Risk of improper installation. Can cause equipment damage, injury or death.
Only a qualified service professional should install these products. Emerson recommends
having an Emerson Network Power
in large UPS’s. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications.
Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected
from the electrical source.
Check the circuits with a voltmeter before beginning installation.
Important Safety Instructions
®
Liebert Services representative perform the installation
Reset
Button
(Reboot or
reset to
factory
defaults)
BACnet MSTP
Modbus RTU
YDN23
Micro-USB AB
(future release)
This Liebert IntelliSlot Unity platform delivers enhanced communication and control of AC Power,
Power Distribution and Thermal Management products. The platform communicates with Emerson
Network Power
™
Web
and Liebert Nform®.
The platform includes the Liebert IntelliSlot Unity-DP
Each card employs the Emerson Protocol to monitor and manage a wide range of operating
parameters, alarms and notifications about the power, distribution and Thermal Management
equipment. The cards also communicate with Building Management Systems and Network
Management Systems.
Figure 1Liebert IntelliSlot Unity-DP card features
®
software tools and services, including Trellis®, LIFE™ Technology, Liebert SiteScan
™
and Liebert IntelliSlot Unity LIFE™ cards.
IS-UNITY-DP
Introduction
1.1Protocols
Each card supports the Emerson Protocol, Remote Service Delivery Protocol and HTTP Web by
default.
The Liebert IntelliSlot Unity-DP supports selecting two third-party protocols; the Liebert IntelliSlot
Unity LIFE card supports the default protocols only (Emerson Protocol, Remote Service Delivery
Protocol and HTTP Web).
Available protocols are
• BACnet IP—BACnet over Internet Protocol
• BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over a
RS-485 serial network (also known as BACnet MSTP RS-485)
• Modbus RTU—Modbus Remote Terminal Unit (RTU) communication protocol over a RS-485
serial network (also known as Modbus RTU RS-485)
• Modbus TCP—Modbus Transmission Control Protocol over Internet Protocol (also known as
Modbus TCP/IP)
•SNMP
• YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
Link
Activity
485
Liebert® IntelliSlot™ Unity™ Card2
Introduction
1.2Compatibility With Other Emerson Products and Communication Protocols
The Liebert IntelliSlot Unity-DP platform supports the following protocols:
Table 2Liebert IntelliSlot card communication protocols
Communication Protocols Available
Remote
Liebert IntelliSlot
Card (Part #)
Liebert IS-UNITY-DP
(IS-UNITY-DP)
Liebert IS-UNITY-LIFE
(IS-UNITY-LIFE)
* YDN23 applicable only to Liebert PeX and Liebert NXL.
HTTP
HTTPS
Emerson
Protocol
✔✔ ✔✔✔✔✔✔✔
✔✔ ✔
Service
Delivery
ProtocolEmail SMS
—— ——— —
Compatible with:
SNMP
v1,v2c, v3
™,
Liebert Challenger 3000™
BACnet IP
BACnet MSTP
Modbus TCP
Modbus RTUYDN23 *
™
The Liebert IntelliSlot Unity platform supports both 10Mbit and 100Mbit communication speeds and
either half or full duplex.
Password Protection
Control and configuration capabilities are protected by an administrator’s username and password
combination. Optionally, status information can be password-protected. The default user name for the
administrator is Liebert and the default password is also Liebert.
The user name and password can be changed with the Web interface. See 2.2 - Change User Names and Passwords Immediately for details.
SNMP Support
The Liebert IntelliSlot Unity card enables SNMP management of Liebert equipment. To integrate the
card into a SNMP implementation, import or compile the Liebert Global Products MIB on the
network management station (NMS).
The Liebert Global Products MIB is available at Liebert’s Web site (www.liebert.com); it supports
both Windows
®
(192436P1) and Unix (192435P1) file formats.
Web Support
The Liebert IntelliSlot Unity card delivers Web management and control to Liebert equipment over
HTTP and HTTPS. All authorized users on your network will be able to view status information.
Modbus TCP and Modbus RTU Support
The Liebert IntelliSlot Unity card supports Modbus TCP and Modbus RTU for the full range of
information available from the managed device. The Modbus protocol mapping document, SL-28170,
is available at Liebert’s Web site: www.liebert.com
BACnet IP and BACnet MSTP Support
The Liebert IntelliSlot Unity card supports BACnet IP and BACnet MSTP for the full range of
information available from the managed device. The BACnet protocol mapping document, SL-28170,
is available at Liebert’s Web site: (www.liebert.com). This document includes the BACnet Protocol
Implementation Conformance Statement (PICS) document as a guide to implementing the BACnet
protocol.
3Liebert
®
IntelliSlot™ Unity™ Card
YDN23 Support
Introduction
The Liebert IntelliSlot Unity card supports YD/T-1363 specification for the full range of information
available from managed Liebert NXL
™
or Liebert PeX™ units.
Trellis™ Support
The Liebert IntelliSlot Unity-DP card communicates a rich set of Emerson Protocol information to the
Trellis DCIM platform.
Trellis can manage and control Liebert equipment using SNMP, Modbus or the Emerson Protocol.
This allows monitoring all Liebert equipment using Liebert IntelliSlot Web, Liebert IntelliSlot 485,
Liebert IntelliSlot IPBML, Liebert IntelliSlot Web ADPT or Liebert IntelliSlot Unity platform
communication interfaces.
Liebert Nform
Utilizing the Emerson Protocol or SNMP and Web technologies built into each Liebert IntelliSlot
Unity card, Liebert Nform will centrally manage alarm notifications to provide an easy interface to
access critical equipment information.
A downloadable version is available online at: nform.liebert.com
Liebert MultiLink
The Liebert IntelliSlot Unity card integrates with Liebert’s MultiLink software to provide
unattended, graceful operating system shutdown of PCs, servers and workstations. The card can be
monitored by Liebert MultiLink over the network, eliminating the need for serial cables.
For more information on Liebert MultiLink and a downloadable version of Liebert MultiLink
software, visit multilink.liebert.com
®
Support
®
Support
Liebert® IntelliSlot™ Unity™ Card4
2.0INSTALLATION
!
Activity
Link
485
IS-UNITY-DP
WARNING
Risk of improper installation. Can cause equipment damage, injury and death.
Only a properly trained and qualified service professional should install these products.
Emerson recommends having an Emerson Network Power
perform the installation in large UPS’s. Contact Liebert Services at 1-800-LIEBERT
(1-800-543-2378).
NOTICE
Risk of duplicate node ID’s if two or more Liebert IntelliSlot cards are installed. Can cause
network conflicts.
An internal networking conflict may occur within a device when multiple communication
cards with duplicate Node IDs are installed in the device.
Each Liebert IntelliSlot card must have a unique node ID. This will not be a problem if only
one card is installed on your system. Duplicate node ID’s are easily averted with the
procedure detailed in 2.4 - Installing Multiple Liebert IntelliSlot Unity Cards in a System.
2.1Installing the Liebert IntelliSlot Unity Card
The Liebert IntelliSlot Unity card may be installed at the factory or field-installed. To perform a
field-installation:
1. Find the Liebert IntelliSlot bay on your Liebert equipment—It may have a plastic cover.
2. Insert the card into the Liebert IntelliSlot bay.
Installation
®
Liebert Services representative
NOTE
The card will only fit one way in the Liebert IntelliSlot bay because the circuit board is not
centered on the faceplate. The slot in the Liebert IntelliSlot bay also is not centered.
3. Secure the card with the screws supplied with the cover plate.
4. Connect an Ethernet cable to the card’s Ethernet RJ-45 port for IP communication interfaces.
5. Connect a serial cable to the card’s 485 RJ-45 port for RS-485 communication interfaces (see
2.1.3 - Connect an RS-485 Serial Cable.
2.1.1Assigning the Card’s IP Address
DHCP
The Liebert IntelliSlot Unity card is factory-configured for DHCP. If you require a Static or BootP
network configuration, be sure to change the Boot Mode as described in Static IP on page 6.
Connect an RJ-45 cable to the card and it will receive an IP address from the DHCP server. Contact
the DHCP administrator to obtain the IP address using the Liebert IntelliSlot Unity card’s MAC
address. The MAC address is printed on the card’s faceplate.
If the DHCP administrator is not available or there is no way of
determining the IP address assigned by the DHCP server, use a
computer with a direct Ethernet connection to the Liebert
IntelliSlot Unity card, and the Autoconfiguration IPv4 Address
convention described in 2.1.2 - Connect an Ethernet Cable to
access the card’s Web page and configure the card. To see the card’s
last DHCP-assigned IP address, click on the Unity Tab, then on
the left side menu select Support > Active Networking. The
table of information will show the last IP address assigned by the
DHCP server. The card may retain that IP address when it
reconnects to the DHCP network because most DHCP systems
reuse the same IP address for the same device.
5Liebert
®
IntelliSlot™ Unity™ Card
Installation
Last
DHCP
Address
Support>Active Networking
Unity Tab
Static IP
To assign a static IP address, use the Ethernet connection to configure the card. Proceed to 2.1.2 Connect an Ethernet Cable and 2.2 - Change User Names and Passwords Immediately.
2.1.2Connect an Ethernet Cable
1. Connect a computer running a Microsoft Windows operating system (Microsoft Windows® XP with
SP2 [64-bit] or SP3 [32-bit] or later) to the card by plugging a network cable into the RJ-45 port on
the computer and the Liebert IntelliSlot Unity card.
2. Autoconfiguration, which is normally enabled on computers running Microsoft Windows
operating systems, will automatically negotiate the communication settings. This takes about one
minute.
NOTE
If the computer does not automatically connect, verify that autoconfiguration is enabled by:
Open the Command Prompt window from the computer’s Start menu.
Enter ipconfig/all to verify that Autoconfiguration is enabled on the computer and that an
Autoconfiguration IPv4 Address has been assigned: Enabled = Yes (see Figure 2). An
Autoconfiguration IPv4 Address begins with 169.254.)
3. If the Ethernet adapter being used to attach to the card does not show an Autoconfiguration IPv4
Address, open a new Command Prompt and type ipconfig/renew and press Enter. This forces the
computer to acquire an Autoconfiguration IPv4 Address.
4. When the computer has an Autoconfiguration IPv4 Address, open a browser window on the
computer and type 169.254.24.7 (the card’s default Autoconfiguration IPv4 Address) in the URL
address field. The card’s Web page will appear.
Figure 2Command prompt access
Liebert® IntelliSlot™ Unity™ Card6
2.1.3Connect an RS-485 Serial Cable
485
+-
Wires
Screws
For Building Management Systems using serial network connections, an RS-485 serial cable
connection will be used.
Liebert IntelliSlot Unity cards come with an Adapter RJ-45-2POS Terminal Block. The adapter has
two screw terminals to attach the ends of a RS-485 cable for communicating to a building
management system.
1. Find the serial cable from the building management system. If it already has an RJ-45 connector
on the end, determine whether it uses the same pinout as the Liebert IntelliSlot Unity card’s
connector. If the pinout is the same as the Liebert IntelliSlot Unity card connector’s pinout, skip
to Step 6.
2. Strip the ends of the positive (typically red) and negative (typically
black) leads on the RS-485 cable so that enough bare wire is exposed for
connection, about 1/4" (6mm).
NOTE
No bare wire should be exposed when the connection is completed.
3. Position the adapter so the side with the positive and negative marks is
face up. The small markings are on the same side as the screw heads,
as shown at right.
4. Loosen the screw to the positive terminal and insert the red wire far
enough to insert the bare wires into the terminal block under the screw, then tighten the screw.
Be careful not to break the wires.
5. Repeat Step 3 with the negative terminal and the black wire.
6. Plug the cable into the 485 RJ-45 port on the Liebert IntelliSlot Unity card.
Installation
2.2Change User Names and Passwords Immediately
Emerson recommends changing the administrative user name and password immediately to
safeguard protected configuration and control areas of the Liebert IntelliSlot Unity card.
The user name and password are set at the factory; each is Liebert (case-sensitive). All printable
characters are valid except \ : ’ < > ~ ? " #
A general user name and password are also set at the factory: User and User (case-sensitive). This
may be left at the factory default or changed. The general user has access only to non-protected
configuration and control areas of the Liebert IntelliSlot Unity card.
To change the default user names:
1. Select the Unity Tab > Configuration > User Settings.
2. Click the Edit button and enter the factory-set user name (Liebert) and password (Liebert).
3. Click OK.
4. Enter a new administrator user name and password.
5. Re-enter the administrator password to confirm it.
Optional General User Name Change
6. Enter a new general user name and password.
7. Re-enter the general user’s password to confirm it.
8. Click the Save button to confirm the changes or click Cancel to discard them.
NOTE
Record the new user names and passwords and save them in a secure place where they can be
found if forgotten.
7Liebert
®
IntelliSlot™ Unity™ Card
Figure 3Change administrator and general user names and passwords
Administrator User
Name and Password
General User Name
and Password
2.3Configure the Card
The Liebert IntelliSlot Unity card requires minor configuration, such as choosing the IP/Web
communication interface, serial RS-485 communication interface, or both. The default for IP/Web
communication is IPv4, but this can be changed to IPv6 for greater security; contact your network
administrator to determine whether it is compatible with your network. To choose the communication
interface refer to Figure 4:
2. Enable the protocol, either IPv4 or IPv6, that will be used to communicate with the Liebert
IntelliSlot Unity card and with the Liebert equipment.
a. Click on either IPv4 Settings or IPv6 Settings.
b. Click the Edit button.
c.When prompted with a login display, enter the user name and password (the defaults are
Liebert and Liebert).
d. Put a check mark (✔) in the enabled box.
e.Insert the desired or assigned IP address along with the rest of the required networking
information; contact your system administrator if necessary.
3. Click on Save to confirm the changes or click on Cancel to discard them. The changes will take
effect after the card is restarted.
Liebert® IntelliSlot™ Unity™ Card8
Figure 4Enabling the communication protocol—IPv4 or IPv6
IPv4
Settings
Shown
Edit Dialog Box
Enter the Administrator Name and Password;
defaults are Liebert and Liebert
These should have been changed; see
2.2 - Change User Names and Passwords
Immediately
Edit Button
Save and Cancel Buttons
2.4Installing Multiple Liebert IntelliSlot Unity Cards in a System
More than one Liebert IntelliSlot card may be installed in a system, but circular routes and duplicate
node ID’s must be avoided during installation. The instructions below apply if the second card to be
installed is a Liebert IntelliSlot Unity card. If the second card is not a Liebert IntelliSlot Unity card,
follow instructions in the user manual for that card.
Before beginning installation of a second Liebert IntelliSlot card, verify that the first card functions
properly.
If the first card is a Liebert IntelliSlot card, but not a Liebert IntelliSlot Unity card, and if both cards
connect to the same Ethernet network, then you should disable the router function on the first card.
This will avoid circular routes. Follow instructions in the user manual for the first card.
If the first and second cards are both Liebert IntelliSlot Unity cards, steps must be taken to avoid
duplicate Emerson Protocol MSTP node ID’s. By default, the two cards would use the same node ID,
and one or both cards would report a duplicate node error and fail to communicate with the system.
The default node ID for a Liebert IntelliSlot Unity card is 0, so the second card should use 1 or 2
preferably, or 127 if necessary. Contact your system administrator about the proper node ID for the
second card, then perform the steps below.
1. Open a Web browser and navigate to the second Liebert IntelliSlot Unity card.
3. Click on Edit and enter a password and username, if required.
4. Enter the new node ID.
5. Click Save to confirm the changes or click Cancel to discard them.
6. Restart the card as follows.
a. Select the Unity Tab > Support.
b. Click on Enable.
c.Click on Restart.
Installation
9Liebert
®
IntelliSlot™ Unity™ Card
3.0ENABLE COMMUNICATION PROTOCOLS
The Liebert IntelliSlot Unity card will communicate with equipment and third-party systems over
these protocols:
• BACnet IP
• BACnet MSTP
• Modbus TCP
• Modbus RTU
•SNMP
•YDN23
NOTE
Only two of the protocols may be enabled on one card.
• Only one version of BACnet may be selected, either BACnet IP or BACnet MSTP
• Only one version of Modbus may be selected, either Modbus TCP or Modbus RTU
• Only one of the protocols can use the 485 port; choosing two 485 protocols will cause
conflicts.
NOTE
Some Building Management Systems can be configured to send continuous updates for device
setpoints, usually setting the same value. The BMS should be configured to send, on a
sustained average, no more than two writes per second to the device. This will allow the device
to catch up after a burst of updates when required while allowing other communication with
the device to proceed.
Enable Communication Protocols
3.1Enable Protocols
Protocols may be enabled after a card has been installed and configured. After a protocol is enabled, it
must be configured, which requires opening that protocol’s folder (Unity>Protocols> (desired
protocol).
To enable two communication protocols:
1. Select Unity Tab > Protocols.
2. Click on Edit and enter the administrator user name and password.
3. Put a check mark (✔) in the desired protocols—Only two may be enabled; only one of the two can
use the 485 port.
4. Click Save to confirm the changes or click on Cancel to discard them.
5. Configure the protocols selected. For details, refer to 5.0 - Edit the Liebert IntelliSlot Unity Card Configuration.
6. Restart the card (refer to 5.11 - Configuration—Unity Tab-Support Folder.
a. Select Unity Tab > Support.
b. Enable the commands.
c.Click on Restart.
Liebert® IntelliSlot™ Unity™ Card10
Figure 5Enable protocols; enable commands
Enable
Protocols
Enable Commands
(Support folder)
Enable Communication Protocols
3.1.1Enable Modbus Protocol
Protocols may be enabled after a card has been installed and configured. To enable Modbus protocol:
1. Select Unity Tab > Protocols > Modbus.
2. Click on Edit and enter a User name and password.
3. Select the access level (Read Only or Read/Write).
4. Select the Modbus interface, (Modbus TCP or Modbus RTU).
5. Click Save to confirm the changes or click on Cancel to discard the changes.
6. Configure the Modbus interface chosen; refer to Configure Modbus TCP or Configure Modbus RTU. For additional details, see 5.7 - Protocols Folder—Modbus.
Configure Modbus TCP
1. Select the Unity Tab > Protocols > Modbus TCP.
2. Click on Edit and enter a User name and password if required.
3. Set the Limit Network Access Type by choosing from the drop-down list (Open/Same
Subnet/Trusted IP List). Refer to 5.7 - Protocols Folder—Modbus for additional details.
4. Enter the port to be used by the Modbus Server to listen for and respond to Modbus protocol
requests based on limit Network Access Type setting.
5. Enter the Maximum Client Connection Count.
6. Click Save to confirm the changes or click on Cancel to discard them.
7. Restart the card to confirm the changes.
a. Select Unity Tab > Support.
b. Enable the commands.
c.Click on Restart.
11Liebert® IntelliSlot™ Unity™ Card
Figure 6Modbus TCP-Trusted IP List
... brings up a screen
where this information
may be entered.
Clicking on
one of the
five Trusted
IP List
folders ...
Enable Communication Protocols
Configure Modbus RTU
1. Select the Unity Tab > Protocols > Modbus RTU.
2. Click on Edit and enter a user name and password if required.
3. Set the Node ID and the Baud Rate.
The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
The default baud rate is 9600; 19200 and 38400 also available.
Contact your system administrator if you are uncertain about the settings.
4. Click Save to confirm the changes or click on Cancel to discard them.
5. Restart the card to confirm the changes.
a. Select Unity Tab > Support.
b. Enable the commands.
c.Click on Restart.
Liebert® IntelliSlot™ Unity™ Card12
Figure 7Modbus-RS-485
Node ID must
be unique on
the RS-485 bus
this card is
connected to.
Enable Communication Protocols
3.1.2Enable BACnet Protocol
Contact your system administrator or building management system administrator if you are
uncertain about the settings.
1. Select Unity Tab > Protocols > BACnet.
2. Click on Edit and enter a user name and password if required.
3. Enter the Managed Device Write Access level (Read Only or Read/Write). This determines a
user’s ability to change settings in the Liebert IntelliSlot Unity card.
4. Choose the BACnet interface, either BACnet IP or BACnet MSTP
5. Set the Device Object Instance Number.
6. Set the Device Object Name.
7. Set the APDU Timeout.
8. Set the APDU Retries.
9. Click Save to confirm the changes or click on Cancel to discard them.
10. Configure the BACnet interface chosen; refer to Configure BACnet IP Protocol or Configure BACnet MSTP Protocol. For additional details, see 5.6 - Protocols Folder—BACnet Folder.
13Liebert® IntelliSlot™ Unity™ Card
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.