Unit capacity data is “net,” and is certified to ASHRAE 127-2007 rating standard
2
Liebert CW Performance Data—50 & 60 Hz Systems
CW026CW038CW041CW051CW060CW076CW084CW106CW114
Fan Section - Variable Pitch, Two-Belt Drive Package* (*Some options or combination of options may result in reduced air flow.
Consult factory for recommendation.)
Air Volume CFM (CMH)
Fan Motor HP (kW)3.0 (2.2)5.0 (3.7)5.0 (3.7)7.5 (5.6)7.5 (5.6)10 (7.5)10 (7.5)15 (11.2)15 (11.2)
Ext. Static Press. in. of water (Pa)0.2 (50)0.2 (50)0.2 (50)0.2 (50)0.2 (50)0.2 (50)0.2 (50)0.2 (50)0.2 (50)
Number of Fans111222233
Chilled Water Coil
Face Area sq. ft. (m2) 11.7 (1.08) 11.7 (1.08) 11.7 (1.08) 18.5 (1.72) 18.5 (1.72) 25.0 (2.32) 25.0 (2.32) 36.28 (3.37) 36.28 (3.37)
* Includes Fan Motor ** Optional 3-Way valve available-consult factory *** 25 PSI (172.4 kPa) Max operating pressure-consult factory for higher pressures.
† Unit CFM reduced by 300 with std. motor (142 l/s) **** 150 PSI (1034.3 kPA) Max operating pressure-consult factory for higher pressures.
Blower Duct & Deck Dimensions, CW106 and CW114, Upflow Models
76"
Ref
F
Blower Deck
Front or Rear Air Supply
Top of Unit
DPN001663
Rev. 0
CC CEE
D
35"
Ref
B
Duct Flanges on Three Blowers
122" Ref
A
Front of Unit
Blower Duct Flange Location
2
1
*Follow standard practices on all duct work.
1. Straight section of duct off of unit to be 1.5
to 2.5 times the longest blower dimension.
2. Typical ducting shown, may run to either
side.
TOP-FRONT
SUPPLY SHOWN
1" (25.4mm) Flange
for Decorative
Plenum Alignment
Filter
Access
(both
ends)
Flanges Provided on
Blower Outlets for
Supply Air Ducting
24-1/4" (616mm)
117-1/2"
(2985mm)
2-1/4"
(57mm)
22"
(546mm)
Air
Return
Opening
4"
(102mm)
NOTE: Only 120"
Upflow has rear
return filter box.
6.0BLOWER DUCT & DECK DIMENSIONS, CW106 AND CW114, UPFLOW MODELS
ModelBlowerSupply
CW10615 x 15
CW114 15 x 11
Motor,
hp
Top Front10-15
Top Rear10-15
Top Front10-15
20
Top Rear10-20
27-1/2
(699)
27-1/2
(699)
30
(762)
30
(762)
30
(762)
Dimensional Data, inches (mm)
3 1/2
(89)
12 5/16
(313)
3 1/2
(89)
3 1/2
(89)
12 5/16
(313)
18-11/16
(475)
18 11/16
(475)
14 3/4
(375)
14 3/4
(375)
14 3/4
(375)
16-3/16
(411)10(254)
16 3/16
(411)10(254)
16 3/16
(411)10(254)
16 3/16
(411)10(254)
16 3/16
(411)10(254)
4 1/2
(114)
4 1/2
(114)
4 1/2
(114)
4 1/2
(114)
4 1/2
(114)
Net Weight
lb. (Kg)AB C DEF
1785
(810)
1925
(873)
12
Electrical Specifications
7.0ELECTRICAL SPECIFICATIONS
Table 5Electrical data—50 Hz systems
Reheat OptionsElectricNoneElectricNone
Humidifier OptionsIR/SGHIR/SGHSteam or NoneSteam or None
Models Motor HP Volts200230380-415 200 230 380-415200230380-415 200 230 380-415
CW026
CW038
CW041
CW051
CW060
CW076
CW084
CW106
CW114
1. FLA = FULL LOAD AMPS
2. Amperage requirements are based on the rated max FLA current of each component in the unit. The rated max FLA current of the unit is
not the sum total of all components, but is the total of the components which operate during maximum electrical load conditions.
3. The values in the table are for power demand of the unit only.
4. Units are 3-phase, 50-cycle.
5. Consult factory engineering department for electrical requirements of units with variations not listed above.
Table 8Indoor evaporator fan motor electrical requirements—60Hz systems
208230460575
Hp
2.0 HP7.546.96.840.83.420.42.716.2
3.0 HP10.666.09.658.04.826.83.923.4
5.0 HP16.7105.015.291.07.645.66.136.6
7.5 HP24.2152.022.0132.011.066.09.054.0
10.0 HP30.8193.028.0168.014.084.011.066.0
15.0 HP46.2290.042.0252.021.0126.017.0102.0
20.0 HP59.4321.054.0290.072.0145.022.0116.0
1. Refer to General Data Section for standard fan motor size on units.
2. FLA = FulL Load Amps
WSA = Wire Sizing Amps (Minimum supply circuit ampacity)
MFCB = Maximum Fuse or Circuit Breaker Size
3. Amperage requirements are based on the rated max FLA current of each component in the unit. The rated max FLA current of the unit
is not the sum total of all components, but is the total of the components which operate during maximum electrical load conditions.
4. The values in the chart are for power of the unit only.
5. Units are 3 phase, 60 cycle.
6. For units with other variations not listed above, consult factory engineering department for electrical requirements.
FLALRAFLALRAFLALRAFLALRA
15
GUIDE SPECIFICATIONS
1.0GENERAL
1.1Summary
These specifications describe requirements for a precision environmental control system. The system
shall be designed to maintain temperature conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation
requirements of the room.
1.2Design Requirements
The precision environmental control system shall be a Liebert self-contained factory assembled unit
with (upflow) (down-flow) air delivery. The system shall have a total cooling capacity of ____ BTU/
HR, (kW) with a sensible cooling capacity of ____ BTU/ HR (kW) based on an entering air temperature
of ____ °F (°C) dry bulb and ____ °F (°C) wet bulb. The unit is to be supplied with ____ volt ____ ph
____ Hz electrical service.
1.3Submittals
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.
2.0PRODUCT
Guide Specifications
2.1Cabinet and Frame Construction
The frame shall be constructed of heliarc welded tubular steel. It shall be painted using the autophoretic coating process for maximum corrosion protection. The exterior panels shall be insulated
with a minimum 1 in. (25.4mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall
have captive 1/4 turn fasteners. The main unit color shall be _________. The accent color shall be
_________. The exterior panels shall be powder coated.
2.2Filter Chamber
The filter chambers shall be an integral part of the system, located within the cabinet serviceable
from either end of the unit. The filters shall be rated not less than ____% efficiency (based on
ASHRAE 52.1).
For models CW106 and CW114, the filters shall be serviceable from the front of the unit.
2.3Fan Section
The fan shall be the centrifugal type, double width double inlet, and shall be factory-balanced as a
completed assembly. The shaft shall be heavy duty steel with self-aligning ball bearings with a minimum life span of 100,000 hours. The fan motor shall be ____ hp at 1750 RPM at 60 Hz (1450 RPM at
50 Hz) and mounted on an adjustable slide base. The drive package shall be two-belt, variable speed,
sized for 200% of the fan motor horsepower. The fans shall be located to draw air over the A-frame coil
to ensure even air distribution and maximum coil performance.
2.3Electronically Commutated (EC) Fan
The fan shall be the plug/plenum type, single inlet and shall be dynamically balanced. The fan motor
shall be 4.2 hp, 1520 rpm maximum operating speed. The drive package shall be direct drive Electronically Commutated, variable speed. The fans shall be located to draw air over the A-frame coil to
ensure even air distribution and maximum coil performance.
2.4Liebert iCOM™ Microprocessor Control With Small Graphic Display
The Liebert iCOM unit control shall be factory-set for Intelligent Control which uses “fuzzy logic” and
“expert systems” methods. Proportional and Tunable PID shall also be user selectable options. Internal unit component control shall include the following:
16
Guide Specifications
System Auto Restart - The auto restart feature will automatically restart the system after a power
failure. Time delay is programmable.
Sequential Load Activation - On initial startup or restart after power failure, each operational
load is sequenced with a minimum of one second delay to minimize total inrush current.
Hot Water Flush Cycles - Hot water reheat coils and Econ-O-Coils are periodically flushed to prevent a buildup of contaminants.
Predictive Humidity Control - calculates the moisture content in the room and prevents unnecessary humidification and dehumidification cycles by responding to changes in dew point temperature.
The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices.
Options are available for BMS interface via MODbus, Jbus, BACNet, Profibus and SNMP.
The Liebert iCOM control processor shall be microprocessor based with a 128x64 dot matrix graphic
front monitor display and control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display & housing shall be viewable while the unit panels are open or closed. The
controls shall be menu driven. The display shall be organized into three main sections: User Menus,
Service Menus and Advanced Menus. The system shall display user menus for: active alarms, event
log, graphic data, unit view/status overview (including the monitoring of room conditions, operational
status in % of each function, date and time), total run hours, various sensors, display setup and service contacts. A password shall be required to make system changes within the service menus. Service
menus shall include: setpoints, standby settings (lead/lag), timers/sleep mode, alarm setup, sensor
calibration, maintenance/wellness settings, options setup, system/network setup, auxiliary boards
and diagnostics/service mode. A password shall be required to access the advanced menus which
include the factory settings and password menus.
The User Menus Shall be Defined as Follows
Active Alarms: Unit memory shall hold the 200 most recent alarms with time and date stamp for
each alarm.
Event Log: Unit memory shall hold the 400 most recent events with ID number, time and date
stamp for each event.
Graphic Data View: Eight graphic records shall be available: return air temperature, return air
humidity, supply air temperature, outdoor temperature and four custom graphs.
Unit View: Status Overview: Simple or Graphical “Unit View” summary displays shall include temperature and humidity values, active functions (and percent of operation) and any alarms of the host
unit.
Total Run Hours: Menu shall display accumulative component operating hours for major components including fan motor, humidifier and reheat.
Various Sensors: Menu shall allow setup and display of optional custom sensors. The control shall
include four customer accessible analog inputs for sensors provided by others. The analog inputs shall
accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC if
desired. The gains for each analog input shall be programmable from the front display. The analog
inputs shall be able to be monitored from the front display.
Display Setup: Customer shall pre-select the desired grouping of display languages at the time of
the order from the following choices:
• Group 1: English, French, Italian, Spanish, German
• Group 2: English, Russian, Greek
•Group 3: English, Japanese, Chinese, Arabic
• Service Contacts: Menu shall allow display of local service contact name and phone number.
17
Guide Specifications
The Service Menus Shall be Defined as Follows
Setpoints: Menu shall allow setpoints within the following ranges:
• Temperature Setpoint 65-85ºF (18-29ºC)*
• Temperature Sensitivity +1-10ºF (0.6-5.6ºC)
• Humidity Setpoint 20-80% RH*
• Humidity Sensitivity 1-30% RH
• High Temperature Alarm 35-90ºF (2-32ºC)
• Low Temperature Alarm 35-90ºF (2-32ºC)
• High Humidity Alarm 15-85% RH
• Low Humidity Alarm 15-85% RH
* The microprocessor may be set within these ranges, however, the unit may not be able to control to
extreme combinations of temperature and humidity.
Standby Settings/Lead-Lag: Menu shall allow planned rotation or emergency rotation of operating
and standby units.
Timers/Sleep Mode: Menu shall allow various customer settings for turning on/off unit.
Alarm Setup: Menu shall allow customer settings for alarm notification (audible/local/remote). The
following alarms shall be available:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• Main Fan Overload (Optional)
• Humidifier Problem
• Change Filter
•Fan Failure
•Unit Off
Audible Alarm: The audible alarm shall annunciate any alarm that is enabled by the operator.
Common Alarm: A programmable common alarm shall be provided to interface user selected alarms
with a remote alarm device.
Remote Monitoring: All alarms shall be communicated to the Liebert monitoring system with the
following information: Date and time of occurrence, unit number and present temperature and
humidity.
Sensor Calibration: Menu shall allow unit sensors to be calibrated with external sensors.
Maintenance/Wellness Settings: Menu shall allow reporting of potential component problems
before they occur.
Options Setup: Menu shall provide operation settings for the installed components.
System/Network Setup: Menu shall allow Unit-to-Unit (U2U) communication and setup for team-
work modes of operation (up to 32 units).
Teamwork Modes of Operation: Saves energy by preventing operation of units in opposite modes
multiple units.
Auxiliary Boards: Menu shall allow setup of optional expansion boards.
Diagnostics/Service Mode: The Liebert iCOM control shall be provided with self-diagnostics to aid
in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as on or off at the front display. Control outputs shall be able to be
turned on or off from the front display without using jumpers or a service terminal. Each control output shall be indicated by an LED on a circuit board.
18
Guide Specifications
Advanced Menus
Factory Settings: Configuration settings shall be factory-set based on the pre-defined component
operation.
Change Passwords: Menu shall allow new passwords to be set or changed.
2.4.1Liebert iCOM Microprocessor Control With Large Graphic Display (Optional)
The Liebert iCOM unit control with large graphic display shall include all of the features as the Liebert iCOM with small graphic display, except that it includes a larger graphical display and shall
include the additional features of:
“System View”, Spare Parts List, Unit Diary.
The Liebert iCOM control processor shall be microprocessor based with a 320x240 dot matrix graphic
front monitor display panel and control keys for user inputs mounted in an ergonomic, aesthetically
pleasing housing.
System View - Status Overview: “System View” shall display a summary of operation for the total
number of operating units within a Unit-to-Unit (U2U) configuration.
Spare Parts List: Menu shall include a list of critical spare parts, their quantity and part numbers.
Unit Diary: Menu shall include a free field area within the unit memory where unit history may be
stored for reference.
2.5Liebert iCOM Wall-Mount Large Graphic Display (Optional)
The Liebert iCOM Large Graphic Display Kit shall include an ergonomic, aesthetically pleasing housing, a 320x240 dot matrix graphic display and a 120V power supply. The Wall-Mount Large Graphic
Display shall be used to allow remote location of a “System View” display and all features of the Large
Graphic User, Service and Advanced menus for use with Liebert iCOM controlled products connected
for Unit-to-Unit (U2U) communications.
2.5.1Control
The control system shall allow programming of the following room conditions:
• Temperature Setpoint: 65-85°F (18-29°C)
• Temperature Sensitivity: ±1° to 9.9°F (0.6 to 5.6°C) in 0.1°F (0.1°C) increments
All setpoints shall be adjustable from the individual unit front monitor panel. Temperature and
humidity sensors shall be capable of being calibrated using the front monitor panel controls to coordinate with other temperature and humidity sensors in the room.
In addition, the system shall provide the following internal controls:
2.5.1.1System Auto-Restart
For startup after power failure, the system shall provide automatic restart with a programmable (up
to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the unit
or from the central site monitoring system.
2.5.1.2Sequential Load Activation
During startup or after a power failure, the Liebert iCOM control shall sequence operational load
activation to minimize inrush current. Systems allowing multiple loads to start simultaneously are
unacceptable.
2.5.1.3Front Monitor Display Panel
The Liebert iCOM control shall provide a front monitor LCD, backlit display panel with 4 rows of 20
characters with adjustable contrast. This display (along with nine front-mounted control keys) shall
be the only operator interface required to obtain all available system information such as room conditions, operational status, alarms, control and alarm setpoints and all user selections including alarm
delays, sensor calibration, DIP switch selections and diagnostics. All indicators shall be in language
form. No symbols or codes shall be acceptable.
19
2.5.1.4Alarms
The Liebert iCOM control shall activate an audible and visual alarm in event of any of the following
conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• Main Fan Overload (opt)
• Change Filters
• Loss of Air Flow
• Loss of Power
• Custom Alarm (#1 to #4)
Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom
alarms can be identified with prepared (programmed) labels for the following frequently used inputs:
• Leak Under Floor
• Smoke Detected
• Loss of Water Flow
•Standby Unit On
User customized text can be entered for two of the four custom alarms.
Guide Specifications
Each alarm (unit and custom) can be separately enabled or disabled, selected to activate the common
alarm, and programmed for a time delay of 0 to 255 seconds.
2.5.1.5Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.
2.5.1.6Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote
alarm device.
2.5.1.7Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following information: date and time of occurrence, unit number and current temperature and humidity.
2.5.1.8Diagnostics
The control system and electronic circuitry shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs
shall be indicated as on or off at the front monitor panel. Control outputs shall be able to be turned On
or Off from the front monitor panel without using jumpers or a service terminal.
2.5.1.9Data Collection
The control system shall maintain accumulative operating hours of compressors, fan motor and EconO-Coil. The 10 most recent alarms shall be retained.
2.5.1.10 Communication
The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices.
2.6Chilled Water Control Valve
The water circuit shall include a 3-way (2-way) modulating valve. The Liebert iCOM positions the
valve in response to room conditions. Cooling capacity will be controlled by bypassing chilled water
around the coil.
20
2.7High Pressure Chilled Water Control Valve—Optional
The chilled water circuit shall include a 3-way (2-way) high pressure modulating valve. The valve
shall be designed for up to 400 PSI (2758 kPa) water pressure.
2.8A-Frame Chilled Water Coil
The cooling coil shall be of A-frame design with a minimum of ____ sq. ft. (sq.m.) face area, ____ rows
deep.
The coil shall be controlled by a 3-way modulating control valve. It shall be constructed of copper
tubes and aluminum fins and have a maximum face velocity of ____ ft. per minute (m/s) at ____ CFM
(CMH).
The water circuit shall be designed to distribute water into the entire coil face area. The coil shall be
supplied with ____ °F (°C) entering water temperature, with a ____ °F (°C) temperature rise. The coil
shall require ____ GPM (l/s) of chilled water and the pressure drop shall not exceed ____ PSI (kPa).
The entire coil assembly shall be mounted in a stainless steel condensate drain pan.
For models CW106 and CW114, the end sheets shall be aluminum, and the coil can be removed from
the front or either side of the unit.
2.9Flow Switch—Optional
The flow switch shall activate the alarm system should the chilled water supply be interrupted. The
switch shall be factory mounted and wired.
Guide Specifications
2.10Variable Speed Drive—Optional
A variable speed drive (VSD) is available for models CW106 and CW114 to reduce energy consumption. The fan motor speed shall be varied from 100% to 60% of rated speed in response to room conditions. This shall be controlled automatically by the Liebert iCOM control. The variable speed drive
option shall be available with an infrared humidifier.
2.11Optional Components
The computer room environmental control system shall be equipped with the following optional components.
2.11.1 Disconnect Switch—Non-Locking Type
The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The
switch shall be accessible with the door closed.
2.11.2 Disconnect Switch—Locking Type
The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The
switch shall be accessible from the outside of the unit with the door closed, and prevent access to the
high voltage electrical components until switched to the “OFF” position.
2.11.3 High Temp Stat
The high temp stat shall immediately shut down the environmental control system when activated.
The high temp stat shall be mounted in the electrical panel with the sensing element in the return
air.
2.11.4 Condensate Pump, Dual Float
The condensate pump shall have a minimum capacity of 100 GPH at 20 ft. (378 l/hr at 6m) head.
(Consult factory for 200V or 230V, 50 Hz applications.) It shall be complete with integral float switch,
pump and motor assembly, and reservoir. Secondary float shall shut down unit if tripped.
2.11.5 Liebert Liqui-tect™ Sensors (Max. of Two Per Unit)
Provide ____ (quantity) solid state water sensors under the raised floor.
21
2.11.6 Floor Stand
The floor stand shall be constructed of a heliarc-welded, tubular steel frame. The floor stand shall
have adjustable legs with vibration isolation pads. The floor stand shall be ____ inches high.
2.11.6.1 Floor Stand Turning Vane
A factory-supplied, field-mounted turning vane shall be provided.
2.11.6.2 Smoke Sensor
The smoke sensor shall immediately shut down the environmental control system and activate the
alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the
sensing element in the return air compartment.
2.11.6.3 Liebert SiteScan® Site Monitoring System
Provide a Liebert SiteScan monitor system with the Liebert CW. The Liebert SiteScan shall have the
capability to monitor and change (at the user direction) the temperature setpoints and sensitivities of
each unit. The printer shall provide the user with chronological alarm information. It shall also be
capable of being programmed to print out environmental conditions or operating modes at each unit.
3.0EXECUTION
3.1Installation of Precision Cooling Units
3.1.1General
Guide Specifications
Install precision cooling units in accordance with manufacturer’s installation instructions. Install
units plumb and level, firmly anchored in locations indicated, and maintain manufacturer’s recommended clearances.
3.1.2Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory
mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical contractor.
3.1.3Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.2Field Quality Control
Startup mainframe coolant units in accordance with manufacturer’s startup instructions. Test controls and demonstrate compliance with requirements.
22
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.