A = Air-Cooled
D = Dual-Cooling, Air-Cooled
W = Water/Glycol
K = GLYCOOL (Liebert Economizer Coil)
H = Dual-Cooling, Water-Cooled
Nominal kW
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons)
Air Distribution
DS = Downflow Standard
VS = Upflow Standard
123456789101112131415
DS035AUA0EI****
Compressor
U - Semi-Hermetic with Four-Step, R-407C
S - Scroll, R-407C
D - Digital Scroll, R-407C
Fan Type
0 = Centrifugal Fans
1 = Electronically
Commutated (EC)
Fans
Humidification
0 - None
I - Infrared
S - Steam Generating
Canister
Reheat Type
0 - None
E - 3-Stage Electric
S - SCR
Voltag e
A - 460/3/60
B - 575/3/60
C - 208/3/60
D - 230/3/60
2 - 380/3/60
Factory Configuration
Number
Liebert DS Model Number
Not all combinations of options are available on all units.
Digital Scroll Compressors
• Not available on 077 and 105 models
• Not compatible with SCR reheat because digital scroll provides variable capacity control
EC Fans, Direct-Drive
• Not available on upflow (VS) configuration
• Liebert Econ-O-Coil
Steam Generating Canister Humidifier
• Not available on upflow (VS) configurations
• Not available on EC fan configurations
575 Volt Option Limitations
• Digital scroll compressors available only on 053, 070 models
GLYCOOL Liebert Economizer Models
• 105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing
Turning Vanes
• Not available on floor stands 6" (152.4mm) tall
• Not available or required on units with EC fans
™
not available on 028, 035, 042 models with 208/230V
1Liebert
®
DS
™
1.0COOLING CONFIGURATIONS
AIR-COOLED
Air-cooled unit piping is spun closed from the
factory and contains a nitrogen holding charge.
Each installation requires field-supplied
refrigerant and piping to a condenser.
GLYCOL-COOLED
Glycol-cooled units are factory-charged and
tested. Field-supplied and field-installed piping is
required from the unit to the drycooler and pump
package.
WATER-COOLED
Water-cooled units are factory-charged and
tested. Field-supplied and field-installed
water piping is required from the unit to the
cooling tower.
GLYCOOL-INTEGRATED FLUID ECONOMIZER
GLYCOOL units are factory-charged and tested. Field-supplied
and field-installed piping is required from the unit to the
drycooler and pump package. An additional Liebert Economizer
coil is included for use when fluid temperatures are sufficiently
low (below room temperature). Economizer cooling is provided
by circulating cold glycol through this second coil, reducing or
eliminating compressor operation.
DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.
NOTE
All field-installed piping must comply with applicable local, state and federal codes.
Cooling Configurations
Liebert® DS
™
2
2.0BLOWER CONFIGURATIONS
Front
Filter
Coil
Blower
Raised
Floor
Return Air
Supply
Air
Front Supply, EC Fans
Front
Filter
Coil
Blower
Raised
Floor
Return Air
Supply
Air
Rear Supply, EC Fans
Applicable to installations
without raised floors
Applicable to installations
without raised floors
Front
Filter
Coil
Blower
Floor
Stand
(optional )
Raised
Floor
Return Air
Supply
Air
Front
Filter
Coil
Blower
Floor Stand
(optional )
Raised
Floor
Return Air
Supply Air
Supply
Air
Under-Floor Supply, EC Fans
Bottom Supply, EC Fans
Figure 1Blower configurations—Downflow, front and rear supply models, EC fans
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Infrared or Steam
Generating Canister
Infrared or Steam
Generating CanisterNoneNone
Liebert® DS
™
10
Table 5Electrical data—Air-cooled systems with centrifugal fans (continued)
Reheat OptionsElectric, Downsized kW
Humidifier OptionsInfrared or Steam Generating CanisterNone
ModelMotor, hpVolts208230460575208230460575
FLA55.452.526.623.952.650.325.319.6
0282.0
0283.0
0353.0
0355.0
0425.0
0427.5
0533.0
0535.0
0705.0
0707.5
0777.5
07710.0
10510.0
10515.0
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
WSA63.961.230.825.663.961.230.823.8
OPD7070353070703525
FLA58.555.32825.155.753.126.720.8
WSA67.064.032.226.867.064.032.225.0
OPD8070353070703525
FLA65.362.130.626.159.156.528.021.3
WSA71.268.233.828.071.268.233.825.7
OPD9080403580804030
FLA71.467.733.428.365.262.130.823.5
WSA77.373.836.630.277.373.836.627.9
OPD9090453590804030
FLA86.482.741.636.173.171.635.828.7
WSA93.589.845.138.986.783.241.732.7
OPD11011050501001005040
FLA93.989.545.039.080.678.439.231.6
WSA101.096.648.541.894.290.045.135.6
OPD12511060501101105045
FLA101.496.049.239.584.380.840.931
WSA109.4104.053.342.5102.798.649.937.8
OPD12512560501101106045
FLA107.5101.652.041.790.486.443.733.2
WSA115.5109.656.144.7108.8104.252.740.0
OPD12512570501251256045
FLA126.1120.257.646.199.79846.535.4
WSA136.5130.662.449.7120.5115.856.242.7
OPD17515080601501257050
FLA133.6127.061.049.0107.2104.849.938.3
WSA144.0137.465.852.6128.0122.659.645.6
OPD17517580601501507050
FLA145138.464.052.6118.4116.252.441.0
WSA156.8150.269.256.6135.1129.861.547.9
OPD20017580701751757060
FLA151.6144.467.054.6125.0122.255.443.0
WSA163.4156.272.258.6141.7135.864.549.9
OPD20020090701751758060
FLA177.4170.288.472.6150.814876.861.0
WSA192.4185.296.378.9175.2168.686.067.4
OPD25022512510022520011090
FLA192.8184.295.478.6166.2162.083.867.0
WSA207.8199.2103.384.9190.6182.693.073.4
OPD25025012510022522511090
Air-Cooled Systems
11Liebert® DS
™
Air-Cooled Systems
See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional
Low-Voltage Terminal Package Connections for keys
to numbered components.
Figure 6Electrical field connections—Upflow and downflow models, single molded case switch
disconnect with main fuses
2
4
Liebert
IntelliSlot
Housing
15
6
60Hz
13
17
5
18
83
88
1
8289
A
24
23
OVERCURRENT PROTECTION DEVICES
CONTACTORS
CONTACTORS, RELAYS, &
OVERLOAD PROTECTORS
Typical orientation of components shown.
6
Component location varies by option and unit size
9
7576949596 97 91
22
16
92
93
80
19
81
12
11
UPFLOW
B
21
7
8
10
20
A
B
CD
Alternate
Location
P64
P67
E
DOWNFLOW
3
DOWNFLOW LOW-VOLT SECTION
CAUTION
Risk of broken or shorted low-voltage
3
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.
50
59
84
5885
37C
38C
37B
38B
37 38 24
51
56
55
7071230
CD
11
SH49-1
49-3
12
Item 12 Installation Conditions
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or
chase as high voltage wires (120-600V).
3. Separate high-voltage wires from CAN wires by 12" (305mm).
4. For runs greater than 350ft (107m), contact Emerson factory.
E
73
72
Point of Hinged Low-Voltage Electric Box
DS UPFLOW LOW VOLT SECTION
DPN000807
Pg. 2, Rev. 8
Liebert® DS
™
12
Air-Cooled Systems
See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional
Low-Voltage Terminal Package Connections for keys
to numbered components.
Figure 7Electrical field connections—Upflow and downflow models, dual fused disconnect switches
Liebert
2
14
4
IntelliSlot
Housing
15
15
13
60 Hz
6
1
1718
8289
24
PRIMARY
83
A
B
Alternate
Alternate
Location
Location
P64
P67
OVERCURRENT PROTECTION DEVICES
SECONDARY
CONTACTORS
A
CD
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS
E
Typical orientation of components shown.
6
Component location varies by option and unit size
9
22
16
19
DOWNFLOW LOW-VOLTAGE SECTION
UPFLOW
92
88
7576949596 97 91
93
80
81
12
11
3
DOWNFLOW
CAUTION:
Risk of broken or shorted low-voltage
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.
3
B
23
21
7
8
10
20
50
E
51
56
55
7071230
11
SH49-1
49-3
72
12
37C
37B
59
84
5885
38C
38B
37 38 24
CD
Item 12 Installation Conditions
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway or
chase as high-voltage wires (120-600V).
3. Separate high-voltage wires from CAN wires by 12" (305mm).
4. Contact Liebert factory for runs greater than 350ft. (107m).
5. All electrical loads may not be capable of being connected to both
power feeds, with automatic transfer switch.
Consult local representative for dual power configurations available.
73
Point of Hinged Low-Voltage
Electric Box
DS UPFLOW LOW-VOLTAGE SECTION
DPN000807
Pg. 3, Rev. 8
13Liebert® DS
™
3.2STANDARD ELECTRICAL CONNECTIONS
Source: DPN000807, Rev. 8
1. Primary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts located in bottom of box.
2. Secondary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts located in top of box.
3. Primary low voltage entrance—Quantity (3) 1.375" (35mm) diameter knockouts located in
bottom of unit.
4. Secondary low voltage entrance—Quantity (3) 1. 375" (35mm) diameter knockouts located in
top of box.
5. Three phase electrical service—Terminals are on main fuse block (disregard if unit has
optional disconnect switch). Three-phase service not by Emerson.
6. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for
Liebert units.
7. Remote unit shutdown—Replace existing jumper between Terminals 37 & 38 with
field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied
Class 1 wiring.
8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a
minimum 75VA, 24VAC rating, between Terminals 24 & 50, 51, 55 & 56. Use field-supplied
Class 1 wiring. Terminal availability varies by unit options.
9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 & 76
for remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring.
10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is
closed across Terminals 70 & 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A,
24VAC maximum load. Use field-supplied Class 1 wiring. When a Liebert DS unit is paired with a
Liebert MC series condenser, remove jumper between Terminal 71 and Terminal 230. Three
wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the
Liebert MC series condenser.
Air-Cooled Systems
Liebert® DS
™
14
3.3OPTIONAL ELECTRICAL CONNECTIONS
Source: DPN000807, Rev. 8
11. Unit factory installed disconnect switch, Fuse Block and Main Fuses—Two types of
disconnect switches are available: Non-Locking and Locking. The Non-Locking Type consists of a
non-automatic molded case switch operational from the outside of the unit. Access to the
high-voltage electric panel compartment can be obtained with the switch in either the On or Off
position. The Locking Type is identical except access to the high-voltage electric panel
compartment can be obtained only with the switch in the Off position. Units with fused
disconnects are provided with a defeater button that allows access to the electrical panel when
power is On. The molded case switch disconnect models contain separate main fuses. Units with
fused disconnect have main fuses within the disconnect. Only fused disconnects are used on dual
disconnect options.
12. Secondary disconnect switch and earth ground
13. Three-phase electrical service—Terminals are on top of disconnect switch. Three-phase
service not by Emerson.
14. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO,
and 93-NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is
not intended to function as or replace any room smoke detection system that may be required by
local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
15. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 & 83 for lockout of
reheat and humidifier.
16. Condensate alarm (with condensate pump option)—On pump high water indication,
normally open dry contact is closed across Terminals 88 & 89 for remote indication. 1A, 24VAC
maximum load. Use field-supplied Class 1 wiring.
17. Remote humidifier—On any call for humidification, normally open dry contact is closed across
Terminals 11 & 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use
Class 1 field-supplied wiring.
18. Auxiliary cool contact—On any call for Econ-O-coil operation, normally open dry contact is
closed across Terminals 72 & 73 on dual cool units only. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
19. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as
37B & 38B, 37C and 38C). Replace jumpers with field-supplied, normally closed switch having a
minimum rating of 75VA, 24VAC. Use field-supplied Class 1 wiring.
20. Common alarm—On any alarm, two additional normally open dry contacts are closed across
Terminals 94 & 95 and 96 & 97 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
21. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is
closed across Terminals 84 & 85 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
22. Liebert Liqui-tect
open dry contact is closed across Terminals 58 & 59 for remote indication (Liebert Liqui-tect
sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
™
shutdown and dry contact—On Liebert Liqui-tect activation, normally
Required for Condenser
cleanout on Water/Glycol or
GLYCOOL/Dual Cool
3"
(77mm)
24-3/8"
(619mm)
Opening
3/4"
(19mm)
Bezels
Shaded area indicates a
recommended minimum
clearance for component access.
3"
(76mm)
(483mm)
19"
3-1/4"
(81mm)
33-3/8"
(848mm)
Air Outlet
Opening
REAR VIEW
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
76"
(1930mm)
2"
(51mm)
FRONT VIEW
AIR INLET OPENING
TOP VIEW
Secondary Entrance
Low-Voltage Connections
A
33-1/2"
(851mm)
19"
(483mm)
Air Outlet
Opening
3-1/4"
(83mm)
B
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals DPN000803, DPN000804 or DPN000900.
A floor stand at least 9" high is recommended if primary connections locations are to be used.
2. If no floor stand is used and unit is placed directly on the floor, then do the following:
a) Use secondary connection locations (shown on standard floor planning submittals).
b) Order a condensate pump.
c) Field pipe condensate and humidier line (if ordered) to secondary connection point in
compressor section.
d) Or order additional SFA's to relocate connection locations
34"
(864mm)
310697
Pg. 1, Rev. 0
Dry Weight, lb (kg) ApproximateDimensions, In. (mm)
Compressor TypeModel
Semi-Hermetic
Scroll / Digital
Source: 310697, Pg. 1, Rev. 0
028-042AB
Air-Cooled1780 (809)
Dual Cool 1930 (877)
Air-Cooled1470 (668)
Dual Cool1620 (736)
86 (2184mm)85 (2159)
73 (1854)72" (1829)
17Liebert® DS
™
Air-Cooled Systems
Figure 10Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), scroll or
digital scroll compressors with centrifugal fans
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
G1
L1
4" (102mm)
L2
11-3/16"
(284mm)
G2
A
FRONT VIEW
SECTION A-A
BLOWER
R
ECS
HUM
CD
E2
ECR
E1
OUTLET
16-1/16"
(408mm)
B
FRONT OF UNIT
73" (1854mm)
A
All dimensions from
rear corner of unit,
including panels
BBlower Outlet21-15/16 (557)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000804, Rev. 3
Y
in. (mm)
Connection Size / Opening
in. (mm)
Liebert® DS
™
18
Air-Cooled Systems
59" (1499mm)
DPN000802
Rev. 2
33"
(838mm)
13"
(330mm)
76"
(1930mm)
72" (1829mm)
Assembled Length
76"
(1930mm)
Assembled
Height
60-3/16"
(1529mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Figure 11Disassembly dimensions—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors with centrifugal fans
Table 8Component weights—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors
Dry Weight, Approximate, lb. (kg)
Component
Compressor Assembly490 (223)490 (223)
Filter and Electric Box Assembly210 (96)210 (96)
Blower and Coil Assembly770 (350)920 (418)
Source: DPN000802, Rev. 2
Air-CooledDual-Cool
19Liebert® DS
™
DPN000795
Rev. 4
Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Shaded area indicates a
recommended minimum
clearance for component
access.
TOP VIEW
FRONT VIEW
Air Inlet Opening
Secondary Entrance
High Volt Connection(s)
Secondary Refrigerant
Piping Entrance
Secondary Entrance
Low Volt Connections
Minimum required
for filter replacement
86" (2184mm)
85" (2159mm)2"
(51mm)
76"
(1930mm)
35"
(889mm)
56-7/8"
(1445mm)
Opening
3/4"
(19mm)
Opening
34"
(864mm)
33"
(838mm)
5"
(127mm)
Bezels
24-3/8"
(619mm)
Air-Cooled Systems
Figure 12Dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with
BBlower Outlet21-15/16 (558)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000803, Rev. 4
Condensate Drain
(infrared humidifier or no humidifier)*
Condensate Drain
(steam generating humidifier)*
W/ Optional Pump46 (1168)29-1/2 (749)1/2" Cu Sweat
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
46 (1168)29-1/2 (749)3/4" FPT
46 (1168)29-1/2 (749)1-1/4" FPT
21Liebert® DS
™
Air-Cooled Systems
39"
991mm
59" (1499mm)
DPN000801
Rev. 2
33"
(838mm)
76"
(1930mm)
26"
(660mm)
85" (2159mm)
Assembled Length
76"
(1930mm)
Assembled
Height
60-3/16"
(1529mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
** Supplied on Dual-Cooling systems only (four-pipe system)
*** Digital scroll compressors not available on DS 077.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000929, Rev 4
Liebert® DS
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
53kW (15 ton) / 70& 77kW (20 & 22 ton)
Condensate Drain
(infrared humidifier or no humidifier)*
Condensate Drain
(steam generating humidifier)*
67-11/16 (1719)30-1/2 (775)3/4" FPT
67-11/16 (1719)30-1/2 (775)1-1/4" FPT
W/ Optional Pump67-11/16 (1719)30-1/2 (775)1/2" Cu Sweat
Blower Outlet (15 x 15)23-1/8 (587)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)27-3/4 (705)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
Blower Outlet (15 x 15)50-3/8 (1280)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)54-3/8 (1381)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Required for Condenser
cleanout on Water/Glycol or
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals DPN000928,
DPN000929 or DPN000933.
A floor stand at least 9" high is recommended if primary connections locations are to be used.
2. If no floor stand is used and unit is placed directly on the floor, then do the following:
a) Use secondary connection locations (shown on standard floor planning submittals).
b) Order a condensate pump.
c) Field pipe condensate and humidier line (if ordered) to secondary connection point in
compressor section.
d) Or order additional SFA's to relocate connection locations
Secondary Refrigerant
Piping Entrance
80" (2032mm)
Opening
24" (610mm)
GLYCOOL/Dual Cool
Minimum required
for filter replacement
Filters are accessible
only through top of unit.
5"
(127mm)
35"
(889mm)
33"
(838mm)
Secondary Entrance
High-Voltage Connection(s)
AIR INLET OPENING
TOP VIEW
A
76"
(1930mm)
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
2"
(51mm)
FRONT VIEW
B
Dry Weight, lb (kg) ApproximateDimensions, in. (mm)
Compressor Type
Semi-Hermetic
Scroll / Digital
* Digital scroll compressors not available on 077 models
Source: 310697, Pg. 2, Rev. 0
Model537077 *AB
Air-Cooled2350 (1069)2400 (1091)2450 (1114)
Dual Cool2530 (11502580 (1173)2630 (1196)
Air-Cooled1920 (873)1970 (896)2020 (919)
Dual Cool2100 (955)2150 (978)2200 (1000)
15-1/8"
(384mm)
29-5/8"
(752mm)
3-1/4"
(83mm)
25-5/8"
(619mm)
Opening
3/4"
Secondary Entrance
Low-Voltage Connections
Air Outlet
Opening
(19mm)
3-1/8"
(79mm)
Shaded area indicates a
recommended minimum
clearance for component access.
15-1/8"
(384mm)
29-5/8"
(752mm)
3-1/4"
(83mm)
Air Outlet
Opening
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
REAR VIEW
109 (2769)108 (2743)
34"
(864mm)
310697
Pg. 2, Rev. 0
98 (2489)97 (2464)
25Liebert® DS
™
Air-Cooled Systems
12-3/16"
(310mm)
FRONT OF UNIT
FRONT VIEW
DPN002182
Rev. 1
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ECS
ECR
E1
E2
CD
R
LV1
LV2
LV3
X
AA
Y
O
All dimensions from
rear corner of unit
including panels
35"
(889mm)
BLOWER
OUTLET
HUM
L1 L2 G1
G2
B1
4" (102mm)
98" (2489mm)
Digital scroll compressors not
available on 077 models.
Figure 18Primary connection locations—downflow air-cooled 53-77kW (15-22 ton), scroll or digital
scroll compressors with EC fans, front, rear or bottom discharge
Table 14Piping details—downflow air-cooled 53-77kW (15-22 ton) with EC fans, scroll or digital scroll
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cooling systems only (four-pipe system)
*** Digital scroll compressors not available on DS 077
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN002182, Rev. 1
Liebert® DS
compressors ***
Condensate Drain
(Infrared Humidifier or No Humidifier)*
W/ Optional Pump68-3/8 (1737)31-3/8 (797)1/2 Cu Sweat
™
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
53kW (15 ton)/ 70 & 77kW (20 & 22 ton)
68-3/8 (1737)31-3/8 (797)3/4 FPT
26
in. (mm)
Loading...
+ 146 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.