Emerson Liebert Economizer Solutions Brochures and Data Sheets

Liebert Economizer Cooling Solutions
Reduce Cooling Costs by up to 50% Without Compromising Reliability
Precision Cooling for Business-Critical Continuity
TM
Lower Cooling Energy Consumption by up to 50%
Fluid- and Air-side economizers take advantage of cold outside
temperatures to provide “free cooling” cycles that reduce or
eliminate the operation of data center precision cooling system
Using economizers, you can lower cooling energy usage by up
to 50% − depending on the average ambient temperature and humidity of your site.
A Focus on Energy Efficiency
While many IT professionals are considering economizers in preparation for potential code or legislation changes, a move toward improved efciencies can pay off with rewards of its own − especially in terms of lower operating costs and utility incentives. For example, some utility companies offer rebates for using energy­efcient equipment, quickly increasing your return on investment and overall savings.
Geographic regions of greatest cooling economization opportunity
Consider Chiller Plant Economizer Consider Chiller Plant or GLYCOOL Cooling Economizer Consider Chiller Plant or Air Economizer Consider Chiller Plant, Air Economizer or GLYCOOL Cooling Economizer
Industry Best Practices
When making the choice to use an economizer solution, it is critical to analyze how changes will impact your entire data center.
®
Industry thought leader ASHRAE
recommends that IT professionals investigating the use of economizers in their data centers consider the impact of incorrect application, and/or maintenance/ operational issues, on the life of protected sensitive equipment:
High humidity can cause condensation that reduces server life and
affects operation
Low dew point can result in problems such as static electricity
Gaseous or particulate contaminants can adversely affect sensitive
electronics
Operational reliability, including redundancy, is required to
achieve IT initiatives
Reliable water sources for cooling towers
Chiller condensate sump heaters for cold climate operation (or
other solutions)
Why Emerson Network Power?
For more than 40 years, Liebert technologies have led the industry in precision cooling for data centers, including economizing solutions such as the free-cooling GLYCOOL system.
Our depth and breadth of experience make us uniquely prepared to serve as trusted advisors to IT professionals. Liebert representatives can help you decide which economization method is the right solution for your application. They will guide you through the complexities of environmental factors affecting your decision making, including temperature ranges, dew point, humidity, and the issue of gaseous and particulate contaminants, as well as maintenance issues that impact all types of econimizers.
It’s how we deliver Efciency Without Compromise™ − providing high availability products with energy-efcient technologies.
Efciency Without Compromise
Efciency Without Compromise provides a path to optimize data center infrastructure around design, operating and management efciencies – while maintaining or improving availability. This is achieved through the proper selection and utilization of cooling, power and monitoring technologies, supported by key services and local expertise.
INFRASTRUCTURE MANAGEMENT
Impro ving perfo rmance of the IT i nfrastru cture and environment
ECO AVAILABILITY
Balan cing high leve ls of availability and efciency
2
FLEX CA PACITY
Adapti ng to IT change s for continuous optimization and design exibility
HIGH DENS ITY
Delivering architectures from 10- 60kW/rack to minimi ze space and cos t
Atlanta Chicago Seattle
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer Full Economizer Hours 25% 17% 18% 48% 41% 14% 39% 23% 27% Partial Economizer Hours 52% 34% 33% 39% 28% 22% 61% 61% 15% Estimated Total Energy Savings 51% 36% 34% 67% 58% 25% 70% 49% 34%
The effect of ambient conditions in representative cities on economization hours and resultant energy savings, using different economization methods (assumes cold aisle temperature 71°–80° F; CRAC return temperature 85° F). Cooling tower calculations were made with Liebert chilled water-based precision cooling products. Drycooler calculations were based on Liebert precision cooling products equipped with GLYCOOL option. Air economizer calculations based on 41.9° F dew point limitation.
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer
Fluid Economizer Liebert
Cooling
Tower
Dry-
cooler
CW or DS
with Air
Economizer
Liebert Precision Cooling Economization
In accordance with ASHRAE’s guidance, and in keeping with our position as the industry’s power and cooling leader, Emerson Network Power provides effective, efcient economizer solutions. Emerson Network Power offers uid-side economization solutions and an air-side economizer – and Liebert technologies are well suited to work with economization solutions from third-party providers.
No economizer
Full economizer
Partial economizer
Potential dependant on dew point
Comparative hours of economizer operations through varying CR AC supply and return temperatures in three cities representing distinct ambient conditions (partial economizer operation = outside ambient used to precool or assist in cooling of data center return air).
Fluid-Side vs. Air-Side Economization Comparison
Fluid-Side Air-Side
Advantages
Can be used in any climate cold enough to provide effective hours
of economization; Glycol-based systems operate effectively at the widest range of outdoor ambient temperatures
Wider operating range results in 2x–3x more effective hours than
air economizer systems in most climates
No outside air is introduced to the data center, so the ltration
and humidication functions of the CRAC unit operate normally to ensure optimal air quality and relative humidity
Service requirements and complexities are reduced compared
to air-side economizers; less lter changing and maintenance are required
Compatible with Liebert DS, Liebert CW, Liebert Challenger 3000
and Liebert XD precision cooling systems (downow and upow)
Challenges
Indirect piping and control are more complex
Higher initial capital costs
Added water use for cooling tower
Advantages
Compatible with moderate climates
More operating hours than uid-side economizers, if
humidication is added
Can be used on systems that don’t use water for heat rejection
Lower initial capital costs
Uses less water than uid-side economizers
Compatible with Liebert DS and Liebert CW precision cooling
products (downow only)
Challenges
Ductwork required to get air into IT space
Narrower range of effective hours of operation if used without
humidication
Dust and pollen sensors are required to minimize lter
maintenance; humidity control can be costly and challenging
Need proven, intelligent controls to ensure proper temperature
and humidity
High-density applications may require more localized cooling
Mildew minimization actions required
3
Fluid-Side Cooling Economization Strategy
Fluid-side economizers work in
conjunction with a heat rejection loop
− consisting of either a cooling tower,
evaporative cooler or drycooler − to
satisfy cooling requirements.
These systems are incorporated into either a chilled water or glycol-based cooling system. For economizer operation, the uid used in the cooling system passes through an additional heat exchanger to cool the room air, reducing or eliminating the use of cooling compressors and pumps.
Energy-efcient Liebert technologies are well suited to uid-side cooling economization.
GLYCOOL Cooling
for Liebert DSTM and Liebert ChallengerTM 3000
How the Liebert GLYCOOL System Works
The self-contained Liebert GLYCOOL system comprises a compressorized Liebert glycol system with advanced controls, a standard cooling coil, an additional “Econ-o-coil” free cooling coil and a drycooler.
At ambient temperatures above the CRAC return temperature (less the drycooler approach), the system functions as a normal glycol-cooled system. As outdoor temperatures drop, the temperature of the uid in the heat rejection loop drops also. Once it is cold enough outside, the control opens the modulating valve to the Econ-o-coil circuit. Depending on ambient conditions, the system either reduces or eliminates cooling compressor and pump operation.
Savings
The Liebert GLYCOOL system delivers an average annual energy savings of 20–50%.
A-frame coil inside
Econ-o-coil rests on A-frame coil
Liebert Drycooler
Centrifugal
blower
Compressors
Liebert GLYCOOL System
Providing free cooling by using outside air through the Econ-o-coil circuit to maximize cooling efciencies
Glycol-cooled condensers and Paradenser
tubes
Glycol circulating pump
4
Chiller Plant
Partnered with Liebert CWTM and Liebert Challenger 3000
How Chiller Plant Economization Works
The chilled water loop that feeds multiple chilled water-based CRAC units uses cold outdoor temperatures to cool the chilled water loop, effectively reducing pump operation.
Full economization hours are dependent upon the outdoor wet bulb temperature, the approach of the cooling tower and heat exchanger, and the chiller water supply temperature. Partial economization hours are dependent upon the factors listed above, as well as the chilled water return temperature.
Savings
A chiller plant, partnered with Liebert precision cooling technologies, delivers an average annual energy savings of 40–60%.
Cooling TowerPumpCRAC Units
Why Liebert Products and Services?
Liebert iCOM® Control – Based on
years of data center precision cooling experience, the intelligent Liebert iCOM control dynamically optimizes the operating parameters of uid-side
economizer solutions
Provides advanced control and monitoring, which allows units to work together as a single system to enhance performance and improve efciency
Service − Industry-leading
local service and support network ensures timely maintenance, service and parts availability
Industry Leadership –
Liebert advanced technologies can help you cut operating costs, improve efciencies, reduce energy
consumption, ensure reliable
performance and maintain optimal conditions within your IT environment
Compatibility – The Liebert GLYCOOL
system is available on Liebert DS and Liebert Challenger 3000 (both downow and upow)
Chiller
Plate Heat E xchanger
Economizer System Chiller Plant
Fluid ow during uid-side cooling economization – taking advantage of environmental conditions to improve cooling efciencies
Liebert CW Chilled Water Based Precision Cooling is designed to handle high heat loads – using an existing building chiller as a chilled water cooling
source
Liebert Challenger 3000
provides complete control of temperature, humidity and air ltration
Liebert DS Precision Cooling System provides efcient,
precise, reliable control
of room temperature, humidity and airow for operation-critical equipment
5
Air-Side Cooling Economization Strategy
Air-side economizers use outside air to
supplement data center cooling. They
utilize a system of sensors, ducts and
dampers to control the entry of outside
air to help satisfy cooling demands.
Sensors monitor outside and inside air conditions, and when outside conditions are suitable for cooling, the economizer adjusts the dampers to introduce the outside air, making it the primary cooling source. This “free cooling” reduces or eliminates the need for cooling compressors, resulting in increased efciencies and signicant energy savings.
Full “free cooling” is attained when the outside air is below the entering cold aisle temperature.
Partial benet is attained when the outside air temperature is 2 degrees Fahrenheit lower than the air temperature returning to the Cooling Room Air Handlers and dew point is less than 59 degrees and above 41.9 degrees Fahrenheit.
Air Economizer System
Liebert Air Economizer System installed on a Liebert CW chilled water-based precision cooling system in downow conguration – using lower outside temperatures to minimize cooling compressor and pump use.
Normal data center
cooling operation
“Free cooling” using lower outside temperatures to effectively cool the data center
Maximizing Economization with Liebert iCOM Control
Intelligent Liebert iCOM control is ideally suited for sensing and controlling Liebert economizers
− or those supplied by other manufacturers.
Multiple parameters within an IT environment add complexity and can be difcult to monitor and manage, but the Liebert iCOM control simplies oversight and puts you back in control − with substantial benets over custom congured controls.
Liebert iCOM control:
Factory tested and warranted
Offers multiple levels of monitoring and control – and compatibility with Liebert SiteScan® Web
Provides consistent, eld-proven operation
Shares a common platform with Liebert Precision Cooling Systems
Equipped with factory-provided installation, operation and maintenance instructions
Supported by factory-trained technicians
6
Lieber t iCOM Control System
Liebert Air Economizer System
with Liebert iCOM Control for Liebert DS and Liebert CW
How the Liebert Air Economizer System Works
The Liebert Air Economizer System reduces cooling costs by taking advantage of cool outdoor air to condition indoor spaces, reducing or eliminating compressor operation in Liebert DS units, and eliminating pump operation in Liebert CW, as well as reducing or eliminating the compressor operation of the supporting chiller plant. The Liebert Air Economizer System is equipped with high-efciency ltration and a sensor network that detects clogged lters – and it communicates with your existing Business Management System.
The Liebert Air Economizer system comprises a plenum with air mixing box; dual enthalpy controls with Liebert iCOM control (temperature/humidity sensors for outdoor air, return air and supply air). The Liebert Air Economizer system must be applied to each CRAC unit.
Three Stages of Cooling
Depending on environmental conditions, the Liebert Air Economizer will adjust to cool your IT environment with:
100% outdoor air
Mixed outdoor air and compressor/pump cooling
100% compressor/pump cooling
Why Liebert Products and Services?
Liebert iCOM control – Dynamically
optimizes both the precision cooling system and the operating parameters of air-side economizer systems
Temperature and humidity sensors –
Our sensors focus on both temperature and humidity, because ignoring the impact of humidity can have a serious short- and long-term impact on your IT equipment and your facility’s infrastructure
Service − Industry-leading
local service and support network ensures timely maintenance, service and parts availability
A long history of success
– Liebert DS and Liebert CW represent the newest generation of the industry’s most reliable and popular precision cooling system, the Liebert Deluxe System/3
Compatibility – The Liebert Air
Economizer System can be used with the Liebert DS and Liebert CW – as well as the Liebert iCOM Control
Liebert CW Chilled Water Based Precision Cooling is designed to handle high heat loads
Savings
The Liebert Air economizer system delivers an average annual energy savings of 30–60%.
Solution Compatibility
Liebert
iCOM
Control
Lieber t DS upow
Lieber t DS downow
Lieber t CW upow
Lieber t CW downow
Lieber t XDTM Systems
Lieber t Challenger 3000
Lieber t Deluxe System/3TM downow systems retrotted with Liebert iCOM controls
GLYCOOL
Cooling
X X
X X X
X X X
X X X
Chiller Plant
Economization
X X
X X X
X X
Liebert Air
Economizer
Liebert DS Precision
Cooling System provides precise, reliable control of
room temperature,
humidity and airow
7
Ensuring the High Availability of Mission-Critical Data and Applications.
Emerson Network Power, a business of Emerson (NYSE: EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, monitoring, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efciency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Emerson Network Power
Liebert Corporation
World Hea dquarters 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 United States O f America 800 877 9222 Phone (U.S. & C anada Only) 614 888 0246 Phone (Out side U.S.) 614 841 6022 FAX
Emers on Network Po wer European Headquarters Via Leonardo Da V inci 8 Zona Industrial e Tognana 35028 Piove Di Sa cco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emers on Network Po wer Asia Pacic 29/F, The Orient Square Building F. Ortigas Jr. Road, Orti gas Center Pasig City 1605 Philippines +63 2 687 6615 +63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone 614 841 6755 (outside U.S.)
While eve ry preca ution has bee n taken to ensur e accurac y and complet eness in this l iterature , Liebert C orporati on assumes no responsibility, and disclaims all liability for damages resulting from use o f this informa tion or for any e rrors or om issions.
© 2010 Lieber t Corporat ion. All rig hts reser ved throug hout the worl d. Specic ations subje ct to change w ithout not ice.
All name s referred to a re trademar ks or regis tered trad emarks of their r espectiv e owners.
® Lieber t is a registe red tradem ark of the Lieb ert Corp oration. SL-18045 (R02/10) Printed in USA
Emerson Network Power. The global leader in enabling Business-Critical Continuity
AC Power Connectivity DC Power
Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.
Embedded Computing Embedded Power Infrastructure Management & Monitoring
TM
.
Outside Plant Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...