Liebert Economizer Cooling Solutions
Reduce Cooling Costs by up to 50% Without Compromising Reliability
Precision Cooling for
Business-Critical Continuity
TM
![](/html/10/1008/1008cb691d2f1393f314b3f146b49ab232a824cac2aaa8e9bdf97adfab843eea/bg2.png)
Lower Cooling Energy Consumption by up to 50%
Fluid- and Air-side economizers take advantage of cold outside
temperatures to provide “free cooling” cycles that reduce or
eliminate the operation of data center precision cooling system
compressors and pumps.
Using economizers, you can lower cooling energy usage by up
to 50% − depending on the average ambient temperature and
humidity of your site.
A Focus on Energy Efficiency
While many IT professionals are considering economizers in
preparation for potential code or legislation changes, a move
toward improved efciencies can pay off with rewards of its own −
especially in terms of lower operating costs and utility incentives.
For example, some utility companies offer rebates for using energyefcient equipment, quickly increasing your return on investment
and overall savings.
Geographic regions of greatest cooling economization opportunity
Consider Chiller Plant Economizer
Consider Chiller Plant or GLYCOOL Cooling Economizer
Consider Chiller Plant or Air Economizer
Consider Chiller Plant, Air Economizer or GLYCOOL Cooling Economizer
Industry Best Practices
When making the choice to use an economizer solution, it is critical
to analyze how changes will impact your entire data center.
®
Industry thought leader ASHRAE
recommends that IT professionals
investigating the use of economizers in their data centers
consider the impact of incorrect application, and/or maintenance/
operational issues, on the life of protected sensitive equipment:
■
High humidity can cause condensation that reduces server life and
affects operation
■
Low dew point can result in problems such as static electricity
■
Gaseous or particulate contaminants can adversely affect sensitive
electronics
■
Operational reliability, including redundancy, is required to
achieve IT initiatives
■
Reliable water sources for cooling towers
■
Chiller condensate sump heaters for cold climate operation (or
other solutions)
Why Emerson Network Power?
For more than 40 years, Liebert technologies have led the industry
in precision cooling for data centers, including economizing
solutions such as the free-cooling GLYCOOL system.
Our depth and breadth of experience make us uniquely prepared to
serve as trusted advisors to IT professionals. Liebert representatives
can help you decide which economization method is the right
solution for your application. They will guide you through the
complexities of environmental factors affecting your decision
making, including temperature ranges, dew point, humidity,
and the issue of gaseous and particulate contaminants, as well as
maintenance issues that impact all types of econimizers.
It’s how we deliver Efciency Without Compromise™ − providing
high availability products with energy-efcient technologies.
Efciency Without Compromise
Efciency Without Compromise provides a path to optimize data center infrastructure around design, operating and management
efciencies – while maintaining or improving availability. This is achieved through the proper selection and utilization of cooling, power and
monitoring technologies, supported by key services and local expertise.
INFRASTRUCTURE
MANAGEMENT
Impro ving perfo rmance
of the IT i nfrastru cture
and environment
ECO AVAILABILITY
Balan cing high leve ls
of availability and
efciency
2
FLEX CA PACITY
Adapti ng to IT change s
for continuous
optimization and
design exibility
HIGH DENS ITY
Delivering architectures
from 10- 60kW/rack to
minimi ze space and cos t
![](/html/10/1008/1008cb691d2f1393f314b3f146b49ab232a824cac2aaa8e9bdf97adfab843eea/bg3.png)
Atlanta Chicago Seattle
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer
Full Economizer Hours 25% 17% 18% 48% 41% 14% 39% 23% 27%
Partial Economizer Hours 52% 34% 33% 39% 28% 22% 61% 61% 15%
Estimated Total Energy Savings 51% 36% 34% 67% 58% 25% 70% 49% 34%
The effect of ambient conditions in representative cities on economization hours and resultant energy savings, using different
economization methods (assumes cold aisle temperature 71°–80° F; CRAC return temperature 85° F). Cooling tower calculations were
made with Liebert chilled water-based precision cooling products. Drycooler calculations were based on Liebert precision cooling products
equipped with GLYCOOL option. Air economizer calculations based on 41.9° F dew point limitation.
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer
Liebert Precision Cooling Economization
In accordance with ASHRAE’s guidance, and in keeping with our position as the industry’s power and cooling leader, Emerson Network
Power provides effective, efcient economizer solutions. Emerson Network Power offers uid-side economization solutions and an air-side
economizer – and Liebert technologies are well suited to work with economization solutions from third-party providers.
No economizer
Full economizer
Partial economizer
■
Potential dependant on dew point
Comparative hours of economizer operations through varying CR AC supply and return temperatures in three cities representing distinct ambient conditions
(partial economizer operation = outside ambient used to precool or assist in cooling of data center return air).
Fluid-Side vs. Air-Side Economization Comparison
Fluid-Side Air-Side
Advantages
■
Can be used in any climate cold enough to provide effective hours
of economization; Glycol-based systems operate effectively at
the widest range of outdoor ambient temperatures
■
Wider operating range results in 2x–3x more effective hours than
air economizer systems in most climates
■
No outside air is introduced to the data center, so the ltration
and humidication functions of the CRAC unit operate normally
to ensure optimal air quality and relative humidity
■
Service requirements and complexities are reduced compared
to air-side economizers; less lter changing and maintenance are
required
■
Compatible with Liebert DS, Liebert CW, Liebert Challenger 3000
and Liebert XD precision cooling systems (downow and upow)
Challenges
■
Indirect piping and control are more complex
■
Higher initial capital costs
■
Added water use for cooling tower
Advantages
■
Compatible with moderate climates
■
More operating hours than uid-side economizers, if
humidication is added
■
Can be used on systems that don’t use water for heat rejection
■
Lower initial capital costs
■
Uses less water than uid-side economizers
■
Compatible with Liebert DS and Liebert CW precision cooling
products (downow only)
Challenges
■
Ductwork required to get air into IT space
■
Narrower range of effective hours of operation if used without
humidication
■
Dust and pollen sensors are required to minimize lter
maintenance; humidity control can be costly and challenging
■
Need proven, intelligent controls to ensure proper temperature
and humidity
■
High-density applications may require more localized cooling
■
Mildew minimization actions required