This manual contains important instructions that should be followed during installation of the
Liebert APM, Liebert Bypass Distribution Cabinet
Read this manual thoroughly, paying special attention to the sections that apply to your installation,
before working with the UPS. Retain this manual for use by installing personnel.
A properly trained and qualified electrical contractor should oversee the installation of the
equipment.
The Liebert APM cannot be put into operation until it is commissioned by the manufacturer or
authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be
covered by the warranty.
The Liebert APM is designed for commercial and industrial uses and cannot be used as life support
equipment.
™
and batteries (where applicable).
WARNING
Risk of moving heavy equipment and electric shock. Can cause equipment damage, injury and
death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg).
Determine unit weight and locate center of gravity symbols before handling the UPS.
Test lift and balance the cabinet before transporting it. Never tilt equipment more
than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In
addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC
and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
Risk of moving electric shock. Can cause equipment damage, injury and death.
As with other types of high power equipment, dangerous voltages are present within the UPS
and battery enclosure even after input power has been disconnected. The risk of contact with
these voltages is minimized as the live component parts are housed behind a metal panel.
Further internal safety screens make the equipment protected to IP20 standards. Never
remove panels or covers or open doors that will expose internal components to contact.
Read and follow all warnings, cautions and safety and operating instructions to avoid serious
injury or death from electric shock. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be
carried out only by trained personnel.
1Liebert
®
APM
™
Page 12
Ground Leakage Currents
!
!
CAUTION
Risk of electric shock from high leakage current. Can cause injury, property damage and
death.
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional
pulses (Class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess
moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system and the internal batteries (internal batteries accommodated
by 45kVA frame only). Observe all safety precautions in this manual before handling or
installing the UPS system as well as during all maintenance procedures. Observe all battery
safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only
test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making
contact or using tools. Even when the power is turned Off, dangerously high electric charges
may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service
personnel and test equipment should be standing on rubber mats. The service personnel
should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.
Liebert® APM
NOTICE
Risk of improper ground connection. Can cause equipment damage.
Ground connection is essential before connecting the input supply. This equipment must be
grounded in accordance with local electrical codes. Maximum load must not exceed that
shown on the UPS rating label.
NOTICE
Risk of improper improper electromagnetic shielding. Can cause radio communication
interference.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. This unit is not designed for use in a residential area.
Operation of this unit in a residential area may cause harmful interference that the user is
solely responsible for correcting.
™
2
Page 13
Battery Cabinet Precautions
!
!
The following warning applies to all battery cabinets supplied with UPS systems. Additional
warnings and cautions applicable to battery cabinets may be found in 5.0 - Battery Installation.
WARNING
Risk of improper handling. Can cause injury, property damage and death.
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
Battery Hazards
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment.
Batteries are always live. Battery terminal voltage will exceed 300VDC and is potentially
lethal.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns.
Batteries should be installed, serviced and replaced only by properly trained and qualified
service personnel trained in safe battery handling methods and who have the correct PPE
(Personal Protection Equipment) and tools.
The following precautions should be observed when working with the batteries:
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and boots.
• When replacing batteries, replace them with the same type and number of batteries or battery packs.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
• Never lay metal objects of any type on top of the batteries.
• Disconnect the charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a
container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large
amounts of water.
3Liebert
®
APM
™
Page 14
GLOSSARYOF SYMBOLS
!
PbH2SO4
-
+
R
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
AC voltage
Equipment grounding conductor
Bonded to ground
Liebert® APM
™
4
Page 15
1.0INTRODUCTION
!
!
The Liebert APM UPS is a transformer-free, hardware-scalable, online uninterruptible power system
with 208/120V input and 208/120V output capability. The Liebert APM can operate with either a 50
or 60Hz input and provide a matching output frequency conversion. The rack-mounted 15kVA/kW
modules allow scaling the UPS’s capacity in 15kVA increments from 15kVA to a maximum of 90kVA
in a single frame.
Optional transformers are available to add 208V Isolation or 480V or 600V input capability to the
Liebert APM in both the UPS, 90kVA/kW frame only, or the Bypass Distribution Cabinet (BDC) in
either the 45kVA/kW or the 90kVA/kW frame.
The Liebert APM UPS is a SmartAisle
approach.
The Liebert APM provides continuous, high-quality AC power to business-critical equipment, such as
telecommunications and data processing equipment. The Liebert APM supplies power free of the
disturbances and variations in voltage and frequency common to utility power, which is subject to
brownouts, blackouts, surges and sags.
The Liebert APM utilizes the latest in high-frequency, double-conversion pulse width modulation
(PWM) technology and fully digital controls to enhance its reliability and increase the ease of use.
Two frame sizes are available: 45kVA/kW and 90kVA/kW. The 45kVA/kW frame is designed to accept
internal batteries; the 90kVA/kW frame does not. The 90kVA frame is, however, designed to accept
Internal Transformers and a four-breaker bypass.
Introduction
™
technology, appropriate for use with the SmartAisle design
Output Voltage Adjustment
This feature allows a Liebert Customer Engineer to adjust the output voltage over a range of -5% to
+16% of nominal. This permits compensation for any IR drop when the UPS is a significant distance
from the protected load. Output voltage adjustment can optimize the UPS output voltage for loads
that operate more efficiently at a UPS output voltage different from the Liebert APM’s standard
output voltage.
1.1Battery Maintenance
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
These maintenance procedures will expose hazardous live parts. Refer servicing to properly
trained and qualified personnel working in accordance with applicable regulations as well as
with manufacturers’ specifications.
1.1.1Battery Safety Precautions
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and
recycled or discarded in accordance with federal, state and local regulations. Because lead is a
toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is toxic.
®
5Liebert
APM
™
Page 16
Introduction
!
!
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If it is grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and
maintenance.
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition, the
electrical connections must be protected against accidental short circuits which can cause sparks. The
following procedures should be followed:
• DO NOT SMOKE when near batteries.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching batteries by first touching a grounded metal
surface.
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the jars in
place on the shelves. This will limit accidental movement of the jars and connectors should the
cabinet ever need to be repositioned or relocated.
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery
and terminal voltages, specific gravity and connection resistance should be made. Strictly follow the
procedures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.
Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although
maintenance of electrolyte levels is not required, visual inspections and checks of battery voltage and
connection resistance should be made.
NOTICE
Risk of equipment damage. Batteries should be cleaned with a dry cloth or a cloth lightly
moistened with water. Do not use cleaners on the batteries. Solvents can make the battery
cases brittle.
Because individual battery characteristics are not identical and may change over time, the UPS
module is equipped with circuitry to equalize battery cell voltages. This circuit increases charging
voltage to maintain flooded type battery cells at full capacity.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries, such as those in
Liebert Battery Cabinets. Refer to the battery manufacturer’s manual, available on the
manufacturer’s Web site, for specific information about equalize charging.
Liebert® APM
™
6
Page 17
Introduction
Matching Battery Cabinets—Optional
Although the individual battery cells are sealed (valve-regulated) and require only minimal
maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks
should be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS
operating, measure and record battery float voltage. With the DC circuit breaker open, measure and
record the nominal (open circuit) voltage. Both these measurements should be made across the final
positive and negative terminal lugs. Compare these values with those shown below. The recorded
nominal voltage should be no less than the value shown; while the recorded float voltage should be
within the range shown. If a discrepancy is found, contact Liebert
Table 1Battery voltage, nominal and float
Battery Voltage, VDC
Nominal/
Number of Cells
144288324
Open CellFloat
Power Connections: Check for corrosion and connection integrity. Inspect wiring for discolored or
cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 2.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and
tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more
than the retorque value. Table 2 shows battery retorque values.
If the system uses a different model battery, contact Liebert
Services.
Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
Other DC Sources
If the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the DC source as recommended in the DC source manufacturer’s maintenance
manual, available on the manufacturer’s Web site.
7Liebert
®
APM
™
Page 18
2.0INSTALLATION
!
This section describes the Liebert APM’s environmental requirements and mechanical considerations
that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because each site is unique, this section presents a guide to general procedures and practices that
should be observed by the installing engineer, rather than step-by-step installation instructions.
WARNING
Risk of electric shock. Can cause injury, property damage and death.
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately
with large amounts of water.
Installation
NOTICE
Risk of improper installation. Can cause equipment damage.
Do not apply electrical power to the UPS equipment before the commissioning engineer
arrives at the installation site.
The UPS must be installed by a properly trained and qualified engineer in accordance with
the information contained in this chapter. All the equipment not referred to in this manual is
shipped with details of its own mechanical and electrical installation information.
NOTE
Three-phase, four-wire input power is required.
NOTE
Input power must be supplied to the Liebert APM from a properly grounded Wye or Delta
source. The Liebert APM is not for use with impedance grounded systems, corner-grounded
systems or high-leg Delta systems. For these applications, an isolation transformer must be
installed between the input power and the Liebert APM.
Liebert® APM
™
8
Page 19
2.1Initial Inspections
!
!
1. While the Liebert APM and ancillary cabinets are still on the truck, inspect the equipment and
shipping container for any signs of damage or mishandling. Do not attempt to install the system if
damage is apparent. If any damage is noted, file a damage claim with the shipping agency
immediately and contact Liebert Services at 1-800-LIEBERT to inform them of the damage claim
and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and your local Emerson representative immediately.
3. Check the product label on the back of front door and confirm the contents match the UPS model,
capacity and main parameters that were ordered.
2.1.1Storing for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the Liebert APM from excessive moisture (see 11.2 - UPS Environmental).
CAUTION
If the UPS must remain disconnected from power for more than six (6) months, the batteries
(if so equipped) must be recharged before use. To charge the batteries, the unit must be
connected to utility power and started up—the charger operates only while the Liebert APM
is operating.
Installation
CAUTION
When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS, the
battery—not the UPS—dictates the designed maximum ambient temperature.
2.2Preliminary Checks
2.2.1Identification
The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.
2.3UPS Location
2.3.1Positioning the UPS
Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
®
9Liebert
APM
™
Page 20
2.3.2Environmental Considerations
!
!
Before installing the Liebert APM, verify that the UPS room satisfies the environmental conditions
stipulated in 11.2 - UPS Environmental, paying particular attention to the ambient temperature
and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating
temperature within the range of 74-80°F, (23-27°C).
The Liebert APM is cooled by internal fans. Cooling air enters the unit through the front of the unit
and is exhausted out the back. To permit proper air flow and prevent overheating, do NOT block or
cover the ventilation openings or blow air down onto the unit. The UPS requires 24 in. (610mm)
ventilation clearance above the unit and 12" (305mm) behind the UPS.
See Table 46 for details on heat dissipation.
Battery Location
Temperature is a major factor in determining battery life and capacity. Battery manufacturers
recommend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce
battery life; temperatures below this reduces battery capacityv. In a typical installation, battery
temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed
where there are no main heat sources or air inlets to prevent portions of batteries from being either
much warmer or much cooler than other parts of the batteries.
Installation
2.4Considerations in Moving the Liebert APM
Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any
handling equipment. See Table 33 for weights of various units.
The Liebert APM may be rolled on its casters for short distances only. For longer distances, move the
UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
The optional battery cabinets should be moved with a forklift or similar equipment.
WARNING
Risk of moving heavy unit. Can cause property damage, injury and death.
Ensure that any equipment that will be used to move the Liebert APM has sufficient lifting
capacity. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg). See Table 33
for details.
The UPS presents a tipping hazard. Do not tilt the Liebert APM more than 15 degrees from
vertical.
The UPS is fitted with casters—Take care to prevent movement when unbolting the
equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are
available when taking the Liebert APM off its shipping pallet.
WARNING
Risk of heavy unit tipping over while being moved. Can cause property damage, injury and
death.
The casters are strong enough for movement across even surfaces only. Casters may fail if
they are subjected to shock loading, such as being dropped or rolled over holes in the floor or
obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging
the equipment.
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum. For further information, see Battery Cabinet Precautions on page 3.
Final Positioning
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the
UPS will remain stationary and stable (see 7.0 - Installation Drawings).
The Liebert APM and its auxiliary cabinets must be installed on a concrete or equivalent, nonresilient floor.
Liebert® APM
™
10
Page 21
2.5Mechanical Considerations
!
The Liebert APM is constructed with a steel frame and removable panels. Top and side panels are
secured to the chassis by screws. The doors may be opened for access to power connections bars,
auxiliary terminals blocks and power switches.
The UPS comes with an Operator Control Panel that provides basic operational status and alarm
information. The cabinet houses both the power components and the internal batteries. Cooling is
provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the
UPS from moving once it has been moved to its final position.
WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and
death.
The Liebert BDC
Improper lifting may cause the cabinets to fall, causing personal injury or death and
equipment damage.
Emerson recommends lifting the units with one of the following methods:
• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit,
attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.
• Placing suitable straps on the Liebert BDC
the unit to be lifted.
™
and battery cabinets must be properly prepared and secured for lifting.
Installation
™
or battery cabinet. The straps must go under
2.5.1Clearances
There are no ventilation grilles on the sides of the UPS. The sides must be accessible during
installation. After installation, the unit must have a clearance of 12 in. (305mm) in the rear to permit
adequate circulation of air exhausted from the UPS. The Top Fan option eliminates the 12" (305mm)
rear clearance requirement, but it increases the Liebert APM’s height by 7.63" (194mm).
To enable routine tightening of power terminations within the UPS, make sure there is sufficient
clearance in front of the Liebert APM to permit free passage of personnel with the door fully opened.
Leave a minimum of 24 in. (610mm) between the top of the UPS frame and the ceiling to permit
adequate air circulation above the unit. Emerson recommends against using air conditioning or other
systems that blow air onto the top of the unit.
2.5.2Floor Installation
If the Liebert APM, Liebert BDC or battery cabinet is to be placed on a raised floor, the UPS should be
mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in
Figures 49, 55 or 58 to design this pedestal.
2.5.3Cable Entry
Cables can enter the Liebert APM, Liebert BDC and battery cabinets from the top or bottom through
removable metal plates.
Some plates have factory-punched holes and others are designed to allow the personnel to punch
holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be
reattached to the UPS. The conduit size and wiring method must be in accordance with all local,
regional and national codes and regulations, including NEC ANSI/NFPA 70.
The UPS must be accessible from the right side to allow personnel to complete the cable connections
and make necessary adjustments. After installation is complete, the Liebert APM may be serviced
from the front.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection
at the output of the UPS.
11Liebert® APM
™
Page 22
2.5.4Special Considerations for Parallel Systems
1. Consider the grounding configuration of the UPS system before finalizing module placement. For
optimal ground performance, the Liebert APM modules should be close together. See 3.2.6 - Cabling Guidelines.
2. For optimal load-sharing performance, the UPS bypass input cables and output cables should be
approximately the same length, ±10 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring
between UPS modules and the paralleling cabinet.
Refer to 4.0 - Parallel System and LBS System Installation for further information on
installing a parallel system.
2.5.5Special Considerations for 1+N Parallel Systems
Consider the grounding configuration of the UPS system before finalizing module placement. See
3.2.6 - Cabling Guidelines.
Emerson recommends matching the impedance in the bypass path of paralleled systems as closely as
possible.
The impedance mismatch can be minimized by controlling the wiring length of each unit. The design
and the layout of the UPS system and associated panels and cabling should be examined closely to
ensure that cable lengths and impedances are closely matched. The Liebert 1+N UPS module is
supplied with a sharing reactor to minimize the impact of cable impedance mismatch. The cabling
impedance must be carefully controlled to ensure good bypass current sharing.
Installation
For Liebert APM systems, the cabling impedances must be within 10% from maximum to minimum.
If the cabling impedances must be greater than 10%, contact your Emerson representative to
calculate whether the system will result in an overload condition when operating on bypass.
When bringing the 1+N system online for the first time or after removing one unit, Emerson
recommends checking the bypass current mismatch. To check the bypass current mismatch:
1. Place a load on the bypass of each UPS module.
2. View the output current of each unit.
The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch
is greater than 10%, the bypass impedances must be balanced or the load must be limited to less than
the maximum rating.
2.645kVA and 90kVA UPS Frames—Auxiliary Cabinets
The 45kVA frame consists of a single cabinet housing the UPS components and the internal battery
string. The 90kVA frame, also a single cabinet, does not accommodate internal batteries, but does
provide for an internal four-breaker bypass or an internal transformer. The internal transformers are
available with 480V:208V; 600V:208V; or 208V:208V isolation input primaries.
Optional battery cabinets are available for each Liebert APM model to provide extended run time.
Each battery cabinet houses a single string of batteries per cabinet that operate in parallel with the
Liebert APM’s internal batteries (45kVA frame only). The battery cabinets are designed to be bolted
to the left side of the UPS (see Figure 1). Refer to 5.4 - External Battery Cabinet Installation for
details.
Optional Liebert BDC
provide an external wraparound maintenance bypass switch for servicing the UPS.
Liebert BDCs are designed to be bolted to the right side of the UPS (see Figure 1). Refer to 6.4 - Locating the Cabinet for further details.
™
units are available. These cabinets house the components necessary to
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the system design
requirements—e.g., UPS cabinet, External Battery Cabinet and External Bypass Cabinet. All
cabinets used will be the same height and will be designed to be positioned side-by-side to form an
aesthetically appealing equipment suite.
Liebert® APM
™
12
Page 23
2.6.1Optional Cabinets
Liebert
APM
Bypass
Distribution
Cabinet
Bypass
Distribution
Cabinet
Liebert
APM
Battery
Cabinet
Battery
Cabinet
Liebert
APM
Battery
Cabinet
Liebert APM connected only to Liebert BDC
(BDC must be on right side of the Liebert APM)
Liebert APM connected to Liebert BDC and Battery Cabinets
(BDC must be on right side of the Liebert APM)
(Battery Cabinets must be on the left side of the Liebert APM)
ALL UNITS VIEWED FROM ABOVE
Liebert APM connected to Battery Cabinet (Battery Cabinets
must be on the left side of the Liebert APM)
If the Liebert APM installation includes a Liebert BDC, the UPS must be positioned to allow the
Liebert BDC to be bolted to right side of the Liebert APM (see Figure 1).
The Liebert BDC must be cabled and bolted to the Liebert APM before the UPS and bypass cabinet
are moved into their final position. Connect the input wiring to the Liebert BDC ONLY after the units
are connected and positioned.
Battery cabinets may be bolted only to the left side of the Liebert APM; see Figure 1.
Figure 1Cabinet arrangement
Installation
2.7Optional Seismic Brackets
Optional seismic mounting brackets to anchor the Liebert APM, Liebert BDC™ and battery cabinet
to the floor are available. Refer to Figure 61 for mounting details.
13Liebert® APM
™
Page 24
2.8Liebert FlexPower™ Assembly
Run LED
Battery Start Button
Ready Switch
Fault LED
DIP Switches
Input/output dry contact and EPO/BCB/MBC interface
J1
J4J7
J10
MFP_O
MFP_S
MFP_C
J11
INPUT_2
INPUT_1
OUT
GND
J8
+12V
BAT-IN
BAT-OUT
GND
J5
PARA
J2
BCB_IN
DRIVER
GND
ONLINE
Q2BP
Q3BP
EXT-OUT
GND
J9J6
J3
PARA
BFP_O
BFP_S
BFP_C
J12
INV_O
INV_S
INV_C
BAT_GND
ENV_DET
BAT_READY
+12V
+12V
EPO-NC
+12V
EPO-NO
LBS
MONITOR
RS485-2RS485-1
RS232
INTELLISLOT3INTELLISLOT2INTELLISLOT1
J1 ~ J3 port can’t connect to phone!
J10
J7
J5
J6
J8
J9
RS-232
Liebert IntelliSlot
Bays 1, 2, 3
RS-485
J4
J11
J12
Monitor
J3
J1
J2
Figure 2Liebert FlexPower assembly indicators and controls
The Battery start button allows starting of UPS on battery; refer to 10.3 - UPS Battery Start.
The Run LED is illuminated Green when the Liebert FlexPower assembly is operating normally.
The Fault LED will illuminate red when the Liebert FlexPower assembly has a problem.
Table 3LED indications
LED StatusIndication
Run LED (Green)
Flashing GreenThe inverter is starting, but has no output yet.
Constant GreenThe inverter has started to supply power.
OFFThe inverter has not started up.
Fault LED (Red)
Auxiliary power failure (15V or 24V), rectifier overtemperature, rectifier failure (including battery
SCR short circuit), battery converter failure, soft start failure, main circuit back feed, abnormal
Constant Red
Flashing Red
input current, inverter failure, output short circuit, bypass SCR short circuit fault, inverter relay
short circuit fault, abnormal bus voltage under non-sleep mode, module not ready, module ID
out of range and duplicated module ID.
Charger failure, abnormal main circuit voltage, abnormal main circuit frequency, main circuit
undervoltage, main circuit reverse phase, battery unavailable, reverse battery, input zero-loss,
current sharing failure, module overload, inverter relay disconnection fault, bypass SCR
disconnection fault and input fuse blown.
Installation
OFFNo above failures or alarms.
2.9Static Bypass Assembly
Figure 3Static bypass assembly connections
The Static bypass assembly has three Liebert IntelliSlot interface card bays and connections for
ancillary cabinets (Liebert BDC and battery) and for options.
Liebert® APM
™
14
Page 25
3.0ELECTRICAL CONNECTIONS—UPS
!
The UPS requires both power and control cabling once it has been mechanically installed. All control
cables must run separate from power cables in metal conduits or metal ducts that are electrically
bonded to the metalwork of the cabinets to which they are connected.
WARNING
Risk of electric shock. Can cause property damage, injury and death.
Before connecting input power to the Liebert APM, ensure that you are aware of the location
and operation of the overcurrent protection devices that connect the UPS input/bypass supply
to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before
installing cables or making any electrical connections.
3.1Power Cabling
3.1.1Cable Rating
The main factors affecting the choice and size of cable are voltage, current (also taking into account
overcurrent), room temperature and conditions of installation of the cable. Refer to ANSI/NFPA 70.
The power cables of the system must be sized with respect to the following description:
Electrical Connections—UPS
• UPS input cables - The UPS input cables must be sized for the maximum input current,
including the maximum battery recharge current, given in Table 41, with respect to the unit
rating and the input AC voltage.
• UPS bypass and output cables - The bypass and output cables must be sized for the nominal
output current, given in Table 41, with respect to the unit rating and the output AC voltage.
• Battery cables - Each UPS unit has its own internal batteries factory-wired. If connecting an
external battery cabinet, the battery cables must be sized for the battery discharge current at the
end-of-discharge voltage, as given in Table 41, with respect to the unit rating.
NOTE
Table 41 gives nominal currents for determining the size of UPS power cables. Other
important factors to consider include cable route length and coordination with protective
devices.
The power cables can be sized to suit the UPS unit rating according to Table 41.
Lug Size and Torque Requirements
Refer to Table 41 for lug size and torque requirements and to Table 18 and Figure 60.
3.2External Protective Devices
For safety concerns, it is necessary to install external circuit breakers or other protective devices for
the input AC supply of the UPS system. This section provides generic practical information for
qualified installation engineers. The installation engineers should be knowledgeable about regulatory
wiring standards and the equipment to be installed.
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection
in accordance with NEC ANSI/NFPA 70.
15Liebert® APM
™
Page 26
3.2.1Rectifier and Bypass Input Supply of the UPS
Overcurrents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering
the power cable current-carrying capacity and overload capacity of the system. Generally, the
magnetic circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the nominal
current listed in Table 41 is recommended.
Split bypass: In case a split bypass is used, separate protective devices should be installed for the
rectifier input and bypass input in the incoming mains distribution panel.
NOTE
The rectifier input and bypass input must use the same neutral line.
For an IT power network system, a 4-pole protective device must be installed on the external
input distribution and external output distribution of the UPS.
Earth Leakage, RCD Devices
Any residual current detector (RCD) installed upstream of the UPS input supply:
• Must be sensitive to DC unidirectional pulses (Class A)
• Must be insensitive to transient current pulses, and
• Must have an average sensitivity, adjustable between 0.3 and 1A.
To avoid false alarms, earth leakage monitoring devices when used in systems with split bypass input
or when used in paralleled UPS configurations, must be located upstream of the common neutral
sinking point. Alternatively, the device must monitor the combined four-wire rectifier and split
bypass input currents.
Electrical Connections—UPS
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than
3.5mA and less than 300mA. Liebert recommends verifying the selectivity with all other differential
devices both upstream of the input distribution board and downstream (toward the load).
3.2.2External Battery
The DC-compatible circuit breaker provides overcurrent protection for UPS system and battery,
which is provided by the external battery cabinet.
3.2.3UPS Output
If an external distribution panel is used for load distribution, the selection of protective devices must
provide discrimination with those that are used at the input to the UPS (see Table 47).
Liebert® APM
™
16
Page 27
3.2.4UPS Input Configuration
By default, the Liebert APM ships with internal links installed between the bypass input and main
(rectifier) input (single input configuration see Figure 84).
Figure 4 shows the Liebert APM in a split bypass (single source dual-input) configuration. In this
configuration, the static bypass and the maintenance bypass lines are supplied by the same source
using separate feeds. Both feeds must be protected externally with properly sized protective devices.
To wire the Liebert APM as a single source dual-input UPS, remove the links and wire the bypass
feed to the bypass busbars, then wire the main feed to the main busbars (see Figure 8).
Figure 4Single UPS block diagram—dual input single source configuration
Bypass Distribution Cabinet
Electrical Connections—UPS
* Bypass
AC Input
BIB
MBB
4-Wire + GND
Static Bypass
* Rectifier
AC Input
4-Wire + GND
See Note 7
UPS Cabinet
Battery
NOTES
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full
capacity neutral conductor is recommended. Grounding
conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run
in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole,
400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.
Figure 5 shows the Liebert APM in a split bypass (single-source, dual-input) configuration using two
transformers. One transformer is inside the Bypass Distribution Cabinet and the other inside the
UPS.
In this configuration, the static bypass and the maintenance bypass lines are supplied by the same
source using separate feeds. Both feeds must be protected externally with properly sized protective
devices.
Figure 6 shows the control wiring for the dual input transformer configuration.
Figure 5Liebert APM in a split bypass configuration
Electrical Connections—UPS
Liebert® APM
™
18
Page 29
Figure 6Control wiring for the dual input transformer configuration
UAM04047
Rev. 0
NOTES
1. Customer-furnished electrode conductor to be installed in
accordance with national and local electrical codes.
2. See installation manual for additional connection information.
3. Optional 54 pole, 225A for 45kVA frame only or optional 54 pole
400A for 90kVA frame only.
4. Transformer available: 208V, 220V, 480V and 600V input.
5. Overcurrent protection is based on 80% rated devices.
6. Ensure that the jumper bars between input and rectifier input
are removed before starting the unit for the first time.
7. See Drawing UAM02022.
SKRU - SOLENOID
KEY RELEASE UNIT
KO - KEY OPERATOR
Field-Supplied Wiring
Factory-Supplied Wiring
* Customer
must supply
shunt trip to
rectifier
input breaker
with 120V coil
RIB
Rect.
Rect. Input
Input
Input Neutral
GRD
ØAØBØC
ØA
Ø to
ØB
ØC
Utility
Customer
Main Input
Busbars
To
Bypass
Input
MBB
W06
W04
W05
Kirk
Key K1
Kirk
Key K2
Liebert
APM UPS
UPS AC
Output
Bypass Input
N
A
B
C
N
PE
A
B
C
1
W88
W89
W90
W91
W85
W84
W86
W08
W09
W07
BIB
MIB
W87
W83
Main Ground Busbar
Ground
To Unit
Frame
Output
Ground
Output
Neutral
AC Output
Ground
To Unit
Frame
2 Fuses, 2A
Inner Door
AC 120V
AC 120V
SKRU
K0
(Optional)
54 Pole
See Note 3
Bypass Distribution Cabinet
TB1
See Note 1
4
4
4
4
3
3
3
3
3
3
112
2
2
Electrical Connections—UPS
The external maintenance bypass is available with a 480V, 600V or 208V optional internal
transformer. Each UPS frame size (45kVA or 90 kVA) is available with a 480V, 600V or 208V optional
internal transformer. Internal batteries are not available for a 45kVA frame that has an the internal
transformer.
19Liebert® APM
™
Page 30
3.2.6Cabling Guidelines
The following are guidelines only and are superseded by local regulations and codes of practice where
applicable. Use wiring rated at 75°C or greater.
1. Take special care when determining the size of the neutral cable, as current circulating on the
neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the
values in 11.4 - UPS Electrical Characteristics.
2. The ground conductor should be sized according to such factors as the fault rating, cable lengths
and type of protection. The ground cable connecting the UPS to the main ground system must
follow the most direct route possible. Control wiring and power wiring must be run in separate
conduit. Output and input cables must be run in separate conduit.
3. Consider using paralleled smaller cables for heavy currents—this can ease installation.
4. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current
ratings in Table 43. For terminal connection sizing, see Tables 41 through 43.
5. In most installations, the load equipment is connected to a distribution network of individually
protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When
this is the case, the UPS output cables can be rated to suit the individual distribution network
demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
6. When laying power cables, do not form coils; this will help avoid increasing formation of
electromagnetic interference.
Electrical Connections—UPS
NOTE
Right-side access may be required when making power connections. Cable connections should
be made before a cabinet is attached to the right side of the Liebert APM or before the UPS is
placed where another obstruction, such as a wall, is against the Liebert APM’s right side.
3.2.7Cable Connections
The rectifier input, bypass output and battery are easily accessible from the right side of the unit for
installation. All require lug type terminations. They are connected to busbars on the right side of the
Liebert APM, as shown in Figures 7 and 8. These busbars are accessible when the right side panel is
removed.
NOTICE
Risk of improper installation. Can cause equipment damage.
When wiring a single-input only system, connect only the power wiring to the input busbars.
Liebert® APM
™
20
Page 31
Figure 7Input busbars—Liebert APM 45kVA frame
1.65"
(42mm)
1.65"
(42mm)
1.6" (41mm)
1.75" (44mm)
1.75" (44mm)
(Typ.)
1.52" (39mm)
(Typ.)
3.54" (90mm) (Typ.)
ø
.55" (14mm)
4 places
ø
.50" (13mm)
2 places
.8" (20mm)
.8" (20mm)
.7" (18mm)
DETAIL D
Top View DC Busbars
DETAIL C
Top View Ground
ø
.50" (13mm)
Typ.
Main Input Busbars
Same for Bypass and
Output Busbars
Main Input
Busbars
1.75" (44mm) Typ.
DETAIL A
DETAIL B
DC Busbars
See Detail A
Ground
See Detail A
See
Detail B
37.5" (953mm)
31.5" (800mm)
BOTTOM VIEW
TOP VIEW
See
Detail D
78.7"
(2000mm)
Bypass
Busbars
Output
Busbars
2.36"
(60mm)
Typ. 2
Places
Battery
Breaker
2.2" (56mm)
Typ. 6 Places
1.97" (50mm)
Typ. 3 Places
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.
FRONT VIEW
Door Removed
RIGHT SIDE VIEW
Panel Removed
Links for Main
to Bypass
(Single Input Only)
Electrical Connections—UPS
21Liebert® APM
™
Page 32
Figure 8Input busbars—Liebert APM 90kVA frame
UAM02021
Rev. 3
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
Electrical Connections—UPS
Liebert® APM
™
22
Page 33
Figure 9Liebert BDC
UAM06020A
Rev. 2
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run
in separate conduits.
3. Only copper cables are recommended.
4. All wiring is to be in accordance with national
and local electrical codes.
5. If bypass distribution cabinet is attached
to the UPS, Emerson will supply the
interconnection cables.
6. See UAM06020B, Pg. 2 of 2.
BOTTOM VIEW
TOP VIEW
LEFT SIDE VIEW
Panel Removed
RIGHT SIDE VIEW
Panel Removed
FRONT VIEW
Door Removed
23.6" (600mm)
LDB
MIB
MBB
BIB
78.7"
(2000mm)
37.5" (953mm)
System
Input
Bus
Input/Output
Neutral Bus
Ground
Bus
See Detail A and
Isometric View
Detail B, Pg. 2
(Note 6)
Electrical Connections—UPS
23Liebert® APM
™
Page 34
Figure 10 Busbars—Liebert BDC
Neutral Bus
5" x 8.9"
(127 x 227mm)
Ground Bus
5" x 4"
(127 x 102mm)
All
Busbars
Input/Outout
Bus Typical
1.5" x 8.9"
(38 x 227mm)
Ø .56"
(14mm)
Typical
Ø .56"
(14mm)
Typical
Ø .56"
(14mm)
Typical
1.75"
(44.5mm)
Typical
Ø .44"
(11mm)
Typical
UPS Bus
Ø .44"
(11mm)
Typical
Ø .44"
(11mm)
Typical
Input
Breaker
Input
Ground
Bus
System
Input
Busbar
Located at
Rear, Typ.
System
Input
Connections
Neutral
Input/Output
Connections
System
Input Bus
See Detail B
1.38" (35mm)
1.38" (35mm)
1.38" (35mm)
1.38" (35mm)
2.44" (62mm)
2.44" (62mm)
DETAIL A
DETAIL B
Iso View Front Left
with Corner Post Not Shown
UAM06020B
Rev. 2
1. See UAM06020A, Pg. 1 of 2
(2) 225A or 400A panelboard.
2. See UAM06021A, Pg. 1 of 2
(2) 225A or (2) 150A subfeed breakers.
3. See UAM06022A, Pg. 1 of 2
without distribution.
Electrical Connections—UPS
Liebert® APM
™
24
Page 35
Figure 11 Busbars—External 600mm battery cabinet
.56" Dia.
(14.3mm)
.44" Dia.
(11.1mm)
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables onlyare recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. If battery cabinet is attached to UPS, Emerson will supply interconnect cables.
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
5. If the battery cabinet is attached to the UPS, Emerson will
supply the interconnect cables.
UAM05022
Rev. 0
Alber Battery
Monitoring
35.4" (900mm)
TOP VIEW
BOTTOM VIEW
78.7"
(2000mm)
.56" Dia.
(14.3mm)
.44" Dia.
(11.1mm)
DETAIL A
See
Detail A
Left Side View
Panel Removed
Front View
Door Removed
Right Side View
Panel Removed
37.5" (953mm)
DC Connection
Busbars
Ground
Bus
3.31"
(84mm)
3.31
"
(84mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.65
"
(42mm)
1.65
"
(42mm)
1.75
"
(45mm)
Electrical Connections—UPS
3.2.8Accessory Fuses and Backfeed Breaker Wiring
Two fuse blocks provide power for the backfeed breakers (standard) and the BDSi (optional). The fuse
blocks are at the lower right of the front of the Liebert APM UPS. Refer to Figure 24 for additional
details. See for fuse holder locations.
The backfeed breaker fuse block provides 120V nominal provided from the UPS output (L-N) and the
fuse is rated for 8 amps. Figure 14 shows the backfeed breaker wiring.
Liebert® APM
The BDSi fuse block provides 208V nominal from the UPS output (L-L) and the fuse is rated at 8A.
The BDSi power wiring is shown in Figures 40 and 66.
™
26
Page 37
Electrical Connections—UPS
BDSi Fuse
Block
(optional)
Backfeed
Breaker
Fuse Block
1. Auxiliary contacts not needed for backfeed breaker operation.
2. A 120V shunt trip coil is required for proper operation.
Dual Input Control Wiring
Upstream Bypass
Input Breaker
Upstream System
Input Breaker
Single Input Control Wiring
Backfeed Breaker
Fuse Block (FH1)
Backfeed Breaker
Fuse Block (FH1)
Upstream Rectifier
Input Breaker
APM Bypass Module
UAM04030
Rev. 3
MX
MX
AUX
AUX
J10
J11
2
C2
C2
C1
C1
2
3
3
N
PH B
J10
23
N
PH B
UHRF3S67X2 (J10, J11)
J10
J11
MX
AUX
J11
2
C2
C1
3
Figure 13 Accessory fuses
Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used
NOTE
Shunt trips are required in upstream breakers to allow backfeed protection to function
properly.
27Liebert® APM
™
Page 38
3.2.9Safety Ground
!
The safety ground busbar is below the neutral input and output busbars as shown in Figure 15
below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in
the system. This ground busbar is then connected to the ground electrode conductor (GEC).
All cabinets and cable conduit should be grounded in accordance with local regulations.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury anddeath.
Failure to follow proper grounding procedures can result in electric shock hazard to personnel
or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces problems caused by electromagnetic interference.
NOTE
The ground and neutral busbars are easily accessible when the right side panel is removed.
Cable connections should be made before a cabinet is attached to the right side of the Liebert
APM or before the UPS is placed where another obstruction, such as a wall, is against the
Liebert APM’s the right side.
Electrical Connections—UPS
Liebert® APM
™
28
Page 39
Figure 15 Ground and neutral busbar connections—45kVA frame busbars
A
1.65"
(42mm)
.8" (20mm)
Top View DC Busbars
DETAIL D
TOP VIEW
1.75" (44mm)
ø .50" (13mm)
2 places
1.6" (41mm)
See
Detail D
1.75" (44mm)
1.65"
(42mm)
3.54" (90mm) (Typ.)
.7" (18mm)
DETAIL C
Top View Ground
BOTTOM VIEW
(Typ.)
1.52" (39mm)
(Typ.)
ø .55" (14mm)
4 places
.8" (20mm)
Electrical Connections—UPS
ø .50" (13mm)
Typ.
Main Input Busbars
Same for Bypass and
Output Busbars
1.75" (44mm) Typ.
78.7"
(2000mm)
31.5" (800mm)
Battery
Breaker
See
Detail B
FRONT VIEW
Door Removed
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.
37.5" (953mm)
RIGHT SIDE VIEW
Panel Removed
DETAIL A
2.2" (56mm)
Typ. 6 Places
1.97" (50mm)
Typ. 3 Places
2.36"
(60mm)
Typ. 2
Places
(Single Input Only)
DETAIL B
Links for Main
to Bypass
Main Input
Busbars
Bypass
Busbars
Ground
See Detail
Output
Busbars
DC Busbars
See Detail A
29Liebert® APM
™
Page 40
Figure 16 Ground and neutral busbar connections—90kVA frame busbars
UAM02021
Rev. 3
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
Electrical Connections—UPS
Liebert® APM
™
30
Page 41
3.2.10 Protective Devices
!
For safety, it is necessary to install circuit breakers in the input AC supply external to the UPS
system. Given that every installation has its own characteristics, this section provides guidelines for
qualified installation engineers with knowledge of operating practices, regulatory standards and the
equipment to be installed.
UPS Rectifier and Bypass Input Supply
Protection from excessive overcurrents and short circuits in power supply input
External overcurrent protection for the AC output circuit is to be provided. See 11.4 - UPS Electrical Characteristics and Table 47 for overload capacity.
A breaker is used for internal battery circuit overcurrent protection. When an external battery
supply is used, overcurrent protection for the battery circuit is to be provided by the customer.
• Dual Input Single Source
When wiring the UPS with dual inputs but with a single input source, the Rectifier input and the
Bypass input must be protected separately. Size the breakers according to the input currents
shown in Table 41.
NOTE
For single or dual input, a 120V shunt trip coil(s) is required when a breaker is supplied by the
customer. See Figures 4 and 5 for details.
Fuses
Electrical Connections—UPS
The Liebert APM’s main input and bypass input busbars are equipped with fuses (six locations; see
Figure 51). The type is Bussman 170M4465, rated at 550A and 700V.
System Output
When using an external distribution panel for load distribution, the output neutral and input neutral
must be separated at the input to the UPS.
3.2.11 Cabling Procedure
CAUTION
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficulties, contact your local Emerson
representative or Liebert Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect
AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground lugs
have been connected (see 3.2.7 - Cable Connections), connect the power cables as described below.
(Study the reference drawing in 7.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the right side panel to gain easier access to the connections busbars.
3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar
located in the middle of the Liebert APM below the Input and Bypass connections. All cabinets in
the UPS system must be connected to the user’s ground connection.
NOTE
The grounding and neutral bonding arrangement must comply with the National Electrical
Code and all applicable local codes.
4. Identify and make power connections with incoming cables according to Steps 5 through 8.
31Liebert® APM
™
Page 42
Electrical Connections—UPS
!
!
Common Input Connections
5. For common bypass and main inputs, connect the AC input supply cables to the UPS input
terminals (A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure
correct phase rotation.
NOTE
For common bypass and main inputs, the AC input cables must be connected to the bypass
terminal (A2-B2-C2-N1) but not the main input terminal (A2-B2-C2).
Split Bypass Connections
6. If a split bypass configuration is used, connect the AC input supply cables to the rectifier input
terminals (A1-B1-C1-N1) and the AC bypass supply cables to the bypass input terminals
(A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure correct phase
rotation.
NOTE
For split bypass operation, ensure that the busbars between bypass and rectifier inputs are
removed. The neutral line of the bypass input must be connected to that of the rectifier input.
Output System Connections—Ensure Correct Phase Rotation
7. Connect the system output cables between the UPS output busbars (A-B-C-N terminals) and the
critical load and tighten the connections to 240lb-in. (27N-m) (M10 bolt).
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
If the load equipment will not be ready to accept power when the commissioning engineer
arrives, ensure that the system output cables are safely isolated.
Internal UPS Battery Connections
The UPS internal batteries will be connected at the factory, EXCEPT the connections between the
shelves and to the breaker.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The DC bus is live when this internal battery connection is made. This connection is to be
performed ONLY by Emerson Network Power
Observe the battery cable polarity. Be sure that the battery connection is made with the correct polarity.
8. Refit all protective covers removed for cable installation.
3.3Control Cables Details
3.3.1Static Bypass Assembly Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
Terminations for these functions are located at the front of the static bypass module. The main
features are:
• Input and output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Liebert IntelliSlot
• Temperature detect interface
®
interface
®
Liebert Services at startup.
Liebert® APM
™
32
Page 43
Figure 17 Static bypass assembly connections to display cabinet and options
Monitor
J4
J8
J5
J12
J11
J10
J4
J9
Operator Control Panel
Battery Cabinet
Bypass Distribution Cabinet
Temp Sensor (optional) and
BCB Control Board
Ground Fault (optional )
Sensor & BCB Control Board
On Generator (optional)
Static
Bypass
Assembly
Mains Backfeed Protection
Bypass Backfeed Protection
LBS
PARA
PARA
J1
J2
J3
J4
J5
J6J9
J8
J7
J10
J11
J12
GND
GND
GND
BAT-OUT
BAT-IN
+12V
GND
OUT
INPUT_2
INPUT_1
EXT-OUT
Q2BP
Q3BP
ONLIN E
BCB_I N
DRIVER
+12V
+12V
EPO-NC
EPO-NC
+12V
BAT -REA DY
BAT-GND
ENV_DB
INV _C
INV_S
INV_O
BFP _C
BFP_O
BFP_S
MFP_C
MFP_S
MFP_O
Input /output dry cont act and EPO /BCB/MBC interface
Terminal block connectors are on the left side of the static bypass assembly.
NOTE
33Liebert® APM
™
Page 44
3.4Dry Contacts
+12V
J9
-
+12V
BAT_READY
ENV_DET
BAT_GND
BAT_OUT
+12V
BAT_IN
J4
GND
GND
EXT_OUT
Q2BP
Q3BP
J5J8
GND
ONLINE
BCB_IN
DRIVER
12V
12V
12V
NOTE: The black square () on each connector indicates Pin 1.
Refer to Figure 18 for the location of connectors J4, J5, J8 and J9.
The UPS provides input dry contacts and output dry contacts on the Auxiliary Terminal Block (ATB).
3.4.1Input Dry Contacts
External input dry contacts are connected via the ATB. Dry contacts are available for environment
detection, battery ground fault detection, etc.
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry
contact terminals produced, and these terminals are on the static bypass assembly. Through software
programming, these signals become active when these contacts connect to +12V to ground (in the
most left side). The cables connected to the monitor board must be separated from power cables.
Moreover, these cables should be double-insulated with a typical cross-section of 0.5 to 1mm
maximum connection length between 82 and 165ft. (25-50m). The ATB has several input dry contacts.
Figure 19 Input dry contacts
Electrical Connections—UPS
2
for a
Table 4Description of dry contact input port
PositionNameDescription
J9.1ENV_DETDetection of battery room environment (normally closed); On Generator; EVN
J9.2BAT_GNDBattery short to ground detection; BtG; On Generator
J9.3BAT_READYNot Used
J9.4+12V+12V power supply
J4.1BAT_INInternal battery temperature detection
J4.2+12V+12V power supply
J4.3BAT_OUTExternal battery temperature detection
J4.4GNDPower supply GND
J5.1Q3BPInput circuit breaker status of external Liebert BDC
J5.2Q2BPOutput circuit breaker status of external Liebert BDC
J5.3EXT_OUTInput circuit breaker status of internal Liebert BDC
J5.4GNDPower supply GND
J8.1DRIVERBCB Driver Signal
J8.2BCB_INBCB Contact State
J8.3GNDPower Ground
J8.4ONLINE
BCB On-Line - Input (N.O.) - This pin will become active when the BCB
interface is connected.
Liebert® APM
™
34
Page 45
3.4.2Output Dry Contacts
J1 0
MFP_O
MFP_S
MFP_C
J12
INV_C
INV_S
INV_O
J11
BF P_C
BFP_S
BFP_O
NOTE: The black square () on each connector indicates Pin 1.
Refer to Figure 18 for the location of connectors J10, J11 and J12.
The Auxiliary Terminal Block has three output dry contact relays (see Figure 20 and Table 5).
Figure 20 Output dry contacts and EPO wiring
Table 5Output dry contact relays
PositionName
J11.2BFP_OBypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J11.3BFP_SBypass feedback protection relay center
J11.4BFP_CBypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J12.2INV_OInverter mode relay. Normally open. Closed when UPS is in inverter mode.
J12.3INV_SInverter mode relay common
J12.4INV_CInverter mode relay. Normally closed. Open when UPS is in inverter mode.
J10.2MFP_OMain feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J10.3MFP_SMain feedback protection relay common
J10.4MFP_CMain feedback protection relay. Normally closed. Open when bypass SCR is shorted.
Description
Electrical Connections—UPS
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
3.4.3Liebert BDC Interface
The Liebert BDC interface is on the Auxiliary Terminal Block at J5. Refer to Figure 18 for the
location of connector J5 and to Figure 19 for circuit details.
Table 6Liebert BDC interface
PositionName
J5.1Q3BPInput circuit breaker status of external Liebert BDC
J5.2Q2BPOutput circuit breaker status of external Liebert BDC
J5.3EXT_OUTInput circuit breaker status of internal Liebert BDC
J5.4GNDPower supply GND
These contacts cannot be active unless they are set via software.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 10 and Figure 45 for the Liebert BDC wiring.
Description
35Liebert® APM
™
Page 46
3.4.4Battery Cabinet Interface Connectors
J6
EPO-NOEPO-NC
J6
EPO-NO
EPO-NC
+12V+12V
+12V
+12V
NOTE: The black square () on each
connector indicates Pin 1.
Refer to Figure 18 for the location of
connector J6.
The battery cabinet interface is on the Auxiliary Terminal Block at J8 and J4. Refer to Figure 18 for
the location of connectors J4 and J8 and to Figure 19 for circuit details.
Table 7Battery cabinet interface
Position
J4.1BAT_INInternal Battery Temperature Detection
J4.2+12V+12V Power Supply
J4.3BAT_OUTExternal Battery Temperature Detection
J4.4GNDPower Ground
J8.1DRIVERBCB Driver Signal
J8.2BCB_INBCB Contact State
J8.3GNDPower Ground
J8.4ONLINE
Name
Description
BCB On-Line - Input (N.O.) - This pin will become
active when the BCB interface is connected.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 9 and Figure 40 for battery cabinet wiring.
Electrical Connections—UPS
3.4.5EPO Input—Optional
NOTICE
Risk of exceeding internal voltage limits. Can cause equipment damage.
Do not apply more than 12V to the Emergency Power Off (EPO) input. Exceeding 12V on this
input can damage the Liebert APM’s internal circuitry and control boards. Exceeding 12V will
also put the Liebert APM in an EPO state, and the unit will not reset, making it nonfunctional.
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by
a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The J6 connector, shown in Figure 21, is the remote EPO input interface. The EPO has NO/NC
contacts that become active when shorting terminals J6: 3 and 4 or open terminal connection J6: 2
and 1.
If an external Emergency Stop capability is required, it is connected at terminals J6: 1 and 2 and at
J6: 3 and 4 on the monitor board. It also is connected to the Normally Open or Normally Closed
remote stop switch between these two terminals using shielded cable (see Figure 21 and Table 8). If
this function is not used, terminals J6:3 and 4 must be opened and J6:1 and 2 must be closed.
Figure 21 EPO wiring and signal names for J6
Liebert® APM
™
36
Page 47
Table 8EPO input contact relays
PositionNameDescription
J6.1EPO_NCEPO Activated when opened to J6.2
J6.2+12VEPO Activated when opened to J6.1
J6.3+12VEPO Activated when shorted to J6.4
J6.4EPO_NOEPO Activated when shorted to J6.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
bypass. It does not internally disconnect the input power supply. To disconnect ALL power to
the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – J6: 1, 2, these terminals are supplied factory-linked on the Bypass
Module on the UPS and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
Figure 22 Single UPS Remote Emergency Power Off
Electrical Connections—UPS
Single Liebert APM Module
Liebert APM
Bypass Module
Liebert APM
Bypass Module
Remote EPO
(Customer-
Supplied)
UHRF3S67X2 (J6)
Field-Supplied Wiring
X2_J6
UHRF3S67X2
UAM04031-00
Rev. 1
37Liebert® APM
™
Page 48
Parallel System and LBS System Installation
!
4.0PARALLEL SYSTEMAND LBS SYSTEM INSTALLATION
This chapter gives details on the installation of a parallel system and an LBS system.
4.1General
A parallel Liebert APM system can consist of two Liebert APM cabinets connected in parallel without
a main system static bypass. Instead, the bypass static switches of each UPS share the load when the
system transfers to the utility bypass supply. A third-party APM paralleling switchboard may be used
to provide external maintenance capability. See Figure 23 for details.
From a power viewpoint, each module is internally identical to the single-module configuration. A
parallel system requires intermodule control signals to manage the load sharing, synchronizing and
bypass switching. The control signals are connected through parallel communication cables, which
provide bi-directional communication between the two Liebert APM units of the system. A second
parallel cable is provided to establish redundancy.
When Liebert APM units are to be connected in parallel, a sharing inductor assembly is required and
must be installed inside the Liebert APM cabinet. The inductor may be installed at the factory or
field-installed.
4.2System Installation Procedures
The installation of a parallel UPS should follow the procedures for a single UPS module with the
additional requirements detailed in this section.
4.2.1Preliminary Checks
Be sure that the options of the parallel cables are correct and that the modules are of the same rating,
model and with the same software and hardware release.
WARNING
To achieve coordinated operation of the modules in the parallel system, it is required to
configure each module separately using Emerson configuration software. This must be done
by Emerson service personnel.
4.2.2Cabinet Installation
Position the UPS modules and make connections as shown in Figure 23. The output distribution
consisting of external UPS output switches and maintenance bypass must be installed, as shown in
Figure 23, to facilitate maintenance and system testing.
Liebert® APM
™
38
Page 49
Figure 23 UPS system with external maintenance switch
UAM01060A
Rev. 0
Buyout Liebert APM Paralleling Switchboard
* System
AC Input
4 Wire +GND
UIB
See
Note 7
UIB
Liebert APM #1
UPS Cabinet
Liebert APM #2
UPS Cabinet
Battery
Output
Busbar
Output
Busbar
Static Bypass
MIB
MBB
MOB1
MOB2
Opt. K
AC Output
4-Wire+GND
NOTES:
1. Install in accordance with national and local
electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source.
A full capacity neutral conductor is recommended.
Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be
run in separate conduits.
5. Control wiring must be run in separate conduits.
8. See drawings UAM01080B, UAM01080C, UAM01080D,
UAM01080E and UAM01080F. Refer to the following
battery cabinet control wiring drawings:
UAM04000
UAM4001A,B
UAM4002A,B D)
Parallel System and LBS System Installation
NOTE
For parallel system installations, an external bypass rated for the total system load must be
installed.
For parallel systems, Emerson recommends installing bypass load sharing inductors to optimize
4.2.3External Protective Device
current sharing during static bypass operation.
Refer to 3.2 - External Protective Devices.
39Liebert® APM
™
Page 50
4.2.4Power Cable
UAM1080C
Pg. 3, Rev. 1
Notes
1. See drawings UAM01080A, UAM01080B,
UAM01080D, UAM01080E and UAM01080F.
The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input
has a current leakage protective device, the current leakage protective device must be fitted upstream
of the neutral line input terminal.
NOTE
The length and specification of power cables including the bypass input cables and UPS output
cables should be the same. This facilitates load sharing in bypass mode.
4.2.5Input Breaker Control Wiring
Figure 24 Input breaker control wiring for parallel systems
Parallel System and LBS System Installation
4.2.6Output Breaker Control Wiring
Liebert® APM
Auxiliary wiring must be installed as shown in Figure 25 to protect the system and enable a single
UPS to be isolated and tested during service.
™
40
Page 51
Figure 25 Output breaker control wiring
Notes
1. See drawings UAM01080A, UAM01080C,
UAM01080D, UAM01080E and UAM01080F.
2. Load Bus Sync cable not used with parallel system.
Factory-Supplied Wiring
Liebert APM 2
Liebert APM 1
J1
J2
J2
J2
J1
J1
Parallel Control Cables
UHRF3S67X2 (J1, J2)
Liebert APM Bypass Module
Only One Shown
UAM1080B
Pg. 2, Rev. 0
Parallel System and LBS System Installation
Buyout Liebert APM Paralleling Switchboard
MBB
UHRF3S67X2 (J5)
J5
Liebert APM Bypass Module
Only One Shown
Notes
1. See drawings UAM01080A, UAM01080B,
UAM01080C, UAM01080E and UAM01080F.
2. MBB auxiliary switch connections are on the normally
closed and common positions.
3. MOBs auxiliary switch connections are on the normally
open and common positions.
4.2.7Parallel Cables
Shielded and double-insulated parallel control cables available in lengths of 16.4ft. and 32.8ft. (5m
and 10m) must be interconnected in a ring configuration between the UPS modules, as shown in
Figure 26. The parallel ports J1 and J2 are provided on the front panel of the bypass module, as
shown in Figure 28. The ring connection ensures the reliability of the control of the parallel system.
Be sure to verify the reliable cable connection before starting up the system!
System
AC Input
4-Wire + GND
UIB
UIB
Liebert
APM #1
X2 J5
Liebert
APM #2
Field-Supplied Wiring
MIB
See Note 2
MOB1
1
2
3
4
1
2
3
4
TB2
1
2
3
4
5
6
See Note 3
MOB2
See Note 3
AC Output
4-Wire + GND
UAM0180D
Rev. 1
NOTE
Use the shortest parallel control cables possible for the application . Do not coil excess cable.
Meanwhile, separate the parallel control cables from the power cables to prevent electrical
inteferences.
Figure 26 Connection of parallel control cables of parallel system
41Liebert® APM
™
Page 52
4.2.8Key Interlock System
Figure 27 Key interlock system control wiring
Parallel System and LBS System Installation
AC Input
Ø A
Ø B
Ø C
UHRF3S67X2 (J5, J12)
J5
Liebert APM Bypass Module
Only One Shown
Notes
1. See drawings UAM01080A, UAM01080B,
UAM01080C, UAM01080D and UAM01080F.
2. MBB auxiliary switch connections are on the normally
closed and common positions.
3. MOBs auxiliary switch connections are on the normally
open and common positions.
4. Contact closes when UPS is on internal bypass.
Field-Supplied Wiring
MBB
Kirk Key
K1
Liebert
APM #1
*See Note 4
3
4
X2 J12
1
2
3
4
X2 J5
Liebert
APM #2
*See Note 4
3
4
X2 J12
1
2
3
4
X2 J5
See Note 2
Buyout Liebert APM Paralleling Switchboard
MOB1
TB3
1
TB2
TB3
TB2
2
1
2
3
3
4
4
5
6
See Note 3
MOB2
See Note 3
MIB
Kirk Key
K2
2 Fuses
2A
Inner Door SWBRD
SKRU
KO
Push
Button
AC Output
ØA
Ø B
Ø C
Neu
UAM0180E
Rev. 0
Transfer Parallel Liebert APM Units to System Bypass Mode
1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the
SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove key.
3. Insert key in MBB interlock K1 and rotate to withdraw interlock. Key will remain in interlock.
4. Close the MBB.
5. Open the MIB and rotate thekey in K2 to extend interlock.
6. Remove key from MIB interlock K2 and place in K0.
7. Rotate key in K0 to lock key.
Return Parallel Liebert APM Units to Normal Mode
1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the
SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove the key.
3. Insert the key in the MIB interlock and rotate the the key in K2 to withdraw interlock.
4. Close the MIB.
5. Open the MBB and rotate the key in K1 to extend interlock.
6. Remove the key from the MBB interlock K1 and place it in K0.
7. Rotate the key in K0 to lock the key.
Liebert® APM
™
42
Page 53
Figure 28 Locations of ports J1, J2 and J3 on bypass module
J1
J2
J3
Input/output dry contact and EPO/BCB/MBC interface
J1 ~ J3 port can’t connect to phone!
J4J7
J1
GND
+12V
BAT-IN
BAT-OUT
J5
J2
PARA
J10
GND
OUT
MFP_C
MFP_S
MFP_O
INPUT_1
INPUT_2
J11
J8
Parallel System and LBS System Installation
INTELLISLOT3INTELLISLOT2INTELLISLOT1
GND
J3
PARA
EPO-NO
LBS
GND
Q3BP
Q2BP
EXT-OUT
J9J6
+12V
+12V
EPO-NC
BFP_C
BFP_S
ONLINE
+12V
BAT_READY
BFP_O
BCB_IN
DRIVER
J12
INV_S
INV_C
INV_O
ENV_DET
BAT_GND
MONITOR
RS485-2RS485-1
RS232
4.2.9Remote EPO
In addition to the EPO switch provided on the operator control and display panel of each UPS module
for controlling the EPO of each module respectively, the parallel system also provides remote EPO
function for controlling all UPS modules to shut down simultaneously from a remote terminal, as
shown in Figure 29.
NOTE
1. The remote EPO switch must provide a dry contact signal, which is normally open or
closed.
2. The open circuit voltage provided is 5VDC, <20mA.
3. The external EPO device can be composed of another control system that can disconnect the
UPS mains supply or the bypass input.
4. Pins 1 and 2 of the normally closed EPO-J6 port on the bypass module are connected at the
factory.
Figure 29 Remote Emergency Power Off wiring for parallel UPS
Two Liebert APM
Modules in Parallel
Liebert APM
Bypass Module 1
Liebert APM
Bypass Module
X2_J6
UHRF3S67X2
Remote EPO
(Customer-
Supplied)
Liebert APM
Bypass Module 2
UHRF3S67X2 (J6)
X2_J6
UHRF3S67X2
UAM04031-00
Field-Supplied Wiring
43Liebert® APM
Rev. 1
™
Page 54
4.3LBS System
Main Input
Bypass
UPS1A
UPS1B
UPS2A
UPS2B
LBS
STS
To Load
Main Input
Parallel
Control
Cable
Main InputMain Input
Bypass
Parallel
Control
Cable
4.3.1Cabinet Installation
A dual bus system consists of two independent UPS systems, each containing one or more parallel
UPS modules, as shown in Figure 30. The dual bus system has high reliability and is suitable for
loads with multiple input terminals. For a single-input load, an optional static transfer switch can be
fitted to achieve the transfer between the two outputs of the dual bus system.
Figure 30 Typical dual bus system (with STS and LBS)
Parallel System and LBS System Installation
The dual bus system uses the LBS to keep the output of the two independent UPS systems (or parallel
systems) in synchronization. One system is designated as the master, the other is designated as the
slave. The operation modes of the parallel system comprise master and/or slave operation in normal
or bypass mode.
Place the UPS modules side by side and interconnect the UPS modules according to the following
instructions.
4.3.2External Protective Device
Refer to 3.2 - External Protective Devices.
4.3.3Power Cable
The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input
has a current leakage protective device, the current leakage protective device must be fitted upstream
of the neutral line input terminal.
4.3.4Control Cable
For Liebert APM-to-Liebert APM dual bus system, connect the optional LBS cables between the two
UPS systems as shown in Figures 31 to 33. The J3 and J4 ports are provided on the front panel of
the bypass module, as shown in Figures 28.
NOTE
Use the shortest LBS cable that will be functional for the application and do not coil excess
cable. Separate the LBS cable from the power cables to prevent electrical inteferences.
Liebert® APM
™
44
Page 55
Parallel System and LBS System Installation
Figure 31 Connection of typical dual bus system of two parallel systems
UPS 1
Bypass Module
J1
J2
J3
UPS 2
Bypass ModuleBypass ModuleBypass Module
J1
J2
J3
LBS Cable
UPS 3UPS 4
J1
J2
J3
LBS Cable
J1
J2
J3
Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable
UPS 1
Bypass Module
J1
J2
UPS 2
Bypass Module
J1
J2
J3
J3
LBS Cable
Figure 33 Connection of typical dual bus system of two single UPS’s with redundant LBS cable
UPS 1
Bypass Module
J1
J2
LBS Cable
J3
LBS Cable
UPS 2
Bypass Module
J1
J2
J3
45Liebert® APM
™
Page 56
5.0BATTERY INSTALLATION
!
!
5.1Introduction
Emerson recommends that the batteries in external cabinets be the same type and made by the same
manufacturer as the internal batteries in the Liebert APM.
If multiple sets of batteries connected in parallel are used to provide the required battery backup run
times, fit each set with an isolating device to permit working on one of the battery sets while leaving
the others in service and providing backup protection.
5.2Safety
Special care should be taken when working with the batteries associated with the Liebert APM
system equipment.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The Liebert APM’s internal batteries are connected and energized even if the UPS is turned
Off. To minimize the risk of injury, a properly trained and qualified service person should
disconnect internal batteries before any maintenance is performed on the unit.
When all batteries are connected together, the battery terminal voltage may exceed 324V and
is potentially lethal.
The center of the battery is connected to the neutral of the UPS and is grounded.
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance.
Battery Installation
When replacing batteries, replace with batteries of the same type and manufacturer, or equivalent.
Refer to 11.2 - UPS Environmental for a list of approved batteries or contact your Emerson
representative.
Liebert® APM
CAUTION
Batteries used in the Liebert APM and its auxiliary cabinets must be of an approved type.
Replacing batteries with an incorrect type can cause an explosion and fire. Refer to Tables 38
and 40 for acceptable batteries.
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate
batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
™
46
Page 57
5.3UPS Batteries—Liebert APM 45kVA Frame Only
See Figure 35
The Liebert APM’s internal batteries are fully charged before the unit is shipped. During storage and
transportation, some charge is lost. All batteries should be recharged before use. The battery charger
works only when the Liebert APM is connected to input power and turned On.
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturer's manuals, available on the manufacturer’s Web site.
The battery safety information contained in this section relates to key considerations that must
be taken into account during the installation design process and might affect the design
outcome, depending on your installation.
5.3.1Internal Battery Breaker Component Locations and Control Wiring
The Liebert APM 45kVA frame contains internal batteries. The batteries are protected by an internal
battery breaker. Figure 34 shows the component location; Figure 35 shows the control wiring.
1. All service and initial battery connections
must be performed by properly trained and
qualified service personel.
X107
3
2
1
2. Jumper X107 must short circuit Pin 1 and Pin 2.
3. The circuit breaker auxiliary blue wire #12 is not used.
4. Shunt trip drive is 220VDC @ 2.4A.
UHRF3S67X2
UAM04052B
Pg. 2, Rev. 0
See Figure 34
Battery Installation
Liebert® APM
™
48
Page 59
5.4External Battery Cabinet Installation
!
DETAIL B
Liebert
APM
Battery
Cabinet
3
Washer
Split, M10
Washer
Split, M10
Hex Head
Bolt, M10
1
2
B
5.4.1Matching Battery Cabinets
A matching battery cabinet is available. Refer to Figure 37. The same model battery cabinet may be
installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on
the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms
of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections, and cabinet for
any damage. Exercise caution; voltage is present within the battery cabinet even before installation.
If there are signs of damage, do not proceed. Call Liebert Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If
planning to store a battery cabinet for longer than six months or at temperatures higher than 77°F
(25°C), contact Liebert Services for recommended precautions.
The following notes, in conjunction with the diagrams (Figure 37), illustrate the broad principles to
be followed when fitting and connecting the majority of battery cabinet installations.
CAUTION
Any battery system should be installed by properly trained and qualified personnel.
When installing an external battery cabinet that is NOT a Liebert APM battery cabinet, the customer
must provide overcurrent protection. See Table 43 for sizing of protection devices.
Battery Installation
NOTE
When using an external battery supply that is not provided with the UPS, please make
reference to the battery manufacturer’s installation manual for battery installation and
maintenance instructions, available on the manufacturer’s Web site. When replacing batteries,
Emerson recommends that the batteries in external cabinets be the same type used internally in
the Liebert APM. See Tables 38 and 40 for batteries that are approved for use with the Liebert
APM.
Figure 36 Bolting the battery cabinet to the Liebert APM
49Liebert® APM
™
Page 60
5.4.2Connecting the Batteries
603705
Pg. 1, Rev. 1
X8
Tray 1
Tray 2
Tray 3
Tray 4
12
34
42
32
39
2X
DETAIL B
4X
40
B
603705G2ASSY BATT NXRA 600 BATT CAB HX330
603705G4ASSY BATT NXRA 600 BATT CAB HX300
603705G5ASSY BATT NXRA 600 BATT CAB HX205
603705G10ASSY BATT NXRA 600 BATT CAB HX150
If the Liebert APM battery cabinets are installed on a raised floor, the battery power cables and
circuit breaker control cables may be routed to the UPS cabinet through the bottom of the cabinet.
If the Liebert APM battery cabinets are installed adjacent to one another on a solid floor, these cables
may be passed between the cabinets through slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet may be used.
Figure 37 Battery cabinet, 600mm wide—details
Battery Installation
Liebert® APM
™
50
Page 61
Figure 38 Battery trays for 600mm battery cabinet
HX330
HX300
HX205
HX150
Battery Installation
51Liebert® APM
™
Page 62
Figure 39 Battery cabinet with trays for 900mm battery cabinet
Tray 1
Tray 2
Tray 3
2x 3
20
2x 13
Tray 5
Tray 6
Tray 4
Detail A
6X
14.5"
(368.3mm)
8
Tray 4 View
Tray 4 with Extra Isolator
1
7
2
2x 6
2x 14
6x 10
12x 11
4x 9
17
16
8
15
12.8"
(325mm)
15
20" (508mm)
Tray View
Battery Installation
Liebert® APM
™
52
Page 63
5.4.3Installation Considerations
Position—Liebert battery cabinets come in versions specific to the left side of the UPS. If the system
includes a matching Liebert BDC, the cabinet should be mounted to the right of the UPS (nearest the
busbars) and the battery cabinet(s) should be installed to the left of the UPS.
The battery cabinet(s) are designed to be located conveniently next to each UPS module on the left
side only and are also available in stand-alone configurations with painted side panels. The front
access design eliminates side and rear service clearance requirements. Refer to Table 36 for battery
cabinet dimensions and weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt only onto the left side of the UPS
module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in
the front and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and
servicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of
clearance at the front of the cabinet when operating. Side and rear panels do not require service
clearance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet,
eliminating the need for external conduit runs. Route cables before moving cabinets into final position
for bolting together. No top or bottom entry cables are required, except for remotely located cabinets
which require conduits.
Software—To allow the UPS to accurately display the battery run time, the number of battery
cabinets must be noted when performing initial startup and setup using the configuration software.
This is to be performed by the Liebert Services engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the
cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small
amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery
cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.
Battery Installation
5.4.4Connecting the Battery Cabinet to the UPS
After the battery cabinet equipment has been positioned and secured for operation and the batteries
have been connected, connect the power cables as described below (see Figure 40).
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the UPS right side panel to gain access to the ground and battery busbars.
3. Remove the battery cabinet front panel to gain access to the busbars.
4. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar.
(example: UPS located on the bottom of the equipment below the power connections).
All cabinets in the UPS system must be connected to the user's ground connection.
NOTE
The grounding and neutral bonding arrangement must be in accordance with the National
Electrical Code and all applicable local codes.
5. Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet
breaker BCB (+ N -) as shown in Figure 40. Be sure that the battery connections are made with
the right polarity, and tighten the connections to 240lb-in. (27N-m) (M10 bolt). Do not close the
battery circuit breaker before the equipment has been commissioned.
6. Connect TB1 from battery cabinet to J4 and J8 on the UPS according to Table 9.
NOTE
The shunt trip drive capability for the battery breaker is 220VDC at 2.4A.
53Liebert® APM
™
Page 64
Table 9Control wiring for Liebert APM to battery cabinet
1. All service and initial connectino of batteries
must be performed by properly trained and
qualified service personnel.
2. The Jumper X107 must short circuit Pin 1 and Pin 2.
External
Connections
AC 120V Power
to Optional BDSi
Controller
AC 120V
from UPS
BDSi Fuse Block
GRD
Fault CT
Positive
Negative
Neutral
Ground W24
W21
W22
W23
Neg. Mid Pt.
Aux.
MX
See
Note 3
Blue (Not Used)
Orange
Black
Black
Blue Com
Blue
TB1
W/R
W/Blk
White
White
Violet NO
1
2
3
4
5
6
7
8
9
10
11
12
RedRed
White
White
Grn
Grn
Wht
Wht
Brn
Brn
Blk
Blk
Blk
Blk
1
2
3
4
1
2
3
4
X2 J8
X2 J4
X108
X105
X102
X100
X107
X101
X104
X103
X106
UHR93S6A1
X2
BCB_IN
BAT-OUT
BAT IN
GND
GND
Driver
Online
+12V
Red
Red
White
White
Wht
Grn
Brn
Blk
Blk
Blk
Red
Blk
1
2
3
3
2
1
DRV
AUX
GND1
USE
TEMP
J2
J3
J4
220VDC
220VDC
Red
Blk
UH8351A8
BIB
BCB
Control
Board
Red
3. The auxilliary blue wire is not used. Cap and coil the
wire and tie it to the bridge lance on the frame below
the breaker.
4. Shunt trip drive is 220VDC @ 2.4A.
UAM04000
Rev. 0
TB2
Brown
Yel /G rn
UPS
Module
FromTo
Liebert APM UPS Bypass
Module (X2 J4 & J8)
Battery Cabinet
Terminal Strip (TB1)
J4-2TB1-12
J4-3TB1-11
J4-4TB1-10
J8-1TB1-6
J8-2TB1-7
J8-3TB1-8
J8-4TB1-9
Figure 40 Battery cabinet connection to Liebert APM
Battery Installation
Liebert® APM
™
54
Page 65
5.5Non-Standard Batteries
UAM04050A-00
Pg. 1, Rev. 0
Battery
Breaker
Battery
Temperature
Sensor Location
UHRF3S67X2
Liebert APM
Bypass
Module
Front
Right Side
Isometric View - Right Side
UHR93S6A1ZA6
Output EMI Board
CT
ULC366SC1 Ground Fault Detect Board
UHW241M5 Auxiliary Power Board
When batteries other than a matching battery cabinet are used, a remote battery disconnect switch
with overcurrent protection is required per the National Electrical Code. Contact your local Emerson
sales representative about this option. Refer to Figures 87 and 88 for details.
Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.
Verify that the battery area has adequate ventilation and battery operating temperature complies
with the manufacturer's specifications and with all applicable national and local codes.
If you have any questions concerning batteries, battery racks or accessories, contact Liebert Services
at 1-800-543-2378.
NOTE
The user-supplied battery DC bypass breakers or fuses should have a minimum overload
rating of 8kA and 500V.
5.6Battery Ground Fault Detection Option
An optional battery ground fault detection device can be added to detect leakage current in the
battery system. The residual current range monitored is 30mA ~ 3000mA. When a battery ground
fault is detected, an alarm will appear on the UPS display panel. The battery ground fault detection
set contains one current transformer (CT). Figures 41 and 42 show the connection of this set for the
Liebert APM.
Figure 42 Control wiring diagram for battery ground fault detection option
Red
UHRF3S67X2 (J9)
UHR93S6A1ZA6
Output EMI Board
Output A
Output B
Output C
Blk
Battery Installation
W600
Liebert APM
Bypass Module
J9
Liebert APM Bypass Module
Liebert
APM
Internal
Battery
Battery
Breaker
Output N
UHW241M5
Red
Brn
Blk
Auxiliary Power Board
W601
W603
W602
CT
Positive
Neutral
Negative
Liebert
APM
DC Bus
Notes
1. All battery service and initial connections
must be performed by properly trained and
qualified personnel.
2. Refer to drawing # UAM04050A, Pg. 1.
X2_J4
UHRF3S67X2
Blk
Red
X2_J9
Blk
Brn
Red
J4
J1
J7
BlkBlk BrnBrn
ULC366SC1
Ground Fault Detect Board
UAM04050B
Pg. 2, Rev. 0
RedBlk
J5
12V
GND
Liebert® APM
™
56
Page 67
Liebert BDC
™
6.0LIEBERT BDC
™
The Liebert BDC is designed to operate in UPS normal mode, static bypass mode and maintenance
mode. The Liebert BDC offers either 45kVA or 90kVA capacity to match the associated Liebert APM
frame offerings. Each of the Liebert BDC capacities offer optional input 208V, 480V and 600V
internal transformers as well as multiple output distribution selections.
Figure 43 Single input UPS with external Liebert BDCwith optional internal transformer—typical
configuration
Bypass Distribution Cabinet
* System
AC Input
3-Wire + GRD
Optional
Transformer
BIB
MBB
MIB
Optional
54-Pole
See Note 5
AC Output
208V
4-Wire + GRD
Local Grounding
Electrode
Static Bypass
See Note 1
UPS Cabinet
Battery
Notes
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. UPS system input and output cables must be run in separate conduits.
4. Control wiring must be run in separate conduits.
5. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, 400A
for 90kVA frame only.
6. Transformer available: 480V or 600V input.
6.1Normal (UPS) Mode
While the Liebert BDC is in Normal mode (MBB open; BIB/MIB closed), the UPS is supplying the
connected load with continuous, high-quality AC power. In this mode of operation, the load is
protected by the UPS.
6.2UPS Static Bypass Mode
When the Liebert APM is in Static Bypass mode, it provides an alternate path for power to the
connected equipment. Should the UPS need to be taken out of service for limited maintenance or
repair, manual activation of the Static Bypass will cause an immediate transfer of the equipment
from the UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS;
however, the load is NOT protected by the UPS.
When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate
path for power to the connected equipment should the UPS need to be taken out of service for limited
maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is
NOT protected by the UPS.
6.4Locating the Cabinet
This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit. In either
case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the
switches and cable connections as required by national and local codes.
6.5Cable Installation
6.5.1Wiring Preparation
Be sure that the unit is not connected to any AC utility power source or UPS before installing any
wiring to this unit. This Liebert BDC should be installed by a qualified / certified electrician.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Read this section thoroughly before attempting to install wiring to this unit. Read and
comply with all warnings and cautions in this manual.
Liebert BDC
™
Removing the Cover Plates
Plates cover the input and output terminals on the front of the Liebert BDC (see Figure 44). Remove
these and keep the screws and plates for reinstallation.
Figure 44 Liebert BDC—access plate removed
6.5.2Power Cable Installation
Refer to Table 43 when selecting cables.
NOTE
Transient and steady state earth leakage currents may occur when starting the equipment.
This should be taken into account when selecting ground current detection devices because
these will carry the earth leakage currents of both the UPS equipment and the load.
Liebert® APM
™
58
Page 69
6.5.3Input/Output Wiring
Follow the steps below to connect the input wiring:
NOTE
Input wiring must be installed using conduit if cabinet is not mounted to the immediate right
of the UPS.
1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch
the appropriate size hole for the size conduit being used. Pull the three/four input wires through
it, allowing some slack for installation. For cabinets that are located to the immediate left of the
UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that
the edge guarding is installed and intact.
2. Secure the conduit to the access plate of the Liebert BDC.
3. Input power cables connect to the system input circuit breaker; refer to Figure 59 and to
Table 18.
4. Connect the ground (earth) wire to the earth busbar and tighten it to 240lb-in. (27N-m) (M10
bolt).
5. Locate UPS input and output cables and access panel to UPS on lower right side.
NOTE
If the Liebert BDC is not to be bolted to the UPS, use either top or bottom access plate.
6. Connect the system ground cable between the Liebert BDC and UPS and tighten the connections
to 240lb-in. (27N-m) (M10 bolt).
7. Connect the system input cables between the Liebert BDC “UPS Input” Busbars (A-B-C N
terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 240lb-in.
(27N-m) (M10 bolt).
8. Connect the system output cables between the Liebert BDC 'UPS Output' Busbars (A-B-C N
terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 240lb-in.
(27N-m) (M10 bolt).
9. Connect TB1 from the Liebert BDC to J5 and J12 on the Liebert APM.
Liebert BDC
™
NOTICE
Risk of improper wiring connection. Can cause equipment damage.
The control wire must be installed to ensure proper operation of the system and fully protect
the load when switching between bypass cabinet and UPS.
Table 10Control wiring for Liebert APM UPS to Liebert BDC
1. Customer-furnished electrode conductor to be
installed in accordance with national and
electrical codes.
W88
4
3
4
3
1
2
W89
3
45
W90
Key K2
3
2
3
4
8
6
11
7
910
SKRU - Solenoid
Key Release Unit
KO - Key Operator
Field-Supplied Wiring
Factory-Supplied Wiring
MIB
Kirk
4
12
AC 120V
(2)
Fuses
2A
Ground
to Unit Frame
SKRU
To T B 1
Inner Door
UAM04012
Rev. 4
K0
Push
Button
Output
Ground
Liebert® APM
NOTE
Install jumper on TB1 pins 4 and 5.
For startup procedure, see 10.2 - UPS Startup.
™
60
Page 71
6.6Bolting Cabinets Together
A
Hardware for bolting units is in a bag attached to
the Liebert BDC. See form included with UPS.
DETAIL A
3
Washer
Flat, M10
Washer
Split, M10
Hex Head
Bolt, M10
1
2
Place cabinets so mounting holes are aligned.
A bolt from the adjacent cabinet may be screwed into the threaded
top hole, or a bolt may be inserted through the lower hole and
screwed into the threaded hole in the adjacent cabinet.
NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.
Figure 46 Bolting Liebert APM to a Liebert BDC
Liebert BDC
™
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the
UPS side or from the Liebert BDC side, whichever is more convenient.
61Liebert® APM
™
Page 72
7.0INSTALLATION DRAWINGS
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4.Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national
and local electrical codes.
9. All battery cabinets must be positioned on the
left side of the UPS.
FRONT VIEW
UAM03000
Rev. 0
UPS
Battery
Cabinet #1
78.7"
(2000mm)
55.4" (1408mm)
23.8" (604mm)
Total Width with Additional Battery Cabinets
Total Width
In. (mm)
79.1 (2008)
102.7 (2608)
126.3 (3208)
Number of
Battery Cabinets
2
3
4
UAM03001
Rev. 1
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert
APM UPS System cabinets (UPS, Liebert BDC and battery).
Figure 47 UPS dimensions- front view
Installation Drawings
Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs
Liebert® APM
™
62
Page 73
Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 12" (305)
rear clearance required for air exhaust and 36" (914)
front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate
conduits.
7. Only copper cables are recommended.
UAM2010A
Rev. 2
Detail A
Mechanical
Stop
Caster
39-1/2"
(1000mm)
78.7"
(2000mm)
1.56"
(40mm)
3"
(77mm)
23.4"
(595mm)
31.8"
(808mm)
8.9"
(226mm)
1.4"
(36mm)
34.3"
(871mm)
28.3"
(719mm)
Bracket
Centers
28.3"
(719mm)
9.2"
(235mm)
0.8"
(21mm)
Vent Screen
Front and Back
Vent Screen
Display
Dimension
Y; See Pg. 2
See Pg. 2
Dimension
X
Dimension
Z
Center of
Gravity
Center of
Gravity
31.5" (800mm)
without Side Panels
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
TOP VIEW
BOTTOM VIEW
OVERALL
FRONT VIEW
LEFT SIDE VIEW
Front
Front
See Detail A
RIGHT SIDE VIEW
See
Page 2
8. All wiring is to be in accordance with national and local
electrical codes.
9. See page 2 of 5 drawing: UAM02010B for weight table
and centers of gravity for UPS at 208V.
10. See page 3 of 5 drawing: UAM02010C for weight table
and centers of gravity for UPS at 480V.
11. See page 4 of 5 drawing:UAM02010D for weight table and
centers of gravity for UPS at 600V.
12. See page 5 of 5 drawing:UAM02010E for weight table and
centers of gravity for UPS with internal maintenance bypass.
Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model.
Installation Drawings
63Liebert® APM
™
Page 74
Figure 50 Liebert APM with top fan kit
Notes
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 36" (914) front access
required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through r emovable access plat es.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
UAM0212A
Pg. 1, Rev. 1
Caster
Mechanical
Stop
DETAIL A
Top Fan
Flange to
Flange
13.2"
(335mm)
12.1"
(308mm)
20.7" (526mm)
9.2"
(235mm)
0.8"
(21mm)
07.6"
(194mm)
Top
Fan
Power Cable
Entry 21.26" x 7.87"
(540x 200mm)
TOP VIEW
78.7"
(2000mm)
31.8"
(808mm)
FRONT
OVERALL
FRONT VIEW
RIGHT SIDE VIEW
LEFT SIDE VIEW
BOTTOM VIEW
FRONT
FRONT
Dim. Y
See Pg. 2
Dimension
X
Dimension Z
Display
Center of
Gravity
Center of
Gravity
Vent Screen
Front and Back
See Pg. 2
See Pg. 2
3"
(77mm)
23.4"
(595mm)
See Detail A
28.3"
(718mm)
Bracket
Centers
34.3"
(871mm)
1.4"
(36mm)
8.9"
(226mm)
28.3" (719mm)
Vent Screen
Power Cable Entry
21.26" x 7.87
(540mm x 200)
31.5" (800mm)
w/o Side Panels
39.5"
(1000mm)
7. Only copper cables are recommended.
8. All wiring is to be in accordance wit h nationaland local electrical codes.
9. See Pg. 2 of 5 drawing: UAM02012B for weight table and centers of gravity for UPS at 208 V.
10. See Pg. 3 of 5 drawing: UAM02012C for weight table and center s of gravity for UPS at 480 V.
11. See Pg. 4 of 5 drawing: UAM02012D for weight table and c enters of gravity for UPS at 600 V.
12. See Pg. 5 of 5 drawing: UAM02012E f or weight table and cent ers of gravit y for UPS wit h internal
maintenance bypass.
Installation Drawings
Liebert® APM
™
64
Page 75
Table 11Center of gravity and weights for Liebert APM 90 kVA frame
JBDC Terminal Block TB1UPS Static Bypass Module J5 and J12Wiring for KO on MBC
See Figure 45 and Table 10 for additional details.
NOTE
Wiring is supplied when the UPS and Liebert BDC are ordered as a system.
Table 18Spring washer torque application
HardwareTwo Belleville Washers
M10 (3/8")240 lb-in. (27 N-m)
Figure 60 Acceptable hardware configuration for torque application
Liebert® APM
™
76
Page 87
Figure 61 Seismic mounting bracket details
Rear
Wall
.5
(13mm)
Rear Cabinet
Base Bracket
.75
FLOOR
Cabinet
Rear Door
Rear Cabinet
Floor Bracket
3.5"
(89mm)
Rear Anchor
Hardware
(Not Supplied)
39.2"
(997mm)
(19mm)
Minimum
Detail A
Cabinet
Front Door
Anchor
Front Cabinet
Base Bracket
3.7"
Front Cabinet
Base Bracket
(See Detail B)
(94mm)
FLOOR
Detail B
Installation Drawings
UAM08020
Rev. 2
6.5"
4.3"
(110mm)
6.9"
9.8"
17.7" (450mm)
(165mm)
(175mm)
(250mm)
6.5"
(165mm)
4.3"
(110mm)
6.9"
(175mm)
9.8"
(250mm)
6.5"
(165mm)
(REAR)
BYPASS
CABINET
DISTRIBUTION
UPS
15-90KVA
(FRONT)
5.5"
(140mm)
5.5"
(140mm)
5.5"
(140mm)
11.0"
5.5"
(140mm)
5.5"
(140mm)
5.5"
(140mm)
11.0"
(280mm)
5.5"
(140mm)
(280mm)
16.5" (420mm)
SEISMIC ANCHORING
5. Move cabinet into position with rear tabs into slots of
floor bracket. Tabs to extend at least 1/2" through floor
bracket (Detail A). Then attach front floor brackets to front
Bottom Of Units
(Viewed From Top Looking Down)
cabinet base bracket but do not fully tighten hardware.
6. Mark hole locations and remove brackets. Drill and install
floor brackets. Unit door can be removed for better access.
Reinstall front floor brackets to front cabinet brackets with
supplied hardware and torque to 235 lb-in (26.5 Nm).
7. After all cabinets are moved into place and secured to the
floor, multiple cabinet configurations are then bolted together.
8. If side walls are present, 1.0" (25.4mm) minimum distance from either
side wall is required.
4.3"
(110mm)
6.9"
(175mm)
Rear Base
Bracket
See Detail A
2.7"
(69mm)
BATTERY
CABINET
5.5"
(140mm)
5.5"
(140mm)
NOTES
1. Recommended floor anchor: 1/2" ITW ramset/red head
self-drilling anchor, ICBO #ER-1372 or equivalent (not
supplied). Follow manufacturer’s instructions.
2. Position rear floor brackets on floor at least .75"
from rear wall. Mark location and drill holes (Detail A)
to a minimum depth of 4.12" (104.6mm) into the concrete.
3. Install rear cabinet base bracket (Detail A) to existing
holes on underside of unit with tabs facing rear wall.
Use supplied hardware and torque to 365 lb-inch (41.2 Nm).
Loosen leveling bolt locking nut and tighten after
bracket is secured.
4. Install front cabinet base bracket (Detail B) to existing
holes on underside of unit with bent flange facing front.
Use supplied hardware and torque to 365 lb-inch (41.2 Nm).
Loosen leveling bolt locking nut and tighten after
3.7"
(94mm)
SLOT 16mm
RAD 7mm, Typical
bracket is secured.
77Liebert® APM
™
Page 88
Liebert IntelliSlot® Installation
8.0LIEBERT INTELLISLOT® INSTALLATION
8.1Liebert IntelliSlot Communication
The Liebert APM has three Liebert IntelliSlot ports to allow installation of optional communication
cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary Velocity protocol to cards that
translate the information into such protocols as SNMP and Modbus. Other cards provide dry contact
signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert APM is
operating.
8.2Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for
connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status
information and all measured parameters for display via a Web browser. The Liebert IntelliSlot bays
are on the right side of the control module and labeled as IntelliSlot1, IntelliSlot2 and IntelliSlot3.
• IS-UNITY-LIFE (Included): Offers a web interface to manage and configure the Emerson
Life.net and Emerson proprietary protocols for use with the Emerson Life Station
®
Nform
and Emerson® Trellis™.
• IS-UNITY-DP: Offers a web interface to monitor and configure the Life.net and Emerson
Network Power proprietary protocols for use with the Emerson Life Station, Liebert Nform and
Emerson Trellis. It allows selection and configuration of two of the available third-party
protocols—SNMP, Modbus or BACnet—for operation with building management systems.
• Liebert IntelliSlot
®
Dry Contact Card (IS-RELAY): Provides dry contact alarm information,
including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals
for communication to a remote monitoring system or for use with Liebert MultiLink
• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) Provides dry contact alarm
information, including: On Battery, Low Battery signals for communication to four servers for use
with Liebert MultiLink software.
• IS-485EXI: The Liebert IntelliSlot 485 EXI Card provides connection to a Liebert SiteLink-E™
allowing Liebert SiteScan® Web 4.0 monitoring and control of your Liebert equipment.
8.3Liebert IntelliSlot Card Web Interface
The IS-Unity-Life and IS-Unity-DP IntelliSlot cards offer a Web interface, yielding a wide variety of
status and summary information through an Ethernet connection. Liebert’s IS-Unity-DP also
provides e-mail and text notification.
™
, Liebert
®
software.
Figure 62 Liebert IntelliSlot Web card display
79Liebert® APM
™
Page 90
8.4Liebert IntelliSlot® Relay Card
18
101
9
TB1
green
TB2
black
The Liebert IntelliSlot Relay card (IS-RELAY) provides voltage-free contact closures for remote
monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS
signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and
other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A. and supported in any of the three Liebert IntelliSlot
bays on the Liebert APM.
The card has two terminals blocks, TB1 (green, numbered 1-9) and TB2 (black, 10-18), as shown in
Figure 63.
Figure 63 Pin location and numbering
Liebert IntelliSlot® Installation
Refer to your Liebert product user manual for the pin configuration for the terminal blocks.
Table 20 Relay card pin configuration
PinFunctionOperation
1Common - Low Battery
2Low BatteryClosed if Low Battery point occurs.
3Low BatteryClosed if battery is OK
4Common - UPS Fault
5UPS FaultClosed if UPS fault occurs
6UPS FaultClosed if no UPS failure
7Common - On Battery
8On BatteryClosed if On Battery power (Utility failure)
9On BatteryClosed if not On Battery power (Utility OK)
10 Not Used
11 Not Used
12 Not Used
13 Summary Alarm*Closed if no alarm conditions are present
14 Summary Alarm*Closed if Summary Alarm occurs
15 Common - Summary Alarm*
16 On UPSClosed if On UPS (inverter) power
17 On BypassClosed if On Bypass
18 Common - On Bypass
Liebert® APM
™
80
Page 91
8.4.2Liebert IntelliSlot® Relay Card Jumper Setup
Jumper
P6
Jumper
P5
Jumper
P4
Jumper
P3
Jumper
P7
Front
of
Card
The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 64. Each
jumper connects two pins.
Figure 64 Jumper location and numbering
Liebert IntelliSlot® Installation
By default all five jumpers have shunts installed. The two pins are shunted together to provide the
functions shown in Table 21, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or
inadvertently be connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are
not tied together.
Table 21 Jumper connections
JumperRelay
P6On Battery
P5UPS Fault
P4Low Battery
P3On Bypass
P7Summary Alarm
NOTE
Refer to the Liebert IntelliSlot Relay Card manual, SL-23211 for additional details. the
document is available at the Liebert Web site, www.liebert.com
81Liebert® APM
™
Page 92
8.5Liebert IntelliSlot™ MultiPort Card
Pin Description
1Low Battery
2Utility Fail
3NOT USED
4NOT USED
5NOT USED
6NOT USED
7Low Battery Common
8Utility Fail Common
IS-MULTIPORTUPS
Liebert
MultiLink
computers
AS/400
system
units
The Liebert IntelliSlot MultiPort card provides four sets of voltage-free contact closures for remote
monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical
application is to allow a maximum of four computer systems to simultaneously monitor the status
(e.g., utility power failure-low battery) of a single UPS.
This card is supported in any of the three Liebert IntelliSlot bays on the Liebert APM.
The matching Liebert battery cabinets allow installing an optional Alber BDSi battery monitoring
system inside the cabinet. The Alber BDSi by Emerson continuously checks all critical battery
parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic
tests of internal resistance of each battery will verify the battery's operating integrity. Additional
capabilities include automatic internal DC resistance tests and trend analysis providing the ability to
analyze performance and aid in troubleshooting.
The Alber BDSi system is installed inside the battery cabinet as shown in Figures 11 and 12. The
monitoring system power inlet is wired to the Alber BDSi Fuse Block on the UPS (see ,Figures 13
and 66). The Alber BDSI fuse block supplies 120VAC and has an 8A fuse.
If required, power can be supplied from the output terminals of the UPS, a distribution panel or
another UPS-protected source.
For details about operating the Alber system, refer to the Alber unit’s documentation, available at
http://www.alber.com/
Liebert® APM
™
82
Page 93
Figure 66 Alber BDSi controller and input connection
!
OUTPUT
POWER X
XXXXXXA
INPUT
XXXXXXXXXXXXXAXA
XXXXXXXXXXXA
Input
120VAC 50/60Hz
Rear Panel
Liebert IntelliSlot® Installation
83Liebert® APM
™
Page 94
8.7Battery Temperature Compensation
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
BCB Control
Board
X103
X105
X104
X106
X108
Static
Bypass
Module
Monitor
Board
– X2
+12V
GND
BAT_OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
+
IN
-
+
IN
-
+
IN
-
+
IN
-
12V
OUT
GND
J4
For a UPS with external batteries, an optional battery temperature interface optimizes the external
battery management by connecting up to four external temperature sensors from the battery cabinets
to a control unit inside the UPS.
Figure 67 Multi-temperature sensors
Liebert IntelliSlot® Installation
Liebert® APM
™
84
Page 95
9.0OPERATOR CONTROLAND DISPLAY PANEL
STATUS
EMERSON
Network Power
TM
F1F2F3F4
HELP
FAULT CLEAR
EPO
INV E R TE R OF F
SILENCE ON/OFF
INV E R TE R ON
Control
buttons
LCD and Menu Buttons
Mimic
current
path
1
2
3
54
6
7
8
9.1Operator Control Panel
The control panel and LCD on the front of the Liebert APM lets the operator:
• Turn the UPS On or Off.
• Transfer into the various operating modes.
• Silence alarms.
• Check the status of the UPS and its batteries, including all measured parameters, events and
alarms.
The main areas of the control panel are shown below in Figure 68 and explained in Table 22.
• Mimic Display - view the status of the Liebert APM in single-line diagram format—indicators
show status by changing color when ON, flashing or OFF
• Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from
the Liebert APM in tabular format
• Control buttons - turn the Liebert APM on or off, silence alarms
Figure 68 Overview of control panel
Operator Control and Display Panel
Table 22Descriptions of UPS operator control and display panel
Mimic Current PathControl Buttons
Item #FunctionButtonFunction
1Rectifier indicator (AC to DC)EPOEPO switch
2Battery indicator (backup DC power)INVERTER ONInverter start button
8Protective cover for EPO buttonF1 through F4 and HELPLCD menu keys
NOTE
Help button menus are not active. Future units will ship with an F5 legend in place of the
HELP legend.
85Liebert® APM
™
Page 96
Operator Control and Display Panel
STATUS
EMERSON
Network Power
TM
1
2
3
4
5
6
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator
9.2Mimic Display Indicators
Figure 69 Mimic display indicators location
Mimic indicators show the operational status of the Liebert APM by their color—green, amber or
red—and whether they are ON (solid), flashing or OFF. Table 23 provides a guide to interpreting the
various states of the indicators.
Table 23Mimic display status indicators
Indicator
(see Figure 69)GreenFlashing Green / AmberRedOff
1. RectifierLoad on Rectifier
2. Battery
3. Bypass
4. Inverter
Battery Powering
the Load
Load on Bypass
Power
Inverter Powering
the Load Normally
Flashing Green: Utility normal,
but rectifier not operating
Flashing Green: Battery
pre-warning (low battery)
—
Flashing Green: Inverter on
standby
Rectifier fault
Battery or battery
converter abnormal*
Bypass out of
normal range
Inverter faultInverter normal but Off
5. LoadUPS output On—UPS output overloadedUPS has no output power
6. Status
* Battery or battery converter abnormal events include these event messages (see Table 57): No Battery, Battery Replaced, Battery
Battery and converter are
normal, and battery is not
discharging
Bypass Normal
Liebert® APM
™
86
Page 97
9.3Control Buttons
STATUS
EMERSON
Network Power
TM
F1F2F 3F4
HELP
FAULT CLEAR
EPO
INVERTER OFF
SILEN CE ON/ OFF
INVERTER ON
EPO Button Cover
EPO Button
Inverter Off Button
Fault Clear Button
Silence On/Off Button
Inverter On Button
LCD Navigation Keys
STATUS
EMERSON
Network Power
TM
F1 F2 F3 F4
HELP
FAULT CLEAR
EPO
INVE R TE R O FF
SILENCE ON/OFF
INVERTER ON
Buzzer
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the
inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 70. The
function of each button is described in Table 24.
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.
Figure 70 Control button layout
Operator Control and Display Panel
Table 24Control buttons
Button
(see Figure 70)Function
Completely shuts down the UPS, including the static switch.
EPO
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button
completely shuts down the unit and the critical load.
INVERTER ON
INVERTER OFF
FAULT CLEAR
Press this button to start the inverter and transfer from static bypass to inverter.
NOTE: If the inverter is not ready, this will not activate the UPS.
Press this button to shut down the inverter during operation. The load will be transferred to
static bypass.
After the UPS shuts down due to a fault and the alarm condition has been resolved, press this
button to clear the fault and restart the UPS.
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will
SILENCE ON/OFF
sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.
9.4Alarm Buzzer
The alarm buzzer produces three types of sounds:
• Single beep—When any Control button is pressed
• Single beep repeating every two seconds—The system has a general alarm
• Continuous—The system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have
been silenced manually.
Figure 71 Alarm buzzer location
87Liebert® APM
™
Page 98
9.5LCD Overview
F1F2F3F4
HELP
SingleAPM 090kVA
02:17:47
L1-N/L2 L2-N/L3 L3-N/L1
L-N voltage (V) 121.4
L-N current (A) 12.2
Frequency (Hz) 59.96
L-L voltage (V)211.3
Power factor0.00
122.7
14.2
59.96
211.6
0.00
121.7
13.5
59.96
210.5
0.00
Mains
UPS System Information
Current menu
Current status
Menu icons
Return to Output
Menu
Move to
Next Menu
Time
Alarms
E-Mail
Notification
Icon
The LCD on the front panel has five main sections, as shown in Figure 72. Press the F1 key below
the LCD to scroll through these sections.
• UPS system information - view UPS name and model, date and time, overall status.
• LCD Menu - choose a category of data items to appear below the menus (see Table 26).
• Data and settings - view data items for the selected menu (see Table 26).
• Current statusmessages - check the most recent UPS event and alarm messages (see
Table 57).
• Navigation key icons - look at the icon above each navigation key to determine how the key
operates when pressed (see 9.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the
LCD, status messages are stored in the history log—512 records can be stored and retrieved.
Figure 72 Sections of the LCD
Operator Control and Display Panel
Liebert® APM
™
88
Page 99
9.6Navigation Keys
ESC
?
The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view
the current status and other information about the Liebert APM.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 25). The
keys are “soft keys” that can change functions according to the icon.
•Use F1 to move to the home portion of the LCD.
•Use F3 and F4 as cursor keys to move left and right or up and down, depending on the icons
displayed above the keys.
•Use F3 and F4 on the display simultaneously to view individual Module information such as
Input and Output conditions and individual Module Firmware versions
•Use F2 as an ESC key.
•Use HELP to access help information on the LCD or to enter a choice.
Table 25Icons for navigation keys
KeyF1F2F3F4HELP
Operator Control and Display Panel
Functions
Available
Home
9.7LCD Menus and Data Items
The LCD menus provide access to the following categories of information and settings for the UPS.
Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The
menu choices are listed below and described in detail in Table 26.
• Mains - view utility power input data: voltage, current, frequency and power factor
• Bypass - view bypass data: voltage and frequency
• Output - view output data: voltage, current, frequency and power factor
• Load - view load data: load percent, output current, output power and crest factor (CF)
• System - view system data
• Battery - view battery characteristics—voltage, current, temperature, remaining time and
capacity—and messages when the battery is boost/float charging or disconnected
• Events - view the events log—displays all recent events added to the log (new records added at
end)
• Records - access the history log—displays all records in the log (new records added at end)
• Language - select a language for LCD text (choices appear in the native language)
• Settings - configure UPS settings: adjust the display contrast, choose a format for date display,
set the date and time, set up the UPS for modem communications (baud rate, address, mode and
phone numbers to dial for alarm notifications) and change the password
• Command - start or stop a battery maintenance test, battery capacity test or system test
• Run Time - view available backup time for the UPS and bypass
• Version - view firmware versions for the inverter, rectifier and software display board and the
model information for the UPS
Figure 73 shows a menu tree of the options available from the LCD menus.
LeftRightEnter
Exit
UpDownHelp
89Liebert® APM
™
Page 100
Figure 73 Menu tree
Battery
Battery voltage (V)
Battery current (A)
Battery temperature (°C)
Remain Time Min.
Battery capacity (%)
Battery boost charging
Battery float charging
Battery disconnected
Command
Battery maintenance test
Battery capacity test
System test
Stop testing
Freshening Charge
Stop Freshening Charge
Modem Auto-answer enable
Battery Reset
Run Time
UPS Run Time
Byp Run Time
System
Sout (kVA)
Pout (kW)
Qout (kVAR)
Records
(history log)
Language
(Choices for
display)
Mains (input)
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
Settings
Display contrast
Date format set
Date & time
Comm1 baud rate
Comm2 baud rate
Comm3 baud rate
Communication address
Communication mode
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
Protocol
ECO Mode
Battery Equalize Charge
Events
(events log)
Version
Monitor version
Rectifier version
Inverter version
Bypass version
UPS model
Operator Control and Display Panel
9.8Language Selection
The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French,
German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different
language:
1. From the main menu, press the F4 (shift) key to move the cursor to the Language menu at the
2. Press HELP to access the language choices.
3. Press F3 and F4 (left and right arrows) as needed to highlight the desired language.
4. Use HELP to select the required language.
Liebert® APM
5. Return to the main menu by repeatedly pressing F2 (ESC) and F1.
bottom of the screen.
All text on the LCD will now be displayed in the selected language.
™
90
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.