Emerson Liebert Vertiv RDU-SIC G2 User Manual

Contents
Chapter 1 Product Description ............................................................................................................................................ 1
1.1 Components Description ....................................................................................................................................... 1
1.2 Main Functions...................................................................................................................................................... 2
1.3 Technical Specifications ....................................................................................................................................... 3
1.3.1 Environment Specifications ....................................................................................................................... 3
1.3.2 Performance Specifications ....................................................................................................................... 3
Chapter 2 Hardware Installation .......................................................................................................................................... 4
2.1 Installation Preparation ......................................................................................................................................... 4
2.1.1 Notes ......................................................................................................................................................... 4
2.1.2 Ambient Requirements .............................................................................................................................. 5
2.2 Installing RDU-SIC G2 Card ................................................................................................................................. 5
Chapter 3 Web Page Of RDU-SIC G2 ................................................................................................................................ 6
3.1 Login Preparation .................................................................................................................................................. 6
3.1.1 Checking IP Address Connectivity ............................................................................................................. 6
3.1.2 Checking Browser Version ........................................................................................................................ 6
3.1.3 Checking Browser Setting ......................................................................................................................... 6
3.2 Log In RDU-SIC G2 ............................................................................................................................................ 10
3.2.1 Login Page .............................................................................................................................................. 10
3.2.2 Forgetting Password ................................................................................................................................ 10
3.3 Homepage Of RDU-SIC G2 ................................................................................................................................ 11
3.3.1 Time Calibrating Link ................................................................................................ ............................... 12
3.3.2 Clearing Time-Out ................................................................................................................................... 12
3.3.3 Logout...................................................................................................................................................... 12
3.3.4 Real-Time Alarm Pop-Up Setting ............................................................................................................ 12
3.4 Menu Items ......................................................................................................................................................... 12
3.4.1 Device Information ................................................................................................................................... 13
3.4.2 Safe Shutdown ........................................................................................................................................ 14
3.4.3 Alarm Management ................................................................................................................................. 16
3.4.4 Data & History ......................................................................................................................................... 19
3.4.5 Device Options ........................................................................................................................................ 21
3.4.6 System Options ....................................................................................................................................... 26
3.4.7 Help ......................................................................................................................................................... 33
Chapter 4 Maintenance ..................................................................................................................................................... 35
4.1 Restoring Default Setting .................................................................................................................................... 35
4.2 FAQ .................................................................................................................................................................... 35
Appendix 1 Glossary ......................................................................................................................................................... 37
Appendix 2 Standard Configuration List ............................................................................................................................ 38
Chapter 1 Product Description 1
Chapter 1 Product Description
The RDU-SIC G2 card is a network management card. It can make the intelligent equipment (such as UPS, PDU, air conditioner and so on) developed by Vertiv have the capacity of network communication. The RDU-SIC G2 card can also connect to the environment monitoring equipment, including IRM series temperature & humidity sensor or dry contact signal input & detecting sensors. In case of an equipment alarm, it notifies the user by multiple ways: recording, sending a Trap message, sending an E-Mail or sending an SMS.
The RDU-SIC G2 card can meet the requirements of TCP/IP, RS232/485 networking modes and can be flexibly configured according to various application conditions.
This chapter expounds the components description, main functions and technical specification.
1.1 Components Description
The appearance and ports of the RDU-SIC G2 card are shown in Figure 1-1.
Figure 1-1 Appearance and ports of RDU-SIC G2 card
Console port
The RDU-SIC G2 card supplies a console port (USB port, see Figure 1-1 for its position), which adopts USB communication mode. Short pin 2 and pin 3 of jumper J20. The communication parameters are given in Table 1-1.
Table 1-1 Communication parameters of console port
Parameter
Baud rate
Bit
Parity
Stop bit
Value
115200bps
8 bits
None
1 bit
USB port
The RDU-SIC G2 card supplies one USB-A type socket port for connecting USB Modem of designated model. Short pin 1 and pin 2 of jumper J20. Its position is shown in Figure 1-1.
Ethernet port
1)
RDU-M
2)
SMTP
3)
NSM management system
4)
Web browser
RS485 port
1)
PDU
2) Air conditioner
3)
UPS
4)
IRM sensor
USB port
1)
Connecting USB Modem
2) Equipment console port
RS485 port
1)
PDU
2) Air conditioner
3)
UPS
RS485/RS232 port
1)
PDU
2) Air conditioner
3)
UPS
2 Chapter 1 Product Description
Network port
The RDU-SIC G2 card provides one network port which adopts 10/100M Base-T self-adaptable Ethernet port. Its position is shown in Figure 1-1. See Table 1-2 for default configuration of the network port.
Table 1-2 Default configuration parameters of the network port
Parameter
Network card
IP address
Subnet mask
Default gateway
Default parameter
192.168.0.252
255.255.255.0
192.168.0.1
COM port
The RDU-SIC G2 card supplies three independent COM ports. Their positions are shown in Figure 1-1. The port adopts RS-485 communication mode; the gold finger adopts RS-485/232C (adaptive) communication mode.
See Table 1-3 for the communication parameters.
Table 1-3 Communication parameters of COM port
Parameter
Baud rate
Bit
Parity
Stop bit
Value
1200bps, 2400bps, 4800bps, 9600bps,
19200bps (optional)
5 ~ 8 bits
Even/Odd/None/Mark/Space
1 ~ 2 bits
Note: The combination mode of 5-bit word size and 2-bit stop bit is not supported
1.2 Main Functions
The main functions of RDU-SIC G2 card are listed in Table 1-4.
Table 1-4 Main functions of RDU-SIC G2
Main function
Description
Device monitoring
Realizing camera viewing in data center; getting and handling the data of different intelligent devices and controlling them through Web interface
Safe shutdown Shutdown
schedule
Configure the maintenance policy of the UPS, and can periodically reboot or close the supervised UPS
Sever shutdown
Used together with the NetworkShutdown software. When the UPS has certain critical alarm, the system will notify the server shutdown to avoid the sever going down
Alarm Management
Current alarm
Displaying alarm in real time, and confirming the current alarm
History alarm
Querying the history alarm
Alarm notification
1. Can be customized according to user requirements, that is, alarm notification content can be customized;
2. You can choose the communication mode to receive alarm information of different level from different equipment;
3. The communication mode includes Email, SMS and phone;
4. Email supports SSL function;
5. Supplying alarm test function to test whether or not users have received the alarm notification information;
6. Sending the system running status periodically according to user configuration
Data & History Device information
Querying the main data of equipment
History data
Querying the history data
History log
Querying the log data
Clear history
Clearing the history data and log data
Device Options Device management
1. Can add, modify and delete equipment actively, and support adding four pieces of intelligent equipment at most;
2. Can install and uninstall equipment type and support connecting third party equipment Note: The default installed equipment cannot be deleted and modified
Signal setting
Modifying equipment name and alarm level online
Batch configuration
Updating and downloading configuration files and system files
Chapter 1 Product Description 3
Main function
Description
System Options
Monitoring unit
Collecting the system information of RDU-SIC G2
Network setting
1. Setting the network information such as IP, subnet mask, gateway and DNS;
2. Controlling whether the upper monitoring system (RDU-M manager) can visit the RDU-SIC G2;
3. Remote service setting
User management
Adding, modifying and deleting user information
Date/time setting
Calibrating the real time clock of RDU-SIC G2
Restore system
Rebooting the RDU-SIC G2 and restoring default configuration
Site setting
Modifying site information online
System upgrade
Upgrading the application program online
System title
Setting title and logo picture at the top of the Web page
Help
About RDU-SIC G2
Displaying serial number, identify code and software version, and supplying links for downloading user manual and tool software
1.3 Technical Specifications
1.3.1 Environment Specifications
See Table 1-5 for the environment specifications of RDU-SIC G2.
Table 1-5 Environment conditions
Item
Requirement
Application location
Usually in data center or computer room, with air conditioner
Working temperature
-10ºC ~ +60ºC
Relative humidity
5%RH ~ 95%RH, no condensing
Working environment
Dust: compliant with the indoor requirements of GR-63. No corrosive gas, flammable gas, oily mist, steam, water drops or salt
Air pressure
70kpa ~ 106kpa
Storage temperature
-40ºC ~ +70ºC
Cooling
Natural cooling
Power distribution network
TT/TN
Protection level
IP20
1.3.2 Performance Specifications
See Table 1-6 for the performance specifications of RDU-SIC G2.
Table 1-6 Performance specifications
Connected component
Cable standard
Connected distance
(unit: m)
Connected number /
connection point
Connecting nodes of COM ports
Standard category 4 twisted-pair cable
≤ 100
Three Intelligent devices
8 test points
[1]
of Sensor
Note: [1]: The RDU-SIC G2 can connect intelligent devices through COM1 or COM2. The connected devices of single COM cascade cannot exceed two
4 Chapter 2 Hardware Installation
Chapter 2 Hardware Installation
This chapter expounds the hardware installation of the RDU-SIC G2.
2.1 Installation Preparation
2.1.1 Notes
When installing RDU-SIC G2, take the following precautions to avoid personnel injury and device damage by accident.
Always cut off the power before performing any installation operation on the RDU-SIC G2 Ensure that the external devices are connected to the correct ports of the RDU-SIC G2 Wear an ESD-proof glove during installation Arrange the wires properly, and do not put any heavy objects on the wires or stamp the wires
The jumper locations of the RDU-SIC G2 card are shown in Figure 2-1.
Jumper J18
Jumper J20
Figure 2-1 Jumper locations of the RDU-SIC G2 card
Make sure that the jumpers of RDU-SIC G2 card are set to correct position. See Table 2-1 for the jumper setting of the RDU-SIC G2 card.
Table 2-1 Jumper setting of the RDU-SIC G2 card
Working mode
Jumper setting
Description
Maintenance mode
J20 J18
The USB port is used to login the RDU-SIC G2 card through Hyper Terminal (TTY)
Normal mode
J20 J18
The USB port is used to connect to the SMS Modem
Reset mode
J18
When you forget the password of rduadmin, password of Web system administrator admin and IP address, set the jumpers according to this mode, reboot the RDU-SIC G2 card, and wait more than 20s to recover the above three parameters to be default values. After successful resetting, you must set the jumpers according to the normal mode to avoid resetting the user setting again after rebooting the RDU-SIC G2 card
Chapter 2 Hardware Installation 5
The jumper setting of the RDU-SIC G2 card is normal mode by default.
2.1.2 Ambient Requirements
Operation environment
The RDU-SIC G2 must be installed indoor. Refer to Table 1-5 for specific requirement.
ESD-proof
To make the static electricity reduce to zero, you must take measures as follows:
Keep proper temperature and humidity in the data center (see Table 1-5). Wear the ESD-proof gloves and work clothes before contacting with the PCB. If there are not ESD-proof gloves
and work clothes, wash hands with water and dry them.
Immunity
Take the following measures for immunity:
Keep the working ground of RDU-SIC G2 away from earthing device of electricity device or SPD earthing device Keep away from the radio-transmitting station, radar transmitter and high-frequency large-current device Use the electromagnetic shielding method if necessary
2.2 Installing RDU-SIC G2 Card
1. Set the jumpers of the RDU-SIC G2 card according to Table 2-1.
2. Insert the RDU-SIC G2 card into position along the guide grooves on both sides of the intellislot intelligent slot, and tighten the screws.
3. Open the power device. At this point, if the RUN indicator (yellow) of the RDU-SIC G2 card turns on, it indicates that the RDU-SIC G2 card is starting up.
6 Chapter 3 Web Page Of RDU-SIC G2
Chapter 3 Web Page Of RDU-SIC G2
This chapter introduces how to log in the RDU-SIC G2 through Web browser and relevant functions of the RDU-SIC G2.
3.1 Login Preparation
To ensure that the RDU-SIC G2 page function can be normally used, please refer to this section for selecting and setting browser options.
3.1.1 Checking IP Address Connectivity
Before logging in RDU-SIC G2 through Web, please first confirm the IP address of RDU-SIC G2, and test its connectivity. Refer to Q5 in 4.2 FAQ for the test method.
3.1.2 Checking Browser Version
For the best user experience, the recommended browser is Internet Explorer, its version includes: IE8, IE9, IE10 or IE11; you can also use other pop web browsers, such as Chrome, Firefox.
3.1.3 Checking Browser Setting
Checking IE General setting
Double-click the icon of IE to run the software, click the menus of Tools -> Internet Options, then click the Settings button on the General tab, and select Every time I visit the webpage for Check for newer versions of stored pages, as shown in Figure 3-1.
Figure 3-1 General setting
Checking IE proxy setting
1. Double-click the icon of IE to run the software, click the menus of Tools -> Internet Options and then choose the Connections tab to pop up the window shown in Figure 3-2.
Chapter 3 Web Page Of RDU-SIC G2 7
Figure 3-2 Choosing the Connections tab
2. In the window shown in Figure 3-2, click the button LAN Settings to pop up the window shown in Figure 3-3.
Figure 3-3 LAN setting
3. Consult the network manager of your area, ask if you need to set a proxy server and get the configuration method. If there is no need to set a proxy server, do not tick any option.
Checking IE security setting
1. Double-click the icon of IE to run the software, click the menus of Tools -> Internet Options and then choose the Security tab to pop up the window shown in Figure 3-4.
8 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-4 Security setting 1
2. In the window shown in Figure 3-4, choose Local intranet and click the Custom level button to pop up the window shown in Figure 3-5.
Figure 3-5 Security setting 2
3. In the window shown in Figure 3-5, set Medium-low for the security level. Click the Reset button to finish Reset custom settings, at last, click OK.
4. In the window shown in Figure 3-6, set Enable for File download.
Chapter 3 Web Page Of RDU-SIC G2 9
Figure 3-6 Enabling file download
5. In the window shown in Figure 3-7, set Enable for Initialize and script ActiveX controls not marked as safe for scripting.
Figure 3-7 Enabling ActiveX controls
6. In the window shown in Figure 3-8, add the IP address of the RDU-SIC G2 into the trusted site list.
10 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-8 Adding trusted sites
3.2 Log In RDU-SIC G2
3.2.1 Login Page
1. Open the IE browser, and enter the IP address of the RDU-SIC G2 in the address box, the login page will appear, as shown in Figure 3-9. If the login page does not appear, refer to Q5 in 4.2 FAQ.
Crystal blue Ocean blue
Figure 3-9 Login page of RDU-SIC G2
2. On the login page, select a preferable theme by clicking or : means crystal blue; means ocean blue, as shown in Figure 3-9.
3. Type the username and password (default username: ‘admin’, default password: Vertiv), and click the Login button, the homepage will appear, as shown in Figure 3-11.
3.2.2 Forgetting Password
If you forget the password, click the Forget Password button on the login page, and the screen will display the page of getting password, as shown in Figure 3-10.
Chapter 3 Web Page Of RDU-SIC G2 11
Figure 3-10 Page of getting password
Type your username, and click the Submit button, your password will be sent to the email box or phone which you have configured before. Clicking the Return button cancels the operation.
Note
1. Only when you have correctly configured the email and SMS parameters on the SMS and Email Server Configuration page can you receive the password sent by the system. Refer to Alarm Notification in 3.4.3 Alarm Management for detailed setting method.
2. The gotten password is a random new password generated by the system; please modify the password after logging in the system successfully.
3.3 Homepage Of RDU-SIC G2
After successful login, the homepage of RDU-SIC G2 is displayed by default, as shown in Figure 3-11.
1
2 34 5
6
8
10
9
7
1. Menu item
2. Controllable status
3. Current number of every level alarm
4. System title
5. Logo
6. [User] Logout
7. Function display area
8. Real-time alarm displaying list
9. Alarm pop-out setting
10. Time calibrating link
Figure 3-11 Homepage of RDU-SIC G2
12 Chapter 3 Web Page Of RDU-SIC G2
3.3.1 Time Calibrating Link
The lower left part displays the system time of RDU-SIC G2. Clicking the RDU-SIC G2 time will jump to the time calibrating page. For detailed operation, refer to Date/Time Setting in 3.4.6 System Options.
3.3.2 Clearing Time-Out
When there is no operation on the page within 15min, the page will become uncontrollable, as shown in Figure 3-12.
Figure 3-12 Controllable status
Click [Clear] Time-out, the input box shown in Figure 3-13 will appear. After typing the password, the controllable status will become normal after about 5s.
Figure 3-13 Password verification
3.3.3 Logout
Click the Logout at the upper right corner of the homepage, the prompt box shown in Figure 3-14 will appear, clicking OK will log out safely.
Figure 3-14 Logout
3.3.4 Real-Time Alarm Pop-Up Setting
The real-time alarm displaying list is contracted on the bottom of the page by default. You can perform the following operation by referring to Figure 3-11:
1. Click Display Current Alarms manually, and the real-time alarm displaying list will pop up;
2. Tick Auto Pop-out, and the real-time alarm displaying list will pop up when an alarm is generated;
3. Tick Alarm Sounds, and the system will play alarm sound through the browser when an alarm is generated.
3.4 Menu Items
On the homepage of RDU-SIC G2, the menu items include Device Info, Safe Shutdown, Alarm Management, Data&History, Device Options, System Options and Help.
Chapter 3 Web Page Of RDU-SIC G2 13
3.4.1 Device Information
Click the Device Info menu in the left, the submenus will appear. When you click the specific device, the right part will display the relative information of the device, including Sampling, Control, Setting and Alarm.
Note
ENV in Device Info is a dummy device, which indicates all temperature sensors and temperature & humidity sensors connected to RDU-SIC G2.
Sampling
Clicking the Sampling tab can enter the sampling page, which displays sampling signals of selected device, as shown in Figure 3-15.
Figure 3-15 Sampling signals
If some signal is in alarm status, it will be displayed in red.
Control
Clicking the Control tab can enter the control page, which displays control signals of selected device, as shown in Figure 3-16.
Figure 3-16 Control signals
Click the Set button to control the device. Setting
Clicking the Setting tab can enter the setting page, which displays setting signals of selected device, as shown in Figure 3-17.
Figure 3-17 Setting signals
14 Chapter 3 Web Page Of RDU-SIC G2
You can set several signals at the same time, and at most 16 signals can be set at the same time for each time.
Alarm
Clicking the Alarm tab can enter the alarm page, which displays alarm signals of selected device, as shown in Figure 3-18.
Figure 3-18 Alarm signals
You can set alarm level of several alarm signals at the same time, and at most 16 signals can be set at the same time for each time.
3.4.2 Safe Shutdown
On the RDU-SIC G2 homepage, click the Safe Shutdown menu on the left, two submenus appear, including
Shutdown Schedule and Server Shutdown. Shutdown Schedule Click Shutdown Schedule under the Safe Shutdown menu, the page shown in Figure 3-19 pops up.
Figure 3-19 Shutdown Schedule page
The Shutdown Schedule page is used to add, delete and modify schedule shutdown task of UPS devices. As shown in Figure 3-19, type a task name of schedule shutdown in the field of Task Name, select a Target
Equipment, select whether to enable the task in the Status field, select ShutDown Mode and Open Mode, and then add Open Time according to the corresponding prompt, the page is shown in Figure 3-20.
Figure 3-20 Schedule shutdown task list
Chapter 3 Web Page Of RDU-SIC G2 15
Click the Add Schedule Shutdown button, the task will be successfully added. As shown in Figure 3-21, a new task has been added in the schedule shutdown task list. The tasks in the task list will be executed automatically according to their Enable/Disable status.
Figure 3-21 Schedule shutdown task list
The descriptions about the RDU-SIC G2 schedule shutdown function are as follows:
1. When the Open Mode is set to Do Not Open Device or Open Device At Once, the Open Time cannot be set, and it is displayed as --;
2. The format of ShutDown Time changes with different options of ShutDown Mode automatically, as shown in Figure 3-22.
Figure 3-22 Format of shutdown time
Note
1. The RDU-SIC G2 can support up to ten shutdown tasks.
2. Only when Enable Device is set for Status can the schedule shutdown task be enabled.
Server Shutdown
Click Server Shutdown under the Safe Shutdown menu, the Server Shutdown page will pop up, as shown in Figure 3-23.
Figure 3-23 Server Shutdown page
On the Server Shutdown page, you can add and delete server shutdown task.
16 Chapter 3 Web Page Of RDU-SIC G2
The procedures for adding a server shutdown task are as follows:
1. Select a UPS from the drop-down box of UPS Name;
2. In the Server IP field, type the IP address of the server to be closed;
3. Click the Add button, the server shutdown task is added, and the basic information of the UPS will be displayed in the upper list of the page
Note
If you want to use the server shutdown function, please install Vertiv network shutdown software in the server.
The procedures for deleting a server shutdown task are as follows:
Select the task to be deleted in the server shutdown task list, and click the Delete button to finish the operation.
3.4.3 Alarm Management
The Alarm Management menu supplies alarm centralized management function, enabling you of self-defining alarm notification and alarm linkage rules, and viewing historic alarm.
On the RDU-SIC G2 homepage, click the Alarm Management menu on the left, three submenus appear, including
Current Alarm, History Alarm and Alarm Notification. Current Alarms
Click Current Alarms under the Alarm Management menu, or refer to 3.3.5 Real-Time Alarm Pop-Up Setting, the current alarm list will pop up, as shown in Figure 3-24.
Figure 3-24 Current alarms
1. You can click the tabs above the alarm list to view current alarms according to alarm levels.
2. Click the Acknowledge button to confirm the alarm. After conformation, no alarm notification about the conformed alarm will be sent.
3. When the mouse is located on the Confirmed link, the alarm confirming information will be hovered; when you move the mouse, the information will disappear, as shown in Figure 3-25.
Figure 3-25 Confirming information
History Alarm
Click History Alarm under the Alarm Management menu to look over historical alarm records. Select a device (for instance, All Devices) and set the start time and end time (for instance, from 2015-04-24 00:00:00 to 2015-04-24 23:59:59). Then click the Query button, all alarm records generated between the start time and end time will be listed,
Chapter 3 Web Page Of RDU-SIC G2 17
including: Index, Device Name, Signal Name, Alarm Level, Trigger valve, Start Date/Time, Confirmed by, Confirmed on Date/Time and End Date/Time, as shown in Figure 3-26.
Figure 3-26 History alarm query
Click the Download button to download the query results. Alarm Notification
1. User Alarm Notification Configuration Click the Alarm Notification under the Alarm Management menu, the page shown in Figure 3-27 pops up. You can
choose the notification method to receive notification of chosen level alarm from chosen equipment, meanwhile, you can also choose the language of alarm notification information and customize the alarm content (including Equip name, Alarm description, Alarm TIME and Alarm state by default).
Click the Save button to finish the alarm configuration. When an alarm is generated, the system will notify users through the chosen notification method.
Note
1. Users must tick the notification method first in the Notification by check boxes, and then the alarm table below can be edited;
2. When all devices are chosen, all devices will be configured with the same alarm level;
3. When low level alarm is chosen, the alarm level above this level will also be chosen;
4. When some device is chosen, the highest level Critical Alarm will be chosen by default.
Figure 3-27 User alarm notification configuration
2. SMS And Email Server Configuration Click the Alarm Notification under the Alarm Management menu, and then click the SMS And Email Server
Configuration tab, the page shown in Figure 3-28 pops up.
18 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-28 SMS/Email server configuration
On the page shown in Figure 3-28, you can perform SMS Modem Configuration for alarm notification reminding through SMS or phone, you can also perform Email Server Configuration for alarm notification reminding through email, the procedures are as follows:
SMS Modem Configuration
1) Connect an SMS Modem through USB port according to need, and choose Port Type, the page will display Parameter automatically;
2) Choose SMS Modem (GPRS/CDMA) according to the SMS Modem type;
3) Set the communication parameter of the SMS Modem;
4) Click the Save Configuration button to save the configuration of current users SMS Modem. Note
If the SMS Modem is connected through USB port, you need to set the jumper by referring to Table 2-1.
Email Server Configuration
1) Type the server IP address or domain name in the Email Server field;
2) Type the Server Port, Email User, Email Password and Sender Email Address in the corresponding fields;
3) Click the Save button to save the configuration of current users Email server. Note
1. The Server Port is 25 by default. When SSL is chosen, the Server Port will become 465 automatically;
2. The Email User is RDU-A’ by default;
3. When using SSL, you need to ensure that the Email server supports SSL function.
3. Scheduled Notification Configuration Click the Alarm Notification under the Alarm Management menu, and then click the Scheduled Notification
Configuration tab, the page shown in Figure 3-29 pops up.
Chapter 3 Web Page Of RDU-SIC G2 19
Figure 3-29 Scheduled notification configuration
Note
1. Scheduled notification configuration must be used together with user alarm notification configuration; otherwise, you cannot select User Name, Notification by and Language Type;
2. For scheduled notification configuration, the notification method Phone’ is not supported;
3. The scheduled notification means sending the running state of the RDU-SIC G2 system (normal or alarm) to the user.
1) First of all, on the User Alarm Notification Configuration page, complete and save the setting of User, Notification by and Language Type.
2) On the Scheduled Notification Configuration page, set the Notification Enabled Period (setting range: 8:00 ~ 20:00), Notification Scheduled Cycle (default: Hour), Interval of Notification (default: 1) and Send Time Setting (default: start time).
3) Click the Save button to save the system notification configuration.
3.4.4 Data & History
The Data & History menu supplies query service of all types of historical data and logs for the user. On the RDU-SIC G2 homepage, click Data & History in the left part, four submenus appear, including: Device
Information, History Data, History Log and Clear History. Device Information
Click the Device Information under the Data & History menu, the page shown in Figure 3-30 pops up. The page includes two tabs: Device Information List and Export SNMP MIB.
1. Device Information List As shown in Figure 3-30, the page lists the main information of all equipment. Click the Download button to download
the query result.
Figure 3-30 Device information list
20 Chapter 3 Web Page Of RDU-SIC G2
2. Export SNMP MIB As shown in Figure 3-31, you can export MIB information according to device type. After selection, click the Download
button to export MIB information.
Figure 3-31 Export SNMP MIB
History Data
Click the History Data under the Data & History menu, the page shown in Figure 3-32 pops up. The page has two tabs: History Data and Historical Curve.
Figure 3-32 History data
1. History Data As shown in Figure 3-32, choose a device (for instance, All Devices) and the log type (for instance, History Data),
and set the start time and the end time (for instance, from 2014-07-30 00:00:00 to 2014-07-30 23:59:59). Then click the Query button, all the history data during the time will be listed, click the Download button to download the query result.
2. Historical Curve As shown in Figure 3-33, choose a device (for instance, ENV) and the query type (for instance, Temp2), and set the
start time and the end time (for instance, from 2014-07-30 00:00:00 to 2014-07-30 23:59:59). Then click the Show Curve button, if history data are queried, a historical curve of the signal will be shown.
Chapter 3 Web Page Of RDU-SIC G2 21
Figure 3-33 Historical curve
History Log Click the History Log under the Data & History menu, the page shown in Figure 3-34 pops up.
Figure 3-34 History log
On the page shown in Figure 3-34, choose the log type (for instance, Control Log) and set the start time and the end time (for instance, from 2014-07-30 00:00:00 to 2014-07-30 23:59:59). Then click the Query button, all control logs during the time will be listed, click the Download button to download the query result.
Note
When the log type is selected as System Log or Driver Log, after clicking the Query button, the query result will not be displayed on the page, instead, it will be directly downloaded as a zip file.
3.4.5 Device Options
On the RDU-SIC G2 homepage, click Device Options in the left part, three submenus will appear, including Device
Management, Signal Setting and Batch Configuration. Device Management
1. Add/Modify/Delete Device Click the Device Management under the Device Options menu, the page shown in Figure 3-35 pops up.
22 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-35 Add/modify/delete equipment
As shown in Figure 3-35, you can add/modify/delete a new device, the procedures are as follows:
Adding a new device
1) Choose the device type in the Device Type textbox;
2) Type the device name in the Device Name textbox, or use the default device name;
3) After the device type is chosen, the drop-down box of Port will list the default port number(s) of the device type automatically; if the device type is not chosen, the port number cannot be chosen;
4) Type the device address, which must be numbers from 1 to xx, in the Device Address textbox. The device addresses under the same port number must be different; for some device types, you need not type the device address, at this point, the Device Address textbox turn gray and cannot be edited. When one kind of device has many models, you need to type the model ID, which must be numbers from 1 to xx. The model IDs under one kind of device must be different;
5) Choose or type the device location;
6) Type the communication parameter in the Parameter textbox. In the event that the device type is certain, the communication parameter prompt information will appear in the Parameter textbox, including the communication parameter format and default communication parameter of the equip type;
7) Click the Add button, the page shown in Prompt information 1 in Figure 3-36 pops up, at the same time, a piece of new device information will be added in the device list;
8) Click the Save Configuration button, the page shown in Prompt information 2 in Figure 3-36 pops up;
Prompt information 1
Prompt information 2
Figure 3-36 Prompt information
If clicking the Cancel button, the added equipment fails; if clicking OK, the dialog box of Security authentication pops up, as shown in Figure 3-13.
9) Type the login password of current user, and click OK. The reboot page pops up, as shown in Figure 3-37;
Chapter 3 Web Page Of RDU-SIC G2 23
Figure 3-37 Reboot page
After the system reboots, adding a device becomes effective.
10) Log in the RDU-SIC G2 webpage again and the added device will appear in the list on device management page. Note
Up to four intelligent devices (excluding RDU-SIC G2 itself) can be added in the system by default.
Deleting a device
1) Choose the device which needs to be deleted in the device list;
2) Click the Delete button to delete the device;
3) Click the Save Configuration button to make the settings become effective, and the detailed procedures are the same as those of adding a new device.
Note
Before clicking the Delete button, if the device information has been modified, it cannot be deleted.
Modifying a device
1) Choose the device which needs to be modified in the device list;
2) Modify the device information;
3) Click the Modify button to make the setting effective;
4) Click the Save Configuration button to make the settings become effective, and the detailed procedures are the same as those of adding a new device.
After adding, modifying or deleting procedures, if you leave the Add/Modify/Delete Device page without clicking the Save Configuration button to make the settings effective, the prompt information will pop up to remind you of saving the configuration, as shown in Figure 3-38.
Figure 3-38 Prompt information 3
Note
Clicking the Save Configuration button can save all the operations at one time.
2. Install/Uninstall Device Type Click the Device Management under the Device Options menu, and then click the Install/Uninstall Device Type tab,
the page shown in Figure 3-39 pops up.
24 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-39 Install/Uninstall Device Type
Click the Browse button to download configure package (file format of .iru) from local content, and click the Install button to install the new device type.
Note
The device type number supported by the system is related to the system remaining memory and the size of driver configuration package, but the number cannot exceed 64.
The page displays the installed device type information in the lower right part. Click the Uninstall button, the confirming dialog box pops up, as shown in Figure 3-40.
Figure 3-40 Confirming dialog box
Click OK, the dialog box of Security authentication pops up, as shown in Figure 3-13, type the login password of current user, and click OK to uninstall the corresponding equipment type.
Note
1. While installing device type, if the device type exists and the device driver has a higher version than the driver to be added, it cannot be installed repeatedly;
2. If the installation pack has no version information, or the version information does not match the software version, the device type cannot be installed.
2. If some device uses the device type, the Uninstall button becomes gray, displaying Using, and the device type cannot be uninstalled.
Signal Setting
Click the Signal Setting under the Device Options menu, the page shown in Figure 3-41 pops up.
Chapter 3 Web Page Of RDU-SIC G2 25
Figure 3-41 Modify device name
On the page shown in Figure 3-41, you can modify the device name. Type the new device name and click the Set button to make all setting effective.
Note
The characters of device name and signal name can be English letters, digits, space and underline. If other characters are typed, the prompt box shown in Figure 3-42 will pop up.
Figure 3-42 Prompt box of invalid characters
Batch Configuration Click the Batch Configuration under the Device Options menu, the page shown in Figure 3-43 pops up.
Figure 3-43 Batch configuration
On the page, you can perform Upload and Download operations to complete batch configuration. Note
1. Only admin has the authority of batch configuration. If you fail in performing batch configuration, please click Show Help to view the help information.
2. The batch configuration file is encrypted after downloaded to local.
26 Chapter 3 Web Page Of RDU-SIC G2
3.4.6 System Options
On the RDU-SIC G2 homepage, click the System Options menu in the left part, eight submenus appear, including:
Monitoring Unit, Network Setting, User Management, Date/Time Setting, Restore System, Site Setting, System Upgrade and System Title.
Monitoring Unit
The Monitoring Unit is used to set the signals of RDU-SIC G2 system, including Sampling, Setting and Alarm signals, the page is shown in Figure 3-44.
Figure 3-44 Monitoring unit (Sampling)
As for the operation method of the three tabs of Sampling, Setting and Alarm on the Monitoring unit page, refer to
3.4.1 Device Information. Note
On the Setting tab, if you set Blocked for Outgoing Alarm Blocked, when an alarm occurs, it will be blocked, in this case:
1. For current alarms, the page only displays the alarm signals, but not send alarm notifications; after the alarm disappears, it will not be saved in history alarm;
2. The Blocked setting for Outgoing Alarm Blocked will be automatically cleared in 24h.
Network Setting
1. IP Setting Click the Network Setting under the System Options menu, the page shown in Figure 3-45 pops up.
Figure 3-45 IP setting
On the page shown in Figure 3-45, you can configure the network parameters, such as IP addressing mode, IP, Mask, GateWay, DNS1 (Preferred DNS server) and DNS2 (Alternate DNS server). After modifying the network parameters, click the Save button to make the setting effective.
Note
After modifying the IP address, the system will jump to the new IP address by default. You must use the new IP address to re-login the RDU-SIC G2.
2. Access Management
Chapter 3 Web Page Of RDU-SIC G2 27
Click the Network Setting under the System Options menu, and then click the Access Management tab, the page shown in Figure 3-46 pops up.
Figure 3-46 Access management
In the event of adding visitor, in the textbox of IP Address of RDU Manager, type the new IP address of the RDU manager, and click the Add Visitor button to finish the configuration.
Note
1. Up to three RDU manager IP addresses can be added in the system.
2. In the event of adding visitor, if you select to use an agent, you also need to configure the agent server.
3. SNMP Configuration Click the Network Setting under the System Options menu, and then click the SNMP Configuration tab, you can
configure SNMP agent. The RDU-SIC G2 system supports V2 and V3 versions of SNMP agent. As shown in Figure 3-47, the specific setting method of SNMP V2 is as follows:
1) Set NMS IP (host IP address of SNMP agent data receiving end);
2) Set Trap Level: Enable or disable;
3) Keep defaults for other items.
Figure 3-47 SNMP V2 setting
As shown in Figure 3-47, the specific setting method of SNMP V3 is as follows:
1) Set NMS IP (host IP address of SNMP agent data receiving end);
2) Set the Trap Level: Enable or disable;
3) Set the Name;
28 Chapter 3 Web Page Of RDU-SIC G2
4) Set the User Type: Authenticated & Encrypted, Authenticated & Not Encrypted, Not Authenticated & Not Encrypted;
5) Select Authentication Protocol: MD5, SHA;
6) Select Privacy Protocol: DES;
7) Self-define Authentication Password and Privacy Password. Note
1. On the base of SNMP V2, SNMP V3 adds user authentication and privacy strategies.
2. If you select Not Authenticated & Not Encrypted for User Type, the drop-down boxes of Authentication Protocol and Privacy Protocol will become gray, so you cannot set them;
3. Currently, only DES is supported for Privacy Protocol.
4. You need to self-define Authentication Password and Privacy Password, which contain at least 8 characters, and be the same as the password set by the host of SNMP agent data receiving end, or it cannot be decrypted and received.
After parameter setting, click the Add button to add NMS; If you need to modify NMS setting, select the NMS which needs to be modified, modify the setting and then click the
Modify button to save the setting; If you need to delete NMS, select the NMS which needs to be deleted, and then click the Delete button to delete the
NMS.
Figure 3-48 SNMP V3 setting
4. Remote Service Click the Network Setting under the System Options menu, and then click the Remote Service tab, the page shown
in Figure 3-49 pops up.
Chapter 3 Web Page Of RDU-SIC G2 29
Figure 3-49 Remote service setting
The remote service setting includes three parts: Request RDU remote, Cancel RDU remote and Replace Host. Meanwhile, you can set the communication parameters of remote service system.
Request RDU remote: used to establish remote service relationship
1) Type the self-defined customer name in the End-User textbox;
2) Choose the contactor for remote service in the Contact Person textbox, when the contactor is chosen, the corresponding mobile and email will be displayed;
Note
The contactor for remote service must be set through System Options -> User Management in advance, and you must provide the mobile or email, or the service request cannot be conducted. Refer to User Management in this section for detailed setting method.
3) Choose Frequency of Reporting: Monthly, Seasonal;
4) Click OK to send the remote service request. Cancel RDU remote: used to cancel the established remote service
Choose Cancel RDU remote and click OK to send a command to cancel the current remote service. Note
Canceling the remote service is effective only under the precondition that the remote service has been established, otherwise, a prompt of failure will pop up after you click OK.
Replace Host: used to replace the local host during remote service
When the host that has established remote service need to quit, but you want to remain the established remote service relationship, you need to replace the local host to participate in the remote service. The detailed setting method is the save as Request RDU remote, besides, type the hardware serial number of the replaced host.
User Management
Click the User Management submenu under the System Options menu, the page shown in Figure 3-50 pops up.
30 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-50 User management
On the page shown in Figure 3-50, you can add user, modify user and delete user.
Add user
1. Type username in the User Name textbox;
2. Choose the user authority;
3. Configure the user password, which cannot be vacant and should contain at least six letters or digits.
4. Re-type the password in the Confirm textbox;
5. (Optional) Type the user telephone number, which can use the following digits and characters: 0123456789, +;
6. (Optional) Type the email address;
7. Click the Add button, the dialog box of Security authentication pops up, as shown in Figure 3-13. Type the login password of current user, and click OK to add a new user.
Note
The characters of username can only be English letters, digits, -, and _. In addition, the initial characters must be letters or digits.
Delete user
1. Choose the user which needs to be deleted in the username list;
2. Click the Delete button to pop up the confirming dialog box, as shown in Figure 3-51.
Figure 3-51 Confirming dialog box
3. Click OK, the dialog box of Security authentication pops up, as shown in Figure 3-13. Type the login password of current user, and click OK to delete the chosen user.
Note
The user of admin cannot be deleted.
Modify user
1. Choose the user which needs to be modified in the username list;
2. Modify the user information;
3. Click the Modify button, the dialog box of Security authentication pops up, as shown in Figure 3-13. Type the login password of current user, and click OK to make the modified user information effective.
Users who access RDU-SIC G2 can be divided into four user groups, and they have different security level and user authority, see Table 3-1 for detailed information.
Chapter 3 Web Page Of RDU-SIC G2 31
Table 3-1 User security level
Security level
User group
User authority
Level A
Browser
All users can browse equipment information
Level B
Operator
The operators can send control command to intelligent equipment
Level C
Engineer
The engineers can get the following access: Send control command to intelligent equipment; Browse, control and modify parameters; Download files; Modify user information of their own
Level D
Administrator
The administrator can get full access: Send control command to intelligent equipment; Brows, control and modify parameters; Upload and download files; Modify, add and delete user information; AC teamwork parameter setting; System upgrade
On the page shown in Figure 3-50, choose the current user, you can perform SMS/Phone Test and Email Test. Before using the test function, users need to configure the SMS/Email server of current user, refer to Alarm Notification
in 3.4.3 Alarm Management for details.
SMS/Phone Test
Type the phone number in the Phone field, and click the SMS/Phone Test button to test that the telephone number of current user can be gotten through. If users receive the test SMS and telephone, the test is successful; if not, the test fails, please check that the telephone number is correct and the SMS Modem is properly connected.
Email Alarm Notify Test
Type the email address in the Email field, and click the Email Test button to test that the email address of current user is correct. If users receive the test email, the test is successful; if not, the test fails, please check that the information above is correctly typed.
Note
When adding and modifying user, you must type the phone number or the email address, or the setting cannot be completed.
Date/Time Setting
Clicking the Date/Time Setting under the System Options menu can synchronize the time. On the page shown in Figure 3-52, RDU-SIC G2 can get time from the time servers automatically. Type IP address in the Primary Server textbox and Secondary Server textbox in sequence, type a figure in Interval to calibrate system time textbox, select the Time zone and Calibrating Protocol, and then click the Set button to make the setting effective.
Figure 3-52 Date/time setting
The RDU-SIC G2 can also get the local time. Choose Specify Date/Time, click the Local Host Time button to get the local time, and then click the Set button to make the new time effective.
Note
Time calibration adopts Specify Date/Time by default.
Restore System
Click the Restore System under the System Options menu, the page shown in Figure 3-53 pops up.
32 Chapter 3 Web Page Of RDU-SIC G2
Figure 3-53 Restore System
Click the Reboot RDU-SIC G2 button to reboot the system. Click the Restore System button to restore all the default settings.
Note
If you use the restore function, the RDU-SIC G2 may lose the original configuration solution. After the restore operation, make sure to wait two minute for the RDU-SIC G2 conducting complete initializing work before re-accessing it through Web.
Site Setting Click the Site Setting under the System Options menu, the page shown in Figure 3-54 pops up.
Figure 3-54 Site information setting
On the page shown in Figure 3-54, you can modify the site information of RDU-SIC G2, including Site Name, Site Location and Site Description.
System Upgrade
Click the System Upgrade under the System Options menu, the page shown in Figure 3-55 pops up.
Chapter 3 Web Page Of RDU-SIC G2 33
Figure 3-55 System upgrade
On the page shown in Figure 3-55, click the Browse button to download configure pack (.rdu file format) from the local catalogue, and then click the Install button to upgrade the system.
Note
The RDU-SIC G2 supports incremental upgrading function.
System Title Click the System Title under the System Options menu, the page shown in Figure 3-56 pops up.
Figure 3-56 Title setting
As shown in Figure 3-56, you can replace the Logo picture in the upper right part by uploading system Logo picture. Click the Browse button, choose the needed Logo picture and click the Upload button to upload the file to RDU-SIC G2. Only [.gif], [.bmp], [.jpg] and [.png] format pictures are allowed, and the picture size should be less than 500K. Clicking the Default button can restore the default Logo picture.
You can also modify the system title Welcome at the top of the page. Type the customized title in the System Title textbox and click OK to make it effective.
3.4.7 Help
On the RDU-SIC G2 homepage, click the Help menu in the left part, one submenu appears: About RDU-SIC G2.
34 Chapter 3 Web Page Of RDU-SIC G2
The About RDU-SIC G2 page displays Software Version, Serial Number and Identify Code of RDU-SIC G2, as shown in Figure3-57.
Figure 3-57 About RDU-SIC G2
Chapter 4 Maintenance 35
Chapter 4 Maintenance
This chapter expounds the maintenance of RDU-SIC G2, including restoring default setting and FAQ.
4.1 Restoring Default Setting
Restoring default setting can be finished through two modes: software or hardware. For software restoring, refer to Restore System in 3.4.6 System Options. Hardware restoring includes restoring admin password (default username: admin, password: Vertiv) and IP address
of RDU-SIC G2 (the default IP address is 192.168.0.252). You can short pin2 and pin3 of jumper J18 on the RDU-SIC G2 card to complete hardware restoring. The jumper position is shown in Figure 4-1.
Jumper J18 amplified
Figure 4-1 Position of jumper J18
4.2 FAQ
Q1: After RDU-SIC G2 is powered on, why the power indicator is not on? A: Please check that the power cable is connected correctly. Q2: How to deal with that the communication of COM port is abnormal? A: Check that the COM ports on the RDU-SIC G2 and the expansion card are RS-232/RS-485 adaptive ports; please
ensure that the communication parameters are correctly configured. Q3: How to deal with that there is no access to RDU-SIC G2 login page when the RDU-SIC G2 communication is
normal? A: There are three measures to solve the problem: Step 1: Ensure that the IP address is correct;
1. Please ensure that the network cable is connected to the correct port.
2. Ensure that the IP address of RDU-SIC G2 is 192.168.0.252.
Step 2: Ensure the connectivity of IP address. To ensure the connectivity of IP address, you can use PING/ping command, and the method is as follows:
1) Click the icon at the lower left corner, and type cmd in the textbox, as shown in Figure 4-2.
36 Chapter 4 Maintenance
Figure 4-2 Typing cmd
2) Press the Enter key, the page shown in Figure 4-3 pops up. Type ping and IP address in the command line (for instance, ping 10.163.162.135 ) and check whether the communication is successful.
Figure 4-3 Communication test
Step 3: If the above-mentioned steps cannot handle the problem, please use the jumper cap on the card to restore default IP. Refer to Table 2-1 for the use of jumper cap.
Step 4: Refer to 3.1 Login Preparation to complete relevant operations. Q4: You have chosen the ocean blue theme, but the page still adopts crystal blue theme while you are viewing the
webpage of the RDU-SIC G2, how to deal with it? A: Click the [User] Logout button to return the login page, click the icon to choose the ocean blue theme, and log
in the system again. Q5: After an alarm is generated, you do not receive any email or SMS notification; or when the alarm does not finish,
the email or SMS notification is less than three times, how to deal with it? A: Please perform troubleshooting according to the following procedures:
1) Please check that the SMS/Email server configuration is correct, refer to Alarm Notification in 3.4.3 Alarm Management.
2) If you do not receive the SMS notification, please check that the phone is out of service because of overdue payment;
3) If you do not receive the email notification, please click the menu Data & History -> History Log to query the system log and check whether there is a record of failure in sending email. If so, it indicates that the network is busy or the email server communication is busy.
Appendix 1 Glossary 37
Appendix 1 Glossary
AC
Alternating Current
CA
Critical Alarm
DC
Direct Current
DI
Digital Input
IE
Internet Explorer, a Web browser developed by Microsoft@
FAQ
Frequently Asked Questions
FTP
File Transfer Protocol, used to transfer large chunks of data
HTML
Hypertext Mark-Up Language, used to create Web pages
HTTP
Hypertext Transfer Protocol, used to convey HTML
LED
Light Emitting Diode
Linux
A UNIX-like operating system with open source, developed under Free Software Foundation (FSF)
LLP
Local Language Package
LUI
Local User Interface
MA
Moderate Alarm
NA
No Alarm
LA
Low Alarm
38 Appendix 2 Standard Configuration List
Appendix 2 Standard Configuration List
No.
Description
Number
Unit
1
RDU-SIC G2 intelligent port monitoring card
1
EA
2
User manual- RDU-SIC G2 Card User Manual (V1.1, Chinese & English Version)-16mo-Glue Binding
1
EA
3
Whole set cable -UH52SA1SL2-UH52SA1Z UPS USB cable -ROHS
1
EA
4
Whole set or other labels – certificate label
1
EA
Appendix 3 Hazardous Substance or Elements Announcement 39
Appendix 3 Hazardous Substance or Elements
Announcement
Parts
Hazardous Substances
Plumbum
Hydrargyrum
Cadmium
Chrome
PBB
PBDE
Pb
Hg
Cd
Cr6+
PBB
PBDE
PCBA × ○ ○ ○ ○ ○
Cables × ○ ○ ○ ○ ○
○: Means the content of the hazardous substances in all the average quality materials of the part is within the limits specified in SJ/T-11363-2006; ×: Means the content of the hazardous substances in at least one of the average quality materials of the part is outside the limits specified in SJ/T11363-2006
Vertiv Tech Co., Ltd. has been committed to the design and manufacturing of environment-friendly products. It will reduce and eventually eliminate the harzardous substances in the products through unremitting efforts in research.
About Environment Protection Period: The Environment Protection Period of the product is marked on the product. Under normal working conditions and normal use of the products observing relevant safety precautions, the hazardous substances in the product will not seriously affect the environment, personnel safety or property in the Environment Protection Period starting from the manufacturing date.
Applicable product: RDU-SIC G2