This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert DCP. Read this manual thoroughly before attempting to install or
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the
unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death.
Open all local and remote electric power supply disconnect switches, verify with a voltmeter
that power is off and wear protective equipment per NFPA 70E before working within electric
control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM
mode. Some internal components require and receive power even during the Unit Off mode of
Liebert iCOM.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
®
microprocessor does not isolate power from the unit, even in the Unit Off
Important Safety Instructions
WARNING
Risk of unit falling over. Can cause property damage, injury or death.
The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit.Verify that all equipment used for lifting and moving is rated for the weight of the unit.
See Table 5 for unit weights.
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
NOTE
This document is intended to be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Inform the facility manager before beginning any action that could cause a disturbance in the
Liebert DCW
action is taken and the work is finished.
™
system’s cooling function. In addition, inform the facility manager after the
®
1Liebert
DCP
™
NOTICE
R
Redundant
Pumps
DCP200B*
Revision
level
Liebert
Data Center
Pumping Unit
Nominal
Capacity
Example: DCP200RA– –*
A
A = 460V-3ph-60Hz
(voltage-phase-frequency)
C = 208V-3ph-60Hz
M = 380/415V-3ph-50Hz
2
2 = 12°F (°C)
Heat
Exchanger
B = Bottom
Piping for
Secondary
Loop
B
B = Bottom
Chilled
Water
Connection
Risk of leaking chilled water and drain lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe
property damage and loss of critical data center equipment. Do not locate unit directly above
any equipment that could sustain water damage. Emerson Network Power
installing monitored leak detection equipment for the unit and its factory- and field-installed
supply, return and drain lines.
Figure 1Model number nomenclature
Important Safety Instructions
®
recommends
Liebert® DCP
™
2
1.0PRODUCT DESCRIPTION
Liebert DCP
Control
Valve
Liebert DCD
Liebert XDK-W
Heat Exchanger
Pump(s)
Chilled
Water
1.1General Product Information
1.1.1Product/System Description
The Liebert DCP chilled water distribution unit is an interface between the building chilled water
system and the cooling modules in the Liebert DCW
chilled water to the cooling modules that are in the room with heat-producing equipment. The Liebert
DCP is rated for 200kW (682,000BTU/H) of cooling.
The Liebert DCP consists of a cabinet that includes a heat exchanger, circulating pump(s), control
valve, receiver, controls, valves and piping.
The Liebert DCP monitors room conditions and prevents coil condensation by maintaining the chilled
water being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling water temperature, etc., are
automatic.
Figure 2Liebert DCP components
Product Description
™
system. It is designed to circulate and control
1.2Equipment Inspection
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be
immediately reported to the carrier and a damage claim filed with a copy sent to Emerson
your sales representative.
®
and to
®
3Liebert
DCP
™
1.3Equipment Handling
!
!
WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert DCP is top-heavy. Use extreme caution and care when moving and installing this
unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified
rating organization. See Table 5 for unit weights. Personnel should be properly trained and
certified to move and rig equipment
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for
installation.
1.3.1Handling the Liebert DCP While it is on Skid and Packaged
• Always keep the unit upright, indoors and protected from damage.
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In
either case, do NOT press on the top edges of the packaging.
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance
to still fit under the skid.
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6"
(152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care
must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift
point of the unit.
Product Description
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) and may be too wide to fit
through a standard doorway. Any attempt to move the unit, while skidded, through a
standard doorway will cause damage to the unit and to the building.
Measure the unit and doorway, and verify that the unit will fit through before attempting to
move it through the doorway.
NOTICE
Risk of improper forklift operation. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the top boards of the skid
and/or the bottom of the unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert DCP upright, indoors and protected from dampness, freezing temperatures
and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that
the straps are not tightened to a point of damaging panels.
Liebert® DCP
™
4
1.3.2Unpacking the Liebert DCP
Remove Stretch WrapRemove Packaging Planks
Stretch
Wrap
1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and
side packaging planks.
2. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The
bag may remain in place for dust and panel protection or removed for immediate unit installation.
3. Remove the bag from the unit when ready to remove the skid for installation.
Figure 3Unpacking the Liebert DCP
Product Description
1.3.3Removing the Unit from the Skid Using a Forklift
1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be
equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without
damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
5Liebert
®
DCP
™
Figure 4Use a forklift to remove the Liebert DCP from the skid
Fit the forklift tines under the Liebert DCP.
Move the forklift forward
until the tines are fully
under the unit.
The forklift tines
must be equally
spaced on either
side of the center of
gravity indicator.
1.3.4Removing the Unit from the Skid using Rigging
1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally
spaced on either side of the center of gravity indicator. Refer to
2. Place slings under the unit using spaces provided between the skid deck boards.
Product Description
Figure 5.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer
packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two
horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the
unit.
7. Remove the skid from under the unit.
Liebert® DCP
™
6
Figure 5Removing the unit from the skid using rigging
Equally
Spaced
Equally
Spaced
Center of
Gravity
Symbols
Spreader
Bars
Lag
Bolts
Bracket
If rigging will be used
to transport the
Liebert DCP, place one
or two horizontal
straps around the unit
and the vertical straps
about this height.
Cushioning material
not shown for clarity.
Product Description
1.3.5Moving the Liebert DCP Using Piano Jacks
1. Elevate the Liebert DCP with a lifting mechanism, such as a forklift or rigging.
2. Position one piano jack at each end of the Liebert DCP.
3. Lower the unit to a height suitable for placing it on the piano jacks.
4. Put protective material between the Liebert DCP and the piano jacks and straps.
5. Secure the Liebert DCP to the piano jacks.
6. Release the Liebert DCP from the straps securing it to the lifting mechanism and move the
mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
®
7Liebert
DCP
™
Figure 6Securing the Liebert DCP to piano jacks
Using a forklift to put a
Liebert DCP on piano jacks
Using rigging to put a
Liebert DCP on piano jacks
Liebert DCP Secured
to piano jacks
Product Description
1.3.6Removing the Unit from the Piano Jacks
1. Lower the Liebert DCP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert DCP off one piano jack with a pry bar or similar device, taking care not
to damage the unit’s cabinet.
4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert DCP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
The shaded area indicates
a recommended clearance
of 36" (914mm) for
component access.
36"
(914mm)
36"
(914mm)
2.1Mechanical Considerations
2.1.1Positioning the Liebert DCP
Install the Liebert DCP according to the site specific documentation and secure the unit to the floor.
The Liebert DCP can be installed near a wall or another Liebert DCP. However, there must be at
least 3
Figure 7Dimensions
feet (92cm) clearance in front of the Liebert DCP as service access for components in the unit.
Installation
9Liebert
®
DCP
™
Figure 8Piping access points
!
!
Floor Piping
16-5/8"
(422mm)
2-1/2"
(64mm)
Secondary In
7-1/4" (184mm)
33"
(838mm)
Each piping outlet connection - A, B, C and D - is 2-5/8".
Rear
BCW OUT
(86mm)
Secondary Out
A
C
BCW IN
36" (914mm)
Front
3-3/8"
B
D
Installation
3-1/4"
(83mm)
6-1/2"
(165mm)
DPN002400
Pg. 3, Rev. 1
2.2Electrical Considerations
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated
on the Liebert DCP’s rating plate. The unit must be installed in accordance with national wiring
regulations.
Connect cables for high voltage supply to the electrical box in the Liebert DCP according to Figure 11
and make sure that the phases are correctly connected.
WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power supply disconnect switches and verify with a
voltmeter that power is Off before working within the unit’s electrical connection enclosures.
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment
damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp
edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Liebert® DCP
Check and retighten all wiring connections before starting the unit.
™
10
2.2.1Connecting High-Voltage Cables
Liebert DCP Input
Power Knockout
Enclosure Cover Not Shown
1. Turn the Liebert DCP’s disconnect switch to the Off position (see Figure 9). Open the front doors
and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 9Front view of Liebert DCP and electrical enclosure
Installation
Disconnect
Switch
Front of Liebert DCP
Hazardous
Voltage
Enclosure Cover
2. Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 10).
Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
Liebert iCOM
User Interface
Enclosure Cover
Latch
Hazardous Voltage
Enclosure Cover
11Liebert® DCP
™
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see
Customer Power
Connection
Ground Lug
Disconnect Switch
Fuse Blocks
Power Block
Pump Fuse
Blocks
Pump Contactors
Transformer 1
Transformer 2
(supplied on 460V
units only)
Transformer 6
Busbar
Customer Power
Connection
Pump Circuit
Breakers
Pump Contactors
Ground Lug
Disconnect Switch
Transformer 1
Power Block
Transformer 2
Transformer 6
Fuse Blocks
Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper
phasing.
4. Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of
the enclosure.
Figure 11 High voltage connections—60Hz
Installation
Figure 12 High voltage connections—50Hz
Liebert® DCP
™
12
2.2.2Extra Low Voltage (ELV) Connections
Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this
equipment (refer to
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 13 Electrical enclosure knockout locations for Extra Low Voltage
Figure 13).
User Interface Wiring
Temperature/Humidity
Sensor Wiring
Installation
Alternate Knockout
for Temperature/Humidity
Sensor Wiring
Enclosure Cover Not Shown
13Liebert® DCP
™
Figure 14 Connecting the remote temperature/humidity sensors
Installation
CAN
Cable
See
Note 4
P64
See Note 4
Unit Display
(Rear View)
Red Crossover
Ethernet Cable
Crossover Coupler
See Note 6
P66
CAN Ground
Coupler
P67
Termination
Plug
See Note 8
P2P4
CAN Iso
Adaptor
P3P1
See
Note 9
T6 Isolation
Transformer
T1 Unit Control
Transformer
P66
Liebert XD
Cooling Module
See Note 8
P66
P67
See Note 5
P67
CAN Ground
Coupler
Remote T/H Sensor BRemote T/H Sensor A
See Note 7
24VAC Nominal
P66
P67
P66P67
Liebert XD
Cooling Module
See Note 5
See Note 3
E5
Liebert IntelliSlot 1
Liebert IntelliSlot 2
Ribbon
Cables
Not
Used
Cable B
Cable A
P63
See
Note 2
P1
P2
P65
P3
Liebert IntelliSlot
Power Supply
1. See unit electrical schematic, installation and user manuals.
2. Cable “A” provided with each unit. Liebert IntelliSlot-based
communications - Cable “A” is preconnected to P65
on the microprocessor and input/output board and P65 on the
Liebert IntelliSlot power supply non-Liebert IntelliSlot-based
communications.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect the ground coupling on the end of the
cable connected to Sensor “A” or Sensor “B.”
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug
the red cable from P64 on the microprocessor and input/output board
and connect it to one side of the crossover coupler. The first customer
P13
P11
P7
P67
P64
P61
P65
P18
P12
1
2
3
P66
P78
SW2
OFF ON
21436
P68
5
P43
P4
E1 E2 E3 E4
TB1
P54
P51
E1
P24
Control
Fuse
Board
P45
P4
Liebert iCOM Microprocessor
P41
and I/O Board
P52
P53
P39
See Table for
P40
P8
P32
Plug Assignments
P34
P33
P36
P35
P22 P38
302211
Rev. 3
connection point is to P64 on the microprocessor and input/output board.
The second customer connection point is to the other side of the crossover
coupler. This connects the microprocessor and input/output board and
display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the Liebert
XD cooling module and which connects to P2 on CAN Iso.
8. Field-install cables with factory-installed ferrite beads (when provided,
typically two places). Each cable must make three passes through the
ferrite bead. Locate the ferrite bead on top of the electric box. See
the instruction sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). The cable passes through
the ferrite bead three times.
Liebert® DCP
™
14
2.2.3DIP Switch and Jumper Settings for Remote Sensors
P68
135
246
SW2
MICROPROCESSOR AND I/O BOARD
REMOTE T/HSENSOR “A”REMOTE T/H SENSOR “B”
SW1SW1
OFF
ON
OFF
ON
Jumper
on 1-2
1
2
3
P78
DIP
Switches
ON
1
3
4
9
10
OFF
2
5
6
7
8
Jumpers
on 1-2, 5-6
OFF ON
1
2
3
4
5
6
7
8
9
10
DIP
Switches
ON
None
OFF
1
2
3
4
5
6
7
8
1
2
3
P78
UNIT DISPLAY
Jumper on 1-2
1 2 3 4 5 6 7 81 2 3 4 5 6 7 8
DIP
Switches
ON
1
5
OFF
2
3
4
6
7
8
DIP
Switc hes
ON
2
5
OFF
1
3
4
6
7
8
SW3
1
2
3
4
5
6
7
8
OFF ON
P3
321
Jumper
on 2-3
P3
321
Jumper
on 2-3
302211
Rev. 3
302211
Rev. 3
Termination
Plug
Liebert iCOM
Microprocessor
& I/O Board
Customer
Connection
Points
Crossover
Coupler
Red Crossover
Ethernet Cable
Straight Through
Ethernet Cables
U2U Networking Switch
(Field-Supplied)
Unit Display
(Rear View)
Not
Used
P64
P66
P64
P66P67
To / From Other
Networked Units
CAN Cable
See Note 1
P65
E5
P61
P63
P11 P13
P7
P12
P67
1. Both cables (P64 and P66) are required.
2. A crossover coupler is provided for unit-to-unit (U2U)
networking. Unplug the red cable from P64 on the
microprocessor and I/O board and connect it to one side
of the crossover coupler. The first customer connection
point is to P64 on the microprocessor and I/O board.
The second customer connection point is to the other
side of the crossover coupler. This connects the
microprocessor and I/O board and display to the
private U2U network.
The Liebert DCP is shipped with jumpers and DIP switch settings for normal operation; refer to
Figure 15.
Figure 15 DIP switch and jumper settings
Installation
Figure 16 Unit-to-unit networking connections
15Liebert® DCP
™
2.3Field Connections—Optional for All Units
1
1
2
K11COM
K11NO
K11NCL
TS-24
TS-50
TS-51
TS-54
K3COM
K3NO
K3NCL
TS-37
TS-38
TS-77
TS-78
K11COM
K11NO
K11NC
K11
K11
2450
5424
5124
3837
K3COM
K3NO
K3NC
K3
K3
BK
78
77
(-)
R or W
(+)
DPN002400
Pg. 5, Rev. 1
Control wiring must be Class 2 and installed in
accordance with the National Electrical Code (NEC).
Requires shielded cable.
2
1
COMMON WARNING OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM
CIRCUIT BY OTHERS
INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.
N.O. CONTACT BY OTHERS
INPUT: CONDENSATION
DETECTION
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: FAN BREAKER STATUS
ALARM WHEN CLOSED.
N.O. CONTACTS REQUIRED
INPUT: REMOTE SHUTDOWN
FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
AND REPLACE WITH N.C. CONTACT.
N.C. CONTACTS BY OTHERS
LIEBERT SITE MONITOR
FOR DIGITAL COMMUNICATION
WITH LIEBERT SITE MONITORS
ONLY. CONNECT 2 WIRE TWISTED
PAIR TO 77 & 78. ALSO SEE SITE
MONITOR INSTALLATION MANUAL.
COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
TO REMOTE ALARM
CIRCUIT BY OTHERS
Factory-Wired
Temperature Sensor
UNIT DISPLAY
(Rear View)
P64
P66 P67
To Remote
T/H Sensor A
To Optional
External
Connections
To Remote
T/H Sensor B
To P64 on Liebert iCOM
Control Board
Red Ethernet Cable
Termination Plug
To P66 on Liebert iCOM
Control Board
DO
NOT
USE
P67
Connect optional field wiring from remote devices to remote alarm device, common alarm outputs,
site monitor and remote shutdown, if applicable. See terminal strip descriptions in
Figure 17 Liebert DCP extra low voltage field connections points
Installation
Figure 17.
Liebert® DCP
™
16
2.4Remote Sensor Installation—Proper Placement
Placement of the two remote temperature/humidity sensors is critical to effective cooling of the
conditioned space.
Installation
The remote sensors must be installed in areas where conditions are representative of the space
conditioned by the Liebert DCP. Emerson
the cooling modules served by the Liebert DCP. If the return air side of the primary air mover, such
as a Liebert DS
™
, represents the conditions where the cooling modules are located, one sensor could
be placed there. Emerson suggests placing the other sensor on the wall opposite the heat load area
(see
Figure 18 for guidance).
Do not install the sensors where ambient air might cause false readings, for example, near unsealed
doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable;
each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM® input/output board inside
the Liebert DCP. Secure the ring terminal on the cable shield to the electric box adjacent to P67
(see
Figure 14).
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the
ring terminal on the cable shield to the grounding screw adjacent to P67.
Figure 18 Suggested remote sensor placement
®
recommends installing the sensors in different areas near
17Liebert® DCP
™
3.0PIPING
Liebert DCPCooling Modules
To Building
Chilled Water
3.1Connection Sizes
The copper pipe connections on the Liebert DCP are:
Building Chilled Water Supply2-5/8" OD
Chilled Water Return2-5/8" OD
Coolant Supply2-5/8" OD
Coolant Return2-5/8" OD
Fill Water Source5/8" OD
3.1.1Recommended Pipe Size
Connect the main pipes between the Liebert DCP and the Liebert DCD™/Liebert XDK-W™ according
to site-specific documentation and the configuration guide for the Liebert DCD/Liebert XDK-W unit.
Elbows and restrictions should be minimized to get good fluid flow.
Table 1Supply and return requirements for Liebert DCD/Liebert XDK-W loop
Maximum Total
Nominal Pipe Size
inches (mm)
2.5 (64)75 (23)Type L Copper
3 (76)150 (46)Copper or Schedule 40 Steel
3.5 (89)300 (91)Copper or Schedule 40 Steel
Equivalent Length
Piping
ft. (m)Piping Material
3.2Air Bleeders
Install air bleeders at each high point in the piping circuits.
3.3Liebert DCP Interconnection with Cooling Modules
All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe.
The Liebert DCP may be connected to Liebert DCD or Liebert XDK-W cooling modules with either
prefabricated piping assembly or rigid, off-the-shelf piping. The cooling modules are connected in
parallel between main return and supply pipes going to and from the Liebert DCP.
represents a typical configuration.
Figure 19 Liebert DCW system diagram
Figure 19
Liebert® DCP
™
18
3.4Piping Installation Methods
The assembly and connection means used for piping in the Liebert DCW™ system are similar to those
used for conventional refrigeration systems. All piping should be installed with high-temperature
brazed joints. Soft soldering is not recommended.
During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and
scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping
supports, leak testing, dehydration and charging. Failure to use good system practices may result in
damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice
refrigeration piping.
Insulate all piping lines to prevent condensation in applications where the dew point approaches the
chilled water temperature.
3.4.1Piping Mains
Install a 20-40 mesh strainer on the chilled water supply to the Liebert DCP. The strainer is needed
to prevent particles in the chilled water from entering the Liebert DCP’s heat exchanger.
3.5Bypass Flow Controllers
The Liebert DCP pumping unit is designed to provide a total of 114GPM (25.9 m3/h) of cooling water
to the cooling modules. The pump operates at its highest efficiency between 90 and 120GPM
(20.4m
this range. Emerson
regulator of similar flow capacity as bypass valves. Bypass lines also prevent excessive flow through
the cooling modules when only a few modules are installed in addition to maintaining high flow rate
through pump.
3
/h and 27.3m3/h). Permanent bypass flow controllers must be installed to ensure flow within
®
recommends using four 22.67 GPM (5.15m3/h) constant flow regulators or other
Piping
Refer to individual cooling module specifications to estimate the maximum combined allowable flow
for all the units connected to the Liebert DCP. If the allowable combined flow rate is less than 90GPM
(20.4 m
90GPM (20.4m
3
/h), then as many bypass controllers as necessary must be opened to maintain a flow above
3
/h) through the Liebert DCP.
For example, the maximum allowable water flow rate for a Liebert DCD™ unit is 22.7GPM (5.2 m3/h).
At least four of these units must be connected to the Liebert DCP in parallel to achieve a total flow of
over 90GPM (20.4m
3
/h).
22.7GPM x 4 Liebert DCD’s = 90.8GPM total flow
5.2m3/h * x Liebert DCD’s = 20.8m3/h total flow
If fewer units are connected to the Liebert DCP, then bypass lines must be opened to maintain the
total flow through the Liebert DCP within the range of 90 to 120GPM (20.4 to 27.3 m
For example, if three Liebert DCD modules are connected to a Liebert DCP, the total flow of 68.1GPM
(15.47 m
3
/h) would be insufficient. A bypass flow controller of 22.67GPM (5.15 m3/h) must be added to
3
/h).
increase the flow rate to at least 90GPM (20.4m3/h)
Emerson recommends
installing shutoff valves
as shown to permit isolating
the Liebert DCP for maintenance.
Isolation valves must be installed on the Liebert DCP’s secondary chilled water circuit to permit
maintenance on the unit (see
Figure 20 General piping details
Figure 20).
Piping
3.6.1Insulation
NOTE
Do not insulate piping before checking it for leaks. Insulating pipes before checking them for
leaks would prevent easy detection of leaks.
Insulate all piping between the Liebert DCP and its connected cooling modules to prevent
condensation where the piping passes through non-conditioned areas.
3.7Filling Instructions
This section provides detailed instructions on how to properly fill the Liebert DCP.
3.7.1Check for Proper Installation of Components and Workmanship
1. Confirm that the flow directions of field-installed components are correct.
2. Confirm that all isolating valves are open (keep the hose bib valve closed when filling).
3. Confirm that all auto air vents are closed (tighten caps if applicable).
4. Test the water quality when filling the system. Refer to the values in Table 2 for minimum
corrosion and erosion.
Table 2Water quality to limit corrosion and erosion
Maximum Conductivity500µS/cm
Minimum PH7.0
Maximum Suspended Matter30 mg/L; no visible particles
Taste and SmellNormal
3.7.2Conduct Air Pressure Test
Liebert® DCP
1. Turn Off power to the unit.
2. Set the pressure at 150 psig (1034kPa; 10.3 bars) maximum for at least 30 minutes or according to
local codes.
3. Repair any leaks if necessary.
™
20
3.7.3Water Fill Line Connection
NOTE
Check with local codes for proper connection to potable water and EPA
conformance.
Do NOT use the hose bib at the bottom of the unit to fill the system (see
Figures 22 and 21).
1. When filling the system, use only water that can be classified and used as drinking water.
a. Open all vents (loosen caps if applicable) to allow air to escape during filling.
b. Remove the Schrader pin in the valve at the top of the standpipe (see Figure 21) to obtain
0 psig pressure.
c.Open Valves #1 and #2 to allow the system to fill (see Figure 22).
d. When the water has reached the FILL level in the bottom sight glass of the standpipe,
immediately close Valve
e.Replace the Schrader pin in the valve at the top of the standpipe.
2. Bleed air thoroughly (keep Valve #1 closed to isolate the standpipe from the system).
a. Depress pins at all vents.
b. Manually depress pins at all Schrader vents on each rack (see Figure 23).
c.Manually vent at pump housing plugs (see Figure 22).
d. Continue to vent until the system is full, then close Valve #2.
3. Open Valve #1 to reconnect the system to the standpipe (fluid level should rise above the fill, but
below the NORMAL level on the sight glass).
a. If the fluid level is above the NORMAL level, release water by opening the hose bib until the
level reaches the NORMAL level on the sight glass.
b. If the fluid level is below the NORMAL level on the sight glass, open Valve #2 until the level
reaches the NORMAL level.
4. Turn the system on (pumps will be in operation) and continue to vent air for 24 hours to remove
as much air as possible.
If Steps 1 through 3 are followed properly, the air pressure in the top of the standpipe should be
14 PSIG (±2PSIG).
Piping
#1 (see Figure 22) to isolate the standpipe from the system.
NOTE
Add water as necessary to maintain a normal level reading.
5. When the system is mostly air-free, close all air vents (tighten caps securely); this includes vents
at each rack (
Figure 23) and auto air vents on the main headers.
6. Conduct a Fluid Pressure Test.
a. Pressure test the system with water at city pressure for six hours or according to local codes.
b. Check for leaks.
7. Add a water corrosion inhibitor.
• The use of a closed system treatment (CST) is strongly recommended. CST is available from
Terlyn Industries at 800-200-4112 or
www.terlyn.com.
• Additional treatment might be required after six to 12 months of operation, depending on the
quality of your water.
Note: Many parameters contribute to water corrosion and erosion, and the requirements stated
above do not guarantee 100% corrosion and erosion prevention. However, when these parameters
are met and a corrosion inhibitor is used, the possibility of corrosion and erosion in the closed loop
water system should be minimized, therefore maximizing the life expectancy of the system.
8. Refill the system by following Steps 1 through 5, then go to Step 9.
9. Turn the unit On by pressing the I/O key.
21Liebert® DCP
™
Figure 21 Standpipe filling components
Piping
Standpipe
Vent
Ports
Sight Glass
(Normal
Level)
Sight Glass
(Fill Level)
Valve #2
Hose
Bib
FRONT OF LIEBERT DCP
Liebert® DCP
™
22
Figure 22 Liebert DCP filling components
Bleed
Valve
Liebert
DCD
Rack
One pump
removed
for clarity
Piping
Vent Port
Vent Port
Sight Glass
(Normal Level)
Standpipe
Valve #2
Valve #1
Figure 23 Liebert DCD™ bleed valve
Sight Glass
(Fill Level)
Hose Bib
FRONT OF LIEBERT DCP
23Liebert® DCP
™
Figure 24 Liebert XDK-W™ bleed valve
Bleed
Valve
3.8Checklist for Proper Installation
___ 1. Unpack and check received material.
___ 2. Position the Liebert DCP and secure to the floor.
___ 3. Wire high-voltage connections.
___ 4. Wire low-voltage connections.
___ 5. Connect building chilled water piping to the Liebert DCP.
___ 6. Connect Liebert DCD™/Liebert XDK-W piping to the Liebert DCP.
___ 7. Make sure air vents are installed at high-point of the system.
___ 8. Make sure isolation valves are installed on the mains and branch piping.
___ 9. Pressure test air.
___ 10. Fill the system with water.
___ 11. Bleed air out of the system.
___ 12. Pressure test fluid.
___ 13. Check for water leaks.
Piping
Liebert® DCP
™
24
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Liquid Crystal
Display screen
Keypad
LED Status Indicators
(top LED is red or flashing
red; bottom LED is green
or amber)
ESC
?
On/Off Key
Escape KeyDown Arrow Key
Up Arrow Key
Left Arrow KeyRight Arrow KeyEnter Key
Alarm Key
Help Key
LEDs
(see Table 3 for
meanings)
4.0LIEBERTICOM® CONTROL—FIRMWARE VERSION XP1.00.DCP.01R
4.1Liebert iCOM Components and Functions
The Liebert iCOM controller layout is shown in Figure 25; the keyboard functions are defined in
Table 3.
Figure 25 Liebert iCOM display components
25Liebert® DCP
™
Table 3Keyboard icons and functions
?
ESC
Icon
Key NameFunction
On/Off KeyControls the operational state of the cooling unit.
Alarm KeySilences an alarm.
Help KeyAccesses integrated Help menus.
ESCape KeyReturns to the previous display view.
Enter KeyConfirms all selections and selects icons or text.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Increase Key
(Up Arrow)
Decrease Key
(Down Arrow)
Left and Right
Arrow Keys
Upper LED
Lower LED
Moves upward in a menu or increases the value of a selected parameter.
Moves downward in a menu or reduces the value of a selected parameter.
Navigates through text and sections of the display.
Blinking Red—Active, unacknowledged alarm exists
Solid Red—Active, acknowledged alarm exists
Amber—Power is available to the unit; unit is NOT operating
Green—Unit is operating with no alarms
4.2Display Lamp Indicators
• The Green lamp will be On only when the Liebert DCP is On and running with no alarms.
• The Red lamp will be On if the unit is On and running with an active alarm, or if the unit is shut
down because of an alarm.
• The Red lamp will flash while an alarm is being annunciated. The Red lamp will stop flashing and
the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
• The Amber lamp will be On if the Liebert DCP has been shut down at the I/O switch or if the unit
has been shut down by an alarm condition.
Liebert® DCP
™
26
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
press : for next /prev uni t for unit /system view
press: for menu; ESC for prev screen ; ? for help
08/2011
Liebert
DCP
57°F
50.0°F set
CFC: 30%
28.02.2014 15:03UNIT ON
Sensor A
Room Data
Date and
Time
Pump Operation
represented by animated
piping
Next Scheduled
Maintenance
Alarm/Event
History
Navigation
Prompts
Unit
Name
Sensor B
Room Data
Unit Status
Coolant
Tem per atu re
Available only
with Liebert XD
Smart Modules
4.3Navigating Through the Liebert iCOM® Display
Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The
Liebert iCOM’s home screen is shown in
Figure 26 Liebert iCOM default home screen
Figure 26.
4.3.1Accessing Menus and Settings
Viewing Data
No password is required to view data or settings.
To view data:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view.
4. Once that icon is highlighted, press Enter again to open that menu.
• If a password is required, see 4.3.3 - Entering the Password.
• If a menu has more than one screen, the Liebert iCOM display will have text at the top similar to this: (page 1 of 2).
5. Press Enter to select the first line of data.
6. Use the Up and Down arrow keys to scroll to the desired data point.
7. Press ESC to move back to higher level menus.
27Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
UNIT 1
OFF9/2015100 %
212°F
Max XD Supply
Air Temp
Liebert XDP
AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01 AA01AA01
(01) 9/12/2014 08:33 RST General Alarm
(01) 9/12/2014 08:20 ACK HIGH CHILLED WATER TEMP
8/4/2012 14:13:54ALARM OFF
? for help
for next/previous unit
for system view
ESC
for previous screen
for menu
°F 70 72 74 76 75 73 74 71 77 72
4.3.2Cooling Module Overview—Applies Only to Liebert XDP
The Liebert iCOM® will display an overview of all connected cooling modules. It does not display a
system view, which would include units other than the cooling modules.
NOTE
The Liebert iCOM control screens display a setting to select a system view, but the Liebert DCP
does not support a system view.
To display an overview of all connected cooling modules:
1. At the default home screen on the Liebert iCOM, press the Down arrow. This will display the first
10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.
Figure 27 Cooling module overview, first 10 modules—Applies only to Liebert XDP
™
2. Press the down arrow button again to display the next 10 modules’ outlet temperature and
capacity levels.
3. Press ESC to return to the default home screen.
Liebert® DCP
™
28
4.3.3Entering the Password
SETPOINTS
to change parameter
to confirm
to select parameter
for next/pr evious unit
then
PASSWORD (Actual Level 0)
Min Room Temperature Setpoint
After highlighting the Password command line, press
Enter again to highlight the first digit. Use the Up and
Down arrow keys to change the first digit. Move to the
next digit in the Password with the right arrow.
Most settings in the Liebert iCOM® are protected by a factory-set password, 1490. To enter the
password:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press Enter to highlight the Password line.
6. With the Password line highlighted, press Enter to highlight the first digit in the password
7. Enter the password, 1490.
Use the Up and Down arrow keys to select a numeral for the first digit of the password.
Move to the next digit of the password with the Right arrow key.
Select the numerals for all four digits with the same process.
8. After all four digits of the password have been entered, press the Enter key.
NOTE
Do not press the ESC key or the Liebert iCOM will move to the previous screen and the
password must be re-entered before changes may be made.
Figure 28 Entering the password
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
29Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit
then
Language
Date
Time
Temperature Indication
Display Contrast
Buzzer Frequency
Backlite Off after
Screen
Highlight the
setting to be
changed by
pressing Enter.
4.4Changing Liebert iCOM®’s Display Settings
No password is required to change the way Liebert iCOM displays data. The Display Setup controls
how the unit shows data, such as temperature, date and time.
To change the display settings:
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the Display Setup icon.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press the Enter key to select the first setting.
Either change that setting or navigate to another setting with the Up and Down arrow keys.
6. Once the desired setting is highlighted, press the Enter key to access that parameter’s display
setting options.
7. Use the Up and Down arrow keys to make changes.
8. Press the Enter key to accept the changes.
9. Press the ESC key twice to return to Liebert iCOM’s user menu.
Figure 29 Display setup screen
4.5Changing Operational Settings
Liebert® DCP
Changes to the Liebert DCP’s operation settings in the Set Alarms and Setpoints menus require a
password.
1. From the home screen, press the Enter key to view the User Menu (see Figure 30).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
If a password is required, see 4.3.3 - Entering the Password.
5. After entering the password, use the Up and Down arrow keys to scroll to and highlight the
operational setting to be changed.
6. Press Enter to highlight the values for that setting.
7. Use the Up and Down arrow keys to change the value.
8. Press Enter to accept the change. (The value will no longer be highlighted.)
9. Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)
10. Press ESC again to move to previous screens.
™
30
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
°C / °F
% RH
SET
EVENT
LOG
SET
ALARMS
!
ACTIVE
ALARMS
1 2
39
6
SET
1234h
XDIO
4.6Graphical Data Record
The Graphical Data Record charts the average temperature from Sensors A and B and the supply
coolant temperature.
The temperature scales can be changed to expand or compress the data.
The time scale also can be altered to any of several selectable values.
NOTE
Changing the time scale eliminates all previous graphical data and the unit will begin
recording new data.
4.7Liebert iCOM® User Menu Icons and Legend
Figure 30 Liebert iCOM User Menu icons
Setpoints
View and change
operational
setpoints
Sensor Data
Shows readings
of sensors; View
Only
Spare Parts List
Contains spare
parts available on
site
Active Alarms
Lists all current
alarms; View Only
Event Log
Lists last 400
events and
alarms
View Only
Display Setup
Change settings
for display:
language and
time
Graphic Data Record
Displays average
temperature from
Sensors A and B, the
average dew point from
Sensors A and B, the
supply coolant
temperature and the
supply coolant control
point graphs; Data is
View Only; Display scale
is adjustable
Total Run Hours
Records the run time of
all components and
allows setting of limits on
run time; View Only
View Network
Shows status of
all connected
units; View Only
Smart Modules
Displays
readings for the
individual smart
modules; View
Only; applies only
to Liebert XDP
™
Set Alarms
Allows user to
change settings for
alarms
Service Contacts
Contains key
contact information
for service
NOTE
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
31Liebert® DCP
™
Figure 31 Liebert DCP User Menu screen
EVENT
LOG
°C / °F
% RH
SET
SET
12
39
6
SET
ALARMS
!
ACTIVE
ALARMS
1234
h
USER MENUS
ESC
to unselect
to change level
to open requested menu
to navigate
XDIO
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Liebert® DCP
™
32
4.8Liebert iCOM® User Menu Screens
SETPOINTS
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0)
Min Room Temperature Setpoint
User menus report general cooling unit operations and status. User menu screens employ a coding
that begins with “U” and is followed by parameters and information, such as settings. Gaining access
to some User menu screens requires entering a password; the User Menu password is 1490.
Check www.liebert.com for the latest Liebert iCOM user manual updates, SL-18835.
Figure 32 Setpoints screen
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to
maintain. If the temperature falls below this point, the unit will raise the coolant temperature to
reduce the amount of cooling.
The setting is intended to keep the room temperature above the setpoint. Without a proper setpoint,
the Liebert DCP can lower the room temperature too much, depending on the room dew point and
load. This setpoint will reduce the cooling to keep the room temperature above this desired
temperature.
NOTE
This is not a true room temperature setpoint. The Liebert DCP has no heaters; it will try to cool
as much as possible. If the Liebert DCP is able to cool the room to this setpoint, it will reduce its
cooling action to try to keep the room temperature at or above this setpoint.
The default setting is 60°F (15.6°C). The range is 50-80°F (10-27°C).
For optimal cooling performance, the minimum temperature setpoint should be 1-2° below the
expected temperature at the remote sensors, which may affect placement of the remote sensors. If the
minimum temperature setpoint is set above the typical remote temperature sensor reading, it will
reduce the Liebert DCP cooling output and, in extreme cases, cause erratic Liebert DCP performance.
Spare Parts
Spare Parts—The spare parts lists contains a detailed description and part number that can be used
to order parts for the unit. These part numbers are specific to each model and option installed on the
unit.
Event Log
Event Log—The event log displays all events and actions that have been generated by the unit.
When multiple units are networked the screen will display the event log of the whole system. Each
event shows the unit that generated the alarm, time and date stamp, a description and the event
type.
33Liebert® DCP
™
Figure 33 Set Alarms screen
SET ALARMS (page 1 of 1)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
PASSWORD (Actual Level 0)
High Room Air Temperature
Low Room Air Temperature
High Room Dewpoint
High Coolant Temperature
High Room Air Temperature—Sets the threshold where a high room temperature alarm will
occur, based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur,
based on the actual reading from either remote Sensor A or B. The range for the high room air
temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on
the calculated values from either remote Sensor A or remote Sensor B. The range for the high room
dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Coolant Temperature—Sets the threshold where a high coolant temperature alarm will
occur based on the actual reading from the supply coolant sensor. The supply coolant temperature is
from the Liebert DCP to the modules. The range for the high supply coolant temperature alarm is
from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply fluid temperature alarm is from
33.8
to 95°F (1 to 35°C); the default is 60°F (15.6°C).
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Sensor A Temperature62.8°F
Sensor A Humidity42.20%
Sensor A Dew Point39.4°F
Sensor B Temperature71.2°F
Sensor B Humidity29.60°%
Sensor B Dew Point37.8°F
Supply Coolant Temperature55.0°F
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor A.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor B.
Supply Coolant Temperature—Displays the actual supply coolant temperature from the Liebert
DCP to the modules.
Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature
to the Liebert DCP.
Daily High Temperature07:49:5772°F
Daily Low Temperature07:11:3064°F
Daily High Humidity11:31:4645%
Daily Low Humidity07:56:1834%
Daily High Dew Point07:47:2645°F
Daily Low Dew Point08:02:2037°F
Daily High Coolant Temp13:01:2569°F
Daily Low Coolant Temp13:01:1169°F
Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A
or remote Sensor B.
Daily High Dew Point—Shows the highest dew point in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Dew Point—Shows the lowest dew point in a 24 hour period for either remote Sensor A
or remote Sensor B.
Daily High Coolant Temperature—Shows the highest supply coolant temperature in a rolling 24
hour period from the Liebert DCP to the modules.
Daily Low Coolant Temperature—Shows the lowest supply coolant temperature in a rolling 24
hour period from the Liebert DCP to the modules.
Daily High Chilled Water Temperature—Shows the highest chilled water supply temperature
being delivered to the Liebert DCP in a rolling 24 hour period.
Daily Low Chilled Water Temperature—Shows the lowest chilled water return temperature
being delivered to the Liebert DCP in a rolling 24 hour period.
Liebert® DCP
™
36
Figure 36 Display Setup screen
DISPLAY SETUP
to change parameter
to confirm
to select parameter
for next/previous unit
then
Language
Date
Time
Temperature Indication
Display Contrast
Buzzer Frequency
Backlite Off after
Screen
Language—Sets the language on the display. Changing this setting changes all menu parameters to
the selected language.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Date—Sets the internal date of the unit. If this unit is connected to other units with the unit-to-unit
network connection, each unit will reflect the last date set.
Time—Sets the internal time of the unit. If this unit is connected to other units with the unit-to-unit
network connection each unit will reflect the last time set.
Temperature Indication—Selects the actual and setpoint temperature scale. Selecting C will set
the unit to display in Celsius and F will set the unit to display in Fahrenheit.
Display Contrast—Changes the contrast of the display to adjust for different viewing angles, low
light and bright light conditions. As the display ages, the contrast may require adjustment for
viewing.
Buzzer Frequency—Changes the audible noise frequency of the built-in buzzer. The buzzer will
sound when its frequency is being adjusted, easing selection of a frequency easily detected when an
alarm occurs.
Backlite Off After—Controls how long the back-light remains active when the display is unused.
When the buttons on the front display have not been pressed for the time selected in this parameter,
the back-light will turn Off, extending the life of the display and saving energy.
Screen—Controls the screen layout. The Liebert DCP has one view, Unit View.
Display Colors—Selects the background color. Inverted sets the display to show white font with
blue background and Normal sets a white background with blue font.
Date Format—Date format changes the month, day and year arrangement shown on the front
display and on event time stamps.
37Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Model / CapacityXDV8SK8KW
Left Fan StatusON
Right Fan StatusON
ONLINE
65°F
NODE 81 AZ81
57°F
92°F
66°F
XDV
Figure 37 Module Status screen, page 1 of 20—Applies to Liebert XD™ smart modules only
Module Node ID—The location within the CANbus. Each module’s ID is factory-set to 80 and is
automatically changed during setup; requires no user action.
Module Labels—A four-character label consisting of two letters and two numerals. This is the standard
nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be
denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or
both labels can be used and are entered using the Module Setup found in the Service menu (S910).
Module Status—Indicates whether the smart module is connected to the CANbus.
Figure 38 Liebert XDV™ Smart Module Status screen—Applies to Liebert XD smart modules only
U905—Displays the temperature of the air entering the Liebert XDV™.
U908—Displays the temperature of the air leaving the right and left fan of the Liebert XDV.
U911—Displays the module type and calculated local module capacity; possible module types are
XDV8SK, XDV8SS, XDV8ST, XDV10SK, XDV10SS and XDV10ST.
U912—Displays the left fan status; possible values are ON and OFF.
U913—Displays the right fan status; possible values are ON, OFF and ON ECON. ON ECON
indicates that only one fan is On.
Liebert® DCP
™
38
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
The parameter shows the actual hours Pump 1 and Pump 2 have operated and the maximum time
Pump 1 can operate before the next maintenance.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
4.9Liebert iCOM® Service Menu Icons and Legend
Figure 42 Liebert iCOM Service Menu icons
Setpoints
View and change
operational
setpoints
Sensor
Calibration/Setup
Setup and calibrate
sensors for site
Liebert® DCP
Unit Diary
Shows all program
changes and
maintenance
performed,
Maintenance/
Wellness
Settings
Shows all
maintenance
records, calculates
next maintenance
date
Diagnostics/
Service Mode
Enter Diagnostics/
Service Mode for
troubleshooting
and repair
Set Alarms
Change settings for
alarms
™
Network
Setup or alter
network setting.
Options Setup
Enter specific
settings for various
options
40
Smart Module
Setup of alarms
and events. Set
temperature limits
for supply and
return sensors.
Label smart
modules, view
firmware version;
applies only to
Liebert XDP
™
Service Contacts
Contains key
contact information
for service
NOTE
SERVICE MENUS
to select parameter
to change level
to open requested menu
ESC
to unselect
to navigate
+
WELLNESS
SET
ALARMS
SERVIC E
+/-
NETWORK
SET
UP
XDIO
°C / °F
% RH
SET
SETPOINTS
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
Min R oom Temperature Setpoint
Temperature Control Type
Temperature Proportional Band
Temperature Integration Tiime
Temperature Derivative
Dewpoint Margin
Minimum Control Point
Min Percent Cooling Setpoint
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
Figure 43 Liebert DCP Service Menu screen
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
4.10Liebert iCOM® Service Menu Screens
Service menus allow customized settings for site operations. Service Menu screens employ a coding
that begins with “S” and is followed by parameters and information, such as settings. Gaining access
to most Service Menus requires entering a password; the Service Menu password is 5010; see
Entering the Password for assistance.
The Liebert iCOM firmware is being updated constantly. As a result, the Service Menu parameters in
this manual may be slightly different from what is shown on a cooling unit’s display. Check
www.liebert.com for the latest Liebert iCOM user manual updates.
Figure 44 Setpoints screen
4.3.3 -
41Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to
maintain. If the temperature falls below this point, unit will raise the coolant temperature to reduce
the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting is 60°F
(15.6°C).
NOTE
This is not a true room temperature setpoint. The Liebert DCP has no heaters; it will try to cool
as much as possible. If the Liebert DCP is able to cool the room to this setpoint, it will reduce its
cooling action to try to keep the room temperature at or above this setpoint.
Temperature Control Type—Selects the type of control the system will use to activate cooling. The
Liebert iCOM
®
control has three temperature control types: Proportional, PI and Intelligent. The
factory default is Intelligent.
Proportional—If Proportional Control is selected, the percent cooling requirement is
determined by the difference between the air temperature sensor reading and the temperature
setpoint. As the air temperature rises above the temperature setpoint, the percent cooling
required increases proportionally (from 0 to 100%) over half the programmable temperature
proportional band. The percent heating requirement (0 to 100%) is determined the same way
when the air temperature falls below the setpoint.
PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two
individual terms, proportional and integral. The proportional term is calculated in a manner
similar to the previously described Proportional control. The integral term (sometimes called
reset action) is calculated by measuring how much and for how long the air temperature has been
above or below the setpoint. If the actual air temperature is above the setpoint, the percent
requirement is slowly but continuously increased until the total is sufficient to bring the return
room air back to the setpoint.
Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the
setpoint. The percent temperature adjustment required is calculated based on logic that is
programmed into the control. These rules simulate the actions that would be taken by a human
operator manually controlling the system.
Temperature Proportional Band—Adjusts the activation points of compressors or rate of change
based on the actual sensor values deviation from setpoint. The smaller this number the faster the
compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short
cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8 to
54.0°F (1.0 to 30.0°C). The factory default setting is 7.0°F (3.9°C).
Temperature Integration Time—Temperature integration takes into consideration the amount of
time the actual temperature has deviated from the setpoint. The larger this deviation is the longer
the unit will wait before corrective action is taken to achieve the setpoint. This parameter is
adjustable from 0 to 15 minutes. The factory default is 0.
Temperature Derivative Time—Monitors the rate of change and will reduce or increase the
amount of corrective action based on the actual temperature increasing or decreasing toward the
temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.
Dewpoint Margin—Selects the difference between the room dew point and the coolant temperature
control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory default is
4.0°F (2.2°C).
Minimum Control Point—Sets the minimum supply coolant temperature the Liebert DCP will
maintain. This parameter is adjustable from 40 to 113°F (4.4 to 45.0°C). The factory default is 55°F
(12.8°C).
Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal
operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go
below this value. The parameter is adjustable from 0 to 30%. The factory default is 15%.
Liebert® DCP
™
42
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Basic Settings (page 1 of 7)
SYSTEM
PASSWORD (Actual Level 0)????
Maintenance Frequency Per Year1
Max Bonus0
Max Penalty0
Last Maintenance08/25/2014
Service EngineerNOBODY
Confirm PMNo
Calculated Next Maintenance08/2014
PASSW ORD (Actual Level 0)????
Number of Starts31
Run Hours453hrs
Average Run Time876min
Starts per Day Best1
Starts per Day Worst24
Number of Alarms1
Actual Bonus0
Figure 45 Maintenance—Basic Settings screen, page 1 of 7
Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year
time span.
Max Bonus—Increases the time until the next required maintenance. Service personnel should
assign a bonus when a service visit finds all components working optimally.
Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign
a penalty when a service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the
date of the last visit.
Service Engineer—Provides a label for the service representative to list either the company name
or representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance
and resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the
last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty
or bonus set in the Liebert iCOM
Figure 46 Maintenance—Pump 1 Settings screen, page 2 of 7
®
control.
43Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
PASSW ORD (Actual Level 0)????
Number of Starts2
Run Hours0hrs
Average Run Time0min
Starts per Day Best1
Starts per Day Worst24
Number of Alarms1
Actual Bonus0
Number of Starts—Shows the number of starts for the unit’s Pump 1.
Run Hours—Shows the number of run hours for the unit’s Pump 1.
Average Run Time—Shows the average run time of the unit’s Pump 1.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1.
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will
always take the value from the worst component for the next maintenance indication.
Figure 47 Maintenance—Pump 2 Settings screen, page 3 of 7
Number of Starts—Shows the number of starts for the unit’s Pump 2.
Run Hours—Shows the number of run hours for the unit’s Pump 2.
Average Run Time—Shows the average run time of the unit’s Pump 2.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2.
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will
always take the value from the worst component for the next maintenance indication.
Figure 50 Diagnostics/Service Mode screen, page 2 of 6
Manual Mode—Used to place the Liebert iCOM® in manual mode. This is the initial setting
necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each
service menu item shows the current status of each parameter.
Pump 1—Starts the unit’s Pump 1.
Pump 2—Starts the unit’s Pump 2.
3P Start Active/Complete—Displays if the startup routine is active, and if it is completed.
3P Actuator Input Request—Shows the percent call for cooling.
3P Actuator Position—Sets the position of the actuator 0-100% in manual mode.
3P Actuator Open—Opens the 3P actuator when set to ON in manual mode.
3P Actuator Close—Closes the 3P actuator when set to ON in manual mode
Valve Feedback—Opens the valve percent in manual mode.
Figure 51 Diagnostics/Service Mode screen, page 3 of 6
Liebert® DCP
Page 3 applies to the Liebert XDC™ only. No Liebert DCP parameters are present.
™
46
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Manual Mode Control TypeFull
Manual Deviation12%
Analog Output R amp 130%
Analog Output R amp 20%
Analog Output R amp 360%
Analog Output R amp 458%
Alarm RelayOff
Warning RelayOff
PASSWORD (Actual Level 0)????
High Room Air Temperature88.0°F
Low Room Air Temperature55.0°F
High Room Dewpoint65.0°F
High Coolant Temperature80.0°F
High Chilled Water Temperature60.0°F
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The
range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range
for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the
high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Coolant Temperature—Sets the threshold for a high a coolant temperature alarm. The range
for the high supply coolant temperature alarm is from 33.8 to 122°F (1 to 50°C); the default is 80°F
(26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply fluid temperature alarm is from
33.8
to 113°F (1 to 45°C); the default is 60°F (15.6°C).
Customer Input 1—Selects the device and operation of the customer input. Each event reflects a
different alarm and possible action to the unit. Selectable options are:
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Call Service
C-Input
Water
Smoke
Customer Input 1 active when—Selects whether the Customer Input 1 input is normally closed or
normally open.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning
occurs.
Reset Disabled Alarms—Resets disabled events.
The Set Alarm Screens (Figure 57 through 61) permit setting the operation of an active alarm. Each
event can be enabled or disabled and can be set to operate as an alarm, warning or message. The
delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Liebert® DCP
™
50
Figure 57 Set Alarms screen, page 3 of 7
SET ALARMS (page 3 of 7)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
HIGH TEMP SENSOR A
LOW TEMP SENSOR A
HIGH TEMP SENSOR B
LOW TEMP SENSOR B
HIGH DEWPOINT
SENSOR A FAILURE
SENSOR B FAILURE
HIGH CHILLED WATER TEMP
SUPPLY CW SENSOR FAILURE
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
HIGH TEMP SENSOR A—Enables or disables the High Temperature Sensor A event, which occurs
when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR A—Enables or disables the Low Temperature Sensor A event, which occurs when
the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH TEMP SENSOR B—Enables or disables the High Temperature Sensor B event, which occurs
when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is
reported as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR B—Enables or disables the Low Temperature Sensor B event, which occurs
when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
HIGH DEWPOINT—Enables or disables the High Dewpoint event, which occurs when the
calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
SENSOR A FAILURE—Enables or disables the Sensor A Failure event, which occurs when the
control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
SENSOR B FAILURE—Enables or disables the Sensor B Failure event, which occurs when the
control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
HIGH CHILLED WATER TEMP—Enables or disables the High Chilled Water Temp event, which
occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint.
Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control
waits before reporting the event.
SUPPLY CW SENSOR FAILURE—Enables or disables the Supply CW Sensor Failure event,
which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the event
is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
51Liebert® DCP
™
Figure 58 Set Alarms screen, page 4 of 7
SET ALARMS (page 4 of 7)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
HIGH COOLANT TEMP
LOW COOLANT TEMP
SUPPLY COOLANT SENSOR
LOSS OF FLOW PUMP 1
LOSS OF FLOW PUMP 2
PUMP SHORT CYCLE
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
HIGH COOLANT TEMP—Enables or disables the High Coolant Temp event, which occurs when
the reading from supply coolant temperature sensor is above the user-specified alarm setpoint. Sets
how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits
before reporting the event.
LOW COOLANT TEMP—Enables or disables the Low Coolant Temp event, which occurs when the
reading from supply coolant temperature sensor is below the user-specified alarm setpoint. Sets how
the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
SUPPLY COOLANT SENSOR—Enables or disables the Supply Coolant Sensor event, which occurs
when the control no longer senses a signal from the Supply Coolant Sensor. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when
Pump 1 is commanded to run and the flow switch does not sense flow. Sets how the event is reported:
as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when
Pump 2 is commanded to run and the flow switch does not sense flow. Sets how the event is reported:
as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow
is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs
when the chilled water control valve has been commanded by the control to open or close and no
change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning
or a message. Specifies how long the control waits before reporting the event.
CONDENSATION DETECTED
FAN FAILURE
CUSTOMER INPUT 1
SMOKE DETECTED
WATER UNDER FLOOR
UNIT X DISCONNECTED
WORKING HRS EXCEEDED
CALL SERVICE
LOSS OF POWER
Pages 5 and 6 apply to the Liebert XDC™ only. No Liebert DCP parameters are present.
Figure 60 Set Alarms screen, page 7 of 7
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
CONDENSATION DETECTED—Enables or disables the Condensation Detected event, which
occurs when water is detected at a cooling module. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event (not currently
used).
FAN FAILURE—Enables or disables the Fan Failure event, which occurs when a fan failure occurs
at a cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies
how long the control waits before reporting the event (not currently used).
CUSTOMER INPUT 1—Enables or disables the Customer Input 1 event, which occurs when 24VAC
is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies
how long the control waits before reporting the event.
SMOKE DETECTED—Enables or disables the Smoke Detected event, which occurs when the
Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
53Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
WATER UNDER FLOOR—Enables or disables the Water Under Floor event, which occurs when
the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets
how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits
before reporting the event.
UNIT X DISCONNECTED—Not currently used.
WORKING HOURS EXCEEDED—Enables or disables the Working Hrs Exceeded event, which
occurs when a component has exceeded the user-specified limit. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
CALL SERVICE—Enables or disables the Call Service event, which occurs when the Customer
Input 1 is configured for “Call Service” and 24VAC is applied to the input. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOSS OF POWER—Enables or disables the Loss of Power event, which occurs when the unit is On
and operational and the 24VAC power to the control is lost. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Liebert® DCP
™
54
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SENSOR CALIBRATION/SETUP (page 1 of 3)UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
Temperature Sensor A
Calibrated Temperature Sensor A
Humidity Sensor A
Calibrated Humidity Sensor A
Temperature Sensor B
Calibrated Temperature Sensor B
Humidity Sensor B
Calibrated Humidity Sensor B
Figure 61 Sensor Calibration/Setup screen, page 1 of 3
Temperature Sensor A—Adjusts the temperature reading from the actual remote CAN Temp
Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other
sensors in the room.
Calibrated Temperature Sensor A—Displays the adjusted temperature value of the remote CAN
Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus
the offset Temperature Sensor A.
Humidity Sensor A—Adjusts the humidity reading from the actual remote CAN Temp Humidity
sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in
the room.
Calibrated Humidity Sensor A—Displays the adjusted humidity value of the remote CAN Temp
Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the
offset Humidity Sensor A.
Temperature Sensor B—Adjusts the temperature reading from the actual remote CAN Temp
Humidity sensor designated as Sensor B to compensate for any error of the sensor or to match other
sensors in the room.
Calibrated Temperature Sensor B—Displays the adjusted temperature value of the remote CAN
Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus
the offset Temperature Sensor B.
Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as
Sensor B to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp
Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the
offset Humidity Sensor B.
55Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Figure 62 Sensor Calibration/Setup screen, page 2 of 3
Supply Coolant Sensor—Adjusts the temperature reading from the actual supply coolant sensor to
compensate for any error of the sensor.
Calibrated Supply Coolant Sensor—Displays the adjusted temperature value of the supply
coolant sensor. This value is the actual sensor reading plus or minus the offset Supply Coolant
Sensor.
Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled
water sensor to compensate for any error of the sensor.
Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled
water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water
Sensor.
Figure 63 Sensor Calibration/Setup screen, page 3 of 3
Liebert® DCP
Supply Coolant Sensor 0%—Allows the sensor reading to be calibrated at the lowest reading of the
sensor. This calibration changes the start point of the sensor reading.
Supply Coolant Sensor 100%—Allows the sensor reading to be calibrated at the highest reading of
the sensor. This calibration changes the end point of the sensor reading.
™
56
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SYSTEM/NETWORK SETUP (page 1 of 2)SYSTEM
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
Number of Connected Units
Figure 64 System/Network Setup screen—System, page 1 of 2
Number of Connected Units—Shows the number of displays connected. This is always 1.
Configuration Safe—Saves or loads configuration settings for the display that have been modified
from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert
®
iCOM
Load will write the settings from the internal storage file to the application software. The internal file
is updated automatically every 12 hours.
Network Safe—Saves or loads network settings for the display that have been modified from the
factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service
Tool. Selecting Save will write the settings to the internal storage file and selecting Load will write
the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM display.
Figure 65 System/Network Setup screen—System, page 2 of 2
IP Address—Contains the network address of the display. This address must be unique on the
network. The factory default is 192.168.254.003.
Service Tool. Selecting Save will write the settings to the internal storage file and selecting
57Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A network point that acts as an entrance to another network. The factory default is
0.000.000.000.
MAC—A unique hardware identifier for the Ethernet device. The following parameters (U2U
Protocol, U2U Address and U2U Group) are for displaying other networked Liebert
Liebert DCP does not perform Teamwork Operations.
U2U Protocol—This is always set to GBP.
U2U Address—A unique identifier for each display on the network. Display addresses range from 33
to 64. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Used to create zones or groups within a U2U network. Once a group number is
selected, the display will see only other devices with the same group number. The group number can
be changed to view other devices in different groups. Not currently used.
Bootloader Variables—Indicates the bootloader has changed since it was last loaded. This
parameter should only be activated by an authorized service person.
Figure 66 System/Network Setup screen—Unit, page 1 of 2
DCP units. The
Monitoring Address—Sets the address used by the Liebert IntelliSlot® cards. This is set to 3 at the
factory and should not be changed.
Unit Name—Identifies the unit from the local or remote display. This label will show at the top right
of every screen that has monitoring or configuration of that unit
Liebert® DCP
Configuration Safe—Saves or loads configuration settings for the control board that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM
selecting “Load” will write the settings from the internal storage file to the application software. The
internal file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the control board that have been modified from
the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM
Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load”
will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM.
™
®
Service Tool. Selecting “Save” will write the settings to the internal storage file and
58
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
SYSTEM/NETWORK SETUP (page 2 of 2)
Attention: any changes done on these parameters
must be followed by a 'Save+Reboot ' command .
PASSW ORD (Actual Level 0)
Monitoring Protocol
IP Address
Netmask
Gateway
MAC
U2U Protocol
U2U Address
U2U Group
Bootloader Variables
Static RAM
Figure 67 System/Network Setup screen—Unit, page 2 of 2
Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default which will
provide communications to the Liebert IntelliSlot
for communication to the Liebert SiteLink(-E)
units.
IP Address—Contains the network address of the display. This address must be unique to every
other device on the network. The factory default is 192.168.254.003.
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A gateway is a network point that acts as an entrance to another network. The factory
default is 0.000.000.000.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other
Liebert DCP units that are networked. The Liebert DCP does not perform Teamwork Operations.
U2U Protocol—Always set to GBP.
U2U Address—Unique identifier for each display on the network. Display addresses range from 1 to
32. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Creates zones or groups within a U2U network. Once a group number is selected the
display will only see other devices with the same group number. The group number can be changed to
view other devices in different groups. Not currently used.
Bootloader Variables—Indicates if there has been a change to the boot loader since it was last
loaded. This parameter should only be activated by authorized service personnel.
Static RAM—Allows service personnel to clear and reboot the RAM of the control board. Only
Emerson
®
service personnel should perform this function.
®
. Liebert Hironet™ is only used on Liebert HPM™
®
housing. IGMnet will activate the 77/78 terminals
59Liebert® DCP
™
Figure 68 Options Setup screen, page 1 of 2
OPTIONS SETUP (page 1 of 2)
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
Autorestart Enabled
Single Unit Auto Restart
Unit Start Sequence D elay
Control Delay Time
Pump Start Time Delay
Pump Wait Time Delay
Pump Off Time Delay
Autorestart Enabled—Restarts the unit after a power cycle when set to Yes. When this parameter
is set to No, the unit will not restart after a power cycle.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Single Unit Auto Restart—Sets a time delay for the unit to restart when the Auto Restart Enabled
is set to Yes. The delay begins once the boot process has completed. This parameter allows units to be
staggered On to reduce the amount of simultaneous power consumption after a loss of power.
Unit Start Sequence Delay—Not currently used.
Control Delay Time—Not currently used.
Pump Start Time Delay—Sets a time delay to ensure that coolant begins flowing when the pump
starts. If coolant does not begin flowing before the user-set delay expires, the pump will be turned Off.
Pump Wait Time Delay—Sets the pump wait time delay to prevent the pump from continuing to
run when coolant is not flowing. If a pump is running normally and coolant flow is lost, the pump will
stay On for the specified time trying to re-establish coolant flow. If coolant flow resumes during the
specified interval, the pump will continue operating. If the wait time expires and coolant flow has not
resumed, the pump will shut down.
Pump Off Time Delay—Sets the length of time a pump will remain off when coolant flow is
interrupted or stops. After the time delay has expired, the control will try to restart the pump.
Lead Pump—Sets which pump is the active pump. It can be set to PUMP 1 or PUMP 2. The control
will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF FLOW
condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time delay
has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.
Pump Short Cycle Delay—Sets the time to lock Off the unit if it is unable to establish coolant flow
within this set amount of time.
Liebert® DCP
™
60
Figure 69 Options Setup screen, page 2 of 2
OPTIONS SETUP (page 2 of 2)
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSW ORD (Actual Level 0)
Valve Start Open
Valve Start TD
3P Actuator Runtime
3P Actuator Direction
Unit Off Valve % Open
PASSW ORD (Actual Level 0)
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
Valve Start Open—Sets position of the valve when the unit starts.
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
Valve Start TD—Sets a time interval for the unit to complete startup and enter into normal
operation.
3P Actuator Runtime—If Valve Control is selected for “Time,” then this parameter sets the travel
time of the valve to determine the full open and closed position of the valve. This parameter is set at
the factory, based on the valve manufacturer’s specifications.
3P Actuator Direction—Sets if the valve is a “Direct” or “Reverse” acting valve.
Unit Off Valve % Open—Sets the valve position when the unit is Off.
Figure 70 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only
61Liebert® DCP
™
Liebert iCOM® Control—Firmware Version XP1.00.DCP.01R
MODULE SETUP (page 1 of 20)UNIT 01
PASSW ORD (Actual Level 0)
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
This screen selects the operation of an active alarm for each smart module. Each event can be enabled
or disabled and can be set to operate as an alarm, a warning or a message. The delay is the time the
control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer/front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Fan Control Type—Sets the fan control mode. Values can be OFF, ON, ON ALL and TEMP CNTL.
Disable Local Button—Disables the push button on the front of the smart module. To disable the
push button, set the parameter to YES. To re-enable the push button, set the parameter to NO.
Flash LED at Module—Flashes the LED on the smart module when set to Yes.
Set Module Label—A four-character label consisting of two letters and two numerals. This is the
standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location
can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list.
Either or both labels can be used and are entered using this screen.
Supply Air Temp Limit—Sets the high and low supply air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Return Air Temp Limit—Sets the high and low return air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Firmware Version—Displays the firmware version installed on the smart module.
Figure 71 Module Setup screen, page 1 of 20—Applies to Liebert XD™ smart modules only
Liebert® DCP
™
62
Start the Liebert DCP with Liebert iCOM
®
5.0STARTTHE LIEBERT DCP WITH LIEBERTICOM
®
5.1Checklist for Liebert DCP Startup
NOTE
Before any action that could cause a disturbance in the Liebert DCP system’s cooling function
is begun, the facility manager MUST be informed. In addition, after the action is taken and the
work is finished, the facility manager MUST be informed
1. Verify that bypass flow controllers were installed (if applicable).
2. Check all isolation ball valves in the Liebert DCP and cooling module and verify that all are open.
3. Check rotation of the Liebert DCP’s pumps.
4. Verify that air is being discharged into the cold aisle.
5. Confirm that the system has been properly filled with water (see 3.7 - Filling Instructions).
6. Confirm that the remote temperature/humidity sensors provided have been installed in optimal
locations (see
The Liebert DCP system is now ready to be turned ON.
5.2Starting the Liebert DCP with Liebert iCOM Controller
The Liebert DCP is started, stopped and controlled through the Liebert iCOM controller. Figure 25
shows the Liebert iCOM keypad.
1. Turn the Liebert DCP On with the user interface (I/O button). Allow the system to attempt to
start for at least 2 minutes.
If the Liebert DCP pump cannot maintain flow and continues to switch over due to starting
difficulties, refer to
2. Check flow switch functionality:
The Liebert DCP system should be On. If it is Off:
a. Turn the Liebert DCP On via user interface (I/O button).
If no “Loss of Flow” alarm is present—This suggests that there is flow. Test the flow
switch by closing the ball valve on either the suction line or discharge line to stop the flow.
This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has
opened on low flow.
If a “Loss of Flow” alarm is present—This suggests that there is no flow. Verify that this
is correctly annunciated by checking for proper water charge (see
However, if there is flow, the flow switch could be faulty. Check the flow switch, making
sure that the electrical connections are properly connected.
Then check the flow switch electrically by making sure that the unit has 24VAC across it.
7.0 - Troubleshooting.
3.7 - Filling Instructions.)
63Liebert® DCP
™
6.0ALARM DESCRIPTIONSAND SOLUTIONS
6.1Alarm Descriptions
NOTE
Alarms must be acknowledged before they can be reset. To acknowledge or silence an alarm,
press the ALARM key one time. This will silence the alarm; the red LED will remain
illuminated until the alarm is reset.
CALL SERVICE—Activated when Customer Input 1 is configured for “Call Service” and 24VAC is
applied to the input. This alarm is reset when the 24VAC is removed.
CONDENSATION DETECTED (optional)—Activated when water is detected at a cooling module.
A 24VAC signal is applied to the condensation input on the control board using a pair of twisted wires
or the alarm is sent via CANbus communication. When this alarm is active, the control will raise its
fluid control point by 4°F (2.2°C). This alarm will reset when the alarms is acknowledged and the
signal stops being sent from CANbus or condensation input. The alarm can also be reset by cycling
the power. The main power must be cycled to remove the 4°F (2.2°C) offset (not currently used).
CONTROL VALVE FAILURE—Activated when the chilled water control valve has been
commanded to open or close by the control and no change is detected by the valve position signal. The
alarm is reset when the main power is cycled.
CUSTOMER INPUT 1—Activated when a 24VAC signal is applied to the customer alarm input on
the control board. This alarm will reset when the 24VAC signal stops being sent from the customer
alarm input. WATER UNDER FLOOR, SMOKE DETECTED, CALL SERVICE, and COMP LOCK
PD are possible designations for this alarm; they are set with the Unit Code.
FAN FAILURE (optional)—Activated when a 24VAC signal is applied to the fan failure input on
the control board using a twisted pair of wires or the alarm is sent via CANbus communication. This
alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or
fan failure input. The alarm can also be reset by cycling the power (not currently used).
HIGH CW TEMP—Activated when the Supply CW sensor reads the chilled water temperature
above the user-specified alarm setpoint. This alarm will reset when the reading from the fluid
temperature sensor drops 5°F (2.8°C) below the user-specified setpoint and the alarm has been
acknowledged.
HIGH DEW POINT—Activates when the calculated dew point at either Sensor A or B exceeds the
user-specified alarm setpoint. The alarm will reset when the calculated room dew point from both
Sensor A and Sensor B is 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.
HIGH COOLANT TEMP—Activated when the coolant temperature sensor reads the coolant
temperature above the user-specified alarm setpoint. This alarm will reset when the reading from the
coolant temperature sensor drops 2°F (1.1°C) below the user-specified setpoint and the alarm has
been acknowledged.
HIGH TEMP SENSOR A—Activated when the reading from Sensor A is above the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the
setpoint and the alarm has been acknowledged.
HIGH TEMP SENSOR B—Activated when the reading from Sensor A is above the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the
setpoint and the alarm has been acknowledged.
LOSS OF FLOW PUMP 1—Activated when Pump 1 is commanded to run and the flow switch does
not sense flow. After attempting to start Pump 1 three times, the Liebert
switch to the other pump to establish flow. This alarm will reset when flow has been established on
Pump 1 and the alarm has been acknowledged.
LOSS OF FLOW PUMP 2—Activated when Pump 2 is commanded to run and the flow switch does
not sense flow. After attempting to start Pump 2 three times, the Liebert DCP will automatically
switch to the other pump to establish flow. This alarm will reset when flow has been established on
Pump 2 and the alarm has been acknowledged.
Alarm Descriptions and Solutions
DCP will automatically
LOW MEMORY—Activated when the control board is low in memory resources. This alarm rests
automatically as soon as memory consumption falls below the threshold.
Liebert® DCP
™
64
Alarm Descriptions and Solutions
LOW COOLANT TEMP—Activated when the supply coolant temperature sensor temperature
reading drops below the higher of the two calculated dew points, assuming that neither Sensor A nor
Sensor B has a sensor failure alarm. This alarm will reset when the coolant temperature sensor reads
the fluid temperature above both of the two calculated dew points and the alarm has been
acknowledged. This alarm can lock the unit Off. If this occurs, the main power must be cycled, or the
Low Coolant Temp Alarm Code in the Service Diagnostics menu must be reset to 0.
LOW TEMP SENSOR A—Activated when the reading from Sensor A drops below the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor A rises 2°F (1.1°C) above the
setpoint and the alarm has been acknowledged.
LOW TEMP SENSOR B—Activated when the reading from Sensor B drops below the user-specified
alarm setpoint. The alarm will reset when the reading from Sensor B rises 2°F (1.1°C) above the
setpoint and the alarm has been acknowledged.
PUMP SHORT CYCLE—Activated when the Liebert DCP is trying to establish flow and is unable
to do so. The Liebert DCP will attempt three times to establish flow on a pump before trying the other
pump. The control will keep cycling three times on one pump, then three times on the other pump
until it is able to establish flow. If this cycling occurs for 30 minutes and the Liebert DCP still does not
establish flow, a PUMP SHORT CYCLE alarm will be present. This alarm will shut down the Liebert
DCP. To reset this alarm, the main power must be cycled.
RAM/BATTERY FAIL—Activated when the RAM backup battery or the RAM itself has failed. This
requires a hardware replacement.
SENSOR A FAILURE—Activated when the controls no longer senses a signal from Sensor A. This
alarm will reset when the signal is returned and the alarms has been acknowledged.
SENSOR B FAILURE— Activated when the controls no longer senses a signal from Sensor B. This
alarm will reset when the signal is returned and the alarm has been acknowledged.
SMOKE DETECTED—Activated when the Customer Input 1 is configured for “Smoke” and 24VAC
is applied to the input. This alarm is reset when the 24VAC is removed.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
SUPPLY CW SENSOR FAILURE—Activated when the control no longer senses a signal from the
Supply CW sensor. This alarm will reset when the signal is returned.
SUPPLY COOLANT SENSOR FAILURE—Activated when the control no longer senses a signal
from the supply coolant sensor. This alarm will reset when the signal is returned.
UNIT CODE MISSING—Activated when a valid unit code has not been entered and saved. To reset,
enter valid unit code, save and execute.
WATER UNDER FLOOR—Activated when Customer Input 1 is configured for “Water Alarm” and
24VAC is applied to the input. This alarm is reset when the 24VAC is removed.
6.2Warning Descriptions
LOSS OF POWER—Activated when the unit is On and operational and 24VAC power to the control
is lost. This alarm will be emitted when power is restored to the control. The Liebert DCP will restart
at a user-defined time delay after power is restored. Once activated, the alarm will remain activated
for 30 minutes.
PUMP 1 HRS EXCEED—Activated when the Pump 1 Actual Hours exceeds the user-specified limit.
To reset, Actual Hours must be reset to 0.
PUMP 2 HRS EXCEED—Activated when the Pump 2 Actual Hours exceeds the user-specified limit.
To reset, Actual Hours must be reset to 0.
65Liebert® DCP
™
6.3System Shutdown Causes
Unit Is Off By Coolant Sens Fail
The control has lost its signal from the coolant temperature sensor. The control has no way of
controlling the coolant temperature, so the unit is shut off. Main power (disconnect switch) must be
turned Off, then back On to clear this alarm.
Unit Is Off By High CW Temp
The entering chilled water temperature is too high to keep the pump(s) running normally. If a HIGH
CW TEMP alarm occurs and the pump loses flow, then the Liebert DCP will go into a pre-chill mode.
The Liebert DCP can attempt to start again only if the entering chilled water temperature drops below
the HIGH CW TEMP setpoint.
Unit Is Off By Pump Short Cycle
The control was unable to get a pump started upon startup or after a loss of flow. The control looks at
the SHORT CYCLE time delay. If it cannot establish flow within that amount of time, the unit is shut
down. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
Unit Is Off By Low Coolant Temp
The control was unable to raise the coolant temperature to the calculated fluid temperature control
point. The unit is shut down because if the control cannot raise the coolant temperature to the
calculated coolant temperature control point, water may condense on the coolant piping and receiving
coils. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
Alarm Descriptions and Solutions
Liebert® DCP
™
66
7.0TROUBLESHOOTING
Table 4Troubleshooting the Liebert DCP
SymptomPossible CauseCheck or Remedy
No main powerCheck L1, L2 and L3 for rated voltage.
Overloads trippedAllow pump to cool. Check amp draw.
Tripped circuit breakerCheck circuit breaker to pump(s).
Incorrect phase wiringCheck wiring phase.
No chilled water
Isolation valve(s) on pump suction
and/or discharge is closed.
Supply chilled water is too high
Liebert XDK™ cooling modules are
Off
Low Coolant Temperature
(high dew point)
Flow switch not functioningCheck for defective switch or miswiring.
Not enough chargeSee 5.1 - Checklist for Liebert DCP Startup.
Chilled water valve not closing
completely.
Cavitation due to vapor in pump
Worn motor bearingsReplace pump
Pump is rotating in reverseCheck wiring phase.
Low Coolant Temperature
Loss of power
Leak in system - loss of charge
Low Chilled Water Temperature
Alarm and Loss of Flow Pump X
Alarm
Supply Fluid Sensor Failure Alarm
Motor operates but valve won't open
No 24 VAC power to motorCheck for 24 VAC between P52-1 and P52-4.
No signal from controlCheck 24 VAC at P22-1 (close) or P22-3 (open).
Motor not operating
Check and verify that there is supply chilled water to the
Liebert DCP.
Open all isolation valves completely during normal operation.
Check and verify that the chilled water temperature setpoint is
at 50°F (10°C) or lower and that there is flow on the chilled
water side.
Check Liebert XDK cooling modules to make sure that they
are On prior to starting the Liebert DCP.
Check alarm(s) history on Liebert DCP. The Liebert DCP was
operating below the dew point for a significant amount of time.
Check humidity in conditioned space, lower humidity if
necessary to allow Liebert DCP to operate at a lower
temperature. (Disconnect must be switched to Off then back
On to allow Liebert DCP to reset itself).
Wait at least 10 minutes before calibrating. Access the
Advanced Menu>Factory Settings>Calibrate Actuator.
Contact Liebert Services for assistance, 1-800-543-2778.
Check for adequate charge in system, refer to the User's
Manual.
1. Check humidity of the room along with the location of
remote sensors. Make sure that the sensors are not in a cold
area where there is insufficient air flow for accurate,
representative readings.
2. Chilled Water temperature is too cold.
3. Load is too light.
When power is restored, the Liebert DCP will automatically
restart.
Check the entire system for leaks with a fluid sniffer. Repair as
necessary.
Check supply chilled water temperature.
Check wiring.
Call service.
Check linkage for adjustment and be sure that it is tight on the
valve.
Unplug P22 from the board. Jumper P22-5 to P52-4 for
grounding, then jumper P22-1 to P52-1 to drive close. Remove
jumper to close and then jumper P22-3 to P52-1 to drive open.
If motor fails to work, replace it.
5.1 - Checklist for Liebert DCP Startup
Troubleshooting
67Liebert® DCP
™
Table 4Troubleshooting the Liebert DCP (continued)
SymptomPossible CauseCheck or Remedy
Motor burnout
Main 24VAC fuse trips
Room becomes too
warm
Check control panel for welded
contactor contacts or welded
overload contacts
Shorts or loose connectionsCheck the wiring connections of the 24 VAC circuit.
Faulty circuit boardReplace the circuit board.
Liebert DCP is Off
High dew point
Liebert XDK™ cooling modules are
Off
Minimum room temperature setpoint
is too high
Temperature/humidity sensors
incorrectly placed
Troubleshooting
Replace defective components.
Check status of the Liebert DCP at the user interface. Turn
system On at I/O button if system is Off.
Check temperature and relative humidity (RH) of room. Lower
RH setpoint if necessary to lower dew point. At normal room
temperature of 68°F (20°C), the RH should be set to 50% or
lower.
Check Liebert XDK cooling modules to make sure that they
are On before starting the Liebert DCP.
Check the setpoint in the User Setpoints menu (see
Figure 44).
Place the sensor on the return air side of the primary air mover
(e.g., Liebert DS
doors, windows or similar areas.
™
). Do not install the sensor near unsealed
Liebert® DCP
™
68
8.0MAINTENANCE
NOTICE
Risk of leaking chilled water and drain lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service
practices can result in water leakage from the unit. Water leakage can result in severe
property damage and loss of critical data center equipment. Do not locate unit directly above
any equipment that could sustain water damage. Emerson
leak detection equipment for the unit and its factory- and field-installed supply, return and
drain lines.
The Liebert DCP system components require little maintenance when proper fluid levels are
maintained and proper startup and operation procedures are followed. The following task should be
performed at the intervals stated:
• Clean or replace chilled water strainer annually. Adjust accordingly based on purity of chilled
water.
Maintenance
®
recommends installing monitored
69Liebert® DCP
™
9.0SPECIFICATIONS
Table 5Liebert DCP200 specifications
Models
Cooling Capacity, Nominal
Electrical Requirements
Dimensions, inches (mm)
Weight, lb (kg)
Installed, with Fluid and Chilled Water 1148 (521)1322 (600)
Pipe Connections
Fluid Supply to Cooling Module2-5/8" OD, Cu
Fluid Return from Cooling Module2-5/8" OD, Cu
Chilled Water Supply and Return2-5/8" OD, Cu
Control Valve
Pressure Drop – Chilled Water Side
Temperature Rise – Chilled Water Side
at Rated Flow, °F (°C)
Number of Liebert Cooling Units Connected, Maximum
Il Produttore dichiara che, se munito di marchio CE, il prodotto è conforme alle direttive dell'Unione
europea:
The Manufacturer hereby declares that this product, when bearing the CE mark, conforms to the
European Union directives:
Der Hersteller erklärt hiermit, dass das vorliegende Produkt, sollte es die CE-Kennzeichnung tragen, den
folgenden Richtlinien der Europäischen Union entspricht:
Le fabricant déclare par la présente que ce produit, portant la marque CE, est conforme aux directives de
l'Union européenne :
El fabricante declara por la presente que si este producto lleva el marcado CE es conforme con las
directivas de la Unión Europea:
O fabricante declara por este meio que este produto, quando ostenta a marca CE, está em conformidade
com as directivas da União Europeia:
Tillverkaren tillkännager härmed att den här produkten, när den är CE-märkt, överensstämmer med EU:s
direktiv:
De fabrikant verklaart hierbij dat dit product, indien het van de CE-markering is voorzien, conform de
EU-richtlijnen is:
Valmistaja vakuuttaa täten, että mikäli tuotteessa on CE-merkintä, se täyttää seuraavien EU-direktiivien
vaatimukset:
Produsenten erklærer herved at dette produktet, når det er CE-merket, er i samsvar med EU-direktiver:
Producenten erklærer hermed, at dette produkt overholder EU's direktiver, når det bærer CE-mærket:
Ο Κατασκευαστής δηλώνει ότι το προϊόν αυτό, το οποίο φέρει σήμανση CE, είναι σύμμορφο με τις
οδηγίες της Ε.Ε.: