Emerson Fisher FIELDVUE DVC6000f Instruction Manual

DVC6000f Digital Valve Controllers
Fisher FIELDVUE DVC6000f Digital Valve Controllers
Instruction Manual
D103189X012
December 2009
This manual applies to:
Standard Control (SC) Fieldbus Control (FC) Fieldbus Logic (FL)
Introduction and Specifications
Installation
Basic Setup
Detailed Setup
Calibration
Viewing Device Variables and Diagnostics
Maintenance and Troubleshooting
Parts
Principle of Operation
1 2 3 4 5 6 7 8
A
Loop Schematics / Nameplates
Using PlantWeb Alerts
F
OUNDATION Fieldbus Communication
Device Description (DD) Installation
Operating with a DeltaV System
Glossary
Index
B C D E F
Glossary
G
Index
www.Fisher.com
Transducer Block
Field Communicator Menu Tree
Configure/Setup
Basic Setup Detailed Setup Calibration
Top Level
Configure/Setup Device Diagnostics Device Variables
Device Variables
All Block Modes AO Control Pre-Char AO Control Post-Char DO Control Input Characterization :Travel/Pressure State :PD Inside Status Protection Drive Signal Temperature Cycle Counter Travel Accumulator :Travel Count Pressures
Basic Setup
Device Setup Performance Tuner
Detailed Setup
Transducer Block Mode Protection Response Control Alerts Instrument Valve and Actuator MAI Channel Map Alert Handling
Alert Handling
PlantWeb Alert Simulate Simulate Active Alerts PlantWeb Alert Handling
Simulate Active Alarms
Failed Active Maint Active Advise Active
PlantWeb Alert Handling
PlantWeb Alerts Set PV Status Block Error Reporting
Calibration
Auto Calibration Manual Calibration Relay Travel Sensor Supply Pressure Pressure A Pressure B
Device Diagnostics
Active PlantWeb Alerts Alert Conditions Status Device Record Stroke Valve Trend
AO Control Pre-Char
AO Control Post-Char
DO Control
Pressures
MAI Channel Map
:MAI Channel 1 :MAI Channel 2 :MAI Channel 3 :MAI Channel 4 :MAI Channel 5 :MAI Channel 6 :MAI Channel 7 :MAI Channel 8
:Setpoint :Setpoint Status :Travel (DeChar)
:Travel Target :Travel :Travel Status
:Setpoint(D) :Travel(D)
:Supply :Pressure A :Pressure B :A Minus B
Response Control
Status
Self Test Status Block Error
Travel Tuning Pressure Tuning Travel Press Control Input Characterization Custom Characterization Table Outblock Selection
Travel Pressure Control
:Travel/Pressure State :Travel/Pressure Select Travel Deviation Pressure Fallback Travel Cutoff Hi Travel Cutoff Lo :Pressure Cutoff Open :Pressure Cutoff Closed :Pressure Range Hi :Pressure Range Lo
Instrument
Tag Description Pressure Units Temperature Units Travel Units Length Units Area Units Spring Rate Units :Relay Type :Zero Power Condition :Maximum Supply Pressure Calibration Person Calibration Location Calibration Date :Last Calibration Type
Valve and Actuator
Valve Trim Actuator Reference
Reference
:Trim Style 1 :Trim Style 2 :Stroke Time Open :Stroke Time Close
Self Test Status
Integrator Suspended Integrator Limited Lo Integrator Limited Hi Travel Sensor Span Error MLFB Error Travel Sensor Hi Error Travel Sensor Lo Error Pressure B Sensor Failure Pressure A Sensor Failure Supply Sensor Failure IOP Failure Drive Current Alert Simulate Jumper ON
Block Error
Block Configuration Error Simulate Active Lost Static Data Device Needs Maintenance Now Out of Service
Device Record
:Maximum Recorded Temperature :Maximum Recorded Temperature Time :Minimum Recorded Temperature :Minimum Recorded Temperature Time :Maximum Recorded Supply Pressure :Maximum Recorded Supply Pressure Time :Minimum Recorded Supply Pressure :Minimum Recorded Supply Pressure Time
Travel Tuning
:Travel Tuning Set Travel Proportional Gain Travel Velocity Gain :Travel MLFB Gain :Travel Integral Enable :Travel Integral Gain :Travel Integral Dead Zone :Travel Integral Limit Hi :Travel Integral Limit Lo Performance Tuner Stabilize / Optimize
Pressure Tuning
:Pressure Tuning Set :Pressure Proportional Gain :Pressure MLFB Gain :Pressure Integral Gain :Pressure Integral Dead Zone :Pressure Integral Limit Hi :Pressure Integral Limit Lo
Alerts
Elect Alerts Configuration Alerts Sensor Alerts Environment Alerts Travel Alerts Prox Alerts Travel History Alerts Performance Alerts PlantWeb Alert Enable PlantWeb Alert Reporting
Valve
Valve Manufacturer Valve Model Number Valve Serial Number Valve Style :Valve Size :Valve Class :Rated Travel :Actual Travel :Shaft Stem Diameter :Packing Type :Inlet Pressure :Outlet Pressure
Trim
:Seat Type :Leak Class :Port Diameter :Port Type :Flow Direction :Push Down To :Flow Tends To :Unbalanced Area
Actuator
Actuator Manufacturer Actuator Model Number :Actuator Style Actuator Serial Number :Actuator Size Actuator Fail Action :Feedback Connection :Travel Sensor Motion :Lever Style :Lever Arm Length :Effective Area :Air :Upper Bench Set :Lower Bench Set :Nominal Supply Pressure :Spring Rate
ALERTS MENU
ON FACING
PAGE
i
i
ALERTS MENU
ii
ALERTS MENU
Alerts
Elect Alerts Configuration Alerts Sensor Alerts Environment Alerts Travel Alerts Prox Alerts Travel History Alerts Performance Alerts PlantWeb Alert Enable PlantWeb Alert Reporting
PlantWeb Alert Enable
Failed Enable Maintenance Enable Advise Enable
PlantWeb Alert
Reporting
Failed Suppress Maintenance Suppress Advise Suppress
Performance Alerts
:PD Inside Status :PD Run Performance Critical Performance Reduced Performance Information
Elect Alerts
Drive Current Drive Signal Processor Impaired
Configuration Alerts
Output Block Timeout Blocks Set to Default Alert Key
Sensor Alerts
Travel Sensor Pressure Sensors Pressure Fallback Temperature Sensor
Environment Alerts
Supply Pressure Temperature Limit
Travel Alerts
:Travel Target :Travel Travel Deviation Travel Limit Travel Hi/Lo
Prox Alerts
:Travel Travel Open Travel Closed Proximity
Travel History Alerts
Cycle Counter Travel Accumulator
Performance Critical
Performance Critical Alert Performance Critical Alert Enable
Performance Reduced
Performance Reduced Alert Performance Reduced Alert Enable
Performance Information
Performance Information Alert Performance Information Alert Enable
Drive Current
Drive Current :Drive Current Alert :Drive Current Alert Enable :Drive Current Shutdown :Drive Current Manual Recovery :Drive Current Alert Point :Drive Current Alert Time
Output Block Timeout
:Output Block Timeout Alert :Output Block Timeout Alert Enable :Output Block Timeout Shutdown :Output Block Timeout Manual Recovery :Output Block Timeout
Supply Pressure
:Supply :Supply Pressure Hi Alert :Supply Pressure Hi Alert Enable Supply Pressure Hi Alert Point :Supply Pressure Lo Alert :Supply Pressure Lo Alert Enable :Supply Pressure Lo Alert Point
Temperature Limit
Temperature :Temperature Hi Alert :Temperature Hi Alert Enable Temperature Hi Alert Point :Temperature Lo Alert :Temperature Lo Alert Enable :Temperature Lo Alert Point
Travel Deviation
Travel Deviation :Travel Deviation Alert :Travel Deviation Alert Enable :Travel Deviation Alert Point :Travel Deviation Time :Travel Deviation Deadband
Travel Hi/Lo
:Travel Hi Alert :Travel Hi Alert Enable :Travel Hi Alert Point :Travel Hi Deadband :Travel Lo Alert :Travel Lo Alert Enable :Travel Lo Alert Point :Travel Lo Deadband
Travel Open
Travel Open Alert Travel Open Alert Enable :Travel Open Alert Point :Travel Open Deadband
Travel Closed
:Travel Closed Alert :Travel Closed Alert Enable :Travel Closed Alert Point :Travel Closed Deadband
Proximity
:Proximity Hi Hi Alert :Proximity Hi Hi Alert Enable :Proximity Hi Alert :Proximity Hi Alert Enable :Proximity Lo Alert :Proximity Lo Alert Enable :Proximity Lo Lo Alert :Proximity Lo Lo Alert Enable
Cycle Counter
Cycle Counter :Cycle Counter Alert :Cycle Counter Alert Enable :Cycle Counter Alert Point :Cycle Counter Deadband
Travel Accumulator
Travel Accumulator :Travel Accumulator Alert :Travel Accumulator Alert Enable :Travel Accumulator Alert Point :Travel Accumulator Deadband
Drive Signal
Drive Signal :Drive Signal Alert :Drive Signal Alert Enable
Processor Impaired
:Program Memory Alert :Program Memory Alert Enable :Program Memory Shutdown :Program Memory Manual Recovery :Static Memory Alert :Static Memory Alert Enable :Static Memory Shutdown :Static Memory Manual Recovery :Processor Alert :Processor Alert Enable :I/O Processor Alert :I/O Processor Alert Enable :I/O Processor Shutdown :I/O Processor Man Recovery
Blocks Set to Default
:Blocks Set to Defaults Alert :Blocks Set to Defaults Alert Enable
Travel Sensor
:Travel Sensor Alert :Travel Sensor Alert Enable :Travel Sensor Shutdown :Travel Sensor Manual Recovery
Pressure Sensors
:Pressure A Sensor Alert :Pressure A Sensor Alert Enable :Pressure A Sensor Shutdown :Pressure A Sensor Manual Recovery :Pressure B Sensor Alert :Pressure B Sensor Alert Enable :Supply Pressure Sensor Alert :Supply Pressure Sensor Alert Enable
Pressure Fallback
:Pressure Fallback Alert :Pressure Fallback Alert Enable
Temperature Sensor
:Temperature Sensor Alert :Temperature Sensor Alert Enable
Travel Limit
:Travel Hi Hi Alert :Travel Hi Hi Alert Enable :Travel Hi Hi Alert Point :Travel Hi Hi Deadband :Travel Lo Lo Alert :Travel Lo Lo Alert Enable :Travel Lo Lo Alert Point :Travel Lo Lo Deadband
ii
Transducer Block (TB) Menu Structure
PARAMETER LABEL MENU STRUCTURE
A Minus B TB > Device Variables > Pressures > A Minus B Actual Travel TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Actual Travel Actuator Fail Action TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Fail Action Actuator Manufacturer TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Manufacturer Actuator Model Number TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Model Number Actuator Serial Number TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Serial Number Actuator Size TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Size Actuator Style TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Style Advise Active TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Advise Active Advise Enable TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Advise Enable Advise Suppress TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Advise Suppress Air TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Air Alert Conditions TB > Device Diagnostics > Alert Conditions Alert Key TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Alert Key Area Units TB > Configure/Setup > Detailed Setup > Instrument > Area Units Block Configuration Error TB > Device Diagnostics > Status > Block Error > Block Error.Block Configuration Error
Blocks Set to Defaults Alert Blocks Set to Defaults Alert
Enable Calibration Date TB > Configure/Setup > Detailed Setup > Instrument > Calibration Date Calibration Location TB > Configure/Setup > Detailed Setup > Instrument > Calibration Location Calibration Person TB > Configure/Setup > Detailed Setup > Instrument > Calibration Person Custom Characterization Table TB > Configure/Setup > Detailed Setup > Response Control > Custom Characterization Table
Cycle Counter
Cycle Counter Alert
Cycle Counter Alert Enable Cycle Counter Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert Point
Cycle Counter Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Deadband Device Needs Maintenance
Now Drive Current TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current
Drive Current Alert Drive Current Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Elect Enable.Drive Current Alert Enable
Drive Current Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Point Drive Current Alert Time TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Time
Drive Current Manual Recovery Drive Current Shutdown TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Shutdown Trigger.Drive Current Shutdown
Drive Signal Drive Signal Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Elect Active.Drive Signal Alert
Drive Signal Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Elect Enable.Drive Signal Alert Enable Effective Area TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Effective Area Failed Active TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Failed Active Failed Enable TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Failed Enable Failed Suppress TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Failed Suppress Feedback Connection TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Feedback Connection Flow Direction TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Direction Flow Tends To TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Tends To I/O Processor Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Active.I/O Processor Alert I/O Processor Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Enable.I/O Processor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Elect Active.Block Set to Defaults Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Elect Enable.Block Set to Defaults Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter TB > Device Variables > Cycle Counter TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Travel History Active.Cycle Counter
Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Travel History Enable.Cycle Counter
Alert Enable
TB > Device Diagnostics > Status > Block Error > Block Error.Device Needs Maintenance Now
TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Drive Current Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Elect Active.Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Shutdown Recovery.Drive Current Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal TB > Device Variables > Drive Signal
Continued
iii
iii
Transducer Block (TB) Menu Structure (Continued)
PARAMETER LABEL MENU STRUCTURE
I/O Processor Man Recovery
I/O Processor Shutdown Inlet Pressure TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Inlet Pressure
Input Characterization Integrator Limited Hi TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Integrator Limited Hi
Integrator Limited Lo TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Integrator Limited Lo Integrator Suspended TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Integrator Suspended IOP Failure TB > Device Diagnostics > Status > Self Test Status > Self Test Status.IOP Failure Last Calibration Type TB > Configure/Setup > Detailed Setup > Instrument > Last Calibration Type Leak Class TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Leak Class Length Units TB > Configure/Setup > Detailed Setup > Instrument > Length Units Lever Arm Length TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Arm Length Lever Style TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Style Lost Static Data TB > Device Diagnostics > Status > Block Error > Block Error.Lost Static Data Lower Bench Set TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lower Bench Set MAI Channel 1 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 1 MAI Channel 2 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 2 MAI Channel 3 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 3 MAI Channel 4 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 4 MAI Channel 5 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 5 MAI Channel 6 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 6 MAI Channel 7 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 7 MAI Channel 8 TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 8 Maint Active TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Maint Active Maintenance Enable TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Maintenance Enable Maintenance Suppress TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Maintenance Suppress Maximum Recorded Supply
Pressure Maximum Recorded Supply
Pressure Time Maximum Recorded
Temperature Maximum Recorded
Temperature Time Maximum Supply Pressure TB > Configure/Setup > Detailed Setup > Instrument > Maximum Supply Pressure Minimum Recorded Supply
Pressure Minimum Recorded Supply
Pressure Time Minimum Recorded
Temperature Minimum Recorded
Temperature Time MLFB Error TB > Device Diagnostics > Status > Self Test Status > Self Test Status.MLFB Error Nominal Supply Pressure TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Nominal Supply Pressure Out of Service TB > Device Diagnostics > Status > Block Error > Block Error.Out of Service Outlet Pressure TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Outlet Pressure Outblock Selection TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection Output Block Timeout TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout
Output Block Timeout Alert Output Block Timeout Alert
Enable Output Block Timeout Manual
Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Recovery.I/O Processor Man Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Trigger.I/O Processor Shutdown
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization TB > Device Variables > Input Characterization
TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure
TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure Time
TB > Device Diagnostics > Device Record > Maximum Recorded Temperature
TB > Device Diagnostics > Device Record > Maximum Recorded Temperature Time
TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure
TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure Time
TB > Device Diagnostics > Device Record > Minimum Recorded Temperature
TB > Device Diagnostics > Device Record > Minimum Recorded Temperature Time
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Elect Active.Output Block Timeout Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Elect Active.Output Block Timeout Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Shutdown Recovery.Output Block Timeout Manual Recovery
Continued
iv
iv
Transducer Block (TB) Menu Structure (Continued)
PARAMETER LABEL MENU STRUCTURE
Output Block Timeout Shutdown
Packing Type TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Packing Type PD Inside Status TB > Configure/Setup > Device Variables > PD Inside Status PD Run TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > PD Run Performance Critical Alert TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Active.Performance Critical Alert Performance Critical Alert
Enable Performance Information Alert TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Active.Peformance Information Alert Performance Information Alert
Enable Performance Reduced Alert TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Active.Peformance Reduced Alert Performance Reduced Alert
Enable Performance Tuner PlantWeb Alert Simulate TB > Configure/Setup > Detailed Setup > Alert Handling > PlantWeb Alert Simulate
Port Diameter TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Diameter Port Type TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Type Pressure A TB > Device Variables > Pressures > Pressure A Pressure A Sensor Alert TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Active.Pressure A Sensor Alert
Pressure A Sensor Alert Enable Pressure A Sensor Failure TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Pressure A Sensor Error
Pressure A Sensor Manual Recovery
Pressure A Sensor Shutdown Pressure B TB > Device Variables > Pressures > Pressure B
Pressure B Sensor Alert TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Active.Pressure B Sensor Alert Pressure B Sensor Alert Enable Pressure B Sensor Failure TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Pressure B Sensor Error
Pressure Cutoff Closed TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Closed Pressure Cutoff Open TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Open Pressure Fallback Alert TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Sensor Active.Pressure Fallback Alert
Pressure Fallback Alert Enable Pressure Integral Dead Zone TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Dead Zone
Pressure Integral Gain TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Gain Pressure Integral Limit Hi TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Hi Pressure Integral Limit Lo TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Lo Pressure MLFB Gain TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure MLFB Gain Pressure Proportional Gain TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Proportional Gain Pressure Range Hi TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Hi Pressure Range Lo TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Lo Pressure Tuning Set TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Tuning Set Pressure Units TB > Configure/Setup > Detailed Setup > Instrument > Pressure Units Processor Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Active.Processor Alert Processor Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Enable.Processor Alert Enable Program Memory Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Active.Program Memory Alert
Program Memory Alert Enable Program Memory Manual
Recovery Program Memory Shutdown Protection TB > Device Variables > Protection
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Shutdown Recovery.Output Block Timeout Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Enable.Performance Critical Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Enable.Peformance Information Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Enable.Peformance Reduced Alert Enable TB > Configure/Setup > Basic Setup > Performance Tuner
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Performance Tuner
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Enable.Pressure A Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Shutdown Recovery.Pressure A Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Shutdown Trigger.Pressure A Sensor Shutdown
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Enable.Pressure B Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Sensor Enable.Pressure Fallback Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Enable.Program Memory Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Recovery.Program Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Trigger.Program Memory Shutdown
Continued
v
v
Transducer Block (TB) Menu Structure (Continued)
PARAMETER LABEL MENU STRUCTURE
Proximity Hi Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Active.Proximity Hi Alert Proximity Hi Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Enable.Proximity Hi Alert Enable Proximity Hi Hi Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Active.Proximity Hi Hi Alert Proximity Hi Hi Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Enable.Proximity Hi Hi Alert Enable Proximity Lo Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Active.Proximity Lo Alert Proximity Lo Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Enable.Proximity Lo Alert Enable Proximity Lo Lo Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Active.Proximity Lo Lo Alert Proximity Lo Lo Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Enable.Proximity Lo Lo Alert Enable Push Down To TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Push Down To Rated Travel TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Rated Travel Relay Type TB > Configure/Setup > Detailed Setup > Instrument > Relay Type Seat Type TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Seat Type Setpoint TB > Device Variables > AO Control-Pre-Char > Setpoint Setpoint Status TB > Device Variables > AO Control-Pre-Char > Setpoint Status Setpoint(D) TB > Device Variables > DO Control > Setpoint(D) Shaft Stem Diameter TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Shaft Stem Diameter Simulate Active TB > Device Diagnostics > Status > Block Error > Block Error.Simulate Active Simulate Jumper ON TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Simulate Jumper ON Spring Rate TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Spring Rate Spring Rate Units TB > Configure/Setup > Detailed Setup > Instrument > Spring Rate Units Static Memory Alert TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Active.Static Memory Alert Static Memory Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Elect Enable.Static Memory Alert Enable Static Memory Manual
Recovery Static Memory Shutdown Stroke Time Close TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Close
Stroke Time Open TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Open Supply
Supply Pressure Hi Alert
Supply Pressure Hi Alert Enable Supply Pressure Hi Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert Point Supply Pressure Lo Alert Supply Pressure Lo Alert
Enable Supply Pressure Lo Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert Point
Supply Pressure Sensor Alert Supply Pressure Sensor Alert
Enable Supply Sensor Failure TB > Device Diagnostics > Status > Self Test Status > Self Test Status.Supply Sensor Failure Tag Description TB > Configure/Setup > Detailed Setup > Instrument > Tag Description Temperature TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature
Temperature Hi Alert
Temperature Hi Alert Enable Temperature Hi Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert Point Temperature Lo Alert
Temperature Lo Alert Enable Temperature Lo Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert Point Temperature Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Recovery.Static Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Shutdown Trigger.Static Memory Shutdown
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply TB > Device Variables > Pressures > Supply TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Environment Active.Supply Pressure
Hi Alert TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Environment Enable.Supply Pressure
Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Environment Active.Supply Pressure Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Environment Enable.Supply Pressure Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Active. Supply Pressure Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Sensor Enable. Supply Pressure Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Environment Active.Temperature Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Environment Enable.Temperature Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Environment Active.Temperature Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Environment Enable.Temperature Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensor > Sensor Active. Temperature Sensor Alert
Continued
vi
vi
Transducer Block (TB) Menu Structure (Continued)
PARAMETER LABEL MENU STRUCTURE
Temperature Sensor Alert Enable
Temperature Units TB > Configure/Setup > Detailed Setup > Instrument > Temperature Units Travel TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Travel (DeChar) TB > Device Variables > AO Control-Pre-Char > Travel(DeChar)
Travel Accumulator
Travel Accumulator Alert Travel Accumulator Alert
Enable Travel Accumulator Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert Point Travel Accumulator Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > T ravel Accumulator > Travel Accumulator Deadband Travel Closed Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Proximity Active.Travel Closed Alert Travel Closed Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Proximity Enabled.Travel Closed Alert Enable Travel Closed Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert Point Travel Closed Deadband TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Deadband Travel Count TB > Device Variables > Travel Count Travel Cutoff Hi TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Hi Travel Cutoff Lo TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Lo Travel Deviation TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Travel Deviation Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Active.Travel Deviation Alert Travel Deviation Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Enable.Travel Deviation Alert Enable Travel Deviation Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert Point Travel Deviation Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Deadband Travel Deviation Pressure
Fallback Travel Deviation Time TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Time Travel Hi Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Active.Travel Hi Alert Travel Hi Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Enable.Travel Hi Alert Enable Travel Hi Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert Point Travel Hi Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Deadband Travel Hi Hi Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Active.Travel Hi Hi Alert Travel Hi Hi Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Enable.Travel Hi Hi Alert Enable Travel Hi Hi Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert Point Travel Hi Hi Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Deadband Travel Integral Dead Zone TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Dead Zone Travel Integral Enable TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Enable Travel Integral Gain TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Gain Travel Integral Limit Hi TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Hi Travel Integral Limit Lo TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Lo Travel Lo Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Active.Travel Lo Alert Travel Lo Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Enable.Travel Lo Alert Enable Travel Lo Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert Point Travel Lo Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Deadband Travel Lo Lo Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Active.Travel Lo Lo Alert Travel Lo Lo Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Enable.Travel Lo Lo Alert Enable Travel Lo Lo Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert Point Travel Lo Lo Deadband TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Deadband Travel MLFB Gain TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel MLFB Gain Travel Open Alert TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Proximity Active.Travel Open Alert Travel Open Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Proximity Enabled.Travel Open Alert Enable Travel Open Alert Point TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert Point Travel Open Deadband TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Deadband Travel Proportional Gain TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Proportional Gain Travel Sensor Alert TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Sensor Active.Travel Sensor Alert Travel Sensor Alert Enable TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Sensor Enable.Travel Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensors > Sensor Enable. Temperature Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator TB > Device Variables > Travel Accumulator TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel History Active.Travel
Accumulator Alert TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel History Enable.Travel
Accumulator Alert Enable
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Deviation Pressure Fallback
Continued
vii
vii
Transducer Block (TB) Menu Structure (Continued)
PARAMETER LABEL MENU STRUCTURE
Travel Sensor Hi Error TB > Device Diagnostics > Status > Self T est Status > Self Test Status.Travel Sensor Hi Error Travel Sensor Lo Error TB > Device Diagnostics > Status > Self Test Status > Self Test Status.T ravel Sensor Lo Error Travel Sensor Manual
Recovery Travel Sensor Motion TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Travel Sensor Motion Travel Sensor Shutdown TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Shutdown Trigger.Travel Sensor Shutdown Travel Sensor Span Error TB > Device Diagnostics > Status > Self Test Status > Self Test Status.T ravel Sensor Span Error Travel Status TB > Device Variables > AO Control-Post-Char > T ravel Status Travel Tuning Set TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Tuning Set Travel Units TB > Configure/Setup > Detailed Setup > Instrument > Travel Units Travel Velocity Gain TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Velocity Gain Travel(D) TB > Device Variables > DO Control > Travel(D) Travel/Pressure Select TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure Select
Travel/Pressure State Trend TB > Device Diagnostics > Trend
Trim Style 1 TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 1 Trim Style 2 TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 2 Unbalanced Area TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Unbalanced Area Upper Bench Set TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Upper Bench Set Valve Class TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Class Valve Manufacturer TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Manufacturer Valve Model Number TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > V alve Model Number Valve Serial Number TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > V alve Serial Number Valve Size TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Size Valve Style TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Style Zero Power Condition TB > Configure/Setup > Detailed Setup > Instrument > Zero Power Condition
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Shutdown Recovery.Travel Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure State TB > Device Variables > Travel/Pressure State
viii
viii
Top Level
Configure/Setup Device Diagnostics Device Variables
Configure/Setup
Resource Block Mode Write Lock Comm Timeout Options Alarm Handling Identification Version
Version
Device Revision Firmware Revision Standby Firmware Revision Hardware Rev ITK Version
Device Diagnostics
Resource Block Error Device State Write Lock Block Alarm Maintenance
Maintenance
Restart Actions Fault State Set Fault State Clear Fault State
Device Variables
Instrument Options DD Information
Resource Block
Field Communicator Menu Tree
Write Lock
Write Lock Write Priority
Comm Timeout
Shed Remote Cascade Shed Remote Out
Options
Diagnostic Options Function Block Options Miscellaneous Options Features Available Features Selected
Alarm Handling
Alert Key Confirm Time Limit Notify Maximum Notify Block Alm Disabled Block Alarm Auto Acknowledge Disc Alm Disabled Discrete Alarm Auto Acknowlege
Resource Block Error
Other Block Configuration Error Simulate Active Device Needs Maintenance Soon Memory Failure Lost Static Data Lost NV Data Device Needs Maintenance Now Power Up Out of Service
Write Lock
Write Alarm Alarm State Write Lock
Block Alarm
Block Alarm Alarm State Block Alarm Unacknowledged
Instrument
Identification Version
Options
Diagnostics Options Function Block Options Miscellaneous Options Features Available
Function Block Options
AO DO AI DI PID IS OS MAI
Function Block Options
AO DO AI DI PID IS OS MAI
Miscellaneous Options
Firmware Download Travel Control Capable Pressure Control Capable Pressure Fallback Capable
Features Available
Reports Fault State Soft W Lock Multi-bit Alarm (Bit-Alarm) Support
Features Selected
Reports Fault State Soft W Lock Multi-bit Alarm (Bit-Alarm) Support
Identification
Device ID Electronics Serial Number Factory Serial Number Field Serial Number Tag Description Strategy Manufacturer Device Type Diagnostics Options
Identification
Device ID Electronics Serial Number Factory Serial Number Field Serial Number Tag Description Strategy Manufacturer Device Type
Version
Device Revision Firwmare Revision Standby Firmware Revision Hardware Rev ITK Version
Miscellaneous Options
Firmware Download Travel Control Capable Pressure Control Capable Pressure Fallback Capable
Features Available
Reports Fault State Soft W Lock Multi-bit Alarm (Bit-Alarm) Support
ix
ix
Resource Block (RB) Menu Structure
PARAMETER LABEL MENU STRUCTURE
Alert Key RB > Configure/Setup > Alarm Handling > Alert Key Block Alarm: Alarm State RB > Device Diagnostics > Block Alarm > Block Alarm: Alarm State Block Alarm: Unacknowledged RB > Device Diagnostics > Block Alarm > Block Alarm: Unacknowledge Block Alarm Disabled RB > Configure/Setup > Alarm Handling > Alarm Summary:Disabled.Block Alarm Disabled Block Alarm Automatically
Acknowledge Confirm Time RB > Configure/Setup > Alarm Handling > Confirm Time DD Information RB > Device Variables > DD information Device ID RB > Configure/Setup > Identification > Device ID or RB > Device Variables > Instrument > Identification > Device ID Device Revision RB > Configure/Setup > Version > Device Revision or RB > Device Variables > Instrument > Version > Device Revision
Device State Device Type RB > Configure/Setup > Identification > Device Type or RB > Device Variables > Instrument > Identification > Device Type
Diagnostics Options RB > Configure/Setup > Options > Diagnostics Options Discrete Alarm Disabled RB > Configure/Setup > Alarm Handling > Alarm Summary:Disabled.Discrete Alarm Disabled Discrete Alarm Automatically
Acknowledge Electronics Serial Number
Factory Serial Number Fault State RB > Device Diagnostics > Maintenance > Fault State
Features Available RB > Configure/Setup > Options > Features Available or RB > Device Variables > Options > Features Available Features Selected RB > Configure/Setup >Options > Features Selected Field Serial Number RB > Configure/Setup > Identification > Field S/N or RB > Device Variables > Instrument > Identification > Field Serial Number Firmware Revision RB > Configure/Setup > Version > Firmware Revision or RB > Device Variables > Instrument > Version > Firmware Revision Function Block Options RB > Configure/Setup > Options > Function Block Options or RB > Device Variables > Options > Function Block Options Hardware Revision RB > Configure/Setup > Version > Hardware Revision or RB > Device Variables > Instrument > Version > Hardware Revision ITK Version RB > Configure/Setup > Version > ITK Version or RB > Device Variables > Instrument > Version > ITK Version Limit Notify RB > Configure/Setup > Alarm Handling > Limit Notify Manufacturer RB > Configure/Setup > Identification > Manufacturer or RB > Device Variables > Instrument > Identification > Manufacturer Maximum Notify RB > Configure/Setup > Alarm Handling > Maximum Notify Miscellaneous Options RB > Configure/Setup > Options >Miscellaneous Options or RB > Device Variables > Options >Miscellaneous Options Resource Block Error RB > Device Diagnostics > Resource Block Error Shed Remote Cascade RB > Configure/Setup > Communication Time Out > Shed Remote Cascade Shed Remote Out RB > Configure/Setup > Communication Time Out > Shed Remote Out
Standby Firmware Revision Strategy RB > Configure/Setup > Identification > Strategy or RB > Device Variables > Instrument > Identification > Strategy
Tag Description RB > Configure/Setup > Identification > Tag Description or RB > Device Variables > Instrument > Identification > Tag Description Write Alarm: Alarm State RB > Device Diagnostics > Write Lock > Write Alarm: Alarm State Write Lock RB > Configure/Setup > Write Lock > Write Lock or RB > Device Diagnostics > Write Lock > Write Lock Write Priority RB > Configure/Setup > Write Lock > Write Priority
RB > Configure/Setup > Alarm Handling > Acknowledge Option.Block Alarm Automatically Acknowledge
RB > Display > Resource Status > Device State RB > Device Diagnostics > Device State
RB > Configure/Setup > Alarm Handling > Acknowledge Option.Discrete Alarm Automatically Acknowledge RB > Configure/Setup > Identification > Elect S/N or RB > Device Variables > Instrument > Identification > Electronics Serial
Number RB > Configure/Setup > Identification > Factory S/N or RB > Device Variables > Instrument > Identification > Factory Serial
Number
RB > Configure/Setup > Version > Standby Software Revision or RB > Device Variables > Instrument > Version > Standby Software Revision
x
x
THE FIELDVUE DVC6000f DIGITAL VALVE CONTROLLER IS A CORE COMPONENT OF THE PLANTWEB DIGITAL PLANT ARCHITECTURE. THE DIGITAL VALVE CONTROLLER POWERS PLANTWEB BY CAPTURING AND DELIVERING VALVE DIAGNOSTIC DATA. COUPLED WITH VALVELINK SOFTWARE, THE DVC6000f PROVIDES USERS WITH AN ACCURATE PICTURE OF VALVE PERFORMANCE, INCLUDING ACTUAL STEM POSITION, INSTRUMENT INPUT SIGNAL AND PNEUMATIC PRESSURE TO THE ACTUATOR. USING THIS INFORMATION, THE DIGITAL VALVE CONTROLLER DIAGNOSES NOT ONLY ITSELF, BUT ALSO THE VALVE AND ACTUATOR TO WHICH IT IS MOUNTED.
FIELDVUE DVC6000f Digital Valve Controller
xi
xi
1-1
Introduction and Specifications

Section 1 Introduction and Specifications

Scope of Manual 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instrument Description 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using this Manual 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Related Information 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fieldbus Installation and Wiring Guidelines 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Related Documents 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
December 2009
1-1
DVC6000f Digital Valve Controllers

Scope of Manual

This instruction manual includes specifications, installation, operating, and maintenance information for FIELDVUE DVC6000f digital valve controllers.
This manual describes device setup using the 475 or 375 Field Communicator. For information on using
1
Fisher ValveLink software with the instrument, refer to the appropriate user guide or help.
Do not install, operate, or maintain a DVC6000f digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson Process Management sales office before proceeding.
W9132-1
Figure 1-1. FIELDVUE DVC6010f Digital Valve
Controller Mounted on Fisher 585C Piston Actuator
Note
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assume responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end user.

Instrument Description

DVC6000f digital valve controllers for FOUNDATION fieldbus are interoperable, communicating, microprocessor-based, digital-to-pneumatic instruments. In addition to the primary function of converting a digital input signal to a pneumatic output, the DVC6000f, using FOUNDATION fieldbus communications protocol, gives easy access to information critical to process operation as well as process control. This can be done using a DeltaV console, another FOUNDATION fieldbus system console, or with ValveLink software.
DVC6000f digital valve controllers can be mounted on single or double-acting sliding-stem actuators, as shown in figure 1-1, or on rotary actuators, as shown in figure 1-2. The DVC6000f mounts on most Fisher and other manufacturers’ rotary and sliding-stem actuators.
DVC6000f digital valve controllers are available with several selections of control and diagnostic capability. Control selections include:
Standard Control (SC)— Digital valve controllers with Standard Control have the AO, PID, ISEL, OS, AI, MAI, DO, and four DI function blocks in addition to the resource and transducer blocks.
Fieldbus Control (FC)—Digital valve controllers with Fieldbus Control have the AO function block in
addition to the resource and transducer blocks.
Fieldbus Logic (FL)—Digital valve controllers with Fieldbus Logic have the DO, and four DI function blocks, in addition to the resource and transducer block.
The diagnostic capabilities include:
Performance Diagnostics (PD)
Advanced Diagnostics (AD)
Fieldbus Diagnostics (FD)
Performance and Advanced Diagnostics are available with ValveLink software. They provide visibility to instrument alerts. Fieldbus Diagnostics can be viewed with any host system.

Instrument Blocks

The digital valve controller is a block-based device. For detailed information on the blocks within the digital
1-2
December 2009
Introduction and Specifications
Analog Output (AO) Function Block—The analog output function block accepts the output from another function block (such as a PID block) and transfers it as an actuator control signal to the transducer block. If the DO block is selected, the AO block is not functional.
W8115-FF
Figure 1-2. Fisher Rotary Control Valve with FIELDVUE
DVC6020f Digital Valve Controller
valve controller, see the Detailed Setup section of this manual.
All DVC6000f digital valve controllers include the resource and transducer block:
Resource Block—The resource block contains the hardware specific characteristics associated with a device; it has no input or output parameters. The resource block monitors and controls the general operation of other blocks within the device. For example, when the mode of the resource block is Out of Service, it impacts all function blocks.
Transducer Block—The transducer block connects the analog output function block to the I/P converter, relay, and travel sensor hardware within the digital valve controller.
Proportional-Integral-Derivative (PID)
Function Block—The PID function block performs
proportional-plus-integral-plus-derivative control.
Input Selector (ISEL) Function block—The input selector function block selects from up to four inputs and may provide the selected signal as input to the PID block. The input selection can be configured to select the first good input signal; a maximum, minimum or average value; or a hot spare.
Output Splitter (OS) Function Block—The output splitter function block accepts the output from another function block (such as a PID block) and creates two outputs that are scaled or split, according to the user configuration. This block is typically used for split ranging of two control valves.
Analog Input (AI) Function Block—The analog input function block monitors the signal from a DVC6000f sensor or internal measurement and provides it to another block.
Multiple Analog Input (MAI) Function Block—The Multiple Analog Input (MAI) function block
has the ability to process up to eight DVC6000f measurements and make them available to other function blocks.
Discrete Output (DO) Function Block—The discrete output function block processes a discrete set point and sends it to a specified output channel, which can be transferred to the transducer block for actuator control. In the digital valve controller, the discrete output block provides both normal open/closed control and the ability to position the valve in 5% increments for course throttling applications. If the AO block is selected, the DO block is not functional.
1

Function Blocks

In addition to the resource and transducer block, the digital valve controller may contain the following function blocks. For additional information on function blocks, refer to Appendix D, FOUNDATION fieldbus Communication.
December 2009
Discrete Input (DI) Function Block—The discrete input function block processes a single discrete input from a DVC6000f and makes it available to other function blocks. In the digital valve controller, the discrete input function block can provide limit switch functionality and valve position proximity detection.
1-3
DVC6000f Digital Valve Controllers

Using This Manual

Procedures that require the use of the Field Communicator have the Field Communicator symbol in the heading.
1
Also included is the path required to accomplish various tasks; the sequence of steps through the Field Communicator menus. For example, the path to Resource Block Mode is RB > Configure/Setup > Setup > Resource Block Mode.
An overview of the Field Communicator resource block and transducer block menu structures are shown at the beginning of this manual. Menu structures for the function blocks are included with each function block section in Detailed Setup / Blocks.
Throughout this document, parameters are typically referred to by their common name or label, followed by the parameter name and index number; for example, Write Priority (WRITE_PRI [39]). However, not all interface systems support the use of the parameter label and instead use only the Parameter Name, followed by the index number, when referring to the block parameters.

Related Documents

Other documents containing information related to DVC6000f digital valve controllers include:
Bulletin 62.1:DVC6000f—Fisher FIELDVUE
DVC6000f Digital Valve Controllers (D103199X012)
Bulletin 62.1:DVC6000(S1)—Fisher FIELDVUE DVC6000, DVC6000 SIS, and DVC6000f Digital Valve Controller Dimensions (D103308X012)
Bulletin 62.1:DVC6000f(S1)—Fisher FIELDVUE DVC6000f Digital Valve Controller Custom Configuration (D103419X012)
Fisher FIELDVUE DVC6000f Digital Valve Controller Quick Start Guide (D103202X012)
ValveLink Software Help or Documentation
Field Communicator User’s Manual
DeltaV Online Help or documentation

Specifications

Specifications for DVC6000f digital valve controllers are shown in table 1-1.

Related Information

Fieldbus Installation and Wiring Guidelines

This manual describes how to connect the fieldbus to the digital valve controller. For a technical description, planning, and installation information for a FOUNDATION fieldbus, refer to the FOUNDATION fieldbus Technical Overview available from the Fieldbus Foundation and Fieldbus Installations in a DeltaV System available from your Emerson Process Management sales office.
All documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com.

Educational Services

For information on available courses for DVC6000f digital valve controllers, as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 e-mail: education@emersonprocess.com
1-4
December 2009
Introduction and Specifications
Table 1-1. Specifications
Available Configurations
DVC6010f: Sliding-stem applications DVC6020f: Rotary and long-stroke sliding-stem applications [over 102 mm (4 inch) travel] DVC6030f: Quarter-turn rotary applications
Remote-Mounted Instrument
DVC6005f: Base unit for 2 inch pipestand or wall
mounting DVC6015: Feedback unit for sliding-stem applications DVC6025: Feedback unit for rotary or long-stroke sliding-stem applications DVC6035: Feedback unit for quarter-turn rotary applications
DVC6000f digital valve controllers can be mounted on Fisher and other manufacturers rotary and sliding-stem actuators.
Function Block Suites
Standard Control (throttling control) Includes AO, PID, ISEL, OS, AI, MAI, DO, and four DI function blocks Fieldbus Control (throttling control) Contains the AO function block Fieldbus Logic [discrete on/off] Includes DO, and four DI function blocks
Block Execution Times
AO Block: 15 ms AI Block: 15 ms PID Block: 20 ms MAI BLock: 35 ms ISEL Block: 20 ms DO Block: 15 ms OS Block: 20 ms DI Block: 15 ms
(1)
Fieldbus Device Capabilities
Backup Link Master capable
Device Description Compatibility
Firmware Revision DD Compatibility
2.0 2 and 3
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure.
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single direct, and Single reverse
Supply Pressure
Recommended: 0.3 bar (5 psi) higher than
maximum actuator requirements, up to maximum
supply pressure
Maximum: 10 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Medium: Air or Natural Gas
Air Quality: Supply pressure must be clean, dry air
that meets the requirements of ISA Standard
7.0.01. A maximum 40 micrometer particle size in
the air system is acceptable. Further filtration down
to 5 micrometer particle size is recommended.
Lubricant content is not to exceed 1 ppm weight
(w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized
Natural Gas: Natural gas must be clean, dry,
oil-free, and noncorrosive. H2S content should not
exceed 20 ppm.
(2)
(3)
1
Electrical Input
Voltage Level: 9 to 32 volts Maximum Current: 19 mA Reverse Polarity Protection: Unit is not polarity
sensitive Termination: Bus must be properly terminated per ISA SP50 guidelines
Digital Communication Protocol
FOUNDATION fieldbus registered device Physical Layer Type(s): 121—Lowpower signaling, buspowered, Entity
Model I.S. 511—Lowpower signaling, buspowered, FISCO
I.S.
December 2009
Steady-State Air Consumption
Maximum Output Capacity
continued
(4,5)
Standard Relay: At 1.4 bar (20 psig) supply
pressure: Less than 0.38 normal m3/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
normal m3/hr (49 scfh)
Low Bleed Relay: At 1.4 bar (20 psig) supply
pressure: Average value 0.056 normal m3/hr
(2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
0.184 normal m3/hr (6.9 scfh)
(4,5)
At 1.4 bar (20 psig) supply pressure:
10.0 normal m3/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure:
29.5 normal m3/hr (1100 scfh)
1-5
DVC6000f Digital Valve Controllers
Table 1-1. Specifications (continued)
Independent Linearity
±0.5% of output span
Electromagnetic Compatibility
1
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of the
EN 61326-1 standard. Performance is shown in table 1-2 below
Emissions—Class A
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of immunity to lightning is specified as Surge immunity in table 1-2. For additional surge protection commercially available transient protection devices can be used.
Vibration Testing Method
Tested per ANSI/ISA-75.13.01 Section 5.3.5. A resonant frequency search is performed on all three axes. The instrument is subjected to the ISA specified 1/2 hour endurance test at each major resonance, plus an additional two million cycles.
Operating Ambient Temperature Limits
40 to 80C (40 to 176F) for most approved valve-mounted instruments.
60 to 125C (76 to 257F) for remote-mounted feedback unit.
52 to 80C (62 to 176F) for valve-mounted instruments utilizing the Extreme Temperature option (fluorosilicone elastomers)
Electrical Classification
CSA— Intrinsically Safe, and FISCO, Explosion
proof, Division 2, Dust-Ignition proof FM— Intrinsically Safe and FISCO, Explosion
proof, Non-incendive, Dust-Ignition proof ATEX—Intrinsically Safe and FISCO, Flameproof,
Type n IECEx— Intrinsically Safe and FISCO, Flameproof,
Type n NEPSI—Intrinsically Safe, Flameproof Refer to Special Instructions for “Safe Use” and
Installation in Hazardous Locations in section 2, tables 1-3, 1-4, 1-5, 1-6, and 1-7 and Appendix B for specific approval information.
(6)
(2)
Other Classifications/Certifications
Connections
Stem/Shaft Travel
Mounting
Weight
continued
Electrical Housing:
CSA—Type 4X, IP66
FM—NEMA 4X
ATEX—IP66
IECEx—NEMA 4X, IP66
NEPSI—IP66
TIIS—Japan
GOST-R—Russian GOST-R
FSETAN—Russian - Federal Service of
Technological, Ecological and Nuclear Inspectorate
INMETRO—Brazil
Contact your Emerson Process Management sales
office for classification/certification specific
information
Supply Pressure: 1/4 NPT internal and integral
pad for mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8-inch metal, recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal, M20 adapter optional
Linear Actuators with rated travel between
6.35 mm (0.25 inch) and 606 mm (23.875 inches)
Rotary Actuators with rated travel between 50
degrees and 180 degrees
(7)
Designed for direct actuator mounting or remote
pipestand or wall mounting. Mounting the
instrument vertically, with the vent at the bottom of
the assembly, or horizontally, with the vent pointing
down, is recommended to allow drainage of
moisture that may be introduced via the instrument
air supply.
Valve-Mounted Instruments
Aluminum: 3.5 Kg (7.7 lbs) Stainless Steel: 7.7 Kg (17 lbs)
Remote-Mounted Instruments
DVC6005f Base Unit: 4.1 Kg (9 lbs) DVC6015 Feedback Unit: 1.3 Kg (2.9 lbs) DVC6025 Feedback Unit: 1.4 Kg (3.1 lbs) DVC6035 Feedback Unit: 0.9 Kg (2.0 lbs)
1-6
December 2009
Introduction and Specifications
Table 1-1. Specifications (continued)
Options
Supply and output pressure gauges or Tire
valves,
Integral mounted filter regulator,
Stainless steel housing, module base and
terminal box (valve-mounted instruments only),
Low bleed relay, Inline 10 micron air filter
Declaration of SEP
Fisher Controls International LLC declares this
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 Process Instrument Terminology.
1. 3-conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 15 meters (50 feet) maximum without performance degradation.
2. The pressure/temperature limits in this manual and any applicable code or standard should not be exceeded.
3. Gas Certified DVC6000f digital valve controllers are FM and CSA Single Seal approved for use with natural gas as the supply medium.
4. Normal m3/hour Normal cubic meters per hour at 0C and 1.01325 bar, absolute. Scfh Standard cubic feet per hour at 60F and 14.7 psia.
5. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
6. Typical value. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also, not applicable to DVC6020f digital valve controllers in long-stroke applications. 7 . Do not use the DVC6010fS or DVC6020fS in high vibration service where the mounting bracket uses standoffs (spacers) to mount to the actuator. Due to NAMUR mounting limitations, do not use the DVC6030fS in high vibration service.
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 /
23 / EC. It was designed and manufactured in
accordance with Sound Engineering Practice (SEP)
and cannot bear the CE marking related to PED
compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
Table 1-2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria
Electrostatic discharge (ESD) IEC 61000-4-2
Enclosure
I/O signal/control
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Radiated EM field IEC 61000-4-3
Rated power frequency magnetic field
Burst IEC 61000-4-4 Surge IEC 61000-4-5 Conducted RF IEC 61000-4-6
IEC 61000-4-8
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
60 A/m at 50 Hz 1 kV
1 kV (line to ground only, each) 150 kHz to 80 MHz at 3 Vrms
A
A
A A
B A
1
(1)
December 2009
1-7
DVC6000f Digital Valve Controllers
Table 1-3. Hazardous Area Classifications—CSA (Canada)
Certification
Body
1
CSA
Type Certification Obtained Entity Rating Temperature Code Enclosure Rating
FIELDBUS
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
FIELDBUS
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 mW
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 mW
Vmax = 30 VDC Imax = 17.5 mA Ci = 0 uF Li = 0 mH Pi = 105 mW
DVC60x0F DVC60x0FS (x = 1,2,3)
DVC6005F
DVC60x5 (x = 1,2,3)
Ex ia—Intrinsically Safe & FISCO Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42818 Natural Gas Approved
Explosion Proof Class I Division 1 GP B,C,D T6 Natural Gas Approved
Class I Division 2 GP A,B,C,D T6 Class II Division 1,2 GP E,F,G T6 Class III Natural Gas Approved
Ex ia—Intrinsically Safe & FISCO Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42818 Natural Gas Approved
Explosion Proof Class I Division 1 GP B,C,D T6 Natural Gas Approved
Class I Division 2 GP A,B,C,D T6 Class II Division 1,2 GP E,F,G T6 Class III Natural Gas Approved
Ex ia— Intrinsically Safe Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42818
Explosion Proof Class I Division 1 GP B,C,D
Class I Division 2 GP A,B,C,D Class II Division 1,2 GP E,F,G
T4(Tamb v 80C)
FISCO
− − − T6(Tamb v 80C)
− − − T6(Tamb v 80C)
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mW
FISCO
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Pi = 105 mW
− − − T6(Tamb v 80C)
− − − T6(Tamb v 80C)
− − −
− − −
T5(Tamb v 77C) T6(Tamb v 62C)
T4(Tamb v 80C) T5(Tamb v 77C) T6(Tamb v 62C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Single Seal Device
Type 4X, IP66
Type 4X, IP66
Type 4X, IP66
1-8
December 2009
Certification
Body
FM
Introduction and Specifications
Table 1-4. Hazardous Area Classifications—FM (United States)
Type Certification Obtained Entity Rating Temperature Code Enclosure Rating
FIELDBUS
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Vmax = 30 VDC Imax = 17.5 mA Ci = 0 nF Li = 0 mH Pi = 105 mW
T4(Tamb v 80C)
FISCO
− − − T6(Tamb v 80C) NEMA 4X
− − − T6(Tamb v 80C) NEMA 4X
FIELDBUS
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mH
FISCO
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mW
− − − T6(Tamb v 80C) NEMA 4X
− − − T6(Tamb v 80C) NEMA 4X
− − −
− − −
T5(Tamb v 77C) T6(Tamb v 62C)
T4(Tamb v 80C) T5(Tamb v 77C) T6(Tamb v 62C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
NEMA 4X
NEMA 4X
NEMA 4X
NEMA 4X
NEMA 4X
DVC60x0F DVC60x0FS (x = 1,2,3)
DVC6005F
DVC60x5 (x = 1,2,3)
Intrinsically Safe & FISCO Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42819 Natural Gas Approved
Explosion Proof Class I, Division 1 GP B,C,D T6 Natural Gas Approved
Class I Division 2 GP A,B,C,D T6 Class II Division 1 GP E,F,G T6 Class II Division 2 GP F,G T6 Class III Natural Gas Approved
Intrinsically Safe & FISCO Class/Division Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42819 Natural Gas Approved
Explosion Proof Class I Division 1 GP B,C,D T6 Natural Gas Approved
Class I Division 2 GP A,B,C,D Class II,III Division 1 GP E,F,G Class II,III Division 2 GP F,G Natural Gas Approved
Intrinsically Safe Class I,II,III Division 1 GP A,B,C, D,E,F,G per drawing GE42819
Explosion Proof Class I Division 1 GP A,B,C,D
Class I Division 2 GP A,B,C,D Class II,III Division 1 GP E,F,G Class II,III Division 2 GP F,G
1
December 2009
1-9
DVC6000f Digital Valve Controllers
Table 1-5. Hazardous Area Classifications—ATEX
Certificate Type Certification Obtained Entity Rating
1
ATEX
DVC60x0F DVC60x0FS (x = 1,2,3)
DVC6005F
DVC60x5 (x = 1,2,3)
II 1 G D Gas Ex ia IIC T4/T5/T6—Intrinsically Safe Dust Ex iaD 20 T100C (Tamb Ex iaD 20 T85C (Tamb v 75C)
II 2 G D Gas Ex d IIB+H2 T5/T6—Flameproof Dust Ex tD A21 IP66 T90C (Tamb v 85C) Ex tD A21 IP66 T80C (Tamb v 75C)
II 3 G D Gas Ex nCL IIC T5/T6—Type n Dust Ex tD A22 IP66 T85C (Tamb v 80C) Ex tD A22 IP66 T80C (Tamb v 75C)
II 1 G D Gas Ex ia IIC T4/T5/T6—Intrinsically Safe Dust Ex iaD 20 T100C (Tamb Ex iaD 20 T85C (Tamb v 75C)
II 2 G D Gas Ex d IIB T5/T6—Flameproof Dust Ex tD A21 IP66 T85C (Tamb v 80C) Ex tD A21 IP66 T75C (Tamb v 70C)
II 3 G D Gas Ex nL IIC T5/T6—Type n Dust Ex tD A22 IP66 T85C (Tamb v 80C) Ex tD A22 IP66 T80C (Tamb v 75C)
II 1 G D Gas Ex ia IIC T4/T5/T6—Intrinsically Safe Dust Ex iaD 20 T135C (Tamb v 125C) Ex iaD 20 T100C (Tamb v 95C) Ex iaD 20 T85C (Tamb v 80C)
II 2 G D Gas Ex d IIC T4/T5/T6—Flameproof Dust Ex tD A21 IP66 T130C (Tamb v 125C) Ex tD A21 IP66 T100C (Tamb v 95C) Ex tD A21 IP66 T85C (Tamb v 80C)
II 3 G D Gas Ex nA IIC T4/T5/T6—Type n Dust Ex tD A22 IP66 T130C (Tamb v 125C) Ex tD A22 IP66 T100C (Tamb v 95C) Ex tD A22 IP66 T85C (Tamb v 80C)
v 80C)
v 80C)
Ui = 24 VDC , Ii = 380 mA , Ci = 5 nF , Li = 0 mH , Pi = 1.4 W
Ui = 17.5 VDC , Ii = 380 mA , Ci = 5 nF , Li = 0 mH , Pi = 5.32 W
Ui = 24 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
Ui = 17.5 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Ui = 30 VDC Ii = 17.5 mA Ci = 0 μF Li = 0 mH Pi = 105 mW
FIELDBUS
FISCO
− − −
− − −
FIELDBUS
Uo = 24 VDC Io = 17.5 mA Co = 121 nF Lo = 100 mH Po = 105 mW
FISCO
Uo = 24 VDC Io = 17.5 mA Co = 121 nF Lo = 100 mH Po = 105 mW
− − −
− − −
− − −
− − −
Temperature
Code
T4(Tamb v 80C) T5(Tamb v 77C) T6(Tamb v 62C)
T5(Tamb v 85C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T4(Tamb v 80C) T5(Tamb v 77C) T6(Tamb v 62C)
T5(Tamb v 80C) T6(Tamb v 70C)
T5(Tamb v 80C) T6(Tamb v 75C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
Enclosure Rating
IP66
IP66
IP66
IP66
IP66
IP66
IP66
IP66
IP66
1-10
December 2009
Introduction and Specifications
Table 1-6. Hazardous Area Classifications—IECEx
Certificate Type Certification Obtained Entity Rating
FIELDBUS
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
FISCO
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
FIELDBUS
Vmax = 24 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
FISCO
Vmax = 17.5 VDC Imax = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Ui = 30 VDC Ii = 17.5 mA Ci = 0 uF Li = 0 mH Pi = 105 mW
− − −
− − −
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mH
Voc = 24 VDC Isc = 17.5 mA Ca = 121 nF La = 100 mH Po = 105 mH
− − −
− − −
− − −
− − −
IECEx
DVC60x0F DVC60x0FS (x = 1,2,3)
DVC6005F
DVC60x5 (x = 1,2,3)
Intrinsically Safe Gas Ex ia IIC T4/T5/T6
Flameproof Gas Ex d IIB+H2 T5/T6
Type n Gas Ex nC IIC T5/T6
Intrinsically Safe Gas Ex ia IIC T5/T6
Flameproof Gas Ex d IIB T5/T6
Type n Gas Ex nC IIC T5/T6
Intrinsically Safe Gas Ex ia IIC T4/T5/T6
Flameproof Gas Ex d IIC T4/T5/T6
Type n Gas Ex nA IIC T4/T5/T6
Temperature
Code
T4(Tamb v 80C) T5(Tamb v 77C) T6(Tamb v 62C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
Enclosure Rating
1
IP66
IP66
IP66
IP66
IP66
IP66
IP66
IP66
IP66
December 2009
1-11
DVC6000f Digital Valve Controllers
Table 1-7. Hazardous Area Classifications—NEPSI
Certificate Type Certification Obtained Entity Rating
Ui = 24 VDC Ii = 226 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
Ui = 17.5 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Ui = 24 VDC Ii = 226 mA Ci = 5 nF Li = 0 mH Pi = 1.4 W
Ui = 17.5 VDC Ii = 380 mA Ci = 5 nF Li = 0 mH Pi = 5.32 W
Ui = 10 VDC Ii = 5 mA Ci = 0 uF Li = 0 mH Pi = 10 mW
1
DVC60x0f (x = 1,2,3)
NEPSI
DVC6005f
DVC60x5 (x = 1,2,3)
1. Except acetylene.
Intrinsically Safe Gas Ex ia IIC T5/T6 Dust DIP A21 T5
Flameproof Gas Ex d IIB+H2 T5/T6 Dust DIP A21 T5
Intrinsically Safe Ex ia IIC T5,T6
Flameproof Ex d IIB T5,T6
Intrinsically Safe Ex ia IIC T4,T5,T6
Flameproof Ex d IIC T4,T5,T6
(1)
FIELDBUS
FISCO
FIELDBUS
Uo = 8.6 VDC Io = 2.3 mA Co = 8.2 uF Lo = 100 mH Po = 5 mW
FISCO
Uo = 8.6 VDC Io = 2.3 mA Co = 8.2 uF Lo = 100 mH Po = 5 mW
− − −
− − −
Temperature
Code
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T5(Tamb v 80C) T6(Tamb v 75C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
T4(Tamb v 125C) T5(Tamb v 95C) T6(Tamb v 80C)
Enclosure Rating
IP66
IP66
IP66
IP66
IP66
IP66
1-12
December 2009
2-2
Installation

Section 2 Installation

Special Instructions for “Safe Use” and
Installation in Hazardous Locations
CSA 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FM 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ATEX 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IECEx 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NEPSI 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Guidelines
DVC6010f on Sliding-Stem Actuators (up to 4 inches travel) 2-7. . . . . . . . . . . . . . .
DVC6020f on Long-Stroke Sliding-Stem Actuators
(4 to 24 inches travel) and Rotary Actuators
2
2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6030f on Quarter-Turn Actuators 2-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6005f Base Unit 2-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wall Mounting 2-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipestand Mounting 2-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6015 on Sliding-Stem Actuators (up to 4 inches travel) 2-14. . . . . . . . . . . . . . . .
DVC6025 on Long-Stroke Sliding-Stem Actuators
(4 to 24 inches travel) and Rotary Actuators
DVC6035 on Quarter-Turn Actuators 2-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Control 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actuator Mounting 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67CFR Filter Regulator
Integral-Mounted Regulator 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Yoke-Mounted Regulator 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Casing-Mounted Regulator 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Connections
Supply Connections 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Connections 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single-Acting Actuators 2-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Double-Acting Actuators 2-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Construction to Support Solenoid Valve Testing 2-20. . . . . . . . . . . . . . . . . . . . . . .
2-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 2-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
December 2009
Vent Connections 2-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fieldbus Connections 2-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
DVC6000f Digital Valve Controllers
Making Fieldbus Connections with a Twisted-Shielded Pair 2-23. . . . . . . . . . . . . . . . . . . .
Making Fieldbus Connections with a Quick Connect Cable Entry 2-23. . . . . . . . . . . . . . .
Feedback Unit Connections for Remote Mounting 2-24. . . . . . . . . . . . . . . . . . . . . . . . .
Communication Connections 2-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulate Enable Jumper 2-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Commissioning Tag 2-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
December 2009

Installation

Installation
The DVC6000f can be used with either air or natural gas as the supply medium. If using natural gas as the pneumatic supply medium, natural gas will be used in the pneumatic output connections of the DVC6000f to any connected equipment. In normal operation the unit will vent the supply medium into the surrounding atmosphere unless it is remotely vented. When using natural gas as the supply medium, in a non-hazardous location in a confined area, remote venting of the unit is required. Failure to do so could result in personal injury, property damage, and area re-classification. For hazardous locations remote venting of the unit may be required, depending upon the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations. Failure to do so when necessary could result in personal injury, property damage, and area re-classification.
Note
Gas Certified DVC6000f digital valve controllers are FM and CSA Single Seal approved for use with natural gas as the supply medium.
If installing this into an existing application, also refer to the WARNING at the beginning of the Maintenance section of this instruction manual.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
2
WARNING
To avoid static discharge from the plastic cover, do not rub or clean the cover with solvents. To do so could result in an explosion. Clean with a mild detergent and water only.
WARNING
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before proceeding with any Installation procedures:
Always wear protective clothing, gloves, and eyewear to prevent personal injury and property damage.
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken. Preventive measures may include, but are not limited, to one or more of the following: Remote venting of the unit, re-evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources. For information on remote venting of this controller, refer to page 2-21.
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non-hazardous (non-classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area re-classification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations. Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area re-classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside diameter and few bends to reduce case pressure buildup.
December 2009
2-3
DVC6000f Digital Valve Controllers
In addition to remote venting of the unit, ensure that all caps and covers are correctly installed. Failure to do so could result in personal injury or property damage from fire or explosion, and area re-classification.
2

Special Instructions for “Safe Use” and Installation in Hazardous Locations

Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
WARNING
Failure to follow these conditions of safe use could result in personal injury or property damage from fire or explosion, and area re-classification.
ATEX
Special Conditions for Safe Use Intrinsically Safe, Dust DVC6010f, DVC6020f, DVC6030f, and DVC6005f
1. This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be compatible as regards the intrinsically safe rules.
2. The FISCO electrical parameters of this equipment must not exceed any following values: UOv 17.5 V; IO v380 mA; POv 5.32 W
3. Operating ambient temperature: −52C or −40C to + 85C
4. For the model with aluminum body: the apparatus must not be submitted to frictions or mechanical impacts.
DVC6015, DVC6025, and DVC6035
1. This apparatus can only be connected to an intrinsically safe certified equipment and this combination must be compatible as regards the intrinsically safe rules.
Refer to table 1-5 for additional approval information, and figure B-11 for the the ATEX Intrinsic Safety, Dust nameplates.
Flameproof, Dust DVC6010f, DVC6020f, and DVC6030f
CSA
Special Conditions of Safe Use Intrinsically Safe and FISCO, Explosion proof,
Division 2, Dust-Ignition proof
No special conditions for safe use. Refer to table 1-3 for approval information, figures B-1
and B-4 for CSA loop schematics, and figures B-3 and B-5 for the CSA nameplates.
FM
Special Conditions of Safe Use Intrinsically Safe and FISCO, Explosion proof,
Non-incendive, Dust-Ignition proof
Refer to table 1-4 for approval information, figures B-6 and B-9 for FM loop schematics, and figures B-8 and B-10 for the FM nameplates.
2-4
Operating ambient temperature: −52C or −40C to + 85C
DVC6005f, DVC6015, DVC6025, and DVC6035
Operating ambient temperature as indicated on the nameplate.
Refer to table 1-5 for additional approval information, and figure B-12 for the ATEX Flameproof, Dust nameplates.
Type n, Dust DVC6010f, DVC6020f, and DVC6030f
Operating ambient temperature: −52C or −40C to + 80C
DVC6005f, DVC6015, DVC6025, and DVC6035
Operating ambient temperature as indicated on the nameplate.
Refer to table 1-5 for additional approval information, and figure B-13 for the ATEX Type n, Dust nameplates.
December 2009
Installation
IECEx
Conditions of Certification
Intrinsically Safe, Flameproof, Type n
DVC6010f, DVC6020f, DVC6030f, and DVC6005f
Ex ia / Ex d / Ex n
1. Warning: Electrostatic charge hazard. Do not rub or clean with solvents. To do so could result in an explosion.
DVC6010f, DVC6020f, DVC6030f, DVC6005f, DVC6015, DVC6025, and DVC6035
EX d / Ex n
2. Do not open while energized. Refer to table 1-6 for additional approval information,
figures B-14 and B-17 for IECEx loop schematics and figures B-16 and B-18 for the IECEx nameplates.
Mounting Style
Integral Mounting
Main Unit DVC6005f
Separate Mounting
Feedback
Unit
Product
Type
DVC6010f DVC6020f DVC6030f
DVC6015 Ex ia II CT6
DVC6025 Ex ia II CT5
DVC6035 Ex ia II CT4
Ex Marking
Ex ia II CT6
Ex ia II CT5
Ex ia II CT6
Ex ia II CT5
Ambient
Temperature
40C to +75C
40C to +80C
40C to +75C
40C to +80C
60C to +80C
60C to +95C
60C to
+125C
2. The enclosure of the controller provides a grounding terminal, and the user should install a reliable grounding wire connected to it when mounting and using the controller.
3. The values for intrinsically safe parameters and maximum internal equivalent parameters of the controller are as follow:
Max Input
Voltage
Ui (V)
24 226 1.4 5 0
17.5 380 5.32 5 0
Max Input
Current
Ii (mA)
Max Input
Power
Pi (W)
Max Internal
Equivalent Parameter
Ci (nF) Li (mH)
2
NEPSI
Notes for Safe Use of the Certified Product
Intrinsically Safe
DVC6000f digital valve controllers (designated as controller hereafter) have been proved to be in conformity with the requirements specified in the national standards GB3836.1-2000 and GB3836.4-2000 through inspections conducted by National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation (NEPSI). The Ex marking for the products is Ex ia II CT6/T5/T4, and their Ex certificate number is GYJ06280. When using the product, the user should pay attention to the items stated below:
1. The correlation of approved DVC6000f digital valve controllers in specific product type, Ex marking and operating ambient temperature this time is as follows:
4. As a main unit of a separate design product, the values for intrinsically safe output parameters of DVC6005f are as follows:
Max Output
Voltage
Uo (V)
8.6 2.3 5 8.2 100
Max Output
Current Io (mA)
Max Output
Power
Po (mW)
Max Equivalent
Parameter allowed
Co (mF) Lo (mH)
5. While the controller forms an intrinsically safe explosion protection system together with an associated equipment, the following requirements must be met: Uo vUi, Io vIi, Po vPi, Co wCi + Cc, Lo wLi + Lc.
Note
Where Cc and Lc represent distributing capacitance and inductance of the connecting cable respectively.
6. The connection cable between the product and associated equipment should be a cable with insulation screen and sheath. The screen should be connected to the ground.
December 2009
2-5
DVC6000f Digital Valve Controllers
7. An appropriate heat-resistant cable should be selected for use with the controller in an application where the ambient temperature exceeds 70C.
8. When using and maintaining the product in the field, cleaning the plastic surface of the product with dry cloth is strictly prohibited to avoid the risk of producing electrical spark.
9. The user must not be allowed to replace at will the electric components of the product on his own to avoid
2
damage to the intrinsically safe performance of explosion protection of the product.
10. The user must follow the relevant rules specified by the product instruction manual, the “13th Section of Electric Equipment Used in Explosive Gaseous Environment: Maintenance of Electric Equipment Used in Explosive Gaseous Environment” of GB3836.13-1997 standard, the “15th Section of Electric Equipment Used in Explosive Gaseous Environment: Electric Installation in Hazardous Locations (except for coal mine)” of GB3836.15-2000 standard and the “Electric installation construction and acceptance test code for electric equipment mounting engineering in an explosive and fire-hazardous environment” of GB50257:1996 standard while performing installation, operation, and maintenance for the product.
Refer to figure B-19 for NEPSI nameplates.
Flameproof
DVC6000f digital valve controllers (designated as controller hereafter) have been proved to be in conformity with the requirements specified in the national standards GB3836.1-2000 and GB3836.2-2000 through inspections conducted by National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation (NEPSI). The Ex markings for the products are Ex d II B+H2T6/T5 (DVC6010f, DVC6020f, and DVC6030f only), Ex d II BT6/T5 (DVC6005f only), and Ex d II CT6/T5/T4 (DVC6015, DVC6025, and DVC6035 only) respectively and their Ex certificate number is GYJ06279. When using the product , the user should pay attention to the items stated below:
1. The correlation of this approved DVC6000f digital valve controllers in specific product type, Ex marking, and operating ambient temperature is as follows:
Product Type Ex Marking
DVC6010f, DVC6020f,
DVC6030f (integral design)
DVC6005f (main unit of
separate design)
DVC6015, DVC6025,
DVC6035 (feedback units of
separate design
Ex d II B+H2T6
Ex d II B+H2T5
Ex d II BT6
Ex d II BT5
Ex d II CT6
Ex d II CT5
Ex d II CT4
Ambient
Temperature
40C to +75C
40C to +80C
40C to +75C
40C to +80C
60C to +80C
60C to +95C
60C to
+125C
2. The enclosure of the controller provides a grounding terminal, and the user should install a reliable grounding wire connected to it when mounting and using the controller.
3. The controller’s cable entrance (1/2 NPT) must be fitted with a cable entry device which is Ex-approved through inspection of explosion protection, in conformity with relevant standards of GB3836.1-2000 and GB3836.2-2000 and has a corresponding rating of explosion protection.
4. An appropriate heat-resistant cable should be selected for use with the controller in an application where the ambient temperature exceeds 70C.
5. The principle of “Opening equipment’s cover is strictly prohibited while it is active” must be abided by when using and maintaining the controller in the field.
6. The user must follow the relevant rules specified by the product instruction manual, the “13th Section of Electric Equipment Used in Explosive Gaseous Environment: Maintenance of Electric Equipment Used in Explosive Gaseous Environment” of GB3836.13-1997 standard, the “15th Section of Electric Equipment Used in Explosive Gaseous Environment: Electric Installation in Hazardous Locations (except for coal mine)” of GB3836.15-2000 standard and the “Electric installation construction and acceptance test code for electric equipment mounting engineering in an explosive and fire-hazardous environment” of GB50257:1996 standard while performing installation, operation, and maintenance for the product.
Refer to figure B-19 for NEPSI nameplates.
2-6
December 2009
Loading...
+ 354 hidden pages