Emerson Liebert APM 15-90kVA, Liebert APM 120, Liebert APM 208, Liebert APM 480, Liebert APM 600V User Manual

Page 1
Liebert® APM
User Manual–15-90kVA, 120, 208, 480 and 600V, 50/60Hz
Page 2
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Initial Inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Storing for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.1 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 UPS Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Positioning the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.2 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Considerations in Moving the Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.1 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.2 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.3 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.4 Special Considerations for Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.5 Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6 45kVA and 90kVA UPS Frames—Auxiliary Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.1 Optional Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7 Optional Seismic Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8 Liebert FlexPower
2.9 Static Bypass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.0 ELECTRICAL CONNECTIONS—UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1 Power Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.1 Cable Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1 Rectifier and Bypass Input Supply of the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.2 External Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.3 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.4 UPS Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.5 UPS Input Configuration with Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.6 Cabling Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.7 Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.8 Accessory Fuses and Backfeed Breaker Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2.9 Safety Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.2.10 Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.2.11 Cabling Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3 Control Cables Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.3.1 Static Bypass Assembly Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
i
Page 4
3.4 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.4.1 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.4.2 Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.4.3 Liebert BDC Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.4.4 Battery Cabinet Interface Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.4.5 EPO Input—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.0 PARALLEL SYSTEM AND LBS SYSTEM INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2 System Installation Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.1 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.2 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.2.3 External Protective Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.2.4 Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.5 Input Breaker Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.6 Output Breaker Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2.7 Parallel Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.2.8 Key Interlock System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.2.9 Remote EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.3 LBS System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.1 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.2 External Protective Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.3 Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.3.4 Control Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3 UPS Batteries—Liebert APM 45kVA Frame Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.3.1 Internal Battery Breaker Component Locations and Control Wiring. . . . . . . . . . . . . . . . . . . 47
5.4 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.1 Matching Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.4.2 Connecting the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.3 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.4.4 Connecting the Battery Cabinet to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.5 Non-Standard Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.6 Battery Ground Fault Detection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.0 LIEBERT BDC™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
6.1 Normal (UPS) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.2 UPS Static Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.3 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.4 Locating the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5 Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.1 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.2 Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.3 Input/Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.6 Bolting Cabinets Together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
ii
Page 5
7.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.0 LIEBERT INTELLISLOT® INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.1 Liebert IntelliSlot Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.2 Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . 78
8.2.1 Liebert IntelliSlot® Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP . . . . . . . . 79
8.3 Liebert IntelliSlot Card Web Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.4 Liebert IntelliSlot
8.4.1 Liebert IntelliSlot Relay Card Pin Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
8.4.2 Liebert IntelliSlot
®
Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
®
Relay Card Jumper Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
8.5 Liebert IntelliSlot™ MultiPort Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.6 Alber
®
BDSi™ Battery Monitoring System—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.7 Battery Temperature Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.0 OPERATOR CONTROL AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
9.1 Operator Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.2 Mimic Display Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.3 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.4 Alarm Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.5 LCD Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.6 Navigation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.7 LCD Menus and Data Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.8 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.9 Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.10 UPS History Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11 Types of LCD Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11.1 Opening Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.11.2 Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.11.3 UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.11.4 Screen Saver Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12 Pop-Up Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.1 From Bypass to Inverter Mode With Power Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.2 From Inverter to Bypass Mode With Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.12.3 System Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.4 Battery Capacity Test Confirmation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.5 Battery Self-Test Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.6 Battery Equalize Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.7 Battery Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.8 Battery Refresh Charge Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.12.9 Enter Control Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
10.1 Liebert APM Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
10.2 UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10.2.1 Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
10.2.2 Startup in ECO Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.2.3 Switching Between UPS Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
iii
Page 6
10.3 UPS Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10.4 Switching the UPS from Normal Operation to Maintenance Bypass . . . . . . . . . . . . . . . . . 103
10.5 Switching the UPS from Maintenance Bypass to Normal Operation . . . . . . . . . . . . . . . . . 104
10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . 105
10.7 De-Energize Liebert APM Without Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . 106
10.8 Operation of Two Liebert APM Units in Parallel Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
10.8.1 Procedure to Take UPS1 Offline While Leaving UPS2 Online . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.2 Procedure to Put UPS1 Back Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.3 Procedure to Take UPS2 Offline While Leaving UPS1 Online . . . . . . . . . . . . . . . . . . . . . . . 108
10.8.4 Procedure to Put UPS2 Back Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
10.9 APM Procedure from Parallel Inverter Operation to Wrap-Around Bypass . . . . . . . . . . . 109
10.10 APM Procedure from Wrap-Around Bypass to Parallel Inverter Operation . . . . . . . . . . . 109
10.11 Parallel APM System Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.12 Parallel APM System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
10.13 Emergency Shutdown With EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.14 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.15 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . 110
10.16 Battery Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.16.1 Battery Undervoltage Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.16.2 Battery End-of-Discharge (EOD) Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.17 Replacing Dust Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
10.18 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
10.19 Static Bypass Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
11.0 SPECIFICATIONS AND TECHNICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.1 Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.2 UPS Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.3 Batteries Approved for Use in Liebert APM Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
11.4 UPS Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
12.1 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.2 Limited Life Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3 Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3.1 Record Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.3.2 Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3.3 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3.4 Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.3.5 Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12.4 Detecting Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.5 Reporting a Problem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.6 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.7 Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
APPENDIX A-HAZARDOUS SUBSTANCES OR ELEMENTS ANNOUNCEMENT . . . . . . . . . . . . . . . A129
APPENDIX B-UPS STATUS MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A130
iv
Page 7
FIGURES
Figure 1 Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 2 Liebert FlexPower assembly indicators and controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 3 Static bypass assembly connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 4 Single UPS block diagram—dual input single source configuration . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 5 Liebert APM in a split bypass configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 6 Control wiring for the dual input transformer configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 7 Input busbars—Liebert APM 45kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 8 Input busbars—Liebert APM 90kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 9 Liebert BDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 10 Busbars—Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 11 Busbars—External 600mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 12 Busbars—External 900mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 13 Accessory fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used. . . . . . . . . . . . . 27
Figure 15 Ground and neutral busbar connections—45kVA frame busbars . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 16 Ground and neutral busbar connections—90kVA frame busbars . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 17 Static bypass assembly connections to display cabinet and options . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 18 Auxiliary terminal block detail (static switch assembly front panel) . . . . . . . . . . . . . . . . . . . . . . 33
Figure 19 Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 20 Output dry contacts and EPO wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 21 EPO wiring and signal names for J6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 22 Single UPS Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 23 UPS system with external maintenance switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 Input breaker control wiring for parallel systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 25 Output breaker control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 26 Connection of parallel control cables of parallel system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 27 Key interlock system control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 28 Locations of ports J1, J2 and J3 on bypass module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 29 Remote Emergency Power Off wiring for parallel UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 30 Typical dual bus system (with STS and LBS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 31 Connection of typical dual bus system of two parallel systems . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable . . . . . 45
Figure 33 Connection of typical dual bus system of two single UPS’s with redundant LBS cable . . . . . . . . 45
Figure 34 Internal battery breaker component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 35 Internal battery control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 36 Bolting the battery cabinet to the Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 37 Battery cabinet, 600mm wide—details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 38 Battery trays for 600mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 39 Battery cabinet with trays for 900mm battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 40 Battery cabinet connection to Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 41 Battery ground fault detection component location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 42 Control wiring diagram for battery ground fault detection option . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 43 Single input UPS with external Liebert BDCwith optional internal transformer—typical
configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 44 Liebert BDC—access plate removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 45 BDC connection to Liebert APM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 46 Bolting Liebert APM to a Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 47 UPS dimensions- front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs . . . . . . . . . . . . . . . . . . . . . . . 62
v
Page 8
Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views . . . . . . . . . . . . . . . . . 63
Figure 50 Liebert APM with top fan kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Figure 51 UPS main components—typical unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Figure 52 UPS cable connections—45kVA and 90kVA frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 53 Battery cabinet connection to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 54 Battery cabinet connection to UPS (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Figure 55 Battery cabinet outline drawing, weights and center of gravity, 600mm cabinet . . . . . . . . . . . . 72
Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet . . . . . . . . . . . . . 73
Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 58 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 59 Liebert BDC connection to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 60 Acceptable hardware configuration for torque application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Figure 61 Seismic mounting bracket details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 62 Liebert IntelliSlot Web card display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 63 Pin location and numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Figure 64 Jumper location and numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 65 Liebert IntelliSlot MultiPort card pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Figure 66 Alber BDSi controller and input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Figure 67 Multi-temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Figure 68 Overview of control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 69 Mimic display indicators location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Figure 70 Control button layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 71 Alarm buzzer location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 72 Sections of the LCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 73 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 74 Language selection screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 75 Date and time screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 76 History log records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 77 Opening display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 78 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 79 Screen saver window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 80 Battery start button location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Figure 81 Typical configuration for single UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Figure 82 Liebert APM six-breaker buyout paralleling configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 83 Dust filter replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Figure 84 Single module block diagram—Single input configuration with three-breaker
Liebert BDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Figure 85 Single module block diagram—Dual input configuration with three-breaker Liebert BDC . . . 113
Figure 86 Block diagram—Single input configuration with four-breaker internal bypass. . . . . . . . . . . . . 114
Figure 87 Battery, circuit breaker and UPS wiring with external batteries with four connecting
wires. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Figure 88 Battery, circuit breaker and UPS wiring with external batteries with three connecting
wires. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
vi
Page 9
TABLES
Table 1 Battery voltage, nominal and float . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2 Battery retorque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 3 LED indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 4 Description of dry contact input port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 5 Output dry contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 6 Liebert BDC interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 7 Battery cabinet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 8 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 9 Control wiring for Liebert APM to battery cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 10 Control wiring for Liebert APM UPS to Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 11 Center of gravity and weights for Liebert APM 90 kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Table 12 Center of gravity and weights for Liebert APM 90 kVA frame with top fan option . . . . . . . . . . . 66
Table 13 Center of gravity and weights for Liebert APM 45 kVA frame with top fan option . . . . . . . . . . . 67
Table 14 Center of gravity and weights for Liebert APM 45 kVA frame . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 15 Interconnect wiring for Liebert APM to battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 16 Battery cabinet, center of gravity and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Table 17 Interconnect wiring for Liebert APM to Liebert BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table 18 Spring washer torque application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Table 19 Liebert APM communication options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Table 20 Relay card pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Table 21 Jumper connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Table 22 Descriptions of UPS operator control and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Table 23 Mimic display status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Table 24 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Table 25 Icons for navigation keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Table 26 UPS menus and data window items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Table 27 Dip switch matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Table 28 Mimic indicators for normal mode operation with battery breaker open . . . . . . . . . . . . . . . . . . 101
Table 29 Mimic indicators for normal mode operation with battery breaker closed . . . . . . . . . . . . . . . . . 101
Table 30 Mimic indicators after initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table 31 UPS operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Table 32 Environmental requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Table 33 UPS mechanical characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Table 34 45kVA Liebert BDC mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 35 90kVA Liebert BDC mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 36 600mm battery cabinet mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Table 37 Batteries approved for use in External Battery Cabinet, 600mm . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 38 Batteries approved for use in External Battery Cabinet, 900mm . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 39 Internal batteries approved for use with 45kVA frame Liebert APM . . . . . . . . . . . . . . . . . . . . . 117
Table 40 900mm battery cabinet mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 41 UPS currents and terminals—Input (for single-input unit, 208V operation) . . . . . . . . . . . . . . . 118
Table 42 UPS currents and terminals—Input (for dual-input unit only, 208V operation) . . . . . . . . . . . . 118
Table 43 UPS currents and terminals—Bypass input (for dual-input units, 208V operation) . . . . . . . . . 118
Table 44 UPS currents and terminals—Battery (288V string) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 45 AC/AC efficiency, loss and air exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 46 UPS currents and terminals—Output 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Table 47 Battery DC intermediate circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table 48 Rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table 49 Bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
vii
Page 10
Table 50 Inverter output to critical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Table 51 Component service life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Table 52 Battery voltage record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 53 Terminal block with compression lugs (for control wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 54 Battery retorque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Table 55 Recommended test equipment and tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Table 56 Hazardous substances or elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table 57 UPS status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
viii
Page 11

IMPORTANT SAFETY INSTRUCTIONS

!
!

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of the Liebert APM, Liebert Bypass Distribution Cabinet
Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
A properly trained and qualified electrical contractor should oversee the installation of the equipment.
The Liebert APM cannot be put into operation until it is commissioned by the manufacturer or authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty.
The Liebert APM is designed for commercial and industrial uses and cannot be used as life support equipment.
and batteries (where applicable).
WARNING
Risk of moving heavy equipment and electric shock. Can cause equipment damage, injury and death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg).
Determine unit weight and locate center of gravity symbols before handling the UPS. Test lift and balance the cabinet before transporting it. Never tilt equipment more than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
Risk of moving electric shock. Can cause equipment damage, injury and death.
As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure even after input power has been disconnected. The risk of contact with these voltages is minimized as the live component parts are housed behind a metal panel. Further internal safety screens make the equipment protected to IP20 standards. Never remove panels or covers or open doors that will expose internal components to contact.
Read and follow all warnings, cautions and safety and operating instructions to avoid serious injury or death from electric shock. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
1Liebert
®
APM
Page 12

Ground Leakage Currents

!
!
CAUTION
Risk of electric shock from high leakage current. Can cause injury, property damage and death.
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.
WARNING
Risk of electric shock. Can cause injury, property damage and death. Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the internal batteries (internal batteries accommodated by 45kVA frame only). Observe all safety precautions in this manual before handling or installing the UPS system as well as during all maintenance procedures. Observe all battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with AC and DC voltmeters to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.
Liebert® APM
NOTICE
Risk of improper ground connection. Can cause equipment damage. Ground connection is essential before connecting the input supply. This equipment must be
grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label.
NOTICE
Risk of improper improper electromagnetic shielding. Can cause radio communication interference.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting.
2
Page 13

Battery Cabinet Precautions

!
!
The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in 5.0 - Battery Installation.
WARNING
Risk of improper handling. Can cause injury, property damage and death. Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).

Battery Hazards

WARNING
Risk of electric shock. Can cause injury, property damage and death. Special care should be taken when working with the batteries associated with this equipment.
Batteries are always live. Battery terminal voltage will exceed 300VDC and is potentially lethal.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns.
Batteries should be installed, serviced and replaced only by properly trained and qualified service personnel trained in safe battery handling methods and who have the correct PPE (Personal Protection Equipment) and tools.
The following precautions should be observed when working with the batteries:
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and boots.
• When replacing batteries, replace them with the same type and number of batteries or bat­tery packs.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
• Never lay metal objects of any type on top of the batteries.
• Disconnect the charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
3Liebert
®
APM
Page 14

GLOSSARY OF SYMBOLS

!
PbH2SO4
-
+
R
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
AC voltage
Equipment grounding conductor
Bonded to ground
Liebert® APM
4
Page 15

1.0 INTRODUCTION

!
!
The Liebert APM UPS is a transformer-free, hardware-scalable, online uninterruptible power system with 208/120V input and 208/120V output capability. The Liebert APM can operate with either a 50 or 60Hz input and provide a matching output frequency conversion. The rack-mounted 15kVA/kW modules allow scaling the UPS’s capacity in 15kVA increments from 15kVA to a maximum of 90kVA in a single frame.
Optional transformers are available to add 208V Isolation or 480V or 600V input capability to the Liebert APM in both the UPS, 90kVA/kW frame only, or the Bypass Distribution Cabinet (BDC) in either the 45kVA/kW or the 90kVA/kW frame.
The Liebert APM UPS is a SmartAisle approach.
The Liebert APM provides continuous, high-quality AC power to business-critical equipment, such as telecommunications and data processing equipment. The Liebert APM supplies power free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The Liebert APM utilizes the latest in high-frequency, double-conversion pulse width modulation (PWM) technology and fully digital controls to enhance its reliability and increase the ease of use.
Two frame sizes are available: 45kVA/kW and 90kVA/kW. The 45kVA/kW frame is designed to accept internal batteries; the 90kVA/kW frame does not. The 90kVA frame is, however, designed to accept Internal Transformers and a four-breaker bypass.
Introduction
technology, appropriate for use with the SmartAisle design

Output Voltage Adjustment

This feature allows a Liebert Customer Engineer to adjust the output voltage over a range of -5% to +16% of nominal. This permits compensation for any IR drop when the UPS is a significant distance from the protected load. Output voltage adjustment can optimize the UPS output voltage for loads that operate more efficiently at a UPS output voltage different from the Liebert APM’s standard output voltage.

1.1 Battery Maintenance

WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death.
These maintenance procedures will expose hazardous live parts. Refer servicing to properly trained and qualified personnel working in accordance with applicable regulations as well as with manufacturers’ specifications.

1.1.1 Battery Safety Precautions

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and recycled or discarded in accordance with federal, state and local regulations. Because lead is a toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is toxic.
®
5Liebert
APM
Page 16
Introduction
!
!
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death.
The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition, the electrical connections must be protected against accidental short circuits which can cause sparks. The following procedures should be followed:
• DO NOT SMOKE when near batteries.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the jars in place on the shelves. This will limit accidental movement of the jars and connectors should the cabinet ever need to be repositioned or relocated.
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery and terminal voltages, specific gravity and connection resistance should be made. Strictly follow the procedures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.
Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although maintenance of electrolyte levels is not required, visual inspections and checks of battery voltage and connection resistance should be made.
NOTICE
Risk of equipment damage. Batteries should be cleaned with a dry cloth or a cloth lightly moistened with water. Do not use cleaners on the batteries. Solvents can make the battery cases brittle.
Because individual battery characteristics are not identical and may change over time, the UPS module is equipped with circuitry to equalize battery cell voltages. This circuit increases charging voltage to maintain flooded type battery cells at full capacity.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries, such as those in Liebert Battery Cabinets. Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for specific information about equalize charging.
Liebert® APM
6
Page 17
Introduction
Matching Battery Cabinets—Optional
Although the individual battery cells are sealed (valve-regulated) and require only minimal maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks should be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS operating, measure and record battery float voltage. With the DC circuit breaker open, measure and record the nominal (open circuit) voltage. Both these measurements should be made across the final positive and negative terminal lugs. Compare these values with those shown below. The recorded nominal voltage should be no less than the value shown; while the recorded float voltage should be within the range shown. If a discrepancy is found, contact Liebert
Table 1 Battery voltage, nominal and float
Battery Voltage, VDC
Nominal/
Number of Cells
144 288 324
Open Cell Float
Power Connections: Check for corrosion and connection integrity. Inspect wiring for discolored or cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 2.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more than the retorque value. Table 2 shows battery retorque values.
Table 2 Battery retorque values
Battery Mfr. Battery Model # Retorque Value
HX205-FR 65 in-lb HX300-FR 65 in-lb HX330-FR 65 in-lb
Enersys
HX400-FR 65 in-lb HX500-FR 65 in-lb HX540-FR 65 in-lb 16HX800F 100 in-lb 16HX925F 100 in-lb
If the system uses a different model battery, contact Liebert
Services.
Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts. The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value. When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and insulate the cables connected to the battery. Secure each battery shelf with retaining screws when maintenance is complete.
Other DC Sources
If the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform maintenance on the DC source as recommended in the DC source manufacturer’s maintenance manual, available on the manufacturer’s Web site.
7Liebert
®
APM
Page 18

2.0 INSTALLATION

!
This section describes the Liebert APM’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because each site is unique, this section presents a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.
WARNING
Risk of electric shock. Can cause injury, property damage and death. Special care should be taken when working with the batteries associated with this equipment.
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves. If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
Installation
NOTICE
Risk of improper installation. Can cause equipment damage. Do not apply electrical power to the UPS equipment before the commissioning engineer
arrives at the installation site. The UPS must be installed by a properly trained and qualified engineer in accordance with
the information contained in this chapter. All the equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information.
NOTE
Three-phase, four-wire input power is required.
NOTE
Input power must be supplied to the Liebert APM from a properly grounded Wye or Delta source. The Liebert APM is not for use with impedance grounded systems, corner-grounded systems or high-leg Delta systems. For these applications, an isolation transformer must be installed between the input power and the Liebert APM.
Liebert® APM
8
Page 19

2.1 Initial Inspections

!
!
1. While the Liebert APM and ancillary cabinets are still on the truck, inspect the equipment and shipping container for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency immediately and contact Liebert Services at 1-800-LIEBERT to inform them of the damage claim and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Emerson representative immediately.
3. Check the product label on the back of front door and confirm the contents match the UPS model, capacity and main parameters that were ordered.

2.1.1 Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the Liebert APM from excessive moisture (see 11.2 - UPS Environmental).
CAUTION
If the UPS must remain disconnected from power for more than six (6) months, the batteries (if so equipped) must be recharged before use. To charge the batteries, the unit must be connected to utility power and started up—the charger operates only while the Liebert APM is operating.
Installation
CAUTION
When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS, the battery—not the UPS—dictates the designed maximum ambient temperature.

2.2 Preliminary Checks

2.2.1 Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

2.3 UPS Location

2.3.1 Positioning the UPS

Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
®
9Liebert
APM
Page 20

2.3.2 Environmental Considerations

!
!
Before installing the Liebert APM, verify that the UPS room satisfies the environmental conditions stipulated in 11.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating temperature within the range of 74-80°F, (23-27°C).
The Liebert APM is cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the back. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. The UPS requires 24 in. (610mm) ventilation clearance above the unit and 12" (305mm) behind the UPS.
See Table 46 for details on heat dissipation.
Battery Location
Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce battery life; temperatures below this reduces battery capacityv. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.
Installation

2.4 Considerations in Moving the Liebert APM

Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any handling equipment. See Table 33 for weights of various units.
The Liebert APM may be rolled on its casters for short distances only. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
The optional battery cabinets should be moved with a forklift or similar equipment.
WARNING
Risk of moving heavy unit. Can cause property damage, injury and death. Ensure that any equipment that will be used to move the Liebert APM has sufficient lifting
capacity. The Liebert APM’s weight ranges from 800 to 3500 lb. (363 to 1590kg). See Table 33 for details.
The UPS presents a tipping hazard. Do not tilt the Liebert APM more than 15 degrees from vertical.
The UPS is fitted with casters—Take care to prevent movement when unbolting the equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are available when taking the Liebert APM off its shipping pallet.
WARNING
Risk of heavy unit tipping over while being moved. Can cause property damage, injury and death.
The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a minimum. For further information, see Battery Cabinet Precautions on page 3.

Final Positioning

When the equipment has been finally positioned, ensure that the adjustable stops are set so that the UPS will remain stationary and stable (see 7.0 - Installation Drawings).
The Liebert APM and its auxiliary cabinets must be installed on a concrete or equivalent, non­resilient floor.
Liebert® APM
10
Page 21

2.5 Mechanical Considerations

!
The Liebert APM is constructed with a steel frame and removable panels. Top and side panels are secured to the chassis by screws. The doors may be opened for access to power connections bars, auxiliary terminals blocks and power switches.
The UPS comes with an Operator Control Panel that provides basic operational status and alarm information. The cabinet houses both the power components and the internal batteries. Cooling is provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the UPS from moving once it has been moved to its final position.
WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and death.
The Liebert BDC Improper lifting may cause the cabinets to fall, causing personal injury or death and equipment damage.
Emerson recommends lifting the units with one of the following methods:
• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.
• Placing suitable straps on the Liebert BDC the unit to be lifted.
and battery cabinets must be properly prepared and secured for lifting.
Installation
or battery cabinet. The straps must go under

2.5.1 Clearances

There are no ventilation grilles on the sides of the UPS. The sides must be accessible during installation. After installation, the unit must have a clearance of 12 in. (305mm) in the rear to permit adequate circulation of air exhausted from the UPS. The Top Fan option eliminates the 12" (305mm) rear clearance requirement, but it increases the Liebert APM’s height by 7.63" (194mm).
To enable routine tightening of power terminations within the UPS, make sure there is sufficient clearance in front of the Liebert APM to permit free passage of personnel with the door fully opened.
Leave a minimum of 24 in. (610mm) between the top of the UPS frame and the ceiling to permit adequate air circulation above the unit. Emerson recommends against using air conditioning or other systems that blow air onto the top of the unit.

2.5.2 Floor Installation

If the Liebert APM, Liebert BDC or battery cabinet is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in Figures 49, 55 or 58 to design this pedestal.

2.5.3 Cable Entry

Cables can enter the Liebert APM, Liebert BDC and battery cabinets from the top or bottom through removable metal plates.
Some plates have factory-punched holes and others are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS. The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70.
The UPS must be accessible from the right side to allow personnel to complete the cable connections and make necessary adjustments. After installation is complete, the Liebert APM may be serviced from the front.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS.
11 Liebert® APM
Page 22

2.5.4 Special Considerations for Parallel Systems

1. Consider the grounding configuration of the UPS system before finalizing module placement. For optimal ground performance, the Liebert APM modules should be close together. See 3.2.6 - Cabling Guidelines.
2. For optimal load-sharing performance, the UPS bypass input cables and output cables should be approximately the same length, ±10 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring between UPS modules and the paralleling cabinet.
Refer to 4.0 - Parallel System and LBS System Installation for further information on installing a parallel system.

2.5.5 Special Considerations for 1+N Parallel Systems

Consider the grounding configuration of the UPS system before finalizing module placement. See
3.2.6 - Cabling Guidelines.
Emerson recommends matching the impedance in the bypass path of paralleled systems as closely as possible.
The impedance mismatch can be minimized by controlling the wiring length of each unit. The design and the layout of the UPS system and associated panels and cabling should be examined closely to ensure that cable lengths and impedances are closely matched. The Liebert 1+N UPS module is supplied with a sharing reactor to minimize the impact of cable impedance mismatch. The cabling impedance must be carefully controlled to ensure good bypass current sharing.
Installation
For Liebert APM systems, the cabling impedances must be within 10% from maximum to minimum. If the cabling impedances must be greater than 10%, contact your Emerson representative to calculate whether the system will result in an overload condition when operating on bypass.
When bringing the 1+N system online for the first time or after removing one unit, Emerson recommends checking the bypass current mismatch. To check the bypass current mismatch:
1. Place a load on the bypass of each UPS module.
2. View the output current of each unit.
The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch is greater than 10%, the bypass impedances must be balanced or the load must be limited to less than the maximum rating.

2.6 45kVA and 90kVA UPS Frames—Auxiliary Cabinets

The 45kVA frame consists of a single cabinet housing the UPS components and the internal battery string. The 90kVA frame, also a single cabinet, does not accommodate internal batteries, but does provide for an internal four-breaker bypass or an internal transformer. The internal transformers are available with 480V:208V; 600V:208V; or 208V:208V isolation input primaries.
Optional battery cabinets are available for each Liebert APM model to provide extended run time. Each battery cabinet houses a single string of batteries per cabinet that operate in parallel with the Liebert APM’s internal batteries (45kVA frame only). The battery cabinets are designed to be bolted to the left side of the UPS (see Figure 1). Refer to 5.4 - External Battery Cabinet Installation for details.
Optional Liebert BDC provide an external wraparound maintenance bypass switch for servicing the UPS.
Liebert BDCs are designed to be bolted to the right side of the UPS (see Figure 1). Refer to 6.4 - Locating the Cabinet for further details.
units are available. These cabinets house the components necessary to

System Composition

A UPS system can comprise a number of equipment cabinets, depending on the system design requirements—e.g., UPS cabinet, External Battery Cabinet and External Bypass Cabinet. All cabinets used will be the same height and will be designed to be positioned side-by-side to form an aesthetically appealing equipment suite.
Liebert® APM
12
Page 23

2.6.1 Optional Cabinets

Liebert
APM
Bypass
Distribution
Cabinet
Bypass
Distribution
Cabinet
Liebert
APM
Battery
Cabinet
Battery Cabinet
Liebert
APM
Battery
Cabinet
Liebert APM connected only to Liebert BDC
(BDC must be on right side of the Liebert APM)
Liebert APM connected to Liebert BDC and Battery Cabinets
(BDC must be on right side of the Liebert APM)
(Battery Cabinets must be on the left side of the Liebert APM)
ALL UNITS VIEWED FROM ABOVE
Liebert APM connected to Battery Cabinet (Battery Cabinets
must be on the left side of the Liebert APM)
If the Liebert APM installation includes a Liebert BDC, the UPS must be positioned to allow the Liebert BDC to be bolted to right side of the Liebert APM (see Figure 1).
The Liebert BDC must be cabled and bolted to the Liebert APM before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Liebert BDC ONLY after the units are connected and positioned.
Battery cabinets may be bolted only to the left side of the Liebert APM; see Figure 1.
Figure 1 Cabinet arrangement
Installation

2.7 Optional Seismic Brackets

Optional seismic mounting brackets to anchor the Liebert APM, Liebert BDC™ and battery cabinet to the floor are available. Refer to Figure 61 for mounting details.
13 Liebert® APM
Page 24

2.8 Liebert FlexPower™ Assembly

Run LED
Battery Start Button
Ready Switch
Fault LED
DIP Switches
Input/output dry contact and EPO/BCB/MBC interface
J1
J4 J7
J10
MFP_O
MFP_S
MFP_C
J11
INPUT_2
INPUT_1
OUT
GND
J8
+12V
BAT-IN
BAT-OUT
GND
J5
PARA
J2
BCB_IN
DRIVER
GND
ONLINE
Q2BP
Q3BP
EXT-OUT
GND
J9J6
J3
PARA
BFP_O
BFP_S
BFP_C
J12
INV_O
INV_S
INV_C
BAT_GND
ENV_DET
BAT_READY
+12V
+12V
EPO-NC
+12V
EPO-NO
LBS
MONITOR
RS485-2RS485-1
RS232
INTELLISLOT3INTELLISLOT2INTELLISLOT1
J1 ~ J3 port can’t connect to phone!
J10
J7
J5
J6
J8
J9
RS-232
Liebert IntelliSlot Bays 1, 2, 3
RS-485
J4
J11
J12
Monitor
J3
J1
J2

Figure 2 Liebert FlexPower assembly indicators and controls

The Battery start button allows starting of UPS on battery; refer to 10.3 - UPS Battery Start. The Run LED is illuminated Green when the Liebert FlexPower assembly is operating normally. The Fault LED will illuminate red when the Liebert FlexPower assembly has a problem.

Table 3 LED indications

LED Status Indication
Run LED (Green)
Flashing Green The inverter is starting, but has no output yet.
Constant Green The inverter has started to supply power.
OFF The inverter has not started up.
Fault LED (Red)
Auxiliary power failure (15V or 24V), rectifier overtemperature, rectifier failure (including battery SCR short circuit), battery converter failure, soft start failure, main circuit back feed, abnormal
Constant Red
Flashing Red
input current, inverter failure, output short circuit, bypass SCR short circuit fault, inverter relay short circuit fault, abnormal bus voltage under non-sleep mode, module not ready, module ID out of range and duplicated module ID.
Charger failure, abnormal main circuit voltage, abnormal main circuit frequency, main circuit undervoltage, main circuit reverse phase, battery unavailable, reverse battery, input zero-loss, current sharing failure, module overload, inverter relay disconnection fault, bypass SCR disconnection fault and input fuse blown.
Installation
OFF No above failures or alarms.

2.9 Static Bypass Assembly

Figure 3 Static bypass assembly connections

The Static bypass assembly has three Liebert IntelliSlot interface card bays and connections for ancillary cabinets (Liebert BDC and battery) and for options.
Liebert® APM
14
Page 25

3.0 ELECTRICAL CONNECTIONS—UPS

!
The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.
WARNING
Risk of electric shock. Can cause property damage, injury and death.
Before connecting input power to the Liebert APM, ensure that you are aware of the location and operation of the overcurrent protection devices that connect the UPS input/bypass supply to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before installing cables or making any electrical connections.

3.1 Power Cabling

3.1.1 Cable Rating

The main factors affecting the choice and size of cable are voltage, current (also taking into account overcurrent), room temperature and conditions of installation of the cable. Refer to ANSI/NFPA 70.
The power cables of the system must be sized with respect to the following description:
Electrical Connections—UPS
UPS input cables - The UPS input cables must be sized for the maximum input current, including the maximum battery recharge current, given in Table 41, with respect to the unit rating and the input AC voltage.
UPS bypass and output cables - The bypass and output cables must be sized for the nominal output current, given in Table 41, with respect to the unit rating and the output AC voltage.
Battery cables - Each UPS unit has its own internal batteries factory-wired. If connecting an external battery cabinet, the battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 41, with respect to the unit rating.
NOTE Table 41 gives nominal currents for determining the size of UPS power cables. Other
important factors to consider include cable route length and coordination with protective devices.
The power cables can be sized to suit the UPS unit rating according to Table 41.
Lug Size and Torque Requirements
Refer to Table 41 for lug size and torque requirements and to Table 18 and Figure 60.

3.2 External Protective Devices

For safety concerns, it is necessary to install external circuit breakers or other protective devices for the input AC supply of the UPS system. This section provides generic practical information for qualified installation engineers. The installation engineers should be knowledgeable about regulatory wiring standards and the equipment to be installed.
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection in accordance with NEC ANSI/NFPA 70.
15 Liebert® APM
Page 26

3.2.1 Rectifier and Bypass Input Supply of the UPS

Overcurrents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power cable current-carrying capacity and overload capacity of the system. Generally, the magnetic circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the nominal current listed in Table 41 is recommended.
Split bypass: In case a split bypass is used, separate protective devices should be installed for the rectifier input and bypass input in the incoming mains distribution panel.
NOTE
The rectifier input and bypass input must use the same neutral line.
For an IT power network system, a 4-pole protective device must be installed on the external input distribution and external output distribution of the UPS.
Earth Leakage, RCD Devices
Any residual current detector (RCD) installed upstream of the UPS input supply:
• Must be sensitive to DC unidirectional pulses (Class A)
• Must be insensitive to transient current pulses, and
• Must have an average sensitivity, adjustable between 0.3 and 1A.
To avoid false alarms, earth leakage monitoring devices when used in systems with split bypass input or when used in paralleled UPS configurations, must be located upstream of the common neutral sinking point. Alternatively, the device must monitor the combined four-wire rectifier and split bypass input currents.
Electrical Connections—UPS
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than
3.5mA and less than 300mA. Liebert recommends verifying the selectivity with all other differential devices both upstream of the input distribution board and downstream (toward the load).

3.2.2 External Battery

The DC-compatible circuit breaker provides overcurrent protection for UPS system and battery, which is provided by the external battery cabinet.

3.2.3 UPS Output

If an external distribution panel is used for load distribution, the selection of protective devices must provide discrimination with those that are used at the input to the UPS (see Table 47).
Liebert® APM
16
Page 27

3.2.4 UPS Input Configuration

By default, the Liebert APM ships with internal links installed between the bypass input and main (rectifier) input (single input configuration see Figure 84).
Figure 4 shows the Liebert APM in a split bypass (single source dual-input) configuration. In this configuration, the static bypass and the maintenance bypass lines are supplied by the same source using separate feeds. Both feeds must be protected externally with properly sized protective devices.
To wire the Liebert APM as a single source dual-input UPS, remove the links and wire the bypass feed to the bypass busbars, then wire the main feed to the main busbars (see Figure 8).
Figure 4 Single UPS block diagram—dual input single source configuration
Bypass Distribution Cabinet
Electrical Connections—UPS
* Bypass AC Input
BIB
MBB
4-Wire + GND
Static Bypass
* Rectifier
AC Input
4-Wire + GND
See Note 7
UPS Cabinet
Battery
NOTES
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, 400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.
Optional
MIB
54-Pole
See Note 6
BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by others
Field-Supplied Wiring
AC Output
4-Wire + GND
UAM01023 Rev. 3
208V
17 Liebert® APM
Page 28

3.2.5 UPS Input Configuration with Transformers

AC Output 208V 4 Wire + GRD
* Rectifier AC Input 4 Wire + GRD See Note 7
* Bypass AC Input 4-Wire + GRD
Bypass Distribution Cabinet
(Optional) 54 Pole See Note 6
MIB
BIB
MBB
Static Bypass
UPS Cabinet
Battery
UAM01024 Rev. 0
NOTES:
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54 pole, 225A for 45kVA frame only or optional 54 pole 400A for 90kVA frame only.
7. Customer must supply shunt trip breaker with 120V coil.
8. Input voltage options of the isolation transformer: 600V, 480V, 220V and 208V.
BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker
Field-Supplied Wiring
* External Overcurrent Protection by Others
Figure 5 shows the Liebert APM in a split bypass (single-source, dual-input) configuration using two transformers. One transformer is inside the Bypass Distribution Cabinet and the other inside the UPS.
In this configuration, the static bypass and the maintenance bypass lines are supplied by the same source using separate feeds. Both feeds must be protected externally with properly sized protective devices.
Figure 6 shows the control wiring for the dual input transformer configuration.
Figure 5 Liebert APM in a split bypass configuration
Electrical Connections—UPS
Liebert® APM
18
Page 29
Figure 6 Control wiring for the dual input transformer configuration
UAM04047
Rev. 0
NOTES
1. Customer-furnished electrode conductor to be installed in
accordance with national and local electrical codes.
2. See installation manual for additional connection information.
3. Optional 54 pole, 225A for 45kVA frame only or optional 54 pole
400A for 90kVA frame only.
4. Transformer available: 208V, 220V, 480V and 600V input.
5. Overcurrent protection is based on 80% rated devices.
6. Ensure that the jumper bars between input and rectifier input
are removed before starting the unit for the first time.
7. See Drawing UAM02022.
SKRU - SOLENOID
KEY RELEASE UNIT
KO - KEY OPERATOR
Field-Supplied Wiring
Factory-Supplied Wiring
* Customer
must supply
shunt trip to
rectifier
input breaker
with 120V coil
RIB
Rect.
Rect. Input
Input
Input Neutral
GRD
ØAØBØC
ØA
Ø to
ØB
ØC
Utility
Customer
Main Input
Busbars
To
Bypass
Input
MBB
W06
W04
W05
Kirk
Key K1
Kirk
Key K2
Liebert
APM UPS
UPS AC
Output
Bypass Input
N
A
B
C
N
PE
A
B
C
1
W88
W89
W90
W91
W85
W84
W86
W08
W09
W07
BIB
MIB
W87
W83
Main Ground Busbar
Ground
To Unit
Frame
Output
Ground
Output
Neutral
AC Output
Ground
To Unit
Frame
2 Fuses, 2A
Inner Door
AC 120V
AC 120V
SKRU
K0
(Optional)
54 Pole
See Note 3
Bypass Distribution Cabinet
TB1
See Note 1
4
4
4
4
3
3
3
3
3
3
112
2
2
Electrical Connections—UPS
The external maintenance bypass is available with a 480V, 600V or 208V optional internal transformer. Each UPS frame size (45kVA or 90 kVA) is available with a 480V, 600V or 208V optional internal transformer. Internal batteries are not available for a 45kVA frame that has an the internal transformer.
19 Liebert® APM
Page 30

3.2.6 Cabling Guidelines

The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.
1. Take special care when determining the size of the neutral cable, as current circulating on the neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the values in 11.4 - UPS Electrical Characteristics.
2. The ground conductor should be sized according to such factors as the fault rating, cable lengths and type of protection. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit.
3. Consider using paralleled smaller cables for heavy currents—this can ease installation.
4. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in Table 43. For terminal connection sizing, see Tables 41 through 43.
5. In most installations, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
6. When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference.
Electrical Connections—UPS
NOTE
Right-side access may be required when making power connections. Cable connections should be made before a cabinet is attached to the right side of the Liebert APM or before the UPS is placed where another obstruction, such as a wall, is against the Liebert APM’s right side.

3.2.7 Cable Connections

The rectifier input, bypass output and battery are easily accessible from the right side of the unit for installation. All require lug type terminations. They are connected to busbars on the right side of the Liebert APM, as shown in Figures 7 and 8. These busbars are accessible when the right side panel is removed.
NOTICE
Risk of improper installation. Can cause equipment damage. When wiring a single-input only system, connect only the power wiring to the input busbars.
Liebert® APM
20
Page 31
Figure 7 Input busbars—Liebert APM 45kVA frame
1.65"
(42mm)
1.65"
(42mm)
1.6" (41mm)
1.75" (44mm)
1.75" (44mm) (Typ.)
1.52" (39mm) (Typ.)
3.54" (90mm) (Typ.)
ø
.55" (14mm)
4 places
ø
.50" (13mm)
2 places
.8" (20mm)
.8" (20mm)
.7" (18mm)
DETAIL D
Top View DC Busbars
DETAIL C
Top View Ground
ø
.50" (13mm)
Typ.
Main Input Busbars Same for Bypass and Output Busbars
Main Input Busbars
1.75" (44mm) Typ.
DETAIL A
DETAIL B
DC Busbars See Detail A
Ground
See Detail A
See
Detail B
37.5" (953mm)
31.5" (800mm)
BOTTOM VIEW
TOP VIEW
See
Detail D
78.7"
(2000mm)
Bypass Busbars
Output Busbars
2.36"
(60mm)
Typ. 2
Places
Battery
Breaker
2.2" (56mm)
Typ. 6 Places
1.97" (50mm) Typ. 3 Places
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.
FRONT VIEW
Door Removed
RIGHT SIDE VIEW
Panel Removed
Links for Main
to Bypass
(Single Input Only)
Electrical Connections—UPS
21 Liebert® APM
Page 32
Figure 8 Input busbars—Liebert APM 90kVA frame
UAM02021 Rev. 3
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
Electrical Connections—UPS
Liebert® APM
22
Page 33
Figure 9 Liebert BDC
UAM06020A Rev. 2
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Only copper cables are recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. If bypass distribution cabinet is attached to the UPS, Emerson will supply the interconnection cables.
6. See UAM06020B, Pg. 2 of 2.
BOTTOM VIEW
TOP VIEW
LEFT SIDE VIEW
Panel Removed
RIGHT SIDE VIEW
Panel Removed
FRONT VIEW
Door Removed
23.6" (600mm)
LDB
MIB
MBB
BIB
78.7"
(2000mm)
37.5" (953mm)
System Input Bus
Input/Output Neutral Bus
Ground Bus
See Detail A and Isometric View Detail B, Pg. 2 (Note 6)
Electrical Connections—UPS
23 Liebert® APM
Page 34
Figure 10 Busbars—Liebert BDC
Neutral Bus
5" x 8.9"
(127 x 227mm)
Ground Bus
5" x 4"
(127 x 102mm)
All
Busbars
Input/Outout
Bus Typical
1.5" x 8.9"
(38 x 227mm)
Ø .56"
(14mm)
Typical
Ø .56"
(14mm)
Typical
Ø .56"
(14mm)
Typical
1.75"
(44.5mm)
Typical
Ø .44"
(11mm)
Typical
UPS Bus
Ø .44" (11mm) Typical
Ø .44"
(11mm)
Typical
Input
Breaker
Input
Ground
Bus
System
Input
Busbar Located at Rear, Typ.
System
Input
Connections
Neutral Input/Output Connections
System
Input Bus
See Detail B
1.38" (35mm)
1.38" (35mm)
1.38" (35mm)
1.38" (35mm)
2.44" (62mm)
2.44" (62mm)
DETAIL A
DETAIL B
Iso View Front Left
with Corner Post Not Shown
UAM06020B Rev. 2
1. See UAM06020A, Pg. 1 of 2 (2) 225A or 400A panelboard.
2. See UAM06021A, Pg. 1 of 2 (2) 225A or (2) 150A subfeed breakers.
3. See UAM06022A, Pg. 1 of 2 without distribution.
Electrical Connections—UPS
Liebert® APM
24
Page 35
Figure 11 Busbars—External 600mm battery cabinet
.56" Dia.
(14.3mm)
.44" Dia.
(11.1mm)
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables onlyare recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. If battery cabinet is attached to UPS, Emerson will supply interconnect cables.
Top View
Bottom View
Left Side View
Panel Removed
Front View
Door Removed
Right Side View
Panel Removed
23.6"
(600mm)
37.5"
(953mm)
DC Connection Busbars
Alber Battery Monitoring
Ground Bus
See Detail A
78.7"
(2000mm)
UAM05020 Rev. 1
DETAIL A
3.66"
(93mm)
3.66
"
(93mm)
3.66
"
(93mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.65
"
(42mm)
1.65
"
(42mm)
4.96"
(126mm)
TERMINAL SPECIFICATIONS Unit Rating: 15-90kVA Bolt Shaft Size: M10 Torque: 240 lb-In (27Nm)
Electrical Connections—UPS
25 Liebert® APM
Page 36
Figure 12 Busbars—External 900mm battery cabinet
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
5. If the battery cabinet is attached to the UPS, Emerson will supply the interconnect cables.
UAM05022 Rev. 0
Alber Battery Monitoring
35.4" (900mm)
TOP VIEW
BOTTOM VIEW
78.7"
(2000mm)
.56" Dia. (14.3mm)
.44" Dia.
(11.1mm)
DETAIL A
See Detail A
Left Side View
Panel Removed
Front View
Door Removed
Right Side View
Panel Removed
37.5" (953mm)
DC Connection Busbars
Ground Bus
3.31"
(84mm)
3.31
"
(84mm)
1.75
"
(45mm)
1.75
"
(45mm)
1.65
"
(42mm)
1.65
"
(42mm)
1.75
"
(45mm)
Electrical Connections—UPS

3.2.8 Accessory Fuses and Backfeed Breaker Wiring

Two fuse blocks provide power for the backfeed breakers (standard) and the BDSi (optional). The fuse blocks are at the lower right of the front of the Liebert APM UPS. Refer to Figure 24 for additional details. See for fuse holder locations.
The backfeed breaker fuse block provides 120V nominal provided from the UPS output (L-N) and the fuse is rated for 8 amps. Figure 14 shows the backfeed breaker wiring.
Liebert® APM
The BDSi fuse block provides 208V nominal from the UPS output (L-L) and the fuse is rated at 8A. The BDSi power wiring is shown in Figures 40 and 66.
26
Page 37
Electrical Connections—UPS
BDSi Fuse Block (optional)
Backfeed Breaker Fuse Block
1. Auxiliary contacts not needed for backfeed breaker operation.
2. A 120V shunt trip coil is required for proper operation.
Dual Input Control Wiring
Upstream Bypass
Input Breaker
Upstream System
Input Breaker
Single Input Control Wiring
Backfeed Breaker Fuse Block (FH1)
Backfeed Breaker Fuse Block (FH1)
Upstream Rectifier
Input Breaker
APM Bypass Module
UAM04030 Rev. 3
MX
MX
AUX
AUX
J10
J11
2
C2
C2
C1
C1
2
3
3
N
PH B
J10
23
N
PH B
UHRF3S67X2 (J10, J11)
J10
J11
MX
AUX
J11
2
C2
C1
3
Figure 13 Accessory fuses
Figure 14 Dual input backfeed breaker wiring when bypass distribution cabinet not used
NOTE
Shunt trips are required in upstream breakers to allow backfeed protection to function properly.
27 Liebert® APM
Page 38

3.2.9 Safety Ground

!
The safety ground busbar is below the neutral input and output busbars as shown in Figure 15 below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in the system. This ground busbar is then connected to the ground electrode conductor (GEC).
All cabinets and cable conduit should be grounded in accordance with local regulations.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury anddeath. Failure to follow proper grounding procedures can result in electric shock hazard to personnel
or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces problems caused by electromagnetic interference.
NOTE
The ground and neutral busbars are easily accessible when the right side panel is removed. Cable connections should be made before a cabinet is attached to the right side of the Liebert APM or before the UPS is placed where another obstruction, such as a wall, is against the Liebert APM’s the right side.
Electrical Connections—UPS
Liebert® APM
28
Page 39
Figure 15 Ground and neutral busbar connections—45kVA frame busbars
A
1.65"
(42mm)
.8" (20mm)
Top View DC Busbars
DETAIL D
TOP VIEW
1.75" (44mm)
ø .50" (13mm)
2 places
1.6" (41mm)
See
Detail D
1.75" (44mm)
1.65"
(42mm)
3.54" (90mm) (Typ.) .7" (18mm)
DETAIL C
Top View Ground
BOTTOM VIEW
(Typ.)
1.52" (39mm) (Typ.)
ø .55" (14mm)
4 places
.8" (20mm)
Electrical Connections—UPS
ø .50" (13mm)
Typ.
Main Input Busbars Same for Bypass and Output Busbars
1.75" (44mm) Typ.
78.7"
(2000mm)
31.5" (800mm)
Battery Breaker
See
Detail B
FRONT VIEW
Door Removed
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring must be in accordance with national and local electrical codes.
37.5" (953mm)
RIGHT SIDE VIEW
Panel Removed
DETAIL A
2.2" (56mm)
Typ. 6 Places
1.97" (50mm) Typ. 3 Places
2.36"
(60mm)
Typ. 2
Places
(Single Input Only)
DETAIL B
Links for Main
to Bypass
Main Input Busbars
Bypass Busbars
Ground
See Detail
Output Busbars
DC Busbars See Detail A
29 Liebert® APM
Page 40
Figure 16 Ground and neutral busbar connections—90kVA frame busbars
UAM02021 Rev. 3
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
Electrical Connections—UPS
Liebert® APM
30
Page 41

3.2.10 Protective Devices

!
For safety, it is necessary to install circuit breakers in the input AC supply external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating practices, regulatory standards and the equipment to be installed.
UPS Rectifier and Bypass Input Supply
Protection from excessive overcurrents and short circuits in power supply input
External overcurrent protection for the AC output circuit is to be provided. See 11.4 - UPS Elec­trical Characteristics and Table 47 for overload capacity.
A breaker is used for internal battery circuit overcurrent protection. When an external battery supply is used, overcurrent protection for the battery circuit is to be provided by the customer.
• Dual Input Single Source
When wiring the UPS with dual inputs but with a single input source, the Rectifier input and the Bypass input must be protected separately. Size the breakers according to the input currents shown in Table 41.
NOTE
For single or dual input, a 120V shunt trip coil(s) is required when a breaker is supplied by the customer. See Figures 4 and 5 for details.
Fuses
Electrical Connections—UPS
The Liebert APM’s main input and bypass input busbars are equipped with fuses (six locations; see Figure 51). The type is Bussman 170M4465, rated at 550A and 700V.
System Output
When using an external distribution panel for load distribution, the output neutral and input neutral must be separated at the input to the UPS.

3.2.11 Cabling Procedure

CAUTION
The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulties, contact your local Emerson representative or Liebert Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground lugs have been connected (see 3.2.7 - Cable Connections), connect the power cables as described below. (Study the reference drawing in 7.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections.
2. Remove the right side panel to gain easier access to the connections busbars.
3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar located in the middle of the Liebert APM below the Input and Bypass connections. All cabinets in the UPS system must be connected to the user’s ground connection.
NOTE
The grounding and neutral bonding arrangement must comply with the National Electrical Code and all applicable local codes.
4. Identify and make power connections with incoming cables according to Steps 5 through 8.
31 Liebert® APM
Page 42
Electrical Connections—UPS
!
!
Common Input Connections
5. For common bypass and main inputs, connect the AC input supply cables to the UPS input terminals (A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure correct phase rotation.
NOTE
For common bypass and main inputs, the AC input cables must be connected to the bypass terminal (A2-B2-C2-N1) but not the main input terminal (A2-B2-C2).
Split Bypass Connections
6. If a split bypass configuration is used, connect the AC input supply cables to the rectifier input terminals (A1-B1-C1-N1) and the AC bypass supply cables to the bypass input terminals (A2-B2-C2-N1) and tighten the connections to 240lb-in. (27N-m) (M10 Bolt). Ensure correct phase rotation.
NOTE
For split bypass operation, ensure that the busbars between bypass and rectifier inputs are removed. The neutral line of the bypass input must be connected to that of the rectifier input.
Output System Connections—Ensure Correct Phase Rotation
7. Connect the system output cables between the UPS output busbars (A-B-C-N terminals) and the critical load and tighten the connections to 240lb-in. (27N-m) (M10 bolt).
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
If the load equipment will not be ready to accept power when the commissioning engineer arrives, ensure that the system output cables are safely isolated.
Internal UPS Battery Connections
The UPS internal batteries will be connected at the factory, EXCEPT the connections between the shelves and to the breaker.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The DC bus is live when this internal battery connection is made. This connection is to be performed ONLY by Emerson Network Power
Observe the battery cable polarity. Be sure that the battery connection is made with the cor­rect polarity.
8. Refit all protective covers removed for cable installation.

3.3 Control Cables Details

3.3.1 Static Bypass Assembly Features

Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). Terminations for these functions are located at the front of the static bypass module. The main features are:
• Input and output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Liebert IntelliSlot
• Temperature detect interface
®
interface
®
Liebert Services at startup.
Liebert® APM
32
Page 43
Figure 17 Static bypass assembly connections to display cabinet and options
Monitor
J4
J8
J5
J12
J11
J10
J4
J9
Operator Control Panel
Battery Cabinet
Bypass Distribution Cabinet
Temp Sensor (optional) and
BCB Control Board
Ground Fault (optional )
Sensor & BCB Control Board
On Generator (optional)
Static
Bypass
Assembly
Mains Backfeed Protection
Bypass Backfeed Protection
LBS
PARA
PARA
J1
J2
J3
J4
J5
J6 J9
J8
J7
J10
J11
J12
GND
GND
GND
BAT-OUT
BAT-IN
+12V
GND
OUT
INPUT_2
INPUT_1
EXT-OUT
Q2BP
Q3BP
ONLIN E
BCB_I N
DRIVER
+12V
+12V
EPO-NC
EPO-NC
+12V
BAT -REA DY
BAT-GND
ENV_DB
INV _C
INV_S
INV_O
BFP _C
BFP_O
BFP_S
MFP_C
MFP_S
MFP_O
Input /output dry cont act and EPO /BCB/MBC interface
J1~J3 port c an’t connect to hone !
Auxiliary Terminal
Block
Electrical Connections—UPS
Figure 18 Auxiliary terminal block detail (static switch assembly front panel)
Terminal block connectors are on the left side of the static bypass assembly.
NOTE
33 Liebert® APM
Page 44

3.4 Dry Contacts

+12V
J9
-
+12V
BAT_READY
ENV_DET
BAT_GND
BAT_OUT
+12V
BAT_IN
J4
GND
GND
EXT_OUT
Q2BP
Q3BP
J5 J8
GND
ONLINE
BCB_IN
DRIVER
12V
12V
12V
NOTE: The black square () on each connector indicates Pin 1. Refer to Figure 18 for the location of connectors J4, J5, J8 and J9.
The UPS provides input dry contacts and output dry contacts on the Auxiliary Terminal Block (ATB).

3.4.1 Input Dry Contacts

External input dry contacts are connected via the ATB. Dry contacts are available for environment detection, battery ground fault detection, etc.
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry contact terminals produced, and these terminals are on the static bypass assembly. Through software programming, these signals become active when these contacts connect to +12V to ground (in the most left side). The cables connected to the monitor board must be separated from power cables. Moreover, these cables should be double-insulated with a typical cross-section of 0.5 to 1mm maximum connection length between 82 and 165ft. (25-50m). The ATB has several input dry contacts.
Figure 19 Input dry contacts
Electrical Connections—UPS
2
for a
Table 4 Description of dry contact input port
Position Name Description
J9.1 ENV_DET Detection of battery room environment (normally closed); On Generator; EVN
J9.2 BAT_GND Battery short to ground detection; BtG; On Generator
J9.3 BAT_READY Not Used
J9.4 +12V +12V power supply
J4.1 BAT_IN Internal battery temperature detection
J4.2 +12V +12V power supply
J4.3 BAT_OUT External battery temperature detection
J4.4 GND Power supply GND
J5.1 Q3BP Input circuit breaker status of external Liebert BDC
J5.2 Q2BP Output circuit breaker status of external Liebert BDC
J5.3 EXT_OUT Input circuit breaker status of internal Liebert BDC
J5.4 GND Power supply GND
J8.1 DRIVER BCB Driver Signal
J8.2 BCB_IN BCB Contact State
J8.3 GND Power Ground
J8.4 ONLINE
BCB On-Line - Input (N.O.) - This pin will become active when the BCB interface is connected.
Liebert® APM
34
Page 45

3.4.2 Output Dry Contacts

J1 0
MFP_O
MFP_S
MFP_C
J12
INV_C
INV_S
INV_O
J11
BF P_C
BFP_S
BFP_O
NOTE: The black square () on each connector indicates Pin 1. Refer to Figure 18 for the location of connectors J10, J11 and J12.
The Auxiliary Terminal Block has three output dry contact relays (see Figure 20 and Table 5).
Figure 20 Output dry contacts and EPO wiring
Table 5 Output dry contact relays
Position Name
J11.2 BFP_O Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J11.3 BFP_S Bypass feedback protection relay center
J11.4 BFP_C Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J12.2 INV_O Inverter mode relay. Normally open. Closed when UPS is in inverter mode.
J12.3 INV_S Inverter mode relay common
J12.4 INV_C Inverter mode relay. Normally closed. Open when UPS is in inverter mode.
J10.2 MFP_O Main feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J10.3 MFP_S Main feedback protection relay common
J10.4 MFP_C Main feedback protection relay. Normally closed. Open when bypass SCR is shorted.
Description
Electrical Connections—UPS
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.

3.4.3 Liebert BDC Interface

The Liebert BDC interface is on the Auxiliary Terminal Block at J5. Refer to Figure 18 for the location of connector J5 and to Figure 19 for circuit details.
Table 6 Liebert BDC interface
Position Name
J5.1 Q3BP Input circuit breaker status of external Liebert BDC
J5.2 Q2BP Output circuit breaker status of external Liebert BDC
J5.3 EXT_OUT Input circuit breaker status of internal Liebert BDC
J5.4 GND Power supply GND
These contacts cannot be active unless they are set via software.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 10 and Figure 45 for the Liebert BDC wiring.
Description
35 Liebert® APM
Page 46

3.4.4 Battery Cabinet Interface Connectors

J6
EPO-NO EPO-NC
J6
EPO-NO
EPO-NC
+12V +12V
+12V
+12V
NOTE: The black square () on each connector indicates Pin 1.
Refer to Figure 18 for the location of connector J6.
The battery cabinet interface is on the Auxiliary Terminal Block at J8 and J4. Refer to Figure 18 for the location of connectors J4 and J8 and to Figure 19 for circuit details.
Table 7 Battery cabinet interface
Position
J4.1 BAT_IN Internal Battery Temperature Detection
J4.2 +12V +12V Power Supply
J4.3 BAT_OUT External Battery Temperature Detection
J4.4 GND Power Ground
J8.1 DRIVER BCB Driver Signal
J8.2 BCB_IN BCB Contact State
J8.3 GND Power Ground
J8.4 ONLINE
Name
Description
BCB On-Line - Input (N.O.) - This pin will become active when the BCB interface is connected.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.
NOTE
Refer to Table 9 and Figure 40 for battery cabinet wiring.
Electrical Connections—UPS

3.4.5 EPO Input—Optional

NOTICE
Risk of exceeding internal voltage limits. Can cause equipment damage. Do not apply more than 12V to the Emergency Power Off (EPO) input. Exceeding 12V on this
input can damage the Liebert APM’s internal circuitry and control boards. Exceeding 12V will also put the Liebert APM in an EPO state, and the unit will not reset, making it non­functional.
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The J6 connector, shown in Figure 21, is the remote EPO input interface. The EPO has NO/NC contacts that become active when shorting terminals J6: 3 and 4 or open terminal connection J6: 2 and 1.
If an external Emergency Stop capability is required, it is connected at terminals J6: 1 and 2 and at J6: 3 and 4 on the monitor board. It also is connected to the Normally Open or Normally Closed remote stop switch between these two terminals using shielded cable (see Figure 21 and Table 8). If this function is not used, terminals J6:3 and 4 must be opened and J6:1 and 2 must be closed.
Figure 21 EPO wiring and signal names for J6
Liebert® APM
36
Page 47
Table 8 EPO input contact relays
Position Name Description
J6.1 EPO_NC EPO Activated when opened to J6.2
J6.2 +12V EPO Activated when opened to J6.1
J6.3 +12V EPO Activated when shorted to J6.4
J6.4 EPO_NO EPO Activated when shorted to J6.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – J6: 1, 2, these terminals are supplied factory-linked on the Bypass Module on the UPS and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.
Figure 22 Single UPS Remote Emergency Power Off
Electrical Connections—UPS
Single Liebert APM Module
Liebert APM
Bypass Module
Liebert APM
Bypass Module
Remote EPO
(Customer-
Supplied)
UHRF3S67X2 (J6)
Field-Supplied Wiring
X2_J6
UHRF3S67X2
UAM04031-00 Rev. 1
37 Liebert® APM
Page 48
Parallel System and LBS System Installation
!

4.0 PARALLEL SYSTEM AND LBS SYSTEM INSTALLATION

This chapter gives details on the installation of a parallel system and an LBS system.

4.1 General

A parallel Liebert APM system can consist of two Liebert APM cabinets connected in parallel without a main system static bypass. Instead, the bypass static switches of each UPS share the load when the system transfers to the utility bypass supply. A third-party APM paralleling switchboard may be used to provide external maintenance capability. See Figure 23 for details.
From a power viewpoint, each module is internally identical to the single-module configuration. A parallel system requires intermodule control signals to manage the load sharing, synchronizing and bypass switching. The control signals are connected through parallel communication cables, which provide bi-directional communication between the two Liebert APM units of the system. A second parallel cable is provided to establish redundancy.
When Liebert APM units are to be connected in parallel, a sharing inductor assembly is required and must be installed inside the Liebert APM cabinet. The inductor may be installed at the factory or field-installed.

4.2 System Installation Procedures

The installation of a parallel UPS should follow the procedures for a single UPS module with the additional requirements detailed in this section.

4.2.1 Preliminary Checks

Be sure that the options of the parallel cables are correct and that the modules are of the same rating, model and with the same software and hardware release.
WARNING
To achieve coordinated operation of the modules in the parallel system, it is required to configure each module separately using Emerson configuration software. This must be done by Emerson service personnel.

4.2.2 Cabinet Installation

Position the UPS modules and make connections as shown in Figure 23. The output distribution consisting of external UPS output switches and maintenance bypass must be installed, as shown in Figure 23, to facilitate maintenance and system testing.
Liebert® APM
38
Page 49
Figure 23 UPS system with external maintenance switch
UAM01060A Rev. 0
Buyout Liebert APM Paralleling Switchboard
* System
AC Input 4 Wire +GND
UIB See Note 7
UIB
Liebert APM #1 UPS Cabinet
Liebert APM #2 UPS Cabinet
Battery
Output Busbar
Output Busbar
Static Bypass
MIB
MBB
MOB1
MOB2
Opt. K
AC Output 4-Wire+GND
NOTES:
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run in separate conduits.
5. Control wiring must be run in separate conduits.
Field-Supplied Wiring
LEGEND UIB - UPS Input Breaker MOB - Module Output Breaker MIB - Maintenance Isolation Breaker MBB - Maintenance Bypass Breaker
* External overcurrent protection by others
6. The 90kVA frame has a capacity of up to six Flex Power assemblies and the 45kVA frame has a capacity of up to three Flex Power assemblies.
7. Paralleling switchboard requires shunt trip UIB breakers with 120V coils.
8. See drawings UAM01080B, UAM01080C, UAM01080D, UAM01080E and UAM01080F. Refer to the following battery cabinet control wiring drawings: UAM04000 UAM4001A,B UAM4002A,B D)
Parallel System and LBS System Installation
NOTE
For parallel system installations, an external bypass rated for the total system load must be installed.
For parallel systems, Emerson recommends installing bypass load sharing inductors to optimize

4.2.3 External Protective Device

current sharing during static bypass operation.
Refer to 3.2 - External Protective Devices.
39 Liebert® APM
Page 50

4.2.4 Power Cable

UAM1080C Pg. 3, Rev. 1
Notes
1. See drawings UAM01080A, UAM01080B, UAM01080D, UAM01080E and UAM01080F.
2. Paralleling switchboard requires shunt trip UIB breakers with 120V coils.
Field-Supplied Wiring
Liebert APM Bypass Module
Only One Shown
Liebert APM Detail View
with Door Open
Backfeed Breaker Fuse Block (FH1)
Backfeed Breaker Fuses, (2) 8
Backfeed Breaker Fuses, (2) 8
BDSi Fuse Block (FH2) (Optional)
UHRF3S67X2
(J10, J11)
Input Neutral
Ø A Ø B Ø C
Input Neutral
Ø A Ø B Ø C
Liebert APM
Bypass
Liebert APM
Bypass
Liebert APM #2
Liebert APM #1
UIB Liebert APM 1
Paralleling
Switchboard
UIB Liebert APM 2
Paralleling
Switchboard
J10
J10
J11
J11
J11
J10
TB1
TB1
1
2
3
2
3
2
3
2
3
2
3
4
5
6
7
8
9
10
11
12
Phase
Neutral
Phase
Neutral
The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input has a current leakage protective device, the current leakage protective device must be fitted upstream of the neutral line input terminal.
NOTE
The length and specification of power cables including the bypass input cables and UPS output cables should be the same. This facilitates load sharing in bypass mode.

4.2.5 Input Breaker Control Wiring

Figure 24 Input breaker control wiring for parallel systems
Parallel System and LBS System Installation

4.2.6 Output Breaker Control Wiring

Liebert® APM
Auxiliary wiring must be installed as shown in Figure 25 to protect the system and enable a single UPS to be isolated and tested during service.
40
Page 51
Figure 25 Output breaker control wiring
Notes
1. See drawings UAM01080A, UAM01080C, UAM01080D, UAM01080E and UAM01080F.
2. Load Bus Sync cable not used with parallel system.
Factory-Supplied Wiring
Liebert APM 2
Liebert APM 1
J1
J2
J2
J2
J1
J1
Parallel Control Cables
UHRF3S67X2 (J1, J2)
Liebert APM Bypass Module
Only One Shown
UAM1080B Pg. 2, Rev. 0
Parallel System and LBS System Installation
Buyout Liebert APM Paralleling Switchboard
MBB
UHRF3S67X2 (J5)
J5
Liebert APM Bypass Module
Only One Shown
Notes
1. See drawings UAM01080A, UAM01080B, UAM01080C, UAM01080E and UAM01080F.
2. MBB auxiliary switch connections are on the normally closed and common positions.
3. MOBs auxiliary switch connections are on the normally open and common positions.

4.2.7 Parallel Cables

Shielded and double-insulated parallel control cables available in lengths of 16.4ft. and 32.8ft. (5m and 10m) must be interconnected in a ring configuration between the UPS modules, as shown in Figure 26. The parallel ports J1 and J2 are provided on the front panel of the bypass module, as shown in Figure 28. The ring connection ensures the reliability of the control of the parallel system. Be sure to verify the reliable cable connection before starting up the system!
System
AC Input
4-Wire + GND
UIB
UIB
Liebert
APM #1
X2 J5
Liebert
APM #2
Field-Supplied Wiring
MIB
See Note 2
MOB1
1
2
3
4
1
2
3
4
TB2
1
2
3
4
5
6
See Note 3
MOB2
See Note 3
AC Output
4-Wire + GND
UAM0180D Rev. 1
NOTE
Use the shortest parallel control cables possible for the application . Do not coil excess cable. Meanwhile, separate the parallel control cables from the power cables to prevent electrical inteferences.
Figure 26 Connection of parallel control cables of parallel system
41 Liebert® APM
Page 52

4.2.8 Key Interlock System

Figure 27 Key interlock system control wiring
Parallel System and LBS System Installation
AC Input
Ø A Ø B Ø C
UHRF3S67X2 (J5, J12)
J5
Liebert APM Bypass Module
Only One Shown
Notes
1. See drawings UAM01080A, UAM01080B,
UAM01080C, UAM01080D and UAM01080F.
2. MBB auxiliary switch connections are on the normally
closed and common positions.
3. MOBs auxiliary switch connections are on the normally
open and common positions.
4. Contact closes when UPS is on internal bypass.
Field-Supplied Wiring
MBB
Kirk Key K1
Liebert
APM #1
*See Note 4
3 4
X2 J12
1 2 3 4
X2 J5
Liebert
APM #2
*See Note 4
3 4
X2 J12
1 2 3 4
X2 J5
See Note 2
Buyout Liebert APM Paralleling Switchboard
MOB1
TB3
1
TB2
TB3
TB2
2
1
2 3
3 4
4
5
6
See Note 3
MOB2
See Note 3
MIB
Kirk Key K2
2 Fuses
2A
Inner Door SWBRD
SKRU
KO
Push Button
AC Output
ØA Ø B Ø C Neu
UAM0180E Rev. 0
Transfer Parallel Liebert APM Units to System Bypass Mode
1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove key.
3. Insert key in MBB interlock K1 and rotate to withdraw interlock. Key will remain in interlock.
4. Close the MBB.
5. Open the MIB and rotate thekey in K2 to extend interlock.
6. Remove key from MIB interlock K2 and place in K0.
7. Rotate key in K0 to lock key.
Return Parallel Liebert APM Units to Normal Mode
1. Verify that all Liebert APM units are in internal maintenance bypass mode. The light in the SKRU push button will turn On when all units are in bypass.
2. Hold the push button in and rotate the key in K0 to remove the key.
3. Insert the key in the MIB interlock and rotate the the key in K2 to withdraw interlock.
4. Close the MIB.
5. Open the MBB and rotate the key in K1 to extend interlock.
6. Remove the key from the MBB interlock K1 and place it in K0.
7. Rotate the key in K0 to lock the key.
Liebert® APM
42
Page 53
Figure 28 Locations of ports J1, J2 and J3 on bypass module
J1
J2
J3
Input/output dry contact and EPO/BCB/MBC interface
J1 ~ J3 port can’t connect to phone!
J4 J7
J1
GND
+12V
BAT-IN
BAT-OUT
J5
J2
PARA
J10
GND
OUT
MFP_C
MFP_S
MFP_O
INPUT_1
INPUT_2
J11
J8
Parallel System and LBS System Installation
INTELLISLOT3INTELLISLOT2INTELLISLOT1
GND
J3
PARA
EPO-NO
LBS
GND
Q3BP
Q2BP
EXT-OUT
J9J6
+12V
+12V
EPO-NC
BFP_C
BFP_S
ONLINE
+12V
BAT_READY
BFP_O
BCB_IN
DRIVER
J12
INV_S
INV_C
INV_O
ENV_DET
BAT_GND
MONITOR
RS485-2RS485-1
RS232

4.2.9 Remote EPO

In addition to the EPO switch provided on the operator control and display panel of each UPS module for controlling the EPO of each module respectively, the parallel system also provides remote EPO function for controlling all UPS modules to shut down simultaneously from a remote terminal, as shown in Figure 29.
NOTE
1. The remote EPO switch must provide a dry contact signal, which is normally open or closed.
2. The open circuit voltage provided is 5VDC, <20mA.
3. The external EPO device can be composed of another control system that can disconnect the UPS mains supply or the bypass input.
4. Pins 1 and 2 of the normally closed EPO-J6 port on the bypass module are connected at the factory.
Figure 29 Remote Emergency Power Off wiring for parallel UPS
Two Liebert APM
Modules in Parallel
Liebert APM
Bypass Module 1
Liebert APM
Bypass Module
X2_J6
UHRF3S67X2
Remote EPO
(Customer-
Supplied)
Liebert APM
Bypass Module 2
UHRF3S67X2 (J6)
X2_J6
UHRF3S67X2
UAM04031-00
Field-Supplied Wiring
43 Liebert® APM
Rev. 1
Page 54

4.3 LBS System

Main Input
Bypass
UPS1A
UPS1B
UPS2A
UPS2B
LBS
STS
To Load
Main Input
Parallel
Control
Cable
Main Input Main Input
Bypass
Parallel Control Cable

4.3.1 Cabinet Installation

A dual bus system consists of two independent UPS systems, each containing one or more parallel UPS modules, as shown in Figure 30. The dual bus system has high reliability and is suitable for loads with multiple input terminals. For a single-input load, an optional static transfer switch can be fitted to achieve the transfer between the two outputs of the dual bus system.
Figure 30 Typical dual bus system (with STS and LBS)
Parallel System and LBS System Installation
The dual bus system uses the LBS to keep the output of the two independent UPS systems (or parallel systems) in synchronization. One system is designated as the master, the other is designated as the slave. The operation modes of the parallel system comprise master and/or slave operation in normal or bypass mode.
Place the UPS modules side by side and interconnect the UPS modules according to the following instructions.

4.3.2 External Protective Device

Refer to 3.2 - External Protective Devices.

4.3.3 Power Cable

The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input has a current leakage protective device, the current leakage protective device must be fitted upstream of the neutral line input terminal.

4.3.4 Control Cable

For Liebert APM-to-Liebert APM dual bus system, connect the optional LBS cables between the two UPS systems as shown in Figures 31 to 33. The J3 and J4 ports are provided on the front panel of the bypass module, as shown in Figures 28.
NOTE
Use the shortest LBS cable that will be functional for the application and do not coil excess cable. Separate the LBS cable from the power cables to prevent electrical inteferences.
Liebert® APM
44
Page 55
Parallel System and LBS System Installation
Figure 31 Connection of typical dual bus system of two parallel systems
UPS 1
Bypass Module
J1
J2
J3
UPS 2
Bypass Module Bypass Module Bypass Module
J1
J2
J3
LBS Cable
UPS 3 UPS 4
J1
J2
J3
LBS Cable
J1
J2
J3
Figure 32 Connection of typical dual bus system of two single UPS’s without redundant LBS cable
UPS 1
Bypass Module
J1
J2
UPS 2
Bypass Module
J1
J2
J3
J3
LBS Cable
Figure 33 Connection of typical dual bus system of two single UPS’s with redundant LBS cable
UPS 1
Bypass Module
J1
J2
LBS Cable
J3
LBS Cable
UPS 2
Bypass Module
J1
J2
J3
45 Liebert® APM
Page 56

5.0 BATTERY INSTALLATION

!
!

5.1 Introduction

Emerson recommends that the batteries in external cabinets be the same type and made by the same manufacturer as the internal batteries in the Liebert APM.
If multiple sets of batteries connected in parallel are used to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection.

5.2 Safety

Special care should be taken when working with the batteries associated with the Liebert APM system equipment.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
The Liebert APM’s internal batteries are connected and energized even if the UPS is turned Off. To minimize the risk of injury, a properly trained and qualified service person should disconnect internal batteries before any maintenance is performed on the unit.
When all batteries are connected together, the battery terminal voltage may exceed 324V and is potentially lethal.
The center of the battery is connected to the neutral of the UPS and is grounded. A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If the battery is grounded, remove source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
Battery Installation
When replacing batteries, replace with batteries of the same type and manufacturer, or equivalent. Refer to 11.2 - UPS Environmental for a list of approved batteries or contact your Emerson representative.
Liebert® APM
CAUTION
Batteries used in the Liebert APM and its auxiliary cabinets must be of an approved type. Replacing batteries with an incorrect type can cause an explosion and fire. Refer to Tables 38 and 40 for acceptable batteries.
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
46
Page 57

5.3 UPS Batteries—Liebert APM 45kVA Frame Only

See Figure 35
The Liebert APM’s internal batteries are fully charged before the unit is shipped. During storage and transportation, some charge is lost. All batteries should be recharged before use. The battery charger works only when the Liebert APM is connected to input power and turned On.
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturer's manuals, available on the manufacturer’s Web site.
The battery safety information contained in this section relates to key considerations that must be taken into account during the installation design process and might affect the design outcome, depending on your installation.

5.3.1 Internal Battery Breaker Component Locations and Control Wiring

The Liebert APM 45kVA frame contains internal batteries. The batteries are protected by an internal battery breaker. Figure 34 shows the component location; Figure 35 shows the control wiring.
Figure 34 Internal battery breaker component locations
UHRF3S67X2 Liebert APM Bypass Module
TB1
Battery Installation
Battery Temperature Sensor Location
FRONT
Battery Breaker
UH8351A8 Capacitor Board
See Detail A
Detail A
UHW241C2 BIB Board
UAM04052A Pg. 1, Rev. 0
47 Liebert® APM
Page 58
Figure 35 Internal battery control wiring
Liebert APM Internal Battery
Liebert APM DC Bus
Liebert APM
Bypass Module
Battery
Breaker
Detail A
See Note 2
Internal Battery Temperature Sensor
Neg. Midpoint
W61
W1
W3
W2
W4
W62
W63
Aux. MX
Positive (+)
Neutral (Neg. Midpoint)
Negative (-)
TB1
Red
Red
Red
Red
Black
Black
J4
J3
J2
Black
Black
Black
Black
Black
Black
Black
Brown
Brown
Green
Green
Green
Striped Com
White
White
White
White
White
White
White
Brown
Capacitor
Board
UH8351A8
BIB
Board
UHW241C2
Yellow NO
220VDC
220VDC
DRV AUX GND1 USE
Driver
See Detail A
X101
BCB_IN
X102
X107
X2 J8
X100
X103
X104
X105
X106
X108
X2
J4
BAT IN
GND
Online
+12V
BAT-OUT
GND
1 2 3
1
2
3
4
1
2
3
4
NOTES
1. All service and initial battery connections must be performed by properly trained and qualified service personel.
X107
3 2 1
2. Jumper X107 must short circuit Pin 1 and Pin 2.
3. The circuit breaker auxiliary blue wire #12 is not used.
4. Shunt trip drive is 220VDC @ 2.4A.
UHRF3S67X2
UAM04052B Pg. 2, Rev. 0
See Figure 34
Battery Installation
Liebert® APM
48
Page 59

5.4 External Battery Cabinet Installation

!
DETAIL B
Liebert
APM
Battery
Cabinet
3
Washer Split, M10
Washer Split, M10
Hex Head Bolt, M10
1
2
B

5.4.1 Matching Battery Cabinets

A matching battery cabinet is available. Refer to Figure 37. The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections, and cabinet for any damage. Exercise caution; voltage is present within the battery cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If planning to store a battery cabinet for longer than six months or at temperatures higher than 77°F (25°C), contact Liebert Services for recommended precautions.
The following notes, in conjunction with the diagrams (Figure 37), illustrate the broad principles to be followed when fitting and connecting the majority of battery cabinet installations.
CAUTION
Any battery system should be installed by properly trained and qualified personnel.
When installing an external battery cabinet that is NOT a Liebert APM battery cabinet, the customer must provide overcurrent protection. See Table 43 for sizing of protection devices.
Battery Installation
NOTE
When using an external battery supply that is not provided with the UPS, please make reference to the battery manufacturer’s installation manual for battery installation and maintenance instructions, available on the manufacturer’s Web site. When replacing batteries, Emerson recommends that the batteries in external cabinets be the same type used internally in the Liebert APM. See Tables 38 and 40 for batteries that are approved for use with the Liebert APM.
Figure 36 Bolting the battery cabinet to the Liebert APM
49 Liebert® APM
Page 60

5.4.2 Connecting the Batteries

603705 Pg. 1, Rev. 1
X8
Tray 1
Tray 2
Tray 3
Tray 4
12
34
42
32
39
2X
DETAIL B 4X
40
B
603705G2 ASSY BATT NXRA 600 BATT CAB HX330
603705G4 ASSY BATT NXRA 600 BATT CAB HX300
603705G5 ASSY BATT NXRA 600 BATT CAB HX205
603705G10 ASSY BATT NXRA 600 BATT CAB HX150
If the Liebert APM battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet through the bottom of the cabinet.
If the Liebert APM battery cabinets are installed adjacent to one another on a solid floor, these cables may be passed between the cabinets through slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet may be used.
Figure 37 Battery cabinet, 600mm wide—details
Battery Installation
Liebert® APM
50
Page 61
Figure 38 Battery trays for 600mm battery cabinet
HX330
HX300
HX205
HX150
Battery Installation
51 Liebert® APM
Page 62
Figure 39 Battery cabinet with trays for 900mm battery cabinet
Tray 1
Tray 2
Tray 3
2x 3
20
2x 13
Tray 5
Tray 6
Tray 4
Detail A
6X
14.5" (368.3mm)
8
Tray 4 View
Tray 4 with Extra Isolator
1
7
2
2x 6
2x 14
6x 10
12x 11
4x 9
17
16
8
15
12.8" (325mm)
15
20" (508mm)
Tray View
Battery Installation
Liebert® APM
52
Page 63

5.4.3 Installation Considerations

Position—Liebert battery cabinets come in versions specific to the left side of the UPS. If the system includes a matching Liebert BDC, the cabinet should be mounted to the right of the UPS (nearest the busbars) and the battery cabinet(s) should be installed to the left of the UPS.
The battery cabinet(s) are designed to be located conveniently next to each UPS module on the left side only and are also available in stand-alone configurations with painted side panels. The front access design eliminates side and rear service clearance requirements. Refer to Table 36 for battery cabinet dimensions and weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt only onto the left side of the UPS module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and servicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of clearance at the front of the cabinet when operating. Side and rear panels do not require service clearance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminating the need for external conduit runs. Route cables before moving cabinets into final position for bolting together. No top or bottom entry cables are required, except for remotely located cabinets which require conduits.
Software—To allow the UPS to accurately display the battery run time, the number of battery cabinets must be noted when performing initial startup and setup using the configuration software. This is to be performed by the Liebert Services engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.
Battery Installation

5.4.4 Connecting the Battery Cabinet to the UPS

After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below (see Figure 40).
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections.
2. Remove the UPS right side panel to gain access to the ground and battery busbars.
3. Remove the battery cabinet front panel to gain access to the busbars.
4. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar. (example: UPS located on the bottom of the equipment below the power connections).
All cabinets in the UPS system must be connected to the user's ground connection.
NOTE
The grounding and neutral bonding arrangement must be in accordance with the National Electrical Code and all applicable local codes.
5. Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet breaker BCB (+ N -) as shown in Figure 40. Be sure that the battery connections are made with the right polarity, and tighten the connections to 240lb-in. (27N-m) (M10 bolt). Do not close the battery circuit breaker before the equipment has been commissioned.
6. Connect TB1 from battery cabinet to J4 and J8 on the UPS according to Table 9.
NOTE
The shunt trip drive capability for the battery breaker is 220VDC at 2.4A.
53 Liebert® APM
Page 64
Table 9 Control wiring for Liebert APM to battery cabinet
1. All service and initial connectino of batteries must be performed by properly trained and qualified service personnel.
2. The Jumper X107 must short circuit Pin 1 and Pin 2.
External Connections
AC 120V Power
to Optional BDSi
Controller
AC 120V
from UPS
BDSi Fuse Block
GRD
Fault CT
Positive
Negative
Neutral
Ground W24
W21
W22
W23
Neg. Mid Pt.
Aux.
MX
See
Note 3
Blue (Not Used)
Orange
Black
Black
Blue Com
Blue
TB1
W/R
W/Blk
White
White
Violet NO
1 2 3
4
5
6 7
8
9
10 11
12
Red Red
White
White
Grn
Grn
Wht
Wht
Brn
Brn
Blk
Blk
Blk
Blk
1 2 3
4
1 2 3
4
X2 J8
X2 J4
X108
X105
X102
X100
X107
X101
X104 X103
X106
UHR93S6A1
X2
BCB_IN
BAT-OUT
BAT IN
GND
GND
Driver
Online
+12V
Red
Red
White
White
Wht
Grn
Brn
Blk
Blk
Blk
Red
Blk
1 2 3
3 2 1
DRV AUX GND1
USE
TEMP
J2
J3
J4
220VDC
220VDC
Red
Blk
UH8351A8
BIB
BCB
Control
Board
Red
3. The auxilliary blue wire is not used. Cap and coil the wire and tie it to the bridge lance on the frame below the breaker.
4. Shunt trip drive is 220VDC @ 2.4A.
UAM04000 Rev. 0
TB2
Brown
Yel /G rn
UPS
Module
From To
Liebert APM UPS Bypass
Module (X2 J4 & J8)
Battery Cabinet
Terminal Strip (TB1)
J4-2 TB1-12
J4-3 TB1-11
J4-4 TB1-10
J8-1 TB1-6
J8-2 TB1-7
J8-3 TB1-8
J8-4 TB1-9
Figure 40 Battery cabinet connection to Liebert APM
Battery Installation
Liebert® APM
54
Page 65

5.5 Non-Standard Batteries

UAM04050A-00 Pg. 1, Rev. 0
Battery Breaker
Battery Temperature Sensor Location
UHRF3S67X2 Liebert APM Bypass Module
Front
Right Side
Isometric View - Right Side
UHR93S6A1ZA6 Output EMI Board
CT
ULC366SC1 Ground Fault Detect Board
UHW241M5 Auxiliary Power Board
When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Emerson sales representative about this option. Refer to Figures 87 and 88 for details.
Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions. Verify that the battery area has adequate ventilation and battery operating temperature complies
with the manufacturer's specifications and with all applicable national and local codes. If you have any questions concerning batteries, battery racks or accessories, contact Liebert Services
at 1-800-543-2378.
NOTE
The user-supplied battery DC bypass breakers or fuses should have a minimum overload rating of 8kA and 500V.

5.6 Battery Ground Fault Detection Option

An optional battery ground fault detection device can be added to detect leakage current in the battery system. The residual current range monitored is 30mA ~ 3000mA. When a battery ground fault is detected, an alarm will appear on the UPS display panel. The battery ground fault detection set contains one current transformer (CT). Figures 41 and 42 show the connection of this set for the Liebert APM.

Figure 41 Battery ground fault detection component location

Battery Installation
55 Liebert® APM
Page 66

Figure 42 Control wiring diagram for battery ground fault detection option

Red
UHRF3S67X2 (J9)
UHR93S6A1ZA6 Output EMI Board
Output A
Output B
Output C
Blk
Battery Installation
W600
Liebert APM
Bypass Module
J9
Liebert APM Bypass Module
Liebert
APM
Internal
Battery
Battery Breaker
Output N
UHW241M5
Red
Brn
Blk
Auxiliary Power Board
W601
W603
W602
CT
Positive
Neutral
Negative
Liebert
APM
DC Bus
Notes
1. All battery service and initial connections must be performed by properly trained and qualified personnel.
2. Refer to drawing # UAM04050A, Pg. 1.
X2_J4
UHRF3S67X2
Blk
Red
X2_J9
Blk
Brn
Red
J4
J1
J7
BlkBlk Brn Brn
ULC366SC1
Ground Fault Detect Board
UAM04050B Pg. 2, Rev. 0
Red Blk
J5
12V
GND
Liebert® APM
56
Page 67
Liebert BDC
6.0 LIEBERT BDC
The Liebert BDC is designed to operate in UPS normal mode, static bypass mode and maintenance mode. The Liebert BDC offers either 45kVA or 90kVA capacity to match the associated Liebert APM frame offerings. Each of the Liebert BDC capacities offer optional input 208V, 480V and 600V internal transformers as well as multiple output distribution selections.
Figure 43 Single input UPS with external Liebert BDCwith optional internal transformer—typical
configuration
Bypass Distribution Cabinet
* System
AC Input
3-Wire + GRD
Optional
Transformer
BIB
MBB
MIB
Optional
54-Pole
See Note 5
AC Output
208V
4-Wire + GRD
Local Grounding
Electrode
Static Bypass
See Note 1
UPS Cabinet
Battery
Notes
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. UPS system input and output cables must be run in separate conduits.
4. Control wiring must be run in separate conduits.
5. Optional 54-pole, 225A for 45kVA frame only or optional 54-pole, 400A for 90kVA frame only.
6. Transformer available: 480V or 600V input.

6.1 Normal (UPS) Mode

While the Liebert BDC is in Normal mode (MBB open; BIB/MIB closed), the UPS is supplying the connected load with continuous, high-quality AC power. In this mode of operation, the load is protected by the UPS.

6.2 UPS Static Bypass Mode

When the Liebert APM is in Static Bypass mode, it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the Static Bypass will cause an immediate transfer of the equipment from the UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS; however, the load is NOT protected by the UPS.
BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection by Others
Field-Supplied Wiring
UAM01004 Rev. 3
57 Liebert® APM
Page 68

6.3 Maintenance Mode

!
When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS.

6.4 Locating the Cabinet

This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit. In either case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes.

6.5 Cable Installation

6.5.1 Wiring Preparation

Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Liebert BDC should be installed by a qualified / certified electrician.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Read this section thoroughly before attempting to install wiring to this unit. Read and comply with all warnings and cautions in this manual.
Liebert BDC
Removing the Cover Plates
Plates cover the input and output terminals on the front of the Liebert BDC (see Figure 44). Remove these and keep the screws and plates for reinstallation.
Figure 44 Liebert BDC—access plate removed

6.5.2 Power Cable Installation

Refer to Table 43 when selecting cables.
NOTE
Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load.
Liebert® APM
58
Page 69

6.5.3 Input/Output Wiring

Follow the steps below to connect the input wiring:
NOTE
Input wiring must be installed using conduit if cabinet is not mounted to the immediate right of the UPS.
1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through it, allowing some slack for installation. For cabinets that are located to the immediate left of the UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that the edge guarding is installed and intact.
2. Secure the conduit to the access plate of the Liebert BDC.
3. Input power cables connect to the system input circuit breaker; refer to Figure 59 and to Table 18.
4. Connect the ground (earth) wire to the earth busbar and tighten it to 240lb-in. (27N-m) (M10 bolt).
5. Locate UPS input and output cables and access panel to UPS on lower right side.
NOTE
If the Liebert BDC is not to be bolted to the UPS, use either top or bottom access plate.
6. Connect the system ground cable between the Liebert BDC and UPS and tighten the connections to 240lb-in. (27N-m) (M10 bolt).
7. Connect the system input cables between the Liebert BDC “UPS Input” Busbars (A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 240lb-in. (27N-m) (M10 bolt).
8. Connect the system output cables between the Liebert BDC 'UPS Output' Busbars (A-B-C N terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 240lb-in. (27N-m) (M10 bolt).
9. Connect TB1 from the Liebert BDC to J5 and J12 on the Liebert APM.
Liebert BDC
NOTICE
Risk of improper wiring connection. Can cause equipment damage. The control wire must be installed to ensure proper operation of the system and fully protect
the load when switching between bypass cabinet and UPS.
Table 10 Control wiring for Liebert APM UPS to Liebert BDC
From To
Liebert APM UPS Bypass
Module (X2 J5 & J12) Liebert BDC Terminal Strip (TB1)
J12-3 TB1-11
J12-4 TB1-12
J5-1 TB1-3
J5-3 TB1-6
J5-4 TB1-5
Jumper TB1-4 to TB1-5
59 Liebert® APM
Page 70
Figure 45 BDC connection to Liebert APM
MBB
W04
W05
W06
Utility
ØA ØB ØC
W91
Liebert BDC
Output
Neutral
AC Output
Kirk
Key K1
AC Input
BIB W07 W08
W09
W85
W86
W87
A B
C N
PE
2
3
1
Input Neutral
Main Ground Busbar
See Note 1
Ground
to Unit Frame
1. Customer-furnished electrode conductor to be installed in accordance with national and electrical codes.
W88
4
3
4 3
1
2
W89
3
45
W90
Key K2
3
2
3
4
8
6
11
7
910
SKRU - Solenoid Key Release Unit KO - Key Operator
Field-Supplied Wiring Factory-Supplied Wiring
MIB
Kirk
4
12
AC 120V
(2)
Fuses
2A
Ground
to Unit Frame
SKRU
To T B 1
Inner Door
UAM04012 Rev. 4
K0
Push Button
Output
Ground
Liebert® APM
NOTE
Install jumper on TB1 pins 4 and 5.
For startup procedure, see 10.2 - UPS Startup.
60
Page 71

6.6 Bolting Cabinets Together

A
Hardware for bolting units is in a bag attached to the Liebert BDC. See form included with UPS.
DETAIL A
3
Washer Flat, M10
Washer Split, M10
Hex Head Bolt, M10
1
2
Place cabinets so mounting holes are aligned. A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet.
NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.

Figure 46 Bolting Liebert APM to a Liebert BDC

Liebert BDC
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the Liebert BDC side, whichever is more convenient.
61 Liebert® APM
Page 72

7.0 INSTALLATION DRAWINGS

1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4.Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national and local electrical codes.
9. All battery cabinets must be positioned on the left side of the UPS.
FRONT VIEW
UAM03000 Rev. 0
UPS
Battery
Cabinet #1
78.7"
(2000mm)
55.4" (1408mm)
23.8" (604mm)
Total Width with Additional Battery Cabinets
Total Width
In. (mm)
79.1 (2008)
102.7 (2608)
126.3 (3208)
Number of
Battery Cabinets
2 3 4
UAM03001 Rev. 1
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert APM UPS System cabinets (UPS, Liebert BDC and battery).

Figure 47 UPS dimensions- front view

Installation Drawings

Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs

Liebert® APM
62
Page 73

Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views

1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 12" (305) rear clearance required for air exhaust and 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Only copper cables are recommended.
UAM2010A Rev. 2
Detail A
Mechanical
Stop
Caster
39-1/2"
(1000mm)
78.7"
(2000mm)
1.56"
(40mm)
3"
(77mm)
23.4"
(595mm)
31.8"
(808mm)
8.9"
(226mm)
1.4"
(36mm)
34.3"
(871mm)
28.3"
(719mm)
Bracket Centers
28.3"
(719mm)
9.2" (235mm)
0.8" (21mm)
Vent Screen Front and Back
Vent Screen
Display
Dimension Y; See Pg. 2
See Pg. 2
Dimension
X
Dimension
Z
Center of
Gravity
Center of
Gravity
31.5" (800mm)
without Side Panels
Power Cable Entry
21.26 x 7.87" (540 x 200mm)
Power Cable Entry
21.26 x 7.87" (540 x 200mm)
TOP VIEW
BOTTOM VIEW
OVERALL
FRONT VIEW
LEFT SIDE VIEW
Front
Front
See Detail A
RIGHT SIDE VIEW
See
Page 2
8. All wiring is to be in accordance with national and local electrical codes.
9. See page 2 of 5 drawing: UAM02010B for weight table and centers of gravity for UPS at 208V.
10. See page 3 of 5 drawing: UAM02010C for weight table and centers of gravity for UPS at 480V.
11. See page 4 of 5 drawing:UAM02010D for weight table and centers of gravity for UPS at 600V.
12. See page 5 of 5 drawing:UAM02010E for weight table and centers of gravity for UPS with internal maintenance bypass.
Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model.
Installation Drawings
63 Liebert® APM
Page 74

Figure 50 Liebert APM with top fan kit

Notes
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through r emovable access plat es. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
UAM0212A Pg. 1, Rev. 1
Caster
Mechanical Stop
DETAIL A
Top Fan Flange to Flange
13.2" (335mm)
12.1"
(308mm)
20.7" (526mm)
9.2"
(235mm)
0.8"
(21mm)
07.6"
(194mm)
Top Fan
Power Cable Entry 21.26" x 7.87" (540x 200mm)
TOP VIEW
78.7"
(2000mm)
31.8"
(808mm)
FRONT
OVERALL
FRONT VIEW
RIGHT SIDE VIEW
LEFT SIDE VIEW
BOTTOM VIEW
FRONT
FRONT
Dim. Y
See Pg. 2
Dimension
X
Dimension Z
Display
Center of
Gravity
Center of
Gravity
Vent Screen
Front and Back
See Pg. 2
See Pg. 2
3"
(77mm)
23.4"
(595mm)
See Detail A
28.3"
(718mm)
Bracket Centers
34.3"
(871mm)
1.4"
(36mm)
8.9"
(226mm)
28.3" (719mm)
Vent Screen
Power Cable Entry
21.26" x 7.87 (540mm x 200)
31.5" (800mm)
w/o Side Panels
39.5"
(1000mm)
7. Only copper cables are recommended.
8. All wiring is to be in accordance wit h nationaland local electrical codes.
9. See Pg. 2 of 5 drawing: UAM02012B for weight table and centers of gravity for UPS at 208 V.
10. See Pg. 3 of 5 drawing: UAM02012C for weight table and center s of gravity for UPS at 480 V.
11. See Pg. 4 of 5 drawing: UAM02012D for weight table and c enters of gravity for UPS at 600 V.
12. See Pg. 5 of 5 drawing: UAM02012E f or weight table and cent ers of gravit y for UPS wit h internal maintenance bypass.
Installation Drawings
Liebert® APM
64
Page 75

Table 11 Center of gravity and weights for Liebert APM 90 kVA frame

Center of Gravity
Weight, lb (kg)
KVA Rating
Dimension X
in. (mm)
Dimension Y
in. (mm)
Dimension Z
in. (mm) Unit Shipping
No Internal Options
15 16.65 (423) 37.64 (956) 18.78 (477) 796 (362) 896 (407)
30 16.18 (411) 38.66 (982) 18.54 (471) 872 (396) 972 (442)
45 15.79 (401) 39.88 (1013) 18.35 (466) 948 (431) 1048 (476)
60 15.47 (393) 41.30 (1049) 18.15 (461) 1024 (465) 1124 (511)
75 15.16 (385) 42.87 (1089) 17.99 (457) 1100 (500) 1200 (545)
90 14.88 (378) 44.57 (1132) 17.83 (453) 1176 (535) 1276 (580)
480V Internal Transformer
15 13.78 (350) 29.72 (755) 20.43 (519) 1728 (785) 1828 (831)
30 13.66 (347) 30.94 (786) 20.67 (525) 1804 (820) 1904 (865)
45 13.43 (341) 32.32 (821) 20.87 (530) 1880 (855) 1980 (900)
60 13.23 (336) 33.43 (849) 21.06 (535) 1979 (900) 2079 (945)
75 13.15 (334) 34.96 (888) 21.26 (540) 2055 (934) 2155 (980)
90 13.03 (331) 36.26 (921) 21.50 (546) 2131 (969) 2231 1014)
600V Internal Transformer
15 14.37 (365) 32.40 (823) 19.80 (503) 1743 (792) 1843 (838)
30 14.25 (362) 33.70 (856) 19.96 (507) 1819 (827) 1919 (872)
45 14.02(356) 35.16 (893) 20.16 (512) 1895 (861) 1995 (907)
60 13.86 (352) 36.73 (933) 20.35 (517) 1989 (904) 2089 (950)
75 13.70 (348) 38.43 (976) 20.59 (523) 2065 (939) 2165 (984)
90 13.50 (343) 40.20 (1021) 20.91 (531) 2141 (973) 2241 (1019
Internal Maintenance Bypass
15 16.02 (407) 43.94 (1116) 21.89 (556) 985 (448) 1085 (493)
30 15.55 (395) 44.96 (1142) 22.13 (562) 1061 (482) 1161 (528)
45 15.16 (385) 46.22 (1174) 22.32 (567) 1137 (517) 1237 (562)
60 14.80 (376) 47.64 (1210) 22.52 (572) 1213 (551) 1313 (597)
75 14.57 (370) 49.21 (1250) 22.68 (576) 1289 (586) 1389 (631)
90 14.33 (364) 50.91 (1293) 22.80 (579) 1365 (620) 1465 (666)
Installation Drawings
65 Liebert® APM
Page 76
Installation Drawings

Table 12 Center of gravity and weights for Liebert APM 90 kVA frame with top fan option

Center of Gravity
Weight, lb (kg)
KVA Rating
Dimension X
in. (mm)
Dimension Y
in. (mm)
Dimension Z
in. (mm) Unit Shipping
Top Fan Option Only
15 17.99 (457) 37.83 (961) 18.70 (475) 827 (376) 927 (421)
30 16.34 (415) 38.90 (988) 18.43 (468) 903 (410) 1003 (456)
45 15.94 (405) 40.08 (1018) 18.23 (463) 979 (445) 1097 (498)
60 15.63 (397) 41.54 (1055) 18.03 (458) 1055 (480) 1155 (525)
75 15.31 (389) 43.11 (1095) 17.91 (455) 1131 (514) 1231 (560)
90 15.04 (382) 44.72 (1136) 17.72 (450) 1027 (549) 1127 (512)
480V Internal Transformer
15 13.94 (354) 29.92 (760) 20.31(516) 1759 (800) 1859 (845)
30 13.82 (351) 31.14(791) 20.55 (522) 1835 (834) 1935 (880)
45 13.58 (345) 32.52 (826) 20.79 (528) 1911 (869) 2011 (914)
60 13.39 (340) 33.66 (855) 20.94 (532) 2010 (914) 2110 (959)
75 13.27 (337) 35.16 (893) 21.14 (537) 2086 (948) 2186 (994)
90 13. 19(335) 36.46 (926) 21.38(543) 2162 (983) 2262 (1028)
600V Internal Transformer
15 14.53 (369) 32.60 (828) 19.69 (500) 1774 (806) 1874 (852)
30 14.41 (366) 33.86 (860) 19.84 (504) 1850 (841) 1950 (887)
45 14.17 (360) 35.35 (898) 20.04 (509) 1926 (875) 2026 (921)
60 14.02 (356) 36.93 (938) 20.24 (514) 2020 (918) 2120 (964)
75 13.86 (352) 38.58 (980) 20.47 (520) 2096 (953) 2196 (998)
90 13.58 (345) 40.39 (1026) 20.79 (528) 2172 (987) 2272 (1033)
Internal Maintenance Bypass
15 16.18 (411) 44.13 (1121) 21.77 (553) 1016 (462) 1116 (507)
30 15.67 (398) 45.20 (1148) 21.97 (558) 1092 (496) 1192 (542)
45 15.31 (389) 46.38 (1178) 22.20 (564) 1168 (531) 1268 (576)
60 14.96 (380) 47.83 (1215) 22.36 (568) 1244 (565) 1344 (611)
75 14.72 (374) 49.41 (1255) 22.56 (573) 1320 (600) 1420 (645)
90 14.49 (368) 51.02 (1296) 22.64 (575) 1396 (635) 1496 (680)
Liebert® APM
66
Page 77
Installation Drawings

Table 13 Center of gravity and weights for Liebert APM 45 kVA frame

Center of Gravity Weight, lb (kg)
kVA Rating
12HX100 Batteries
15 14.29 (363) 31.50 (800) 21.30 (541) 1922 (874) 2022 (919)
30 13.94 (354) 33.46 (850) 21.59 (548.4) 1998 (908) 2098 (954)
45 13.62 (346) 35.04 (890) 21.73 (552) 2074 (943) 2174 (988)
12HX150 Batteries
15 14.25 (362) 30.91 (785) 21.54 (547) 2114 (961) 2214 (1006)
30 13.78 (350) 32.87 (835) 21.81 (554) 2190 (995) 2290 (1041)
45 13.39 (340) 34.72 (882) 22.05 (560) 2260 (1030) 2360 (1073)
Dimension X
in. (mm)
Dimension Y
in. (mm)
Dimension Z
in. (mm) Unit Shipping

Table 14 Center of gravity and weights for Liebert APM 45 kVA frame with top fan option

Center of Gravity Weight, lb (kg)
Dimension X
kVA Rating
12HX100 Batteries
15 14.45 (367) 31.69 (805) 21.18 (538) 1953 (888) 2053 (933)
30 14.09 (358) 33.66 (855) 22.83 (580) 2029 (922) 2129 (968)
45 13.78 (350) 35.24 (895) 21.61 (549) 2105 (957) 2205 (1002)
12HX150 Batteries
15 14.41 (366) 31.10 (790) 21.42 (544) 2145 (975) 2245 (1020)
30 13.94 (354) 33.07 (840) 21.65 (550) 2221 (1010) 2321 (1055)
45 13.58 (345) 34.92 (887) 21.93 (557) 2297 (1044) 2397 (1090)
in. (mm)
Dimension Y
in. (mm)
Dimension Z
in. (mm) Unit Shipping
67 Liebert® APM
Page 78

Figure 51 UPS main components—typical unit

UAM02000 Rev. 2
Liebert APM 90kVA Frame
Liebert APM 45kVA Frame
UAM02000 Rev. 2
Installation Drawings
Liebert® APM
68
Page 79

Figure 52 UPS cable connections—45kVA and 90kVA frames

90kVA frame
45kVA frame
Installation Drawings
69 Liebert® APM
Page 80

Figure 53 Battery cabinet connection to UPS

UAM02021 Rev. 3
NOTES
1. Dimensions are in inches [mm].
2. Control wiring and power wiring must be run in separate conduits.
3. Emerson recommends using only copper cables.
4. All wiring must be in accordance with national and local electrical codes.
Refer to Table 15 for interconnect wiring
Installation Drawings
Liebert® APM
70
Page 81

Figure 54 Battery cabinet connection to UPS (continued)

600mm
Battery Cabinet
900mm
Battery Cabinet
Installation Drawings

Table 15 Interconnect wiring for Liebert APM to battery cabinet

Run From To Conductors
A UPS Battery Busbar External Battery Cabinet Busbar Positive, DC Neutral, Negative
B Battery Cabinet Terminal Block TB1
UPS Static Bypass Assembly J4 and J8
Battery Breaker Shunt and Aux Contacts
See Figure 40 for additional details.
NOTE
Wiring is supplied when the UPS and external battery cabinet are ordered as a system.
71 Liebert® APM
Page 82

Figure 55 Battery cabinet outline drawing, weights and center of gravity, 600mm cabinet

UAM05010 Rev. 2
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
13" (300mm) Outside Frame
Cable Entry Area
14.6" x 7.6" (370 x 190mm)
Cable Entry Area
8.2" x 8.7" (210 x 220mm) 2 Places
Cable Entry Area
7.9" x 23.6" (200 x 600mm)
7.9" (200mm) Outside Frame
5.6"
(142mm)
3.75" (95mm) Outside Panel
2.5" (65mm)
Outside Panel
34.3"
(872mm)
23.7"
(602mm)
23.6" (600mm)
78.7"
(2000mm)
See
Table
See
Ta bl e
39.5" (1000mm) Door Closed
28.3"
(719mm)
Bracket
Centers
24"
(609mm)
FRONT VIEW
Without Covers
RIGHT SIDE VIEW
Center
of Gravity
Center
of Gravity
Leveling Feet
BOTTOM VIEW
FRONT
TOP VIEW
Maximum
Door Swing - 120°
Z
X
Battery
and
Tray
Installation Drawings

Table 16 Battery cabinet, center of gravity and weights

Battery Model
12HX150-FR 300 580 900 1490 (677)
12HX205-FR 300 570 890 1755 (798)
12HX300-FR 290 550 870 2213 (1006)
12HX330-FR 280 550 860 2477 (1126)
* For shipping weight, add 100 lb. (45 kg). Source: UAM05010, Rev. 2
Center of gravity
X
in (mm)Yin (mm)Zin (mm)
Battery
Weights *
lb (kg)
Liebert® APM
72
Page 83

Figure 56 Battery cabinet outline drawing, weights and center of gravity 900mm cabinet

1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
UAM05012 Rev. 1
Cable Entry Area
8.2" x 8.7" (210 x 220mm) 2 Places
Cable Entry Area
14.6" x 7.6" (370 x 190mm)
Cable Entry Area
7.9" x 23.6" (200 x 600mm)
7.5" (190mm) Outside Frame
12.6" (320mm) Outside Frame
5.5"
(140mm)
4" (101mm)
Outside Panel
17.1" (434mm) Outside Panel
14.1"
(359mm)
Bracket Centers
14.1"
(359mm)
Bracket
Centers
35.8" (908mm)
20"
(507mm)
78.8"
(2000mm)
39.5" (1003mm) Door Closed
18.2"
(464mm)
34.3"
(782mm)
35.2" (895mm)
FRONT VIEW
Without Covers
RIGHT SIDE VIEW
Center
of Gravity
Center
of Gravity
BOTTOM VIEW
FRONT
TOP VIEW
Maximum Door Swing - 120°
Z
Battery
and
Tray
X
Leveling Feet
Center of Gravity, In. (mm)
Battery Type 12HX400-FR 12HX505-FR 12HX540-FR
X
17.3 (440)
17.3 (440)
17.3 (440)
Y 35 (890) 33 (840) 33 (840)
Z
20 (510)
20.9 (530)
20.9 (530)
Battery Type 12HX400-FR 12HX505-FR 12HX540-FR
Weight, Lb. (kg)
2693 (1224)
3245 (1475
3345 (1520)
Approximate Weights *
* For shipping weights, add 100 lb. (45 kg)
Installation Drawings
73 Liebert® APM
Page 84

Figure 57 Outline drawing, Liebert BDC for Liebert APM, 15-45kVA

1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
Cable Entry Area
11.4" x 13.2" (290 x 335mm)
Cable Entry Area
11.4" x 13.2" (290 x 335mm)
Cable Entry Area
6.2" x 13.2" (57 x 335mm)
Cable Entry Area
6.2" x 13.2" (57 x 335mm)
6.5"
(164mm)
Outside Panel
6.5"
(164mm)
Outside
Panel
11. 5"
(292mm)
Outside
Panel
5.5"
(140mm)
34.6"
(870mm)
23.7"
(602mm)
23.6"
(600mm)
39.5" (1000mm)
78.7"
(200mm)
28.3"
(719mm)
Bracket Centers
6.4"
(162mm)
Outside Panel
X
Y
24"
(609mm)
FRONT VIEW
RIGHT SIDE VIEW
Center
of Gravity
Leveling Feet
Z
BOTTOM VIEW
TOP VIEW
Maximum
Door Swing - 120°
UAM06008 Rev. 5
Liebert BDC with Distribution Type
Dimension, in. (mm)
Weight,*
lb (kg)XYZ
Without Panelboard 11.8" (300)
39.4"
(1000)
14.9" (379) 525 (239)
With Panelboard 11.8" (300)
39.4"
(1000)
14.9" (379) 625 (284)
* Shipping weight, add 100 lb. (45kg)
UAM06010 Rev. 5
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Only copper cables are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
Cable Entry Area
11.4" x 13.2" (290 x 335mm)
Cable Entry Area
11.4" x 13.2" (290 x 335mm)
Cable Entry Area
6.2" x 13.2" (57 x 335mm)
Cable Entry Area
6.2" x 13.2" (57 x 335mm)
6.5"
(164mm)
Outside Panel
5.5"
(140mm)
6.5"
(164mm)
Outside
Panel
11. 5"
(292mm)
Outside
Panel
34.6"
(870mm)
23.7"
(602mm)
23.6" (600mm)
39.5" (1000mm)
78.7"
(200mm)
28.3"
(719mm)
Bracket Centers
6.4"
(162mm)
Outside Panel
24"
(609mm)
FRONT VIEW
RIGHT SIDE VIEW
Center
of Gravity
Leveling Feet
Z
BOTTOM VIEW
TOP VIEW
Maximum
Door Swing - 120°
X
Y
Liebert BDC with Distribution Type
Dimension, in. (mm)
Weight,* lb (kg)XYZ
No Distribution 11.8" (300) 39.4" (1000) 14.9" (379) 550 (250)
With 2-225A Subfeed Breakers 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
With 400A Panelboard 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
* Shipping weight, add 100 lb. (45kg)
Installation Drawings

Figure 58 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA

Liebert® APM
74
Page 85

Figure 59 Liebert BDC connection to UPS

2.2" (56mm) Typ. 6 Places
1.97" (50mm) Typ. 3 Places
2.36" (60mm) Typ. 2 Places
37.5" (953mm)
Main Input Busbars
Links for Main to Bypass (Single Input Only)
Bypass Busbars
Output Busbars
DC Busbars See Detail D
Ground See Detail C
DETAIL B
See Detail B
UAM02021 Rev. 3
RIGHT SIDE
(Panel Removed)
Input Breaker
Input Ground
Bus System Input Busbar Located at Rear, Typ.
System Input Connections
Neutral Input Connections
DETAIL B
Iso View, Front Left
Corner Post Removed
UAM06020B Rev. 0
23.6" (600mm)
78.7"
(2000mm)
MBB
BIB
MIB
LDB
System
Input
Bus
UAM06020A Rev. 0
FRONT
(Door Removed)
See Detail A and
Isometric View
Detail B, Page 2
(See Note 6)
Installation Drawings

NOTES

1. All Emerson-supplied cable must be repositioned prior to and while the cabinets are being placed in their final installed location.
2. All interconnection hardware supplied by Emerson.
3. AC connections must be made to the UPS module before attaching Liebert BDC to UPS module.
4. All cabling will be field-supplied when a Liebert BDC is configured as a stand-alone cabinet.
5. Liebert BDCs must attach to the right side only of the Liebert APM.
6. Refer to the individual drawing of each piece of equipment for additional details.
75 Liebert® APM
Page 86
Installation Drawings

Table 17 Interconnect wiring for Liebert APM to Liebert BDC

Run
From To Conductors
A Utility AC source BDC System Input Bus Phase A, B, C
B Utility AC Source BDC System Input Bus Neutral
C BDC Bypass Isolation Breaker UPS Main Input Phase A, B, C
D BDC Bypass Isolation Breaker UPS Main Input Neutral
E UPS Output MBC Maintenance Isolation Breaker Phase A, B, C
F UPS Output MBC Maintenance Isolation Breaker Neutral
G BDC Panelboard Load AC Connection Phase A, B, C
H BDC Panelboard Load AC Connection Neutral
I Utility AC Source All Ground Connections Ground
J BDC Terminal Block TB1 UPS Static Bypass Module J5 and J12 Wiring for KO on MBC
See Figure 45 and Table 10 for additional details.
NOTE
Wiring is supplied when the UPS and Liebert BDC are ordered as a system.

Table 18 Spring washer torque application

Hardware Two Belleville Washers
M10 (3/8") 240 lb-in. (27 N-m)

Figure 60 Acceptable hardware configuration for torque application

Liebert® APM
76
Page 87

Figure 61 Seismic mounting bracket details

Rear
Wall
.5
(13mm)
Rear Cabinet
Base Bracket
.75
FLOOR
Cabinet
Rear Door
Rear Cabinet
Floor Bracket
3.5" (89mm)
Rear Anchor
Hardware
(Not Supplied)
39.2" (997mm)
(19mm)
Minimum
Detail A
Cabinet
Front Door
Anchor
Front Cabinet
Base Bracket
3.7" Front Cabinet
Base Bracket
(See Detail B)
(94mm)
FLOOR
Detail B
Installation Drawings
UAM08020
Rev. 2
6.5"
4.3" (110mm)
6.9"
9.8"
17.7" (450mm)
(165mm)
(175mm)
(250mm)
6.5" (165mm)
4.3" (110mm)
6.9" (175mm)
9.8" (250mm)
6.5" (165mm)
(REAR)
BYPASS
CABINET
DISTRIBUTION
UPS
15-90KVA
(FRONT)
5.5" (140mm)
5.5" (140mm)
5.5" (140mm)
11.0"
5.5" (140mm)
5.5" (140mm)
5.5" (140mm)
11.0" (280mm)
5.5" (140mm)
(280mm)
16.5" (420mm)
SEISMIC ANCHORING
5. Move cabinet into position with rear tabs into slots of
floor bracket. Tabs to extend at least 1/2" through floor
bracket (Detail A). Then attach front floor brackets to front
Bottom Of Units
(Viewed From Top Looking Down)
cabinet base bracket but do not fully tighten hardware.
6. Mark hole locations and remove brackets. Drill and install
floor brackets. Unit door can be removed for better access.
Reinstall front floor brackets to front cabinet brackets with
supplied hardware and torque to 235 lb-in (26.5 Nm).
7. After all cabinets are moved into place and secured to the
floor, multiple cabinet configurations are then bolted together.
8. If side walls are present, 1.0" (25.4mm) minimum distance from either
side wall is required.
4.3" (110mm)
6.9" (175mm)
Rear Base
Bracket
See Detail A
2.7" (69mm)
BATTERY
CABINET
5.5" (140mm)
5.5" (140mm)
NOTES
1. Recommended floor anchor: 1/2" ITW ramset/red head
self-drilling anchor, ICBO #ER-1372 or equivalent (not
supplied). Follow manufacturer’s instructions.
2. Position rear floor brackets on floor at least .75"
from rear wall. Mark location and drill holes (Detail A)
to a minimum depth of 4.12" (104.6mm) into the concrete.
3. Install rear cabinet base bracket (Detail A) to existing
holes on underside of unit with tabs facing rear wall.
Use supplied hardware and torque to 365 lb-inch (41.2 Nm).
Loosen leveling bolt locking nut and tighten after
bracket is secured.
4. Install front cabinet base bracket (Detail B) to existing
holes on underside of unit with bent flange facing front.
Use supplied hardware and torque to 365 lb-inch (41.2 Nm).
Loosen leveling bolt locking nut and tighten after
3.7" (94mm)
SLOT 16mm
RAD 7mm, Typical
bracket is secured.
77 Liebert® APM
Page 88
Liebert IntelliSlot® Installation

8.0 LIEBERT INTELLISLOT® INSTALLATION

8.1 Liebert IntelliSlot Communication

The Liebert APM has three Liebert IntelliSlot ports to allow installation of optional communication cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary Velocity protocol to cards that translate the information into such protocols as SNMP and Modbus. Other cards provide dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert APM is operating.

8.2 Liebert IntelliSlot Web Card—SNMP/HTTP Network Interface Card

This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured parameters for display via a Web browser. The Liebert IntelliSlot bays are on the right side of the control module and labeled as IntelliSlot1, IntelliSlot2 and IntelliSlot3.

Table 19 Liebert APM communication options

Port Type and
Location
Left Liebert
IntelliSlot
Center Liebert
IntelliSlot
Right Liebert
IntelliSlot
Labeled ID
Name of Port
IntelliSlot 1
IntelliSlot 2
IntelliSlot 3
Monitoring
Devices Supported
IS-MultiPort
IS-Relay
IS-485EXI
IS-MultiPort
IS-Relay
IS-Unity-DP
IS-Unity-LIFE
IS-485EXI
IS-MultiPort
IS-Relay
IS-Unity-DP
IS-Unity-LIFE
IS-485EXI
Liebert® APM
78
Page 89
Liebert IntelliSlot® Installation

8.2.1 Liebert IntelliSlot® Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP

IS-UNITY-LIFE (Included): Offers a web interface to manage and configure the Emerson Life.net and Emerson proprietary protocols for use with the Emerson Life Station
®
Nform
and Emerson® Trellis™.
IS-UNITY-DP: Offers a web interface to monitor and configure the Life.net and Emerson Network Power proprietary protocols for use with the Emerson Life Station, Liebert Nform and Emerson Trellis. It allows selection and configuration of two of the available third-party protocols—SNMP, Modbus or BACnet—for operation with building management systems.
Liebert IntelliSlot
®
Dry Contact Card (IS-RELAY): Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals for communication to a remote monitoring system or for use with Liebert MultiLink
Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) Provides dry contact alarm information, including: On Battery, Low Battery signals for communication to four servers for use with Liebert MultiLink software.
IS-485EXI: The Liebert IntelliSlot 485 EXI Card provides connection to a Liebert SiteLink-E™ allowing Liebert SiteScan® Web 4.0 monitoring and control of your Liebert equipment.

8.3 Liebert IntelliSlot Card Web Interface

The IS-Unity-Life and IS-Unity-DP IntelliSlot cards offer a Web interface, yielding a wide variety of status and summary information through an Ethernet connection. Liebert’s IS-Unity-DP also provides e-mail and text notification.
, Liebert
®
software.

Figure 62 Liebert IntelliSlot Web card display

79 Liebert® APM
Page 90

8.4 Liebert IntelliSlot® Relay Card

18
101
9
TB1
green
TB2
black
The Liebert IntelliSlot Relay card (IS-RELAY) provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A. and supported in any of the three Liebert IntelliSlot bays on the Liebert APM.

8.4.1 Liebert IntelliSlot Relay Card Pin Configuration

The card has two terminals blocks, TB1 (green, numbered 1-9) and TB2 (black, 10-18), as shown in Figure 63.
Figure 63 Pin location and numbering
Liebert IntelliSlot® Installation
Refer to your Liebert product user manual for the pin configuration for the terminal blocks.
Table 20 Relay card pin configuration
Pin Function Operation
1 Common - Low Battery
2 Low Battery Closed if Low Battery point occurs.
3 Low Battery Closed if battery is OK
4 Common - UPS Fault
5 UPS Fault Closed if UPS fault occurs
6 UPS Fault Closed if no UPS failure
7 Common - On Battery
8 On Battery Closed if On Battery power (Utility failure)
9 On Battery Closed if not On Battery power (Utility OK)
10 Not Used
11 Not Used
12 Not Used
13 Summary Alarm* Closed if no alarm conditions are present
14 Summary Alarm* Closed if Summary Alarm occurs
15 Common - Summary Alarm*
16 On UPS Closed if On UPS (inverter) power
17 On Bypass Closed if On Bypass
18 Common - On Bypass
Liebert® APM
80
Page 91

8.4.2 Liebert IntelliSlot® Relay Card Jumper Setup

Jumper P6
Jumper P5
Jumper P4
Jumper P3
Jumper P7
Front
of
Card
The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 64. Each jumper connects two pins.
Figure 64 Jumper location and numbering
Liebert IntelliSlot® Installation
By default all five jumpers have shunts installed. The two pins are shunted together to provide the functions shown in Table 21, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or inadvertently be connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are not tied together.
Table 21 Jumper connections
Jumper Relay
P6 On Battery
P5 UPS Fault
P4 Low Battery
P3 On Bypass
P7 Summary Alarm
NOTE
Refer to the Liebert IntelliSlot Relay Card manual, SL-23211 for additional details. the document is available at the Liebert Web site, www.liebert.com
81 Liebert® APM
Page 92

8.5 Liebert IntelliSlot™ MultiPort Card

Pin Description
1 Low Battery
2 Utility Fail
3 NOT USED
4 NOT USED
5 NOT USED
6 NOT USED
7 Low Battery Common
8 Utility Fail Common
IS-MULTIPORTUPS
Liebert MultiLink computers
AS/400 system units
The Liebert IntelliSlot MultiPort card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical application is to allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure-low battery) of a single UPS.
This card is supported in any of the three Liebert IntelliSlot bays on the Liebert APM.

Figure 65 Liebert IntelliSlot MultiPort card pin assignment

Liebert IntelliSlot® Installation

8.6 Alber® BDSi™ Battery Monitoring System—Optional

The matching Liebert battery cabinets allow installing an optional Alber BDSi battery monitoring system inside the cabinet. The Alber BDSi by Emerson continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery's operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting.
The Alber BDSi system is installed inside the battery cabinet as shown in Figures 11 and 12. The monitoring system power inlet is wired to the Alber BDSi Fuse Block on the UPS (see ,Figures 13 and 66). The Alber BDSI fuse block supplies 120VAC and has an 8A fuse.
If required, power can be supplied from the output terminals of the UPS, a distribution panel or another UPS-protected source.
For details about operating the Alber system, refer to the Alber unit’s documentation, available at
http://www.alber.com/
Liebert® APM
82
Page 93

Figure 66 Alber BDSi controller and input connection

!
OUTPUT POWER X XXXXXXA
INPUT
XXXXXXXXXXXXXAXA
XXXXXXXXXXXA
Input
120VAC 50/60Hz
Rear Panel
Liebert IntelliSlot® Installation
83 Liebert® APM
Page 94

8.7 Battery Temperature Compensation

Temperature
Sensor
TMP-2
NC
12V
GND
OUT
BCB Control Board
X103
X105
X104
X106
X108
Static Bypass Module
Monitor
Board
– X2
+12V
GND
BAT_OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
NC
12V
GND
OUT
+
IN
-
+
IN
-
+
IN
-
+
IN
-
12V
OUT
GND
J4
For a UPS with external batteries, an optional battery temperature interface optimizes the external battery management by connecting up to four external temperature sensors from the battery cabinets to a control unit inside the UPS.

Figure 67 Multi-temperature sensors

Liebert IntelliSlot® Installation
Liebert® APM
84
Page 95

9.0 OPERATOR CONTROL AND DISPLAY PANEL

STATUS
EMERSON
Network Power
TM
F1 F2 F3 F4
HELP
FAULT CLEAR
EPO
INV E R TE R OF F
SILENCE ON/OFF
INV E R TE R ON
Control buttons
LCD and Menu Buttons
Mimic current path
1
2
3
54
6
7
8

9.1 Operator Control Panel

The control panel and LCD on the front of the Liebert APM lets the operator:
• Turn the UPS On or Off.
• Transfer into the various operating modes.
• Silence alarms.
• Check the status of the UPS and its batteries, including all measured parameters, events and alarms.
The main areas of the control panel are shown below in Figure 68 and explained in Table 22.
Mimic Display - view the status of the Liebert APM in single-line diagram format—indicators show status by changing color when ON, flashing or OFF
Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from the Liebert APM in tabular format
Control buttons - turn the Liebert APM on or off, silence alarms

Figure 68 Overview of control panel

Operator Control and Display Panel

Table 22 Descriptions of UPS operator control and display panel

Mimic Current Path Control Buttons
Item # Function Button Function
1 Rectifier indicator (AC to DC) EPO EPO switch
2 Battery indicator (backup DC power) INVERTER ON Inverter start button
3 Bypass input indicator INVERTER OFF Inverter shutdown button
4 Inverter indicator (DC to AC) FAULT CLEAR Fault reset button
5 Load indicator (AC output) SILENCE ON/OFF Alarm mute button
6 UPS status and alarm indicator Menu Buttons
7 Audible alarm (buzzer) Button Function
8 Protective cover for EPO button F1 through F4 and HELP LCD menu keys
NOTE
Help button menus are not active. Future units will ship with an F5 legend in place of the HELP legend.
85 Liebert® APM
Page 96
Operator Control and Display Panel
STATUS
EMERSON
Network Power
TM
1
2
3
4
5
6
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator

9.2 Mimic Display Indicators

Figure 69 Mimic display indicators location

Mimic indicators show the operational status of the Liebert APM by their color—green, amber or red—and whether they are ON (solid), flashing or OFF. Table 23 provides a guide to interpreting the various states of the indicators.

Table 23 Mimic display status indicators

Indicator
(see Figure 69) Green Flashing Green / Amber Red Off
1. Rectifier Load on Rectifier
2. Battery
3. Bypass
4. Inverter
Battery Powering the Load
Load on Bypass Power
Inverter Powering the Load Normally
Flashing Green: Utility normal, but rectifier not operating
Flashing Green: Battery pre-warning (low battery)
Flashing Green: Inverter on standby
Rectifier fault
Battery or battery converter abnormal*
Bypass out of normal range
Inverter fault Inverter normal but Off
5. Load UPS output On UPS output overloaded UPS has no output power
6. Status
* Battery or battery converter abnormal events include these event messages (see Table 57): No Battery, Battery Replaced, Battery
Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
No Alarms—UPS Working Normally
Amber: UPS has a general alarm
UPS has a serious alarm
Rectifier is normal, but utility is abnormal
Battery and converter are normal, and battery is not discharging
Bypass Normal
Liebert® APM
86
Page 97

9.3 Control Buttons

STATUS
EMERSON
Network Power
TM
F1 F2 F 3 F4
HELP
FAULT CLEAR
EPO
INVERTER OFF
SILEN CE ON/ OFF
INVERTER ON
EPO Button Cover
EPO Button
Inverter Off Button
Fault Clear Button
Silence On/Off Button
Inverter On Button
LCD Navigation Keys
STATUS
EMERSON
Network Power
TM
F1 F2 F3 F4
HELP
FAULT CLEAR
EPO
INVE R TE R O FF
SILENCE ON/OFF
INVERTER ON
Buzzer
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 70. The function of each button is described in Table 24.
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.

Figure 70 Control button layout

Operator Control and Display Panel

Table 24 Control buttons

Button
(see Figure 70) Function
Completely shuts down the UPS, including the static switch.
EPO
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button completely shuts down the unit and the critical load.
INVERTER ON
INVERTER OFF
FAULT CLEAR
Press this button to start the inverter and transfer from static bypass to inverter. NOTE: If the inverter is not ready, this will not activate the UPS.
Press this button to shut down the inverter during operation. The load will be transferred to static bypass.
After the UPS shuts down due to a fault and the alarm condition has been resolved, press this button to clear the fault and restart the UPS.
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will
SILENCE ON/OFF
sound the buzzer again. If the alarm buzzer is not beeping, press this button to test the alarm sound.

9.4 Alarm Buzzer

The alarm buzzer produces three types of sounds:
Single beep—When any Control button is pressed
Single beep repeating every two seconds—The system has a general alarm
Continuous—The system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have been silenced manually.

Figure 71 Alarm buzzer location

87 Liebert® APM
Page 98

9.5 LCD Overview

F1 F2 F3 F4
HELP
Single APM 090kVA
02:17:47
L1-N/L2 L2-N/L3 L3-N/L1 L-N voltage (V) 121.4 L-N current (A) 12.2 Frequency (Hz) 59.96 L-L voltage (V) 211.3 Power factor 0.00
122.7
14.2
59.96
211.6
0.00
121.7
13.5
59.96
210.5
0.00
Mains
UPS System Information
Current menu
Current status
Menu icons
Return to Output Menu
Move to Next Menu
Time
Alarms
E-Mail Notification Icon
The LCD on the front panel has five main sections, as shown in Figure 72. Press the F1 key below the LCD to scroll through these sections.
UPS system information - view UPS name and model, date and time, overall status.
LCD Menu - choose a category of data items to appear below the menus (see Table 26).
Data and settings - view data items for the selected menu (see Table 26).
Current status messages - check the most recent UPS event and alarm messages (see Table 57).
Navigation key icons - look at the icon above each navigation key to determine how the key operates when pressed (see 9.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the LCD, status messages are stored in the history log—512 records can be stored and retrieved.

Figure 72 Sections of the LCD

Operator Control and Display Panel
Liebert® APM
88
Page 99

9.6 Navigation Keys

ESC
?
The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the Liebert APM.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 25). The keys are “soft keys” that can change functions according to the icon.
•Use F1 to move to the home portion of the LCD.
•Use F3 and F4 as cursor keys to move left and right or up and down, depending on the icons displayed above the keys.
•Use F3 and F4 on the display simultaneously to view individual Module information such as Input and Output conditions and individual Module Firmware versions
•Use F2 as an ESC key.
•Use HELP to access help information on the LCD or to enter a choice.

Table 25 Icons for navigation keys

Key F1 F2 F3 F4 HELP
Operator Control and Display Panel
Functions Available
Home

9.7 LCD Menus and Data Items

The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and described in detail in Table 26.
Mains - view utility power input data: voltage, current, frequency and power factor
Bypass - view bypass data: voltage and frequency
Output - view output data: voltage, current, frequency and power factor
Load - view load data: load percent, output current, output power and crest factor (CF)
System - view system data
Battery - view battery characteristics—voltage, current, temperature, remaining time and capacity—and messages when the battery is boost/float charging or disconnected
Events - view the events log—displays all recent events added to the log (new records added at end)
Records - access the history log—displays all records in the log (new records added at end)
Language - select a language for LCD text (choices appear in the native language)
Settings - configure UPS settings: adjust the display contrast, choose a format for date display, set the date and time, set up the UPS for modem communications (baud rate, address, mode and phone numbers to dial for alarm notifications) and change the password
Command - start or stop a battery maintenance test, battery capacity test or system test
Run Time - view available backup time for the UPS and bypass
Version - view firmware versions for the inverter, rectifier and software display board and the model information for the UPS
Figure 73 shows a menu tree of the options available from the LCD menus.
Left Right Enter
Exit
Up Down Help
89 Liebert® APM
Page 100

Figure 73 Menu tree

Battery
Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min. Battery capacity (%) Battery boost charging Battery float charging Battery disconnected
Command
Battery maintenance test Battery capacity test System test Stop testing Freshening Charge Stop Freshening Charge Modem Auto-answer enable Battery Reset
Run Time
UPS Run Time Byp Run Time
System
Sout (kVA) Pout (kW) Qout (kVAR)
Records
(history log)
Language
(Choices for display)
Mains (input)
L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
Load
Sout (kVA) Pout (kW) Qout (kVAR) Load level % Crest factor
Bypass
L-N voltage (V) Frequency (Hz) L-L voltage (V)
Output
L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
Settings
Display contrast Date format set Date & time Comm1 baud rate Comm2 baud rate Comm3 baud rate Communication address Communication mode Callback times Phone No.1 Phone No.2 Phone No.3 Command password Protocol ECO Mode Battery Equalize Charge
Events
(events log)
Version
Monitor version Rectifier version Inverter version Bypass version UPS model
Operator Control and Display Panel

9.8 Language Selection

The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different language:
1. From the main menu, press the F4 (shift) key to move the cursor to the Language menu at the
2. Press HELP to access the language choices.
3. Press F3 and F4 (left and right arrows) as needed to highlight the desired language.
4. Use HELP to select the required language.
Liebert® APM
5. Return to the main menu by repeatedly pressing F2 (ESC) and F1.
bottom of the screen.
All text on the LCD will now be displayed in the selected language.
90
Loading...