Emerson 7829 User Manual

Installation and Configuration Manual
P/N MMI-20015441, Rev. AA July 2009
Micro Motion® 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
©2009, Micro Motion, Inc. All rights reserved. Viscomaster is a registered trademark, and Viscomaster Dynamic is a trademark of one of the companies of Emerson Electric Co. Micro Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. All other trademarks are property of their respective owners.
Micro Motion pursues a policy of continuous development and product improvement. The specification in this document may therefore be changed without notice. To the best of our knowledge, the information contained in this document is accurate and Micro Motion cannot be held responsible for any errors, omissions, or other misinformation contained herein. No part of this document may be photocopied or reproduced without prior written consent of Micro Motion.
Contents
Chapter 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Safety guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 About the meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.1 What is it? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.2 7829 Viscomaster meter measurements . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2.3 7829 Viscomaster Dynamic meter measurements . . . . . . . . . . . . . . . . . . 2
1.2.4 What is it used for? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Installation effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2.1 Boundary effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2.2 Fluid at the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2.3 Thermal effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2.4 Entrained gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.5 Solids contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.6 Vibration effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 General fitting notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Standard installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Meter orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.3 Flow-through chamber installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4.4 VAF Viscosense retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.5 VAF Viscotherm retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.6 During normal running . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.7 Removal and refitting procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 3 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.2 Installation considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.1 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.2 EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.3 Ground connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.4 Cabling requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.5 Surge protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.6 Installation in explosive areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.3 Wiring the meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4 Power supply input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.5 Modbus (RS-485) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.6 4-20 mA outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.7 Wiring procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.8 Further information on RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.8.1 RS-485. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.8.2 RS-485 to RS-232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installation and Configuration Manual i
Contents
3.8.3 RS-485 multi-drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.8.4 Transmission mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Chapter 4 Using ADView and ProLink II . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.1 Using ADView software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.1.1 What is ADView? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.1.2 Installing ADView . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.1.3 Starting ADView. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.1.4 Understanding ADView features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.2 Using ProLink II software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2.2 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2.3 Connecting from a PC to a meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2.4 ProLink II configuration upload/download . . . . . . . . . . . . . . . . . . . . . . . . 46
4.2.5 ProLink II language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 5 Calibration Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1.1 Factory calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1.2 Calibration of Transfer Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1.3 Instrument calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.1.4 General viscosity equation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.1.5 General density equation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.2 Calibration certificate examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.2.1 Viscomaster sample calibration certificate . . . . . . . . . . . . . . . . . . . . . . . 49
5.2.2 Viscomaster Dynamic sample calibration certificate . . . . . . . . . . . . . . . . 50
5.3 User calibration checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.3.1 Ambient air calibration check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.3.2 On-line calibration adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Chapter 6 General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2 General maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2.1 Physical checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2.2 Electrical check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.2.3 Performance check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.2.4 Calibration check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.3 Fault analysis and remedial action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.3.1 Troubleshooting faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.3.2 Mechanical servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.3.3 Time period trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Appendix A Factory Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
A.1 Default configuration for analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Appendix B Calculated Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
B.2 Base density referral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
B.2.1 API density referral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
ii Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Contents
B.3 Kinematic viscosity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
B.4 Base kinematic viscosity referral using ASTM D341 . . . . . . . . . . . . . . . . . . . . . . . . . 63
B.5 Ignition quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix C Safety Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
C.1 Safety certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix D Modbus Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
D.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
D.2 Accessing Modbus registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
D.2.1 Establishing Modbus communications . . . . . . . . . . . . . . . . . . . . . . . . . . 68
D.3 Modbus implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
D.3.1 Register size and content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
D.4 Modbus register assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
D.5 Index codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
D.5.1 API product type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
D.5.2 Pressure, Temperature, Density and other Units . . . . . . . . . . . . . . . . . . . 73
D.5.3 Output averaging time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
D.5.4 Analog output selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
D.5.5 Referral temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
D.5.6 Software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
D.5.7 Hardware type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
D.5.8 Unit type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
D.5.9 Status register flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
D.5.10 Line dynamic viscosity units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
D.6 Establishing Modbus communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
D.7 Example of direct Modbus access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
D.7.1 Example 1: Reading line density (16-bit register size) . . . . . . . . . . . . . . 78
D.7.2 Example 2: Reading line density (32-bit register size) . . . . . . . . . . . . . . 79
Appendix E Product Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
E.1 Density / temperature relationship of hydrocarbon products. . . . . . . . . . . . . . . . . . . 81
E.1.1 Crude oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
E.1.2 Refined products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
E.1.3 Platinum resistance law . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
E.1.4 Density of ambient air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
E.1.5 Density of water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
E.1.6 Velocity of sound in liquids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Appendix F Return Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
F.1 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
F.2 New and unused equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
F.3 Used equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Installation and Configuration Manual iii
Contents
iv Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Chapter 1

Introduction

1.1 Safety guidelines

Handle the 7829 Viscomaster
Do not drop the meter.
Do not use liquids incompatible with materials of construction.
Do not operate the meter above its rated pressure or maximum temperature.
Do not pressure test beyond the specified test pressure.
Ensure all explosion-proof requirements have been applied.
Ensure the meter and associated pipework are pressure tested to 1-1/2 times the maximum operating pressure after installation.
Always store and transport the meter in its original packaging, including the transit cover secured by grub screws.
To return a meter, refer to the Return Policy appendix for more information on the Micro Motion return policy.
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
®
/ Viscomaster Dynamic™ viscosity meter with great care.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction

1.2 About the meter

1.2.1 What is it?

The 7829 Viscomaster the proven tuning fork technology of Micro Motion. It is an all-welded sensor designed to be mounted directly into a pipeline or in a tank. Viscosity and density are determined from the resonance of the tuning fork immersed in the fluid, and a temperature sensor (RTD) is also fitted within the meter.
The meter is available in a 316 stainless steel, and the immersed tines can be laminated with PFA to inhibit the build up of residues such as asphaltenes.
The meter contains integral processing electronics to provide full configuration, enabling it to perform a variety of calculations.
Installation and Configuration Manual 1
®
/ Viscomaster Dynamic™ viscosity meter is a digital viscosity meter, based on
Introduction
Two forms of output are available:
Note: The Viscomaster Dynamic meter’s analog output 2 is set to temperature and only the span, bias, and limits can be changed.
No signal converter is required, which simplifies wiring and enables the meter to be connected directly to a plant monitoring and control systems and/or a local indicator.
The meter is factory set to perform API density referral. Re-configuration of the meter’s default settings (see Appendix A) is achieved by linking a PC to the Modbus (RS-485) connection and running Micro Motion's ADView or ProLink II (v2.9 or later) software. Once configured, the PC can be removed.
Two off 4-20 mA analog outputs, factory set but have individually configurable span, bias, limits, and filter options. The standard factory settings for these outputs are Line Kinematic Viscosity on Analog Output 1 and Line Temperature on Analog Output 2. Alternatively, the analog outputs may be controlled by one of the following:
Line dynamic viscosity
Line density
Base or referred kinematic viscosity
Base or referred density (API or Matrix referral)
Line temperature
An RS-485 (Modbus) interface, giving access to other measurement results, system information and configuration parameters.

1.2.2 7829 Viscomaster meter measurements

The 7829 Viscomaster meter directly measures the following fluid properties:
Line dynamic viscosity – measured in centiPoise - cP.
Line Density – measured in kg/m
3
, g/cc, lb/gal, or lb/ft3.
Temperature – measured in °C or °F.
From these properties, the meter calculates:
Line and base (referred) kinematic viscosity – measured in centiStokes - cSt.
Line and base (referred) density – API or Matrix.
Referral is made to 15°C, 1.013 bar; or at 60°F, 14.5 psi.

1.2.3 7829 Viscomaster Dynamic meter measurements

The 7829 Viscomaster Dynamic meter directly measures the following fluid properties:
Line dynamic viscosity – measured in centiPoise - cP.
Temperature – measured in °C or °F.
From these properties, the meter calculates:
Line kinematic viscosity – measured in centiStokes - cSt.
Note: The line kinematic viscosity calculation requires the user input of a base (or reference) density value and a temperature (at which the base density value is valid).
2 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Introduction

1.2.4 What is it used for?

The 7829 Viscomaster the viscosity of Heavy Fuel Oil (HFO) used by power plants. This is typically achieved by adjusting the heating of incoming HFO to maintain the viscosity within the limits set by the engine manufacturer.
HFO is a low cost, high viscosity fuel derived from refinery wastes. The quality of the oil and its viscosity/temperature characteristics can vary due to:
HFO heating is usually required to ensure that the viscosity of the oil at the injectors of a large diesel engine or burner nozzle is maintained at the optimum value (typically between 10 cSt and 20 cSt). Failure to observe the viscosity limits results in inefficient combustion, pollution problems and higher operating costs (either due to excessive fuel being burnt or premature wear to engine components).
Since simple temperature control has been shown to be ineffective due to the variability of oil quality in HFO, viscosity control is usually performed.
A typical HFO fuel circuit is shown in Figure 1-1.
®
/ Viscomaster Dynamic™ viscosity meter is designed specifically to control
Stratification within storage tanks.
Contamination in transit storage.
Variations in the production process at the refinery or at the blending plant.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Note: In some installations, equipment may be installed in between the viscosity transmitter and the burner / engine to remove contaminants from the fuel; the efficient operation of this equipment may also depend on the viscosity of the HFO.
Installation and Configuration Manual 3
Introduction
1 HFO fuel tank 2 Mixer 3 Re-circulation pump 4 Fuel heater 5 Control valve 6 Viscomaster
7 Heater Controller 8 Personal Computer (PC) 9 Engine Management Computer 10 Burner or 11 Large Diesel Engine 12 Unburned fuel return
Figure 1-1 Typical HFO Fuel Circuit
4 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Chapter 2

Installation

2.1 Introduction

All drawings and dimensions given in this manual are given here for planning purposes only. Before commencing fabrication, reference should always be made to the current issue of the appropriate drawings. Contact Micro Motion for details.
For further information on handling and using the meter, see “Safety guidelines” on page 1
There are a variety of external factors that affect the ability of the 7829 Viscomaster Dynamic correctly, the effects of these factors must be taken into consideration when designing your installation.
There are two main aspects to consider:
viscosity meter to operate successfully. In order to ensure that your system works
The accuracy and repeatability of the measurements
®
/ Viscomaster
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
The relevance of the measurements to the overall purpose of the system
Factors which may adversely affect accuracy and repeatability include:
The presence of gas or bubbles within the fluid being measured
Non-uniformity of the fluid
The presence of solids as contaminants
Fouling of the meter
Temperature gradients
Cavitations and swirls
Operating at temperatures below the wax point of crude oils
The correct pipe diameter that corresponds to the calibration of the meter.
In some applications, absolute accuracy is less important than repeatability. For example, in a system where the control parameters are initially adjusted for optimum performance, and thereafter only checked periodically.
The term achievable accuracy can be used to describe a measure of the product quality that can be realistically obtained from a process system. It is a function of measurement accuracy, stability and system response. High accuracy alone is no guarantee of good product quality if the response time of the system is measured in tens of minutes, or if the measurement bears little relevance to the operation of the system. Similarly, systems which require constant calibration and maintenance cannot achieve good achievable accuracy.
Installation and Configuration Manual 5
Installation
long axis
short
axis
Factors which may adversely affect the relevance of the measurements could include:
Measurement used for control purposes being made too far away from the point of control, so that the system cannot respond properly to changes.
Measurements made on fluid which is unrepresentative of the main flow.

2.2 Installation effects

Unlike other Micro Motion meters, the vibrating tines of the 7829 Viscomaster Dynamic
viscosity meter are not totally enclosed. The walls of the pipe or tank in which the meter is installed will introduce boundaries to the fluid flow, and this will have an effect on the calibration of the sensor.
To overcome this, Micro Motion calibrates the meter under a variety of pre-defined conditions corresponding to the installation and pipe schedule. This condition is selected when ordering the 7829 Viscomaster the same boundary conditions as the installation, the need for additional on-site calibration is eliminated.

2.2.1 Boundary effects

®
/ Viscomaster
®
/ Viscomaster Dynamic™ viscosity meter, so that by calibrating the meter under
Any insertion device or meter can only measure the properties of the fluid within the region of fluid to which it is sensitive.
For practical reasons, it is helpful to consider the sensitive, or effective region, for the viscometer as an ovoid centered on the tips of the tines with its long axis aligned with the direction in which the tines vibrate, as shown below. The meter is insensitive to the properties of the fluid outside this region and progressively more sensitive to fluid properties the closer the fluid is to the tines. Density can be considered a “mass centered” effect and viscosity a “surface centered” effect in this visualization; i.e. the measurement of density is more uniformly sensitive to the density of fluid throughout the region while viscosity measurement is much more critically sensitive to fluid on the surface of the tines.
If part of this volume is taken up by the pipework or fittings there is said to be a boundary effect; i.e., the intrusion of the pipe walls will alter the calibration. The diagram below illustrates the meter installed in a pocket on the side of a 4" (100 mm) horizontal pipe line (viewed from above). The effective region is completely enclosed within the pipe line and thus is completely fluid.
6 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
Top or Plan view
4” horizontal pipe
2”Schedule 40
Pocket or “T”
This next view shows other pipe outlines superimposed:
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Installation and Configuration Manual 7
The smaller circle represents a 4" (100 mm) vertical pipe, which because the meter orientation is constant irrespective of pipe orientation intersects the effective region. The 6" (150 mm) pipe is the smallest pipe diameter to completely enclose the effective region when the pipe is vertical. Thus smaller pipe diameters can lead to a variety of different geometries which would each require a separate calibration.
An alternative condition is shown in the next diagram where the side pocket is extended until it passes completely through the effective region producing a “core”:
Installation
From this, it would appear that almost every installation requires a separate in situ calibration – a very undesirable situation. The problem is resolved by providing standard calibration geometries which can be used in all pipe work configurations and thereby allow the factory calibration conditions to be reproduced in the process.

2.2.2 Fluid at the sensor

The fluid in the effective zone of the meter must be of uniform composition and at uniform temperature. It must be representative of the fluid flow as a whole.
This is achieved either by mixing of the fluid either using a static inline mixer or taking advantage of any natural pipe condition that tends to cause mixing, such as pump discharge, partially open valves. The viscometer should be installed downstream where the flow is just returning to laminar flow conditions.

2.2.3 Thermal effects

Avoid temperature gradients in the fluid and in the pipe work and fittings immediately upstream and downstream of the viscometer.
Always insulate the viscometer and surrounding pipework thoroughly. Insulation must be at least 1" (25 mm) of rockwool, preferably 2" (50 mm) (or equivalent insulating heat jacket) and enclosed in a sealed protective casing to prevent moisture ingress, air circulation, and crushing of the insulation. Special insulation jackets are available from Micro Motion for the flow-through chambers, which, because of the low volumetric flow rates and hence low heat flow, are more vulnerable to temperature effects.
Avoid direct heating or cooling of the viscometer and associated pipe work upstream and downstream that is likely to create temperature gradients. If it is necessary to provide protection against cooling due to loss of flow, electrical trace heating may be applied, provided it is thermostatically controlled and the thermostat is set to operate below the minimum operating temperature of the system.
8 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation

2.2.4 Entrained gas

Gas pockets can disrupt the measurement. A brief disruption in the signal caused by transient gas pockets can be negated in the signal conditioning software, but more frequent disruptions or serious gas entrainment must be avoided. This can be achieved by observing the following conditions:

2.2.5 Solids contamination

Keep pipe lines fully flooded at all times
Vent any gas prior to the viscometer
Avoid sudden pressure drops or temperature changes which may cause dissolved gases to break out of the fluid
Maintain a back pressure on the system sufficient to prevent gas break out (e.g. back pressure equivalent to twice the ‘head loss’ plus twice the vapour pressure)
Maintain flow velocity at the sensor within the specified limits.
Avoid sudden changes of velocity that may cause sedimentation.
Install the viscometer far enough downstream from any pipework configuration which may cause centrifuging of solids (e.g. bends).
Maintain flow velocity at the sensor within the specified limits.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Use filtration if necessary.

2.2.6 Vibration effects

The 7829 Viscomaster severe vibration conditions, both in the test laboratory and Marine/Power Station/Burner applications. The meter is approved according to the Lloyds Register standard, levels ENV 1, 2 and 3 and operates correctly up to the classification level of ENV4 (vibration test 2). This vibration level, ENV 4 includes correct operation at vibration levels of 4 g rms between frequencies of 5–100 Hz, and is used to describe the requirements for engine mounted equipment.
If vibration levels exceed these limits, or the meters are not installed as recommended by Micro Motion, Micro Motion cannot take responsibility for the correct operation of these units.

2.3 General fitting notes

The 7829 Viscomaster which requires no seals, minimizing maintenance and spares. These fittings are leak proof over a wide range of pressure and temperature conditions, and during rapid temperature cycling, which may occur during the transfer from HFO to distillate fuel.
The meter should normally be installed horizontally, with the slot between the tines vertical; this ensures that, for low flow rates, any solids or gas bubbles are not trapped. When installed in a flow-through chamber, however, provided that the flow rate is within the recommended range, the transmitter can be mounted horizontally or vertically.
Allow at least 7.8” (200 mm) clearance to enable the meter to be removed from the fitting.
®
/ Viscomaster Dynamic™ viscosity meter has been extensively tested under
®
/ Viscomaster Dynamic™ viscosity meter uses a 1.5” Swagelok style of fitting
Installation and Configuration Manual 9
Installation

2.4 Standard installations

2.4.1 Overview

To overcome the need for in situ calibration for every installation, three standard installations are proposed. If an installation conforms to one of these standards, the factory calibration of the 7829 Visc o master
®
/ Viscomaster Dynamic™ viscosity meter is valid, and in-situ calibration unnecessary.
The three installations are summarized in Table 2-1.
Note: Higher flow rate installations (up to 100 m for details.
Table 2-1. Descriptions of standard installations
3
/hr) can be accommodated. Contact Micro Motion
Standard installation
Description
Flow rate
(1)
Viscosity
VAF VISCOTHERM / NAKAKITA Retrofit
Viscomaster tines project into adapter kit with 2½“ Schedule 40 boundary.
10 to 330 l/min (0.6 to 20 m (2.6 to 87 US gal./min).
Up to 100 cSt. Up to 100 cSt Up to 100 cSt.
3
/hr)
VAF VISCOSENSE Retrofit Flow-through chamber
Viscomaster tines are contained in a side pocket off the main flow, recessed by
25.4 mm (1 inch).
10 to 330 l/min (0.6 to 20 m (2.6 to 87 US gal./min).
3
/hr)
Viscomaster tines are contained in a flow-through chamber in which fluid is circulated from the main flow.
10 to 330 l/min (0.6 to 20 m (2.6 to 87 US gal./min).
limits
Tem perature
Main flow pipe size
-50 to 200°C (-58 to 392°F).
As defined by capillary Viscomaster chamber.
• Simple replacement of capillary viscometer.
• Fast response.
• Good flow and temperature conditioning.
Advantages
(1) Viscomaster tines project into adapter kit with 2-½“ Schedule 40 boundary and retracted by 1” (25 mm).
-50 to 200°C (-58 to 392°F).
50 mm (2"). 50 mm (2").
• Simple replacement of torsional viscometer.
• Fast response.
• Good flow and temperature conditioning.
-50 to 200°C (-58 to 392°F).
• Adaptable installation to any diameter main pipe and for tank applications.
• Ideal for flow and temperature conditioning.
• Fast response.
3
/hr)
10 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
To engine
Direct 4-20mA
Direct 4-20mA
Alarms
Relays
Fuel oil
Direct 4-20mA
Heating fluid
Control valve
Visc5.7 cSt Temp 124°C
Key
1 In-line viscometer replacement 2 Capillary viscometer replacement 3 Micro Motion flow through chamber
1
3
2
Fuel oil heat exchanger
These three types of standard installation are graphically shown in the following schematic.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction

2.4.2 Meter orientation

The meter must always be installed horizontally, and orientated to allow flow in the gap between the tines. This is irrespective of the pipe line orientation, and helps to prevent the trapping of bubbles or solids on the meter.
Installation and Configuration Manual 11
Installation
Bubbles rise!
Solids sink!
the slot must be
vertical
.
For ALL pipe and flow directions
.
the meter
must be
horizontal
Figure 2-1 Meter orientation
Note: All drawings and dimensions given in the following sections are derived from detailed dimensional drawings. They are given here for planning purposes only. Before commencing fabrication, reference should always be made to the current issue of the appropriate drawings ­contact Micro Motion for details.

2.4.3 Flow-through chamber installation

Flow-through chambers are fabricated by Micro Motion, and are available with either weld prepared ends or with flange or compression fittings for connection into the process pipe lines. They are available with 2" NB inlet and outlet pipes.
Note: The length of the inlet and outlet pipes must not be altered, otherwise the temperature response and stability of the fitting may be adversely affected.
Conditions:
Flow: constant, 5–300 l/min for 3" sch 80 calibration bore.
Viscosity: 0.5 to 100 cP
Temperature: -50 °C to 200 °C (–58 °F to 392 °F)
[-40 °C to 200 °C (-40 °F to 392 °F) in hazardous areas]
Pressure: 70 bar @ 204 °C, subject to process connections.
The PT100 is a direct insertion type, without a thermowell, and uses a ¾" Swagelok connection.
The diagram below shows an example of this type of standard installation.
12 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
Dimensions shown in inches (mm)
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
The three compression fittings on the flow pockets (½" drain, ¾" temp probe, and 1-½" mounting nut for the meter) are rated to above the working pressure of the flow pocket. The fittings may be Swagelok or Parker; both are used in manufacture.
The fittings are certified to the following standards:
Swagelok: SO9001 / 9002, ASME,TUV,CSA,DNV
Parker: ISO 9001 / 9002, TUV, DNV, LLOYDS

2.4.4 VAF Viscosense retrofit

Conditions:
Temperature: -50 to +200 °C (–58 °F to 392 °F)
Flow: 40 to 330 l/min (2.5 to 20 m
Viscosity limit: Up to 100 cSt
Pressure: As defined by process flanges
Calibration boundary: 2-½” Schedule 40
This retro-fit kit has been specifically designed to provide a simple, direct replacement for existing vibration-type viscometers. Typically, the flange-to-flange distance is 5.9” (150 mm), although other larger versions can be accommodated (contact Micro Motion for details of the Universal retro-fit adapter). Usually, no pipework changes are necessary.
3
/hr) (11 to 87 US gal/min)
Installation and Configuration Manual 13
Installation
The 7829 Viscomaster® / Viscomaster Dynamic™ viscosity meter is mounted 0.98” (25 mm) away from the main flow line, allowing good product mixing, sensor protection and stable measurement conditions.
Typical dimensions are shown in Figure 2-2.
Note: The schematic shown may vary without notice, although overall dimensions will remain unchanged.
14 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
14.49 (368)
5.9 (150)
150 mm unit shown DN50 PN16 flanges shown
Dimensions shown in inches (mm)
Figure 2-2 VAF Viscosense retrofit dimensions
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Installation and Configuration Manual 15
Installation

2.4.5 VAF Viscotherm retrofit

Conditions:
This retro-fit kit has been specifically designed to provide a simple, direct replacement for existing capillary viscometers. Typically, these viscometers are designed to operate with their own measurement chamber, to which this adapter will be attached. No pipework changes are necessary.
Typical dimensions are shown in Figure 2-3.
Note: The schematic shown may vary without notice, although overall dimensions will remain unchanged.
Temperature: -50 to +200°C (–58 °F to 392 °F)
Flow: 40 to 330 l/min (2.5 to 20 m
3
/hr) (11 to 87 US gal/min)
Viscosity limit: Up to 100 cSt
Pressure: As defined by process flanges
Calibration boundary: 2–½” Schedule 40
16 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
Dimensions shown in inches (mm)
1.57
(40)
11.85 (301)
4.5 (115)
Ø 6.3 (160)
Figure 2-3 VAF Viscotherm retrofit dimensions
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Installation and Configuration Manual 17
Installation

2.5 Commissioning

1. Once the pipework installation has been prepared, and before installing the 7829 Viscomaster / Viscomaster Dynamic nut to the meter mounting, and pressurise and flush the system.
2. Isolate the system, depressurize and remove the blanking compression nut.
3. Install the meter, and tighten the fitting nut, but do not fit the thermal insulation.
4. Slowly pressurize the system and check for leaks, particularly if the normal operating temperature is high, or the meter has been fitted cold; tighten as necessary.
5. Now tighten the nut again, if necessary. Once you are satisfied with the integrity of the seal, the insulation can be fitted.
6. Once the system has stabilized and is leak free, fit the insulation material.

2.6 During normal running

Observe and record the normal operating temperatures and viscosity readings. You can monitor the system using ADView or ProLink II. (See the Using ADView and ProLink II chapter.)
When several systems are run in parallel and use the same fuel source, comparison of the readings between installations can be a useful indicator of possible system faults. Differences between readings or changes from the normally observed conditions should always be investigated to confirm that instrumentation is functioning correctly.
Particular attention should be paid to the conditions before and after engine shutdowns in order to detect any possibility of asphaltenes coating (precipitation of asphaltenes from the HFO caused by dilution with distillate fuel) which may cause the instrument to read high. If the re-circulation flow is high enough or the instruments have been supplied with PFA coating, asphaltenes or any other deposits should quickly be removed and the expected operating temperatures should be restored.
If the meter is still reading high and the oil quality is known not to have changed, then the instrument should be removed and cleaned with a rag. Removal should only be performed in accordance with the engine or burner manufacturers’ recommendations or in accordance with safe site practice. This must include isolation and depressurization.
viscosity meter and thermal insulation, fit a blanking compression
®

2.7 Removal and refitting procedure

All national and international safety regulations should be observed.
Observe safe working practice, wear protective clothing and safety glasses, and use suitable gloves to prevent burns or absorption of hot oil.
Check that the isolation valves have been fully closed, remove insulation and allow to cool to a safe level (cooling will tend to reduce any retained pressure) and de-pressurize the system if a drain valve or pressure relieving valve is fitted.
18 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Installation
When the above conditions are satisfied, slacken the lock nut by 1-½ to 2 turns, sufficient for the sensor to be rocked. (If necessary, jolt the meter loose with a blow of the hand to the amplifier housing.) This will allow the seal between the sensor and the chamber retro-fit kit to be broken. Do not slacken the lock nut further unless the seal is broken and the sensor is definitely loose in the fitting.
Note: If the system is still pressurized, the meter may lift and be held against the retaining nut. Rocking and alternately pushing the sensor in and out of the pocket within the limits allowed by the slackened nut will break any seal and allow oil under pressure to seep past the lock nut. If this leakage is excessive, re-tighten the lock nut and take further action to de-pressurize the system.
When the meter can be rocked in the flow chamber and there is no serious or continuous escape of oil, it is safe to remove the lock nut.
Always keep all parts of your body away from the axis of the sensor (i.e., the direction in which the sensor will be withdrawn). If the system is under pressure or suddenly comes under pressure (e.g., due to valve failure or pump start), and the lock nut is not in place, the instrument may be forcibly ejected from the flow chamber and cause serious injury.
Clean and maintain the meter as directed and then refit it, as described in Section 2.5.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
Installation and Configuration Manual 19
Installation
20 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters

Electrical Connections

Chapter 3
Electrical Connections
For installations in hazardous areas:
For ATEX installations, the electrical installation must strictly adhere to the safety information given in the ATEX safety instructions booklet shipped with this manual. See Section 1.1 for important information.
For installations in USA and Canada, the electrical installation must strictly adhere to the Electrical Codes and a conduit seal is required within 2” (50 mm) of the enclosure.

3.1 Introduction

®
The 7829 Viscomaster
Two 4-20mA analog outputs
/ Viscomaster Dynamic™ viscosity meter has two types of output:
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
The Viscomaster Dynamic has a single fully configurable output proportional to a user-specified parameter. The Viscomas t e r has two fully configurable outputs.
The parameters that can be output on each analog output are as follows:
Note: In all cases, the limit values of each analog output are configurable.
Viscomaster Dynamic Viscomaster
Analog Output 1 Analog Output 2 Analog Output 1 Analog Output 2
Dynamic viscosity (cP) Temperature
Kinematic viscosity (cSt)
Line density Temperature
Temperature Line density Line density
(1) Factory default selection.
(1)
(1)
Dynamic viscosity (cP) Dynamic viscosity (cP)
Kinematic viscosity (cSt)
Referred density Referred density
Referred viscosity Referred viscosity
CII CII
CCAI CCAI
(1)
Kinematic viscosity (cSt)
Temperature
(1)
A Modbus (RS-485) interface, giving access to other measurement results, system information
and configuration parameters. The Modbus interface is also used to configure the meter, using a PC running the Micro Motion ADView or ProLink II software (see Using ADView and ProLink II chapter).
Installation and Configuration Manual 21
Electrical Connections
It is recommended that both outputs are installed, requiring a minimum of eight wires (two for each output, and two for power). Although you may not immediately require the Modbus connection, it may be required for in-situ calibration adjustment and future system enhancements, and the cost of the additional wires is trivial compared to the expense of installing them retrospectively.
A number of factors must be taken into account when planning the electrical installation. These include:
•Power supply
•EMC
Ground connections
•Cables
Surge protection
Installation in explosive area
Modbus connections
Analog connections.

3.2 Installation considerations

3.2.1 Power supply

®
The power supply to the 7829 Viscomaster
/ Viscomaster Dynamic™ viscosity meter must have the
following requirements:
Voltage: Nominally 24 VDC, but in the range 20 to 28 VDC.
Current: for transmitter – 50 mA; for mA outputs – 22 mA per output.
If several meters are to be used within a local area, one power supply can be used to power them all; where the meters are distributed over a wide area and cabling costs are high, it may be more cost effective to use several smaller, local power supplies.
Upon leaving the factory, the two 4-20 mA analog outputs are non-isolated as they are powered through internal links to the power supply input. However, if split-pads “LNK A” (Analog Output 1) and “LNK B” (Analog Output 2) by the terminal block are ‘broken’, they become isolated and require a separate 20-28 VDC power supply (see the 4–20 mA outputs section for details).
If an RS-232 to RS-485 converter is used (for example to connect to a serial port on a PC), this may also require a power supply (see the Further information on RS-485 section for details).
Care should be taken where there is the possibility of significant common-mode voltages between different parts of the system. For example, if the meter is locally powered from a power supply which is at a different potential to the RS-485 ground connection (if used).

3.2.2 EMC

To meet the EC Directive for EMC (Electromagnetic Compatibility), it is recommended that the meter be connected using a suitable instrumentation cable containing an overall screen. This should be earthed at both ends of the cable. At the meter, the screen can be earthed to the meter body (and therefore to the pipework), using a conductive cable gland.
22 Micro Motion 7829 Viscomaster® and Viscomaster Dynamic™ Viscosity Meters
Electrical Connections

3.2.3 Ground connections

It is not necessary to earth the meter through a separate connection; this is usually achieved directly through the metalwork of the installation.
The electronics and communications connections (RS-485/Modbus and 4-20 mA analog output) of the meter are not connected to the body of the meter. This means that the negative terminal of the power supply can be at a different potential to the earthed bodywork.
In the majority of applications, it is not necessary to connect the RS-485 ground connection. In areas where there is a significant amount of electrical noise, higher communications integrity may be obtained by connecting the negative power terminal (pin 2) of the meter to the communications ground. If this is done, it is important to ensure that the possibility of ground loops (caused by differences in earth potential) is eliminated.

3.2.4 Cabling requirements

Although it is possible to connect separate cables to the meter for power, RS-485 and the 4-20 mA analog output, it is recommended that all connections are made through one instrumentation-grade cable.
Connections for the Analog and Modbus signals should be individually screened twisted-pairs with an overall screen, foil or braid for the cable. Where permissible, the screen should be connected to earth at both ends. (At the meter, this is best done using a conductive cable gland.)
Cables should conform to BS2538. In the USA, use Belden 9402 (two-pair) or Beldon 85220 (single-pair). Other cables that are suitable are those that meet BS5308 Multi-pair Instrumentation Types 1 and 2, Belden Types 9500, 9873, 9874, 9773, 9774 etc.
The typical maximum recommended cable length for the above cable types is 1000 m (3200 ft), but care must be taken to ensure that the power supply at the meter is at least 20 V. Thus, for 24 V power supply, the overall resistance for the power supply connections (both wires in series) must be less than 100 ohms.
Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction Installation Using ADView and ProLink IIElectrical ConnectionsIntroduction
In order to complete the wiring, you will need the following parts:
½” NPT to M20 gland adapter
½” NPT blanking plug
M20 x 1 cable gland (not supplied).
The gland adapter and blanking plug are supplied with the meter – these two parts are Exd rated. However, you will need to get a suitably rated cable gland:
For non-hazardous area installations, use an IP68 or higher rated cable gland.
For hazardous area installations use an Exd-rated cable gland.
In hazardous areas, all parts must be explosion-proof. Alternative parts may be required in order to meet local electrical installation regulations.

3.2.5 Surge protection

Careful consideration should be given to the likelihood of power supply surges or lightning strikes. The power supply connections of the meter have a surge arrestor fitted that gives protection against power supply transients.
If there is a possibility of lightning strikes, external surge protection devices - one for each pair of signals and the power supply - should be installed as close to the meter as possible.
Installation and Configuration Manual 23
Loading...
+ 67 hidden pages