Emerson Liebert DCP Water-Based Pumping Unit 200kW User Manual

Liebert® DCP™ with Liebert iCOM® Control
User Manual–50-60 Hz; 200kW Nominal Capacity
TABLE OF CONTENTS
1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 General Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Equipment Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Field Connections—Optional for All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Remote Sensor Installation—Proper Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.0 PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.1 Connection Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2 Air Bleeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3 Liebert DCP Interconnection with Cooling Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4 Piping Installation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.5 Bypass Flow Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.6 Piping Details—Shutoff/Isolation Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.7 Filling Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.8 Checklist for Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.0 LIEBERT ICOM® CONTROL—FIRMWARE VERSION XP1.00.DCP.01R . . . . . . . . . . . . . . . . 25
4.1 Liebert iCOM Components and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Display Lamp Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3 Navigating Through the Liebert iCOM® Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.4 Changing Liebert iCOM®’s Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5 Changing Operational Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.6 Graphical Data Record. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.7 Liebert iCOM® User Menu Icons and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.8 Liebert iCOM® User Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.9 Liebert iCOM® Service Menu Icons and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.10 Liebert iCOM® Service Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.0 START THE LIEBERT DCP WITH LIEBERT ICOM® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
5.1 Checklist for Liebert DCP Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.2 Starting the Liebert DCP with Liebert iCOM Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6.0 ALARM DESCRIPTIONS AND SOLUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
6.1 Alarm Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6.2 Warning Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.3 System Shutdown Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
9.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
FIGURES
Figure 1 Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 2 Liebert DCP components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 3 Unpacking the Liebert DCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4 Use a forklift to remove the Liebert DCP from the skid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 5 Removing the unit from the skid using rigging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 6 Securing the Liebert DCP to piano jacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 8 Piping access points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 9 Front view of Liebert DCP and electrical enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring . . . . . . . . . . . . . . . . . . . . . . 11
Figure 11 High voltage connections—60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 12 High voltage connections—50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 14 Connecting the remote temperature/humidity sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 15 DIP switch and jumper settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 16 Unit-to-unit networking connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 17 Liebert DCP extra low voltage field connections points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 18 Suggested remote sensor placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 19 Liebert DCW system diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 20 General piping details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 21 Standpipe filling components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 22 Liebert DCP filling components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 23 Liebert DCD™ bleed valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 24 Liebert XDK-W™ bleed valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 25 Liebert iCOM display components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 26 Liebert iCOM default home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 27 Cooling module overview, first 10 modules—Applies only to Liebert XDP . . . . . . . . . . . . . . . . . . 28
Figure 28 Entering the password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 29 Display setup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 30 Liebert iCOM User Menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 31 Liebert DCP User Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 32 Setpoints screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 33 Set Alarms screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 34 Sensor Data screen, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 35 Sensor Data screen, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 36 Display Setup screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 37 Module Status screen, page 1 of 20—Applies to Liebert XD™ smart modules only . . . . . . . . . . . 38
Figure 38 Liebert XDV™ Smart Module Status screen—Applies to Liebert XD smart modules only . . . . . 38
Figure 39 Liebert XDH™ Smart Module Status screen—each bank shown separately—Applies to
Liebert XD™ smart modules only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 40 Liebert XDO™ Smart Module Status screen—Applies to Liebert XD™ smart modules only. . . . 39
Figure 41 Total Run Hours screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 42 Liebert iCOM Service Menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ii
Figure 43 Liebert DCP Service Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 44 Setpoints screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 45 Maintenance—Basic Settings screen, page 1 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 46 Maintenance—Pump 1 Settings screen, page 2 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 47 Maintenance—Pump 2 Settings screen, page 3 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 48 Maintenance screens, pages 4 through 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 49 Diagnostics/Service Mode screen, page 1 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 50 Diagnostics/Service Mode screen, page 2 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 51 Diagnostics/Service Mode screen, page 3 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 52 Diagnostics/Service Mode screen, page 4 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 53 Diagnostics/Service Mode screen, page 5 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 54 Diagnostics/Service Mode screen, page 6 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 55 Set Alarms screen, page 1 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 56 Set Alarms screen, page 2 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 57 Set Alarms screen, page 3 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 58 Set Alarms screen, page 4 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 59 Set Alarms screens, pages 5 and 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 60 Set Alarms screen, page 7 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 61 Sensor Calibration/Setup screen, page 1 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 62 Sensor Calibration/Setup screen, page 2 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 63 Sensor Calibration/Setup screen, page 3 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 64 System/Network Setup screen—System, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 65 System/Network Setup screen—System, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 66 System/Network Setup screen—Unit, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 67 System/Network Setup screen—Unit, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 68 Options Setup screen, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 69 Options Setup screen, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 70 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only. . . . . . . . . . . . 61
Figure 71 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only. . . . . . . . . . . . 62
TABLES
Table 1 Supply and return requirements for Liebert DCD/Liebert XDK-W loop. . . . . . . . . . . . . . . . . . . . 18
Table 2 Water quality to limit corrosion and erosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 3 Keyboard icons and functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 4 Troubleshooting the Liebert DCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 5 Liebert DCP200 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
iii
iv
IMPORTANT SAFETY INSTRUCTIONS
!
!
!
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert DCP. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death. Open all local and remote electric power supply disconnect switches, verify with a voltmeter
that power is off and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power. The Liebert iCOM
mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM.
The line side of the disconnect switch on the front of the unit contains live high-voltage. The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic. Follow all local codes.
®
microprocessor does not isolate power from the unit, even in the Unit Off

Important Safety Instructions

WARNING
Risk of unit falling over. Can cause property damage, injury or death. The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit.Verify that all equipment used for lifting and moving is rated for the weight of the unit. See Table 5 for unit weights.
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.
NOTE
This document is intended to be used together with site specific documentation and documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Inform the facility manager before beginning any action that could cause a disturbance in the Liebert DCW action is taken and the work is finished.
system’s cooling function. In addition, inform the facility manager after the
®
1Liebert
DCP
NOTICE
R
Redundant
Pumps
DCP 200 B *
Revision
level
Liebert
Data Center
Pumping Unit
Nominal
Capacity
Example: DCP200RA– –*
A
A = 460V-3ph-60Hz
(voltage-phase-frequency) C = 208V-3ph-60Hz M = 380/415V-3ph-50Hz
2
2 = 12°F (°C)
Heat Exchanger
B = Bottom
Piping for Secondary Loop
B
B = Bottom
Chilled Water Connection
Risk of leaking chilled water and drain lines. Can cause equipment and building damage. Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson Network Power installing monitored leak detection equipment for the unit and its factory- and field-installed supply, return and drain lines.

Figure 1 Model number nomenclature

Important Safety Instructions
®
recommends
Liebert® DCP
2

1.0 PRODUCT DESCRIPTION

Liebert DCP
Control
Valve
Liebert DCD
Liebert XDK-W
Heat Exchanger
Pump(s)
Chilled
Water

1.1 General Product Information

1.1.1 Product/System Description

The Liebert DCP chilled water distribution unit is an interface between the building chilled water system and the cooling modules in the Liebert DCW chilled water to the cooling modules that are in the room with heat-producing equipment. The Liebert DCP is rated for 200kW (682,000BTU/H) of cooling.
The Liebert DCP consists of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls, valves and piping.
The Liebert DCP monitors room conditions and prevents coil condensation by maintaining the chilled water being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling water temperature, etc., are automatic.
Figure 2 Liebert DCP components
Product Description
system. It is designed to circulate and control

1.2 Equipment Inspection

When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Emerson your sales representative.
®
and to
®
3Liebert
DCP

1.3 Equipment Handling

!
!
WARNING
Risk of unit falling over. Can cause injury or death. The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified rating organization. See Table 5 for unit weights. Personnel should be properly trained and certified to move and rig equipment
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.

1.3.1 Handling the Liebert DCP While it is on Skid and Packaged

• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than 6"
(152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift point of the unit.
Product Description
NOTICE
Risk of structural interference. Can cause equipment or building damage. While on the skid, the unit is too tall (83" [2108mm] overall height) and may be too wide to fit
through a standard doorway. Any attempt to move the unit, while skidded, through a standard doorway will cause damage to the unit and to the building.
Measure the unit and doorway, and verify that the unit will fit through before attempting to move it through the doorway.
NOTICE
Risk of improper forklift operation. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the top boards of the skid and/or the bottom of the unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert DCP upright, indoors and protected from dampness, freezing temperatures and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels. Place a protective material between the straps of the piano jacks and the unit. Ensure that
the straps are not tightened to a point of damaging panels.
Liebert® DCP
4

1.3.2 Unpacking the Liebert DCP

Remove Stretch Wrap Remove Packaging Planks
Stretch
Wrap
1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and side packaging planks.
2. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The bag may remain in place for dust and panel protection or removed for immediate unit installation.
3. Remove the bag from the unit when ready to remove the skid for installation.
Figure 3 Unpacking the Liebert DCP
Product Description

1.3.3 Removing the Unit from the Skid Using a Forklift

1. Align the forklift with either the front or rear side of the unit. Make sure the tines of the forklift are locked to the widest position. Use the center of gravity indicators to determine the entry points for the tines. The tines must be
equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit. Make sure the tines are level. The tines must be low enough to fit under the unit without
damaging it. Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
5Liebert
®
DCP
Figure 4 Use a forklift to remove the Liebert DCP from the skid
Fit the forklift tines under the Liebert DCP.
Move the forklift forward until the tines are fully under the unit.
The forklift tines must be equally spaced on either side of the center of gravity indicator.

1.3.4 Removing the Unit from the Skid using Rigging

1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally spaced on either side of the center of gravity indicator. Refer to
2. Place slings under the unit using spaces provided between the skid deck boards.
Product Description
Figure 5.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the unit.
7. Remove the skid from under the unit.
Liebert® DCP
6
Figure 5 Removing the unit from the skid using rigging
Equally Spaced
Equally Spaced
Center of Gravity Symbols
Spreader
Bars
Lag Bolts
Bracket
If rigging will be used to transport the Liebert DCP, place one or two horizontal straps around the unit and the vertical straps about this height.
Cushioning material not shown for clarity.
Product Description

1.3.5 Moving the Liebert DCP Using Piano Jacks

1. Elevate the Liebert DCP with a lifting mechanism, such as a forklift or rigging.
2. Position one piano jack at each end of the Liebert DCP.
3. Lower the unit to a height suitable for placing it on the piano jacks.
4. Put protective material between the Liebert DCP and the piano jacks and straps.
5. Secure the Liebert DCP to the piano jacks.
6. Release the Liebert DCP from the straps securing it to the lifting mechanism and move the mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
®
7Liebert
DCP
Figure 6 Securing the Liebert DCP to piano jacks
Using a forklift to put a
Liebert DCP on piano jacks
Using rigging to put a
Liebert DCP on piano jacks
Liebert DCP Secured
to piano jacks
Product Description

1.3.6 Removing the Unit from the Piano Jacks

1. Lower the Liebert DCP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert DCP off one piano jack with a pry bar or similar device, taking care not to damage the unit’s cabinet.
4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert DCP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
Liebert® DCP
8

2.0 INSTALLATION

Drip tray dimensions
Shipping Weight Domestic: 1100 Lb. (500kg) Export: 1275 Lb. (575kg)
Drip tray dimensions
Drip tray dimensions
Does not include Disconnect Switch Bezel
DPN002400 Pg. 2, Rev. 1
27"
(686mm)
11-1/2"
(292mm)
1"
(25mm)
1"
(25mm)
33"
(838mm)
33"
(838mm)
Cutout
33-1/8"
(841mm)
Side Panel
38" (965mm)
Overall
34" (864mm)
Overall
Floor Cutout Dimensions
78" (1981mm)
Height of Unit
The shaded area indicates a recommended clearance of 36" (914mm) for component access.
36"
(914mm)
36"
(914mm)

2.1 Mechanical Considerations

2.1.1 Positioning the Liebert DCP

Install the Liebert DCP according to the site specific documentation and secure the unit to the floor.
The Liebert DCP can be installed near a wall or another Liebert DCP. However, there must be at least 3
Figure 7 Dimensions
feet (92cm) clearance in front of the Liebert DCP as service access for components in the unit.
Installation
9Liebert
®
DCP
Figure 8 Piping access points
!
!
Floor Piping
16-5/8"
(422mm)
2-1/2"
(64mm)
Secondary In
7-1/4" (184mm)
33"
(838mm)
Each piping outlet connection - A, B, C and D - is 2-5/8".
Rear
BCW OUT
(86mm)
Secondary Out
A
C
BCW IN
36" (914mm)
Front
3-3/8"
B
D
Installation
3-1/4"
(83mm)
6-1/2"
(165mm)
DPN002400 Pg. 3, Rev. 1

2.2 Electrical Considerations

Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated on the Liebert DCP’s rating plate. The unit must be installed in accordance with national wiring regulations.
Connect cables for high voltage supply to the electrical box in the Liebert DCP according to Figure 11 and make sure that the phases are correctly connected.
WARNING
Risk of electric shock. Can cause injury or death. Open all local and remote electric power supply disconnect switches and verify with a
voltmeter that power is Off before working within the unit’s electrical connection enclosures.
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Liebert® DCP
Check and retighten all wiring connections before starting the unit.
10

2.2.1 Connecting High-Voltage Cables

Liebert DCP Input Power Knockout
Enclosure Cover Not Shown
1. Turn the Liebert DCP’s disconnect switch to the Off position (see Figure 9). Open the front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 9 Front view of Liebert DCP and electrical enclosure
Installation
Disconnect Switch
Front of Liebert DCP
Hazardous Voltage Enclosure Cover
2. Determine which knockouts in the electrical enclosure will be used and remove them (see Figure 10).
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
Liebert iCOM User Interface
Enclosure Cover Latch
Hazardous Voltage Enclosure Cover
11 Liebert® DCP
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see
Customer Power Connection
Ground Lug
Disconnect Switch
Fuse Blocks
Power Block
Pump Fuse Blocks
Pump Contactors
Transformer 1
Transformer 2 (supplied on 460V units only)
Transformer 6
Busbar
Customer Power Connection
Pump Circuit Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Transformer 6
Fuse Blocks
Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper phasing.
4. Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of the enclosure.
Figure 11 High voltage connections—60Hz
Installation
Figure 12 High voltage connections—50Hz
Liebert® DCP
12

2.2.2 Extra Low Voltage (ELV) Connections

Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this equipment (refer to
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage
Figure 13).
User Interface Wiring
Temperature/Humidity Sensor Wiring
Installation
Alternate Knockout for Temperature/Humidity Sensor Wiring
Enclosure Cover Not Shown
13 Liebert® DCP
Figure 14 Connecting the remote temperature/humidity sensors
Installation
CAN Cable
See Note 4
P64
See Note 4
Unit Display (Rear View)
Red Crossover Ethernet Cable
Crossover Coupler
See Note 6
P66
CAN Ground Coupler
P67
Termination Plug
See Note 8
P2 P4
CAN Iso Adaptor
P3P1
See Note 9
T6 Isolation
Transformer
T1 Unit Control
Transformer
P66
Liebert XD
Cooling Module
See Note 8
P66
P67
See Note 5
P67
CAN Ground Coupler
Remote T/H Sensor BRemote T/H Sensor A
See Note 7
24VAC Nominal
P66
P67
P66 P67
Liebert XD
Cooling Module
See Note 5
See Note 3
E5
Liebert IntelliSlot 1
Liebert IntelliSlot 2
Ribbon Cables
Not Used
Cable B
Cable A
P63
See Note 2
P1
P2
P65
P3
Liebert IntelliSlot Power Supply
1. See unit electrical schematic, installation and user manuals.
2. Cable “A” provided with each unit. Liebert IntelliSlot-based communications - Cable “A” is preconnected to P65 on the microprocessor and input/output board and P65 on the Liebert IntelliSlot power supply non-Liebert IntelliSlot-based communications.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect the ground coupling on the end of the cable connected to Sensor “A” or Sensor “B.”
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and input/output board and connect it to one side of the crossover coupler. The first customer
P13
P11
P7
P67
P64
P61
P65
P18
P12
1
2
3
P66
P78
SW2
OFF ON
21436
P68
5
P43
P4
E1 E2 E3 E4
TB1
P54
P51
E1
P24
Control
Fuse
Board
P45
P4
Liebert iCOM Microprocessor
P41
and I/O Board
P52
P53
P39
See Table for
P40
P8
P32
Plug Assignments
P34
P33
P36
P35
P22 P38
302211 Rev. 3
connection point is to P64 on the microprocessor and input/output board. The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and input/output board and display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the Liebert XD cooling module and which connects to P2 on CAN Iso.
8. Field-install cables with factory-installed ferrite beads (when provided, typically two places). Each cable must make three passes through the ferrite bead. Locate the ferrite bead on top of the electric box. See the instruction sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). The cable passes through the ferrite bead three times.
Liebert® DCP
14

2.2.3 DIP Switch and Jumper Settings for Remote Sensors

P68
135
246
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A” REMOTE T/H SENSOR “B”
SW1SW1
OFF
ON
OFF
ON
Jumper on 1-2
1
2
3
P78
DIP
Switches
ON
1 3 4 9
10
OFF
2 5 6 7 8
Jumpers
on 1-2, 5-6
OFF ON
1 2 3 4 5 6 7 8 9
10
DIP
Switches
ON
None
OFF
1 2 3 4 5 6 7 8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
DIP
Switches
ON
1 5
OFF
2 3 4 6 7 8
DIP
Switc hes
ON
2 5
OFF
1 3 4 6 7 8
SW3
1 2 3 4 5 6 7 8
OFF ON
P3
321
Jumper on 2-3
P3
321
Jumper on 2-3
302211 Rev. 3
302211 Rev. 3
Termination Plug
Liebert iCOM Microprocessor & I/O Board
Customer Connection Points
Crossover Coupler
Red Crossover Ethernet Cable
Straight Through Ethernet Cables
U2U Networking Switch
(Field-Supplied)
Unit Display (Rear View)
Not Used
P64
P66
P64
P66P67
To / From Other Networked Units
CAN Cable
See Note 1
P65
E5
P61
P63
P11 P13
P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and I/O board and connect it to one side of the crossover coupler. The first customer connection point is to P64 on the microprocessor and I/O board. The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and I/O board and display to the private U2U network.
The Liebert DCP is shipped with jumpers and DIP switch settings for normal operation; refer to Figure 15.
Figure 15 DIP switch and jumper settings
Installation
Figure 16 Unit-to-unit networking connections
15 Liebert® DCP

2.3 Field Connections—Optional for All Units

1
1
2
K11COM
K11NO
K11NCL
TS-24
TS-50
TS-51
TS-54
K3COM
K3NO
K3NCL
TS-37
TS-38
TS-77
TS-78
K11COM
K11NO
K11NC
K11
K11
24 50
5424
5124
3837
K3COM
K3NO
K3NC
K3
K3
BK
78
77
(-)
R or W
(+)
DPN002400 Pg. 5, Rev. 1
Control wiring must be Class 2 and installed in accordance with the National Electrical Code (NEC).
Requires shielded cable.
2
1
COMMON WARNING OUTPUT
FOR CONTACTS INDICATING AN ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM
CIRCUIT BY OTHERS
INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE N.O. CONTACTS FROM REMOTE ALARM DEVICE AS SHOWN.
N.O. CONTACT BY OTHERS
INPUT: CONDENSATION DETECTION
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: FAN BREAKER STATUS
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: REMOTE SHUTDOWN
FOR SHUTDOWN OF CONTROL CIRCUIT, REMOVE JUMPER BETWEEN TERMINALS 37 & 38 AND REPLACE WITH N.C. CONTACT.
N.C. CONTACTS BY OTHERS
LIEBERT SITE MONITOR
FOR DIGITAL COMMUNICATION WITH LIEBERT SITE MONITORS ONLY. CONNECT 2 WIRE TWISTED PAIR TO 77 & 78. ALSO SEE SITE MONITOR INSTALLATION MANUAL.
COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM CIRCUIT BY OTHERS
Factory-Wired Temperature Sensor
UNIT DISPLAY
(Rear View)
P64
P66 P67
To Remote T/H Sensor A
To Optional External Connections
To Remote T/H Sensor B
To P64 on Liebert iCOM Control Board Red Ethernet Cable
Termination Plug
To P66 on Liebert iCOM Control Board
DO NOT USE
P67
Connect optional field wiring from remote devices to remote alarm device, common alarm outputs, site monitor and remote shutdown, if applicable. See terminal strip descriptions in

Figure 17 Liebert DCP extra low voltage field connections points

Installation
Figure 17.
Liebert® DCP
16

2.4 Remote Sensor Installation—Proper Placement

Placement of the two remote temperature/humidity sensors is critical to effective cooling of the conditioned space.
Installation
The remote sensors must be installed in areas where conditions are representative of the space conditioned by the Liebert DCP. Emerson the cooling modules served by the Liebert DCP. If the return air side of the primary air mover, such as a Liebert DS
, represents the conditions where the cooling modules are located, one sensor could be placed there. Emerson suggests placing the other sensor on the wall opposite the heat load area (see
Figure 18 for guidance).
Do not install the sensors where ambient air might cause false readings, for example, near unsealed doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable; each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM® input/output board inside
the Liebert DCP. Secure the ring terminal on the cable shield to the electric box adjacent to P67 (see
Figure 14).
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the
ring terminal on the cable shield to the grounding screw adjacent to P67.

Figure 18 Suggested remote sensor placement

®
recommends installing the sensors in different areas near
17 Liebert® DCP

3.0 PIPING

Liebert DCP Cooling Modules
To Building
Chilled Water

3.1 Connection Sizes

The copper pipe connections on the Liebert DCP are:
Building Chilled Water Supply 2-5/8" OD
Chilled Water Return 2-5/8" OD
Coolant Supply 2-5/8" OD
Coolant Return 2-5/8" OD
Fill Water Source 5/8" OD

3.1.1 Recommended Pipe Size

Connect the main pipes between the Liebert DCP and the Liebert DCD™/Liebert XDK-W™ according to site-specific documentation and the configuration guide for the Liebert DCD/Liebert XDK-W unit.
Elbows and restrictions should be minimized to get good fluid flow.
Table 1 Supply and return requirements for Liebert DCD/Liebert XDK-W loop
Maximum Total
Nominal Pipe Size
inches (mm)
2.5 (64) 75 (23) Type L Copper
3 (76) 150 (46) Copper or Schedule 40 Steel
3.5 (89) 300 (91) Copper or Schedule 40 Steel
Equivalent Length
Piping
ft. (m) Piping Material

3.2 Air Bleeders

Install air bleeders at each high point in the piping circuits.

3.3 Liebert DCP Interconnection with Cooling Modules

All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe. The Liebert DCP may be connected to Liebert DCD or Liebert XDK-W cooling modules with either
prefabricated piping assembly or rigid, off-the-shelf piping. The cooling modules are connected in parallel between main return and supply pipes going to and from the Liebert DCP. represents a typical configuration.

Figure 19 Liebert DCW system diagram

Figure 19
Liebert® DCP
18

3.4 Piping Installation Methods

The assembly and connection means used for piping in the Liebert DCW™ system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft soldering is not recommended.
During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.
Insulate all piping lines to prevent condensation in applications where the dew point approaches the chilled water temperature.

3.4.1 Piping Mains

Install a 20-40 mesh strainer on the chilled water supply to the Liebert DCP. The strainer is needed to prevent particles in the chilled water from entering the Liebert DCP’s heat exchanger.

3.5 Bypass Flow Controllers

The Liebert DCP pumping unit is designed to provide a total of 114GPM (25.9 m3/h) of cooling water to the cooling modules. The pump operates at its highest efficiency between 90 and 120GPM (20.4m this range. Emerson regulator of similar flow capacity as bypass valves. Bypass lines also prevent excessive flow through the cooling modules when only a few modules are installed in addition to maintaining high flow rate through pump.
3
/h and 27.3m3/h). Permanent bypass flow controllers must be installed to ensure flow within
®
recommends using four 22.67 GPM (5.15m3/h) constant flow regulators or other
Piping
Refer to individual cooling module specifications to estimate the maximum combined allowable flow for all the units connected to the Liebert DCP. If the allowable combined flow rate is less than 90GPM (20.4 m 90GPM (20.4m
3
/h), then as many bypass controllers as necessary must be opened to maintain a flow above
3
/h) through the Liebert DCP.
For example, the maximum allowable water flow rate for a Liebert DCD™ unit is 22.7GPM (5.2 m3/h). At least four of these units must be connected to the Liebert DCP in parallel to achieve a total flow of over 90GPM (20.4m
3
/h).
22.7GPM x 4 Liebert DCD’s = 90.8GPM total flow
5.2m3/h * x Liebert DCD’s = 20.8m3/h total flow
If fewer units are connected to the Liebert DCP, then bypass lines must be opened to maintain the total flow through the Liebert DCP within the range of 90 to 120GPM (20.4 to 27.3 m
For example, if three Liebert DCD modules are connected to a Liebert DCP, the total flow of 68.1GPM (15.47 m
3
/h) would be insufficient. A bypass flow controller of 22.67GPM (5.15 m3/h) must be added to
3
/h).
increase the flow rate to at least 90GPM (20.4m3/h)
22.7GPM x 3 Liebert DCDs = 68.1GPM
22.7GPM x 3 Liebert DCDs + 22.67GPM bypass flow controller = 90.77 GPM
5.2m3/h * 3 Liebert DCDs = 15.47m3/h
5.2m3/h *3 Liebert DCDs + 5.15m3/h bypass flow controller =20.75m3/h
19 Liebert® DCP

3.6 Piping Details—Shutoff/Isolation Valves

To Building Chilled Water Supply
Supply
Return
Emerson recommends installing shutoff valves as shown to permit isolating the Liebert DCP for maintenance.
Isolation valves must be installed on the Liebert DCP’s secondary chilled water circuit to permit maintenance on the unit (see

Figure 20 General piping details

Figure 20).
Piping

3.6.1 Insulation

NOTE
Do not insulate piping before checking it for leaks. Insulating pipes before checking them for leaks would prevent easy detection of leaks.
Insulate all piping between the Liebert DCP and its connected cooling modules to prevent condensation where the piping passes through non-conditioned areas.

3.7 Filling Instructions

This section provides detailed instructions on how to properly fill the Liebert DCP.

3.7.1 Check for Proper Installation of Components and Workmanship

1. Confirm that the flow directions of field-installed components are correct.
2. Confirm that all isolating valves are open (keep the hose bib valve closed when filling).
3. Confirm that all auto air vents are closed (tighten caps if applicable).
4. Test the water quality when filling the system. Refer to the values in Table 2 for minimum
corrosion and erosion.
Table 2 Water quality to limit corrosion and erosion
Maximum Conductivity 500µS/cm
Minimum PH 7.0
Maximum Suspended Matter 30 mg/L; no visible particles
Taste and Smell Normal

3.7.2 Conduct Air Pressure Test

Liebert® DCP
1. Turn Off power to the unit.
2. Set the pressure at 150 psig (1034kPa; 10.3 bars) maximum for at least 30 minutes or according to
local codes.
3. Repair any leaks if necessary.
20

3.7.3 Water Fill Line Connection

NOTE
Check with local codes for proper connection to potable water and EPA conformance.
Do NOT use the hose bib at the bottom of the unit to fill the system (see Figures 22 and 21).
1. When filling the system, use only water that can be classified and used as drinking water.
a. Open all vents (loosen caps if applicable) to allow air to escape during filling. b. Remove the Schrader pin in the valve at the top of the standpipe (see Figure 21) to obtain
0 psig pressure. c. Open Valves #1 and #2 to allow the system to fill (see Figure 22). d. When the water has reached the FILL level in the bottom sight glass of the standpipe,
immediately close Valve e. Replace the Schrader pin in the valve at the top of the standpipe.
2. Bleed air thoroughly (keep Valve #1 closed to isolate the standpipe from the system). a. Depress pins at all vents. b. Manually depress pins at all Schrader vents on each rack (see Figure 23). c. Manually vent at pump housing plugs (see Figure 22). d. Continue to vent until the system is full, then close Valve #2.
3. Open Valve #1 to reconnect the system to the standpipe (fluid level should rise above the fill, but below the NORMAL level on the sight glass).
a. If the fluid level is above the NORMAL level, release water by opening the hose bib until the
level reaches the NORMAL level on the sight glass.
b. If the fluid level is below the NORMAL level on the sight glass, open Valve #2 until the level
reaches the NORMAL level.
4. Turn the system on (pumps will be in operation) and continue to vent air for 24 hours to remove as much air as possible.
If Steps 1 through 3 are followed properly, the air pressure in the top of the standpipe should be 14 PSIG (±2PSIG).
Piping
#1 (see Figure 22) to isolate the standpipe from the system.
NOTE
Add water as necessary to maintain a normal level reading.
5. When the system is mostly air-free, close all air vents (tighten caps securely); this includes vents at each rack (
Figure 23) and auto air vents on the main headers.
6. Conduct a Fluid Pressure Test. a. Pressure test the system with water at city pressure for six hours or according to local codes. b. Check for leaks.
7. Add a water corrosion inhibitor.
• The use of a closed system treatment (CST) is strongly recommended. CST is available from Terlyn Industries at 800-200-4112 or
www.terlyn.com.
• Additional treatment might be required after six to 12 months of operation, depending on the quality of your water.
Note: Many parameters contribute to water corrosion and erosion, and the requirements stated above do not guarantee 100% corrosion and erosion prevention. However, when these parameters are met and a corrosion inhibitor is used, the possibility of corrosion and erosion in the closed loop water system should be minimized, therefore maximizing the life expectancy of the system.
8. Refill the system by following Steps 1 through 5, then go to Step 9.
9. Turn the unit On by pressing the I/O key.
21 Liebert® DCP
Figure 21 Standpipe filling components
Piping
Standpipe
Vent Ports
Sight Glass (Normal Level)
Sight Glass (Fill Level)
Valve #2
Hose Bib
FRONT OF LIEBERT DCP
Liebert® DCP
22
Figure 22 Liebert DCP filling components
Bleed Valve
Liebert DCD
Rack
One pump removed for clarity
Piping
Vent Port
Vent Port
Sight Glass (Normal Level)
Standpipe
Valve #2
Valve #1
Figure 23 Liebert DCD™ bleed valve
Sight Glass (Fill Level)
Hose Bib
FRONT OF LIEBERT DCP
23 Liebert® DCP
Figure 24 Liebert XDK-W™ bleed valve
Bleed Valve

3.8 Checklist for Proper Installation

___ 1. Unpack and check received material.
___ 2. Position the Liebert DCP and secure to the floor.
___ 3. Wire high-voltage connections.
___ 4. Wire low-voltage connections.
___ 5. Connect building chilled water piping to the Liebert DCP.
___ 6. Connect Liebert DCD™/Liebert XDK-W piping to the Liebert DCP.
___ 7. Make sure air vents are installed at high-point of the system.
___ 8. Make sure isolation valves are installed on the mains and branch piping.
___ 9. Pressure test air.
___ 10. Fill the system with water.
___ 11. Bleed air out of the system.
___ 12. Pressure test fluid.
___ 13. Check for water leaks.
Piping
Liebert® DCP
24
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Liquid Crystal Display screen
Keypad
LED Status Indicators (top LED is red or flashing red; bottom LED is green or amber)
ESC
?
On/Off Key
Escape Key Down Arrow Key
Up Arrow Key
Left Arrow Key Right Arrow KeyEnter Key
Alarm Key
Help Key
LEDs
(see Table 3 for
meanings)

4.0 LIEBERT ICOM® CONTROL—FIRMWARE VERSION XP1.00.DCP.01R

4.1 Liebert iCOM Components and Functions

The Liebert iCOM controller layout is shown in Figure 25; the keyboard functions are defined in Table 3.

Figure 25 Liebert iCOM display components

25 Liebert® DCP

Table 3 Keyboard icons and functions

?
ESC
Icon
Key Name Function
On/Off Key Controls the operational state of the cooling unit.
Alarm Key Silences an alarm.
Help Key Accesses integrated Help menus.
ESCape Key Returns to the previous display view.
Enter Key Confirms all selections and selects icons or text.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Increase Key (Up Arrow)
Decrease Key (Down Arrow)
Left and Right Arrow Keys
Upper LED
Lower LED
Moves upward in a menu or increases the value of a selected parameter.
Moves downward in a menu or reduces the value of a selected parameter.
Navigates through text and sections of the display.
Blinking Red—Active, unacknowledged alarm exists
Solid Red—Active, acknowledged alarm exists
Amber—Power is available to the unit; unit is NOT operating
Green—Unit is operating with no alarms

4.2 Display Lamp Indicators

• The Green lamp will be On only when the Liebert DCP is On and running with no alarms.
• The Red lamp will be On if the unit is On and running with an active alarm, or if the unit is shut down because of an alarm.
• The Red lamp will flash while an alarm is being annunciated. The Red lamp will stop flashing and the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
• The Amber lamp will be On if the Liebert DCP has been shut down at the I/O switch or if the unit has been shut down by an alarm condition.
Liebert® DCP
26
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
UNIT 1
Sensor A B Temp: 74°F 72°F Hum: 50% 50% Dew Pt: 55°F 54°F
28.02.2012 14:07(01) UNIT ON
28.02.2012 14:07(01) UNIT ON
press : for next /prev uni t for unit /system view press: for menu; ESC for prev screen ; ? for help
08/2011
Liebert
DCP
57°F
50.0°F set
CFC: 30%
28.02.2014 15:03 UNIT ON
Sensor A Room Data
Date and Time
Pump Operation represented by animated piping
Next Scheduled Maintenance
Alarm/Event History
Navigation Prompts
Unit Name
Sensor B Room Data
Unit Status
Coolant Tem per atu re
Available only with Liebert XD Smart Modules

4.3 Navigating Through the Liebert iCOM® Display

Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The Liebert iCOM’s home screen is shown in

Figure 26 Liebert iCOM default home screen

Figure 26.

4.3.1 Accessing Menus and Settings

Viewing Data
No password is required to view data or settings.
To view data:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view.
4. Once that icon is highlighted, press Enter again to open that menu.
• If a password is required, see 4.3.3 - Entering the Password.
• If a menu has more than one screen, the Liebert iCOM display will have text at the top simi­lar to this: (page 1 of 2).
5. Press Enter to select the first line of data.
6. Use the Up and Down arrow keys to scroll to the desired data point.
7. Press ESC to move back to higher level menus.
27 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
UNIT 1
OFF 9/2015100 %
212°F
Max XD Supply
Air Temp
Liebert XDP
AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01AA01
(01) 9/12/2014 08:33 RST General Alarm (01) 9/12/2014 08:20 ACK HIGH CHILLED WATER TEMP
8/4/2012 14:13:54 ALARM OFF
? for help
for next/previous unit
for system view
ESC
for previous screen
for menu
°F 70 72 74 76 75 73 74 71 77 72
4.3.2 Cooling Module Overview—Applies Only to Liebert XDP
The Liebert iCOM® will display an overview of all connected cooling modules. It does not display a system view, which would include units other than the cooling modules.
NOTE
The Liebert iCOM control screens display a setting to select a system view, but the Liebert DCP does not support a system view.
To display an overview of all connected cooling modules:
1. At the default home screen on the Liebert iCOM, press the Down arrow. This will display the first 10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.
Figure 27 Cooling module overview, first 10 modules—Applies only to Liebert XDP
2. Press the down arrow button again to display the next 10 modules’ outlet temperature and capacity levels.
3. Press ESC to return to the default home screen.
Liebert® DCP
28

4.3.3 Entering the Password

SETPOINTS
to change parameter
to confirm
to select parameter
for next/pr evious unit then
PASSWORD (Actual Level 0) Min Room Temperature Setpoint
????
68.0°F
UNIT 01
U101 U102 U103 U104 U105 U106 U107 U108 U109 U110 U111
Password command line—highlight by pressing Enter
After highlighting the Password command line, press Enter again to highlight the first digit. Use the Up and Down arrow keys to change the first digit. Move to the next digit in the Password with the right arrow.
Most settings in the Liebert iCOM® are protected by a factory-set password, 1490. To enter the password:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press Enter to highlight the Password line.
6. With the Password line highlighted, press Enter to highlight the first digit in the password
7. Enter the password, 1490. Use the Up and Down arrow keys to select a numeral for the first digit of the password. Move to the next digit of the password with the Right arrow key. Select the numerals for all four digits with the same process.
8. After all four digits of the password have been entered, press the Enter key.
NOTE
Do not press the ESC key or the Liebert iCOM will move to the previous screen and the password must be re-entered before changes may be made.
Figure 28 Entering the password
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
29 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit then
Language Date Time Temperature Indication Display Contrast Buzzer Frequency Backlite Off after Screen
Display Colors Date Format
SYSTEM
U401 U402 U403 U404 U405 U406 U407 U408 U409 U410 U411
ENGLISH (US)
8/27/2012
15:03:17
°C 50
Off/ 50
5 min
DCP
Normal
mm/dd/yyyy
Highlight the setting to be changed by pressing Enter.

4.4 Changing Liebert iCOM®’s Display Settings

No password is required to change the way Liebert iCOM displays data. The Display Setup controls how the unit shows data, such as temperature, date and time.
To change the display settings:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the Display Setup icon.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press the Enter key to select the first setting. Either change that setting or navigate to another setting with the Up and Down arrow keys.
6. Once the desired setting is highlighted, press the Enter key to access that parameter’s display setting options.
7. Use the Up and Down arrow keys to make changes.
8. Press the Enter key to accept the changes.
9. Press the ESC key twice to return to Liebert iCOM’s user menu.

Figure 29 Display setup screen

4.5 Changing Operational Settings

Liebert® DCP
Changes to the Liebert DCP’s operation settings in the Set Alarms and Setpoints menus require a password.
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu. If a password is required, see 4.3.3 - Entering the Password.
5. After entering the password, use the Up and Down arrow keys to scroll to and highlight the operational setting to be changed.
6. Press Enter to highlight the values for that setting.
7. Use the Up and Down arrow keys to change the value.
8. Press Enter to accept the change. (The value will no longer be highlighted.)
9. Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)
10. Press ESC again to move to previous screens.
30
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
°C / °F
% RH
SET
EVENT
LOG
SET
ALARMS
!
ACTIVE
ALARMS
1 2
39
6
SET
1234h
XDIO

4.6 Graphical Data Record

The Graphical Data Record charts the average temperature from Sensors A and B and the supply coolant temperature.
The temperature scales can be changed to expand or compress the data.
The time scale also can be altered to any of several selectable values.
NOTE
Changing the time scale eliminates all previous graphical data and the unit will begin recording new data.

4.7 Liebert iCOM® User Menu Icons and Legend

Figure 30 Liebert iCOM User Menu icons

Setpoints
View and change
operational
setpoints
Sensor Data
Shows readings
of sensors; View
Only
Spare Parts List
Contains spare
parts available on
site
Active Alarms
Lists all current
alarms; View Only
Event Log
Lists last 400
events and
alarms
View Only
Display Setup
Change settings
for display:
language and
time
Graphic Data Record
Displays average temperature from
Sensors A and B, the
average dew point from
Sensors A and B, the
supply coolant
temperature and the
supply coolant control
point graphs; Data is
View Only; Display scale
is adjustable
Total Run Hours
Records the run time of
all components and
allows setting of limits on
run time; View Only
View Network
Shows status of
all connected
units; View Only
Smart Modules
Displays readings for the individual smart
modules; View
Only; applies only
to Liebert XDP
Set Alarms
Allows user to
change settings for
alarms
Service Contacts
Contains key
contact information
for service
NOTE
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
31 Liebert® DCP

Figure 31 Liebert DCP User Menu screen

EVENT
LOG
°C / °F
% RH
SET
SET
12
39
6
SET
ALARMS
!
ACTIVE
ALARMS
1234
h
USER MENUS
ESC
to unselect
to change level to open requested menu
to navigate
XDIO
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Liebert® DCP
32

4.8 Liebert iCOM® User Menu Screens

SETPOINTS
to change parameter
to confirm
to select parameter
for next/previous unit then
PASSWORD (Actual Level 0) Min Room Temperature Setpoint
????
68.0°F
UNIT 01
U101 U102 U103 U104 U105 U106 U107 U108 U109 U110 U111
User menus report general cooling unit operations and status. User menu screens employ a coding that begins with “U” and is followed by parameters and information, such as settings. Gaining access to some User menu screens requires entering a password; the User Menu password is 1490.
Check www.liebert.com for the latest Liebert iCOM user manual updates, SL-18835.

Figure 32 Setpoints screen

Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, the unit will raise the coolant temperature to reduce the amount of cooling.
The setting is intended to keep the room temperature above the setpoint. Without a proper setpoint, the Liebert DCP can lower the room temperature too much, depending on the room dew point and load. This setpoint will reduce the cooling to keep the room temperature above this desired temperature.
NOTE
This is not a true room temperature setpoint. The Liebert DCP has no heaters; it will try to cool as much as possible. If the Liebert DCP is able to cool the room to this setpoint, it will reduce its cooling action to try to keep the room temperature at or above this setpoint.
The default setting is 60°F (15.6°C). The range is 50-80°F (10-27°C). For optimal cooling performance, the minimum temperature setpoint should be 1-2° below the
expected temperature at the remote sensors, which may affect placement of the remote sensors. If the minimum temperature setpoint is set above the typical remote temperature sensor reading, it will reduce the Liebert DCP cooling output and, in extreme cases, cause erratic Liebert DCP performance.

Spare Parts

Spare Parts—The spare parts lists contains a detailed description and part number that can be used to order parts for the unit. These part numbers are specific to each model and option installed on the unit.

Event Log

Event Log—The event log displays all events and actions that have been generated by the unit. When multiple units are networked the screen will display the event log of the whole system. Each event shows the unit that generated the alarm, time and date stamp, a description and the event type.
33 Liebert® DCP
Figure 33 Set Alarms screen
SET ALARMS (page 1 of 1)
to change parameter
to confirm
to select parameter
for next/previous unit then
UNIT 01
PASSWORD (Actual Level 0) High Room Air Temperature Low Room Air Temperature High Room Dewpoint High Coolant Temperature
High Chilled Water Temperature
????
80.0°F
55.0°F
65.0°F
80.0°F
60.0°F
U201 U202 U203 U204 U205 U206 U207 U208 U209 U210 U211
High Room Air Temperature—Sets the threshold where a high room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on the calculated values from either remote Sensor A or remote Sensor B. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Coolant Temperature—Sets the threshold where a high coolant temperature alarm will occur based on the actual reading from the supply coolant sensor. The supply coolant temperature is from the Liebert DCP to the modules. The range for the high supply coolant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high chilled water temperature alarm. The range for the high supply fluid temperature alarm is from
33.8
to 95°F (1 to 35°C); the default is 60°F (15.6°C).
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Liebert® DCP
34
Figure 34 Sensor Data screen, page 1 of 2
SENSOR DATA (page 1 of 2) UNIT 01
U301 U302 U303 U304 U305 U306 U307 U308 U309 U310 U311 U312
This window is READ ONLY
Sensor A Temperature 62.8°F Sensor A Humidity 42.20% Sensor A Dew Point 39.4°F Sensor B Temperature 71.2°F Sensor B Humidity 29.60°% Sensor B Dew Point 37.8°F Supply Coolant Temperature 55.0°F
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated as Sensor A.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated as Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated as Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated as Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated as Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated as Sensor B.
Supply Coolant Temperature—Displays the actual supply coolant temperature from the Liebert DCP to the modules.
Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature to the Liebert DCP.
35 Liebert® DCP
Figure 35 Sensor Data screen, page 2 of 2
SENSOR DATA (page 2 of 2) UNIT 01
U313 U314 U315 U316 U317 U318 U319 U320 U321 U322 U323 U324
This window is READ ONLY
Daily High Temperature 07:49:57 72°F Daily Low Temperature 07:11:30 64°F Daily High Humidity 11:31:46 45% Daily Low Humidity 07:56:18 34% Daily High Dew Point 07:47:26 45°F Daily Low Dew Point 08:02:20 37°F Daily High Coolant Temp 13:01:25 69°F Daily Low Coolant Temp 13:01:11 69°F
Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A or remote Sensor B.
Daily High Dew Point—Shows the highest dew point in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily Low Dew Point—Shows the lowest dew point in a 24 hour period for either remote Sensor A or remote Sensor B.
Daily High Coolant Temperature—Shows the highest supply coolant temperature in a rolling 24 hour period from the Liebert DCP to the modules.
Daily Low Coolant Temperature—Shows the lowest supply coolant temperature in a rolling 24 hour period from the Liebert DCP to the modules.
Daily High Chilled Water Temperature—Shows the highest chilled water supply temperature being delivered to the Liebert DCP in a rolling 24 hour period.
Daily Low Chilled Water Temperature—Shows the lowest chilled water return temperature being delivered to the Liebert DCP in a rolling 24 hour period.
Liebert® DCP
36
Figure 36 Display Setup screen
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit then
Language Date Time Temperature Indication Display Contrast Buzzer Frequency Backlite Off after Screen
Display Colors Date Format
SYSTEM
U401 U402 U403 U404 U405 U406 U407 U408 U409 U410 U411
ENGLISH (US)
8/27/2012
15:03 :17
°F
30
Off/ 50
5 min
Unit View
Normal
mm/dd/yyyy
Language—Sets the language on the display. Changing this setting changes all menu parameters to the selected language.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Date—Sets the internal date of the unit. If this unit is connected to other units with the unit-to-unit network connection, each unit will reflect the last date set.
Time—Sets the internal time of the unit. If this unit is connected to other units with the unit-to-unit network connection each unit will reflect the last time set.
Temperature Indication—Selects the actual and setpoint temperature scale. Selecting C will set the unit to display in Celsius and F will set the unit to display in Fahrenheit.
Display Contrast—Changes the contrast of the display to adjust for different viewing angles, low light and bright light conditions. As the display ages, the contrast may require adjustment for viewing.
Buzzer Frequency—Changes the audible noise frequency of the built-in buzzer. The buzzer will sound when its frequency is being adjusted, easing selection of a frequency easily detected when an alarm occurs.
Backlite Off After—Controls how long the back-light remains active when the display is unused. When the buttons on the front display have not been pressed for the time selected in this parameter, the back-light will turn Off, extending the life of the display and saving energy.
Screen—Controls the screen layout. The Liebert DCP has one view, Unit View.
Display Colors—Selects the background color. Inverted sets the display to show white font with
blue background and Normal sets a white background with blue font.
Date Format—Date format changes the month, day and year arrangement shown on the front display and on event time stamps.
37 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
MODULE STATUS (page 1 of 20) UNIT 01
U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913
Model / Capacity XDV8SK 8 KW Left Fan Status ON Right Fan Status ON
ONLINE
65°F
NODE 81 AZ81
57°F
92°F
66°F
XDV
MODULE STATUS (page 1 of 20) UNIT 01
U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913
Model / Capacity XDV8SK 8 KW Left Fan Status ON Right Fan Status ON
ONLINE
65°F
NODE 81 AZ81
57°F
92°F
66°F
XDV
Figure 37 Module Status screen, page 1 of 20—Applies to Liebert XD™ smart modules only
Module Node ID—The location within the CANbus. Each module’s ID is factory-set to 80 and is automatically changed during setup; requires no user action.
Module Labels—A four-character label consisting of two letters and two numerals. This is the standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or both labels can be used and are entered using the Module Setup found in the Service menu (S910).
Module Status—Indicates whether the smart module is connected to the CANbus.
Figure 38 Liebert XDV™ Smart Module Status screen—Applies to Liebert XD smart modules only
U905—Displays the temperature of the air entering the Liebert XDV™.
U908—Displays the temperature of the air leaving the right and left fan of the Liebert XDV.
U911—Displays the module type and calculated local module capacity; possible module types are
XDV8SK, XDV8SS, XDV8ST, XDV10SK, XDV10SS and XDV10ST.
U912—Displays the left fan status; possible values are ON and OFF.
U913—Displays the right fan status; possible values are ON, OFF and ON ECON. ON ECON
indicates that only one fan is On.
Liebert® DCP
38
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
MODULE STATUS (page 1 of 20) UNIT 01
U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913
NODE 82 AA82
57°F
98°F
98°F
Model / Capacity XDH32SK 15 KW Middle Fan Status ON Top and Bottom Fan Status ON
ONLINE
73°F
XDH
TOP/
BOTTOM
XDO
92°F92 °F
68°F
MODULE STATUS (page 1 of 20) UNIT 01
U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913
Model / Capacity XDO20 SK 20 KW Fan Status ON
ONLINE
NODE 81 AF01
57°F
Figure 39 Liebert XDH™ Smart Module Status screen—each bank shown separately—Applies to Liebert
U904—Displays the temperature of the air entering the top of the bank of the Liebert XDH.
U905—Displays the temperature of the air leaving the Liebert XDH.
U907—Displays the temperature of the air entering the bottom of the bank of the Liebert XDH.
U911—Displays the module type and calculated local module capacity; possible module types are
XDH20SK, XDH20SS, XDH32SK and XDH32SS.
U912—Displays the middle fan status; possible values are ON and OFF.
U913—Displays the top and bottom fans’ status; possible values are ON, OFF and ON ECON. (ON
ECON indicates that two fans have been turned On.)
XD
smart modules only
Figure 40 Liebert XDO™ Smart Module Status screen—Applies to Liebert XD™ smart modules only
U907—Displays the temperature of the air entering from the right and left of the Liebert XDO.
U910—Displays the temperature of the air leaving the Liebert XDO.
U911—Displays the module type and calculated local module capacity; possible module types
XDO16SK, XDO16SS and XDO20SS.
U912—Displays the fan status; possible values are ON and OFF.
39 Liebert® DCP
Figure 41 Total Run Hours screen
TOTAL RUN HOURS
to confirm
for next/previous unit then
to select parameter
to change parameter
U501 U502 U503 U504 U505 U506 U507 U508 U509 U510 U511
UNIT 01
Actual H ours Limit Pump 1 454 0 Pump 2 413 0
°C / °F
% RH
SET
WELLNESS
SERVICE
SET
ALARMS
+ / -
NETWORK
SET UP
XDIO
The parameter shows the actual hours Pump 1 and Pump 2 have operated and the maximum time Pump 1 can operate before the next maintenance.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R

4.9 Liebert iCOM® Service Menu Icons and Legend

Figure 42 Liebert iCOM Service Menu icons

Setpoints
View and change
operational
setpoints
Sensor
Calibration/Setup
Setup and calibrate
sensors for site
Liebert® DCP
Unit Diary
Shows all program
changes and maintenance
performed,
Maintenance/
Wellness
Settings
Shows all
maintenance
records, calculates
next maintenance
date
Diagnostics/
Service Mode
Enter Diagnostics/
Service Mode for
troubleshooting
and repair
Set Alarms
Change settings for
alarms
Network
Setup or alter
network setting.
Options Setup
Enter specific
settings for various
options
40
Smart Module
Setup of alarms and events. Set
temperature limits
for supply and
return sensors.
Label smart
modules, view
firmware version;
applies only to
Liebert XDP
Service Contacts
Contains key
contact information
for service
NOTE
SERVICE MENUS
to select parameter
to change level to open requested menu
ESC
to unselect
to navigate
+
WELLNESS
SET
ALARMS
SERVIC E
+/-
NETWORK
SET UP
XDIO
°C / °F
% RH
SET
SETPOINTS
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Min R oom Temperature Setpoint Temperature Control Type Temperature Proportional Band Temperature Integration Tiime Temperature Derivative Dewpoint Margin Minimum Control Point Min Percent Cooling Setpoint
S101 S102 S103 S104 S105 S106 S107 S108 S109 S110 S111
????
60.0 °F
Intelligent
7.0 °F min sec
4.0 °F
50.0 °F 10%
UNIT 01
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.

Figure 43 Liebert DCP Service Menu screen

Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R

4.10 Liebert iCOM® Service Menu Screens

Service menus allow customized settings for site operations. Service Menu screens employ a coding that begins with “S” and is followed by parameters and information, such as settings. Gaining access to most Service Menus requires entering a password; the Service Menu password is 5010; see Entering the Password for assistance.
The Liebert iCOM firmware is being updated constantly. As a result, the Service Menu parameters in this manual may be slightly different from what is shown on a cooling unit’s display. Check
www.liebert.com for the latest Liebert iCOM user manual updates.

Figure 44 Setpoints screen

4.3.3 -
41 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, unit will raise the coolant temperature to reduce the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting is 60°F (15.6°C).
NOTE
This is not a true room temperature setpoint. The Liebert DCP has no heaters; it will try to cool as much as possible. If the Liebert DCP is able to cool the room to this setpoint, it will reduce its cooling action to try to keep the room temperature at or above this setpoint.
Temperature Control Type—Selects the type of control the system will use to activate cooling. The Liebert iCOM
®
control has three temperature control types: Proportional, PI and Intelligent. The
factory default is Intelligent.
Proportional—If Proportional Control is selected, the percent cooling requirement is determined by the difference between the air temperature sensor reading and the temperature setpoint. As the air temperature rises above the temperature setpoint, the percent cooling required increases proportionally (from 0 to 100%) over half the programmable temperature proportional band. The percent heating requirement (0 to 100%) is determined the same way when the air temperature falls below the setpoint.
PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two individual terms, proportional and integral. The proportional term is calculated in a manner similar to the previously described Proportional control. The integral term (sometimes called reset action) is calculated by measuring how much and for how long the air temperature has been above or below the setpoint. If the actual air temperature is above the setpoint, the percent requirement is slowly but continuously increased until the total is sufficient to bring the return room air back to the setpoint.
Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the setpoint. The percent temperature adjustment required is calculated based on logic that is programmed into the control. These rules simulate the actions that would be taken by a human operator manually controlling the system.
Temperature Proportional Band—Adjusts the activation points of compressors or rate of change based on the actual sensor values deviation from setpoint. The smaller this number the faster the compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8 to
54.0°F (1.0 to 30.0°C). The factory default setting is 7.0°F (3.9°C).
Temperature Integration Time—Temperature integration takes into consideration the amount of time the actual temperature has deviated from the setpoint. The larger this deviation is the longer the unit will wait before corrective action is taken to achieve the setpoint. This parameter is adjustable from 0 to 15 minutes. The factory default is 0.
Temperature Derivative Time—Monitors the rate of change and will reduce or increase the amount of corrective action based on the actual temperature increasing or decreasing toward the temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.
Dewpoint Margin—Selects the difference between the room dew point and the coolant temperature control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory default is
4.0°F (2.2°C).
Minimum Control Point—Sets the minimum supply coolant temperature the Liebert DCP will maintain. This parameter is adjustable from 40 to 113°F (4.4 to 45.0°C). The factory default is 55°F (12.8°C).
Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go below this value. The parameter is adjustable from 0 to 30%. The factory default is 15%.
Liebert® DCP
42
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Basic Settings (page 1 of 7)
SYSTEM
PASSWORD (Actual Level 0) ???? Maintenance Frequency Per Year 1 Max Bonus 0 Max Penalty 0 Last Maintenance 08/25/2014 Service Engineer NOBODY Confirm PM No Calculated Next Maintenance 08/2014
S001 S002 S003 S004 S005 S006 S007 S008 S009 S010 S011
to confirm
for next/previous unit then
to select parameter
to change parameter
Pump 1 Settings ( page 2 of 7)
UNIT 1
S012 S013 S014 S015 S016 S017 S018 S019 S020 S021 S022
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ???? Number of Starts 31 Run Hours 453hrs Average Run Time 876min Starts per Day Best 1 Starts per Day Worst 24 Number of Alarms 1 Actual Bonus 0

Figure 45 Maintenance—Basic Settings screen, page 1 of 7

Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year time span.
Max Bonus—Increases the time until the next required maintenance. Service personnel should assign a bonus when a service visit finds all components working optimally.
Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign a penalty when a service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of the last visit.
Service Engineer—Provides a label for the service representative to list either the company name or representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance and resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus set in the Liebert iCOM

Figure 46 Maintenance—Pump 1 Settings screen, page 2 of 7

®
control.
43 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Pump 2 Settings ( page 3 of 7)
UNIT 1
S023 S024 S025 S026 S027 S028 S029 S030 S031 S032 S033
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ???? Number of Starts 2 Run Hours 0hrs Average Run Time 0min Starts per Day Best 1 Starts per Day Worst 24 Number of Alarms 1 Actual Bonus 0
Number of Starts—Shows the number of starts for the unit’s Pump 1.
Run Hours—Shows the number of run hours for the unit’s Pump 1.
Average Run Time—Shows the average run time of the unit’s Pump 1.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1.
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will
always take the value from the worst component for the next maintenance indication.

Figure 47 Maintenance—Pump 2 Settings screen, page 3 of 7

Number of Starts—Shows the number of starts for the unit’s Pump 2. Run Hours—Shows the number of run hours for the unit’s Pump 2. Average Run Time—Shows the average run time of the unit’s Pump 2. Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2. Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2. Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2 Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will
always take the value from the worst component for the next maintenance indication.
Liebert® DCP
44

Figure 48 Maintenance screens, pages 4 through 7

Compressor 1A Sett ings (page 4 of 7)
UNIT 1
S034 S035 S036 S037 S038 S039 S040 S041 S042 S043 S044
to conf irm
for next /prev ious unit then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
Compressor 1B Settings (page 5 of 7)
UNIT 1
S045 S046 S047 S048 S049 S050 S051 S052 S053 S054 S055
to confirm
for next/previous unit then
to sel ect parameter
to change parameter
PAS SW OR D (Actual Lev el 0 ) ????
Compressor 2A Sett ings (page 6 of 7)
UNIT 1
S056 S057 S058 S059 S060 S061 S062 S063 S064 S065 S066
to conf irm
for next /prev ious unit then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
Compressor 2B Settings (page 7 of 7)
UNIT 1
S067 S068 S069 S070 S071 S072 S073 S074 S075 S076 S077
to confirm
for nex t/ prev ious unit then
to sel ect parameter
to change parameter
PAS SW OR D (Actual Lev el 0 ) ????
DIAGNOSTICS/SERVICE MODE (page 1 of 6) UNIT 01
S301 S302 S303 S304 S305 S306 S307 S308 S309 S310 S311
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ????
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Pages 4 through 7 apply only to the Liebert XDC™. No Liebert DCP parameters are present.

Figure 49 Diagnostics/Service Mode screen, page 1 of 6

Page 1 applies to the Liebert XDC™ only. No Liebert DCP parameters are present.
45 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
DIAGNOSTICS/SERVICE MODE (page 2 of 6) UNIT 01
S312 S313 S314 S315 S316 S317 S318 S319 S320 S321 S322
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ???? Manual Mode No Pump 1 Off Pump 2 Off
3P Start Completed/Active No No 3P Actuator Input Request 30.00% 3P Actuator Position 30% 3P Actuator Open Off 3P Actuator Close Off Valve Feedback 30%
DIAGNOSTICS/SERVICE MODE (page 3 of 6) UNIT 01
S323 S324 S325 S326 S327 S328 S329 S330 S331 S332 S333
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ????

Figure 50 Diagnostics/Service Mode screen, page 2 of 6

Manual Mode—Used to place the Liebert iCOM® in manual mode. This is the initial setting necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each service menu item shows the current status of each parameter.
Pump 1—Starts the unit’s Pump 1.
Pump 2—Starts the unit’s Pump 2.
3P Start Active/Complete—Displays if the startup routine is active, and if it is completed.
3P Actuator Input Request—Shows the percent call for cooling.
3P Actuator Position—Sets the position of the actuator 0-100% in manual mode.
3P Actuator Open—Opens the 3P actuator when set to ON in manual mode.
3P Actuator Close—Closes the 3P actuator when set to ON in manual mode
Valve Feedback—Opens the valve percent in manual mode.

Figure 51 Diagnostics/Service Mode screen, page 3 of 6

Liebert® DCP
Page 3 applies to the Liebert XDC™ only. No Liebert DCP parameters are present.
46
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
DIAGNOSTICS/SERVICE MODE (page 4 of 6) UNIT 01
S334 S335 S336 S337 S338 S339 S340 S341 S342 S343 S344
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ????
Manual Mode Control Type Full Manual Deviation 12% Analog Output R amp 1 30% Analog Output R amp 2 0% Analog Output R amp 3 60% Analog Output R amp 4 58% Alarm Relay Off Warning Relay Off
DIAGNOSTICS/SERVICE MODE (page 5 of 6) UNIT 01
S345 S346 S347 S348 S349 S350 S351 S352 S353 S354 S355
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ???? Status Remote Shutdown o –o On Status Fan Failure o/o Ok Status Diff Press Switch 1 o/o Act
Status Customer Input 1 o/o Ok Status Condensation Detect o/o Ok Status Unit Ready o–o On

Figure 52 Diagnostics/Service Mode screen, page 4 of 6

Manual Mode Control Type—Not currently used.
Manual Deviation—Not currently used.
Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory
default for the Liebert DCP is the Valve Percent Open.
Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory default for the Liebert DCP is the Call for Cooling.
Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory default for the Liebert DCP is the CW Temp.
Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory default for the Liebert DCP is the coolant temperature.
Alarm Relay—Used to activate the Liebert iCOM® common alarm relay output.
Warning Relay—Used to activate the Liebert iCOM’s warning relay output.

Figure 53 Diagnostics/Service Mode screen, page 5 of 6

47 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
DIAGNOSTICS/SERVICE MODE (page 6 of 6) UNIT 01
S356 S357 S358 S359 S360 S361 S362 S363 S364 S365 S366
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ????
Status Remote Shutdown—Displays the status of the unit’s remote shutdown input.
Status Fan Failure—Displays the status of the dry contact to communicate fan failure at a module.
(The dry contacts are not used to communicate a fan failure alarm when using CANbus.)
Status Diff Press Switch 1—Displays the status of the differential pressure switch.
Status Customer Input 1—Displays the status of the customer input 1 alarm.
Status Condensation Detect—Displays the status of the dry contact to communicate condensate
detection at a module.
Status Unit Ready—Shows unit status when a secondary device, such as a fire detection system, is employed.

Figure 54 Diagnostics/Service Mode screen, page 6 of 6

Page 6 applies to the Liebert XDC™ only. No Liebert DCP parameters are present.
Liebert® DCP
48

Figure 55 Set Alarms screen, page 1 of 7

SET ALARMS (page 1 of 7) UNIT 01
S201 S202 S203 S204 S205 S206 S207 S208 S209 S210 S211
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ???? High Room Air Temperature 88.0°F Low Room Air Temperature 55.0°F High Room Dewpoint 65.0°F High Coolant Temperature 80.0°F
High Chilled Water Temperature 60.0°F
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Coolant Temperature—Sets the threshold for a high a coolant temperature alarm. The range for the high supply coolant temperature alarm is from 33.8 to 122°F (1 to 50°C); the default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high chilled water temperature alarm. The range for the high supply fluid temperature alarm is from
33.8
to 113°F (1 to 45°C); the default is 60°F (15.6°C).
49 Liebert® DCP

Figure 56 Set Alarms screen, page 2 of 7

SET ALARMS (page 2 of 7) UNIT 01
S212 S213 S214 S215 S216 S217 S218 S219 S220 S221 S222
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) ???? Customer Input 1 Water Alarm Customer Input 1 active when Closed
WARNING ACTIVATES ALARM RELAY Yes Reset Disabled Alarms No
Customer Input 1—Selects the device and operation of the customer input. Each event reflects a different alarm and possible action to the unit. Selectable options are:
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Call Service C-Input Water Smoke
Customer Input 1 active when—Selects whether the Customer Input 1 input is normally closed or normally open.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning occurs.
Reset Disabled Alarms—Resets disabled events.
The Set Alarm Screens (Figure 57 through 61) permit setting the operation of an active alarm. Each event can be enabled or disabled and can be set to operate as an alarm, warning or message. The delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Liebert® DCP
50

Figure 57 Set Alarms screen, page 3 of 7

SET ALARMS (page 3 of 7) UNIT 01
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
HIGH TEMP SENSOR A LOW TEMP SENSOR A HIGH TEMP SENSOR B LOW TEMP SENSOR B HIGH DEWPOINT SENSOR A FAILURE SENSOR B FAILURE HIGH CHILLED WATER TEMP SUPPLY CW SENSOR FAILURE
S223 S224 S225 S226 S227 S228 S229 S230 S231 S232 S233 S234 S235
DELAY
30 30 30 30 30
30
????
TYPE
ALM ALM ALM ALM ALM ALM ALM ALM ALM
EN-DIS ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
HIGH TEMP SENSOR A—Enables or disables the High Temperature Sensor A event, which occurs when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOW TEMP SENSOR A—Enables or disables the Low Temperature Sensor A event, which occurs when the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH TEMP SENSOR B—Enables or disables the High Temperature Sensor B event, which occurs when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is reported as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOW TEMP SENSOR B—Enables or disables the Low Temperature Sensor B event, which occurs when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH DEWPOINT—Enables or disables the High Dewpoint event, which occurs when the calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
SENSOR A FAILURE—Enables or disables the Sensor A Failure event, which occurs when the control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
SENSOR B FAILURE—Enables or disables the Sensor B Failure event, which occurs when the control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH CHILLED WATER TEMP—Enables or disables the High Chilled Water Temp event, which occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
SUPPLY CW SENSOR FAILURE—Enables or disables the Supply CW Sensor Failure event, which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
51 Liebert® DCP

Figure 58 Set Alarms screen, page 4 of 7

SET ALARMS (page 4 of 7) UNIT 01
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
HIGH COOLANT TEMP LOW COOLANT TEMP SUPPLY COOLANT SENSOR LOSS OF FLOW PUMP 1 LOSS OF FLOW PUMP 2 PUMP SHORT CYCLE
CONTROL VALVE FAILURE
S236 S237 S238 S239 S240 S241 S242 S243 S244 S245 S246 S247 S248
DELAY
30 30
????
TYPE
ALM ALM ALM ALM ALM ALM
ALM
EN-DIS ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE
ENABLE
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
HIGH COOLANT TEMP—Enables or disables the High Coolant Temp event, which occurs when the reading from supply coolant temperature sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOW COOLANT TEMP—Enables or disables the Low Coolant Temp event, which occurs when the reading from supply coolant temperature sensor is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
SUPPLY COOLANT SENSOR—Enables or disables the Supply Coolant Sensor event, which occurs when the control no longer senses a signal from the Supply Coolant Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when Pump 1 is commanded to run and the flow switch does not sense flow. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when Pump 2 is commanded to run and the flow switch does not sense flow. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs when the chilled water control valve has been commanded by the control to open or close and no change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Liebert® DCP
52

Figure 59 Set Alarms screens, pages 5 and 6

SET ALARMS (page 5 of 7) UNIT 01
to confirm
for next/previous unit then
to select paramet er
to change parameter
PAS SW OR D (Actual Level 0)
S259 S250 S251 S252 S253 S254 S255 S256 S257 S258 S259 S260 S261
DELAY
????
TYPEEN-DIS
SET ALARMS (page 6 of 7) UNIT 01
to confirm
for next/previous unit then
to select paramet er
to change parameter
PAS SW OR D (Actual Level 0)
S262 S263 S264 S265 S266 S267 S268 S269 S270 S271 S272 S273 S274
DELAY
????
TYPEEN-DIS
SET ALARMS (page 7 of 7) UNIT 01
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
CONDENSATION DETECTED FAN FAILURE CUSTOMER INPUT 1 SMOKE DETECTED WATER UNDER FLOOR UNIT X DISCONNECTED WORKING HRS EXCEEDED CALL SERVICE LOSS OF POWER
S275 S276 S277 S278 S279 S280 S281 S282 S283 S284 S285 S286 S287
DELAY
3 3 5 5 5
5
????
TYPE
ALM ALM ALM ALM
ALM WRN WRN
ALM WRN
EN-DIS
ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE
Pages 5 and 6 apply to the Liebert XDC™ only. No Liebert DCP parameters are present.

Figure 60 Set Alarms screen, page 7 of 7

Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
CONDENSATION DETECTED—Enables or disables the Condensation Detected event, which occurs when water is detected at a cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event (not currently used).
FAN FAILURE—Enables or disables the Fan Failure event, which occurs when a fan failure occurs at a cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event (not currently used).
CUSTOMER INPUT 1—Enables or disables the Customer Input 1 event, which occurs when 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
SMOKE DETECTED—Enables or disables the Smoke Detected event, which occurs when the Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
53 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
WATER UNDER FLOOR—Enables or disables the Water Under Floor event, which occurs when the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
UNIT X DISCONNECTED—Not currently used.
WORKING HOURS EXCEEDED—Enables or disables the Working Hrs Exceeded event, which
occurs when a component has exceeded the user-specified limit. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
CALL SERVICE—Enables or disables the Call Service event, which occurs when the Customer Input 1 is configured for “Call Service” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOSS OF POWER—Enables or disables the Loss of Power event, which occurs when the unit is On and operational and the 24VAC power to the control is lost. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Liebert® DCP
54
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SENSOR CALIBRATION/SETUP (page 1 of 3) UNIT 01
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Temperature Sensor A Calibrated Temperature Sensor A Humidity Sensor A Calibrated Humidity Sensor A Temperature Sensor B Calibrated Temperature Sensor B Humidity Sensor B Calibrated Humidity Sensor B
S601 S602 S603 S604 S605 S606 S607 S608 S609 S610 S611
???? +0.0 °F
70.3°F +0.0 °F
38.3% +0.0 °F
72.3°F +0.0 °F
35.6%

Figure 61 Sensor Calibration/Setup screen, page 1 of 3

Temperature Sensor A—Adjusts the temperature reading from the actual remote CAN Temp Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Temperature Sensor A—Displays the adjusted temperature value of the remote CAN Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the offset Temperature Sensor A.
Humidity Sensor A—Adjusts the humidity reading from the actual remote CAN Temp Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor A—Displays the adjusted humidity value of the remote CAN Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the offset Humidity Sensor A.
Temperature Sensor B—Adjusts the temperature reading from the actual remote CAN Temp Humidity sensor designated as Sensor B to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Temperature Sensor B—Displays the adjusted temperature value of the remote CAN Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Temperature Sensor B.
Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as Sensor B to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Humidity Sensor B.
55 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SENSOR CALIBRATION/SETUP (page 2 of 3) UNIT 01
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSWORD (Actual Level 0) Supply Coolant Sensor Calibrated Supply Coolant Sensor
Supply Chilled Water Sensor Calibrated Supply Chilled Water Sensor
S612 S613 S614 S615 S616 S617 S618 S619 S620 S621 S622
???? +0.0°F
58.5°F
+0.0°F
60.1°F
SENSOR CALIBRATION/SETUP (page 3 of 3) UNIT 01
PASSWORD (Actual Level 0) Supply Coolant Sensor 0% Supply Coolant Sensor 100%
S623 S624 S625 S626 S627 S628 S629 S630 S631 S632 S633
????
30.0°F
90.0°F
to confirm
for next/previous unit then
to select parameter
to change parameter

Figure 62 Sensor Calibration/Setup screen, page 2 of 3

Supply Coolant Sensor—Adjusts the temperature reading from the actual supply coolant sensor to compensate for any error of the sensor.
Calibrated Supply Coolant Sensor—Displays the adjusted temperature value of the supply coolant sensor. This value is the actual sensor reading plus or minus the offset Supply Coolant Sensor.
Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled water sensor to compensate for any error of the sensor.
Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water Sensor.

Figure 63 Sensor Calibration/Setup screen, page 3 of 3

Liebert® DCP
Supply Coolant Sensor 0%—Allows the sensor reading to be calibrated at the lowest reading of the sensor. This calibration changes the start point of the sensor reading.
Supply Coolant Sensor 100%—Allows the sensor reading to be calibrated at the highest reading of the sensor. This calibration changes the end point of the sensor reading.
56
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SYSTEM/NETWORK SETUP (page 1 of 2) SYSTEM
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Number of Connected Units
Configuration Safe Network Safe SW Version
S801 S802 S803 S804 S805 S806 S807 S808 S809 S810 S811
????
1
No No
OK OK
XP1.00.010.STD
SYSTEM/NETWORK SETUP (page 2 of 2) SYSTEM
Attention: any changes done on these parameters must be followed by a 'Save+Reboot ' command .
PASSW ORD (Actual Level 0) IP Address Netmask Gateway MAC U2U Protocol U2U Address U2U Group
Bootloader Variables
S812 S813 S814 S815 S816 S817 S818 S819 S820 S821 S822
????
192.168.254.003
255.255.255.000
0.000 .000 .000
00:00 :68:19 :40:C7
GBP
33
1
NoOK

Figure 64 System/Network Setup screen—System, page 1 of 2

Number of Connected Units—Shows the number of displays connected. This is always 1.
Configuration Safe—Saves or loads configuration settings for the display that have been modified
from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert
®
iCOM Load will write the settings from the internal storage file to the application software. The internal file is updated automatically every 12 hours.
Network Safe—Saves or loads network settings for the display that have been modified from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service Tool. Selecting Save will write the settings to the internal storage file and selecting Load will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM display.

Figure 65 System/Network Setup screen—System, page 2 of 2

IP Address—Contains the network address of the display. This address must be unique on the network. The factory default is 192.168.254.003.
Service Tool. Selecting Save will write the settings to the internal storage file and selecting
57 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SYSTEM/NETWORK SETUP (page 1 of 2)
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Monitoring Address
Unit Name
Configuration Safe Network Safe SW Verson
S823 S824 S825 S826 S827 S828 S829 S830 S831 S832 S833
????
3
UNIT
No No
OK OK
XP1.00.008.STD
UNIT 01
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A network point that acts as an entrance to another network. The factory default is
0.000.000.000.
MAC—A unique hardware identifier for the Ethernet device. The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other networked Liebert Liebert DCP does not perform Teamwork Operations.
U2U Protocol—This is always set to GBP.
U2U Address—A unique identifier for each display on the network. Display addresses range from 33
to 64. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Used to create zones or groups within a U2U network. Once a group number is selected, the display will see only other devices with the same group number. The group number can be changed to view other devices in different groups. Not currently used.
Bootloader Variables—Indicates the bootloader has changed since it was last loaded. This parameter should only be activated by an authorized service person.

Figure 66 System/Network Setup screen—Unit, page 1 of 2

DCP units. The
Monitoring Address—Sets the address used by the Liebert IntelliSlot® cards. This is set to 3 at the factory and should not be changed.
Unit Name—Identifies the unit from the local or remote display. This label will show at the top right of every screen that has monitoring or configuration of that unit
Liebert® DCP
Configuration Safe—Saves or loads configuration settings for the control board that have been modified from the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM selecting “Load” will write the settings from the internal storage file to the application software. The internal file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the control board that have been modified from the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load” will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM.
®
Service Tool. Selecting “Save” will write the settings to the internal storage file and
58
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SYSTEM/NETWORK SETUP (page 2 of 2)
Attention: any changes done on these parameters must be followed by a 'Save+Reboot ' command .
PASSW ORD (Actual Level 0) Monitoring Protocol IP Address Netmask Gateway MAC U2U Protocol U2U Address U2U Group Bootloader Variables Static RAM
S834 S835 S836 S837 S838 S839 S840 S841 S842 S843 S844
????
Velocity V4
192.168.254.003
255.255.255.000
0.000 .000 .000
00:00:68 :19:9B:42
GBP
1
1 No No
OK OK
UNIT 01

Figure 67 System/Network Setup screen—Unit, page 2 of 2

Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default which will provide communications to the Liebert IntelliSlot for communication to the Liebert SiteLink(-E) units.
IP Address—Contains the network address of the display. This address must be unique to every other device on the network. The factory default is 192.168.254.003.
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A gateway is a network point that acts as an entrance to another network. The factory default is 0.000.000.000.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other Liebert DCP units that are networked. The Liebert DCP does not perform Teamwork Operations.
U2U Protocol—Always set to GBP.
U2U Address—Unique identifier for each display on the network. Display addresses range from 1 to
32. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Creates zones or groups within a U2U network. Once a group number is selected the display will only see other devices with the same group number. The group number can be changed to view other devices in different groups. Not currently used.
Bootloader Variables—Indicates if there has been a change to the boot loader since it was last loaded. This parameter should only be activated by authorized service personnel.
Static RAM—Allows service personnel to clear and reboot the RAM of the control board. Only Emerson
®
service personnel should perform this function.
®
. Liebert Hironet™ is only used on Liebert HPM™
®
housing. IGMnet will activate the 77/78 terminals
59 Liebert® DCP

Figure 68 Options Setup screen, page 1 of 2

OPTIONS SETUP (page 1 of 2)
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Autorestart Enabled Single Unit Auto Restart Unit Start Sequence D elay Control Delay Time Pump Start Time Delay Pump Wait Time Delay Pump Off Time Delay
Pump Short Cycle Delay
S401 S402 S403 S404 S405 S406 S407 S408 S409 S410 S411
????
Yes
5sec 1sec
1sec 10sec 10sec
5sec
30min
UNIT 01
Autorestart Enabled—Restarts the unit after a power cycle when set to Yes. When this parameter is set to No, the unit will not restart after a power cycle.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Single Unit Auto Restart—Sets a time delay for the unit to restart when the Auto Restart Enabled is set to Yes. The delay begins once the boot process has completed. This parameter allows units to be staggered On to reduce the amount of simultaneous power consumption after a loss of power.
Unit Start Sequence Delay—Not currently used.
Control Delay Time—Not currently used.
Pump Start Time Delay—Sets a time delay to ensure that coolant begins flowing when the pump
starts. If coolant does not begin flowing before the user-set delay expires, the pump will be turned Off.
Pump Wait Time Delay—Sets the pump wait time delay to prevent the pump from continuing to run when coolant is not flowing. If a pump is running normally and coolant flow is lost, the pump will stay On for the specified time trying to re-establish coolant flow. If coolant flow resumes during the specified interval, the pump will continue operating. If the wait time expires and coolant flow has not resumed, the pump will shut down.
Pump Off Time Delay—Sets the length of time a pump will remain off when coolant flow is interrupted or stops. After the time delay has expired, the control will try to restart the pump.
Lead Pump—Sets which pump is the active pump. It can be set to PUMP 1 or PUMP 2. The control will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF FLOW condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time delay has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.
Pump Short Cycle Delay—Sets the time to lock Off the unit if it is unable to establish coolant flow within this set amount of time.
Liebert® DCP
60

Figure 69 Options Setup screen, page 2 of 2

OPTIONS SETUP (page 2 of 2)
to confirm
for next/previous unit then
to select parameter
to change parameter
PASSW ORD (Actual Level 0) Valve Start Open Valve Start TD 3P Actuator Runtime 3P Actuator Direction Unit Off Valve % Open
S412 S413 S414 S415 S416 S417 S418 S419 S420 S421 S422
????
30%
90sec 70sec
Direct
30%
UNIT 01
MODULE SETUP (page 1 of 20) UNIT 01
PASSW ORD (Actual Level 0) NODE ID 81 CONDENSATION DETECTED LOCAL MODULE SHUTDOWN SENSOR FAILURE FAN FAILURE FAN CONTROL MODE DISABLE LOCAL BUTTON FLASH LED AT MODULE SET MODULE LABEL SUPPLY AIR TEMP LIMITS RETURN AIR TEMP LIMITS FIRMWARE VERSION
S901 S902 S903 S904 S905 S906 S907 S908 S909 S910 S911 S912 S913
DELAY
15 15 30 30
????
TYPE
ALM ALM ALM
EN-DIS ENABLE ENABLE ENABLE ENABLE
A Z 81 High 80 Low 50 °F High 120 Low 60 °F
XXX.XX.XXX
OFF NO NO
Valve Start Open—Sets position of the valve when the unit starts.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Valve Start TD—Sets a time interval for the unit to complete startup and enter into normal operation.
3P Actuator Runtime—If Valve Control is selected for “Time,” then this parameter sets the travel time of the valve to determine the full open and closed position of the valve. This parameter is set at the factory, based on the valve manufacturer’s specifications.
3P Actuator Direction—Sets if the valve is a “Direct” or “Reverse” acting valve.
Unit Off Valve % Open—Sets the valve position when the unit is Off.

Figure 70 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only

61 Liebert® DCP
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
MODULE SETUP (page 1 of 20) UNIT 01
PASSW ORD (Actual Level 0) NODE ID 81 CONDENSATION DETECTED LOCAL MODULE SHUTDOWN SENSOR FAILURE FAN FAILURE FAN CONTROL MODE DISABLE LOCAL BUTTON FLASH LED AT MODULE SET MODULE LABEL SUPPLY AIR TEMP LIMITS RETURN AIR TEMP LIMITS FIRMWARE VERSION
S901 S902 S903 S904 S905 S906 S907 S908 S909 S910 S911 S912 S913
DELAY
15 15 30 30
????
TYPE
ALM ALM ALM
EN-DIS ENABLE ENABLE ENABLE ENABLE
A Z 81 High 80 Low 50 °F High 120 Low 60 °F
XXX.XX.XXX
OFF NO NO
This screen selects the operation of an active alarm for each smart module. Each event can be enabled or disabled and can be set to operate as an alarm, a warning or a message. The delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer/front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Fan Control Type—Sets the fan control mode. Values can be OFF, ON, ON ALL and TEMP CNTL.
Disable Local Button—Disables the push button on the front of the smart module. To disable the
push button, set the parameter to YES. To re-enable the push button, set the parameter to NO.
Flash LED at Module—Flashes the LED on the smart module when set to Yes.
Set Module Label—A four-character label consisting of two letters and two numerals. This is the
standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or both labels can be used and are entered using this screen.
Supply Air Temp Limit—Sets the high and low supply air temperature to from the module. An alarm will occur if the temperature falls outside the limits.
Return Air Temp Limit—Sets the high and low return air temperature to from the module. An alarm will occur if the temperature falls outside the limits.
Firmware Version—Displays the firmware version installed on the smart module.

Figure 71 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only

Liebert® DCP
62
Start the Liebert DCP with Liebert iCOM
®
5.0 START THE LIEBERT DCP WITH LIEBERT ICOM
®

5.1 Checklist for Liebert DCP Startup

NOTE
Before any action that could cause a disturbance in the Liebert DCP system’s cooling function is begun, the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed
1. Verify that bypass flow controllers were installed (if applicable).
2. Check all isolation ball valves in the Liebert DCP and cooling module and verify that all are open.
3. Check rotation of the Liebert DCP’s pumps.
4. Verify that air is being discharged into the cold aisle.
5. Confirm that the system has been properly filled with water (see 3.7 - Filling Instructions).
6. Confirm that the remote temperature/humidity sensors provided have been installed in optimal locations (see
The Liebert DCP system is now ready to be turned ON.
2.4 - Remote Sensor Installation—Proper Placement)

5.2 Starting the Liebert DCP with Liebert iCOM Controller

The Liebert DCP is started, stopped and controlled through the Liebert iCOM controller. Figure 25 shows the Liebert iCOM keypad.
1. Turn the Liebert DCP On with the user interface (I/O button). Allow the system to attempt to start for at least 2 minutes.
If the Liebert DCP pump cannot maintain flow and continues to switch over due to starting difficulties, refer to
2. Check flow switch functionality: The Liebert DCP system should be On. If it is Off: a. Turn the Liebert DCP On via user interface (I/O button).
If no “Loss of Flow” alarm is present—This suggests that there is flow. Test the flow switch by closing the ball valve on either the suction line or discharge line to stop the flow.
This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has opened on low flow.
If a “Loss of Flow” alarm is present—This suggests that there is no flow. Verify that this is correctly annunciated by checking for proper water charge (see
However, if there is flow, the flow switch could be faulty. Check the flow switch, making sure that the electrical connections are properly connected.
Then check the flow switch electrically by making sure that the unit has 24VAC across it.
7.0 - Troubleshooting.
3.7 - Filling Instructions.)
63 Liebert® DCP

6.0 ALARM DESCRIPTIONS AND SOLUTIONS

6.1 Alarm Descriptions

NOTE
Alarms must be acknowledged before they can be reset. To acknowledge or silence an alarm, press the ALARM key one time. This will silence the alarm; the red LED will remain illuminated until the alarm is reset.
CALL SERVICE—Activated when Customer Input 1 is configured for “Call Service” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.
CONDENSATION DETECTED (optional)—Activated when water is detected at a cooling module. A 24VAC signal is applied to the condensation input on the control board using a pair of twisted wires or the alarm is sent via CANbus communication. When this alarm is active, the control will raise its fluid control point by 4°F (2.2°C). This alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or condensation input. The alarm can also be reset by cycling the power. The main power must be cycled to remove the 4°F (2.2°C) offset (not currently used).
CONTROL VALVE FAILURE—Activated when the chilled water control valve has been commanded to open or close by the control and no change is detected by the valve position signal. The alarm is reset when the main power is cycled.
CUSTOMER INPUT 1—Activated when a 24VAC signal is applied to the customer alarm input on the control board. This alarm will reset when the 24VAC signal stops being sent from the customer alarm input. WATER UNDER FLOOR, SMOKE DETECTED, CALL SERVICE, and COMP LOCK PD are possible designations for this alarm; they are set with the Unit Code.
FAN FAILURE (optional)—Activated when a 24VAC signal is applied to the fan failure input on the control board using a twisted pair of wires or the alarm is sent via CANbus communication. This alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or fan failure input. The alarm can also be reset by cycling the power (not currently used).
HIGH CW TEMP—Activated when the Supply CW sensor reads the chilled water temperature above the user-specified alarm setpoint. This alarm will reset when the reading from the fluid temperature sensor drops 5°F (2.8°C) below the user-specified setpoint and the alarm has been acknowledged.
HIGH DEW POINT—Activates when the calculated dew point at either Sensor A or B exceeds the user-specified alarm setpoint. The alarm will reset when the calculated room dew point from both Sensor A and Sensor B is 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.
HIGH COOLANT TEMP—Activated when the coolant temperature sensor reads the coolant temperature above the user-specified alarm setpoint. This alarm will reset when the reading from the coolant temperature sensor drops 2°F (1.1°C) below the user-specified setpoint and the alarm has been acknowledged.
HIGH TEMP SENSOR A—Activated when the reading from Sensor A is above the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.
HIGH TEMP SENSOR B—Activated when the reading from Sensor A is above the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.
LOSS OF FLOW PUMP 1—Activated when Pump 1 is commanded to run and the flow switch does not sense flow. After attempting to start Pump 1 three times, the Liebert switch to the other pump to establish flow. This alarm will reset when flow has been established on Pump 1 and the alarm has been acknowledged.
LOSS OF FLOW PUMP 2—Activated when Pump 2 is commanded to run and the flow switch does not sense flow. After attempting to start Pump 2 three times, the Liebert DCP will automatically switch to the other pump to establish flow. This alarm will reset when flow has been established on Pump 2 and the alarm has been acknowledged.
Alarm Descriptions and Solutions
DCP will automatically
LOW MEMORY—Activated when the control board is low in memory resources. This alarm rests automatically as soon as memory consumption falls below the threshold.
Liebert® DCP
64
Alarm Descriptions and Solutions
LOW COOLANT TEMP—Activated when the supply coolant temperature sensor temperature reading drops below the higher of the two calculated dew points, assuming that neither Sensor A nor Sensor B has a sensor failure alarm. This alarm will reset when the coolant temperature sensor reads the fluid temperature above both of the two calculated dew points and the alarm has been acknowledged. This alarm can lock the unit Off. If this occurs, the main power must be cycled, or the Low Coolant Temp Alarm Code in the Service Diagnostics menu must be reset to 0.
LOW TEMP SENSOR A—Activated when the reading from Sensor A drops below the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A rises 2°F (1.1°C) above the setpoint and the alarm has been acknowledged.
LOW TEMP SENSOR B—Activated when the reading from Sensor B drops below the user-specified alarm setpoint. The alarm will reset when the reading from Sensor B rises 2°F (1.1°C) above the setpoint and the alarm has been acknowledged.
PUMP SHORT CYCLE—Activated when the Liebert DCP is trying to establish flow and is unable to do so. The Liebert DCP will attempt three times to establish flow on a pump before trying the other pump. The control will keep cycling three times on one pump, then three times on the other pump until it is able to establish flow. If this cycling occurs for 30 minutes and the Liebert DCP still does not establish flow, a PUMP SHORT CYCLE alarm will be present. This alarm will shut down the Liebert DCP. To reset this alarm, the main power must be cycled.
RAM/BATTERY FAIL—Activated when the RAM backup battery or the RAM itself has failed. This requires a hardware replacement.
SENSOR A FAILURE—Activated when the controls no longer senses a signal from Sensor A. This alarm will reset when the signal is returned and the alarms has been acknowledged.
SENSOR B FAILURE— Activated when the controls no longer senses a signal from Sensor B. This alarm will reset when the signal is returned and the alarm has been acknowledged.
SMOKE DETECTED—Activated when the Customer Input 1 is configured for “Smoke” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
SUPPLY CW SENSOR FAILURE—Activated when the control no longer senses a signal from the Supply CW sensor. This alarm will reset when the signal is returned.
SUPPLY COOLANT SENSOR FAILURE—Activated when the control no longer senses a signal from the supply coolant sensor. This alarm will reset when the signal is returned.
UNIT CODE MISSING—Activated when a valid unit code has not been entered and saved. To reset, enter valid unit code, save and execute.
WATER UNDER FLOOR—Activated when Customer Input 1 is configured for “Water Alarm” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.

6.2 Warning Descriptions

LOSS OF POWER—Activated when the unit is On and operational and 24VAC power to the control is lost. This alarm will be emitted when power is restored to the control. The Liebert DCP will restart at a user-defined time delay after power is restored. Once activated, the alarm will remain activated for 30 minutes.
PUMP 1 HRS EXCEED—Activated when the Pump 1 Actual Hours exceeds the user-specified limit. To reset, Actual Hours must be reset to 0.
PUMP 2 HRS EXCEED—Activated when the Pump 2 Actual Hours exceeds the user-specified limit. To reset, Actual Hours must be reset to 0.
65 Liebert® DCP

6.3 System Shutdown Causes

Unit Is Off By Coolant Sens Fail

The control has lost its signal from the coolant temperature sensor. The control has no way of controlling the coolant temperature, so the unit is shut off. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.

Unit Is Off By High CW Temp

The entering chilled water temperature is too high to keep the pump(s) running normally. If a HIGH CW TEMP alarm occurs and the pump loses flow, then the Liebert DCP will go into a pre-chill mode. The Liebert DCP can attempt to start again only if the entering chilled water temperature drops below the HIGH CW TEMP setpoint.

Unit Is Off By Pump Short Cycle

The control was unable to get a pump started upon startup or after a loss of flow. The control looks at the SHORT CYCLE time delay. If it cannot establish flow within that amount of time, the unit is shut down. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.

Unit Is Off By Low Coolant Temp

The control was unable to raise the coolant temperature to the calculated fluid temperature control point. The unit is shut down because if the control cannot raise the coolant temperature to the calculated coolant temperature control point, water may condense on the coolant piping and receiving coils. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
Alarm Descriptions and Solutions
Liebert® DCP
66

7.0 TROUBLESHOOTING

Table 4 Troubleshooting the Liebert DCP

Symptom Possible Cause Check or Remedy
No main power Check L1, L2 and L3 for rated voltage.
Loose electrical connections Tighten connections.
Pump will not energize
Pump will not start or run
Pump will not start
Pump noisy
Liebert DCP (Pump) suddenly stops
Pipe rattle Loose pipe connections Check pipe connections.
Chilled water valve not working
Overloads tripped Allow pump to cool. Check amp draw.
Tripped circuit breaker Check circuit breaker to pump(s).
Incorrect phase wiring Check wiring phase.
No chilled water
Isolation valve(s) on pump suction and/or discharge is closed.
Supply chilled water is too high
Liebert XDK™ cooling modules are Off
Low Coolant Temperature (high dew point)
Flow switch not functioning Check for defective switch or miswiring.
Not enough charge See 5.1 - Checklist for Liebert DCP Startup.
Chilled water valve not closing completely.
Cavitation due to vapor in pump
Worn motor bearings Replace pump
Pump is rotating in reverse Check wiring phase.
Low Coolant Temperature
Loss of power
Leak in system - loss of charge
Low Chilled Water Temperature Alarm and Loss of Flow Pump X Alarm
Supply Fluid Sensor Failure Alarm
Motor operates but valve won't open
No 24 VAC power to motor Check for 24 VAC between P52-1 and P52-4.
No signal from control Check 24 VAC at P22-1 (close) or P22-3 (open).
Motor not operating
Check and verify that there is supply chilled water to the Liebert DCP.
Open all isolation valves completely during normal operation.
Check and verify that the chilled water temperature setpoint is at 50°F (10°C) or lower and that there is flow on the chilled water side.
Check Liebert XDK cooling modules to make sure that they are On prior to starting the Liebert DCP.
Check alarm(s) history on Liebert DCP. The Liebert DCP was operating below the dew point for a significant amount of time. Check humidity in conditioned space, lower humidity if necessary to allow Liebert DCP to operate at a lower temperature. (Disconnect must be switched to Off then back On to allow Liebert DCP to reset itself).
Wait at least 10 minutes before calibrating. Access the Advanced Menu>Factory Settings>Calibrate Actuator. Contact Liebert Services for assistance, 1-800-543-2778.
Check for adequate charge in system, refer to the User's Manual.
1. Check humidity of the room along with the location of remote sensors. Make sure that the sensors are not in a cold area where there is insufficient air flow for accurate, representative readings.
2. Chilled Water temperature is too cold.
3. Load is too light.
When power is restored, the Liebert DCP will automatically restart.
Check the entire system for leaks with a fluid sniffer. Repair as necessary.
Check supply chilled water temperature.
Check wiring.
Call service.
Check linkage for adjustment and be sure that it is tight on the valve.
Unplug P22 from the board. Jumper P22-5 to P52-4 for grounding, then jumper P22-1 to P52-1 to drive close. Remove jumper to close and then jumper P22-3 to P52-1 to drive open. If motor fails to work, replace it.
5.1 - Checklist for Liebert DCP Startup
Troubleshooting
67 Liebert® DCP
Table 4 Troubleshooting the Liebert DCP (continued)
Symptom Possible Cause Check or Remedy
Motor burnout
Main 24VAC fuse trips
Room becomes too warm
Check control panel for welded contactor contacts or welded overload contacts
Shorts or loose connections Check the wiring connections of the 24 VAC circuit.
Faulty circuit board Replace the circuit board.
Liebert DCP is Off
High dew point
Liebert XDK™ cooling modules are Off
Minimum room temperature setpoint is too high
Temperature/humidity sensors incorrectly placed
Troubleshooting
Replace defective components.
Check status of the Liebert DCP at the user interface. Turn system On at I/O button if system is Off.
Check temperature and relative humidity (RH) of room. Lower RH setpoint if necessary to lower dew point. At normal room temperature of 68°F (20°C), the RH should be set to 50% or lower.
Check Liebert XDK cooling modules to make sure that they are On before starting the Liebert DCP.
Check the setpoint in the User Setpoints menu (see Figure 44).
Place the sensor on the return air side of the primary air mover (e.g., Liebert DS doors, windows or similar areas.
). Do not install the sensor near unsealed
Liebert® DCP
68

8.0 MAINTENANCE

NOTICE
Risk of leaking chilled water and drain lines. Can cause equipment and building damage. Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson leak detection equipment for the unit and its factory- and field-installed supply, return and drain lines.
The Liebert DCP system components require little maintenance when proper fluid levels are maintained and proper startup and operation procedures are followed. The following task should be performed at the intervals stated:
• Clean or replace chilled water strainer annually. Adjust accordingly based on purity of chilled water.
Maintenance
®
recommends installing monitored
69 Liebert® DCP

9.0 SPECIFICATIONS

Table 5 Liebert DCP200 specifications

Models
Cooling Capacity, Nominal
Electrical Requirements
Dimensions, inches (mm)
Weight, lb (kg)
Installed, with Fluid and Chilled Water 1148 (521) 1322 (600)
Pipe Connections
Fluid Supply to Cooling Module 2-5/8" OD, Cu
Fluid Return from Cooling Module 2-5/8" OD, Cu
Chilled Water Supply and Return 2-5/8" OD, Cu
Control Valve
Pressure Drop – Chilled Water Side
Temperature Rise – Chilled Water Side at Rated Flow, °F (°C)
Number of Liebert Cooling Units Connected, Maximum
Liebert DCD35 10 @ 20 kW
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Operating Ambient Temperature, Maximum, °F (°C)
1. WSA = Wire Sizing Amps (Minimum supply circuit ampacity)
2. MFCB = Maximum Fuse or Circuit Breaker Size
DCP200RA2BB0 DCP200RM2BB0
200kW / 57 Tons, 60Hz 200kW / 57 Tons, 50Hz
Each capacity is based on 45ºF (7ºC) entering water temperature
and 114 gpm (26 m
3
/h) water flow rate. Capacity is reduced when
glycol mixtures are used in place of 100% water.
Input 460V/3/ph60Hz 380/415V/3ph/50Hz
Full Load Amps 7.3A 8.7A
1
WSA
MFCB
2
8 9
15 15
Height – Unit Only 78 (1981)
Height – As Shipped 83 (2108)
Width 38 (965)
Depth 34 (864)
Unit Only 931(423) 1105 (502)
Shipping Weight 1100 (499) 1275 (579)
2-way, 2" nominal; 35 PSIG close-off pressure rating;
150 PSIG maximum allowable pressure
14.0 psig (97kPa, 0.97bar), with 114 gpm (26 m3/h) water flow rate, control valve fully open
12.0 (6.7)
86 (30)
Specifications
Liebert® DCP
70
NOTES
Specifications
71 Liebert® DCP
Specifications
Liebert® DCP
72

COMPLIANCE WITH EUROPEAN UNION DIRECTIVES

Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 USA
Il Produttore dichiara che, se munito di marchio CE, il prodotto è conforme alle direttive dell'Unione europea:
The Manufacturer hereby declares that this product, when bearing the CE mark, conforms to the European Union directives:
Der Hersteller erklärt hiermit, dass das vorliegende Produkt, sollte es die CE-Kennzeichnung tragen, den folgenden Richtlinien der Europäischen Union entspricht:
Le fabricant déclare par la présente que ce produit, portant la marque CE, est conforme aux directives de l'Union européenne :
El fabricante declara por la presente que si este producto lleva el marcado CE es conforme con las directivas de la Unión Europea:
O fabricante declara por este meio que este produto, quando ostenta a marca CE, está em conformidade com as directivas da União Europeia:
Tillverkaren tillkännager härmed att den här produkten, när den är CE-märkt, överensstämmer med EU:s direktiv:
De fabrikant verklaart hierbij dat dit product, indien het van de CE-markering is voorzien, conform de EU-richtlijnen is:
Valmistaja vakuuttaa täten, että mikäli tuotteessa on CE-merkintä, se täyttää seuraavien EU-direktiivien vaatimukset:
Produsenten erklærer herved at dette produktet, når det er CE-merket, er i samsvar med EU-direktiver:
Producenten erklærer hermed, at dette produkt overholder EU's direktiver, når det bærer CE-mærket:
Ο Κατασκευαστής δηλώνει ότι το προϊόν αυτό, το οποίο φέρει σήμανση CE, είναι σύμμορφο με τις οδηγίες της Ε.Ε.:
2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Lieber t is a registered t rademark of Lieber t Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-17310_REV6_09-14
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
Emerson Network Power
Liebert www.emerson.com
www.EmersonNetworkPower.com
Loading...