Emerson 7000 User Manual 3

Operator’s
y
pp
7000 Series Medium-Voltage
Automatic Transfer Switches
4.76, 15.0, 27 kV; 1200, 2000, 3000 ampere
DANGER
!
DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
WARNING
!
CAUTION
!
Refer to the outline and wiring drawings provided with your 7000 Series ATS for all installation and connection details and accessories.
Refer to the Group 5 Controller User’s Guide 381333-126 for ATS status display messages, time dela
s, pickup & dropout settings, & adjustments.
ASCO 7000 Series Medium-Voltage Automatic Transfer Switches (ATS) are designed to ANSI C37.20.2 standard for metal-clad switchgear and are UL 1008A Listed.
Nameplate and Rating Label
The nameplate includes data for each specific automatic transfer switch. Use the ATS only within the limits shown on this nameplate. Each ATS has a rating label to define the loads, interrupting, short-time, and close & latch ratings. Refer to the label for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
This equipment is designed for use with dangerous levels of power from multiple sources. Additionally, voltage transformers and standby control power sources (i.e. station battery system, UPS) included in the equipment must be disconnected when servicing this equipment. Persons installing, servicing, and operating this equipment must be trained, licensed appropriately, and familiar with medium voltage electrical power equipment and adhere to required a
arel, protection, tools, controls, and procedures.
WARNING
!
Table of Contents
Catalog No., major components view...............i
INSTALLATION
Mounting, Connections ................................1-1
OPERATION
Energizing ATS after Installation..................2-1
Controller, Lock-out relay (optional)............. 2-2
Transfer Test ATS, ACTS, ADTS ..2-3, 2-4, 2-5
Typical 7000 Series MV ATS, 1200 A
TROUBLESHOOTING
ATS, ACTS, ADTS.........................3-1, 3-2, 3-3
INDEX...............................................back page
381333-395
i Catalog Number 381333-395
g
(
)
(
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a 7000 Series Automatic Transfer Switch, class A interrupting rating, automatic, open-transition transfer, dual­circuit breaker, 3 pole, 1200 ampere, 6.6 kV 60 Hz, in a Type 1 enclosure.
Fixed elements
Catalo
Number
Variable elements
Interrupting
Rating
A = 25 kAIC B = 40 kAIC C = 50 kAIC D = 16 kAIC
NOTE Interrupting rating A (25 kAIC) is not available for voltage ratings below 5 kV.
Product Series
7 = 7000
Operation
Type
A = Automatic N = Non-auto
Emergency Source Circuit Breaker
Emergency source Breaker Control switch
Device Type
M = dual CB transfer
Poles
3 = 3 pole
Controller
5 = Group 5
A 7 A T M 0 3 1200 6 5 X C
Transition
Type
blank = Open C = Closed D = Delayed S = Soft load
Construction
T = Transfer (non-soft load) L = Soft load transfer U = Service entrance (Normal) G = Service entrance (Emerg) P = Service entrance (N & E)
Transfer Switch
CB SECTION
Neutral
Type
0 = None A = Solid
Amperes
1200 2000 3000
CONTROL SECTION)
Voltage
T = 2.4 kV U = 4.16 kV V = 11 kV W = 12.47 kV X = 13.2 kV Z = 14.4 kV 3 = 3.3 kV 6 = 6.6 kV 7 = 7.2 kV 8 = 10 kV 9 = 13.8 kV O = Other
Controls
Accessories
X = yes Z = special
Enclosure
Type
C = 1 M = 3R (secure)
Voltage transformer
Transfer control & lights
Controller
Normal Source Breaker Control switch
Transfer Switch control
Customer
Normal Source
terminal block
Circuit Breaker
Voltage transformer
Typical 7000 Series MV ATS with location of major components (1200 amp shown)
381333-395 Installation 1-1
Installation
The ASCO 7000 Series Medium-Voltage Automatic Transfer Switch (ATS) is factory wired and tested.
Refer to the manual from the manufacturer of the metal-clad switchgear for section handling, installation, power connections, and testing.
Supporting Structure
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the transfer switch for all mounting details including door opening space.
Mounting
Refer to the outline and mounting diagram and mount the automatic transfer switch according to details and instructions shown on the diagram.
Protect the transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the transfer switch.
NOTICE
Testing Power Conductors
Engine-Generator Control Connections
All customer connections, including the engine control contact connections, are located on terminal block TB. This terminal block is located on the interior left side of the control section. Refer to the wiring diagram provided with the automatic transfer switch. Connect the engine start wires to the appropriate terminals. See Figure 1-1 and Table A.
Table A. Engine-generator control contacts
When normal source fails TB terminals
contact closes TB1 and TB2 contact opens TB1 and TB3
engine­generator control contacts
1 2 3
Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs, and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.
Line Connections
Refer to the wiring diagram provided with the transfer switch. All wiring must be made in accordance with the National Electrical Code and local codes.
DANGER
!
De-energize all conductors, open all circuit breakers, and rack out all voltage transformers before making any connections. De-energize any UPS, station battery system, or any similar system providing standby control power. Be sure that the Normal and Emergency line connections are in proper phase rotation. Place the engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Figure 1-1. Customer terminal block TB in controls section.
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on terminal block TB as shown on the wiring diagram provided with the automatic transfer switch.
2-1 Operation 381333-395
(
)
Configuration of Shipped ATS
CB SECTION) (CONTROL SECTION
The MV ATS is shipped with the circuit breakers and controls in the following state:
ON CB SECTION(S) - Circuit Breakers, check these items
Emergency source
circuit breaker
control switch
Normal source circuit breaker (CBN) in the OPEN position with the closing spring discharged.
Emergency source circuit breaker (CBE) in the OPEN position with the closing spring discharged.
Normal source circuit breaker control switch (53CBN) in the TRIP position (green target displayed on control switch)
Emergency source circuit breaker control switch (53CBE) in the TRIP position (green target displayed on control switch)
Transfer Switch
control switch
ON CONTROL SECTION – Controls, check this item
Transfer Switch Auto-Man selector switch (53AM) in the MAN (manual) position.
Circuit breaker
position lights
green=CB open
red=CB closed
Breaker control
target indicator
green=tripped
red=closed
Figure 2-2. Control switches
Be sure to close both enclosure doors before proceeding to prevent personal injury in case of electrical system fault.
Normal source circuit breaker control switch
Figure 2-1. Location of control switches
WARNING
!
Energizing the Normal Source, Setting Automatic Operation Mode
After the MV ATS is installed, the Normal source can be energized. Then the controls can be set for automatic (standby) operation. The Normal and Emergency sources must be available. Follow this procedure:
ON CONTROL SECTION – Controls, check these items
The transfer control indicator lights Normal Source Accepted and TS Locked Out should be on. The controller display should show that the transfer switch is Locked Out.
ON CB SECTION(S) - Circuit Breakers, check these items
Normal source circuit breaker control switch should indicate that the circuit breaker is OPEN (green light). Emergency source circuit breaker control switch should indicate that the circuit breaker is OPEN (green light).
Energizing procedure
1. On Control Section, turn the Transfer Switch Auto-Man selector switch to the AUTO (automatic) position.
2. On CB Section, turn the Normal source circuit breaker control switch to CLOSE position (red target window).
3. On CB Section, turn the Emergency source circuit breaker control switch to the CLOSE position (red target).
4. On Control Section, press the transfer controls Alarm Reset button. Normal source circuit breaker should close. The Normal source CB control switch should indicate that the circuit breaker is CLOSED (red light).
The ATS is now in an automatic (standby) operating mode. Proceed to transfer test.
Loading...
+ 8 hidden pages