Precision Cooling
For Business-Critical Continuity™
Liebert® CRV
User Manual–60Hz, 24-Inch Wide, Air-Cooled, Water/Glycol-Cooled and Chilled Water
™
MODEL NUMBER NOMENCLATURE - 25 DIGIT CONFIGURATION NUMBER
Model # Part 1 *Model DetailsModel # Part 2 *
12345678910111213141516171819202122232425
CR0 2 0 RA1 C 7 S D 1 8 1 1 E L 1 0 P A * * *
Digits 1-2 - Unit FamilyDigit 17 - High-Voltage Options
Digits 3-5 - Nominal Capacity, kW
Digit 6
Digit 7 - System Type
Digit 8 - Fan TypeH = Reheat and Humidifier Lockout
Digit 9 - Power Supply
Digit 10 - Cooling System
Digit 11 - Humidifier2 = (2) Web Cards
Digit 12 - Display Type5 = (1) Web Card and (1) 485 Card
Digit 13 - ReheatD = (1) Liebert SiteLink-E Card and (1) Web Card
Digit 14 - Air FilterG = (2) Building Management Cards
Digit 15 - Water/Glycol Valve Type
Digit 16 - Unit ColorP = Domestic
* The 14-digit model number consists of the first 10 digits and last four digits of the Configuration Number.
** L and 5 for CW models; A and E for DX models.
®
Liebert
CRV™ = CR
L or A = NO dual-float condensate pump (for units without
humidifier), 5kA SCCR**
DX = 020, 035
CW = 040
5 or E = Dual-float condensate pump (for units with or
without humidifier), 5kA SCCR**
M = No dual-float condensate pump (for units without
R = Row-Based, 1100mm unit depth
humidifier), 65kA SCCR, 600 series only
P = Dual-float condensate Pump (for units with or without
A = Air Cooled
humidifier), 65kA SCCR, 600 series only
W = Water\Glycol CooledDigit 18 - Option Package
C = Chilled Water Cooled0 = None
Variable Speed EC Plug Fans = 1
C = Reheat and Humidifier Lockout Additional Alarm
Contact
A = 460V / 3ph / 60HzD = Low Sound Package (20kW and 35kW only)
C = 208V / 3ph / 60Hz
L = Low Sound Package & Reheat and Humidifier Lockout
This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert CRV. Read this manual thoroughly before attempting to carry out
any operations on the Liebert CRV, including installation and operation. Retain this manual for the
entire service life of the Liebert CRV.
Only properly trained and qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in
this manual. Follow all operating and user instructions.
Any operation that requires opening doors or equipment panels must be carried out only by properly
trained and qualified personnel.
Each machine is equipped with an electric insulation device that allows the operator to work safely.
Switch Off the machine with this electric insulation device before beginning any maintenance
operation to eliminate remaining risks (electric shocks, burns, automatic restarting, moving parts
and remote control).
The panel key supplied with the unit must be kept by the person responsible for maintenance. To
identify the unit by model and serial number in order to obtain assistance or spare parts, locate the
identification label on the outside of the unit.
Important Safety Instructions
A warning label on the front and back panels reminds users that:
• the Liebert CRV restarts automatically
• the main switch must be opened before opening the internal compartments for any operation.
WARNING
Risk of high temperatures, extreme cold and high-speed rotating fan blades. Can cause
equipment damage, injury and death.
Disconnect all local and remote electrical power supplies, confirm that all fan blades have
stopped rotating and allow the component temperatures to become safe for human contact
before opening doors and/or removing protective covers and working within.
If the doors are opened immediately after the Liebert CRV has been switched Off:
• some components, such as electrical heaters, compressor, outlet area and outlet piping, may
remain at high temperature about 212°F (100°C);
• some components, such as the evaporator, may remain at low temperature;
• fan blades may continue to rotate by inertia.
These residual risks are highlighted by warning labels on the Liebert CRV.
WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury and death.
This unit contains fluids and gases under high pressure. Relieve pressure before working with
piping.
WARNING
Risk of hair, clothing and jewelry entanglement with high speed rotating fan blades. Can
cause equipment damage, serious injury or death.
Keep hair, jewelry and loose clothing secured and away from rotating fan blades during
operation.
®
1Liebert
CRV
™
Important Safety Instructions
!
!
!
!
WARNING
Arc flash and electric shock hazard. Can cause injury and death.
Disconnect local and remote power supplies and wear appropriate personal protective
equipment per NFPA 70E before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM
mode.
Some internal components require and receive power even during the Unit Off mode of the
Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch
contains live hazardous voltage potential.
Install and open a remote disconnect switch and verify with a voltmeter that live hazardous
voltage potential is not present inside the unit cabinet before working within. Refer to the
unit electrical schematic.
Follow all national and local codes.
®
microprocessor does not isolate power from the unit, even in the Unit Off
WARNING
Risk of refrigerant system rupture or explosion from overpressurization. Can cause
equipment damage, injury and death.
A pressure relief valve is required for compliance with the EU Pressure Equipment Directive
and may be required for compliance with local codes. If a discharge pressure relief device is
not provided with the condenser unit, the system installer must install one in the high side of
the refrigerant circuit and rated for a maximum of:
• 675psig (46.5bar) for water/glycol-cooled units
• 700psig (48.3bar) for air-cooled units
A shutoff valve must not be installed between the compressor and the field-installed relief
valve.
One or more additional pressure relief valves are required downstream of any and all
field-installed isolation. Do not isolate any refrigerant circuits from overpressurization
protection.
WARNING
Risk of top-heavy unit falling over. Can cause equipment damage, personal injury and death.
Read all of the following instructions before attempting to move, lift or remove packaging
from the Liebert CRV.
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or
prepare the unit for installation.
NOTICE
Risk of overhead interference. Can cause unit and/or building damage.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and
doorway heights and refer to the installation plans prior to moving the unit to verify
clearances.
NOTICE
Risk of improper storage, Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and
contact damage.
Liebert® CRV
™
2
Important Safety Instructions
NOTICE
Risk of water leakage. Can cause severe property damage and loss of critical data center
equipment.
This unit requires a water drain connection. It may require an external water supply to
operate the humidifier. Improper installation, application and service practices can result in
water leakage from the unit.
Do not locate the Liebert CRV directly above any equipment that could sustain water damage.
Emerson recommends installing monitored leak detection equipment for the unit and supply
lines.
NOTICE
Risk of frozen fluids. Can cause equipment damage and building damage.
Freezing system fluids can rupture piping. Complete system drain-down cannot be ensured.
When the field piping or unit may be exposed to freezing temperatures, charge the system
with the proper percentage of glycol and water for the coldest design ambient.
Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system.
NOTICE
Risk of corrosion. Can cause equipment damage.
Read and follow individual unit installation instructions for precautions regarding fluid
system design, material selection and use of field-provided devices. Liebert systems contain
iron and copper alloys that require appropriate corrosion protection.
Contact a local water consultant regarding water quality, corrosion and freeze protection
requirements.
Water chemistry varies greatly by location, as do the required additives, called inhibitors,
that reduce the corrosive effect of the fluids on the piping systems and components. The
chemistry of the water used must be considered, because water from some sources may
contain corrosive elements that reduce the effectiveness of the inhibited formulation.
Sediment deposits prevent the formation of a protective oxide layer on the inside of the
coolant system components and piping. The water/coolant fluid must be treated and
circulating through the system continuously to prevent the buildup of sediment deposits and
or growth of sulfate reducing bacteria.
Preferably, surface waters that are classified as soft and are low in chloride and sulfate ion
content should be employed. Proper inhibitor maintenance must be performed in order to
prevent corrosion of the system. Consult glycol manufacturer for testing and maintenance of
inhibitors.
Commercial ethylene glycol (Union Carbide Ucartherm, Dow Chemical Dowtherm SR-1 and
Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive to the common
metals of construction than water itself. It will, however, assume the corrosivity of the water
from which it is prepared and may become increasingly corrosive with use if not properly
inhibited.
NOTICE
Risk of no-flow condition. Can cause equipment damage.
Do not leave the unit in a no-flow condition. Idle fluid allows the collection of sediment that
prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched
On and system pump operating.
NOTE
The Liebert indoor cooling unit has a factory-installed high pressure safety switch in the high
side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp
Consult your local building code to determine if the Liebert VFD condensers will require
field-provided pressure-relief devices. A fusible plug kit for Liebert VFD condensers is available
for field installation.
3Liebert
™
condensers.
®
CRV
™
1.0LIEBERT CRV COMPONENT LOCATION
1Liebert iCOM® control display
2Electric box
3Evaporator / CW coil
4Condensate pump
5Electric heaters
6Humidifier distributor
7
Top humidifier water supply,
condensate pump drain
8Drain trays, two places
9EC plug fans
10Bottom electrical entrance
11Serial tag inside door
12Bottom condensate pump drain
13Top electrical entrance
14
Supply air temperature sensor
location (sensor not shown)
1
2
11
3
12
10
4
8
8
6
5
9
13
7
14
Front
Rear
8
1
10
3
4
7
9
2
5
6
11
12
13
1Thermostatic expansion valve
2Solenoid valve
3Sight glass
4Filter dryer
7Humidity/temperature sensor
8Humidifier
9Top refrigerant connections
10Bottom refrigerant connections
11Bottom humidifier water supply
12Air filters
13Bottom drain
14Compressor
15Vibasorber
Rear
Front
Figure 1Component location, common components—All models
Liebert CRV Component Location
Figure 2Component location - Liebert CR035RA, CR020RA air-cooled units
Liebert® CRV
™
4
Liebert CRV Component Location
2
3
1
4
5
6
7
1Top water/glycol connections
2Compressor
3Brazed plate condenser
4Bottom water/glycol connections
5Water/glycol valve
6Refrigerant receiver
7Air filters
8Vibasorber
9Thermostatic expansion valve
10Sight glass
11Filter dryer
12Humidity/temperature sensor
13Bottom humidifier water supply
2
3
1
5
4
1Top CW connections
2Air filters
3Three-way CW valve
4Bottom CW connections
5Humidifier
6Humidity/temperature sensor
7Bottom humidifier water supply
Figure 3Component location - Liebert CR035RW, CR020RW water/glycol-cooled units
Figure 4Component location - Liebert CR040RC chilled water units
5Liebert
®
CRV
™
Figure 5Overall dimensions / service area
Only front or back
clearance required
BS
S
A
Rear
Rear
Access Required to Remove / Install
Entire Unit Within The Row
The Liebert CRV is a precision cooling unit available in compressorized (air-, water- or glycol-cooled)
and chilled water configurations to be installed within a row of high-density computing racks in a
“hot aisle-cold aisle” configuration.
Air enters the rear of the Liebert CRV from the hot aisle, is filtered, cooled and conditioned, then
discharged into the cold aisle. The Liebert CRV provides all the necessary functions of a standard
precision air conditioner, including cooling, heating, humidification, dehumidification, air filtration,
condensate management, temperature control, alarm monitoring and data communication. The
Liebert CRV is optimized for maximum cooling capacity in a minimal footprint.
Figure 6Liebert CRV, front and rear views
Introduction
®
7Liebert
CRV
™
3.0INSPECTIONAND UNPACKING
!
!
R
Z
Y
X
WARNING
Risk of top-heavy unit falling over. Can cause equipment damage, personal injury and death.
Read all of the following instructions before attempting to move, lift or remove packaging
from the Liebert CRV.
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or
prepare the unit for installation.
NOTICE
Risk of overhead interference. Can cause unit and/or building damage.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and
doorway heights and refer to the installation plans prior to moving the unit to verify
clearances.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and
contact damage.
Inspection and Unpacking
3.1Equipment Inspection
After the Liebert CRV unit arrives and before it is unpacked, verify that the delivered equipment
matches the bill of lading. Examine the packaging for any signs of mishandling or damage. Inspect all
items for damage, visible or concealed. Report any damage immediately to the carrier and file a
damage claim. Send a copy of the claim to Emerson Network Power or your Emerson representative.
3.1.1Packing Material
All material used to package this unit is recyclable. Please save this material for future
use or dispose of it appropriately.
3.2Handling
Figure 7Liebert CRV center of gravity
Liebert® CRV
™
8
Inspection and Unpacking
• Always keep the packaged Liebert CRV upright and never leave it outdoors.
• Be aware of the center of gravity indicated on the package and in Table 2 below:
Table 2Center of gravity
Distance from lower right front corner, ± 2 in. (51m)
Model no.
CR02020 (508)12 (305)28 (711)
CR03520 (508)12 (305)32 (813)
CR04021 (533)12 (305)32 (813)
The center of gravity on the Liebert CRV varies with the options and the model's size.
AirWater/GlycolChilled WaterAirWater/GlycolChilled Water
3.2.1Handling the Unit While it is Packaged
Figure 8Recommended unit handling equipment
Forklift
Pallet Jack
• Transport the packaged unit using a forklift, pallet jack or by overhead lift with slings and
spreader bars that are rated for the weight of the unit (see tables above).
• When using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest
allowable distance to still fit under the skid. Make sure the fork length is suitable for the skid
length. Skid length is 60" (1524mm).
• Do not lift the packaged unit any higher than 4" (102mm). All personnel except those moving the
Liebert CRV must be kept 12' (3.7m) or more from the unit while it is being moved.
• If the unit must be lifted higher than 4" (102mm) all personnel not directly involved in moving the
Liebert CRV must be 20' (5m) or more from the unit.
Spreader Bars
and Slings
®
9Liebert
CRV
™
3.3Moving the Unit Using Rigging
!
197023
Rev. 4
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or
prepare the unit for installation.
1. Use a pallet jack or forklift to raise the packaged unit.
2. Place slings under the skid runners, equally spacing the slings to make sure the unit is balanced
(see Figure 9).
3. Lower the unit and remove the pallet jack or forklift.
4. Connect the slings to the lifting device, using spreader bars or similar equipment to protect the
unit (see Figure 9).
NOTE
Wrapping one or two more straps around the middle of the Liebert CRV will improve stability
when it is lifted.
5. Move the unit to its installation location. Two or more properly trained and qualified personnel
are required to move the Liebert CRV to its installation location.
6. Lower the Liebert CRV and remove the slings.
Inspection and Unpacking
Figure 9Moving the unit using rigging
3.4Unpacking the Liebert CRV
1. Remove the lag bolts securing ramp to skid.
2. Place the ramp and and the plastic bag with orange clips to the side for use in removing the unit
from the skid.
3. Remove the stretch film and corner/side packaging planks from around the unit.
4. Remove the unit bag when ready to install the unit.
Liebert® CRV
™
10
Figure 10 Unpacking the Liebert CRV
!
!
197023
Rev. 4
3.5Removing the Unit from the Skid
WARNING
Risk of top-heavy unit falling over. Can cause equipment damage, personal injury and death.
Read all of the following instructions before attempting to move, lift or remove packaging
from the Liebert CRV.
Inspection and Unpacking
CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or
prepare the unit for installation.
1. Open the top panel door with the mounted control (refer to Figure 11).
2. Remove the bottom baffle panel assembly by removing the screws with a T30 Torx screwdriver.
3. Set the baffle panel assembly aside until the Liebert CRV is ready for it to be to reattached.
4. Close and latch the top panel door.
5. Place the ramp against the skid as shown in Figure 11.
6. Remove the orange clips from the plastic bag.
7. Insert clips into holes of the skid and ramp.
8. Remove the eight bolts, four on each side, that secure side tie-down brackets to skid.
Bolts can be removed using a 17mm socket wrench, open-end wrench or pliers.
9. Lower the four stabilizer feet until the side tie-down brackets no longer contact the skid.
10. Remove the six bolts, three on each side), that secure the side tie-down brackets to the unit base.
The bolts can be removed using a 13mm socket wrench, open-end wrench or pliers.
11. Remove the side tie-down brackets.
12. Remove the eight bolts, four on each side, that secure the lift block to the skid.
The bolts can be removed using a 17mm socket wrench, open-end wrench or pliers.
13. Remove the lift blocks from the skid.
14. Using the stabilizer feet, lower the unit to the skid.
15. Move the unit to its installation location. Two or more properly trained and qualified personnel
are required to move the Liebert CRV to its installation location.
11Liebert® CRV
™
Figure 11 Removing the unit from the skid
4 Bolts on Each Side
Secure the Tie-Down
Bracket to the Skid
Step 5
197023
Rev. 4
Step 1
Step 8
Step 8
Step 15
Inspection and Unpacking
3.6Reattach the Baffle Panel
Once the Liebert CRV has been moved to where it will be installed, the baffle panel can be reattached.
1. Open top panel door (the one with the Liebert iCOM
2. Reattach the bottom baffle panel assembly with screws, using a T30 Torx drive.
3. Close and latch top panel door.
M17 Socket
M13 Socket
®
).
Liebert® CRV
™
12
4.0PREPARETHE LIEBERT CRV FOR INSTALLATION
Adjust the
height of the
feet
Tighten this nut after
the foot is adjusted to
the desired height
1. Open the display door and remove the lower front baffle panel using a 10mm nutdriver or T30
Torx Bit to prepare for installation.
2. Open the rear panel, referring to Figure 10. The documents are located inside the display door.
3. After the Liebert CRV is in its final installation position, adjust the four base supports, or feet,
with an adjustable wrench. Ensure that the unit is level to avoid corrosion or health hazards
caused by condensate accumulation.
a. Turning the base supports, or feet, clockwise, will extend them, lifting the unit one corner at a
time.
b. Tighten the nut on the top of each adjustable foot, inside the Liebert CRV, to lock the feet.
Figure 12 Adjust leveling feet
Prepare the Liebert CRV for Installation
13Liebert® CRV
™
5.0PIPING
All fluid and refrigeration connections to the unit, with the exception of the condensate drain, are
sweat copper. Factory-installed piping brackets must not be removed. Field-installed piping must be
installed in accordance with local codes and must be properly assembled, supported, isolated and
insulated. Avoid piping runs through noise-sensitive areas, such as office walls and conference rooms.
Refer to specific text and detailed diagrams in this manual for other unit-specific piping
requirements.
All piping below the elevated floor must be arranged so that it offers the least resistance to airflow.
Careful planning of the piping layout under the raised floor is required to prevent the airflow from
being blocked. When installing piping on the subfloor, Emerson recommends installing the pipes in a
horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be run
parallel to the airflow.
5.1Fluid Connections
NOTICE
Risk of water leakage. Can cause severe property damage and loss of critical data center
equipment.
This unit requires a water drain connection. It may require an external water supply to
operate the humidifier. Improper installation, application and service practices can result in
water leakage from the unit.
Do not locate the Liebert CRV directly above any equipment that could sustain water damage.
Emerson recommends installing monitored leak detection equipment for the unit and supply
lines.
Piping
Liebert® CRV
™
14
5.1.1Condensate Piping—Field-Installed
CORRECT
INCORRECT
UNIT
Internal
Drain
External
Drain
Continuous Downward Slope
Internal
Drain
UNIT
UNIT
External
Drain
Internal
Drain
External
Drain
These are external traps also, although
unintentional. Lines must be rigid enough
not to bow over top of other objects.
INCORRECT
Do Not Externally
Trap the Unit
DPN001556
Rev. 0
• Do not reduce drain lines
• Do not expose drain line to freezing temperatures
• Drain line may contain boiling water. Use copper or other suitable material
• Drain line must comply with local building codes
Gravity Drain—Units Without Factory-Installed Condensate Pump
• 3/4" FPT drain connection is provided on units without optional factory-installed condensate
pump with infrared humidifier or no humidifier; 1-1/4" FPT connection is provided on units with
steam generating humidifier
• Pitch the drain line toward the drain a minimum of 1/8" (3mm) per 1 foot (305mm) of length
• Drain is trapped internally. Do not trap the drain external to equipment
• Drain line must be sized for 2 gpm (7.6 l/m) flow
NOTICE
Risk of improper piping connections. Can cause damage to the equipment and to the building.
The drain line has an internal trap and must not be trapped outside the unit or water may
back up into the drain pan and overflow the unit cabinet.
Figure 13 Gravity drain
Piping
Condensate Pump
• 1/2" copper sweat connection is provided on units with optional factory-installed condensate
pump
• Condensate pump is rated for approximately 6 GPM (22.7 l/min) at 30 ft (9m) total head
• 1/4" supply line; maximum water pressure is 145psi (1000kPa)
• Fill valve is sized for pressure range of 30 to 120psi (207-827kPa)
• Do not supply steam generating humidifier with softened water
• Do not use hot water source
• Water conductivity must be in the range of 330-670 micro-siemens
15Liebert® CRV
™
5.1.3Requirements of Systems Using Water or Glycol
These guidelines apply to the field leak checking and fluid requirements for field piping systems,
including Liebert chilled water, condenser (water or glycol) and drycooler circuits.
General Guidelines
• Equipment damage and personal injury can result from improper piping installation, leak checking, fluid chemistry and fluid maintenance.
• Follow local piping codes, safety codes.
• Qualified personnel must install and inspect system piping.
• Contact a local water consultant regarding water quality, corrosion protection and freeze protection requirements.
• Install manual shutoff valves at the supply and return line to each indoor unit and drycooler to
permit routine service and emergency isolation of the unit.
NOTICE
Risk of frozen fluids. Can cause equipment damage and building damage.
Freezing system fluids can rupture piping. Complete system drain-down cannot be ensured.
When the field piping or unit may be exposed to freezing temperatures, charge the system
with the proper percentage of glycol and water for the coldest design ambient.
Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system.
Piping
NOTICE
Risk of corrosion. Can cause equipment damage.
Read and follow individual unit installation instructions for precautions regarding fluid
system design, material selection and use of field-provided devices. Liebert systems contain
iron and copper alloys that require appropriate corrosion protection.
Contact a local water consultant regarding water quality, corrosion and freeze protection
requirements.
Water chemistry varies greatly by location, as do the required additives, called inhibitors,
that reduce the corrosive effect of the fluids on the piping systems and components. The
chemistry of the water used must be considered, because water from some sources may
contain corrosive elements that reduce the effectiveness of the inhibited formulation.
Sediment deposits prevent the formation of a protective oxide layer on the inside of the
coolant system components and piping. The water/coolant fluid must be treated and
circulating through the system continuously to prevent the build up of sediment deposits and
or growth of sulfate reducing bacteria.
Preferably, surface waters that are classified as soft and are low in chloride and sulfate ion
content should be employed. Proper inhibitor maintenance must be performed in order to
prevent corrosion of the system. Consult glycol manufacturer for testing and maintenance of
inhibitors.
Commercial ethylene glycol (Union Carbide Ucartherm, Dow Chemical Dowtherm SR-1 and
Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive to the common
metals of construction than water itself. It will, however, assume the corrosivity of the water
from which it is prepared and may become increasingly corrosive with use if not properly
inhibited.
Liebert® CRV
NOTICE
Risk of no-flow condition. Can cause equipment damage.
Do not leave the unit in a no-flow condition.
Idle fluid allows the collection of sediment that prevents the formation of a protective oxide
layer on the inside of tubes. Keep unit switched ON and system pump operating.
™
16
Piping
Leak Checking of Unit and Field Piping
Liebert unit fluid systems are factory-checked for leaks and may be shipped with a nitrogen holding
charge. Liebert unit fluid circuits should be checked for leaks at installation as described below.
NOTE
During leak checking of field-installed piping, Emerson recommends that the unit be isolated
using field-installed shutoff valves. When the Liebert units are included in a leak test, use of
fluid for pressure testing is recommended. When pressurized gas is used for leak testing the
Liebert unit, the maximum recommended pressure is 30 psig (2 bars) and tightness of the unit
should be verified by pressure decay over time, (<2 psig/hour [0.3 bars/hour]) or sensing a
tracer gas with suitable instrumentation. Dry seals in fluid valves and pumps may not hold a
high gas pressure.
17Liebert® CRV
™
6.0REFRIGERANT CONNECTIONS
!
!
WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and/or gases under high pressure.
Relieve pressure before working with piping.
WARNING
Risk of refrigerant system rupture or explosion from overpressurization. Can cause
equipment damage, injury and death.
A pressure relief valve is required for compliance with the EU Pressure Equipment
Directive and may be required for compliance with local codes. If a discharge pressure relief
device is not provided with the condenser unit, the system installer must install one in the
high side of the refrigerant circuit and rated for a maximum of:
• 675psig (46.5bar) for water/glycol-cooled units
• 700psig (48.3bar) for air-cooled units
A shutoff valve must not be installed between the compressor and the field-installed relief
valve.
One or more additional pressure relief valves are required downstream of any and all
field-installed isolation. Do not isolate any refrigerant circuits from overpressurization
protection.
Refrigerant Connections
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
The piping must not be open to the atmosphere for extended periods because the Liebert CRV
requires POE (polyol ester) oil. POE oil absorbs water at a much faster rate when exposed to
air than previously used oils. Because water is the enemy of a reliable refrigeration system,
extreme care must be used when opening systems during installation or service. If water is
absorbed into the POE oil, it will not be easily removed and will not be removed through the
normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also
have a property that makes them act as a solvent in a refrigeration system. Maintaining
system cleanliness is extremely important because the oil will tend to bring any foreign
matter back to the compressor.
The Liebert CRV can be connected to a condenser through either the top or bottom of the unit. The
unit is piped for connections at the top of the unit as shown in Figure 14, with provision for
connection through the bottom of the unit.
Connecting through the bottom of the unit requires cutting the liquid and suction lines as shown in
Figure 15. Cutting these lines disconnects the top connections from the rest of the refrigeration system.
Air-cooled units are shipped with a holding charge of nitrogen.
Liebert® CRV
™
18
6.1Piping Guidelines—Air-Cooled Units
If using bottom
connections, cut
the pipes just
below the black
pipe clamps
• Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant
piping is in place, ready for connection to the unit and condenser
• Use copper piping with high temperature brazed joints
• Isolate piping from building using vibration-isolating supports
• Refer to Tables 7 through 10 for piping sizes
• Refer to condenser installation manual for charging information
• Install traps on hot gas (discharge) lines at the base of vertical risers and every 15 feet (4.6m) of
vertical rise.
• See Table 6 for the allowable elevation difference between the condenser and the Liebert CRV.
• Consult factory if piping run exceeds 300 feet (91m) equivalent length
• Keep piping clean and dry, especially on units with R-410A refrigerant
• Avoid piping runs through noise-sensitive areas
• Do not run piping directly in front of airstream of any air conditioner
• Refrigerant oil – do not mix oil types
Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
6.2Refrigerant Piping—Air-Cooled Models
Figure 14 Top refrigerant piping connections
Refrigerant Connections
Figure 15 Bottom refrigerant piping connections
19Liebert® CRV
™
6.2.1General Layout
15 ft. (4.6m)
(See *)
Gas
Liquid
* Oil traps every 15 ft. (4.6m)
of vertical piping
Room Unit
(See **)
Liquid
Room Unit
(See**)
1. Piping must be Type ACR copper tubing and sized per Tables 7, 8, 9 and 10.
NOTE
All field-installed piping must comply with applicable national, state and local codes.
Use the shortest possible refrigeration pipelines to minimize the total charge of refrigerant and
the number of pressure drops.
2. Minimize the number of bends and make the bends the largest radius practical to prevent
constricting refrigerant flow.
3. Insulate the piping as specified in Table 5. If the pipes are installed next to electrical cables, they
must be isolated from the building using vibration-isolating supports to avoid damage to cable
insulation.
4. There must be at least one inch (25mm) separation between the gas and liquid pipelines. If this is
not possible, insulate both lines.
5. Support both horizontal and vertical pipes with vibration-damping clamps, which include rubber
gaskets. Place these clamps every 5 to 7 ft. (1.5 to 2m).
Table 5Condenser positioning
Insulation
Condenser
Position
Discharge
Line
Liquid
Line
Indoornecessarynecessarynecessary
Outdoor only for aesthetic reasonsonly for aesthetic reasonsonly for aesthetic reasons
Indoor only for aesthetic reasonsonly for aesthetic reasons no (expose to cold under-floor air)
Outdoor only for aesthetic reasonsonly if exposed to sunonly if exposed to sun
Condenser Above
Liebert CRV
Condenser and
Liebert CRV
at Same Level
Refrigerant Connections
Condenser Below
Liebert CRV
(Not Recommended)
Layout
** See Table 6
Table 6Liebert CRV position relative to the remote condenser
ParameterMaximum Distances, ft. (m)
From Liebert CRV to condenser300 (91.4) equivalent length
From Liebert CRV to VFD condenserAbove: 60 (18.3)Below: 15 (4.5)
™
From Liebert CRV to Liebert Lee-Temp
Requirements
Oil traps on vertical line of gas refrigerantEvery 15 (4.6)
condenserAbove: 60 (18.3)Below: 0 (0)
Room Unit
Gas
Liquid
Liebert® CRV
™
20
Figure 16 Pipeline air conditioner - condenser
!
B
C
CDT
COND
A
(Distance) D = A + B + C
CDT = Conditioner
COND = Condenser
6.2.2Pipe Diameter and Thickness
WARNING
Risk of explosive discharge. Can cause equipment damage, injury or death.
Use only Type ACR copper tubing sized per Tables 7, 8, 9 and 10 for pipes connecting the
Liebert CRV and the condensing unit.
Table 7Piping and refrigerant sizes for Liebert Lee-Temp
Condenser Piping Connection Sizes
Condenser Connections, O.D., in.
Refrigerant Connections
™
condensers with R-410A
Liebert Lee-Temp Connections, I.D., in.
Liebert Lee-Temp
Condenser Model #Hot GasLiquid
DCSL28K1-1/87/89 x 36 (229 x 914)1-1/85/87/8
DCSL60K1-1/87/811 x 36 (279 x 914)1-1/85/87/8
DCSL90K1-1/87/811 x 48 (279 x 1219)1-1/85/87/8
Source: DPN001623, Rev. 6, Page 3
Size, in. (mm)
Hot Gas
Tee
Liquid To
L-T Valve
Receiver
Out
Table 8Recommended refrigerant line sizes for Liebert Lee-Temp condensers with R-410A Cu, OD
Liebert CRV Model #
CR020RA
CR035RA
Consult factory for proper line sizing for runs longer than 300 ft. (91.4m) equivalent length.
* Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4”).
Source: DPN001623, Rev. 6, Page 3
Total Equivalent
Length, ft. (m)
50 (15.2)3/4 (19.1)5/8 (15.9)
100 (30.5)3/4 (19.1)5/8 (15.9)
150 (45.7)3/4 (19.1)5/8 (15.9)
300 (91.4)7/8 (22.2)*3/4 (19.1)
50 (15.2)7/8 (22.2)3/4 (19.1)
100 (30.5)7/8 (22.2)3/4 (19.1)
150 (45.7)7/8 (22.2)3/4 (19.1)
300 (91.4)1-1/8 (28.6)*7/8 (22.2)
Hot Gas Line,
in. (mm)
Liquid Line,
in. (mm)
21Liebert® CRV
™
Refrigerant Connections
Table 9Piping and refrigerant sizes for Liebert air-cooled, VFD control condensers with R-410A
Condenser Piping Connection Sizes, Cu, O.D.
Condenser Model #
Entering Hot Gas
Line, in. (mm)
Returning Liquid
Line, in. (mm)
TCSV28K1-1/8 (28.6)7/8 (22.2)
TCSV60K1-1/8 (28.6)7/8 (22.2)
TCSV90K1-1/8 (28.6)7/8 (22.2)
Source: DPN001624, Rev. 5, Page 3
Table 10Recommended refrigerant line sizes for Liebert air-cooled, VFD control condensers
with R-410A, Cu, OD
Liebert CRV Model #
Total Equivalent
Length, ft. (m)
Hot Gas Line,
in. (m)
Liquid Line,
in. (m)
50 (15.2)3/4 (19.1)5/8 (15.9)
CR020RA
100 (30.5)3/4 (19.1)5/8 (15.9)
150 (45.7)3/4 (19.1)5/8 (15.9)
300 (91.4)7/8 (22.2)
2
3/4 (19.1)
50 (15.2)7/8 (22.2)3/4 (19.1)
CR035RA
1. Consult factory for proper line sizing for runs longer than 300 ft. (91.4m) equivalent length.
2. Must downsize vertical riser one trade size (1-1/8" to 7/8" or 7/8" to 3/4" ).
Source: DPN001624, Rev. 5, Page 3
100 (30.5)7/8 (22.2)3/4 (19.1)
150 (45.7)7/8 (22.2)3/4 (19.1)
300 (91.4)1-1/8 (28.6)
2
7/8 (22.2)
Liebert® CRV
™
22
6.2.3Installing Piping
The following operations must be carried out by an experienced refrigeration technician.
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
The piping must not be open to the atmosphere for extended periods because the Liebert CRV
requires POE (polyol ester) oil. POE oil absorbs water at a much faster rate when exposed to
air than previously used oils. Because water is the enemy of a reliable refrigeration system,
extreme care must be used when opening systems during installation or service. If water is
absorbed into the POE oil, it will not be easily removed and will not be removed through the
normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also
have a property that makes them act as a solvent in a refrigeration system. Maintaining
system cleanliness is extremely important because the oil will tend to bring any foreign
matter back to the compressor.
1. When installing the refrigerant piping, note the following:
•Brazing:
• All joints must be brazed.
• Avoid butt brazes by using couplings or swaging one of the pipes with a swaging tool.
• Ensure that all brazed joints are leak-free.
• Flow dry nitrogen through the pipes during brazing.
• Always use large-radius curves (bending radius at least equal to pipe diameter). Bend the pipes
as follows:
• soft copper: bend by hand or use bending device;
• hard copper: use preformed curves.
• To minimize oxidation, avoid overheating the pipes when brazing.
2. Connect the pipes to the condenser:
• Condensers with butt-brazed pipe connections: Cut the pipe, enlarge it and braze it to the pipeline.
Respect the direction of refrigerant flow. (See labels on refrigerant.)
3. Wash out the pipelines as follows:
a. Plug up the free ends of the pipes.
b. Connect a helium or nitrogen cylinder, fitted with a reducer (max. pressure 10 bar), to the
1/4" SAE Schrader valve of the condenser.
c.Pressurize the pipes with helium or nitrogen.
d. Unplug the pipes instantaneously.
e.Repeat Steps a through d several times.
This operation is especially important when hard copper piping is used.
4. Open all the shutoff valves on the room unit.
5. Discharge the room unit pressurized with helium (at 1 bar) by opening the charge valves so that
all the branches of the circuit are discharged (e.g., on the receiver, on the low pressure side and on
the compressor delivery).
6. Debraze the bottoms from the connections of the room unit.
7. Fix (braze) the pipes to the connections on the air conditioner.
8. Connect the refrigerant safety pressure relief valve to the outdoors with a 16 mm (5/8") copper
pipe. Only water/glycol units have a indoor relief valve. Air cooled units do not have an indoor
pressure relief valve.
Refrigerant Connections
23Liebert® CRV
™
Figure 17 Connections—air-cooled models
LVT
LVT
RG
RL
RL
GD or CP
RG
Piping and electrical connections available at the top and bottom of unit.
Air-cooled systems may require oil to be added in the field to allow
sufficient compressor lubrication.
Top Connections
Unsolder when
connecting
through bottom
Bottom Connections
(possible with raised floor)
Rear
DPN001792
Rev. 2
HS
CP
CR
GDH
or HS
4-13/16"
(122.2mm)
23-5/8"
(600mm)
2-1/8" (54mm)
LVB
LVB 2
HVT
HVB
8-7/8"
(226mm)
1-1/8" (28mm)
7-13/16"
(199mm)
3-1/16"
(77mm)
5"
(127mm)
1-3/4"
(44mm)
5-1/8"
(130mm)
9-3/4"
(248mm)
12-3/4"
(325mm)
2-15/16"
(74mm)
2-3/16" (56mm)
2-11/16"
(69mm)
9-5/16"
(237mm)
3-1/16"
(77mm)
2-11/16"
(69mm)
2-11/16"
(69mm)
2-15/16"
(74mm)
3-1/4"
(83mm)
3-13/16"
(97mm)
5-3/8"
(136mm)
1-3/8"
(35mm)
2-1/8" (54.7mm)
1-3/4"
(45mm)
1-3/4"
(45mm)
1-1/2"
(38mm)
46-1/4"
(1175mm)
3-1/4" (83mm)
17-5/16"
(440mm)
9-1/2"
(242mm)
Refrigerant Connections
Liebert® CRV
™
24
Refrigerant Connections
Table 11Unit connections, air-cooled models
Unit ConnectionsCR20A (50Hz)CR35A (50Hz)CR20A (60Hz)CR35A (60Hz)
RL
RG
GDGravity Coil Pan Drain20mm I.D.1" MPT
GDH Gravity Humidifier Drain22mm I.D.N/A
CPCondensate Pump1/2" GAS F1/2" FPT
HSHumidifier Supply
HVT
HVB
LVT
LVB
LVB
2
Source: DPN001792, Rev.2
Refrigerant Liquid
Line Inlet
Refrigerant Gas
Line Outlet
High Voltage
Top Connection
High Voltage Bottom
Entrance (feed through
the base of the unit)
Low Voltage
Top Connection
Low Voltage Bottom
Entrance (feed through
the base of the unit)
Low Voltage Bottom
Entrance (feed through
the base of the unit)
12mm O.D. Cu Sweat 16mm O.D. Cu Sweat1/2" O.D. Cu Sweat5/8" O.D. Cu Sweat
16mm O.D. Cu Sweat 22mm O.D. Cu Sweat5/8" O.D. Cu Sweat7/8" O.D. Cu Sweat
Risk of improper refrigerant charge. Can cause equipment damage and reduced efficiency.
Check the refrigerant type to be used on the data plate of the air conditioner and on the
refrigerating compressor.
Table 12R-410A refrigerant and oil charge for air-cooled models
1/2" x 0.049 (12 x 1)-0.05 (0.08)0.05 (0.07)0.04 (0.07)
9/16" x 0.049 (14 x 1)0.0084 (0.0124)0.07 (0.11)0.07 (0.11)0.06 (0.10)
5/8" x 0.049 (16 x 1)0.0114 (0.0169)0.10 (0.16)0.10 (0.14)0.09 (0.13)
3/4" x 0.049 (18 x 1)0.0149 (0.0221)0.14 (0.20)0.13 (0.19)0.11 (0.17)
7/8" x 0.065 (22 x 1.25)0.0232 (0.0346)———
1-1/8" x 0.065 (28 x 1.5)0.0392 (0.0584)———
(+) Liquid pressure and density varies according to condensing temperature (see refrigerant tables).
1. For distance D see Figure 16 Pipeline air conditioner - condenser
1
Gas R-410A,
lb/feet (kg/m)
Liquid (+), at Different Condensing
Temperatures - R-410A, lb/ft (kg/m)
95°F (35°C)115°F (46°C)135°F (57°C)
Table 14Air-cooled condenser refrigerant charge
Liebert Lee-Temp
VFD
Model
28 K7 (3.2)41 (18.6)
60 K16 (7.3)75 (34.0)
90 K25 (11.3)109 (49.4)
Topping up is requested for short pipeline, too, due to the extra-charge of refrigerant.
The air conditioner is supplied pressurized with helium at 1 bar.
lb (kg)lb (kg)
(inc. receiver)
™
Table 15Refrigerant and oil charge for water-cooled models
R-410A
Refrigerant Charge
Model
CR020RW 13.0 (5.9) 60 (1.68)
CR035RW 17.0 (7.7)110 (3.08)
The air conditioner is supplied complete with refrigerant and oil.
1. The recommended oil is EMKARATE RL 32-3MA.
Liebert® CRV
™
lb (kg)oz (kg)
Initial Oil
Charge
1
26
Figure 18 Connections for vacuum creation and refrigerant charge
Suction and Supply Line Connections
Liquid Line Connection
Thermostatic Valve Connection
6.3.1Evacuation Air-Cooled Models
Variable Fan Speed Control Leak Check and Evacuation Procedure
Refrigerant Connections
Proper leak check and evacuation can be accomplished only with all system solenoid valves open and
check valves accounted for.
NOTE
The system include a factory-installed check valve and an additional downstream Schrader
valve with core in the compressor discharge line. Proper evacuation of the condenser side of the
compressor can be accomplished only using the downstream Schrader valve. See piping
schematic.
1. If unit power is available, open the unit liquid line solenoid valves using the evacuation function
for System #1 in the diagnostic section of the Liebert iCOM
power is not available, a field-supplied 24VAC / 75VA power source must be directly connected to
the unit solenoid valve.
2. Connect refrigerant gauges to the suction rotalock valves and discharge line Schrader valves.
3. Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of
refrigerant. Check system for leaks with a suitable leak detector.
4. After completion of leak testing, release the test pressure (per local code) and pull an initial deep
vacuum on the system with a suitable pump.
5. After four hours, check the pressure readings and, if they have not changed, break vacuum with
dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after
two hours. After completing this step, proceed to Variable Fan Speed Charging on page 28.
®
control (see Figure 68). If unit
27Liebert® CRV
™
Refrigerant Connections
Variable Fan Speed Charging
1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending
on refrigerant type.
2. Charging the system with refrigerant requires the unit to be in an operational state..
3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line
charge data in Tables 12, 13 and 14.
4. Weigh in as much of the system charge as possible before starting the unit.
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant R-410A is a blend of two components and must be introduced and charged from
the cylinder only as a liquid.
When adding liquid refrigerant to an operating system, it may be necessary to add the
refrigerant through the compressor suction service valve. Care must be exercised to avoid
damage to the compressor. Emerson recommends connecting a sight glass between the
charging hose and the compressor suction service valve. This will permit adjustment of the
cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the
compressor.
5. Turn on unit disconnect switch. Operate the unit for 30 minutes using the charging function in
the diagnostic section of the Liebert iCOM
operates the compressor at full capacity and energizes the blower motor and the liquid line
solenoid valve. The reheat and humidifier are disabled. A minimum 20psig (138kPa) must be
established and maintained for the compressor to operate. The charging function can be reset as
many times as required to complete unit charging.
6. Charge the unit until the liquid line sight glass becomes clear, then add one additional pound
(2.2kg) of refrigerant.
®
control (see Figure 68). The charging function
NOTE
A digital scroll compressor will have a clear sight glass only when operating at 100% capacity.
When operating below 100%, the sight glass may show bubbles with each 15-second unloading
cycle.
7. As head pressure builds, the variable fan speed controlled condenser fan begins rotating. The fan
will run at full speed when sufficient head pressure is developed—fan starts to rotate at 310psig
(2137kPa) and is full speed at 400psig (2758kPa).
7.1Water Connections—Supply Humidifier and Drain Water, All Models
Units with a condensate pump and humidifier are preset to be connected from the top. If floor
connections are used, the water lines can be intercepted at the following points:
AvailableAvailable
AvailableAvailable
Not AvailableAvailable
Water Connections
Figure 19 Water connection points, bottom entry
• Condensate drain without pump:
• Use tubing rated to carry water up to 212°F (100°C) copper, PVC or flexible polythene tubing.
• Allow a 2% gradient toward the drain.
• Drain is trapped internally. Do not trap the drain external to the equipment.
• Fill the drain trap with water.
• Humidifier (optional): See Appendix A - Humidifier.
29Liebert® CRV
™
7.2Glycol Mixture
Add ethylene glycol or propylene glycol to the circuit in the percentages shown in Table 18.
Table 18Glycol mixtures
Water Connections
Glycol Percentage *
by Volume
0%32 (0)32 (0)
10%25.3 (-3.7)28.9 (-1.7)
20%16 (-8.9)18.7 (-7.4)
30%3.7 (-15.7)8.4 (-13.1)
40%-12.6 (-24.8)-6.7 (-21.5)
* Freezing temperatures may vary slightly among commercially available glycol products; refer to manufacturer’s specifications.
Ethylene Glycol -
Freezing Temperature, °F (°C)
Freezing Temperature, °F (°C)
7.3Water Connections: Water/Glycol-Cooled Models
The unit must receive cooling water as follows:
• From an external cooling water source, in open circuit.
• Using a drycooler, in closed circuit.
1. Connect the piping as shown in Appendix D - Refrigeration and Hydraulic Circuits.
2. Use hoses connected with three-piece joints to the condenser water inlet and outlet couplings.
3. Install a 16-20 mesh strainer on the water/glycol supply to the Liebert CRV. The strainer is
needed to prevent particles in the water from entering the unit’s heat exchanger.
4. Place shutoff ball valves at the conditioner inlet and outlet to allow easy maintenance.
5. Install a water drain system at the lowest point in the circuit.
6. Fully drain the piping before connecting it to the air conditioner.
Propylene Glycol -
7.3.1Notes for Open-Circuit Applications
• Use the unit with mains or well water. Do not use water from an evaporative cooling tower unless
the water hardness is controlled.
• The water pressure must be 29-145psi (2-10 bar). If water pressure is outside this range, contact
Emerson for technical support.
• The required water flow at different temperatures is available from Emerson.
• If water temperature is very low, insulate both pipes.
7.3.2Notes for Closed-Circuit Applications
The installation in Figure 3 is illustrative only; for individual installations follow the project diagram.
• Install a pump system calculated on the basis of the flow and total head of the system (see site
plan data) and controlled by the compressor running (see label on the Liebert CRV).
• Insulate both pipes.
• Very important: Add water and ethylene glycol to the circuit when the ambient temperature is
below 32°F (0°C); refer to the Liebert CRV technical data manual, SL-11978). Do not exceed the
nominal operating pressure of the circuit components.
• Bleed air out of the circuit.
Liebert® CRV
™
30
7.4Chilled Water Connections: Chilled Water Units
Top Connections
Bottom Rear Connections
Tubing Support
Water Drain Tap
Ball
Valves
Thermostat
Pressure
Gauge
Insulation
Liebert CRV
Figure 20 Chilled water connections
Refer to Figure 21 when performing these installation steps:
• Use copper tubing or steel pipe.
• Place the tubing on supporting saddles.
• Insulate both tubes
• Install shutoff ball valves on the inlet and outlet pipes to ease maintenance.
• Install optional thermostats and pressure gauges on the inlet and outlet pipes.
• Install a water drain tap at the lowest point in the circuit.
• Fill the circuit with water or glycol.
Figure 21 Chilled water circuit
Water Connections
31Liebert® CRV
™
Figure 22 Air bleeding valve position CW
REAR VIEW
Water Connections
Liebert® CRV
™
32
Figure 23 Connections—water/glycol models
HVT
LVT
LVT
HS
CP
CR
CS
GDH
or HS
CR
Piping and electrical
connections available at
the top and bottom of unit.
* Install a 35 mesh strainer, in an easily accessible location, on the Water/Glycol Supply
to prevent particles from entering the heat exchanger. Strainer bypass valves are
recommended to allow the strainer to be cleaned while maintaining flow to the cooling unit.
Piping and electrical
connections available
at the top and bottom
of the unit.
TOP CONNECTIONS
BOTTOM CONNECTIONS
(possible with raised floor)
REAR
LVT
LVT
HVT
LVB
LVB2
GDH or HS
CWR
CWR
CWS
CWS
HS
CP
GD or CP
46-1/4"
(1175)
5"
(127)
3-1/4" (83)
17-5/16"
(440)
3-1/16" (77)
9-5/16
"
(237)
1-3/4"
(45)
9-1/2"
(242)
2-11/16"
(69)
1-1/8"
(28)
2-3/16" (56)
3-13/16"
(97)
3-1/16")
(77)
3-7/8"
(98)
HVB
9-3/4"
(248)
8-7/8"
(226)
(325)
12-3/4"
2-11/16"
(69)
2-11/16"
(69)
2-3/16"(56)
4-1/8"
(105)
6-1/8"
(155)
2-1/8" (54.71)
2-1/8" (54)
5-3/8" (136.01)
23-5/8" (600)
3-1/4" (83)
1-3/4" (45.2)
1-1/2"
(38.1)
4-13/16"
(122.16)
7-13/16"
(199)
1-3/8"
(35)
1-3/4"
(44)
5-1/8"
(130)
2-15/16"
(74)
DPN001794
Rev. 2
Water Connections
35Liebert® CRV
™
Water Connections
APPLIANCE
TSHTC
Filling
Water
(optional)
HTC
TS
Shutoff Valve
Pump
Check Valve
Gauge
Thermostat
Variex (50Hz Opt.)
Safety Valve
Expansion Tank
Air Separator
Charge Group (Filter,
Reducer, Check Valve)
Filling Meter
Drain (at Lowest Point)
(*)
Standby Pump
Standby Pump
Pressure-Operated Bypass
See hydraulic drawings in the Appendix D
Disconnect
After Charge
Table 20Unit connections, chilled water models
Unit ConnectionsCR040C (50 Hz)CR040C (60 Hz)
CWSChilled Water Supply32mm GAS F 1-1/4" FPT
CWRChilled Water Return32mm GAS F 1-1/4" FPT
GDGravity Coil Pan Drain20mm I.D.1" MPT
GDHGravity Humidifier Drain22mm I.D.N/A
HSHumidifier Supply
1/2" GAS F (top connection)
3/4" GAS F (bottom connection)
CPCondensate Pump1/2" GAS F1/2" FPT
Combination Knockout Hole
HVTHigh Voltage Top Connection
Diameter 1-3/8" (35mm)
1-3/4" (44.5mm) and 2-1/2" (63.5mm)
HVB
High Voltage Bottom Entrance
(feed through the base of the unit)
LVTLow Voltage Top Connection
LVB
LVB2
Source: DPN001794, Rev. 2
Low Voltage Bottom Entrance
(feed through the base of the unit)
Low Voltage Bottom Entrance
(feed through the base of the unit)
Hole Diameter
2-1/2" (63.5mm)
Hole Diameter
7/8" (22mm) 2 places
Hole Diameter
1-7/64" (28mm) 2 places
—
1/2" FPT (top connection)
1/4" Compression Fitting
(bottom connection)
Combination Knockout Hole
Diameter 1-3/8" (35mm)
1-3/4" (44.5mm) and 2-1/2" (63.5mm)
Knockout Hole Diameter
2-1/2" (63.5mm)
Knockout Hole Diameter
7/8" (22mm) 4 Places
Knockout Hole Diameter
1-3/32" (27.8mm) 2 Places
Combination Knockout Hole
Diameter 1-3/4" (44.5mm) 1 Place
Figure 25 Recommended drycooler Installation
Liebert® CRV
™
36
8.0ELECTRICAL CONNECTIONS
!
!
Remove these bolts
to access low voltage
electrical panel
Remove these bolts
to access high voltage
electrical panel
Remove these bolts to open
lower front baffle panel
8.1Electrical connections
WARNING
Arc flash and electric shock hazard. Can cause injury and death.
Disconnect local and remote power supplies and wear appropriate personal protective
equipment per NFPA 70E before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM
mode.
Some internal components require and receive power even during the Unit Off mode of the
Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch
contains live hazardous voltage potential.
Install and open a remote disconnect switch and verify with a voltmeter that live hazardous
voltage potential is not present inside the unit cabinet before working within. Refer to the
unit electrical schematic.
Follow all national and local codes.
®
microprocessor does not isolate power from the unit, even in the Unit Off
Electrical Connections
WARNING
Risk of electric shock. Can cause injury or death.
This unit has a high leakage current potential. Proper earth ground connection per national
and local codes is required before connection to the electric power supply.
Figure 26 Remove electrical panel and lower front panel
37Liebert® CRV
™
Figure 27 Power and control cable entry points and routing
High Voltage
Top Entry Port
Low Voltage Channel
opening provides access
to the Liebert IntelliSlot
®
card housing
Low voltage cables are
routed through a channel
in the side panel to
connect the bottom of the
unit to the electrical panel
High voltage
bottom entry port
Low voltage bottom
entry port
High Voltage Top
Entry Port
Low Voltage Top
Entry Port
Electrical Connections
8.1.1Power Supply Cable Connections
Before proceeding with the electrical connections, ensure that:
• all electrical components are undamaged
• all terminal screws are tight
• the supply voltage and frequency are as indicated on the unit
• Connect the cable to the line inlet terminal board.
• Use the appropriate cable size for the current draw, supply voltage and installation type.
• Protect the supply using a backup fuse or circuit breaker.
• Do not fit the supply cable in the raceways inside the machine electric board.
• Use only multipolar cables with sheath (CEI20-22).
Wiring Connections
• Remote On/Off connections must be provided by the installer.
• The General Alarm terminals allow remote alarm signalling.
In case of short circuit, check the affected switch for sticking and replace it if necessary.
See electrical data in Appendix B - Electrical Data.
Liebert® CRV
™
38
8.2Protective Features of the Electrically Commutated Fans
Temperature
sensor
protection
The EC fans are protected against:
• Overtemperature of electronics
• Overtemperature of motor
• Locked rotor protection
• Short circuit at the motor output
When any of these failures occurs, the motor stops, electronically, with no potential for separation,
and the status relay is released.
The unit does not restart automatic automatically. To reset the alarm, the power supply must be
switched Off for 20 minutes once motor is at standstill.
• Input power undervoltage detection:
If the utility power falls below 3ph/290VAC (typical value) for 5 seconds or longer, the motor is
switched Off, electronically, with no potential for separation, and the status relay is released.
When the utility voltage returns to a correct value, the motor restarts automatically.
• Phase failure recognition:
If one phase fails for 5 seconds or longer, the motor is switched Off, electronically, with no poten-
tial for separation, and the status relay is released.
When all three phases return to correct values, the motor restarts automatically in 10 to 40 sec-
onds.
Electrical Connections
The power supply for an external speed-setting potentiometer is protected against short-circuiting.
The motor is overload-protected via motor current limitation.
8.3Protective Features of Electrical Heaters
Figure 28 Electrical heating with temperature sensor protection
When the temperature sensor detects overtemperature of electrical heating, the thermal protection
turns Off the current. To reset the thermal protection, push the button on the front of the unit (see
Figure 28).
39Liebert® CRV
™
9.0STARTUP
!
!
9.1Initial Startup
WARNING
Risk of hair, clothing and jewelry entanglement with high speed rotating fan blades. Can
cause equipment damage, serious injury or death.
Keep hair, jewelry and loose clothing secured and away from rotating fan blades during unit
operation.
WARNING
Risk of contact with rotating fan blades. Can cause injury or death.
The Liebert CRV’s fan blades will continue spinning after the unit is shut Off. Wait until the
fan blades have stopped before working on the unit.
To start the Liebert CRV:
1. Open all valves in the refrigeration circuit according to the instruction label attached to the valve.
2. W Models Only: Open all valves in the water circuit according to the instruction label attached
to the valve.
3. Ensure that the refrigerant charge is correct (see 6.0 Refrigerant Connections).
4. Using a leak detector, verify that there are no refrigerant leaks. If any leaks are detected, repair
them and recharge as described in 6.0 Refrigerant Connections.
5. At least 4 hours before startup, close the main switch and the compressor switch on the electrical
panel.
Startup
NOTE
The default setting for the Liebert iCOM
mode allows users to turn on the unit simply by rotating the main switch on the electrical
panel. The yellow LED on the Liebert iCOM will light after the unit is turned on because
electrical power is present.
If the LED does not light:
• check the electrical panel power supply
• check the protection devices (e.g., thermal switches)
• check the fuses.
6. Verify that the crankcase heater is working.
7. Check to ensure that there are no water leaks.
8. If an external condenser or drycooler is installed, start it by supplying power to it.
9. Close all MCBs on the electrical panel.
10. Check the supply voltage on all phases.
11. Check the supply voltage on all phases for the external condenser or drycooler, if fitted.
12. Start the unit by pressing the On/Off switch.
13. Check the amp draw of all components (see 8.0 Electrical Connections).
14. Check the amp draw of the external condenser/drycooler, if fitted.
15. If the compressor makes a loud, unusual noise, invert the electrical connections of the phases
supplying the corresponding digital scroll compressor, which accepts only one direction of
rotation.
16. Ensure that the fans rotate in the correct direction (see arrow on fan).
17. Ensure that all control system settings are correct and that there are no alarms (see Figure 48).
18. W Models Only: Verify the water flow is adequate.
19. W Models Only: For closed circuit units, ensure that the water pump starts when the
compressor starts.
®
control is for stand-alone operation. The stand-alone
Liebert® CRV
™
40
Checks to Perform after Startup
Liquid Receiver Valve
Filter
Dryer
Inlet
Schrader
Val ve
Filter
Dryer
Sight Glass
Solenoid Valve
Thermostatic
expansion
valve
Once the system is operating under load, check the various components, as follows:
1. Verify that the fans are operating properly.
2. Ensure that the temperature and relative humidity are being controlled, and that the humidifier
(optional) and heating steps (optional) operate when required.
3. Ensure that the compressor operates when required.
4. Ensure that the fan operation controller on the external condenser/drycooler (if fitted) is
calibrated correctly, and that it controls the fan operation.
5. Record all of the following on the warranty inspection form:
a. All component voltages and current draws
b. All air / water temperatures indoor and outdoor
c.All refrigerant and water / glycol pressures,
d. All levels of refrigerant and oil in sight glasses
e.Record refrigerant pressure switch settings and operating pressures
f.Record superheat and sub-cooling.
9.2Automatic Restart
If desired, the unit will automatically restart on the return of power after a supply interruption (see
Figure 90).
Startup
To avoid an automatic cold restart of the compressor if a power interruption of several hours is
expected, stop the unit before the blackout. After power returns, allow the compressor to preheat
before restarting the unit.
Figure 29 Refrigerant line components
41Liebert® CRV
™
9.3Chilled Water Valve: Chilled Water Models
!
0
1
0
1
Position indicator on
0 = CLOSED valve
(3-way valve: bypass open)
Position indicator on
1 = OPEN valve
(3-way valve: by-pass closed)
The 3-way valve controls the chilled water flow and operates as follows (refer to Figure 4):
• When the valve is fully open (i.e., maximum chilled water flow), the actuator slot is set to “1.”
• When the valve is closed (i.e., no chilled water flow), the actuator slot is set to “0.”
The valve running time is set to the value specified in the control manual.
For more details, see the technical bulletin for chilled water valves and related actuators. Technical
bulletins are enclosed with documentation onboard the unit.
NOTE
1. In the unlikely event of control system failure, the valve can be manually controlled with
the rotary knob. It can be used to drive the actuator into any position between 0 and 1.
2. When the actuator stem is completely down, the valve is open and chilled water coil is
supplied.
Figure 30 Position of the chilled water valve actuator (for 2- or 3-way valve)
Startup
9.4Adjust Baffles to Direct Air Properly
WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
Ensure that the Liebert CRV is shut down and power has been disconnected before beginning
any work on the unit.
The Liebert CRV has been equipped with an adjustable, modular supply air baffle system. The baffles
should be adjusted prior to start-up to direct air towards the racks the cooling unit is intended to
condition. Ideally, these should be the same racks the cooling unit is pulling hot air from. The baffles
can be readjusted at any time as cooling needs change.
The Liebert CRV is shipped with the baffles in an alternating pattern to direct cold air left and right.
This configuration should be used when the cooling unit is located between racks. If a Liebert CRV is
installed at the end of a row, all the baffles should be adjusted to blow air down the cold-aisle, toward
the racks. The baffle segments at the top of the panel will direct more air than the segments at the
Liebert® CRV
bottom. The supply air will travel the furthest when all baffle segments are pointed in the same
direction, left or right.
™
42
To adjust the baffles:
1. Open Liebert
CRV Display Door
Inside view, showing
baffle removal for changing
airflow direction
2. Remove two bolts
3. Tilt and lift
baffle panel
For proper operation, the baffles
must be installed so the discharge
air points upward
DPN001863
Pg. 1, Rev. 2
1. Open the door containing the Liebert iCOM
®
display.
2. Remove the two screws holding a baffle panel segment in place.
3. Slide out the baffle segment.
4. There is one screw on each side of the baffle, as shown in Figure 31. Remove the screws and
rotate the baffle segment around its horizontal axis to change the airflow direction.
5. Reinsert the baffle segment and reinstall the screws.
Figure 31 Adjust the baffles to ensure correct airflow direction
Startup
A blocker plate inside the display door should also be adjusted to direct air towards the racks the
Liebert CRV is intended to condition. The blocker plate can be installed on the left or right side of the
display door, or it can be removed to discharge air left and right.
43Liebert® CRV
™
Figure 32 Adjust air-blocking plate
Perforated Supply
Air Opening
Air Blocker Installed
Over Perforation
Attachment
Screws
FRONT VIEW
DPN001863
Pg. 2, Rev. 2
INSIDE DISPLAY DOOR
Startup
9.5Remote Rack Sensor Wiring
Instructions to adjust the air blocker:
1. Remove the three screws that attach the blocker plate to the display door.
2. Reattach the blocker plate to the other side of the display door or remove entirely.
The Liebert CRV is capable of supporting up to ten (10) 2T remote rack temperature sensor housings.
It is recommended that one (1) 2T housing be attached to each rack the Liebert CRV is intended to
cool. The sensors provide feedback directly to the cooling unit to improve efficiency and performance.
Rack sensors help combat cooling problems related to recirculation air, uneven rack loading and air
distribution. The 2T rack sensors are intended for cold aisle use only.
While installing the rack sensors is optional, Emerson recommends that they be installed.
Installations with multiple Liebert CRV cooling units should be connected in a Unit-to-Unit (U2U)
Ethernet network to leverage all of the Liebert iCOM
®
iCOM
U2U Network.
®
control benefits, see 11.3 Wiring a Liebert
A sensor network can be extended at any time by connecting additional 2T sensors to the last 2T
sensor on the network. Sensors connect in a daisy chain fashion back to the cooling unit; individual
wires
from each sensor to the cooling unit are avoided.
There are two steps to setting up a remote rack sensor:
• The DIP switches of the remote rack sensor must be configured to have a unique ID
• The Liebert iCOM control must be set to use the remote rack sensor as either a controlling sensor
or as a reference sensor.
Liebert® CRV
™
44
Figure 33 Figure 2T rack sensor
Each temperature
probe wire is 1830mm
(6 feet) long
Temperature sensing probe
2T Sensor
Back
Front View
86
(3-3/8")
41
(1-5/8")
4.5
(3/16")
67 (2-5/8")
Max. depth
41 (1-5/8")
1
1
2
(
4
-
7
/
1
6
"
)
Switch Up = ON
Switch Down = OFF
9.5.1DIP Switch Settings
Three 2T sensor housings are included with each Liebert CRV. The DIP switches in these sensors
have been preset at the factory. It is recommended that you confirm that the DIP switches have been
set correctly using the below table. Any additional 2T sensor housings will need their dip switches set
per the below table. If the dip switches are not set correctly, the control will not operate properly.
1. Confirm the DIP switches are set correctly for 2T sensors numbered 1, 2 and 3.
2. If additional sensors are to be connected to a cooling unit:
a. Apply numbered stickers to the sensor housings, corresponding to sensor chain position.
b. Based on the sensor number, use the included DIP switch tool to set the DIP switches
according to the table above. If you are having difficulty setting switches through the opening
in the housing or if the hole is not present, you may open the case by removing the three
Phillips-head screws. Reassemble housing once complete.
Figure 35 Setting 2T Sensor DIP Switches
Startup
Note: Use included DIP switch tool (or similar tool). DO NOT insert any metal object into the sensor
case.
9.5.3Terminating the Last 2T Sensor on a Network
The last 2T sensor on the network, which can be identified by only having one CAN cable plugged into
it, needs to be “Terminated”. All other 2T sensors on the network need to remain “Un-terminated”.
Sensor #3 is setup as “Terminated” when it leaves the factory. As long as Sensor #3 is the last sensor
on the network, none of the other termination jumpers in the other sensors need to be adjusted.
Note: The sensors do not need to be connected in numerical order.
For example, if five sensors are purchased, they can be connected in the following pattern:
Note: In the above example, if additional sensors are added at a later time to extend the existing
sensor network, Sensor #3 will have to be “Un-terminated”. The additional sensors can then be
connected, and the new last sensor on the network will have to be “Terminated”.
• the last sensor in the new network must be terminated.
To terminate a 2T sensor:
1. Open the sensor’s case by removing the three screws that hold it together.
2. Pull the black jumper off the circuit board from Pins 1 and 2 (see Figure 36).
The CAN bus sensors connect to the open CAN port on the back of the unit display panel. The Display
comes “Terminated” from the factory and will have to be “Un-terminated’ to allow for additional
sensors to be added. See photo above for termination jumper location for front panel display and
sensor boards. Note that connecting the CAN bus sensors will require entering the High Voltage
electrical compartment of the Liebert CRV. If you are not comfortable with the installation procedure,
it is recommended that you hire a certified electrician.
Connect the 10ft CAN wire to the open CAN bus port on the rear of the iCOM graphic display.
Ensure there is enough slack in the wire to allow the door to open and close freely, but not too much
slack to bind or pinch when the door is shut. It is recommended that a cable tie is used to secure the
wiring.
Connect the other end of the 10ft CAN cable to the nearest 2T rack sensor. Use additional CAN cables
to connect the remaining 2T rack sensors to each other. The order in which the 2T sensors are
attached does not matter; however, be sure that the last sensor connected is the one set to
“terminated”. As a best practice, avoid using excessive lengths of cable between sensors.
47Liebert® CRV
™
9.5.5Installing 2T sensors on racks
2T SENSOR CHAIN
Approx. center
of rack/in front
of IT equipment.
Install temperature sensors on the
perforated portion of the rack door
using the supplied zip-ties.
Ensure that the doors swing freely without
binding cables.
305
(12in)
Source DPN001983 rev0
Both temperature sensors attached to a 2T sensor housing are to be installed on 1 rack. The sensor
can be attached to the inside or outside of the rack's front door.
• One temperature sensor is to be attached near the top of the rack’s front door by using a cable tie
to secure the wire to the perforation (approx. 12" [305mm] from the top). Do not wrap a cable tie
around the actual sensor on the end of the wire. This sensor will monitor for hot air wrapping over
the top of the rack from the hot aisle.
• The other temperature sensor is to be attached to the rack's front door, centered in front of the
heat generating equipment that will be drawing in air.
• If the rack is completely filled with equipment, locate the sensor in the middle of the door,
width and height.
• If the rack is partially filled with equipment, locate the sensor in the center of the equipment
on the front door.
•Do NOT
• Install a sensor in the hot aisle
• Leave a sensor coiled on top of or inside the rack.
• With the temperature sensors in place, neatly route the wires up the rack door and into the rack
using the supplied cable ties. Be sure to leave an appropriate amount of slack in the cable to allow
the rack door to open and close without binding or pinching the wires.
• Affix the 2T sensor housing to the rack using the supplied hook-and-loop fastener. It is recommended that the housing be installed in an easily accessible space with the sensor number label
visible in case the housing needs accessed at a later time.
• Repeat this process until all sensors have been installed.
Startup
Figure 37 2T rack sensors installed on neighboring racks
Liebert® CRV
™
48
Located in the Service / Rack Setup Menu of the Liebert iCOM® display, the sensors can be set up to
press: for next/pr ev unit; and to select par ameter
press: , t hen to change par ameter
Rack Setup (page 2 of 3)
Liebert CRV= CRV
No Sensors= NoS
No rack= [blank ]
Sensor Note= 01-10
Assign Names :
01-06
07-12
13-18
19-22
0200000000000103040506
DC01DC03
DD02
DC05DC07
DD04
CRV
DC09DC11
00000000080700CRV000000
Cold Aisle
Use the navigation keys to move from rack to rack,
Enter to select a rack, and up- or down keys to
scroll through options.
UNIT 01
either display or control temperature, give them a rack name and draw a rack layout that can be
viewed in the User menu.
9.5.6Remote Rack Sensor Operation and Rack View Setup
Figure 38 Rack setup screen, page 1 of 3
Once the remote rack sensors have been configured and plugged into the CAN bus network, the
control can be configured to use the sensor for either control or reference. If the sensor is set to
“Disable,” it will be ignored. The sensor node number corresponds to the DIP switch assignment of the
sensor.
Startup
Figure 39 Rack setup screen, page 2 of 3
Once a sensor has been assigned to either control or display its temperature data a virtual position
can then be assigned to the sensor. This screen configures the Rack View layout in the User menu.
This step is not required for the sensor to operate but does provide a logical position in the row for
quickly referencing affected racks near the Liebert CRV. To set up navigate using the arrow and enter
keys to highlight the Assign Sensors number range. Once the range is selected then press the enter
key to move to the rack location blocks at the bottom of the screen. The Up and Down arrow keys can
be used to select the sensor node number. For the Liebert CRV select “CRV.”
49Liebert® CRV
™
Figure 40 Rack setup screen, page 3 of 3
Rack Setup (page 3 of 3)
Liebert CRV= CRV
No Sensors= NoS
No rack= [blank]
Sensor Note = 01-10
Assign Names:
01-06
07-12
13-18
19-22
0200000000000103040506
DC01DC03
DD02
DC05DC07
DD04
CRV
DC09DC11
00000000080700CRV000000
Cold Aisle
Use the navigation keys to move from rack to rack,
Enter to select a rack, and up- or down keys to
scroll through options.
UNIT 01
Rack Overview (page 1 of 1)UNIT 01
Cold Aisle
RAC1
71.4
EMAL
72.8
BLAD
69.4
RAC4
70.1
DC0 7
74.5
RAC6
71.0
72.4
06KW
69.3
CRV1
70.8
DISC
All temperatures shown in °F
010203040506
0708 CRV
Once a sensor has been assigned to either control or display its temperature data, a custom label can
be assigned to the sensor. This step is not required for the sensor to operate but does provide a logical
name for identification. Navigate using the arrow and enter keys to highlight the Assign Names
number range. Once the range is selected then press the Enter key to move to the rack location blocks
at the bottom of the screen. The Up and Down arrow keys can be used to select any alpha or numeric
value up to four positions.
Startup
Figure 41 Rack overview screen
If the Rack Setup menus are configured in the Service menu to locate and label the remote rack
sensors, then the Rack View in the User menu should look similar to the screen above. This screen
will show the node number at the top of each block, the label and the actual temperature that each
sensor is currently measuring.
Liebert® CRV
™
50
10.0 LIEBERTICOM® CONTROL
?
ESC
The Liebert CRV is equipped with the most advanced Liebert iCOM control system. The large Liebert
iCOM display is standard on the Liebert CRV.
Each Liebert CRV contains a return air temperature and humidity sensor, supply air temperature
sensor and three remote rack sensors. Up to an additional 7 remote rack sensors can be added to the
sensor network. Each rack sensor takes two temperature readings and reports either the average or
the maximum temperature of the two sensors.
The 2T rack temperature sensors provide feedback to the cooling unit about the condition of the air
entering the server racks. This information allows the Liebert CRV to ensure it is providing just
enough cold air to each rack, virtually eliminating hot spots. Overcooling and excessive airflow are
avoided, greatly reducing unnecessary energy consumption.
Each Liebert CRV includes three 2T rack temperature sensors to monitor three racks. A total of ten
2T temperature sensors can be connected to each cooling unit to monitor every rack a Liebert CRV is
protecting. When multiple cooling units are connected in a Unit-to-Unit iCOM control network, all
sensor data is shared to optimize their performance as a system.
2T rack sensors can also be initially installed on empty racks reserved for future growth with the
control set to ignore these sensor readings. The extra 2T temperature sensor readings can also be
displayed on the local display and reported remotely for monitoring purposes only; not impacting unit
operation. This function provides users with a built-in mini-monitoring system.
Table 22Keyboard icons and functions
Icon
Key NameFunction
Liebert iCOM® Control
On/Off KeyControls the operational state of the cooling unit.
Alarm KeySilences an alarm.
Help KeyAccesses integrated Help menus.
ESCape KeyReturns to the previous display view.
Enter KeyConfirms all selections and selects icons or text.
Increase Key
(Up Arrow)
Decrease Key
(Down Arrow)
Left and Right
Arrow Keys
Upper LED
Moves upward in a menu or increases the value of a selected parameter.
Moves downward in a menu or reduces the value of a selected parameter.
Navigates through text and sections of the display.
Blinking Red—Active, unacknowledged alarm exists
Lower LED
Solid Red—Active, acknowledged alarm exists
Amber—Power is available to the unit; unit is NOT operating
Green—Unit is operating with no alarms
51Liebert® CRV
™
Figure 42 Liebert iCOM® default screen symbols
fan
cooling
maintenance
hot water
electric heat
dehumidificationhumidification
freecooling
10.1Navigating Through the Liebert iCOM Menus
Liebert iCOM shows icons and text for monitoring and controlling your Liebert cooling units or
network of cooling units. The number of icons and amount of text shown depends on the display size.
10.1.1 Control Interface
Liebert iCOM® Control
When the buttons on the Liebert iCOM control have not been pressed for a short period, the display
backlight turns off. Pressing any key will turn the backlight on (wake up the screen) and display the
Status menu of the last cooling unit viewed. The Status menu will show the cooling unit’s operational
mode(s), return air temperature and humidity readings, temperature and humidity setpoints and any
active alarm conditions.
If the cooling unit has a large display and is not on a network, whether it is networked or stand-alone,
the Status menu will display only that cooling unit’s information. Any large display that is connected
to a network can be used to view any cooling unit on the network or show an average view of the
entire system of cooling units.
The Liebert iCOM control has three main menus: User, Service and Advanced.
The User menu contains the most frequently used features, settings and status information. The
Service menu contains settings and features used to set up unit communications and for unit
maintenance. The Advanced menu contains settings used to set up the unit at the factory.
NOTE
Menu settings may be viewed without a password, but changing settings requires a password.
If a password is required, Liebert iCOM shows a prompt to enter the password. The password
for the User menu is 1490. The password for Service menu is 5010. For details on entering a
password, see Entering a Password on page 53
10.1.2 Accessing Submenus
To access the User, Service or Advanced menu, press the Enter or down arrow key while viewing the
Status menu of the unit you wish to access. The User menu will be displayed first. To view the Service
or Advanced menus, press the right arrow key.
Liebert® CRV
Accessing Submenus on Large Displays
While viewing the menu you wish to access (User, Service or Advanced), press the enter key to
highlight the first icon. Use the arrow keys to navigate through the icons. With the desired icon
highlighted, press the enter key to enter that submenu. Once in a Submenu, a list of parameters will
be displayed.
The up and down arrow keys may be used to scroll through the parameters page-by-page if the
submenu has multiple pages. To scroll item-by-item, press the Enter key and then use the up and
down arrow keys. Using the right or left arrow keys on large displays attached to a network will
™
52
Liebert iCOM® Control
SETPOINTS
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0)
Temperature Setpoint
Humidity Setpoint
Humidity Control Type
Supply Sensor
Supply Setpoint
Backup Temperature Setpoint
change the unit being viewed. Pressing the ESC key will go back a level. Figures 44 and 45 show the
Liebert iCOM
respectively.
®
control menus for a stand-alone large display and for a networked large display,
NOTE
Settings are readable without a password, but changing settings requires a password.
10.1.3 Entering a Password
To change the value of a parameter in a menu, you must first enter the password for that menu. Each
menu—User, Service and Advanced—has a unique password to prevent unauthorized changes.
The User menu password is 1490; the Service menu password is 5010.
NOTE
Entering the Service menu password permits access to both the User and Service menus;
changes can then be made to parameters in either level.
To enter a password:
1. Navigate to the menu that contains the parameter to be changed.
2. Select Password in the submenu by pressing the Enter key
3. Press the Enter key to move your cursor to the right side of the screen to select the question
marks.
4. Use the arrow keys to enter the numeral for the password’s first digit (the up arrow key moves
from 1 to the next digit).
5. Use the right arrow key to move to the next question mark and repeat Step 4 to enter all digits in
the password.
6. After entering the password, press enter.
Figure 43 Entering a password
If the password is correct, the Actual Level shown to the right of Password will change
from 0 to 1 or 2. The menu will remain locked if the password was incorrect.
NOTE
Returning to the Status menu will require re-entering a password to make changes.
53Liebert® CRV
™
Figure 44 Menu tree—Large display, stand-alone
Status Menu – System View
Status Menu
Unit 1 View
User Menu
Unit 1
Password
Setpoints
Spare Part List
Event Log
Graphics
View Network
Set Alarms
Sensor Data
Active Alarms
Display Setup
Total Run Hours
Sleep Mode
iCOM-DO
Service Contact Info
Service Menu
Unit 1
Password
Setpoints
Unit Diary
Standby Settings/Lead-Lag
Maintenance/Wellness Settings
Diagnostics / Service Mode
Set Alarms
Sensor Calibration/Setup
System/Network Setup
Options Setup
iCOM-DO
Service Contact Info
Advanced Menu
Unit 1
Password
Factory Settings
Compressor Info
Access Passwords
Unit 1 will be displayed
in the top left corner of
the screen.
Liebert iCOM® Control
Liebert® CRV
™
54
10.1.4 Viewing Multiple Units with a Networked Large Display
Status Menu – System View
(Networked Large Display Only)
Status Menu
Unit 1 View
Status Menu
Unit 2, 3, 4...
User Menu
Unit #
Password
Setpoints
Spare Part List
Event Log
Graphics
View Network
Set Alarms
Sensor Data
Active Alarms
Display Setup
Total Run Hours
Sleep Mode
iCOM-DO
Service Contact Info
Service Menu
Unit #
Password
Setpoints
Unit Diary
Standby Settings/Lead-Lag
Maintenance/Wellness Settings
Diagnostics / Service Mode
Set Alarms
Sensor Calibration/Setup
System/Network Setup
Options Setup
iCOM-DO
Service Contact Info
Advanced Menu
Unit #
Password
Factory Settings
Compressor Info
Access Passwords
Unit # or System will be
displayed in the top left
corner of the screen .
When you first wake up the control, press the ESC key to return to the System view Status menu.
This view shows an average of all the units on the network and any alarms present. To view a specific
unit on the network, press either the enter key or down arrow key. When you do this, you will see the
word System in the top left of the screen change to a unit number. Using the left and right arrow keys
you can toggle through the various units on the network. To go back to the System view, or back one
level from any menu in the control, press the ESC key.
Figure 45 Menu tree—Large display, networked
Liebert iCOM® Control
55Liebert® CRV
™
Figure 46 User menu icons
EVENT
LOG
°C / °F
% RH
SET
SET
12
39
6
SET
ALARMS
!
ACTIVE
ALARMS
1234
h
RACK
VIEW
User Menu
password: 1490
°C / °F
% RH
SET
EVENT
LOG
SET
ALARMS
!
ACTIVE
ALARMS
1 2
39
6
SET
1234h
Table 23User menu icons
IconName
SetpointsView and change temperature and humidity setpoints
Liebert iCOM® Control
Description
Spare Part List
Displays the various part numbers of the components/parts
in the cooling unit
Event LogContains last 400 events
GraphicsDisplays temperature and humidity graphs
View NetworkShows status of all connected units
Set AlarmsAllows enable, disable and settings for alarms
Sensor DataShows readings of standard and optional sensors
Liebert® CRV
Active AlarmsAllows the user to view all current active alarms
Display SetupChange settings for display: language, time, simple or graphic view
Total Run Hours
™
Records the run time of all components and allows setting
of limits on run time
56
Table 23User menu icons (continued)
RACK
VIEW
DO
+
WELLNESS
SET
ALARMS
SERVIC E
+/-
NETWORK
SET
UP
RACK
SETU P
°C / °F
% RH
SET
Service Menu
password: 5010
°C / °F
% RH
SET
WELLNESS
SERVICE
SET
ALARMS
IconName
Rack ViewAllows viewing data, collected by sensors, about rack status
Liebert iCOM® Control
Description
Service Contact Info
iCOM-DOChange settings for Liebert iCOM
Figure 47 Service menu icons
Table 24Service menu icons
IconName
SetpointsTo view and change temperature and humidity setpoints
Contains key contact information for local service, including names
and phone numbers
®
Discrete Output card
Description
Unit Diary
Standby Settings/ Lead-LagAllows lead/lag setup when multiple units are connected
Maintenance/
Wellness Settings
Diagnostics/
Service Mode
Set AlarmsAllows enable, disable and settings for alarms
Shows all entered program changes and maintenance performed
on the unit
Allows setting maintenance interval reminder, maintenance
message, number of unit starts and stops and time since last
maintenance
Allows troubleshooting, manual mode, read analog and digital
inputs
57Liebert® CRV
™
Table 24Service menu icons (continued)
+ / -
NETWORK
IconName
Sensor Calibration/SetupAllows calibration of sensors
System/Network SetupAllows setup and U2U communication for multiple units
Options SetupAllows setup of component operation
Rack SetupLabel racks, establish settings for sensors
Liebert iCOM® Control
Description
Service Contact Info
Humidifier SettingsChange Humidifier settings
Contains key contact information for local service, including
names and phone numbers
press : for next/prev unit; for unit/sys tem v iew
press: for menu; ESC for prev screen; ? for help
The Liebert iCOM controller for the Liebert CRV supports multiple main screen layouts. The screens
are a graphical representation of the Liebert CRV, selectable to show unit operation with or without
rack sensors, unit operation with a rack sensor summary, historical temperature and humidity
trending or trending the screens used on other Liebert products. Unlike other Liebert cooling
products, the Liebert CRV display will always revert to the Unit Screen instead of the System Screen.
The following screens are user preference. The remote rack sensor screens should be used only when
remote rack sensors are connected.
Figure 48 Liebert CRV system screen
Liebert iCOM® Control
The System screen can be accessed by pressing the Up arrow key when the Unit screen is displayed.
The System screen shows the fan speed and cooling capacity averages of all connected units. The
Supply, Return and Remote Rack sensors of all connected units are also displayed showing the
average, maximum and minimum of all connected sensors.
59Liebert® CRV
™
Figure 49 Liebert iCOM® menu components for Liebert CRV
UNIT 1
Liebert
CRV
Rack Inlet Temp
Average :71°F
Maximum: 73°F
Minimum:69°F
28.02.2011 15:03UNIT ON
28.02.2011 14:07 (01) UNIT ON
28.02.2011 14:07 (01) POWER ON
press: for next/prev unit; for unit/system view
press: for menu; ESC for prev screen; ? for help
89%
67%
04/2011
98°F
20%RH
69
51
°F
%RH
SYSTEM
Liebert
CRV
28.02.2011 15:03UNIT ON
28.02.2011 14:07 (01) UNIT ON
28.02.2011 14:07 (01) POWER ON
press: for next/prev unit; for unit/system vie w
press: for me nu; ESC for prev scr een; ? for help
89%
67%
0%
04/2011
°F 71.4 72.8 69.4 70.1 70.8 71.074.577.772.476.8
RAC1 EMAL BLAD RAC4 DISC R AC606KWDC08DC07DC10
69.3
Front
Supply
°F
SYSTEM
Liebert
CRV
28.02.2011 15:03UNIT ON
28.02.2011 14:07 (01) UNIT ON
28.02.2011 14:07 (01) POWER ON
press: for next/prev unit; for unit/sy stem view
press: for menu; ESC for prev s cre en; ? for help
69.3
Front
Supply
°F
89%
0%
67%
04/11
16d12d8d4d
+5
69°
-5
+10
51%
-10
Av. Rack
Temp
Supply
Hum.
18:55
Supply Temperature
and Humidity
Last Two Events,
Warnings or Alarms
Individual Rack
Sensor Temperatures
The rack graph is empty
at 68°F (20°C) and full at
77°F (25°C).
Historical Supply
Air Temperature
Graph
Historical Supply
Air Humidity
Graph
Fan Speed
Return Temperature
and Humidity
Cooling Capacity
Next recommended
maintenance
Summary of Rack
Sensor Readings
Humidification
Liebert iCOM® Control
Liebert® CRV
™
60
10.3Liebert iCOM® Control Setup
SETPOINTSUNIT 02
U101
U102
U103
U104
PASSWORD (Actual Level 0)
Controlling Sensor
Temperature Setpoint
Humidity Setpoint
????
Supply
70°F
50%
for next/previous unit
then
Supply Sensor
Return Sensor
Remote Sensor
to change parameter
70°
50%
to select parameter
to confirm
The Liebert iCOM on the Liebert CRV leaves the factory with the fan speed and cooling capacity
controlled by the supply air sensor. This control mode is extremely robust and will ensure that you
are delivering precise cooling to the cold aisle. To unlock the full capability of the Liebert CRV, the
remote rack sensors should be installed, which will allow the fan speed and the cooling capacity to be
“de-coupled.” This means that the fan speed can now be controlled independently of the cooling
capacity. In this advanced configuration, the Liebert CRV can control the discharge temperature of
the unit by modulating cooling capacity based on the supply sensor and use the remote rack sensors
to ensure that the cool air is being delivered to the inlet of the racks. Using the supply and remote
rack sensors in this de-coupled mode is the preferred method for controlling the Liebert CRV in a hot
/ cold aisle configuration. In addition to this configuration Emerson has provided additional flexibility
for other applications shown in Table 25.
Figure 50 Setpoint screen
Liebert iCOM® Control
In Figure 50, the controlling temperature sensor can be set to either Supply, Return or Remote. As
the selection is changed from one sensor to another, the setpoint is displayed next to the
corresponding sensor on the illustration, giving a visual indication of the sensor placement in
relationship to the Liebert CRV.
A password must be entered to change the setting; see 10.1.3 Entering a Password for assistance
on entering the password.
Temperature sensor settings are based on user preference. Use the settings below as a guideline.
1. Set the remote temperature setpoint to the desired server inlet temperature
2. Set the humidity setpoint to 45% with a 10 to 20% deadband.
This will control the moisture content well inside the AHSRAE standard.
3. Set the supply setpoint 5°F below the setting for the remote rack sensor.
This will serve as a starting point.
If 75°F (24°C) server entering air temperature is desired, the supply air must be colder to account for
any thermal pickup of the air as it flows to the cold aisle. If this does not achieve the cold aisle
temperature Setpoint, then set the supply sensor setpoint lower. Continue to do this until the cold
aisle temperature setpoint is achieved.
61Liebert® CRV
™
The supply temperature Setpoint may require adjusting since it will be dependent on the distance of
the CRV to the server racks being cooled. This temperature will also be dependant on rack blanking
panels, server population and if containment is being used
Table 25Controlling sensor settings
Fan Control
Table 25 shows the flexibility of the Liebert CRV and how the different sensor configurations can be
used to control the Liebert CRV fan speed and cooling capacity. The table shows the different coupled
and decoupled modes available for the Liebert CRV.
10.4Event Log
The event log displays all events and actions that have been generated by the unit. When multiple
units are networked you will see the event log of the whole system. Each event shows the unit that
generated the alarm, time and date stamp, a description and the event type.
.
Cooling Control
S103Cool / S125 FanSupplyRemote SensorReturn
Supply
Remote Sensor
Return
Factory Default
(Coupled)
Recommended
(Decoupled)
X
(Decoupled)
N/AN/A
X
(Coupled)
X
(Decoupled)
N/A
X
(Coupled)
Liebert iCOM® Control
10.5Spare Part List
The spare parts lists contains a detailed description and part number that can be used to order parts
for the unit. These part numbers are specific to each model and option installed on the unit.
10.6Wellness—Next Maintenance Calculation
The next maintenance calculation, as well as the included diagnostics feature, will help keep the
cooling unit running at peak performance to ensure minimum component stress and maximum
reliability. The diagnostics will help the service engineer evaluate the unit’s operation since the last
maintenance.
10.6.1 Calculation of Next Maintenance and Diagnostics
If the unit includes any of the following components, they are included in the calculation:
•Fan(s)
• Compressor 1
• Compressor 2
• Electric Heaters
• Humidifier
For each component, the next maintenance will be calculated from the following parameters:
• Standard service interval (1, 2 or 4 times a year) (to be set)
• Working hours (counted)
• Number of starts (counted)
• Average running time (calculated)
• Optimum number of starts per hour (to be set)
• Maximum number of starts per hour (to be set)
• Maximum bonus to enlarge time to next maintenance (to be set)
• Maximum penalty to reduce time to next maintenance (to be set)
Liebert® CRV
™
62
Liebert iCOM® Control
Calculating Unit Wellness
Liebert iCOM® keeps tabs on the condition of a cooling unit, determining its wellness and projecting
when service will be needed, for the entire unit as well as for individual components. This assists in
scheduling maintenance calls and helps pinpoint components likely to require service.
Liebert iCOM displays a graphic for needed maintenance. It begins with the standard maintenance
interval—12 months, six months or three months—and adjusts that based on its calculation of
components’ wellness.
To calculate wellness, Liebert iCOM keeps a running total of component working hours and the
number of times it has been started. Liebert iCOM relates that data to the optimum/maximum starts
per hour. Accordingly, Liebert iCOM will increase or decrease the time before the next service call will
be needed.
The more frequently a component starts, the sooner it is likely to need maintenance. If, for example, a
unit’s fan runs continuously, but it’s compressor starts and stops often, Liebert iCOM records that
and calls for maintenance based on the compressor’s wellness factor.
Alarms and warnings, such as clogged filters or high or low pressure, reduce the time till the next
maintenance to zero. If the alarm is cleared and reset, Liebert iCOM recalculates wellness. It begins
with the pre-alarm maintenance time and factors in the alarm.
Parameters for Next Maintenance Calculation
General Maintenance Settings
• Maintenance Frequency—can be set as one to 12 months or to zero, which disables maintenance calculation
• Max. Bonus—increases the time to next maintenance with the set value, if all components run
optimally (number of starts, average running time)
• Max. Penaltyvalue—decreases the time to next maintenance with the set value, if some components run in non-optimum way (number of starts, average running time)
• Last Maintenance—date can be set from service-engineer; informational
• Service-Engineer—name of the service engineer; editable
• Reset—puts all counters of all components, such as (motor, compressors, heaters and humidifier),
at zero and starts a new maintenance calculation (reset to be done after maintenance)
Fans / Heaters / Humidifier Settings and Diagnostics
• Number of starts and Working hours are counted separately since the last maintenance. Total
working hours can be read in the standard working hours window (customer window).
• Average Working Hours is the calculation, resulting from starts and working hours.
• Starts per Day Optimum is the number of starts considered as optimum.
• Starts per Day Worst is the number of starts considered as hunting (worst case).
• Number of Alarms counts the alarms, happened between two service intervals.
• Actual Bonus is calculated from number of starts and average working time. Can be positive
(bonus) or negative (penalty). This value influences the time remaining to the next maintenance.
Compressor 1 / 2 Settings and Diagnostics
• Number of starts and Working hours are individually counted since the last maintenance. Total
working hours can be read in the standard working hours window (customer window).
• Average Working Hours is the calculation, resulting from starts and working hours.
• Starts per Day Optimum is the number of starts considered as optimum.
• Starts per Day Worst is the number of starts considered as hunting (worst case).
• Number of HP Alarms counts the high-pressure alarms, happened between 2 service intervals.
• Number of LP Alarms counts the low-pressure alarms, happened between 2 service intervals.
• Number of TH Alarms counts the thermal protection alarms, happened between 2 service intervals.
• Actual Bonus is calculated from number of starts and average working time. Can be positive
(bonus) or negative (penalty). This value influences the time remaining to the next maintenance.
63Liebert® CRV
™
10.7Liebert CRV Operation—Liebert iCOM® Control
10.7.1 Cooling
The cooling control of the Liebert CRV can be managed from any of the temperature sensors. Emerson
recommends using the supply temperature sensor to control the cooling capacity of the Liebert CRV.
The supply temperature is an accurate representation of the actual heat rejection the Liebert CRV
needs to perform at an optimal level. A chilled water version of the Liebert CRV will modulate the
cooling capacity from 0% - 100% and the DX version of the Liebert CRV will modulate the cooling
capacity of the unit from 20% -100% compressor capacity.
To avoid short-cycling the compressor during room heat load changes, the Liebert CRV will not
deactivate the compressor until the air temperature is below 150% of temperature setpoint when in
Remote or Supply Air Control or below 200% of temperature setpoint when operating in Return Air
control.
10.7.2 Heating
The heating control is active only when the unit is in dehumidification mode. The reheats will begin
activation when the control temperature has dropped to -66% of the controls proportional band and
will deactivate when the temperature setpoint has been reached.
10.7.3 Air Flow
The Liebert CRV’s airflow can be controlled manually or dynamically by temperature sensors.
Emerson recommends controlling the fan speed using the remote rack temperature sensors. The
remote rack sensors are an accurate representation of the delivery of the Liebert CRV’s discharge air.
When using the remote rack temperature sensors, the fan speed will modulate from 50% to 100%
based on the remote rack temperature setpoint and the sensitivity of the proportional and integral
settings. Manually controlling the Liebert CRV’s fan speed is also possible by setting a fixed fan speed
either from the front display or through a monitoring system. The manual control will be overridden
for freeze protection, humidification and reheat operation. In the event of a single fan failure the
Liebert CRV will ramp the remaining operating fan to 110% of its rated output to compensate for the
loss of airflow. In addition, an alarm will be triggered to report which fan failed.
Liebert iCOM® Control
10.7.4 Humidification
The Liebert CRV’s humidification is activated when the measured temperature and humidity sensor
has been calculated to exceed the corresponding dew point setpoint. The dew point setpoint is
calculated based on the temperature and humidity of the sensor set to control the control setpoint and
relative humidity.
Example: Temperature Setpoint 72°F / Humidity Setpoint 50% = 52°F Dew Point
NOTE
The Liebert iCOM control monitors the condition of the air discharging from the unit to protect
neighboring electronic equipment. Liebert iCOM will prevent the humidifier from activating if
the discharge air is near its saturation point. This protects against discharging fog from the
unit or condensation forming on the unit’s supply air baffles. This protection mode is activated
when the supply sensor reading is below 53°F (11.7°C) or above 55% relative humidity. When
this condition is met a message will display showing “humidifier” suspended.
The status of the humidifier lockout can be viewed in the Service/Diagnostics menu.
These protections do not apply to the external humidifier output.
User menus report general cooling unit operations and status. The user menu password is 1490.
The User menu parameter tables in this manual may differ from the display on your cooling unit. The
Liebert iCOM functions with several Liebert Precision Cooling units, each with its own set of control
commands. In addition, the Liebert iCOM control firmware is being updated constantly. As a result,
the User menu parameter tables in this manual may differ from the display on your cooling unit.
Check www.liebert.com for the latest Liebert iCOM user manual updates.
Figure 51 User menu icons
Figure 52 Setpoints parameters screen
Liebert iCOM® Control
Controlling Sensor—This parameter allows the user to select which sensor will be used to
determine the amount of cooling needed. This parameter can select only a single sensor for both the
temperature and fan speed control. Use the Service / Setpoints menu to decouple the operation of fan
speed to the remote sensors and the cooling capacity to the supply sensor.
Temperature Setpoint—This parameter allows the user to select a temperature that the cooling
unit will maintain by applying cooling and or reheats.
Humidity Setpoint—This parameter allows the user to select a humidity that the cooling unit will
maintain by removing or adding moisture to the air.
Spare Part List
Spare Parts—The spare parts lists contains a detailed description and part number that can be used
to order parts for the unit. These part numbers are specific to each model and option installed on the
unit.
Event Log
Event Log—The event log displays all events and actions that have been generated by the unit.
When multiple units are networked you will see the event log of the whole system. Each event shows
the unit that generated the alarm, time and date stamp, a description and the event type
65Liebert® CRV
™
View Network
This window is READ ONLY
U301
U302
U303
U304
U305
U306
U307
U308
U309
U310
U311
U312
Temperature Setpoint°F
Actual Control Temperature°F
Fan Setpoint°F
Actual Fan Control Temp°F
Humidity Setpoint%
Actual Return Humidity%
Actual Supply Humidity%
Actual CW Temperature°F
DigiScroll 1 Temperature°F
SENSOR DATAUNIT 01
View Network—The view network screen provides an overview of the Liebert iCOM® network and a
status of each unit. This screen will provide the unique unit name given to the unit. If no name is
given, then only the unit number will be displayed.
Figure 53 Sensor data parameters screen
Liebert iCOM® Control
Temperature Setpoint—This parameter shows the cooling setpoint, which is the setpoint used to
drive the compressor capacity. This parameter will automatically change based on which sensor is
used for control (Return, Supply or Remote sensor).
Actual Control Temperature—This parameter is the temperature reading of the actual sensor
that is referenced to U301. This parameter automatically changes based on the control sensor setting.
Fan Setpoint—This parameter defines the fan speed setpoint. This value is not shown when a single
sensor (Coupled Mode) is used to control cooling capacity and fan speed. This parameter is calculated
by adding the temperature setpoint and the fan speed delta in the Service / Setpoints menu.
Actual Fan Control Temp—This parameter is the temperature reading of the actual sensor that is
referenced to U303. This parameter automatically changes based on the control sensor settings.
Humidity Setpoint—This parameter allows the user to select a humidity that the cooling unit will
maintain by removing or adding moisture to the air. This parameter is adjustable from 20-80%. The
factory default setting from the factory is 50%.
Actual Return Humidity—This parameter is the return relative humidity reading of the sensor.
Actual Supply Humidity—This parameter is the calculated relative humidity of the supply sensor
Liebert® CRV
based on the actual return humidity reading. This value is calculated by using a reverse look up
algorithm based on dew point.
Actual CW Temperature—This parameter displays the actual chilled water supply temperature
being delivered to the unit.
DigiScroll 1 Temperature—When digital scroll compressors are installed in the unit then the
actual digital scroll number 1 head temperature will be shown.
Active Alarms
Active Alarms—Permits viewing all current, active alarms.
™
66
Figure 54 Display setup parameters screen
to change parameter
for next/previous unit
to select parameter
to confirm
then
S401
S402
S403
S404
S405
S406
S407
S408
S409
S410
S411
LanguageENGLISH (US)
Date7/17/2010
Time09:20:19
Temperature Indication°F
Display Contrast50
Buzzer FrequencyOff/ 0
Backlite Off after30 min
ScreenRack View
Display ColorsNormal
Date Formatmm/dd/yyyy
DISPLAY SETUPSYSTEM
Language—This parameter sets the language on the display. When this parameter is changed all
menu parameters will be converted to the selected language.
Liebert iCOM® Control
Date—This parameter sets the internal date of the unit. If this unit is connected to other units with
the unit to unit network connection. All units will reflect the last date set.
Time—This parameter sets the internal time of the unit. If this unit is connected to other units with
the unit to unit network connection. All units will reflect the last time set.
Temperature Indication—This parameter selects the actual and set point temperature indication.
Selecting C will set the unit to display in Celsius and F will set the unit to display in Fahrenheit.
Display Contrast—This parameter changes the contrast of the display to adjust for different
viewing angles, low light and bright light conditions. As the display ages the contrast may need to be
adjusted for better viewing clarity.
Buzzer Frequency—This parameter changes the audible noise frequency of the built in buzzer.
When adjusting the buzzer frequency the buzzer will sound allowing you to select a frequency that is
easily detected when an alarm occurs.
Backlite Off After—This parameter controls the length of time that the backlite remains active
when the display is unused. When the buttons on the front display have not been pressed for the time
selected in this parameter the backlite will turn off, extending the life of the display and saving
energy.
Screen—Multiple screen layouts exist for the CRV, Including Rack View and Trends to be
monitoring on the main display. Views include a Unit View with or without sensors, Rack View and
Graphical Data Record View. See Figure 49 for screen layouts.
Display Colors—This parameter selects the background color. Inverted sets the display to show
white font with blue background and Normal sets a white background with blue font.
Date Format—Date format changes the month, day and year arrangement shown on the front
display and on event time stamps.
67Liebert® CRV
™
Figure 55 Total run hours parameters screen
U501
U502
U503
U504
U505
U506
U507
U508
U509
U510
U511
Actual HoursLimit
Fan Motor (s)35130
Compressor 135110
Chilled Water00
Electric Heater00
Humidifier1600
Dehumidification50
TOTAL RUN HOURSUNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
SERVICE MENUS
to select parameter
to change level
to open requested menu
ESC
to unselect
to navigate
+
WELLNESS
SET
ALARMS
SERVIC E
+/-
NETWORK
SET
UP
RACK
SETU P
°C / °F
% RH
SET
Each parameter shows the actual hours the component has operated and the maximum time the
component can operate before the next maintenance.
Liebert iCOM® Control
10.9Liebert iCOM® Service Menu Screens
Service menus allow customized settings for site operations. The password for service menu
parameters is 5010.
The Liebert iCOM control firmware is being updated constantly. As a result, the Service menu
parameter tables shown in this manual may be slightly different than what is shown on your cooling
unit's display. Please check www.liebert.com for the latest Liebert iCOM User manual updates.
Figure 56 Service Menu Main Screen
Liebert® CRV
™
68
Figure 57 Setpoints parameters screen - Page 1
S101
S102
S103
S104
S105
S106
S107
S108
S109
S110
S111
PASSWORD (Actual Level 0)????
Temperature Setpoint68 °F
Temperature Control SensorRemote Sens or
Temperature Control TypeProportional
Temperature Deadband2°F
Cooling Proportional Band9°F
Cooling Integration /Derivative min /sec
Heating Proportional Band9°F
Heating Integration /Derivative min /sec
CRV ControlAverage
SETPOINTS (page 1 of 4)UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
Temperature Setpoint—This parameter selects a temperature that the cooling unit will maintain
by applying cooling and or reheats. This parameter is adjustable from 41-104°F (5-40°C), the factory
default setting is 73°F (22.7°C).
Liebert iCOM® Control
Temperature Control Sensor—This sensor controls the cooling capacity of the Liebert CRV. If the
unit is chilled water model, then this sensor controls the chilled water valve opening. If the unit is a
DX (direct expansion) model then this sensor will control the amount of digital scroll capacity.
Temperature Control Type—This parameter selects the type of control the system will use to
activate cooling, heating, humidification and dehumidification. A detailed description of each control
type can be found in 3.7 - Supply Control.
Temperature Deadband—This parameter can be set to avoid overshooting of the setpoint and
cycling between the reheats and cooling. The value entered into this field will be split in half by the
temperature setpoint. Example—If the temperature setpoint is 70°F (21.1°C) and a 4°F (2.2°C)
deadband is set, then no cooling will be activated until 72°F (22.2°C) and no heating will be activated
until 68°F (20°C) is reached.
Cooling Proportional Band—This parameter adjusts the activation points of compressors or rate
of change based on the actual sensor values deviation from setpoint. The smaller this number the
faster the compressors and valve(s) will increase capacity. Too small of a number may cause the unit
to short cycle the compressors or excessively reposition the valve.
Cooling Integration/Derivative—Cooling integration takes into consideration the amount of time
the actual temperature has deviated from the setpoint. The longer this deviation exists the more
corrective action the unit will use to achieve the setpoint. The derivative term monitors the rate of
change and will reduce or increase the amount of corrective action based on the actual temperature
increasing or decreasing toward the temperature setpoint.
Humidity Setpoint—This parameter allows the user to select a humidity that the cooling unit will
maintain by removing or adding moisture to the air. This parameter is adjustable from 20-80%. The
factory default setting from the factory is 50%.
Liebert iCOM® Control
Humidity Control Type—This parameter selects the humidity control calculation. Setting this
parameter to “Relative” will control the humidity without considering any temperature deviations.
“Predictive” and “Absolute” control consider the temperature deviation from temperature setpoint so
that a constant level of moisture is kept in the area based on the humidity sensor reading and the
temperature deviation from setpoint. The factory default setting is “Predictive.”
Humidity Deadband—This parameter can be set to avoid overshooting of the setpoint and cycling
between humidification and dehumidification. The value entered into this field will be split in half by
the temperature setpoint. Example: If the humidity setpoint is 50% and a 4% deadband is set then no
humidity control will be activated between 48% and 52%.
Humidity Proportional Band—This parameter adjusts the activation points of the humidifier and
compressors based on the actual sensor values deviation from setpoint. The smaller this number the
faster the compressors and humidifier will increase capacity, too small of a number may cause the
unit to short cycle or overshoot setpoint.
Humidity Integration Time—This parameter adjusts the capacity of the unit based on time away
from setpoint so that accurate humidity control can be maintained. This parameter is only active
when Control Type is set to “PI.”
Dehum Proportional Band—The parameter adjusts the activation points of dehumidification
based on the actual sensor values deviation from setpoint. The smaller this number the faster the
compressors and humidifier will increase capacity, too small of a number may cause the unit to short
cycle or overshoot setpoint.
Dehum Integration Time—This parameter adjusts the capacity of the unit based on time away
from setpoint so that accurate humidity control can be maintained. This parameter is only active
when control type is set to “PI”.
Dehum/Heat Low Limit 1—This parameter sets the temperature at which the compressor will be
deactivated for dehumidification control. Example—If Low Limit 1 is set to 4°F (2.2°C) and the
temperature setpoint is 70°F (21.1°C), then dehumidification will turn off at 66°F (18.8°C).
Low Limit 1 reset—This parameter controls when the temperature has increased enough to reenable dehumidification.
Liebert® CRV
™
70
Figure 59 Setpoints parameters screen - Page 3
S123
S124
S125
S126
S127
S128
S129
S130
S131
S132
S133
PASSWORD (Actual Level 0)????
Fan Control Ty peAut o
Fan Control SensorRemote Sensor
Fan Regulation Type
Fan Delta°F
Fan Speed Proportional Band°F
Fan Speed Int egrationmin
Fan Speed Manual Setpoint%
Fan Speed STD75%
Fan Speed Min50%
Fan Speed Dehum70%
SETPOINTS (page 3 of 4)UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
Fan Control Type—This parameter sets how the fan speed will be controlled. This parameter can be
set to Auto mode, which will allow the Liebert CRV to drive the fan based on the temperature sensor
selected for sensor control type. This parameter can also be set to Manual mode, which allows the
Liebert CRV to be set to a fixed fan speed either through the local display or through a building
management system.
Liebert iCOM® Control
Fan Control Sensor—This parameter sets which sensor will drive the Liebert CRV fans when set to
Auto mode for the fan control type.
Fan Regulation Type—This parameter is the fans’ control type. It can be set to Proportional
control, which will modulate the fans linearly based on the deviation from the setpoint. PI control is
also available and works in the same manner as the temperature control integral term.
Fan Delta—This parameter sets the fan speed setpoint. The delta accounts for the temperature rise
from the Supply Air Sensor and the Remote Rack sensors by adding the Fan Delta to the
Temperature Setpoint (S102). This eliminates the possibility of setting the remote rack temperature
setpoint lower than the supply temperature setpoint.
Fan Speed Proportional Band—This parameter adjusts the fans rate of change based on the
actual sensor values deviation from setpoint or the delta. The smaller this number the faster the fan
will increase its speed. Too small of a number may cause the fans to excessively reposition.
Fan Speed Integration—This parameter adjusts the fanspeed of the unit based on time away from
setpoint. This parameter is only active when Control Type is set to “PI.”
Fan Speed Manual Setpoint—This parameter sets the speed of the fans when the unit is placed
into Manual Fan Speed Control mode.
Fan Speed STD—This parameter sets the maximum fan speed of the unit under normal operating
circumstances.
Fan Speed Min—This parameter sets the lowest fan speed operation of the unit.
Fan Speed Dehum—This parameter sets the fan speed the unit will operate at during a call for
dehumidification. The fan speed will position to the highest requirement. If the call for fan speed from
the remote rack sensor is requesting more CFM than the Dehum fan speed, then the fans will run at
the remote sensor fan speed request.
71Liebert® CRV
™
Figure 60 Setpoints parameters screen - Page 4
S134
S135
S136
S137
S138
S139
S140
S141
S142
S143
S144
PASSWORD (Actual Level 0)????
MIN at CFC for EC Fan0%
STD at CFC for EC Fan100%
High Temp Limit ApproachSupply
High Temp Limit Approach at2°F
Ball Valve Setpoint Offset0psig
SETPOINTS (page 4 of 4)UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
MIN at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the
minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;
and the STD speed is reached when the call for fan reaches 100%.
Liebert iCOM® Control
For example, if the minimum is set to 20 and the standard is set to 90, the fan speed MIN is reached
earlier (the fan operates on lower speed compared to the calculated call for fan), and the STD speed is
reached faster when compared to the calculated call for fan.
STD at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the
minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;
and the STD speed is reached when the call for fan reaches 100%.
High Temp Limit Approach—This parameter sets the sensor that controls the fan speed maximum
override. This can be set to Disable, Supply or Return.
NOTE
The Liebert CRV fans are oversized and can be used to help protect equipment in emergency
situations, such as high temperature and a single fan failure.
High Temp Limit Approach at— This parameter sets the temperature when the units fan speed
can operate above the maximum speed. The maximum override speed during this mode is set in
parameter A157 (Advanced menus).
Ball Valve Setpoint Offset—This parameter adjusts the operating compressor discharge pressure
by changing the targeted range of control. Available only on water-cooled units.
Unit Diary—Large Display Only
Shows all entered program changes and maintenance performed on the unit.
PASSWORD(Actual Level 0)????
Number of Standby Units0
Rotation Frequency
Rotate at (hour)
Rotate at (minute)
Rotate by
Perform one R otation
Casc ade U nits
Start all Standby Units by H T
STANDBY SETTINGS/LEAD-LAGSYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then
Number of Standby Units—This parameter selects the number of units that will be in Standby
mode. When a unit is in standby mode the fan will be off and no cooling will be provided.
Liebert iCOM® Control
Rotation Frequency—This parameter controls when a rotation will occur between the standby
units and the operating units within a network.
Rotate at (hour)—This parameter sets the hour of the rotation
Rotate at (minute)—This parameter sets the minute of the rotation
Rotate by—This parameter determines the number of positions to rotate by. Example: If there are 6
units in a unit to unit network and units 1, 3 & 5 are in standby and this parameter is set to “1” then
at the next rotation units 2, 4,& 6 will be placed into standby and 1, 3 & 5 will become operational.
Perform one Rotation—This parameter will manually force a single rotation between units.
Cascade Units—This parameter when set allows units to activate from Standby mode if the room
temperature is unable to be maintained by the non-standby units. If yes is selected then the cascade
units can perform all functions when activated from standby. This parameter can also be set for
Cooling Only or Cool / Heat only.
Start all Standby Units by HT—This parameter activates all units to cool when a High
Temperature alarm occurs.
See 3.9.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
73Liebert® CRV
™
Figure 62 Wellness basic settings screen- Page 1
S001
S002
S003
S004
S005
S006
S007
S008
S009
S010
S011
PASSWORD(Actual Level 0)????
Maintenance Frequency Per Year1
Max Bonus0
Max Penalty0
Last Maintenance06/14/2010
Servic e EngineerNobody
Confirm PMNo
Calculated Next Maintenance06/2011
WELLNESS basic settings (page 1 of 5)SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then
Maintenance Frequency Per Year—This parameter sets the number of expected maintenance
visits in a one year time span.
Liebert iCOM® Control
Max Bonus—This parameter will increase the time to the next maintenance cycle. A bonus should be
assigned when a service visit finds that all components are working optimally.
Max Penalty—This parameter will decrease the time to the next maintenance cycle. A penalty
should be used when a service visit finds excessive wear on components.
Last Maintenance—This parameter is set during the service call. It also indicates to other service
personnel the date of the last visit.
Service Engineer—This parameter provides a label for the service representative to list either the
company name or representative’s name.
Confirm PM—This parameter confirms that the service representative has completed the preventive
maintenance and resets the next maintenance date.
Calculated Next Maintenance—This parameter provides a date to when the next expected
maintenance should take place based on the last confirmed PM, component starts, run hours and the
penalty / bonus currently set in the Liebert iCOM
®
control.
Liebert® CRV
™
74
Figure 63 Wellness motor settings parameters screen - Page 2
S012
S013
S014
S015
S016
S017
S018
S019
S020
S021
S022
PASSWORD(Actual Level 0)????
Number of Starts21
Run Hours3376 hrs
Average Run Time9645 min
Starts per Day Best1
Starts per Day Worst24
Number of Alarms0
Actual Bonus0
WELLNESS motor settings (page 2 of 5)UNIT 1
to change parameter
for next/previous unit
to select parameter
to confirm
then
Liebert iCOM® Control
Number of Starts—This parameter shows the number of starts for the unit’s fans.
Run Hours—This parameter shows the number of run hours for the unit’s fan.
Average Run Time—This parameter displays the average run time of the unit’s fan.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of Alarms—This parameter displays the number of alarms that have occurred with the
unit’s fans.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s fans. The
unit will always take the value from the worst component for the next maintenance indication.
Number of Starts—This parameter shows the number of starts for the unit’s compressor.
Liebert iCOM® Control
Run Hours—This parameter shows the number of run hours for the unit’s compressor.
Average Run Time—This parameter displays the average run time of the unit’s compressor.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of HP Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s compressor.
Number of LP Alarms—This parameter displays the number of low pressure alarms that have
occurred with the unit’s compressor.
Number of OL Alarms—This parameter displays the number of overload alarms that have occurred
with the unit’s compressor.
Number of DS HT Alarms—This parameter displays the number of Digital Scroll High
Temperature alarms that have occurred with the unit’s compressor.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s compressor.
The unit will always take the value from the worst component for the next maintenance indication.
Number of Starts—This parameter shows the number of starts for the unit’s reheats.
Liebert iCOM® Control
Run Hours—This parameter shows the number of run hours for the unit’s reheats.
Average Run Time—This parameter displays the average run time of the unit’s reheats.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of HP Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s reheats.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s reheats. The
unit will always take the value from the worst component for the next maintenance indication.
Number of Starts—This parameter shows the number of starts for the unit’s humidifier.
Liebert iCOM® Control
Run Hours—This parameter shows the number of run hours for the unit’s humidifier.
Average Run Time—This parameter displays the average run time of the unit’s humidifier.
Starts per Day Best—This parameter displays the lowest number of starts in a rolling 24 hour
period.
Starts per Day Worst—This parameter displays the highest number of starts in a rolling 24 hour
period.
Number of Alarms—This parameter displays the number of high pressure alarms that have
occurred with the unit’s humidifier.
Actual Bonus—This parameter displays the actual calculation of wellness for the unit’s humidifier.
The unit will always take the value from the worst component for the next maintenance indication.
HP 1 Alarm Code—Compressor 1 high pressure alarm code.
LP 1 Alarm Code—Indicates which phase compressor 1 is operating in. For more information on
this refer to the Liebert iCOM
HT 1 Alarm Counter—Compressor 1 high temperature event alarm counter. If more than five
events in a rolling 4 hour period occur then the compressor will be locked out.
12h Dehum Counter—
Low Supply Temperature Counter—
Actual LP1 Pressure—Current refrigerant low pressure side reading in atmosphere for
Compressor 1.
Actual HP1 Pressure—Current refrigerant high pressure side liquid reading in atmosphere for
Compressor 1. (This is available only on water cooled units equipped with motorized ball valves.)
®
Training and Service manual’s low pressure transducer flow chart.
Manual Mode—Use this setting to place the Liebert iCOM
initial setting necessary to activate any of the following items.
Motor(s)—Setting this option to ON will start the main fan of the unit. Note that the main fan must
be On in order to activate any of the following overrides.
Compressor 1—Use this setting to turn on compressor 1 and select the mode of compressor
operation. The operation selections are RUN, EVACUATE and CHARGE.
Compressor 1 Capacity—Use this setting to enable Compressor 1 Cycle Ramp.
Compressor 1 Cycle Ramp—This setting allows the user to select the capacity the compressor
should run at. Range on this is 0 – 100%.
Compressor 1 LLSV—This option will control the liquid line solenoid valve for compressor 1.
Alarm Relay—This allows the user to activate the Liebert iCOM
output.
Warning Relay—This allows the user to activate the Liebert iCOM control’s free-cooling relay
output.
3P Actuator Open—This setting will energize the open circuit of the 3P type chilled or freecooling
control valve thus journeying it to the open state.
3P Actuator Close—This setting will energize the close circuit of the 3P type chilled or freecooling
control valve thus journeying it to the closed state.
Current Fanspeed (Read only)—Shows the analog output for the fan in automatic mode.
Fanspeed Manual Setpoint (Read only)—Drives the analog output for the fan in manual mode.
Condenser Control Mode—Defines the condenser control mode in manual or auto mode during
compressor manual mode.
Current MBV / CWV (AnaOut2) (Read only)—Shows the analog output for the MBV (motorized
ball valve) or analog CWV (chilled water valve) in automatic mode.
Manual MBV (AnaOut2)—Drives the analog output for the condenser valve (MBV) in manual
mode.
Manual CWV (AnaOut2)—Drives the analog output for the analog CWV (chilled water valve) in
manual mode.
Status HP1—This shows the status of the unit’s compressor 1 high pressure switch input.
Status LP1—This shows the status of the unit’s compressor 1 low pressure switch input.
Status LWD—This shows the status of the unit’s Leakage Water Detector.
Status Liquitech—This shows the status of the unit’s Liebert Liqui-tect
™
82
®
liquid detection setup.
Figure 73 Set alarms parameters screen - Page 1
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
PASSWORD (Actual Level 0)????
Tem/Hum EventsEnabled
High Supply Temperature80 °F
Low Supply Temperature46 °F
High Return Temperature104 °F
High Return Humidity60%
Low Return Humidity15 %
High CW Temperature°F
SET ALARMS (page 1 of 4)UNIT 01
to change parameter
for next/previous unit
to select parameter
to confirm
then
Temp/Hum Events—This parameter enables or disables all of the temperature and humidity
events.
Liebert iCOM® Control
High Supply Temperature—This parameter sets the high temperature threshold that will trigger
an alarm on the Liebert iCOM
®
local display and any monitoring system that may be connected.
Low Supply Temperature—This parameter sets the low temperature threshold that will trigger an
alarm on the Liebert iCOM local display and any monitoring system that may be connected.
High Return Temperature—This parameter sets the threshold temperature when a return high
temperature alarm will occur.
High Return Humidity—This parameter sets the threshold humidity when a return high humidity
alarm will occur.
Low Return Humidity—This parameter sets the threshold humidity when a return low humidity
alarm will occur.
High CW Temperature—This parameter sets the threshold chilled water when a return high
chilled water temperature alarm will occur.
Customer Input 1, 2, 3 & 4—These parameters select the device and operation of the customer
inputs. Each event reflects a different alarm and possible action to the unit. Refer to table 7 for a
description of selectable options.
Liebert iCOM® Control
Customer Input 1, 2, 3 & 4 active when—These parameters select whether the input is a normally
closed or normally closed input.
Figure 75 Set alarms parameters screen - Page 3
Liebert® CRV
This screen selects the operation of an active alarm. Each event can be enabled or disabled and can be
set to operate as an alarm, warning or message. The delay is the time the control waits before
reporting the event.
• Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
• Warning / Alarm: Annunciates the buzzer, triggers a monitoring event, shows the event in the
event viewer / front display and flashes the red LED on the display.
• Message: Shows the event in the event viewer and on the front display.
™
84
Figure 76 Set alarms parameters screen - Page 4
S234
S235
S236
S237
S238
S239
S240
S241
S242
S243
S244
S245
S246
PASSWORD (Actual Level 0)????
DELAYEN-DISTYPE
CALL SERVICE5ENABLEALM
HIGH TEMPERATURE5ENABLE ALM
This screen selects the operation of an active alarm. Each event can be enabled or disabled and can be
set to operate as an alarm, warning or message. The delay is the time the control waits before
reporting the event.
Liebert iCOM® Control
• Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
• Warning / Alarm: Annunciates the buzzer, triggers a monitoring event, shows the event in the
event viewer / front display and flashes the red LED on the display.
• Message: Shows the event in the event viewer and on the front display.
Ret urn T S ensor PTC or NTCNTC
Ret urn T Sens or+0°F
Calibrated Return T Sensor°F
Supply T Sensor PTC or NTCNTC
Supply T Sensor+1°F
Calibrated Supply T Sensor75°F
CW T Sensor°F
Calibrated CW T Sensor°F
SENSOR CALIBRATION/SETUP (page 2 of 4)UNIT 01
Return Temperature—This parameter adjusts the return temperature reading from the actual
sensor to compensate for any error of the sensor or to match other sensors in the room.
Liebert iCOM® Control
Calibrated Return Temperature—This parameter shows the adjusted temperature value of the
return sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
Return Humidity—This parameter adjusts the return humidity reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Humidity—This parameter shows the adjusted humidity value of the return
sensor. This value is the actual sensor reading (+ or -) the offset “Return Humidity”.
Digiscroll 1 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
Calibrated Digiscroll 1 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Return T Sensor PTC or NTC—This parameter selects the type of sensor being used for the return
to change parameter
for next/previous unit
to select parameter
to confirm
then
S623
S624
S625
S626
S627
S628
S629
S630
S631
S632
S633
PASSWORD Actual Level 0)????
Rac k Temperature Sens or 1+0°F77°F
Rac k Temperature Sens or 2+0°F78°F
Rac k Temperature Sens or 3+0°F77°F
Rac k Temperature Sens or 4+0°F77°F
Rac k Temperature Sens or 5+0°F78°F
Rac k Temperature Sensor 6+0°F °F
Rac k Temperature Sensor 7+0°F °F
Rac k Temperature Sensor 8+0°F °F
Rac k Temperature Sensor 9+0°F °F
Rac k Temperature Sensor 10+0°F °F
SENSOR CALIBRATION/SETUP (page 3 of 4)UNIT 01
air sensor.
Return T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
units sensor to other sensors.
Calibrated Return T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.
Supply T Sensor PTC or NTC—This parameter sets the type of sensor that is connected to the
unit. It is set at the factory as NTC and should be changed only by a certified Emerson technician.
Supply T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
unit’s sensor to other sensors.
Calibrated Supply T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.
CW T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
unit’s sensor to other sensors.
Calibrated CW T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.
This unit can be equipped with a total of 20 rack sensor readings or 10 2T temperature sensor
modules. This menu provides the ability to calibrated by entering a negative or positive offset. The
calibrated reading is displayed in the far right column. If a value is not shown in the far right column,
then the sensor is either not setup correctly or is not connected.
Rac k Temperature Sensor 1B°F77°F
Rac k Temperature Sensor 2B°F78°F
Rac k Temperature Sensor 3B°F77°F
Rac k Temperature Sensor 4B°F77°F
Rac k Temperature Sensor 5B°F78°F
Rac k Temperature Sensor 6B+0°F °F
Rac k Temperature Sensor 7B+0°F °F
Rac k Temperature Sensor 8B+0°F °F
Rac k Temperature Sensor 9B+0°F °F
Rac k Temperature Sensor 10B+ 0°F °F
SENSOR CALIBRATION/SETUP (page 4 of 4)UNIT 01
S801
S802
S803
S804
S805
S806
S807
S808
S809
S810
S811
PASSWORD(Actual Level 0)????
Number of Connected Units1
Teamw ork ModeNo
Teamw ork Mode 1 based on
Conf iguration SafeOKNo
Network SafeOKNo
SW VersionCRB 2.00.006.STD
SYSTEM / NETWORK SETUP (page 1 of 2)SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then
This unit can be equipped with a total of 20 rack sensor readings or 10 2T temperature sensor
modules. This menu provides the ability to calibrated by entering a negative or positive offset. The
calibrated reading is displayed in the far right column. If a value is not shown in the far right column,
then the sensor is either not setup correctly or is not connected.
Liebert iCOM® Control
Figure 81 System / network setup parameters—System - Page 1
Liebert® CRV
Number of Connected Units—This parameter sets the number of units that will be viewable from
the large display and will participate on the unit to unit network.
Teamwork Mode—This parameter selects which teamwork mode to use within a selected group.
Teamwork modes are described in section 4.0 of this manual.
Teamwork Mode 1 based on—
Configuration Safe—This parameter saves or loads configuration settings for the display that have
been modified from the factory defaults to an internal file that can be downloaded / uploaded using
the Liebert iCOM
®
Service Tool. Selecting “Save” will write the settings to the internal storage file
and selecting “Load” will write the settings from the internal storage file to the application software.
The internal file is updated every 12 hours automatically.
™
88
Network Safe—This parameter saves or loads network settings for the display that have been
S812
S813
S814
S815
S816
S817
S818
S819
S820
S821
S822
PASSWORD(Actual Level 0)????
IP Address10.203 .062 .150
Netmask255.255.255.192
Gateway10.203.062.129
MAC00:00:68:19:0B:58
U2U ProtocolGBP
U2U Address33
U2U Group13
Bootloader VariablesChangedNo
SYSTEM / NETWORK SETUP (page 2 of 2)SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM
®
Service Tool. Selecting “Save” will write the settings to the internal storage file and
selecting “Load” will write the settings from the internal storage file to the application software.
SW Version—This parameter contains the application software version loaded into the Liebert
iCOM display.
Figure 82 System / network setup parameters—large display only System - Page 2
Liebert iCOM® Control
IP Address—This parameter contains the network address of the display. This address must be
unique to every other device on the network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—This parameter is a unique identifier for each unit on the network. Display addresses
range from 33 to 64. Each display on the U2U network must have a different U2U address.
U2U Group—This parameter is used to create zones or groups within a U2U network. Once a group
number is selected the display will only see other devices with the same group number. The group
number can be changed to view other devices in different groups.
Bootloader Variables—This parameter indicates if there has been a change to the bootloader since
it was last loaded. This parameter should only be activated by an authorized service person.
Monitoring Address—This parameter sets the address used by the Liebert IntelliSlot
is set to 3 from the factory and should not be changed.
Monitoring Timeout/Handshake—This parameter can be used with a building management
system to verify communications has not been lost between the Liebert iCOM
If the amount of time specified in this parameter elapses before the BMS writes a new value then an
alarm will occur “BMS TIMEOUT” and the temperature setpoint will revert to the backup setpoint
and the fan speed “if equipped” will change to 100%. To disable this feature write a zero to this
parameter when it is active.
Unit Name—This parameter is a label to identify the unit from the local or remote display. This label
will show at the top right of every screen that has monitoring or configuration of that unit.
Configuration Safe—This parameter saves or loads configuration settings for the control board that
have been modified from the factory defaults to an internal file that can be downloaded / uploaded
using the Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage
file and selecting “Load” will write the settings from the internal storage file to the application
software. The internal file is updated every 12 hours automatically.
Network Safe—This parameter saves or loads network settings for the control board that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and
selecting “Load” will write the settings from the internal storage file to the application software.
SW Version—This parameter contains the application software version loaded onto the Liebert
iCOM control board.
®
cards. This
®
control and the BMS.
Liebert® CRV
™
90
Figure 84 System/Network setup parameters Unit - Page 2
Attention: any changes done on these parameters
must befollowed by a 'Save+Reboot' command.
Monitoring Protocol—This parameter selects the monitoring protocol. Velocity V3 is the factory
default which will provide communications to the Liebert IntelliSlot
the 77/78 terminals for communications to the Liebert SiteLink
units.
IP Address—This parameter contains the network address of the display. This address must be
unique to every other device on the network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—This parameter is a unique identifier for each unit on the network. Display addresses
range from 33 to 64. Each display on the U2U network must have a different U2U address.
U2U Group—This parameter is used to create zones or groups within a U2U network. Once a group
number is selected the display will only see other devices with the same group number. The group
number can be changed to view other devices in different groups.
Bootloader Variables—This parameter indicates if there has been a change to the boot loader since
it was last loaded. This parameter should only be activated by an authorized service person.
Static RAM—
®
housing. iGMNet will activate
®
(-E). Hironet is used only on HPM
91Liebert® CRV
™
Figure 85 Rack Overview, Page 1
Rack Overview (page 1 of 1)UNIT 01
All temperatures shown in °F
Cold Aisle
1
77
CC21
2
78
BB01
3
78
BB02
4
77
BB03
78
EC50
5
EC51
6
to change parameter
for next/previous unit
to select parameter
to confirm
then
S901
S902
S903
S904
S905
S906
S907
S908
S909
S910
S911
PASSWORD Actual Level 0)????
Remote Sens or Node 01Control
Remote Sens or Node 02Control
Remote Sens or Node 03Control
Remote Sens or Node 04Control
Remote Sens or Node 05Control
Remote Sens or Node 06Control
Remote Sens or Node 07Disable
Remote Sens or Node 08Disable
Remote Sens or Node 09Disable
Remote Sens or Node 10Disable
RACK SETUP (page 1 of 3)UNIT 01
This screen shows the rack label assigned to each rack and the temperature associated with the rack
sensor. This screen shows the relative distance between the Liebert CRV and each rack sensor.
Liebert iCOM® Control
Figure 86 Rack Setup, Page 1
Rack Sensors are automatically detected when connected and set to “Control.” A maximum of 10
Liebert® CRV
2T sensors can be connected; the control automatically detects the type.
Control—The Liebert CRV is using the sensor for temperature control.
Reference—The sensor value is shown, but not used for temperature control.
Disable—No sensor connected.
™
92
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.