Emerson Liebert UPStation GXT2U User Manual

Page 1
AC Power Systems For Business-Critical Continuity™
Liebert® UPStation GXT2U
User Manual - 230V, 700-3000VA
Page 2
Page 3
TABLE OF CONTENTS
1.0 IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . 1
2.0 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . 3
3.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.1 Transient Voltage Surge Suppression (TVSS)
and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . 5
4.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.4 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.5 DC to DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.7 Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.3 Rack-Mount UPS Conversion and Installation . . . . . . . 9
5.4 External Battery Cabinet Installation . . . . . . . . . . . . . 13
6.0 CONTROLS AND INDICATORS . . . . . . . . . . . . . . . . . . . 14
6.1 ON/Alarm Silence/Manual Battery Test Button . . . . . 14
6.2 Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . 15
6.3 Load/Battery Level Indicators (4 Green, 1 Amber) . . . 15
6.4 Fault Indicator LED (Red). . . . . . . . . . . . . . . . . . . . . . . 15
6.5 Bypass Indicator LED (Amber) . . . . . . . . . . . . . . . . . . . 15
6.6 UPS ON Indicator LED (Green) . . . . . . . . . . . . . . . . . . 15
6.7 Battery Indicator LED (Amber). . . . . . . . . . . . . . . . . . . 16
6.8 AC Input Indicator LED (Green). . . . . . . . . . . . . . . . . . 16
6.9 Output Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . 16
i
Page 4
7.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 17
7.1 Normal Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . 17
7.2 Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.3 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . 18
7.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.1 Communications Interface Port. . . . . . . . . . . . . . . . . . . 19
8.2 Pins 4 & 5 - Remote Shutdown on Battery . . . . . . . . . . 19
8.3 Pins 5 & 6 - Any-Mode Shutdown . . . . . . . . . . . . . . . . . 20
8.3.1 Auto-Enable Output . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.3.2 Pin 6 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.4 UPS Intelligent Communications . . . . . . . . . . . . . . . . . 21
9.0 CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . 22
9.1 Liebert UPStation GXT2U Configuration Program
Abilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.1.1 What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.1 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.1.1 Internal Battery Replacement Procedures . . . . . . . . 24
11.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . 25
12.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12.1 Battery Cabinet Specifications . . . . . . . . . . . . . . . . . . . 32
13.0 BATTERY RUN TIMES. . . . . . . . . . . . . . . . . . . . . . . . . 33
13.1 Product Warranty Registration. . . . . . . . . . . . . . . . . . . 34
ii
Page 5
Important Safety Instructions
1.0 IMPORTANT SAFETY INSTRUCTIONS
WARNING
!
Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, installation, and operating instructions before operating the Uninter­ruptible Power System (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Individuals without previous training can install and operate this equipment.
It is not intended for use with life support and other designated “criti­cal” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly earthed (grounded), 50 Hz or 60Hz, 230V supply (programmable for 200, 208, 220, 230, and 240VAC output). Installation instructions and warning notices are located in this manual.
ELECTROMAGNETIC COMPATIBILITY—The Liebert UPStation GXT2U 2004/108/EC and the published technical standards. Continued com­pliance requires installation in accordance with these instructions and use of manufacturer approved accessories only.
Operate the UPS in an indoor environment only in an ambient tem­perature range of 0°C to +40°C (32°F to +104°F). Install it in a clean environment, free from conductive contaminates, moisture, flammable liquids, gases and corrosive substances.
Series complies with the requirements of the EMC directive
WARNING
!
This UPS should not be supplied from electrical power systems of the “IT” (Impedance á Terre) type (IEC 364 - Electrical Installation of Buildings).
1
Page 6
Important Safety Instructions
This UPS contains no user serviceable parts except the internal bat­tery pack. The UPS ON/Standby push buttons do not electrically iso­late internal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indi­cations are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unau­thorized personnel away from the batteries. PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners, laser printers or hairdryers.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
2
Page 7
2.0 GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Glossary of Symbols
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON
Standby
3
Page 8
Introduction
3.0 INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera­tions, cause data loss, or even damage equipment. The Liebert UPSta­tion GXT2U protects equipment from these disturbances.
The Liebert UPStation GXT2U comes in nominal power ratings of 700, 1000, 1500, 2000 and 3000 VA. Complete model specifications appear at the end of this manual (see 12.0 - Specifications).
The Liebert UPStation GXT2U is a compact, “on-line” UPS. An on-line UPS continuously conditions and regulates its output voltage, whether mains power is present or not. It supplies connected equip­ment with clean sinewave power. Sensitive electronic equipment oper­ates best from sinewave power.
For ease of use, the Liebert UPStation GXT2U features a light-emit­ting diode (LED) display to indicate either load percentage or battery capacity depending upon the mode of operation. It also provides self­diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of alarms when the unit is operating on battery.
The Liebert UPStation GXT2U has an interface port for communica­tion between the UPS and a network server or other computer sys­tems. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ software. Liebert MultiLink software can also remotely control UPS operation.
4
Page 9
4.0 MAJOR COMPONENTS
Major Components
Input Output
L
N G
TVSS & EMI/RFI
Battery
Charger
Rectifier
Dynamic
Bypass
Inverte
DC to DC
Converter
Battery
4.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
L
N
G
These UPS components provide surge protection and filter both elec­tromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected.
4.2 Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
• The mains power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the mains is reduced.
This results in cleaner power being available to other devices in the building not being protected by the Liebert UPStation GXT2U.
4.3 Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
5
Page 10
Major Components
4.4 Battery Charger
The battery charger utilizes energy from the mains power and pre­cisely regulates it to continuously “float charge” the batteries. The bat­teries are being charged whenever the Liebert UPStation GXT2U is plugged in, even when the UPS is not turned on.
4.5 DC to DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its opti­mum efficiency and voltage, thus increasing reliability.
4.6 Battery
The Liebert UPStation GXT2U utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are available to extend battery run times.
4.7 Dynamic Bypass
The Liebert UPStation GXT2U provides an alternate path for mains power to the connected load in the unlikely event of a UPS malfunc­tion. Should the UPS have an overload, overtemperature, or UPS fail­ure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illumi­nated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances on the mains supply.
6
Page 11
Figure 1 Liebert UPStation GXT2U, Rear View
Major Components
DB-9
Communications
Port
Rev. USBCARD
USB card being fitted in Liebert IntelliSlot
®
Port
Cooling Fans
External Battery Connector
Output Sockets
Support Base
Circuit Protector
Mains Input
7
Page 12
Installation
5.0 INSTALLATION
5.1 Preparation
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 12.0 - Specifications section). Take proper precautions when lifting or moving it.
2. Decide where to place the Liebert UPStation GXT2U. Install the
UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 100mm (4 in.) in the front and rear of the UPS. Maintain an ambient temperature range of 0°C to 40°C (32°F to 104°F).
NOTE
UPS operation in temperatures above 25°C (77°F) reduces battery life.
3. The Liebert UPStation GXT2U may be installed in either a tower
configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.2 - Tower UPS Installation or 5.3 - Rack-Mount UPS Conversion and Installation.
5.2 Tower UPS Installation
When using the Liebert UPStation GXT2U in a tower configuration, use the included support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accom­modate the additional cabinets (shown below, right).
Support base Spacers added to support
base to accommodate
additional battery cabinets
8
Page 13
Installation
5.3 Rack-Mount UPS Conversion and Installation
NOTE
When rack mounted, the UPS must be supported by a shelf, brackets or slide rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.
1. For slide rail installations, first remove the top/side fin. Slide the
top/side fin forward, then lift it up to remove. If desired, install the optional rack mount handles that were shipped with the UPS.
UPStation
GXT
+
AC INPUT
BATTERY
UPS ON
BYPASS
Optional rack mount handles
Securing hardware and slide rails are sold separately. Contact your local dealer or Liebert representative for these additional options and any assistance needed.
2. Unpack the two (2) rack-
mounting bracket assemblies and mounting hardware from the rack-mounting kit (P/N: RMKIT18-32). Bracket
Retaining latches
assemblies are interchangeable between left-hand or right-hand. Remove inner member of each bracket assembly as shown at right by extending it to its outermost position,
Inner members
Front members
depressing the retaining latch and then pulling inner member from bracket assembly.
Return flanges
Rear members
9
Page 14
Installation
3. Determine the height position inside the rack enclosure where you
want to mount the UPS or battery cabinet.
CAUTION
!
Reduce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position.
Install rear member of each bracket assembly into rack enclosure with two (2) M5
Front rack mounting rails
M5 screws
screws provided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mounting rails. Insert screws loosely (finger-tight) into top and bottom holes of return flange on rear mem­ber. Extend bracket assem-
M5 screws
Rear rack mounting rails
bly by sliding front member forward until it touches the front rack mounting rail. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes of return flange on each front member. Make sure bracket assemblies are at the same mounting height on all four (4) rack mounting rails.
4. Locate eight (8) M4 screws and eight (8) M4 nuts from hardware
pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten nut and screw completely to assure locking action. Fasten rear member and front member together using four (4) screws and four (4) nuts per bracket assembly as shown in the figures below. For maximum support, locate fasteners for each bracket assembly as far apart as possible, depending on rack depth, while still joining both members (See figures below). Check alignment of bracket assemblies and TIGHTEN ALL SCREWS FROM Steps 3 and 4.
M4 nuts
M4 screws
M4 nuts
M4 screws
18" rack depth
32" rack depth
M4 nuts
M4 nuts
10
Page 15
Installation
Retaini
h
5. Prepare the UPS or battery
M4 screws
ng latc
cabinet (the “equipment”) for rack mounting by following instructions in the equipment’s user manual. The equipment may require
UPS or battery cabinet
additional parts to be added or parts to be removed for rack mounting. After it is prepared, lay equipment in rack­mounting position. Fasten inner members from Step 2 to
Front
M4 screws
the equipment on both sides as shown in the figure at right with (8) M4 screws provided in this kit. Make sure retaining latch is near the rear of the equipment as shown in the figure at right.
6. Open grease packet
provided in this kit. Apply a 1" long bead of grease four (4) places inside the bottom, curved tracks of
UPS or battery cabinet
Apply grease
front members as shown at right. The grease will allow the equipment to slide into the bracket assemblies more easily.
Apply grease (inside)
CAUTION
!
Lifting equipment into rack may be a two-person job, depending on weight of equipment. See equipment’s user manual.
7. Insert the equipment, with inner members attached from Step 5,
into bracket assemblies by inserting top and bottom edges of inner members into the top and bottom, curved tracks of front members and sliding the equipment into rack (see figure in Step 6). Ends of inner members are tapered to allow rear of the equipment to be angled upward before insertion, if space allows.
Then the rear, bottom edges of inner members can be placed into front edge of bottom tracks, and the front of the equipment can be tipped up into horizontal position to insert the top edges of inner members before sliding the equipment into rack (see figure at right). The equipment should move smoothly into bracket assemblies. If not, recheck alignment of front and rear members from Steps 3 and 4.
11
Page 16
Installation
8. Secure front of the equipment to rack mounting rails to prevent
the equipment from sliding out of position. If securing holes are provided on front of the equipment that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment. Otherwise, the equipment should be secured to front of rack mounting rails with four (4) customer-supplied fasteners.
9. To orient the display for
horizontal viewing, remove the front plastic bezel by pulling forward evenly on both sides. The unit has two front panel
Vertical overlay for tower UPS
Horizontal overlay for rack UPS
overlays. Remove the outer overlay (used for tower installation). This reveals a horizontally oriented front panel overlay for rack mounting. Snap the front bezel back into place.
10. Once the UPS is installed in
UPStation GXT
+
UPStation GXT
+
AC INPUT BATTERY UPS ON BYPASS
AC INPUT BATTERY UPS ON BYPASS
the rack, the load may be connected. Ensure the load equipment is turned off; plug all loads into the output sockets on the rear of the UPS.
11. The input supply cable should
be connected to the electrical supply distribution in accordance with local rules and conditions.
12. Turn ON the UPS by pressing the ON button; then turn on the
connected load equipment. The UPS is now providing conditioned power to your equipment.
12
Page 17
Installation
5.4 External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. There is no limit to the number of external battery cabinets that can be used but each cabinet will increase the battery recharge time.
CAUTION
!
The external battery cabinet(s) are heavy (see
12.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.
1. Visually inspect the external battery cabinet for freight damage.
Report damage to the carrier and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side
fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please
contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the
tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.
5. Connect the supplied external battery
cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.
Rev. USBCARD
6. Turn ON the battery breaker on the
rear of the external battery cabinet.
7. The UPS is now equipped with
additional backup battery run time. For approximate battery run times, refer to 13.0 - Battery Run Times.
NOTE
You must use the included Configuration Program to specify the number of external battery cabinets connected to the UPS. For more information, see 9.0 - Configuration Program.
13
Page 18
6.0 CONTROLS AND INDICATORS
All LEDs illuminated
for illustrative purposes only.
Controls and Indicators
6.1 ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
•ON
•Alarm Silence
•Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one second. After the alarm is silenced, the Liebert UPStation GXT2U will reactivate the alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from mains power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Bat­tery LEDs illuminate, contact your local dealer, Liebert represen­tative or Liebert Worldwide Support Group.
14
Page 19
Controls and Indicators
6.2 Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass.
CAUTION
!
While the UPS is in Normal Mode operation, pressing the Standby/ Manual Bypass button once will put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press the Standby/ Manual Bypass button two distinct times (for about one second each time) to turn off the UPS. Perform all necessary shutdown procedures on connected loads before turning off the UPS.
6.3 Load/Battery Level Indicators (4 Green, 1 Amber)
The load/battery level indicators have dual functions. During normal mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity.
The Liebert UPStation GXT2U is equipped with automatic and remote battery test features. The automatic test occurs every 14 days (this option is user configurable) if mains has not been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to 11.0 - Troubleshooting). The remote test feature functions with Liebert MultiLink 3 software and can remotely initiate the battery test.
6.4 Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to 11.0 - Troubleshooting).
6.5 Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a problem, or the manual bypass function has been activated.
6.6 UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is operating and supplying power to your connected loads.
15
Page 20
Controls and Indicators
6.7 Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on battery.
6.8 AC Input Indicator LED (Green)
The AC Input indicator LED is illuminated when mains power is available and within the input specifications.
6.9 Output Voltage Selection
The Output Voltage is user configurable and is designed to allow selecting or changing the desired output voltage to match the mains via the Liebert UPStation GXT2U Configuration Program provided with the UPS. The settings to choose from are 200, 208, 220, 230, and 240 VAC output. The factory default setting is 230 VAC.
CAUTION
!
Never change the voltage settings while the UPS is ON and powering connected loads.
NOTE
Setting output voltage to 200 VAC will cause the UPS unit to be derated (700/1000 VA to 90%, 1500/2000/3000 VA to 80%) of the VA and watt ratings listed in 12.0 - Specifications.
16
Page 21
Operating Instructions
7.0 OPERATING INSTRUCTIONS
7.1 Normal Mode Operation
During normal operation, mains power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this
AC INPUTBATTERY UPS ON BYPASS
Normal Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.
power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state.
7.2 Bypass Mode Operation
Bypass mode occurs when the OFF button is pressed once while the UPS is in Nor­mal Mode. During bypass operation, mains power pro-
AC INPUTBATTERY UPS ON BYPASS
Bypass Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.
vides energy to the UPS. The mains power bypasses the inverter and provides power for the connected load.
CAUTION
!
Turning OFF the UPS while in bypass mode will result in loss of output power.
17
Page 22
Operating Instructions
7.3 Battery Mode Operation
Battery mode occurs in event of an extreme input voltage condition or com­plete mains failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load.
During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illumi­nate to warn that a mains problem has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 11.0 - Troubleshooting.
AC INPUTBATTERY UPS ON BYPASS
Battery Mode Operation at 80-61%
For approximate battery run times, refer to 13.0 - Battery Run Times. These times are approximates based on resistive load and an
ambient temperature of 25°C (77°F). To increase this time, turn off non-essential pieces of equipment (such as idle computers and moni­tors) or add the optional external battery cabinet.
CAUTION
!
Turning OFF the UPS while in battery mode will result in loss of output power.
7.4 Battery Recharge Mode
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.
18
Page 23
Communications
r
8.0 COMMUNICATIONS
8.1 Communications Interface Port
The Liebert UPStation GXT2U UPS has a standard DB-9 serial port female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:
Pin Assignment Description
1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Remote Shutdown (5-12VDC, 10-24 mA max); battery operation 5 Common 6 Remote Shutdown (short to pin 5); all modes of operation 7 Low Battery (open emitter) 8 Mains Fail (open emitter) 9 Mains Fail (open collector)
Pin Assignment Collector to Emitter*
6789
330 Ohms
54321
* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.
(+)
(-)
Open Collecto
Open Emitter
8.2 Pins 4 & 5 - Remote Shutdown on Battery
This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the mains, Pin 4 will ignore any signal on this pin.
Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using Liebert’s contact closure cable. It cannot be used with just a contact closure unless the relay is used to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown. Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the command cannot be canceled.
A battery shutdown signal on Pin 4 will NOT cause an immediate shut­down. A shutdown signal will start a 2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.
19
Page 24
Communications
If the mains returns during the 2-minute timer countdown, the shut­down timer will continue until the end of 2 minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power returns before the UPS turns OFF. This serves to reset and restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after perform­ing the 2-minute shutdown delay.
8.3 Pins 5 & 6 - Any-Mode Shutdown
Pin 6 of the 9-pin communication connector is used for “Any-Mode Shutdown” of the UPS output. This control input may be used in spe­cial applications to disable the UPS output power—both Inverter and Bypass.
The Options tab allows the behavior of the Any-Mode Shutdown fea­ture to be modified. When the program opens, or the REFRESH but­ton is pressed, the UPS setting is read by the configuration program and displayed.
8.3.1 Auto-Enable Output
WARNING
!
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS output can turn on automatically and without warning if the Pin 6 connection is changed.
8.3.2 Pin 6 Logic
WARNING
!
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to install a normally-closed connection between Pins 5 & 6. This connection must be maintained to use the UPS or to use the configuration program again, including the ability to change the UPS setting back to the default setting using the configuration program via a serial communication link.
If version 1.6 (or later) is used with an earlier Liebert UPStation GXT2U model (with an earlier UPS firmware version), the Any-Mode Shutdown features cannot be changed.
If the configuration program is used with an earlier UPS model (with an earlier UPS firmware version) that does not support the modifica­tion of these settings, the Options tab will display a reminder of the factory default settings. These cannot be changed.
20
Page 25
Communications
8.4 UPS Intelligent Communications
The Liebert UPStation GXT2U is equipped with a Liebert IntelliSlot® port to provide advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
Liebert MultiLink can also be configured for use without the serial cable when the Liebert IntelliSlot SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown across the network with other computers running Liebert MultiLink when you purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/Web Card and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Liebert IntelliSlot port of the Liebert UPStation GXT2U. The Liebert IntelliSlot SNMP/ Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Liebert IntelliSlot MultiPort 4 Card allows you to install Liebert MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shut­down for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.
21
Page 26
Configuration Program
9.0 CONFIGURATION PROGRAM
This is a new feature included with the new Liebert UPStation GXT2U line. Several UPS settings that were previously not available or required custom manufacturing may now be modified using this program. For most users, the factory default settings will be adequate. This manual illustrates the features available for modification, as well as the factory default setting.
NOTE
The UPS must be turned off—and not powering connected equip­ment—before you make any changes to configuration settings.
While the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to turn off the UPS.
9.1 Liebert UPStation GXT2U Configuration Program Abilities
• Select one of five output voltages to match voltages found around the world.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see 8.0 - Communications).
NOTE
This program is compatible with UPS models beginning with “GXT2-”, as in “GXT2-1500RT230.” It is not compatible with earlier versions of Liebert UPStation GXT UPS.
9.1.1 What You Will Need
In addition to the Liebert UPStation GXT2U UPS, you will need the configuration program diskette and serial cable (beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK ML9P9S CONTACT CLOSURE communi­cation cable IS NOT compatible with the configuration program. A Windows 95 required to set up and run the configuration program.
®
, 98®, or NT® computer—desktop or laptop—is also
22
Page 27
Maintenance
10.0 MAINTENANCE
The Liebert UPStation GXT2U requires very little maintenance. The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the mains supply.
When storing the UPS for any length of time, it is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries.
The Liebert UPStation GXT2U is designed to allow the user to safely replace the internal batteries. Read the safety cautions before pro­ceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.
10.1 Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
• Remove rings, watches, or other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
23
Page 28
Maintenance
10.1.1 Internal Battery Replacement Procedures
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the four screws on the front battery door. Lay the battery door aside for reassembly.
3. Gently pull battery wiring out and disconnect the two slotted battery connectors.
4. Grasp the battery pack assembly, and pull it out of the front of the UPS.
5. Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 6; otherwise STOP and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.
6. Line up and slide in the new replacement battery pack.
7. Reconnect the two slotted battery connectors and gently push the battery wiring and battery pack assembly back into the UPS.
8. Reattach the front battery door with the four screws.
9. Reattach the front plastic bezel cover to the UPS.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.
24
Page 29
Troubleshooting
11.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the Liebert UPStation GXT2U develops a prob­lem. Use this information to determine whether external factors caused the problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:
Fault
E
D
C
B
A
BYPASS
UPS ON
BATTERY
AC INPUT
This example shows the UPS on bypass due to output overload.
ABC DEFault
AC INPUT BATTERY UPS ON BYPASS
LOAD/BATTERY
LEVEL INDICATORS
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep every half-second A LED On bypass due to overtemperature condition; beep every 4 sec. B LED On bypass due to DC bus overvoltage; beep every 4 sec. C LED On bypass due to control power supply failure; beep every 4 sec. D LED On bypass due to PFC failure; beep every 4 sec. E LED On bypass due to inverter failure; beep every 4 sec. A&C LEDs UPS failed battery test; long beep every minute C&E LEDs UPS shutdown due to command from communication port
(SNMP); no beep
Battery LED Flashing
AC LED Flashing
Bypass LED Flashing
Internal Battery source not available (continuous horn). Check battery connection, completely power down and reboot UPS.
Line-to-neutral reversal in the AC input power supply or a loss of proper grounding; continuous horn and UPS will not start.
Mains power voltage or frequency is out of tolerance; bypass is unavailable.
25
Page 30
Troubleshooting
Under fault conditions, the Fault indicators will be illuminated indefi­nitely while battery charger is operational, or for a maximum of 5 min­utes while battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.
Table 1 Troubleshooting guide
Problem Cause Solution
Ensure UPS is OFF.
UPS fails to start when the ON button is pressed.
UPS is short circuited or overloaded.
UPS not plugged in.
Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
UPS is operating from battery mode, make certain UPS is securely plugged into the wall receptacle.
Battery indicator LED is illuminated.
UPS has reduced battery time.
UPS input protection fuse has blown/opened.
Mains voltage out of UPS input range.
Batteries are not fully charged.
UPS is overloaded.
Batteries may not be able to hold a full charge due to age.
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
Check load level display and reduce the load on the UPS.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit.
26
Page 31
Table 1 Troubleshooting guide (continued)
Problem Cause Solution
Check load level display Fault and Bypass indicator LEDs and all load level LEDs are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED A are illuminated.
UPS overloaded or load equipment is faulty.
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
and remove non-essential
loads. Recalculate the load
and reduce number of
loads connected to UPS.
Check load equipment for
faults.
Ensure UPS is not
overloaded, ventilation
openings not blocked, or
room ambient temperature
is not excessive. Wait 30
minutes to allow UPS to
cool, then restart UPS. If
UPS does not restart,
contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
Troubleshooting
Fault and Bypass indicator LEDs and diagnostic LED B are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED C are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED D are illuminated.
Fault and Bypass indicator LEDs and diagnostic LED E are illuminated.
Fault indicator LED and diagnostic LED A and C are illuminated.
UPS internal DC bus overvoltage.
UPS control power supply fault.
UPS PFC (Power Factor Correction Circuit) fault.
UPS inverter fault.
UPS failed the battery test.
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS requires service.
Contact your local dealer,
Liebert Representative or
the Liebert Worldwide
Support Group.
Replace batteries. Contact
your local dealer, Liebert
representative or the
Liebert Worldwide Support
Group.
27
Page 32
Table 1 Troubleshooting guide (continued)
Problem Cause Solution
Your UPS has received a
signal or command from
the attached computer. If
Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated.
AC LED is flashing.
UPS shutdown due to a command from the communications port(s).
UPS detected a line-to­neutral reversal or a loss of proper grounding; continuous horn and UPS will not start. This is active only when power is first applied to the input. Once the UPS is running, the AC LED will not start flashing, even if the input wiring is changed.
this was inadvertent,
ensure the communication
cable used is correct for
your system. For
assistance, contact your
local dealer, Liebert
representative or the
Liebert Worldwide Support
Group.
Contact a qualified
electrician to verify site
wiring.
Troubleshooting
Battery LED is flashing.
Bypass LED is flashing.
Battery source is not available; continuous horn.
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits.
Check battery connections,
completely power down
and restart UPS.
NOTE: If the battery circuit
opens while the UPS is
running, it will be detected
when the next battery test
is performed.
The AC input powers the
PFC input and serves as
the bypass source. If the
AC is present but the
voltage or frequency
exceeds the acceptable
range for safe operation
with a load, the bypass will
be disabled and this LED
will flash, indicating that the
bypass is unavailable.
28
Page 33
Table 2 Alarm Conditions
Condition Alarm
Troubleshooting
Battery Mode (mains failure)
Low Battery
Output Overload (bypass)
Overtemperature (bypass)
DC Bus Overvoltage (bypass)
Control Power Supply Failure (bypass)
One short beep every 10 seconds; more than 2 minutes of run time remaining
Two short beeps every 5 seconds; less than 2 minutes of run time remaining
One short beep every half second
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A one-second beep every 4 seconds
PFC Failure (bypass) A one-second beep every 4 seconds
Inverter Failure A one-second beep every 4 seconds
Battery Test Failure A 2-second beep every minute
29
Page 34
12.0 SPECIFICATIONS
Specifications
Model Number Model Rating DIMENSIONS: mm
Unit W x D x H: mm
Shipping W x D x H: mm
WEIGHT: kg
Unit: kg
Shipping: kg
INPUT AC PARAMETERS
Voltage Range
(typical)
100% - 90% loading
90% -70% loading 70% -30% loading
30% - 0% loading
Frequency
Input Connector
OUTPUT AC PARAMETERS
Output Sockets
Voltage
Frequency
Waveform
Main Mode
Overload
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Mfg/Part #
Back-up Time
Recharge Time
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
RFI/EMI
Surge Immunity
Transportation
GXT2-700RT230 GXT2-1000RT230 GXT2-1500RT230
700VA / 490W 1000VA / 700W 1500VA / 1050W
87 x 547 x 430 87 x 547 x 430 87 x 547 x 430
268 x 692 x 585 268 x 692 x 585 268 x 692 x 585
22.5 22.6 23.2
26.5 26.6 27.2
230 VAC nominal;
variable based on output load 159VAC / 280VAC 159VAC / 280VAC 176 VAC / 280VAC 159VAC / 280VAC 159VAC / 280VAC 159 VAC / 280VAC 139VAC / 280VAC 139VAC / 280VAC 139 VAC / 280VAC 119VAC / 280VAC 119 VAC / 280VAC 119VAC / 280VAC
40 - 70 Hz; Auto Sensing
IEC320-10A
(6) EN 60320/C13
200/208/220/230/240 (user configurable) VAC; ±3%
50 Hz or 60 Hz
Sinewave
200% for 8 cycles;
130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, lead acid
4 x 12V x 7.0 or 7.2 AH
China Storage Battery / CSB 1270 F2
See 13.0 - Battery Run Times
5 Hours to 95% capacity after full discharge
into 100% load (Internal Batteries Only)
0°C to +40°C (+32°F to +104°F)
-15°C to +50°C (+5°F to +122°F) 0% to 95%, non-condensing
Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
15,000 m (50,000 ft.) maximum
<50 dBA, at 1 metre from the rear
<45 dBA, at 1 metre from the front or sides
EN 62040-1, CE compliance mark,
for both Low Voltage and EMC Directives
EN 62040-2, Class B
EN 61000 4-2, 4-3, 4-4, 4-5
ISTA Procedure 1A
30
Page 35
Specifications
SPECIFICATIONS, CONTINUED
Model Number GXT2-2000RT230 GXT2-3000RT230 / 3KRT230E Model Rating 2000VA / 1400W 3000VA / 2100W DIMENSIONS: mm
Unit W x D x H: mm 87 x 547 x 430 87 x 618 x 430 Shipping W x D x H: mm 268 x 692 x 585 268 x 692 x 585
WEIGHT: kg
Unit: kg 24.7 31.9 Shipping: kg 28.7 35.9
INPUT AC PARAMETERS
Voltage Range (typical) 100% - 90% loading 176VAC / 280VAC 176VAC / 280VAC 90% -70% loading 159VAC / 280VAC 159VAC / 280VAC 70% -30% loading 139VAC / 280VAC 139VAC / 280VAC 30% - 0% loading 119VAC / 280VAC 119VAC / 280VAC Frequency 40 - 70 Hz; Auto Sensing Input Connector IEC320-10A IEC320-16A
OUTPUT AC PARAMETERS
Output Sockets (6) IEC320-10A
Voltage 200/208/220/230/240 (user configurable) VAC; ±3% Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid Qty x V x Rating 4 x 12V x 9.0 AH 6 x 12V x 9.0 AH
Battery Mfg/Part #
Back-up Time See 13.0 - Battery Run Times
Recharge Time
ENVIRONMENTAL
Operating Temp 0°C to +40°C (+32°F to +104°F) Storage Temp -15°C to +50°C (+5°F to +122°F) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating Storage Elevation 15,000 m (50,000 ft.) maximum
Audible Noise
AGENCY
Safety
RFI/EMI EN 62040-2, Class B Surge Immunity EN 61000 4-2, 4-3, 4-4, 4-5 Transportation ISTA Procedure 1A
130% for 10 seconds with transfer to bypass
5 Hours to 95% capacity after full discharge
into 100% load (Internal Batteries Only)
<55 dBA, at 1 metre from the rear
<50 dBA, at 1 metre from the front or sides
EN 62040-1, CE compliance mark,
for both Low Voltage and EMC Directives
230 VAC nominal;
variable based on output load
(6) IEC320-10A,
(1) IEC320-16A
200% for 8 cycles;
Panasonic UP-VW1245P1
Yuasa / REW 45-12
31
Page 36
Specifications
12.1 Battery Cabinet Specifications
Model Number GXT2-48VBATT GXT2-72VBATT
GXT2-700RT230
Used w/ UPS Model
DIMENSIONS: mm
Unit W x D x H: mm 87 x 547 x 430 87 x 618 x 430
Shipping W x D x H: mm 268 x 692 x 585 268 x 692 x 585
WEIGHT: kg
Unit: kg 28.3 42.5
Shipping: kg 32.3 46.5
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty x V x Rating 2 x 4 x 12V x 7.0 or 7.2 AH 2 x 6 x 12V x 9.0 AH
Battery Mfg / Part #
Back-up Time See 13.0 - Battery Run Times
ENVIRONMENTAL
Operating Temp 0°C to +40°C (+32°F to +104°F)
Storage Temp -15°C to +50°C (+5°F to +122°F)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
Storage Elevation 15,000 m (50,000 ft.) maximum
AGENCY
Safety
RFI/EMI EN 62040-2, Class B
Transportation ISTA Procedure 1A
GXT2-1000RT230 GXT2-1500RT230 GXT2-2000RT230
China Storage Battery /
CSB 1270 F2
EN 62040-1, CE compliance mark,
for both Low Voltage and EMC Directives
GXT2-3000RT230
Panasonic / UP-VW1234P1
Yuasa / REW 45-12
32
Page 37
Battery Run Times
13.0 BATTERY RUN TIMES
Load% 700VA 1000VA 1500VA 2000VA 3000VA
10% 248 191 144 56 91 20% 115 87 53 33 46 30% 79 48 38 26 30
Internal Battery (minutes)
Internal Battery + 1 External Battery Cabinet (minutes)
Internal Battery + 2 External Battery Cabinets (minutes)
Internal Battery + 3 External Battery Cabinets (minutes)
Internal Battery + 4 External Battery Cabinets (minutes)
Note: Approximate discharge times are in minutes and at 25°C (77°F) with a 100% resistive load.
40% 58 34 28 19 21 50% 44 25 20 14 16 60% 35 19 15 12 11 70% 29 16 12 10 9 80% 24 13 10 8 8 90% 20 12 8 7 7
100% 17 11 7 6 5
10% 992 764 576 328 364 20% 460 348 212 159 184 30% 316 192 152 88 120 40% 232 136 112 67 84 50% 176 100 80 52 64 60% 140 76 60 36 44 70% 116 64 48 30 36 80% 96 52 40 24 32 90% 80 48 32 21 28
100% 68 44 28 18 20
10% 1984 1528 1152 392 728 20% 920 696 424 231 368 30% 632 384 304 182 240 40% 464 272 224 133 168 50% 352 200 160 98 128 60% 280 152 120 84 88 70% 232 128 96 70 72 80% 192 104 80 56 64 90% 160 96 64 49 56
100% 136 88 56 42 40
10% 2976 2292 1728 560 1092 20% 1380 1044 636 330 552 30% 948 576 456 260 360 40% 696 408 336 190 252 50% 528 300 240 140 192 60% 420 228 180 120 132 70% 348 192 144 100 108 80% 288 156 120 80 96 90% 240 144 96 70 84
100% 204 132 84 60 60
10% 3968 3056 2304 840 1456 20% 1840 1392 848 495 736 30% 1264 768 608 390 480 40% 928 544 448 285 336 50% 704 400 320 210 256 60% 560 304 240 180 176 70% 464 256 192 150 144 80% 384 208 160 120 128 90% 320 192 128 105 112
100% 272 176 112 90 80
33
Page 38
13.1 Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
Battery Run Times
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877 Outside the US: 614-841-6755
upstech@liebert.com
34
Page 39
Page 40
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877 monitoring@emersonnetworkpower.com Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877 upstech@emersonnetworkpower.com Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378 powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778 Outside the United States 614-888-0246
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is the registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
35028 Piove Di Sacco (PD) Italy
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
1050 Dearborn Drive
Columbus, OH 43229
Via Leonardo Da Vinci 8
Zona Industriale Tognana
Fax: +39 049 5841 257
Locations
United States
P.O. Box 29186
Europe
+39 049 9719 111
Asia
Hong Kong
852 2572220
Fax: 852 28029250
SLI-23150_REV07_01-08
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™.
AC Power Systems
EmersonNetworkPower.com
Outside Plant
Connectivity
DC Power Systems
Embedded Computing
Embedded Power
Integrated Cabinet Solutions
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Power Switching & Control
Precision Cooling
Services
Site Monitoring
Surge Protection
Loading...