Emerson Fisher FIELDVUE DVC5000 Instruction Manual Supplement

Instruction Manual Supplement
D103266X012
HARTr Field Device Specification
DVC5000 Digital Valve Controller
May 2018
Fisher
FIELDVUE™ DVC5000 Digital Valve
Controllers
HART Revision Device Type Device Revision Firmware Revision
Introduction 2.................................
Product Overview 2............................
Purpose of this document 2.....................
Abbreviations and definitions 2..................
Reference Documentation 3....................
Device Identification 3..........................
Product Interfaces 4............................
Control Valve Interface 4.......................
Host interface 4...............................
Internal Jumpers And Switches 5.................
Write Protection 5.............................
Firmware Upgrade 5...........................
Dynamic Variables 6............................
Device Variables 6..............................
Status Information 7............................
Device Status 7...............................
Universal Commands 8..........................
CommonPractice Commands 13.................
Supported Commands 13......................
Device-Specific Commands 21....................
Burst Mode 21................................
Catch Device Variable 21.......................
Performance 21................................
Annex A Compatibility Checklist 22................
Annex B DVC5000 Parameters as part of a Rosemountr 1410/1420 WirelessHARTr
Gateway 23...............................
2 3, 4 3 5, 6
Product removed from sale October 2003
www.Fisher.com
DVC5000 Digital Valve Controller
May 2018
Instruction Manual Supplement
D103266X012
Introduction
Product Overview
The FIELDVUE DVC5000 digital valve controller is designed to control the pneumatic actuator of a process control valve. It receives a current signal from a host and uses instrument air supply to create a metered pressure output signal to the pneumatic actuator. Movement of the actuator as it positions the process control valve is measured by the DVC5000 travel sensor as its primary feedback. The name plate is located on the side of the DVC5000 master module assembly and indicates the model name, individual product serial number, and any applicable third party approvals.
Purpose of this document
This specification is designed to be a technical reference for HART capable host application developers, system integrators and knowledgeable end-users. It also provides functional specifications (e.g., commands, enumerations and performance requirements) used during field device development, maintenance and testing. This document assumes the reader is familiar with HART Protocol requirements and terminology. Additional product information is available in the DVC5000 product literature, available from your Emerson sales office
or Local Business Partner.
Abbreviations and definitions
AR Alert Record
Configuration Variables
Device Variable
Enumeration A pre-defined set of values or text.
MV Measured Variable, a physical input to the instrument.
NV
Point
Byte An 8bit unsigned integer.
Word A 16bit unsigned integer.
Float Refers to the IEEE 754 floating point format.
Packed ASCII
Standard Span Format
Variables which represent nonvolatile values of manufacturinginitialized data or userspecified configuration information. These variables cannot be enumerated via Command 54 and as such stand on their own with no associated units or range information.
Measured variables that are exposed to HART and can be enumerated using Command 54. Generally there are variables whose ID is in the range of 0 to 10 and are associated with units codes, status, and range values.
Named Variable – a logical point inside the device, hardmapped to a given MV as the source of NV data.
A term that applies to diagnostic data packets. It is defined as a collection of periodically sampled variables captured at a single instant in time. It does not include the “Monitor” point.
A special form of characters defined by HART in which 6bit ASCII characters are packed into byte data.
A proprietary 16bit integer format for numerical values used by some of this device’s Device Specific commands.
2
Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
Reference Documentation
HART Smart Communications Protocol Specification Revision 5; a group of documents specifying the HART Communication Protocol, physical layers, and Data Link Layers as defined by the HART Communications Foundation.
The DVC5000 is not an Active product. Contact your Emerson sales office instruction manual is required.
or Local Business Partner if a copy of the
Device Identification
Manufacturer Name Fisher Controls Model Name(s) DVC5000
Manufacture ID Code 19 (13 Hex) Device Type Code 02 (02 Hex)
HART Protocol Revision 5 Device Revision 2 or 3
User Selectable HART Revision
between HART 5 and HART 7
Number of Device Variables 9
Physical Layers Supported FSK
Physical Device Category Valve Positioner
No
3
DVC5000 Digital Valve Controller
May 2018
Instruction Manual Supplement
D103266X012
Product Interfaces
Control Valve Interface
The DVC5000 digital valve controller is mechanically attached to the valve’s actuator by means of a mounting bracket. The control valve's position is conveyed to the travel sensor of the DVC5000 digital valve controller by means of the feedback bracket attached to the actuator’s stem and the rotating travel sensor.
MOUNTING
BRACKET
Pneumatic tubing connected to the DVC5000 brings instrument supply air to the DVC5000 and takes controlled output air from the DVC5000 to the actuator. The pressure sensor in the DVC5000 measures the output pressure and presents it as a device variable.
Host interface
The input to the DVC5000 can either be twowire 4to20 mA current loop (in pointtopoint mode) or 24 VDC (in multidrop mode). This input is connected in the DVC5000’s terminal box on two terminals marked “LOOP +” and “LOOP ”. Refer to the DVC5000 instruction manual for connection details.
4
Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
Internal Jumpers And Switches
The input to the DVC5000 is determined by the PtPt/MultiDrop switch on the printed wiring board.
LOOP-
LOOP+
UP
(MULTI‐DROP)
MULTI‐DROP SWITCH
AUXILIARY SWITCH
May 2018
DOWN
(POINT-TO-POINT)
A6191‐1
X
X
Refer to the DVC5000 instruction manual for additional details on the settings of the selection switches.
Write Protection
There are two Write Protection states for the DVC5000: Not Protected or Protected. Protected prevents configuration and calibration changes to the instrument. The default setting is Not Protected. Protection is controlled under software control. Write Protection can be enabled remotely. However, to disable Write Protection to Not Protected, you must have physical access to the instrument. The procedure will require you to short the AUX terminals inside the terminal box when directed by the software as a security measure.
Firmware Upgrade
The firmware of a DVC5000 printed wiring board assembly cannot be upgraded.
5
DVC5000 Digital Valve Controller
May 2018
Instruction Manual Supplement
D103266X012
Dynamic Variables
Four Dynamic Variables are implemented.
COMMAND/RESPONSE MODE BURST MODE
Default Meaning Units Default Meaning Units
PV Analog Input mA, % Valve Travel % SV Aux Contact Status % Travel Setpoint % TV Pressure PSI, BAR, KPA Pressure PSI, BAR, KPA
FV Valve Travel %
FW5: Aux Status % FW6: Drive Signal %
Device Variables
These variables represent measurements taken by the device, are read only values, and are all in float format. These can be read with Commands 33 and 54.
Variable ID Meaning Units
0 Analog Input mA, % 1 Auxiliary Contact Status (0% = Open, 100% = Shorted) % 2 Output Pressure PSI, BAR, KPA 3 Valve Travel % 4 Drive Signal % 5 Unused 6 Travel Setpoint % 7 Unused 8 Unused 9 Implied Valve Position (Travel Target) %
10 Valve Travel %
211 Temperature _C, _F
Unit Codes
Variable Units Code Units
0 No Units 6 Pounds per square inch, psi
7 Bar 12 ($0C) Kilopascals, kPa 32 ($20) Celsius, _C 33 ($21) Fahrenheit, _F 39 ($27) Milliamps, mA 57 ($39) Percent, %
6
Instruction Manual Supplement
D103266X012
DVC5000 Digital Valve Controller
May 2018
Status Information
Device Status
The Field Device Status Byte is the only status byte defined in the HART protocol. The order and meaning of each of the eight bits within the byte are fixed by the protocol. This byte is one of the status bytes included with each HART response. It is not part of the Command 48 data.
Bit Device Revision Name of Status Bit Meaning
Set / cleared by the firmware based on self test results.
7 2, 3 Field Device Malfunction
6 2, 3 Configuration Changed
5 2, 3 Cold Start
4 2, 3 More Status Active when any bit in command 48 is active.
2 Not Used
3
2
1 2, 3 Internal Sensor Out of Limits
0 2, 3 Loop Current Out of Range Set when any variable 0 (Analog Input) is saturated.
3 Analog Input Fixed
2 Analog Input Saturated
3 Not Used
This bit is set if the pressure, position or temperature sensors provide invalid readings.
Two such bits exist internally, one for each HART master. Both copies are set when any variable, HART message, tag, descriptor or date are changed from HART. Cleared by command 38, separately for each master. This bit survives loss of power.
Set by the firmware whenever a RESET sequence is executed or at initial device power up. Cleared by the first HART command.
Active if the Instrument Mode of the DVC5000 is in the “Out Of Service” condition or if the Control Mode of the DVC5000 is in one of the digital set point modes.
Active if the Instrument Mode of the DVC5000 is in the “Out Of Service” condition or if the Control Mode of the DVC5000 is in one of the digital set point modes.
(This bit is named “NonPrimary Variable Out Of Limits” in the HART documentation for transmitters. It has been renamed to reflect the fact that these variables are INTERNAL INPUTS to FIELDVUE products). The firmware sets this bit when any sensor (pressure, position, temperature) exceeds its operating limits.
7
DVC5000 Digital Valve Controller
May 2018
Instruction Manual Supplement
Universal Commands
The DVC5000 field device implements all HART Revision 5 Universal Commands.
Command 0: Read Unique Identifier Command 1: Read Primary Variable Command 2: Read Loop Current and Percent of Range Command 3: Read Dynamic Variables and P.V. Current Command 6: Write Polling Address Command 11: Read Unique Identifier Associated with Tag Command 12: Read Message Command 13: Read Tag, Descriptor, Date Command 14: Read Primary Variable Transducer Information Command 15: Read Primary Variable Output Information Command 16: Read Final Assembly Number Command 17: Write Message Command 18: Write Tag, Descriptor, Date Command 19: Write Final Assembly Number
D103266X012
8
Instruction Manual Supplement
D103266X012
Command 0: Read Unique Identifiers
Byte Description Format Value
Request
Data Bytes
Response
Data Bytes
Command
Specific
Response
Codes
none
0 Data type expansion code Byte, hex $FE 1 Manufacturer identification code Byte, hex $13 2 Manufacturer’s Device Type code Byte, hex $02 3 Number of preambles Byte, hex $05 4 Universal command revision Byte, hex $05 5 Device revision Byte, hex See table 1 below 6 Software revision Byte, unsigned integer See table 1 below 7 Hardware revision Byte, unsigned integer See table 2 below 8 Device function flags Not Used $00 9 Device Identification number 3 Bytes, hex
Code Description
none
DVC5000 Digital Valve Controller
May 2018
Table 1. Device and Software Revision
Device Revision Software Revision Description
$02
$03
$03 Firmware Revision 3 $04 Firmware Revision 4 $05 Firmware Revision 5 $06 Firmware Revision 6
Table 2. Hardware Revision
Hardware Revision Description
($08) Not applicable ($10) Hardware revision 2 ($18) Hardware revision 3 ($20) Hardware revision 4 ($28) Hardware revision 5
9
Loading...
+ 19 hidden pages