This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert DCP. Read this manual thoroughly before attempting to install or
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the
unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death.
Open all local and remote electric power supply disconnect switches, verify with a voltmeter
that power is off and wear protective equipment per NFPA 70E before working within electric
control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM
mode. Some internal components require and receive power even during the Unit Off mode of
Liebert iCOM.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
®
microprocessor does not isolate power from the unit, even in the Unit Off
Important Safety Instructions
WARNING
Risk of unit falling over. Can cause property damage, injury or death.
The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit.Verify that all equipment used for lifting and moving is rated for the weight of the unit.
See Table 5 for unit weights.
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
NOTE
This document is intended to be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Inform the facility manager before beginning any action that could cause a disturbance in the
Liebert DCW
action is taken and the work is finished.
™
system’s cooling function. In addition, inform the facility manager after the
®
1Liebert
DCP
™
NOTICE
R
Redundant
Pumps
DCP200B*
Revision
level
Liebert
Data Center
Pumping Unit
Nominal
Capacity
Example: DCP200RA– –*
A
A = 460V-3ph-60Hz
(voltage-phase-frequency)
C = 208V-3ph-60Hz
M = 380/415V-3ph-50Hz
2
2 = 12°F (°C)
Heat
Exchanger
B = Bottom
Piping for
Secondary
Loop
B
B = Bottom
Chilled
Water
Connection
Risk of leaking chilled water and drain lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe
property damage and loss of critical data center equipment. Do not locate unit directly above
any equipment that could sustain water damage. Emerson Network Power
installing monitored leak detection equipment for the unit and its factory- and field-installed
supply, return and drain lines.
Figure 1Model number nomenclature
Important Safety Instructions
®
recommends
Liebert® DCP
™
2
1.0PRODUCT DESCRIPTION
Liebert DCP
Control
Valve
Liebert DCD
Liebert XDK-W
Heat Exchanger
Pump(s)
Chilled
Water
1.1General Product Information
1.1.1Product/System Description
The Liebert DCP chilled water distribution unit is an interface between the building chilled water
system and the cooling modules in the Liebert DCW
chilled water to the cooling modules that are in the room with heat-producing equipment. The Liebert
DCP is rated for 200kW (682,000BTU/H) of cooling.
The Liebert DCP consists of a cabinet that includes a heat exchanger, circulating pump(s), control
valve, receiver, controls, valves and piping.
The Liebert DCP monitors room conditions and prevents coil condensation by maintaining the chilled
water being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling water temperature, etc., are
automatic.
Figure 2Liebert DCP components
Product Description
™
system. It is designed to circulate and control
1.2Equipment Inspection
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be
immediately reported to the carrier and a damage claim filed with a copy sent to Emerson
your sales representative.
®
and to
®
3Liebert
DCP
™
1.3Equipment Handling
!
!
WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified
rating organization. See Table 5 for unit weights. Personnel should be properly trained and
certified to move and rig equipment
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
1.3.1Handling the Liebert DCP While it is on Skid and Packaged
• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In
either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6"
(152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care
must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift
point of the unit.
Product Description
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) and may be too wide to fit
through a standard doorway. Any attempt to move the unit, while skidded, through a
standard doorway will cause damage to the unit and to the building.
Measure the unit and doorway, and verify that the unit will fit through before attempting to
move it through the doorway.
NOTICE
Risk of improper forklift operation. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the top boards of the skid
and/or the bottom of the unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert DCP upright, indoors and protected from dampness, freezing temperatures
and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that
the straps are not tightened to a point of damaging panels.
Liebert® DCP
™
4
1.3.2Unpacking the Liebert DCP
Remove Stretch WrapRemove Packaging Planks
Stretch
Wrap
1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and
side packaging planks.
2. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The
bag may remain in place for dust and panel protection or removed for immediate unit installation.
3. Remove the bag from the unit when ready to remove the skid for installation.
Figure 3Unpacking the Liebert DCP
Product Description
1.3.3Removing the Unit from the Skid Using a Forklift
1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be
equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without
damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
5Liebert
®
DCP
™
Figure 4Use a forklift to remove the Liebert DCP from the skid
Fit the forklift tines under the Liebert DCP.
Move the forklift forward
until the tines are fully
under the unit.
The forklift tines
must be equally
spaced on either
side of the center of
gravity indicator.
1.3.4Removing the Unit from the Skid using Rigging
1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally
spaced on either side of the center of gravity indicator. Refer to
2. Place slings under the unit using spaces provided between the skid deck boards.
Product Description
Figure 5.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer
packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two
horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the
unit.
7. Remove the skid from under the unit.
Liebert® DCP
™
6
Figure 5Removing the unit from the skid using rigging
Equally
Spaced
Equally
Spaced
Center of
Gravity
Symbols
Spreader
Bars
Lag
Bolts
Bracket
If rigging will be used
to transport the
Liebert DCP, place one
or two horizontal
straps around the unit
and the vertical straps
about this height.
Cushioning material
not shown for clarity.
Product Description
1.3.5Moving the Liebert DCP Using Piano Jacks
1. Elevate the Liebert DCP with a lifting mechanism, such as a forklift or rigging.
2. Position one piano jack at each end of the Liebert DCP.
3. Lower the unit to a height suitable for placing it on the piano jacks.
4. Put protective material between the Liebert DCP and the piano jacks and straps.
5. Secure the Liebert DCP to the piano jacks.
6. Release the Liebert DCP from the straps securing it to the lifting mechanism and move the
mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
®
7Liebert
DCP
™
Figure 6Securing the Liebert DCP to piano jacks
Using a forklift to put a
Liebert DCP on piano jacks
Using rigging to put a
Liebert DCP on piano jacks
Liebert DCP Secured
to piano jacks
Product Description
1.3.6Removing the Unit from the Piano Jacks
1. Lower the Liebert DCP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert DCP off one piano jack with a pry bar or similar device, taking care not
to damage the unit’s cabinet.
4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert DCP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
The shaded area indicates
a recommended clearance
of 36" (914mm) for
component access.
36"
(914mm)
36"
(914mm)
2.1Mechanical Considerations
2.1.1Positioning the Liebert DCP
Install the Liebert DCP according to the site specific documentation and secure the unit to the floor.
The Liebert DCP can be installed near a wall or another Liebert DCP. However, there must be at
least 3
Figure 7Dimensions
feet (92cm) clearance in front of the Liebert DCP as service access for components in the unit.
Installation
9Liebert
®
DCP
™
Figure 8Piping access points
!
!
Floor Piping
16-5/8"
(422mm)
2-1/2"
(64mm)
Secondary In
7-1/4" (184mm)
33"
(838mm)
Each piping outlet connection - A, B, C and D - is 2-5/8".
Rear
BCW OUT
(86mm)
Secondary Out
A
C
BCW IN
36" (914mm)
Front
3-3/8"
B
D
Installation
3-1/4"
(83mm)
6-1/2"
(165mm)
DPN002400
Pg. 3, Rev. 1
2.2Electrical Considerations
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated
on the Liebert DCP’s rating plate. The unit must be installed in accordance with national wiring
regulations.
Connect cables for high voltage supply to the electrical box in the Liebert DCP according to Figure 11
and make sure that the phases are correctly connected.
WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power supply disconnect switches and verify with a
voltmeter that power is Off before working within the unit’s electrical connection enclosures.
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment
damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp
edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Liebert® DCP
Check and retighten all wiring connections before starting the unit.
™
10
2.2.1Connecting High-Voltage Cables
Liebert DCP Input
Power Knockout
Enclosure Cover Not Shown
1. Turn the Liebert DCP’s disconnect switch to the Off position (see Figure 9). Open the front doors
and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 9Front view of Liebert DCP and electrical enclosure
Installation
Disconnect
Switch
Front of Liebert DCP
Hazardous
Voltage
Enclosure Cover
2. Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 10).
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
Liebert iCOM
User Interface
Enclosure Cover
Latch
Hazardous Voltage
Enclosure Cover
11Liebert® DCP
™
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see
Customer Power
Connection
Ground Lug
Disconnect Switch
Fuse Blocks
Power Block
Pump Fuse
Blocks
Pump Contactors
Transformer 1
Transformer 2
(supplied on 460V
units only)
Transformer 6
Busbar
Customer Power
Connection
Pump Circuit
Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Transformer 6
Fuse Blocks
Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper
phasing.
4. Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of
the enclosure.
Figure 11 High voltage connections—60Hz
Installation
Figure 12 High voltage connections—50Hz
Liebert® DCP
™
12
2.2.2Extra Low Voltage (ELV) Connections
Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this
equipment (refer to
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage
Figure 13).
User Interface Wiring
Temperature/Humidity
Sensor Wiring
Installation
Alternate Knockout
for Temperature/Humidity
Sensor Wiring
Enclosure Cover Not Shown
13Liebert® DCP
™
Figure 14 Connecting the remote temperature/humidity sensors
Installation
CAN
Cable
See
Note 4
P64
See Note 4
Unit Display
(Rear View)
Red Crossover
Ethernet Cable
Crossover Coupler
See Note 6
P66
CAN Ground
Coupler
P67
Termination
Plug
See Note 8
P2P4
CAN Iso
Adaptor
P3P1
See
Note 9
T6 Isolation
Transformer
T1 Unit Control
Transformer
P66
Liebert XD
Cooling Module
See Note 8
P66
P67
See Note 5
P67
CAN Ground
Coupler
Remote T/H Sensor BRemote T/H Sensor A
See Note 7
24VAC Nominal
P66
P67
P66P67
Liebert XD
Cooling Module
See Note 5
See Note 3
E5
Liebert IntelliSlot 1
Liebert IntelliSlot 2
Ribbon
Cables
Not
Used
Cable B
Cable A
P63
See
Note 2
P1
P2
P65
P3
Liebert IntelliSlot
Power Supply
1. See unit electrical schematic, installation and user manuals.
2. Cable “A” provided with each unit. Liebert IntelliSlot-based
communications - Cable “A” is preconnected to P65
on the microprocessor and input/output board and P65 on the
Liebert IntelliSlot power supply non-Liebert IntelliSlot-based
communications.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect the ground coupling on the end of the
cable connected to Sensor “A” or Sensor “B.”
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug
the red cable from P64 on the microprocessor and input/output board
and connect it to one side of the crossover coupler. The first customer
P13
P11
P7
P67
P64
P61
P65
P18
P12
1
2
3
P66
P78
SW2
OFF ON
21436
P68
5
P43
P4
E1 E2 E3 E4
TB1
P54
P51
E1
P24
Control
Fuse
Board
P45
P4
Liebert iCOM Microprocessor
P41
and I/O Board
P52
P53
P39
See Table for
P40
P8
P32
Plug Assignments
P34
P33
P36
P35
P22 P38
302211
Rev. 3
connection point is to P64 on the microprocessor and input/output board.
The second customer connection point is to the other side of the crossover
coupler. This connects the microprocessor and input/output board and
display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the Liebert
XD cooling module and which connects to P2 on CAN Iso.
8. Field-install cables with factory-installed ferrite beads (when provided,
typically two places). Each cable must make three passes through the
ferrite bead. Locate the ferrite bead on top of the electric box. See
the instruction sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). The cable passes through
the ferrite bead three times.
Liebert® DCP
™
14
2.2.3DIP Switch and Jumper Settings for Remote Sensors
P68
135
246
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A”REMOTE T/H SENSOR “B”
SW1SW1
OFF
ON
OFF
ON
Jumper
on 1-2
1
2
3
P78
DIP
Switches
ON
1
3
4
9
10
OFF
2
5
6
7
8
Jumpers
on 1-2, 5-6
OFF ON
1
2
3
4
5
6
7
8
9
10
DIP
Switches
ON
None
OFF
1
2
3
4
5
6
7
8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
DIP
Switches
ON
1
5
OFF
2
3
4
6
7
8
DIP
Switc hes
ON
2
5
OFF
1
3
4
6
7
8
SW3
1
2
3
4
5
6
7
8
OFF ON
P3
321
Jumper
on 2-3
P3
321
Jumper
on 2-3
302211
Rev. 3
302211
Rev. 3
Termination
Plug
Liebert iCOM
Microprocessor
& I/O Board
Customer
Connection
Points
Crossover
Coupler
Red Crossover
Ethernet Cable
Straight Through
Ethernet Cables
U2U Networking Switch
(Field-Supplied)
Unit Display
(Rear View)
Not
Used
P64
P66
P64
P66P67
To / From Other
Networked Units
CAN Cable
See Note 1
P65
E5
P61
P63
P11 P13
P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U)
networking. Unplug the red cable from P64 on the
microprocessor and I/O board and connect it to one side
of the crossover coupler. The first customer connection
point is to P64 on the microprocessor and I/O board.
The second customer connection point is to the other
side of the crossover coupler. This connects the
microprocessor and I/O board and display to the
private U2U network.
The Liebert DCP is shipped with jumpers and DIP switch settings for normal operation; refer to
Figure 15.
Figure 15 DIP switch and jumper settings
Installation
Figure 16 Unit-to-unit networking connections
15Liebert® DCP
™
2.3Field Connections—Optional for All Units
1
1
2
K11COM
K11NO
K11NCL
TS-24
TS-50
TS-51
TS-54
K3COM
K3NO
K3NCL
TS-37
TS-38
TS-77
TS-78
K11COM
K11NO
K11NC
K11
K11
2450
5424
5124
3837
K3COM
K3NO
K3NC
K3
K3
BK
78
77
(-)
R or W
(+)
DPN002400
Pg. 5, Rev. 1
Control wiring must be Class 2 and installed in
accordance with the National Electrical Code (NEC).
Requires shielded cable.
2
1
COMMON WARNING OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM
CIRCUIT BY OTHERS
INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.
N.O. CONTACT BY OTHERS
INPUT: CONDENSATION
DETECTION
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: FAN BREAKER STATUS
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: REMOTE SHUTDOWN
FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
AND REPLACE WITH N.C. CONTACT.
N.C. CONTACTS BY OTHERS
LIEBERT SITE MONITOR
FOR DIGITAL COMMUNICATION
WITH LIEBERT SITE MONITORS
ONLY. CONNECT 2 WIRE TWISTED
PAIR TO 77 & 78. ALSO SEE SITE
MONITOR INSTALLATION MANUAL.
COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM
CIRCUIT BY OTHERS
Factory-Wired
Temperature Sensor
UNIT DISPLAY
(Rear View)
P64
P66 P67
To Remote
T/H Sensor A
To Optional
External
Connections
To Remote
T/H Sensor B
To P64 on Liebert iCOM
Control Board
Red Ethernet Cable
Termination Plug
To P66 on Liebert iCOM
Control Board
DO
NOT
USE
P67
Connect optional field wiring from remote devices to remote alarm device, common alarm outputs,
site monitor and remote shutdown, if applicable. See terminal strip descriptions in
Figure 17 Liebert DCP extra low voltage field connections points
Installation
Figure 17.
Liebert® DCP
™
16
2.4Remote Sensor Installation—Proper Placement
Placement of the two remote temperature/humidity sensors is critical to effective cooling of the
conditioned space.
Installation
The remote sensors must be installed in areas where conditions are representative of the space
conditioned by the Liebert DCP. Emerson
the cooling modules served by the Liebert DCP. If the return air side of the primary air mover, such
as a Liebert DS
™
, represents the conditions where the cooling modules are located, one sensor could
be placed there. Emerson suggests placing the other sensor on the wall opposite the heat load area
(see
Figure 18 for guidance).
Do not install the sensors where ambient air might cause false readings, for example, near unsealed
doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable;
each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM® input/output board inside
the Liebert DCP. Secure the ring terminal on the cable shield to the electric box adjacent to P67
(see
Figure 14).
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the
ring terminal on the cable shield to the grounding screw adjacent to P67.
Figure 18 Suggested remote sensor placement
®
recommends installing the sensors in different areas near
17Liebert® DCP
™
3.0PIPING
Liebert DCPCooling Modules
To Building
Chilled Water
3.1Connection Sizes
The copper pipe connections on the Liebert DCP are:
Building Chilled Water Supply2-5/8" OD
Chilled Water Return2-5/8" OD
Coolant Supply2-5/8" OD
Coolant Return2-5/8" OD
Fill Water Source5/8" OD
3.1.1Recommended Pipe Size
Connect the main pipes between the Liebert DCP and the Liebert DCD™/Liebert XDK-W™ according
to site-specific documentation and the configuration guide for the Liebert DCD/Liebert XDK-W unit.
Elbows and restrictions should be minimized to get good fluid flow.
Table 1Supply and return requirements for Liebert DCD/Liebert XDK-W loop
Maximum Total
Nominal Pipe Size
inches (mm)
2.5 (64)75 (23)Type L Copper
3 (76)150 (46)Copper or Schedule 40 Steel
3.5 (89)300 (91)Copper or Schedule 40 Steel
Equivalent Length
Piping
ft. (m)Piping Material
3.2Air Bleeders
Install air bleeders at each high point in the piping circuits.
3.3Liebert DCP Interconnection with Cooling Modules
All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe.
The Liebert DCP may be connected to Liebert DCD or Liebert XDK-W cooling modules with either
prefabricated piping assembly or rigid, off-the-shelf piping. The cooling modules are connected in
parallel between main return and supply pipes going to and from the Liebert DCP.
represents a typical configuration.
Figure 19 Liebert DCW system diagram
Figure 19
Liebert® DCP
™
18
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.