant from the Liebert XDCF.
The Liebert XDCF has supply and return piping access on the top of each module.
5.2.1Header System
The Liebert XDCF module system requires use of the Liebert XD prefabricated piping assembly. The
prefabricated piping is compatible with the Liebert XD Flex Pipe required to attach to the Liebert
XDCF modules.
Figure 12 Liebert XDCF supply and return piping access points
Return Pipe
(5/8" diameter)
7-5/16"
(186mm)
3-9/16"
(90mm)
Pipe locations and
dimensions are the same
for upper and lower units
1-7/16"
Supply Pipe
(1/2" diameter)
For additional information, refer to the Liebert Xtreme Density System Design Manual, SL-16655.
13
(37mm)
Piping Connections and Piping Access Points
5.3Recommended Piping Size
Connect the main pipes between the Liebert XDCF branch piping and the Liebert XDP or Liebert
XDC according to Table 1. Elbows and restrictions must be minimized to get good fluid flow.
Connect the branch pipes between the main piping and the Liebert XDCF according to Table 1.
Table 1Branch piping sizes for refrigerant loop
Pipe FunctionSize / Equivalent Pipe Length
Liebert XDP/Liebert XDC supply line, from
Liebert XDP/Liebert XDC supply
to farthest Liebert XDCF
Liebert XDP/Liebert XDC return line, from
farthest Liebert XDCF to Liebert XDP/Liebert
XDC return
From Liebert XDCF supply to supply line of
Liebert XDP/Liebert XDC
From Liebert XDCF return to return line of
Liebert XDP/Liebert XDC
1-1/8" OD (1.025" ID) for lengths up to 60 feet (18m)
1-3/8" OD (1.265" ID) for lengths over 60 but less than 175 feet (18 to 53m)
2-1/8" OD (1.985" ID) for lengths up to 60 feet (18m)
2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet (18 to 53m)
1/2" OD (0.430" ID) for lengths up to 6 feet (1.8m)
5/8" OD (0.545" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)
5/8" OD (0.545" ID) for lengths up to 6 feet (1.8m)
7/8" OD (0.785" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)
5.4Connecting Liebert XD Flex Pipes to Liebert XDCF Modules
1. Remove the caps on the supply and return lines on the top of the Liebert XDCF.
2. Lubricate the threads, diaphragm and O-ring with one or two drops of mineral oil.
3. Connect the line-set coupling finger-tight.
4. Make sure the Schrader valve is properly oriented; refer to the label on the top of the Liebert
XDCF.
5. Hold the backup hex nut with a wrench while tightening the swivel nut.
6. Tighten the swivel nut on the female coupling until it is seated or a definite resistance is felt.
7. Once a definite bottoming resistance is felt (as in metal to metal), place a mark lengthwise from
the swivel nut to the backup hex and tighten the swivel nut on the female coupling an additional
1/4 turn.
8. Tighten both the supply fittings and the return fittings to 35-45 ft/lb (47-61Nm).
9. Mark the female and male coupler with for future reference.
5.5Connecting a Liebert XDCF with Liebert XD Flex Pipe to an Operational Liebert XD
System
NOTE
Before connecting the Liebert XDCF with Liebert XD Flex Pipe to the prefabricated piping
mains, check the entire system for leaks.
Check the Liebert XDCF to ensure that the unit has no refrigerant leaks.
Read all instructions before beginning installation.
Tools Required
• Two adjustable wrenches, with a maximum adjustment size of 2-1/2 inches
• Screwdriver, Phillips or blade type
NOTE
This operation requires two people.
1. Determine the port location of the supply and return piping overhead
2. Make sure the service valve for each port is closed
3. Remove cap for only the required ports. Do not remove caps from the unused ports.
4. Once Step 3 has been completed, remove the pipe plugs that are supplied on the Liebert XD Flex
5. Thread the return couplers together, the larger of the two couplers (Liebert XD Flex Pipe and
return main).
6. Use one of the adjustable wrenches to hold the fixed side of the female coupler on the Liebert
XDCF stationary. With the other adjustable wrench, tighten the collar onto the coupler.
Tighten these only until the force required to tighten abruptly increases. See Figure 14.
NOTICE
Do not overtighten the couplers. Overtightening of couplers will damage the couplers.
Figure 14 Detail view of Liebert XD Flex Pipe and prefabricated piping port
Service Valve
Note:
Make sure the valve
Tighten collar
ith wrench.
DO NOT
OVERTIGHTEN!
Supply Side Torque Range for
1/2" coupler is 22.1 to 25.8 lb/ft (30-35Nm)
Return Side Torque Range for
1" coupler is 59 to 62.7 lb/ft (80-85Nm)
7. Repeat Steps 5 and 6 for the smaller coupler (supply line).
is closed before attaching
flex pipe to the system.
Hold threaded coupler here
with a wrench to keep the
pipe stationary while tightening
collar with another wrench.
Flex Pipe
8. Once the supply and return connections are completed, open the return service valve, then open
the supply service valve.
With the equipment running, cool air is discharged from the back of the Liebert XDCF.
15
Piping Connections and Piping Access Points
Figure 15 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe
Return Service Valve
Make sure valve is
open after system
leak check
Supply Service Valve
Make sure valve is
open after system
leak check
Return
Main
Supply Main
Return Flex pipe
Supply Flex Pipe
5.6Disconnecting a Liebert XDCF With Liebert XD Flex Pipe From a Liebert XD
System
NOTE
Before uninstalling a Liebert XDCF with Liebert XD Flex Pipe from the prefabricated piping
mains: Close the supply service valve, wait approximately two minutes, then close the return
service valve.
Read all instructions before beginning.
Tools Required
• Two adjustable wrenches, maximum adjustment size of 2-1/2 inches
• Phillips head #2 screwdriver
1. Close the service valve in the supply line to the Liebert XDCF (smaller coupler).
2. Close the service valve in the return line to the Liebert XDCF (larger coupler).
3. Locate and have at the ready the caps and plugs for both ends of the supply and return couplers.
4. Loosen the female supply coupler from the male supply coupler (smaller coupler). This requires
two adjustable wrenches. Refer to Figure 14.
5. The Liebert XDCF side of the female coupler must be held stationary while the collar on the
coupler is being loosened. Refer to Figure 14.
6. Disconnect the coupler.
16
Figure 16 Profile view of the Liebert XD system
Piping Connections and Piping Access Points
Service
Valve
Return
Line
7. Place the protective dust cap and plug back onto both ends of the coupler on the Liebert XDCF
and the port pipe.
Figure 17 Piping mains without Liebert XDCF and Liebert XD Flex Pipe
Supply
Line
8. Repeat Steps 5 through 7 for the return coupler (larger coupler).
9. Carefully lay the Liebert XD Flex Pipe aside.
NOTICE
Do not fold or bend Liebert XD Flex Pipe. Kinks in the tubing can cause permanent damage to
the Liebert XD Flex Pipes.
10. Carefully unbolt the Liebert XDCF from the cabinet.
11. Place the Liebert XDCF on a stable surface.
5.7Insulation
To minimize the possibility of condensation, insulate all piping between the Liebert XDCF and the
Liebert XDP or Liebert XDC.
17
6.0CHECKLISTFOR PROPER INSTALLATION
___ 1. Liebert XDCF modules are securely attached to the cabinet.
___ 2. Piping from Liebert XDP or Liebert XDC, with isolation valves, properly connected to each
Liebert XDCF module.
___ 3. Flex piping connections to prefabricated header assembly are secure and according to
specifications.
___ 4. Check the R-134a refrigerant charge.
___ 5. System checked for leakage.
___ 6. Run system and verify that the Liebert XDP or Liebert XDC and the Liebert XDCF modules
operate properly.
___ 7. Piping is insulated.
Checklist for Proper Installation
18
7.0MAINTENANCE
Minimal maintenance is required to keep the Liebert XDCF operating at optimal levels. The unit
should be cleaned and checked for damage. Suggested maintenance includes:
• Cooling fins—Clean any dust and debris from the cooling fins, taking care not to bend them.
7.1Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas),
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to
recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
Height – including pipe connections31-3/8" (797mm)
Weight, lb (kg)
Pipe connections
Refrigerant supply
from Liebert XDP/Liebert XDC
Refrigerant return
to Liebert XDP/Liebert XDC
Cabinet exterior finishGray
Agency
Specifications
XD-CF-10-TPE-0, XD-CF Top EXP
XD-CF-10-TP-0, XD-CF Top
XD-CF-10-BPE-0, XD-CF BTM EXP
XD-CF-10-BP-0, XD-CF BTM
55°F (13°C) entering fluid temperature,
50°F (10°C) or lower dew point
Width13-7/16" (341mm)
Depth7-5/16" (186mm)
Unit only18 (8.2)
Shipping30 (13.6)
1/2" threaded one-shot coupling on the unit
5/8" threaded one-shot coupling on the unit
SafetyCSA, CE Approved
20
NOTES
Specifications
21
Specifications
22
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.