Rosemount 848L Discrete Logic
Temperature Transmitter with
OUNDATION Fieldbus
F
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 P.M. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a Emerson Process
Management Sales Representative.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Electrical shock could cause death or serious injury.
• If the device or senors are installed in a high voltage environment and a fault
condition or installation error occurs, high voltage may be present on transmitter
leads and terminals.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Reference Manual
00809-0100-4696, Rev AA
Rosemount 848L
September 2004
OVERVIEW
TransmitterThe 848L provides a cost effective field mounted interface for discrete inputs
and outputs on a Foundation Fieldbus H1 network. The 848L allows you to
leverage the fieldbus network to reduce discrete input and output wiring and
eliminate the need for a separate bus for discrete inputs and outputs. The
848L can communicate with other devices on the segment to provide logic
interactions independent of any upper level controller.
The 848L also has logic capability allowing it to independently control outputs
based on the state of one or more of it's inputs or discrete signals from other
devices on the network. A Logic Block allows for up to 20 Boolean equations,
8 Inputs, and 4 Outputs.
ManualThis manual is designed to assist in the installation, operation, and
maintenance of the Rosemount 848L Logic Transmitter.
Section 1: Introduction
•Overview
•Considerations
•Return of Materials
Section 2: Installation
•Mounting
•Installation
•Wiring
•Power Supply
•Commissioning
Section 3: Configuration
OUNDATION fieldbus Technology
•F
•Configuration
•Function Block Configuration
Section 4: Operation and Maintenance
•Hardware Maintenance
•Troubleshooting
1-2
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
Appendix A: Specification and Reference Data
•Specifications
•Dimensional Drawings
•Ordering Information
Appendix B: Product Certificates
•Hazardous Locations Certificates
•Intrinsically Safe and Non-Incendive Installations
•Installation Drawings
Appendix C: Function Blocks
•Device Descriptions
•Block Operation
Appendix D: Logic Equation Syntax
•Error Handling
•Examples
Appendix E: Motor Control
•Variations of Motor Control
•Writing 848L Equations
Appendix F: Valve Control
RETURN OF MATERIALSTo expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist with any needed information or
materials.
The center will ask for the following information:
•Product model
•Serial numbers
•The last process material to which the product was exposed
The center will provide
•A Return Material Authorization (RMA) number
•Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations, please contact an Emerson Process Management sales
representative.
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS),
required by law to be available to people exposed to specific hazardous
substances, must be included with the returned materials.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Electrical shock could cause death or serious injury.
• If the device or sensors are installed in a high voltage environment and a fault
condition or installation error occurs, high voltage may be present on transmitter
leads and terminals.
• Use extreme caution when making contact with the leads and terminals.
MOUNTING The 848L is always mounted remote from the sensors and output devices.
There are three mounting configurations:
•To a DIN rail without an enclosure
•To a panel with an enclosure
•To a 2-in pipe stand with an enclosure using a pipe mounting kit
www.rosemount.com
Rosemount 848L
Reference Manual
00809-0100-4696, Rev AA
September 2004
Mounting to a DIN Rail
Without an Enclosure
Figure 2-1. Mounting the 848L to
a DIN Rail
Mounting to a Panel with
a Junction Box
To mount the 848L to a DIN rail without an enclosure, follow these steps:
1.Pull up the DIN rail mounting clip located on the top back side of the
transmitter.
2.Hinge the DIN rail into the slots on the bottom of the transmitter.
3.Tilt the 848L and place onto the DIN rail. Release the mounting clip.
The transmitter should be securely fastened to the DIN rail.
848L without
enclosure
DIN Rail Mounting Clip
DIN Rail
When inside of a plastic or aluminum junction box, the 848L mounts to a panel
1
using four
/4-20 x 1.25-in. screws.
When inside of a stainless steel junction box, the 848L mounts to a panel
using two
1
/4-20 x 1/2-in. screws.
Figure 2-2. Mounting the 848L
junction box to a panel
848L with aluminum or plastic box
Cover
Screws (4)
Mounting
Screws (4)
Panel
Aluminum/PlasticStainless Steel
848L with a stainless steel box
Mounting
Screws (2)
Panel
2-2
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
Mounting to a 2-Inch
Pipe Stand
Use the optional mounting bracket (option code B6) to mount the 848L to a
2-inch pipe stand when using a junction box.
Aluminum/Plastic Junction Box
(styles JA and JP)
Front ViewSide ViewFront ViewSide View
5.1
(130)
10.2
(260)
Aluminum/Plastic Junction Box
Mounted on a Vertical Pipe
6.6 (167)
fully
assembled
Dimensions are in inches (millimeters)
Stainless Steel Junction Box
4.5
(114)
Stainless Steel Junction Box
Mounted on a Vertical Pipe
(style JS)
7.5 (190)
fully
assembled
848_848A52A, B, 53A, B
848_848A54A, 55A
2-3
Reference Manual
00809-0100-4696, Rev AA
Rosemount 848L
September 2004
WIRINGIf the device or sensors are installed in a high-voltage environment and a fault
condition or installation error occurs, the sensor leads and transmitter
terminals could carry lethal voltages. Use extreme caution when making
contact with the leads and terminals.
NOTE
Do not apply high voltage (e.g. AC line voltage) to the transmitter bus or I/O
power terminals. Abnormally high voltage can damage the unit (bus and I/O
power terminals are rated to 42.4 VDC).
Figure 2-3. 848L Transmitter
Fieldbus Wiring
Integrated Power
Conditioner
and Filter
Power
Supply
6234 ft (1900 m) max
(depending upon cable
characteristics)
Terminators
(Trunk)
Power Supply
Connections
FOUNDATION
fieldbus Host or
configuration tool
(Spur)
Devices 1 through 16*
(Spur)
Signal
Wiring
The transmitter requires both a fieldbus connection and power for the discrete
I/O channels.
Fieldbus Connection
The fieldbus connection requires between 9 and 32VDC to operate the
electronics. The dc power supply should provide power with less than 2%
ripple. A fieldbus segment requires a power conditioner to isolate the power
supply filter and decouple the segment from other segments attached to the
same power supply. Signal wiring should be shielded, twisted pair for best
results in electrically noisy environments. Do not use unshielded signal wiring
in open trays with power wiring or near heavy electrical equipment. Use
ordinary copper wire of sufficient size to ensure that the voltage across the
bus terminals does not go below 9 VDC. The power terminals are not polarity
sensitive. To power the electronics and establish communications:
1.Connect the fieldbus wires to the terminals marked "Bus" as shown in
Figure 2-4 on page 2-5.
2.Tighten the terminal screws to ensure adequate contact.
848-848_01A
2-4
Reference Manual
00809-0100-4696, Rev AA
September 2004
Figure 2-4. “Bus” location on the
Rosemount 848L
Rosemount 848L
848/848L/848L_19_AA.EPS
Input/Output Power:
The discrete I/O requires a 9-32VDC power supply that is separate from the
fieldbus power. The voltage level will depend on the type of sensors being
used and outputs being driven. To power the I/O:
1.Connect the positive lead from the power supply to the (+) terminal
marked "PWR".
2.Connect the return lead to the (-) terminal marked "PWR"
3.Tighten the terminal screws to ensure adequate contact.
Surges/TransientsThe transmitter will withstand electrical transients encountered through static
discharges or induced switching transients. However, a transient protection
option (option code T1) is available to protect the 848L against high-energy
transients. The device must be properly grounded using the ground terminal.
GROUNDINGAlthough not required, a ground terminal is provided that can be connected to
earth ground for optimal EMC performance. A wire of 14AWG or larger is
recommend using appropriate terminal connectors at both ends.
Transmitter Enclosure (optional)
Ground the transmitter in accordance with local electrical requirements.
SWITCHES
Figure 2-5. Switch Location on
the Rosemount 848L
NOT USED
SECURITY
SIMULATE ENABLE
2-5
848/848L/848L_17_AA.EPS
Rosemount 848L
Reference Manual
00809-0100-4696, Rev AA
September 2004
Security
After configuring the transmitter, the data can be protected from unwarranted
changes. Each 848L is equipped with a security switch that can be positioned
“ON” to prevent the accidental or deliberate change of configuration data.
This switch is located on the front side of the electronics module and
is labeled SECURITY.
See Figure 2-5 on page 2-5 for switch location on the transmitter label. Refer
to Section 3: Configuration, “SOFT WRITE LOCK and HARD WRITE LOCK”
on page 3-5.
Simulate Enable
The switch labeled SIMULATE ENABLE is used in conjunction with the with
the Discrete Input (DI) and Discrete Output (DO) function blocks. This switch
is used to simulate input status. As a lock-out feature, the switch must
transition from “OFF” to “ON” after power is applied to the transmitter. This
feature prevents the transmitter from being left in simulator mode.
NOT USED
The switch labeled NOT USED is only used for product engineering and
development purposes and should always remain in the “OFF” position. If the
switch is turned to the “ON” position and power is applied, the 848L will not be
present on the fieldbus segment.
The 848L is supplied with a removable commissioning tag that contains both
the Device ID (the unique code that identifies a particular device in the
absence of a device tag) and a space to record the device tag (the operational
identification for the device as defined by the Piping and Instrumentation
Diagram (P&ID)).
When commissioning more than one device on a fieldbus segment, it can be
difficult to identify which device is at a particular location. The removable tag,
provided with the transmitter, can aid in this process by linking the Device ID
to its physical location. The installer should note the physical location of the
transmitter on both the upper and lower location of the commissioning tag.
The bottom portion should be torn off for each device on the segment and
used for commissioning the segment in the control system.
Figure 2-6. Commissioning Tag
Reference Manual
00809-0100-4696, Rev AA
September 2004
Device ID
Device Tag
to denote
physical
location
Transmitter Tag
Hardware
• tagged in accordance with customer requirements
• permanently attached to the transmitter
Software
• the transmitter can store up to 30 characters
• if no characters are specified, the first 30 characters of the hardware tag
will be used
Sensor Tag
Hardware
• a plastic tag is provided to record identification of the I/O
• in the field, the tag can be removed, printed on, and reattached to the
transmitter
Software
• the I/O Transducer Block provides the ability to record the I/O tags.
2-8
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
TRANSMITTER LABEL
Figure 2-7. Transmitter Label
INSTALLATION
Using Cable GlandsUse the following steps to install the 848L with Cable Glands:
1.Remove the junction box cover by unscrewing the four cover screws.
2.Run the sensor and power/signal wires through the appropriate cable
glands using the pre-installed cable glands (see Figure 2-8).
3.Install the I/O wires into the correct screw terminals.
4.Install the power/signal wires onto the correct screw terminals. Bus
power is polarity insensitive, allowing the user to connect positive (+)
or negative (–) to either Fieldbus wiring terminal labeled “Bus.” I/O
power is polarity sensitive and must be connected correctly to avoid
damage to the transmitter. See Figure 2-4 on page 2-5.
5.Replace the enclosure cover and securely tighten all cover screws.
848/848_21_AA.EPS
Figure 2-8. Installing the 848L
with Cable Glands
Enclosure Cover
Screw (4)
Cable Gland
I /O
Power/Signal
848_848A19A
2-9
Reference Manual
00809-0100-4696, Rev AA
Rosemount 848L
September 2004
Using Conduit EntriesUse the following steps to install the 848L with Conduit Entries:
1.Remove the junction box cover by unscrewing the four cover screws.
2.Remove the five conduit plugs and install five conduit fittings
(supplied by the installer).
3.Run sensor and output wires through each conduit fitting.
4.Install the I/O wires into the correct screw terminals.
5.Install the power/signal wires into the correct screw terminals. Bus
power is polarity insensitive, allowing the user to connect positive (+)
or negative (–) to either Fieldbus wiring terminal labeled “Bus.” I/O
power is polarity sensitive and must be connected correctly to avoid
damage to the transmitter. See Figure 2-4 on page 2-5.
6.Replace the junction box cover and securely tighten all cover screws.
Figure 2-9. Installing the 848L
with Conduit Entries
OVERVIEWThis section covers basic operation, software functionality, and basic
configuration procedures for the Rosemount 848L transmitter with
F
OUNDATION fieldbus. This section is organized by block information. For
detailed information about the function blocks used in the Rosemount 848L
logic transmitter, refer to “Foundation Fieldbus Block Information” on page A-1
and the Foundation Fieldbus Function Block manual (00809-0100-4783).
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
Warnings
Explosions can result in death or serious injury.
Before connecting a configuration tool in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with nonincendive field wiring
practices.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
www.rosemount.com
Reference Manual
00809-0100-4696, Rev AA
Rosemount 848L
September 2004
GENERAL BLOCK
INFORMATION
ModesThe Resource, Transducer, and all function blocks in the device have modes
of operation. These modes govern the operation of the block. Every block
supports both automatic (AUTO) and out of service (OOS) modes. Other
modes may also be supported.
Changing Modes
To change the operating mode, set the MODE_BLK.TARGET to the desired
mode. After a short delay, the parameter MODE_BLOCK.ACTUAL should
reflect the mode change if the block is operating properly.
Permitted Modes
It is possible to prevent unauthorized changes to the operating mode of a
block. To do this, configure MODE_BLOCK.PERMITTED to allow only the
desired operating modes. It is recommended to always select OOS as one of
the permitted modes.
Types of Modes
For the procedures described in this manual, it will be helpful to understand
the following modes:
AUTO
The functions performed by the block will execute. If the block has any
outputs, these will continue to update. This is typically the normal
operating mode.
Out of Service (OOS)
The functions performed by the block will not execute. If the block has any
outputs, these will typically not update and the status of any values passed
to downstream blocks will be “BAD”. To make some changes to the
configuration of the block, change the mode of the block to OOS. When
the changes are complete, change the mode back to AUTO.
MAN
In this mode, variables that are passed out of the block can be manually
set for testing or override purposes.
Other Types of Modes
Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these
may be supported by different function blocks in the Rosemount 848L. For
more information, see the Function Block manual, document
00809-0100-4783.
NOTE
When an upstream block is set to OOS, this will impact the output status of all
downstream blocks. The figure below depicts the hierarchy of blocks:
3-2
Resource
Block
Transducer
Block
Discrete Input
(DI Block)
Other
function
blocks
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
Link Active SchedulerThe Rosemount 848L can be designated to act as the backup Link Active
Scheduler (LAS) in the event that the LAS is disconnected from the segment.
As the backup LAS, the Rosemount 848L will take over the management of
communications until the host is restored.
The host system may provide a configuration tool specifically designed to
designate a particular device as a backup LAS. Otherwise, this can be
configured manually as follows:
1. Access the Management Information Base (MIB) for the Rosemount
848L.
2. To activate the LAS capability, write 0x02 to the
BOOT_OPERAT_FUNCTIONAL_CLASS object (Index 605). To
deactivate, write 0x01.
3. Restart the processor.
Block InstantiationRosemount devices are pre-configured with function blocks at the factory, the
default permanent configuration for the Rosemount 848L is listed below. The
Rosemount 848L can have one additional instantiated function block.
•8 Discrete Input Blocks
•4 Discrete Output Blocks
•Multiple Discrete Input Block
•Multiple Discrete Output Block
The Rosemount 848L supports the use of Function Block Instantiation. When
a device supports block instantiation, the number of blocks and block types
can be defined to match specific application needs.The number of blocks that
can be instantiated is only limited by the amount of memory within the device
and the block types that are supported by the device. Instantiation does not
apply to standard device blocks like the Resource, I/O Transducer, and Logic
Transducer Block.
Block instantiation is done by the host control system or configuration tool, but
not all hosts are required to implement this functionality. Please refer to your
specific host or configuration tool manual for more information.
3-3
Rosemount 848L
CapabilitiesVirtual Communication Relationship (VCRs)
There are a total of 20 VCRs. Two are permanent and 18 are fully
configurable by the host system. 25 link objects are available.
Network ParameterValue
Slot Time8
Maximum Response Delay4
Maximum Inactivity to Claim LAS Delay60
Minimum Inter DLPDU Delay7
Time Sync class4 (1ms)
Maximum Scheduling Overhead21
Per DLPDU PhL Overhead4
Maximum Inter-channel Signal Skew0
Required Number of Post-transmission-gap-ext Units0
Required Number of Preamble-extension Units1
Host timer recommendations
T1 = 96000
T2 = 1920000
T3 = 480000
Reference Manual
00809-0100-4696, Rev AA
September 2004
RESOURCE BLOCK
FEATURES and
FEATURES_SEL
Block Execution times
Discrete Input = 40 ms
Discrete Output = 40 ms
Multiple Discrete Input = 40 ms
Multiple Discrete Output = 40 ms
The parameters FEATURES and FEATURE_SEL determine optional
behavior of the Rosemount 848L.
FEATURES
The FEATURES parameter is read only and defines which features are
supported by the Rosemount 848L. Below is a list of the FEATURES the
Rosemount 848L supports.
UNICODE
All configurable string variables in the Rosemount 848L, except tag names,
are octet strings. Either ASCII or Unicode may be used. If the configuration
device is generating Unicode octet strings, you must set the Unicode option
bit.
REPORTS
The Rosemount 848L supports alert reports. The Reports option bit must be
set in the features bit string to use this feature. If it is not set, the host must
poll for alerts.
3-4
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
SOFT WRITE LOCK and HARD WRITE LOCK
Inputs to the security and write lock functions include the hardware security
switch, the hardware and software write lock bits of the FEATURE_SEL
parameter, the WRITE_LOCK parameter, and the DEFINE_WRITE_LOCK
parameter.
The WRITE_LOCK parameter prevents modification of parameters within the
device except to clear the WRITE_LOCK parameter. During this time, the
block will function normally updating inputs and outputs and executing
algorithms. When the WRITE_LOCK condition is cleared, a WRITE_ALM
alert is generated with a priority that corresponds to the WRITE_PRI
parameter.
The FEATURE_SEL parameter enables the user to select a hardware or
software write lock or no write lock capability. To enable the hardware security
function, enable the HW_SEL bit in the FEATURE_SEL parameter. When this
bit has been enabled the WRITE_LOCK parameter becomes read only and
will reflect the state of the hardware switch. In order to enable the software
write lock, the SW_SEL bit must be set in the FEATURE_SEL parameter.
Once this bit is set, the WRITE_LOCK parameter may be set to “Locked” or
“Not Locked.” Once the WRITE_LOCK parameter is set to “Locked” by either
the software or the hardware lock, all user requested writes as determined by
the DEFINE_WRITE_LOCK parameter shall be rejected.
The DEFINE_WRITE_LOCK parameter allows the user to configure whether
the write lock functions (both software and hardware) will control writing to all
blocks, or only to the resource and transducer blocks. Internally updated data
such as process variables and diagnostics will not be restricted by the
security switch.
The following table displays all possible configurations of the WRITE_LOCK
parameter.
(1) The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit if set to 1
(on), the SW_SEL bit is automatically set to 0 (off) and is read only.
FEATURE_SEL
SW_SEL bit
(1)
WRITE_LOCK
SECURITY SWITCH WRITE_LOCK
0 (unlocked)1 (unlocked)Read onlyNAAll
Read/Write
DEFINE_WRITE_LOCK
Write access
to blocks
Blocks only
Blocks only
FEATURE_SEL
FEATURE_SEL is used to turn on any of the supported features. The default
setting of the Rosemount 848L does not select any of these features. Choose
one of the supported features if any.
MAX_NOTIFYThe MAX_NOTIFY parameter value is the maximum number of alert reports
that the resource can have sent without getting a confirmation, corresponding
to the amount of buffer space available for alert messages. The number can
be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
3-5
Reference Manual
00809-0100-4696, Rev AA
Rosemount 848L
September 2004
PlantWeb™ AlarmsThe Resource Block will act as a coordinator for PlantWeb alarms. There will
be three alarm parameters (FAILED_ALARM, MAINT_ALARM, and
ADVISE_ALARM) which will contain information regarding some of the device
errors which are detected by the transmitter software. There will be a
RECOMMENDED_ACTION parameter which will be used to display the
recommended action text for the highest priority alarm. FAILED_ALARM will
have the highest priority followed by MAINT_ALARM and ADVISE_ALARM
will be the lowest priority.
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device or
some part of the device non-operational. This implies that the device is in
need of repair and must be fixed immediately. There are five parameters
associated with FAILED_ALARMS specifically, they are described below.
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the
device non-operational that will cause an alarm to be sent. Below is a list
of the failures with the highest priority first.
1.Electronics Failure
2.NV Memory Failure
3.No I/O Power
4.Primary Value Failure
5.Secondary Value Failure
FAILED_MASK
This parameter will mask any of the failed conditions listed in
FAILED_ENABLED. A bit on means that the condition is masked out from
alarming and will not be reported.
FAILED_PRI
Designates the alarming priority of the FAILED_ALM. The default is 0 and
the recommended value is between 8 and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with
the highest priority will be displayed. This priority is not the same as the
FAILED_PRI parameter described above. This priority is not user
configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device
non-operational.
3-6
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs
maintenance soon. If the condition is ignored, the device will eventually fail.
There are five parameters associated with MAINT_ALARMS, they are
described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating
the device or some part of the device needs maintenance soon. If the
condition is ignored, the device will eventually fail.
Below is a list of the conditions with the highest priority first.
1.Secondary Value Degraded
2.Configuration Error
MAINT_MASK
The MAINT_MASK parameter will mask any of the failed conditions listed
in MAINT_ENABLED. A bit on means that the condition is masked out
from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM. The
default is 0 and the recommended value is 3 to 7.
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active.
Only the condition with the highest priority will be displayed. This priority is
not the same as the MAINT_PRI parameter described above. This priority
is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is
ignored, the device will eventually fail.
Advisory Alarms
An advisory alarm indicates informative conditions that do not have a direct
impact on the device's primary functions There are five parameters
associated with ADVISE_ALARMS, they are described below.
ADVISE_ENABLED
The ADVISE_ENABLED parameter contains a list of informative
conditions that do not have a direct impact on the device's primary
functions. Below is a list of the advisories with the highest priority first.
1.Prescaler Overflow
2.NV Write Deferred
3.PWA Simulate Active
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed
in ADVISE_ENABLED. A bit on means the condition is masked out from
alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM. The
default is 0 and the recommended value is 1 or 2.
3-7
Rosemount 848L
Table 3-1.
RB.RECOMMENDED_ATION
Reference Manual
00809-0100-4696, Rev AA
September 2004
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is
active. Only the advisory with the highest priority will be displayed. This
priority is not the same as the ADVISE_PRI parameter described above.
This priority is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do
not have a direct impact on the process or device integrity.
Recommended Actions for PlantWeb Alarms
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will
give a recommended course of action to take based on which type and
which specific event of the PlantWeb alarms is active.
Alarm Type
NONENoneNo action required
ADVISORY
MAINTENANCE
FAILED
Failed/Maint/Advise
Active Event
Prescaler Overflow Check the Divisor parameter of all PS function
NV Write DeferredReduce the frequency in which applications
PWA Simulate ActiveDisable PWA_SIMULATE parameter in the
Secondary Value
Degraded
Configuration ErrorVerify that the Logic equations are correct in
Electronics FailureReplace the electronics
NV Memory FailureReplace the electronics
No I/O PowerCheck the IO Power supply, polarity, wiring,
Primary Value FailureCheck the sensor, configuration, wiring, and
Secondary Value
Failure
Recommended Action
Text String
calls in the logic equations
write to NV Memory
Resource Block
Ensure that the transmitter is not too close to
extreme hot or cold environments
the Logic transducer block
and connections.
connection for open or shorted sensors.
Verify that the body temperature is within the
operating limits of this device.
3-8
Reference Manual
00809-0100-4696, Rev AA
September 2004
Rosemount 848L
AlarmsUse the following steps to configure the alarms, which are located in the
Resource Block.
1.Set the resource block to OOS.
2.Set WRITE_PRI to the appropriate alarm level (WRITE_PRI has a
selectable range of priorities from 0 to 15. Set the other block alarm
parameters at this time.
1
3.Set CONFIRM_TIME to the time, in
device will wait for confirmation of receiving a report before trying
again (the device does not retry if CONFIRM_TIME is 0).
4.Set LIM_NOTIFY to a value between zero and MAX_NOTIFY.
LIM_NOTIFY is the maximum number of alert reports allowed before
the operator needs to acknowledge an alarm condition.
5.Enable the reports bit in FEATURE_SEL.
6.Set the resource block to AUTO.
/32 of a millisecond, that the
I/O TRANSDUCER
BLOCK
The 848L is ordered with either Dry Contact, VDC or NAMUR Inputs. Each
input can have a filter which determines the minimum time a contact needs to
be at a given state to be acknowledged as a state change.
The following procedure allows the sensors to be configured:
1.Set MODE_BLK.TARGET to OOS
2.For each Input “n” select the parameter IN_n_CONFIG.FILTER
a. Select the desired filter time in the range of 0 to 128msec
3.Set MODE_BLK.TARGET to AUTO
3-9
Rosemount 848L
Reference Manual
00809-0100-4696, Rev AA
September 2004
The 848L can force the outputs to a predetermined state in the event of a
device malfunction.
The following procedure can be used to set the fail safe condition for each
output:
1.Set MODE_BLK.TARGET to OOS
2.For each Output "n" select the parameter
OUT_n_CONFIG.FAIL_SAFE
3.Select False, True or Last Good Value
4.Set MODE_BLK.TARGET to AUTO
Latching
Most often the inputs are scanned and the logic equations processed at a rate
greater than the macrocycle frequency. To be certain that positive or negative
transitions are communicated, the inputs, equation results, and output values
can be latched until read by the function blocks.
The following procedure is used to set the latching state of each input,
equation or output:
LOGIC TRANSDUCER
BLOCK
1.Set MODE_BLK.TARGET to OOS
2.Select the appropriate parameter for either inputs, equations, or
outputs:
a. Inputs use parameter MACRO_IN_LATCH
b. Outputs use parameter MACRO_OUT_LATCH
c. Equations use parameter MACRO_EQ_LATCH
For each input, output or equation select either "Latch Positive Pulses" or
"Latch Negative Pulses" or “disabled”.
Logic Equations
The 848L provides for 16 Logic Equations and 4 Output Equations. The
Output Equations drive the hardware outputs. Each logic equation consists of
up to 80 characters with a semicolon as the last character. The equations are
evaluated at a nominal rate of 100msec. However this will vary based on the
number and complexity of the equations used. The logic block consists of
variables that are connected to the hardware I/O, obtain values or send
values over the bus and internally calculated variables as shown in
Figure 3-1.
The value or state of the logic block variables can be communicated on the
bus by assigning the appropriate channel number of a DI or MDI block. The
DO variables can be set externally by assigning the appropriate channel
number in a DO or MDO function block. The DO function blocks do not drive
the outputs directly. The DO function block can drive the output by referencing
the appropriate DO variable in the output equations.
3-10
Loading...
+ 75 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.