Industrial Power for
Business-Critical Continuity
™
Chloride FP-40R
Rectier - battery charger
The Chloride FP-40R industrial rectier
is the result of engineering research
in product simplication to offer an
SCR-based standardized design with
improved reliability and adaptability
to industrial requirements.
The Chloride FP range is designed to
meet the most demanding schedules of
industrial projects.
Each Chloride FP product includes a wide
choice of ratings and a selection of indus-
trialized and pre-congured options to
allow the product to be quickly congured and delivered.
Benets
Improved reliability provided by a fully
controlled SCR bridge and a reduced quantity of components
Adaptability thanks to a selection of
industrialized options and an easy parameter
settings for quick on-site adjustments
Simplicity of the product design to improve
MTBF and to reduce MTTR
Key Features
Low Ripple Voltage to optimize battery life
Low inrush current < 8In not to oversize
mains power supply (3-phase)
Compact design with the capability to inte-
grate the battery in the charger cabinet
Human-Machine Interface (HMI) choice
to deliver appropriate information level to
the user
Ingress protection up to IP55 for harsh
environmental conditions
Compatibility with Nickel-Cadmium and
Lead-Acid batteries, open or gas-recombina-
tion types
Galvanic isolation between input and output
Digital control and monitoring
Wide choice of congurations and options
Flexibility for a wide scope of DC applications
The Chloride FP-40R is available from 25A to 100A in single-phase input
conguration, and up to 400A in three-phase input conguration. It offers a
wide range of output voltages, from 24 Vdc to 220 Vdc.
The Chloride FP-40R is suitable for use either as a battery charger, a rectier
or as a DC power supply. It features a microprocessor control which offers
exceptional stability and allows adaptability for different application require-
ments.
To further improve load availability and process reliability, the
Chloride FP-40R is able to operate in dual parallel conguration.
Applications
The Chloride FP-40R suits all DC applications
requiring large battery back-up of the following
industries:
Power Transmission and Distribution
Continuous process industries
Petrochemical and Chemical industries
Water & Wastewater industries
Industrial Power for
Business-Critical Continuity
™
Chloride FP-40R
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson, Business-Critical Continuity and
Emerson Network Power are trademarks of
Emerson Electric Co. or one of its afliated companies.
©2013 Emerson Electric Co.
FP40R-DSUK-Rev1-01/2013
AC Power
Connectivity
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Embedded Computing
Embedded Power
Industrial Power
Precision Cooling
Racks & Integrated Cabinets
Services
While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power IS S.A.S
30 avenue Montgoler - BP90 - 69684 Chassieu Cedex - France
T: +33 (0)4 78 40 13 56 F: +33(0)4 78 90 58 90
Industrial.sales.Chloride@Emerson.com
EmersonNetworkPower.com
Rectier - battery charger
Ratings - Output Current (A) vs Output Voltage (Vdc)
Ratings with single-phase input:
Ratings with three-phase input:
Technical Data
Input
Model FP-40R10 (Single-phase) FP-40R30 (Three-phase)
Input voltage (other voltage on request) 230 VAC ±10% 400 VAC ±10%
Inrush current < 15In < 8In
Power factor 0.7 (typical) 0.8 (typical)
Frequency range From 47 to 63 Hz
Output
Available ratings (see table above) 25 to 100 A 35 to 400 A
Nominal DC voltage 24, 48, 110, 125, 220 VDC
Static regulation 0.5 %
Ripple voltage (disconnected battery) < 0.7 %
Float voltage range From 0.70 Un to 1.47 Un
Charge voltage range From 0.73 Un to 1.60 Un
Equalization voltage range From 0.83 Un to 1.70 Un
Battery
Typ e Lead Acid or Nickel Cadmium, vented or recombination
Autonomy From few minutes to several hours, as required
General Data
Rectier efciency From 83 % to 94 % (according to model)
Operating temperature From 0 to 40 °C
Storage temperature From -20 °C to +70 °C (battery excluded)
Relative humidity <95 % non condensing at 20 °C
Operating altitude 1000 m (without system derating)
Cooling Fan-assisted
External ingress protection IP 20
Noise <60 dB
Input / output isolation 2500 VAC / 1 minute
Frame colour RAL 7035
Dimensions Varying according to ratings and options (consult us)
Options
Charger Paralleling diode
Battery Protection against battery reversed polarity
Mechanical External ingress protection IP21, 23, 40, 41, 43, 55
Load Distribution board (circuit breaker with or without contact)
Standards
Compliance IEC 61000-6-4 - IEC 61000-6-2 - IEC 61000-6-4
Conformity EMC Directive 2004/108/CE
24Vdc 48Vdc 110-125Vdc 220Vdc
- - 25 25
- 40 40
- 60 60
100 100 100
- - 35 35
- 65 65 65
100 100 100 100
160 160 160 160
220 220 220 220
300 300 300 300
400 400 400 400
Dropping diode
DC earth fault monitor
Ultra low ripple voltage <0.1%
Isolated communication interface, RS 485, Modbus
Front panel LEDs status annunciator
Battery Low Voltage Disconnection (LVD)
Batteries in charger cabinet (on shelves or drawers)
Temperature sensor for battery charge compensation
Space heater
Input / output terminal wiring
Internal ingress protection with open door IP20
Internal lighting
Lifting eyes
IEC 60146 - IEC 60439-1 - NFC 58-311
Low voltage Directive (LVD) 2006/95/CE