A = Air-Cooled
D = Dual-Cooling, Air-Cooled
W = Water/Glycol
K = GLYCOOL (Liebert Economizer Coil)
H = Dual-Cooling, Water-Cooled
Nominal kW
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons)
Air Distribution
DS = Downflow Standard
VS = Upflow Standard
123456789101112131415
DS035AUA0EI****
Compressor
U - Semi-Hermetic with Four-Step, R-407C
S - Scroll, R-407C
D - Digital Scroll, R-407C
Fan Type
0 = Centrifugal Fans
1 = Electronically
Commutated (EC)
Fans
Humidification
0 - None
I - Infrared
S - Steam Generating
Canister
Reheat Type
0 - None
E - 3-Stage Electric
S - SCR
Voltag e
A - 460/3/60
B - 575/3/60
C - 208/3/60
D - 230/3/60
2 - 380/3/60
Factory Configuration
Number
Liebert DS Model Number
Not all combinations of options are available on all units.
Digital Scroll Compressors
• Not available on 077 and 105 models
• Not compatible with SCR reheat because digital scroll provides variable capacity control
EC Fans, Direct-Drive
• Not available on upflow (VS) configuration
• Liebert Econ-O-Coil
Steam Generating Canister Humidifier
• Not available on upflow (VS) configurations
• Not available on EC fan configurations
575 Volt Option Limitations
• Digital scroll compressors available only on 053, 070 models
GLYCOOL Liebert Economizer Models
• 105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing
Turning Vanes
• Not available on floor stands 6" (152.4mm) tall
• Not available or required on units with EC fans
™
not available on 028, 035, 042 models with 208/230V
1Liebert
®
DS
™
Page 6
1.0COOLING CONFIGURATIONS
AIR-COOLED
Air-cooled unit piping is spun closed from the
factory and contains a nitrogen holding charge.
Each installation requires field-supplied
refrigerant and piping to a condenser.
GLYCOL-COOLED
Glycol-cooled units are factory-charged and
tested. Field-supplied and field-installed piping is
required from the unit to the drycooler and pump
package.
WATER-COOLED
Water-cooled units are factory-charged and
tested. Field-supplied and field-installed
water piping is required from the unit to the
cooling tower.
GLYCOOL-INTEGRATED FLUID ECONOMIZER
GLYCOOL units are factory-charged and tested. Field-supplied
and field-installed piping is required from the unit to the
drycooler and pump package. An additional Liebert Economizer
coil is included for use when fluid temperatures are sufficiently
low (below room temperature). Economizer cooling is provided
by circulating cold glycol through this second coil, reducing or
eliminating compressor operation.
DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.
NOTE
All field-installed piping must comply with applicable local, state and federal codes.
Cooling Configurations
Liebert® DS
™
2
Page 7
2.0BLOWER CONFIGURATIONS
Front
Filter
Coil
Blower
Raised
Floor
Return Air
Supply
Air
Front Supply, EC Fans
Front
Filter
Coil
Blower
Raised
Floor
Return Air
Supply
Air
Rear Supply, EC Fans
Applicable to installations
without raised floors
Applicable to installations
without raised floors
Front
Filter
Coil
Blower
Floor
Stand
(optional )
Raised
Floor
Return Air
Supply
Air
Front
Filter
Coil
Blower
Floor Stand
(optional )
Raised
Floor
Return Air
Supply Air
Supply
Air
Under-Floor Supply, EC Fans
Bottom Supply, EC Fans
Figure 1Blower configurations—Downflow, front and rear supply models, EC fans
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Infrared or Steam
Generating Canister
Infrared or Steam
Generating CanisterNoneNone
Liebert® DS
™
10
Page 15
Table 5Electrical data—Air-cooled systems with centrifugal fans (continued)
Reheat OptionsElectric, Downsized kW
Humidifier OptionsInfrared or Steam Generating CanisterNone
ModelMotor, hpVolts208230460575208230460575
FLA55.452.526.623.952.650.325.319.6
0282.0
0283.0
0353.0
0355.0
0425.0
0427.5
0533.0
0535.0
0705.0
0707.5
0777.5
07710.0
10510.0
10515.0
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
WSA63.961.230.825.663.961.230.823.8
OPD7070353070703525
FLA58.555.32825.155.753.126.720.8
WSA67.064.032.226.867.064.032.225.0
OPD8070353070703525
FLA65.362.130.626.159.156.528.021.3
WSA71.268.233.828.071.268.233.825.7
OPD9080403580804030
FLA71.467.733.428.365.262.130.823.5
WSA77.373.836.630.277.373.836.627.9
OPD9090453590804030
FLA86.482.741.636.173.171.635.828.7
WSA93.589.845.138.986.783.241.732.7
OPD11011050501001005040
FLA93.989.545.039.080.678.439.231.6
WSA101.096.648.541.894.290.045.135.6
OPD12511060501101105045
FLA101.496.049.239.584.380.840.931
WSA109.4104.053.342.5102.798.649.937.8
OPD12512560501101106045
FLA107.5101.652.041.790.486.443.733.2
WSA115.5109.656.144.7108.8104.252.740.0
OPD12512570501251256045
FLA126.1120.257.646.199.79846.535.4
WSA136.5130.662.449.7120.5115.856.242.7
OPD17515080601501257050
FLA133.6127.061.049.0107.2104.849.938.3
WSA144.0137.465.852.6128.0122.659.645.6
OPD17517580601501507050
FLA145138.464.052.6118.4116.252.441.0
WSA156.8150.269.256.6135.1129.861.547.9
OPD20017580701751757060
FLA151.6144.467.054.6125.0122.255.443.0
WSA163.4156.272.258.6141.7135.864.549.9
OPD20020090701751758060
FLA177.4170.288.472.6150.814876.861.0
WSA192.4185.296.378.9175.2168.686.067.4
OPD25022512510022520011090
FLA192.8184.295.478.6166.2162.083.867.0
WSA207.8199.2103.384.9190.6182.693.073.4
OPD25025012510022522511090
Air-Cooled Systems
11Liebert® DS
™
Page 16
Air-Cooled Systems
See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional
Low-Voltage Terminal Package Connections for keys
to numbered components.
Figure 6Electrical field connections—Upflow and downflow models, single molded case switch
disconnect with main fuses
2
4
Liebert
IntelliSlot
Housing
15
6
60Hz
13
17
5
18
83
88
1
8289
A
24
23
OVERCURRENT PROTECTION DEVICES
CONTACTORS
CONTACTORS, RELAYS, &
OVERLOAD PROTECTORS
Typical orientation of components shown.
6
Component location varies by option and unit size
9
7576949596 97 91
22
16
92
93
80
19
81
12
11
UPFLOW
B
21
7
8
10
20
A
B
CD
Alternate
Location
P64
P67
E
DOWNFLOW
3
DOWNFLOW LOW-VOLT SECTION
CAUTION
Risk of broken or shorted low-voltage
3
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.
50
59
84
5885
37C
38C
37B
38B
37 38 24
51
56
55
7071230
CD
11
SH49-1
49-3
12
Item 12 Installation Conditions
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or
chase as high voltage wires (120-600V).
3. Separate high-voltage wires from CAN wires by 12" (305mm).
4. For runs greater than 350ft (107m), contact Emerson factory.
E
73
72
Point of Hinged Low-Voltage Electric Box
DS UPFLOW LOW VOLT SECTION
DPN000807
Pg. 2, Rev. 8
Liebert® DS
™
12
Page 17
Air-Cooled Systems
See 3.2 - Standard Electrical Connections, 3.3 Optional Electrical Connections and 3.4 - Optional
Low-Voltage Terminal Package Connections for keys
to numbered components.
Figure 7Electrical field connections—Upflow and downflow models, dual fused disconnect switches
Liebert
2
14
4
IntelliSlot
Housing
15
15
13
60 Hz
6
1
1718
8289
24
PRIMARY
83
A
B
Alternate
Alternate
Location
Location
P64
P67
OVERCURRENT PROTECTION DEVICES
SECONDARY
CONTACTORS
A
CD
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS
E
Typical orientation of components shown.
6
Component location varies by option and unit size
9
22
16
19
DOWNFLOW LOW-VOLTAGE SECTION
UPFLOW
92
88
7576949596 97 91
93
80
81
12
11
3
DOWNFLOW
CAUTION:
Risk of broken or shorted low-voltage
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.
3
B
23
21
7
8
10
20
50
E
51
56
55
7071230
11
SH49-1
49-3
72
12
37C
37B
59
84
5885
38C
38B
37 38 24
CD
Item 12 Installation Conditions
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway or
chase as high-voltage wires (120-600V).
3. Separate high-voltage wires from CAN wires by 12" (305mm).
4. Contact Liebert factory for runs greater than 350ft. (107m).
5. All electrical loads may not be capable of being connected to both
power feeds, with automatic transfer switch.
Consult local representative for dual power configurations available.
73
Point of Hinged Low-Voltage
Electric Box
DS UPFLOW LOW-VOLTAGE SECTION
DPN000807
Pg. 3, Rev. 8
13Liebert® DS
™
Page 18
3.2STANDARD ELECTRICAL CONNECTIONS
Source: DPN000807, Rev. 8
1. Primary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts located in bottom of box.
2. Secondary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts located in top of box.
3. Primary low voltage entrance—Quantity (3) 1.375" (35mm) diameter knockouts located in
bottom of unit.
4. Secondary low voltage entrance—Quantity (3) 1. 375" (35mm) diameter knockouts located in
top of box.
5. Three phase electrical service—Terminals are on main fuse block (disregard if unit has
optional disconnect switch). Three-phase service not by Emerson.
6. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for
Liebert units.
7. Remote unit shutdown—Replace existing jumper between Terminals 37 & 38 with
field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied
Class 1 wiring.
8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a
minimum 75VA, 24VAC rating, between Terminals 24 & 50, 51, 55 & 56. Use field-supplied
Class 1 wiring. Terminal availability varies by unit options.
9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 & 76
for remote indication. 1A, 24VAC maximum load. Use Class 1 field-supplied wiring.
10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is
closed across Terminals 70 & 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A,
24VAC maximum load. Use field-supplied Class 1 wiring. When a Liebert DS unit is paired with a
Liebert MC series condenser, remove jumper between Terminal 71 and Terminal 230. Three
wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the
Liebert MC series condenser.
Air-Cooled Systems
Liebert® DS
™
14
Page 19
3.3OPTIONAL ELECTRICAL CONNECTIONS
Source: DPN000807, Rev. 8
11. Unit factory installed disconnect switch, Fuse Block and Main Fuses—Two types of
disconnect switches are available: Non-Locking and Locking. The Non-Locking Type consists of a
non-automatic molded case switch operational from the outside of the unit. Access to the
high-voltage electric panel compartment can be obtained with the switch in either the On or Off
position. The Locking Type is identical except access to the high-voltage electric panel
compartment can be obtained only with the switch in the Off position. Units with fused
disconnects are provided with a defeater button that allows access to the electrical panel when
power is On. The molded case switch disconnect models contain separate main fuses. Units with
fused disconnect have main fuses within the disconnect. Only fused disconnects are used on dual
disconnect options.
12. Secondary disconnect switch and earth ground
13. Three-phase electrical service—Terminals are on top of disconnect switch. Three-phase
service not by Emerson.
14. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO,
and 93-NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is
not intended to function as or replace any room smoke detection system that may be required by
local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
15. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 & 83 for lockout of
reheat and humidifier.
16. Condensate alarm (with condensate pump option)—On pump high water indication,
normally open dry contact is closed across Terminals 88 & 89 for remote indication. 1A, 24VAC
maximum load. Use field-supplied Class 1 wiring.
17. Remote humidifier—On any call for humidification, normally open dry contact is closed across
Terminals 11 & 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use
Class 1 field-supplied wiring.
18. Auxiliary cool contact—On any call for Econ-O-coil operation, normally open dry contact is
closed across Terminals 72 & 73 on dual cool units only. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
19. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as
37B & 38B, 37C and 38C). Replace jumpers with field-supplied, normally closed switch having a
minimum rating of 75VA, 24VAC. Use field-supplied Class 1 wiring.
20. Common alarm—On any alarm, two additional normally open dry contacts are closed across
Terminals 94 & 95 and 96 & 97 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
21. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is
closed across Terminals 84 & 85 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
22. Liebert Liqui-tect
open dry contact is closed across Terminals 58 & 59 for remote indication (Liebert Liqui-tect
sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
™
shutdown and dry contact—On Liebert Liqui-tect activation, normally
Required for Condenser
cleanout on Water/Glycol or
GLYCOOL/Dual Cool
3"
(77mm)
24-3/8"
(619mm)
Opening
3/4"
(19mm)
Bezels
Shaded area indicates a
recommended minimum
clearance for component access.
3"
(76mm)
(483mm)
19"
3-1/4"
(81mm)
33-3/8"
(848mm)
Air Outlet
Opening
REAR VIEW
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
76"
(1930mm)
2"
(51mm)
FRONT VIEW
AIR INLET OPENING
TOP VIEW
Secondary Entrance
Low-Voltage Connections
A
33-1/2"
(851mm)
19"
(483mm)
Air Outlet
Opening
3-1/4"
(83mm)
B
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals DPN000803, DPN000804 or DPN000900.
A floor stand at least 9" high is recommended if primary connections locations are to be used.
2. If no floor stand is used and unit is placed directly on the floor, then do the following:
a) Use secondary connection locations (shown on standard floor planning submittals).
b) Order a condensate pump.
c) Field pipe condensate and humidier line (if ordered) to secondary connection point in
compressor section.
d) Or order additional SFA's to relocate connection locations
34"
(864mm)
310697
Pg. 1, Rev. 0
Dry Weight, lb (kg) ApproximateDimensions, In. (mm)
Compressor TypeModel
Semi-Hermetic
Scroll / Digital
Source: 310697, Pg. 1, Rev. 0
028-042AB
Air-Cooled1780 (809)
Dual Cool 1930 (877)
Air-Cooled1470 (668)
Dual Cool1620 (736)
86 (2184mm)85 (2159)
73 (1854)72" (1829)
17Liebert® DS
™
Page 22
Air-Cooled Systems
Figure 10Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), scroll or
digital scroll compressors with centrifugal fans
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
G1
L1
4" (102mm)
L2
11-3/16"
(284mm)
G2
A
FRONT VIEW
SECTION A-A
BLOWER
R
ECS
HUM
CD
E2
ECR
E1
OUTLET
16-1/16"
(408mm)
B
FRONT OF UNIT
73" (1854mm)
A
All dimensions from
rear corner of unit,
including panels
BBlower Outlet21-15/16 (557)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000804, Rev. 3
Y
in. (mm)
Connection Size / Opening
in. (mm)
Liebert® DS
™
18
Page 23
Air-Cooled Systems
59" (1499mm)
DPN000802
Rev. 2
33"
(838mm)
13"
(330mm)
76"
(1930mm)
72" (1829mm)
Assembled Length
76"
(1930mm)
Assembled
Height
60-3/16"
(1529mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Figure 11Disassembly dimensions—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors with centrifugal fans
Table 8Component weights—downflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors
Dry Weight, Approximate, lb. (kg)
Component
Compressor Assembly490 (223)490 (223)
Filter and Electric Box Assembly210 (96)210 (96)
Blower and Coil Assembly770 (350)920 (418)
Source: DPN000802, Rev. 2
Air-CooledDual-Cool
19Liebert® DS
™
Page 24
DPN000795
Rev. 4
Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Shaded area indicates a
recommended minimum
clearance for component
access.
TOP VIEW
FRONT VIEW
Air Inlet Opening
Secondary Entrance
High Volt Connection(s)
Secondary Refrigerant
Piping Entrance
Secondary Entrance
Low Volt Connections
Minimum required
for filter replacement
86" (2184mm)
85" (2159mm)2"
(51mm)
76"
(1930mm)
35"
(889mm)
56-7/8"
(1445mm)
Opening
3/4"
(19mm)
Opening
34"
(864mm)
33"
(838mm)
5"
(127mm)
Bezels
24-3/8"
(619mm)
Air-Cooled Systems
Figure 12Dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with
BBlower Outlet21-15/16 (558)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000803, Rev. 4
Condensate Drain
(infrared humidifier or no humidifier)*
Condensate Drain
(steam generating humidifier)*
W/ Optional Pump46 (1168)29-1/2 (749)1/2" Cu Sweat
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
46 (1168)29-1/2 (749)3/4" FPT
46 (1168)29-1/2 (749)1-1/4" FPT
21Liebert® DS
™
Page 26
Air-Cooled Systems
39"
991mm
59" (1499mm)
DPN000801
Rev. 2
33"
(838mm)
76"
(1930mm)
26"
(660mm)
85" (2159mm)
Assembled Length
76"
(1930mm)
Assembled
Height
60-3/16"
(1529mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
** Supplied on Dual-Cooling systems only (four-pipe system)
*** Digital scroll compressors not available on DS 077.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000929, Rev 4
Liebert® DS
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
53kW (15 ton) / 70& 77kW (20 & 22 ton)
Condensate Drain
(infrared humidifier or no humidifier)*
Condensate Drain
(steam generating humidifier)*
67-11/16 (1719)30-1/2 (775)3/4" FPT
67-11/16 (1719)30-1/2 (775)1-1/4" FPT
W/ Optional Pump67-11/16 (1719)30-1/2 (775)1/2" Cu Sweat
Blower Outlet (15 x 15)23-1/8 (587)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)27-3/4 (705)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
Blower Outlet (15 x 15)50-3/8 (1280)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)54-3/8 (1381)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
Required for Condenser
cleanout on Water/Glycol or
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals DPN000928,
DPN000929 or DPN000933.
A floor stand at least 9" high is recommended if primary connections locations are to be used.
2. If no floor stand is used and unit is placed directly on the floor, then do the following:
a) Use secondary connection locations (shown on standard floor planning submittals).
b) Order a condensate pump.
c) Field pipe condensate and humidier line (if ordered) to secondary connection point in
compressor section.
d) Or order additional SFA's to relocate connection locations
Secondary Refrigerant
Piping Entrance
80" (2032mm)
Opening
24" (610mm)
GLYCOOL/Dual Cool
Minimum required
for filter replacement
Filters are accessible
only through top of unit.
5"
(127mm)
35"
(889mm)
33"
(838mm)
Secondary Entrance
High-Voltage Connection(s)
AIR INLET OPENING
TOP VIEW
A
76"
(1930mm)
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
2"
(51mm)
FRONT VIEW
B
Dry Weight, lb (kg) ApproximateDimensions, in. (mm)
Compressor Type
Semi-Hermetic
Scroll / Digital
* Digital scroll compressors not available on 077 models
Source: 310697, Pg. 2, Rev. 0
Model537077 *AB
Air-Cooled2350 (1069)2400 (1091)2450 (1114)
Dual Cool2530 (11502580 (1173)2630 (1196)
Air-Cooled1920 (873)1970 (896)2020 (919)
Dual Cool2100 (955)2150 (978)2200 (1000)
15-1/8"
(384mm)
29-5/8"
(752mm)
3-1/4"
(83mm)
25-5/8"
(619mm)
Opening
3/4"
Secondary Entrance
Low-Voltage Connections
Air Outlet
Opening
(19mm)
3-1/8"
(79mm)
Shaded area indicates a
recommended minimum
clearance for component access.
15-1/8"
(384mm)
29-5/8"
(752mm)
3-1/4"
(83mm)
Air Outlet
Opening
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
REAR VIEW
109 (2769)108 (2743)
34"
(864mm)
310697
Pg. 2, Rev. 0
98 (2489)97 (2464)
25Liebert® DS
™
Page 30
Air-Cooled Systems
12-3/16"
(310mm)
FRONT OF UNIT
FRONT VIEW
DPN002182
Rev. 1
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ECS
ECR
E1
E2
CD
R
LV1
LV2
LV3
X
AA
Y
O
All dimensions from
rear corner of unit
including panels
35"
(889mm)
BLOWER
OUTLET
HUM
L1 L2 G1
G2
B1
4" (102mm)
98" (2489mm)
Digital scroll compressors not
available on 077 models.
Figure 18Primary connection locations—downflow air-cooled 53-77kW (15-22 ton), scroll or digital
scroll compressors with EC fans, front, rear or bottom discharge
Table 14Piping details—downflow air-cooled 53-77kW (15-22 ton) with EC fans, scroll or digital scroll
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cooling systems only (four-pipe system)
*** Digital scroll compressors not available on DS 077
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN002182, Rev. 1
Liebert® DS
compressors ***
Condensate Drain
(Infrared Humidifier or No Humidifier)*
W/ Optional Pump68-3/8 (1737)31-3/8 (797)1/2 Cu Sweat
™
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
53kW (15 ton)/ 70 & 77kW (20 & 22 ton)
68-3/8 (1737)31-3/8 (797)3/4 FPT
26
in. (mm)
Page 31
Air-Cooled Systems
Digital scroll compressors
not available on DS 077.
Figure 19Disassembly dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll
compressors
Filter & Electric
Box Assembly
Forward curved
blowers shown.
DA units only
available with EC
blowers, optional
on DS units.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cooling Systems only (four-pipe system)
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN000928, Rev. 4
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
Condensate Drain
(infrared humidifier or no humidifier) *
Condensate Drain
(steam generating humidifier)*
67-11/16 (1719) 30-1/2 (775)3/4" FPT
67-11/16 (1719) 30-1/2 (775)1-1/4" FPT
W/ Optional Pump67-11/16 (1719) 30-1/2 (775)1/2" Cu Sweat
Blower Outlet (15 x 15)23-1/8 (587)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)27-3/4 (705)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
Blower Outlet (15 x 15)50-3/8 (1280)18-1/16 (459)18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)54-3/8 (1381)18-1/16 (459)14-3/4 x 16-1/16 (375 x 408)
29Liebert® DS
™
Page 34
Air-Cooled Systems
16-7/16"
(418mm)
FRONT OF UNIT
FRONT VIEW
DPN002179
Rev. 0
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ECS ECR
E1
CD
R
LV1
LV2
LV3
X
AA
Y
O
All dimensions from
rear corner of unit
including panels
B1Blower Outlet4-1/2 (114)33 (838)58-3/8 x 30 (1483x762)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
** Supplied on Dual-Cooling systems only (four-pipe system)
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN002179, Rev. 0
Liebert® DS
compressors
X
in. (mm)
RRefrigerant Access82-3/4 (2102)13-7/8 (352)16-7/16 x 4 (4181x102)
L1Liquid Line System 197 (2464)16-7/8 (428)1/2 / 5/8 Cu Sweat
L2Liquid Line System 293-5/16 (2370)16-7/8 (428)1/2 / 5/8 Cu Sweat
Condensate Drain
(Infrared Humidifier or No Humidifier)*
68-3/8 (1737)31-3/8 (797)3/4 FPT
W/ Optional Pump68-3/8 (1737)31-3/8 (797)1/2 Cu Sweat
Y
in. (mm)
Connection Size / Opening
in. (mm)
53kW (15 ton) /70 & 77kw (20 & 22 ton)
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
B1Blower Outlet27-7/8 (708)18 (457)14-1/2 x 15-11/16 (368 x 398)
B2Blower Outlet52-1/16 (1322)18 (457)14-1/2 x 15-11/16 (368 x 398)
B3Blower Outlet76-1/4 (1937)18 (457)14-1/2 x 15-11/16 (368 x 398)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on
** Digital scroll compressors not available on DS 105
*
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN001014, Rev. 3
Condensate Drain
(steam generating humidifier)*
Dual-Cooling systems only (four-pipe system)
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
83-13/16 (2129)30 (762)3/4" FPT
83-13/16 (2129)30 (762)1-1/4" FPT
W/ Optional Pump83-13/16 (2129)30 (762)1/2" Cu Sweat
33Liebert® DS
Air-Cooled Systems
in. (mm)
™
Page 38
Air-Cooled Systems
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals DPN001014 or DPN001015.
A floor stand at least 9" high is recommended if primary connections locations are to be used.
2. If no floor stand is used and unit is placed directly on the floor, then do the following:
a) Use secondary connection locations (shown on standard floor planning submittals).
b) Order a condensate pump.
c) Field pipe condensate and humidier line (if ordered) to secondary connection point in
compressor section.
d) Or order additional SFA's to relocate connection locations
Secondary Entrance
High-Voltage Connection(s)
Shaded area indicates a
recommended minimum
clearance for component access.
Secondary Refrigerant
Piping Entrance
Secondary Entrance
Low-Voltage Connections
TOP VIEW
FRONT VIEW
310697
Pg. 3, Rev. 0
Air Outlet
Opening
Air Outlet
Opening
Air Outlet
Opening
3/4"
(19mm)
25-5/8"
(649mm)
24-7/8"
(649mm)
28-1/4"
(718mm)
16-1/8"
(410mm)
16-1/8"
(410mm)
16-1/8"
(410mm)
24-3/8"
(619mm)
Opening
102-7/8" (2611mm)
Opening
132" (3353mm)
30-7/8"
(783mm)
57-1/2"
(1459mm)
131" (3326mm)
3/4"
(19mm)
33"
(838mm)
35"
(889mm)
5"
(127mm)
34"
(864mm)
Required for Condenser
cleanout on Water/Glycol or
GLYCOOL/Dual Cool
Downflow electrical
connections can be made
from top or bottom of unit
24" (610mm)
Minimum required
for filter replacement
Filters are accessible
only through top of unit.
AIR INLET OPENING
76"
(1930mm)
Figure 26Dimensions—downflow, air-cooled, 105kW (30 ton), front discharge models with EC fans
Dry Weight, lb (kg) Approximate
Model105
Air-Cooled
2774 (1258)
Dual Cool3134 (1422)
Air-Cooled
2654 (1204)
Dual Cool3014 (1367)
Compressor Type
Semi-Hermetic
Scroll
Digital scroll compressors not available on DS 105
Source: 310697, Pg. 3, Rev. 0
Liebert® DS
™
34
Page 39
Air-Cooled Systems
16-7/16"
(418mm)
FRONT OF UNIT
FRONT VIEW
DPN002154
Rev. 0
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ECS
ECR
E1
E2
CD
LV1
LV2
LV3
X
Y
O
A
A
All dimensions from
rear corner of unit
including panels
35"
(889mm)
BLOWER
OUTLET
HUM
L1
L2
G1 G2
B1
R
4" (102mm)
132" (3353mm)
Digital scroll compressors
not available on 105
models.
Figure 27Primary connection locations—downflow, air-cooled 105kW (30 ton), standard scroll and
semi-hermetic compressors with EC fans, front, rear or bottom discharge
Table 22Piping data—downflow, air-cooled 105kW (30 ton) with EC fans, standard scroll*** and
PointDescription
RRefrigerant Access109 (2769)15-3/4 (400)16-7/16 x 4 (418 x 102)
L1Liquid Line System 1121-3/4 (3092)16-3/4 (425)5/8 Cu Sweat
L2Liquid Line System 2118-1/8 (3000)16-3/4 (425)5/8 Cu Sweat
G1Hot Gas Discharge 1118-1/4 (3004)14-1/4 (362)1-1/8 Cu Sweat
G2Hot Gas Discharge 2115-5/8 (2937)14-1/4 (362)1-1/8 Cu Sweat
CD
HUMHumidifier Supply Line85-5/16 (2167)32-1/2 (825)1/4 Cu Sweat
ECS **Econ-O-Coil Supply101-7/8 (2588)29 (737)2-5/8 Cu Sweat
ECR **Econ-O-Coil Return 94-9/16 (2402)29 (737)2-5/8 Cu Sweat
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cooling systems only (four-pipe system)
*
** Digital scroll compressors not available on DS 105
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN002154, Rev. 0
semi-hermetic compressors
X
in. (mm)
Condensate Drain
(Infrared Humidifier or No Humidifier)*
87-3/8 (2220)31 (787)3/4 FPT
W/ Optional Pump 83-13/16 (2129)30 (762)1/2 Cu Sweat
4-1/2 (114)33 (838)
Y
in. (mm)
Connection Size / Opening
in. (mm)
77-3/8 x 30 (1965 x 762)
35Liebert® DS
™
Page 40
Air-Cooled Systems
DPN001058
Rev. 2
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Filter & Electric Box Assembly
Compressor Assembly
Blower & Coil
Assembly
39"
(991mm)
41-11/16"
(1059mm)
76"
(1930mm)
Assembled Height
59-7/16"
(1510mm)
37"
(940mm)
105" (2667mm)
131" (3327mm)
Assembled Length
76"
(1930mm)
26"
(660mm)
33"
(838mm)
Digital scroll compressors not
available on 105 models.
Figure 28Disassembly dimensions—downflow, air-cooled, 105kW (30 ton), standard scroll compressors
Figure 30Dimensions—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors with
centrifugal fans
Alternate Refrigerant
Piping Entrance
Note: Front air return unit shown. For
33"
(838mm)
35"
(889mm)
High-Volt Connection(s)
1-1/2"
(38mm)
TOP VIEW
73"
(1854mm)
Low-Volt Connection(s)
rear return unit, in addition to front service
area shown, also include 25" (635mm) on
one side of unit for access to rear return
filter box. See DPN001196.
3/4" (19mm)
Bezels
Minimum required
for blower replacement
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
2"
(51mm)
72" (1829mm)
FRONT VIEW
recommended minimum
clearance for component
access.
DPN001163
Rev. 2
Table 25Weights—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors
Dry Weight, Approximate, lb. (kg)
Model TypeForward-Curved Fans
Air-Cooled1520 (689)
Dual-Cool1670 (758)
Source: DPN001163, Rev. 2
24"
(610mm)
Liebert® DS
™
38
Page 43
Air-Cooled Systems
DPN001119
Rev. 2
O
X
Y
E1
E2
LV1
LV2
LV3
BLOWER
OUTLET
L1
L2
G1
G2
R2
L1 L2 G1G2
R1
FRONT OF UNIT
3.
3.
3.
4.
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
Field routed alternatives for refrigerant
gas and liquid line connection points.
See submittal page DPN001120 for
blower outlet and deck dimensional data.
All dimensions from
rear corner of unit
including panels
73" (1854mm)
LEFT SIDE SECTION
35"
(889mm)
Factory Location
FRONT SECTION
TOP VIEW
CGD*
CGD*
R3
6"
(152mm)
17-3/16"
(437mm)
3-7/8"
(98mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
4
3
4-1/8" (105mm)
10-1/8"
(257mm)
HUM
CPD
ECR
ECS
11-1/8"
(283mm)
4" (102mm)
17-1/16"
(434mm)
(Left Front Panel Not Shown)
3
3
3
Figure 31Primary connection locations—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors with centrifugal fans
Table 26Piping data—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressors
PointDescription
R1Refrigerant Access (Top)60-1/2 (1537)1-7/8" (48mm)10-1/8 x 4-1/8 (257 x 105)
R2Refrigerant Access (Bottom)59-3/8" (1508mm)14-3/4" (375mm)11-1/8 x 4 (283 x 102)
L1Liquid Line System 170" (1778mm)16-3/4 (425)1/2" Cu Sweat
L2Liquid Line System 267-5/8" (1718mm)16-3/4 (425)1/2" Cu Sweat
G1Hot Gas Discharge 165-3/8" (1661mm)16-5/8 (422)5/8" Cu Sweat
G2Hot Gas Discharge 263" (1600mm)16-5/8 (422)5/8" Cu Sweat
R3Refrigerant Access (Side)——6 x 17-3/16 (152 x 437)
CGD*Condensate Gravity Drain——3/4" FPT
CPDCondensate Pump Discharge (Opt)56-1/4 (1429)11-1/8 (283)1/2" Cu Sweat
HUMHumidifier Supply Line56-1/4 (1429)9-1/8 (233)1/4" Cu Sweat
ECS**Econ-O-Coil Supply56 (1423)7-5/16 (186)1-5/8" Cu Sweat
ECR**Econ-O-Coil Return56 (1423)4-1/2 (114)1-5/8" Cu Sweat
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
** Supplied on Dual-Cool systems only (four-pipe system)
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-
18825.
Source: DPN001119, Rev. 2
in. (mm)
X
Y
in. (mm)
Connection Size / Opening
in. (mm)
39Liebert® DS
™
Page 44
Air-Cooled Systems
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
31-1/4"
(794mm)
76" (1930mm)
Assembled
Height
45-13/16"
(1163mm)
DPN001172
Rev. 1
59" (1499mm)
72"
(1829mm)
13"
(330mm)
33"
(838mm)
76"
(1930mm)
Compressor Assembly
Filter & Coil
Assembly
Blower & Electric
Box Assembly
Assembled Length
Figure 32Disassembly dimensions—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors with centrifugal fans
40
Table 27Component weights—upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll
compressors
Dry Weight, Approximate, Including Panels, lb (kg)
Component
Compressor Assembly490 (223)490 (223)
Blower and Electric Box Assembly
(Forward-Curved Fans)
Filter and Coil Assembly520 (236)670 (304)
Source: DPN001172, Rev. 1
Liebert® DS
™
Air-CooledDual-Cool
510 (231)510 (231)
Page 45
Air-Cooled Systems
Figure 33Dimensions—upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressors with
centrifugal fans
Alternate Refrigerant
Piping Entrance
Note: Front air return unit shown. For
rear return unit, in addition to front service
33"
(838mm)
35"
(889mm)
High-Volt Connection(s)
1-1/2"
(38mm)
TOP VIEW
86" (2184mm)
Low-Volt
Connection(s)
area shown, also include 25" (635mm) on
one side of unit for access to rear return
filter box. See DPN001196.
3/4"
(19mm)
Bezels
Minimum required
for blower replacement
24"
(610mm)
76"
(1930mm)
Shaded area indicates a
recommended minimum
clearance for component
access.
All dimensions from
rear corner of unit
including panels
Blower
Outlet
22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
Field-routed alternatives for refrigerant
gas and liquid line connection points.
See submittal page DPN001120 for
blower outlet and deck dimensional data.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cool systems only (four-pipe system)
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN001114, Rev. 2
Liebert® DS
™
X
in. (mm)
Y
in. (mm)
42
Connection Size / Opening
in. (mm)
Page 47
Air-Cooled Systems
DPN001171
Rev. 1
31-1/4"
(794mm)
45-13/16"
(1163mm)
76"
(1930mm)
Assembled\
Height
85" (2159mm)
Assembled Length
59"
(1499mm)
26"
(660mm)
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
NOTE: Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
1-1/2"
(38mm)
TOP VIEW
High-Volt Connection(s)
Alternate Refrigerant
Piping Entrance
Low-Volt
Connection(s)
FRONT VIEW
DPN001166
Rev. 2
3/4"
(19mm) Bezels
35"
(889mm)
76"
(1930mm)
2"
(51mm)
98" (2489mm)
97" (2464mm)
Shaded area indicates a
recommended minimum
clearance for component access.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on dual-cool systems only.
*** Digital scroll compressors not available on DS 077
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN001213, Rev. 1
Liebert® DS
™
X
in. (mm)
Y
in. (mm)Connection Size / Opening, in. (mm)
46
53kW (15 ton) / 70 & 77kW (20 & 22 ton)
Page 51
Air-Cooled Systems
82" (2083mm)
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
33"
(838mm)
76"
(1930mm)
DPN001210
Rev. 1
15"
(381mm)
Compressor Assembly
Blower & Electric
Box Assembly
Filter & Coil
Assembly
45-13/16"
(1163mm)
31-1/4"
(794mm)
76"
(1930mm)
Assembled
Height
97" (2464mm) Assembled Length
Digital scroll compressors
not available on DS 077.
Figure 39Disassembly dimensions—upflow, air-cooled, 53-77kw (15-22 ton), scroll or digital scroll
compressors with centrifugal fans
Table 34Component weights—upflow, air-cooled, 53-77kw (15-22 ton), scroll or digital scroll
Dry Weight, Approximate, Including Panels, lb (kg)
Blower and Electric Box Assembly
Forward-Curved Fans
Filter and Coil Assembly760 (345)940 (426)760 (345)940 (426)
* Digital scroll compressors not available on DS 077
Source: DPN001210, Rev. 1
compressors
Model #053, 070077
CompressorScroll/Digital ScrollStandard Scroll *
Air-CooledDual-CoolAir-CooledDual-Cool
770 (349)770 (349)770 (349)770 (349)
47Liebert® DS
™
Page 52
Air-Cooled Systems
33"
(838mm)
NOTE: Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
1-1/2"
(38mm)
TOP VIEWHigh-Volt Connection(s)
Alternate Refrigerant
Piping Entrance
Low-Volt
Connection(s)
FRONT VIEW
DPN001165
Rev. 2
3/4"
(19mm) Bezels
35"
(889mm)
76"
(1930mm)
2"
(51mm)
109" (2769mm)
108" (2743mm)
Shaded area indicates a
recommended minimum
clearance for component access.
24"
(610mm)
34"
(864mm)
Minimum required
for blower replacement
Figure 40Dimensions—upflow, air-cooled 53-77kw (15-22 ton), semi-hermetic compressors with
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on dual-cool systems only.
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN001212, Rev. 2
X
in. (mm)
Y
in. (mm)
53kW (15 ton) / 70 & 77kW (20 & 22 ton)
49Liebert® DS
Connection Size / Opening
in. (mm)
™
Page 54
Air-Cooled Systems
82" (2083mm)
NOTES: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Shaded area indicates a
recommended minimum
clearance for component
access.
Minimum required
for blower replacement
Note: Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
34"
(864mm)
24"
(610mm)
3/4"
(19mm)
Bezels
33"
(838mm)
35"
(889mm)
2"
(51mm)
76"
(1930mm)
1-1/2"
(38mm)
131" (3327mm)
132" (3353mm)
Digital scroll compressors
not available on 105 models.
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on dual-cool systems only.
*** Digital scroll compressors not available on DS 105
Piping dimensions shown are connection sizes; field piping sizes may be different depending on distance. Refer to user manual, SL-18825.
Source: DPN001257, Rev. 0
CGD*
Factory Location
FRONT SECTION VIEW
(Left Front Panel Not Shown)
DPN001257
Rev. 0
X, in. (mm)Y, in. (mm)Connection Size / Opening
53Liebert® DS
™
Page 58
Air-Cooled Systems
DPN001255
Rev. 1
31-1/4"
(794mm)
33"
(838mm)
76"
(1930mm)
26"
(660mm)
Filter & Coil Assembly
Compressor
Assembly
Blower & Electric
Box Assembly
NOTE: Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
105"
(2667mm)
131" (3327mm
Assembled Length
45-13/16"
(1164mm)
76"
(1930mm)
Assembled
Height
Digital scroll compressors
not available on DS 105.
Figure 46Disassembly dimensions—upflow, air-cooled, 105kW (30 ton), standard scroll compressors
* Cross bracing required for legs longer than 18". Number of legs varies per model and options selected.
Source: DPN002172, Rev. 3; DPN002189, Rev4
Liebert® DS
™
No. of
Fans
A
in. (mm)
105-1/4
(2674)
202-7/16
(5142)
in. (mm)
B
—
113-1/2
(2883)
C
in. (mm)
96-1/16
(2440)
192-1/4
(4883)
in. (mm)
94-7/16
(2398)
94-7/16
(2398)
58
D
E
in. (mm)
—
96-3/16
(2444)
Leg Height
F* in. (m.)Gin. (mm)Hin. (mm)
18
(457)
36
(914)
48
(1219)
60
(1524)
31-5/8
(803)
49-5/8
(1260)
61-5/8
(1565)
73-5/8
(1870)
39-5/8
(1006)
57-5/8
(1464)
69-5/8
(1768)
81-5/8
(2073)
Page 63
Air-Cooled Systems
Figure 50Cabinet and anchor dimensions—Liebert MC™ models MCL110 and MCL220 with Liebert Lee-
Temp receivers
Emerson recommends a clearance of
55-5/8"
(1413mm)
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting condenser
provided on 3&4 fan models
Height
to Top
of Fan
Guard
15-1/4"
(387mm)
15-1/4"
(387mm)
E
D
Provided on
(2806)
(2806)
(1) leg supplied for
each Liebert
Lee-Temp
kit on 2, 3, & 4
fan models
54-3/8"
(1381mm)
—18 (457)
112-1/4
(2851)
3- & 4- Fan
Models
ANCHOR PLAN
Model
No
MCL1102
MCL2204
* Cross bracing required for legs longer than 18". Number of legs varies per model and
options selected.
Source: DPN002415, Rev. 3
No. of
Fans
A
in. (mm)Bin. (mm)Cin. (mm)Din. (mm)Ein (mm)
124 1/8
(3152)
236-5/16
(6003)
—
129-9/16
(3291)
112-1/8
(2848)
224-3/8
5699)
110-1/2
110-1/2
55-1/2"
(1409mm)
48-3/4"
(1239mm)
53-7/8"
(1368mm)
Electric Box End
For
Dual-Circuit
Only
DPN002415
Rev. 3
Leg
Height
F* in. (m.)Gin. (mm)Hin. (mm)
36 (914)
48 (1219)
60 (1524)
35-7/8
(911)
53-7/8
(1368)
65-7/8
(1673)
77-7/8
(1978)
43-5/8
(1108)
61-5/8
(1565)
73-5/8
(1870)
85-5/8
(2175)
59Liebert® DS
™
Page 64
Figure 51Condenser planning dimensions—MCL110 and MCL220
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting condenser
provided on 3&4 fan models
55-5/8"
(1413mm)
55-1/2"
(1409mm)
53-7/8"
(1368mm)
Electric Box End
48-3/4"
(1239mm)
Height to Top
of Fan Guard
DPN002416
Rev. 2
ANCHOR PLAN
Provided on
3- & 4- Fan Models
D
E
Air-Cooled Systems
# of
Model #
MCL1102
MCL2204
* 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). Number varies according to model and options.
Source: DPN002416, Rev. 2
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
2. 208V–460V premium models must be connected to Wye 3-phase systems.
FLAWSAOPD
Electrical Field Connections—Liebert MC Condensers
Figure 53Electrical field connections—Liebert MC Condensers premium efficiency control, with and
without Liebert Lee-Temp
Fan 2
Fan 1
Lee-Temp receiver tank (1 per circuit).
NOTE: Standard heater pads are 150 watt each.
(Optional 300 watt heater pads are available.)
Standard heater pad voltage is 230V.
(120V heater pad voltage is optional.)
Fan 2
Electrical Connection
Box with Cover
Electrical service connection. Pigtails in electric
handy box are factory-wired to Liebert Lee-Temp
heater pads for field-connection of separate
continuous electric source; wire not by Liebert
5A
5B
10
Fan 1
1
6
4
5C7
2
3
8
9
DPN002169
Rev. 3
DPN002374
Pg. 2, Rev. 1
Liebert® DS
™
62
Page 67
Electrical Connections—Premium Efficiency Control, Liebert MC Condensers
1. Three-phase electrical service—Terminals are on top of disconnect switch for one-fan and
two-fan units. Terminals are on bottom of disconnect switch for three-fan and four-fan units.
Three-phase service not by Emerson. See Note 5.
2. Earth ground—Field lug terminal for earth ground connection. Ground terminal strip for fan
motor ground connection.
3. Primary high voltage entrance—Three 7/8" (22.2mm) diameter knockouts located at the
bottom of the enclosure.
4. SPD field connection terminals—High-voltage surge protection device (SPD) terminals. SPD
is an optional device.
5. CANbus terminal connections—Field terminals for CANbus cable connection.
• 5A is the CANbus connectors
• TB49-1 is the input terminal for CANbus high
• TB49-3 is the input terminal for CANbus low
• TB50-1 is output terminal for CANbus high
• TB50-3 is the output terminal for CANbus low
• Each CANbus cable shield is connected to terminal “SH”, Item 9.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Emerson. See Note 2.
6. Remote unit shutdown—Replace exiting jumper between terminals TB38-1 and TB38-2 with
field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied
Class 1 wiring.
7. Alarm terminal connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common; TB74-2 is
normally open; and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use
field-supplied Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power or when a critical alarm has
occurred that shuts down the condenser unit. TB74-4 is common, TB74-5 is normally open
and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied
Class 1 wiring.
8. Indoor unit interlock and SPD alarm terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 &
71 for Circuit 1, and normally open contact is closed across Terminals 70 & 230 for Circuit 2
from indoor room unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 &13. SPD is an
optional device.
9. CANbus shield terminal—Terminal for field connection of the CANbus field-supplied cables.
Shield of CANbus field-supplied cables must not be connected to ground at the condenser.
10. Primary low voltage entrance—One 7/8" (22.2mm) diameter knockout that is free for
customer low-voltage wiring.
Air-Cooled Systems
63Liebert® DS
™
Page 68
NOTES
Air-Cooled Systems
1. Refer to specification sheet for unit voltage rating, full load amp and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
•shielded
• 22-18AWG stranded tinned copper,
• twisted pair (minimum 8 twists per foot),
• low capacitance (15pf/ft or less),
• plenum rated (NEC type CMP) if required by local codes,
• UV and moisture resistant or run within conduit once in an outdoor environment, and
• must be temperature and voltage rated for conditions present.
Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454
(UV resistant outdoor rated) Category 5, 5e or higher.
3. Do not run the CANbus cable in the same conduit, raceway, or chase as high voltage.
4. For CANbus network lengths greater than 350ft. (107m), contact Liebert factory.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. The electrically commutated (EC) motors included in the Liebert MC condensers are suitable for
connection to power supplies with a solidly grounded neutral. (Some platforms can accept power
supplies listed under Item b below. Contact the factory for more information.)
a. Acceptable power supplies for 208 to 480V nominal units
• 208V wye with solidly grounded neutral and 120V line to ground;
• 380V wye with solidly grounded neutral and 220V line to ground;
• 480V wye with solidly grounded neutral and 277V line to ground.
b. Unacceptable power supplies for 208V to 480V nominal units:
• wye with high resistance (or impedance) ground;
• delta without ground or with floating ground;
• delta with corner ground; or
• delta with grounded center tap
Liebert® DS
™
64
Page 69
3.12PIPING—LIEBERT MC™ CONDENSERS
Typical System Configurations—LIEBERT MC CONDENSERS
Figure 54 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (with or without Liebert Lee-Temp
Figure 54Liebert MC piping schematic with and without Liebert Lee-Temp
™
) and field-supplied interconnection piping.
Air-Cooled Systems
Check Valve
Relief Valve
Liebert Lee-Temp Receiver
Condenser
Coil
Liebert Lee-Temp
Service
Valve
Check
Valve
Service
Valve
Liquid Return
Head Pressure
Control Valve
Hot Gas Discharge
Compressor
Liquid
Service
Valve
Sensing
Bulb
Suction
External
Equalizer
Condenser
Coil
Evaporator
Coil
Field installed relief valve(s) required
for 50Hz EU CE units
Optional Field-Installed
Fusible Plug
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or at
evenly divided distances*
*Isolation
Valve
Hot Gas Discharge
Expansion
Valve
NOTES
Single refrigeration circuit shown for clarity.
Schematic representation shown. Do not use for specific connection locations.
Solenoid
Valve
Sight
Glass
Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connection With Valve Core
Filter Drier
Liquid Line
* Components are not supplied by
Liebert but are recommended for
proper circuit operation and
maintenance
*Isolation
Valve
Trap at base of risers
over 5ft. (1.5m)*
DPN002188
Rev. 1
65Liebert® DS
™
Page 70
Air-Cooled Systems
Note:
1. The following materials are supplied by Emerson for each circuit (shipped loose with condenser)
for field installation: insulated Liebert Lee-Temp storage tank with sight glasses, head pressure control
valve, check valve, rotalock valve and pressure relief valve. All other piping to be supplied and installed by others.
2. Consult factory for proper line sizing for runs longer than 150ft. (45.7m) equivalent length.
Field Piping
Detail AA
Isolator
Metal Clamp
Fasten hot gas line to cabinet
using flat surface clamps with
isolators (field-supplied)
See Detail A A
Hot Gas Line
To Condenser
Entering Hot
Gas Line
Entering Hot
Gas Line
Liquid Line
From Condenser
Leaving
Liquid Line
Position elbow to
direct relief valve
downward
Position elbow to
direct relief valve
downward
Liquid Line
From Condenser
Leaving
Liquid Line
Hot Gas Line
To Condenser
Inverted traps in refrigerant
lines are internal to
the condenser. Do not trap
external to the unit.
R407C 2 and 4 Fan
Piping Assembly
R410A 2 Fan
Piping Assembly
Liebert-supplied piping assembly
will include one or two valve and check
valves, depending on condenser
capacity and refrigerant
Table 48Piping dimensions—Liebert MC dual circuit condensers with Liebert Lee-Temp
Model #
Condenser Connections
ODS, in.Liebert Lee-Temp Connections
Circuit
No.Hot GasLiquid
Hot Gas Tee
IDS, in.
Liquid Line
to Lee-Temp Valve
ODS, In.
Receiver Out
MCM08027/85/87/85/85/85/8
MCL11021-1/87/81-1/87/87/87/8
MCM16021-1/87/81-1/87/81-1/81-1/8
MCL22021-3/81-1/81-3/81-1/81-1/81-1/8
Source: DPN002426, Rev. 4
Liebert® DS
™
66
R407C
IDS, in.
Receiver Out
R410A
IDS, in.
Page 71
Figure 56 Piping connections—Liebert MC™ dual circuit two-fan and four-fan units
Optional fusible plug service kit to
be brazed into the liquid line(s) in
either the vertical or horizontal
position. (where required)
(vertical position is preferred,
horizontal position is optional.)
for two circuit systems, one
fusible plug kit will need to
be installed in each circuit.
Circuit #2
Circuit #1
Horizontal
Leaving Liquid
Line
Vertical
Field Piping
Entering Hot
Gas Line
Inverted traps in refrigerant
lines are internal to
the condenser. Do not trap
external to the unit.
DPN002425
Rev. 3
Air-Cooled Systems
Table 48Liebert MC piping connection sizes—Liebert MC dual-circuit, two-fan and four-fan units
Electrical Field Connections—Liebert Fin/Tube Condensers
Earth ground connection (60Hz).
Connection terminals for field
supplied earth grounding wire
when factory disconnect is NOT
supplied.
Electric service, not by Liebert.
Single-phase for condenser
models CSF, CDF with single
fan motor. Three-phase for
all other condenser models.
DPN000666
Rev. 0
Electric service connection
terminals when factory
disconnect is NOT supplied.
Electric service connection
terminals when factory
disconnect is supplied.
Electric service entrance. A 7/8"
(22.2mm) diameter hole in a
1 1/8 in (28.6mm) knockout
provided in bottom of electric box.
Factory installed disconnect
switch (optional).
Electric service connection
and fuse block.
Factory wired to 24V
Class 2 control circuit.
Factory-wired to components
on electric panel.
Earth ground bar (optional on 50Hz only).
Connection terminals with factory
ground from each high voltage
component for field-supplied
earth grounding wire.
Earth ground connection (60Hz).
Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is
supplied.
Control interlock (70, 71)
Field-supplied Class 2 wiring to
interlock condenser 24V controls
to Liebert room unit;
7/8 in. (22.2mm) diameter
hole provided in bottom
of electric box.
NOTE: Refer to specification sheet for full load amp and wire size amp ratings.
Figure 60Electrical field connections for Fan Speed Control fin/tube condensers
Air-Cooled Systems
Liebert® DS
™
72
Page 77
Figure 61Electrical field connections for VFD control fin/tube condensers
V
F
D
SPD
Alarm Connections
Field-supplied 24V Class 1
wiring to remote alarm circuits
Surge Protection Device (SPD)
alarm contact connections (11, 12).
Variable Frequency Drive (VFD)
alarm contact connections (13, 14)
Factory-wired to 24V
control circuit.
Control interlock (70, 71)
Field-supplied
Class 1 wiring to
interlock condenser 24V
controls to Liebert
room unit; 7/8 in.
(22.2mm) diameter
hole provided in
bottom of electric box.
Factory-wired to components
on electric panel.
Earth ground bar (optional on 50Hz only).
Connection terminals with factory
ground from each high voltage
component for field-supplied
earth grounding wire.
Earth ground connection (60Hz).
Connection terminal for
field-supplied earth grounding wire
when factory disconnect is supplied.
Factory-installed fuse block on
60Hz units. Circuit breaker supplied
in lieu of fuse block on 50Hz units.
Electric service connection
terminals with factorysupplied disconnect
Electric service entrance.
A 7/8" (22.2mm) diameter
hole in a 1-1/8 in (28.6mm)
knockout provided in bottom
of electric box.
Electric service,
not by Emerson
Factory-installed
disconnect switch
DPN001051
Rev. 1
NOTE: Refer to specification sheet for full load amp and wire size amp ratings.
Air-Cooled Systems
73Liebert® DS
™
Page 78
Figure 62Electrical field connections for Liebert Lee-Temp control fin/tube condensers
70
71
Electric service. Three-phase for
all models. Wiring not by Emerson.
DPN000683
Rev. 0
Lee-Temp receiver tank (1 per circuit).
NOTE: Standard heater pads are 150 watts each.
(Optional 300 watt heater pads are available.)
Standard heater pad voltage is 230V. (120V
heater pad voltage is optional.)
Electrical connection box with cover.
Electrical service connection.
Pigtails in electric handy
box are factory wired to LeeTemp heater pads for field
connection of separate
continuous electric source,
wiring not by Emerson.
Electric service connection
terminals when factory
disconnect is NOT supplied.
Electric service connection
terminals when factory
disconnect is supplied.
Factory-installed disconnect
switch (optional).
Electric service entrance. A
7/8 in (22.2mm) diameter hole
in a 1 1/8 in (28.6mm) knockout
provided in bottom of electric box.
Earth ground connection (60Hz).
Connection terminal for field-supplied
earth grounding wire when factory disconnect
is supplied.
Earth ground connection (60Hz).
Connection terminal for field-supplied
earth grounding wire when factory
disconnect is NOT supplied.
Earth ground bar (optional on 50Hz only).
Connection terminals with factory ground
from each high-voltage component
for field-supplied earth grounding wire.
Factory-wired to components
on electric panel.
Electric service connection
and fuse block.
Factory wired to 24V
Class 2 control circuit.
Control interlock (70, 71)
Field-supplied Class 2 wiring to
interlock condenser 24V controls
to Liebert room unit;
7/8 in. (22.2mm) diameter
hole provided in bottom
of electric box.
NOTE: Refer to specification sheet for full load amp and wire size amp ratings.
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The condenser is not designed to supply power to the receiver.
Liebert® DS
™
151515151515
74
Page 79
Air-Cooled Systems
DPN000797
Rev. 6
Filter Drier
Solenoid
Val ve
Expansion
Valve
Sight
Glass
SUCTION
LIQUID
COMPRESSOR
EVAPORATOR
COIL
Muffler
CONDENSER
COIL
(FAN SPEED or VFD)
REFRIGERANT PIPING
FIELD PIPING
Service / Schrader (Access) Connection With Valve Core
Service / Schrader (Access) Connection No Valve Core
For rises over
25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided*
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.
Schematic representation shown.
Do not use for specific connection locations.
CONDENSER
COIL
(Liebert Lee-Temp)
Cylinder
Unloader(s)
Sensing
Bulb
Liebert Lee-Temp Receiver
External
Equalizer
* Components are not supplied by
Emerson but are recommended for
proper circuit operation and
maintenance.
** Components supplied by Emerson
and must be field-installed (70kW,
77 kW & 105kW models only)
Service
Valve
Service
Val ve
*Isolation
Valve
**Muffler
*Isolation
Valve
Liquid Return
Hot Gas Discharge
Hot Gas Discharge
LIEBERT LEE-TEMP
Inverted Trap on discharge
and liquid lines to extend above
base of coil by a minimum of
7-1/2" (190mm).
Check Valve
Check
Valve
Service
Valve
Relief Valve
Head Pressure
Control Valve
Liquid Return
Trap at base of risers
over 5ft. (1.5m)*
Optional Field-Installed
Fusible Plug
Optional
Sub-Cooling
Coil
Optional
Sub-Cooling
Coil
Piping—Fin/Tube Condensers
Typical System Configurations—Fin/Tube
Figure 64 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (VFD, Fan Speed Control or Liebert Lee-Temp) and field-supplied interconnection piping.
Figure 63Piping schematic, air-cooled with semi-hermetic compressor with fin/tube condenser
75Liebert® DS
™
Page 80
Air-Cooled Systems
r
Figure 64Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser
Relief
Inverted Trap on discharge
& liquid lines to extend above
Check Valve
Valve
Service Valve
LIQUID RETURN
base of coil by a minimum of
7-1/2" (190mm).
Liebert Lee-Temp Receiver
Head Pressure
Control Valve
CONDENSER
COIL
(Fan Speed or VFD)
FAN SPEED/VFD
(Liebert Lee-Temp or VFD condenser
is required with digital scroll)
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve
Service
Valve
Check
Valve
Compressor
Optional field
installed fusible
plug
LIQUID
Sensing
Bulb
SUCTION
Service
Valve
External
Equalizer
CONDENSER
COIL
(Liebert Lee-Temp)
Hot Gas
LIEBERT LEE-TEMP
Discharge
(Liebert Lee-Temp or VFD condenser
is required with digital scroll)
EVAPORATOR
COIL
HOT GAS DISCHARGE
* For rises over
25ft. (7.6m)
trap every 20ft.
(6m) or evenly
divided
*Isolation
Valve
Expansion
Valve
Solenoid
Valve
Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection; No Valve Core
Service/Schrader (Access) Connection With Valve Core
Sight
Glass
Filter Drier
LIQUID RETURN
* Components are not supplied
by Emerson but are recommended
for proper circuit operation and
maintenance.
NOTES: Schematic representation shown. Do not use for specific connection locations.
Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
Liebert® DS
™
76
*Isolation
Valve
DPN000798
Rev. 5
Trap at base
of risers ove
5ft. (1.5m)
Page 81
Figure 65VFD and Fan Speed Control condenser piping—Fin/tube condensers
Fasten liquid and hot gas lines to leg using
flat surface clamps with isolators (field-supplied).
Support field piping separately to avoid coil damage
and loss of charge.
See
Detail
A-A
Inverted Traps (field-supplied)
to extend a minimum of
7-1/2" (190mm) above coil base
DPN001065
Rev. 1
Entering Hot
Gas Line
Leaving
Liquid Line
Detail A-A
Metal
Clamp
Isolator
Optional fusible plug service kit to
be brazed into the liquid line(s) in
either the vertical or horizontal
position (where required).
(Vertical position is preferable,
horizontal position is optional.)
For two-circuit systems, one
fusible plug kit must to
be installed in each circuit.
Horizontal
Vertical
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
Support field piping separately
to avoid coil damage and loss
of charge.
Liquid
Line
Hot Gas Line
See Detail A-A
Inverted Traps (field-supplied)
to extend 8" (203mm)
above coil base
DPN000669
Rev. 2
Position elbow to direct
relief valve downward
Entering Hot
Gas Line
Leaving
Liquid
Line
Detail A-A
Metal
Clamp
Isolator
Air-Cooled Systems
Figure 66Liebert Lee-Temp head pressure control condenser piping—Fin/tube condensers
77Liebert® DS
™
Page 82
3.12.2 Piggyback Condensers
Piggyback Selections
Table 54Liebert DS piggyback condenser selection
Air-Cooled Condenser SelectionLiebert DS Size
Condenser
Type
Piggyback
Table 55Piggyback condenser airflow and static pressure data
Control interlock Field-supplied, Class 2 wiring to
Terminals 70 & 71 to interlock condenser 24V
controls to Liebert room unit; 7/8 in. (22.2mm)
diameter knockout provided in bottom of box
Factory-wired to components
on electric panel
Refer to specification sheet for full load amp and wire size amp ratings.
Liebert Lee-Temp electric
service connection to terminals
supplied from factory-wired
Liebert Lee-Temp heater pads
for field connection of separate
continuous electrical source,
not supplied by Emerson.
Factory-wired to components
on electric panel.
Three-phase connection. Electric service
connection terminals when factory
disconnect switch is not supplied
Control interlock Field-supplied, Class 2 wiring to
Terminals 70 & 71 to interlock condenser 24V
controls to Liebert room unit; 7/8 in. (22.2mm)
diameter knockout provided in bottom of box
Factory-wired to components
on electric panel
Refer to specification sheet for full load amp and wire size amp ratings.
Liebert Lee-Temp electric
service connection to terminals
supplied from factory-wired
Liebert Lee-Temp heater pads
for field connection of separate
continuous electrical source,
not supplied by Emerson.
Factory-wired to components
on electric panel.
Three-phase connection. Electric service
connection terminals when factory
disconnect switch is not supplied
Table 59Separate electrical supply requirements for Liebert Lee-Temp
™
Voltage120120208/230208/230
Watts/Receiver150300150300
FLA2.55.01.42.8
WSA3.16.21.83.6
OPD15151515
Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.
Figure 69Electrical field connections for Liebert piggyback condensers
receivers, 60Hz, 1 Ph
81Liebert® DS
™
Page 86
Figure 70Piggyback condenser piping and electrical connection locations
See Note 2
See Note 2
See Note 1
C
"
1-13/16"
See Note 3
See Note 2
See Note 1
9-11/16"
(246mm)
(46mm)
7-7/8"
(200mm)
E
D
E
See Note 3
12-5/8"
(321mm)
3" (76mm)
1" (25mm)
Panel
3" (76mm)
3" (76mm)
F
MODELS PB-350A THRU PB-1100A
G
4-1/2" (114mm)
See Note 1
See Note 2
9-11/16"
(246mm)
Air-Cooled Systems
A
1-13/16"
(46mm)
E
D
See Note 2
See Note 1
7-7/8"
(200mm)
MODEL PB-1350A
B
See Note 3
E
12-5/8"
(321mm)
C
3" (76mm)
1" (25mm)
Panel
3" (76mm)
3" (76mm)
4-1/2"
(114mm)
5-1/2" (140mm) See Note 1
3-1/4" (85mm) See Note 2
6"
(152mm)
3"
(76mm)
Drain Outlet
Location
1-1/4" (32mm) F.P.T.
See Note 3
ALL MODELS
1-1/2"
(38mm)
3"
(76mm)
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical).
2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical).
3. Cover plate for access of liquid line and hot gas line.
Figure 71Piping schematic—Liebert DS with piggyback condenser and Liebert Lee-Temp
Condenser Coil
Liquid Return from
Condenser Coil
Rotalock Valve
Pressure
Relief Valve
Sight Glasses
Evaporator
Coil
* Traps
every
25 ft.
(7.6m)
of Rise
Head Pressure
Control with
Integral Check
Valve
Service
Valve
Check
Valve
Liebert
Lee-Temp
Receiver
™
Double discharge risers
are required wWhen unit
is operating below 30%
of full capacity. Consult
factory for proper selection.
Hot Gas
Discharge
* Shutoff
Valve
Liquid
Return
to Unit
Solenoid
Valve
Sight
Glass
Filter
Dryer
* * Muffler
SINGLE CIRCUIT SHOWN
FACTORY PIPING
OPTIONAL PIPING
FIELD PIPING
Expansion
Valve
Sensing Bulb
External
Equalizer
Service
Valves
Muffler
Cylinder
Unloaders
(Optional)
Compressor
* Components are not supplied by Emerson
but are recommended for proper
circuit operation and maintenance
** Components supplied by Emerson
and must be field-installed.
DPN000692
Rev. 0
83Liebert® DS
™
Page 88
3.13ANCILLARY ITEMS—AIR-COOLED SYSTEMS
DPN000820
Rev. 3
NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang
floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
Gussets supplied on floor stands
12" (305 mm) tall and greater
Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.
Supply air
discharge
opening
Optional turning vane
shown as front air discharge.
Supply air
discharge opening
33"
(838mm)
47-15/16"
(1218mm)
34-1/2"
(876mm)
(with feet)
A+1-1/2"
(38mm) (with feet)
16-3/4"
(425mm)
1"
(25mm) TYP.
3"
(76mm)
7/8"
(23mm)
4-1/2"
(114mm)
A
B
Figure 72Floor stand dimensions—28-42kW (8-12 ton), downflow
Air-Cooled Systems
Table 62Floor stand and floor planning dimensions—28-42kW (8-12 ton), downflow
Dimensional Data, in. (mm)Height, in. (mm)
ModelABC*D turning vane
Air-Cooled Semi-Hermetic Models and
All Water/Glycol/GLYCOOL Models85(2159)26(660)
Air-Cooled Scroll Models and
Air-Cooled Digital Scroll Models
Source: DPN000820, Rev. 3
Liebert® DS
™
72
(1829)13(330)
9 (229)4 (111)
12 (305)7 (187)
15 (381)10 (264)
18 (457)13 (340)
21 (533)16 (416)
24 (610)19 (492)
84
Page 89
Figure 73Floor stand dimensions—53-77kW (15-22 ton), downflow
DPN000930
Rev. 2
NOTE: Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang
floor stand 1" (25mm). * Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
Gussets supplied on floor stands
12" (305 mm) tall and greater
Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.
Supply air
discharge
opening
Optional turning vane
shown as front air discharge.
Supply air
discharge opening
34-1/2"
(876mm)
(with feet)
A+1-1/2"
(38mm) (with feet)
33"
(838mm)
69-3/4" (1772mm)
16-3/4"
(425mm)
1"
(25mm) TYP.
3"
(76mm)
7/8"
(23mm)
A
B
Air-Cooled Systems
Table 63Floor stand and floor planning dimensions—53-77kW (15-22 ton), downflow
Dimensional Data, in. (mm)Height, in. (mm)
Air-Cooled Semi-Hermetic Models and
All Water/Glycol/GLYCOOL Models
Air-Cooled Scroll Models and
Air-Cooled Digital Scroll Models
Source: DPN000930, Rev. 2
ModelABC *D - Turning Vane
108
(2743)26(660)
97
(2464)15(381)
9 (229)4 (111)
12 (305)7 (187)
15 (381)10 (264)
18 (457)13 (340)
21 (533)16 (416)
24 (610)19 (492)
85Liebert® DS
™
Page 90
Air-Cooled Systems
B
F *
D
E
A
Piping Access Area
See Note 4
32"
(813mm)
Center Feet
C
Support Feet Centers
3/4"
(19mm)
3/4"
(19mm)
3/4"
(19mm)
31-1/2"
(800mm)
1"
(25mm)
33"
(838mm)
35"
(889mm)
Overall Depth
7/8"
(23mm)
3"
(76mm)
32-3/4"
(832mm)
DPN002151
Rev. 1
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert DS floor stand can be used if the fans are to
remain in their original raised position.
2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides
overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical and its orientation to the
Liebert DSE is critical for lowering the EC fans. Unless the floor stand is installed in
the correct position, the blowers will not lower into the floor stand.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height C.
Figure 74Floor stand and floor planning dimension, downflow 53-77kW (15-22 tons) models with EC
fans
Table 64Floor stand and floor planning dimensions—53-77kW (15-22 ton), downflow with EC fans
Liebert DS Model
AB C D E F
DS053-077, Air-Cooled Semi-Hermetic
and all Water/Glycol/ GLYCOOL
Models
DS053-077, Air-Cooled Scroll and
Air-Cooled Digital Scroll Models
Digital scroll compressors
not available on 105 models.
Figure 75Floor stand and floor planning dimensions—downflow 105kW (30 ton) models with EC fans,
standard scroll and semi-hermetic compressors without turning vane
132-1/2" (3366mm)
34-1/2"
(876mm)
(with feet)
(with feet)
25"
(635mm)
33"
(838mm)
131" (3327mm)
NOTE:
1) This floor stand should be used when EC fans are intended
to be lowered under a raised floor. The standard Liebert DS
floor stand can be used if the fans are to remain in their
original raised position.
2) Right side of paneled unit is flush with right side of floor stand.
All other paneled sides overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical and
its orientation to the Liebert DS is critical for lowering the EC fans.
Unless the floor stand is installed in the correct position,
the blowers will not lower into the floor stand.
4) Jack and jack support are shipped loose and are intended
to be placed into position under each fan and utilized to lower
or raise that fan as needed.
*Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “A”.
74" (1880mm)
Gussets supplied on floor stands
12" (305mm) tall and greater.
1"
(25mm Typ.)
3"
(76mm)
A*
(889mm)
Overall
Depth
DPN002152
Rev. 1
See Note 4
35"
87Liebert® DS
™
Page 92
Air-Cooled Systems
D
DPN001059
Rev. 2
NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang
floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.
Gussets supplied on floor stands
12" (305 mm) tall and greater
Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.
Supply air
discharge
opening
Optional turning vane
shown as front air discharge.
Supply air
discharge opening
33"
(838mm)
34-1/2"
(876mm)
(with feet)
132-1/2"
(3366mm) (with feet)
26"
(660mm)
91-3/4"
(2330mm)
131"
(3327mm)
16-3/4"
(425mm)
1"
(25mm) TYP.
3"
(76mm)
7/8"
(23mm)
4-1/2"
(114mm)
C*
Figure 76Floor stand dimensions—105kW (30 ton), downflow with turning vane and centrifugal fans
Table 65Floor stand and floor planning dimensions—105kW (30 ton), downflow