Emerson 7000 User Manual

We Keep Your Power On
Series 7000
Power Switching and Control Solutions for
Critical and Distributed Power Applications
Healthcare Facilities
Web Hosting, Internet Data Centers
Telecom Central Offices
Process Manufacturing / Wafer Fabrication Plants /
Distributed Power / Load Management
Page 2
Critical Loads Demand ASCO
Series 7000
ASCO
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of power can create serious and even crippling financial losses, or impose dangers to life and safety.
ASCO Power Technologies (ASCO) provides the solutions to handle the transfer of critical loads to emergency sources reliably and with state of the art products. Using ASCO products can mean the difference between a minor inconvenience and a major catastrophe. You’ll find ASCO Power Transfer Switches wherever there is a critical load to be protected.
When flexibility in power switching is a must, ASCO offers a variety of product solutions to meet virtually every application require­ment, including distributed generation applications. That’s why the 7000 Series is available in open, delayed, closed and closed soft load configurations. Additionally, switched or overlapping neutral options provide for reliable operation of ground fault protection systems and reduction of voltage transients from unbalanced load switching.
ASCO Power Transfer Switches are the first CE Marked, IEC 60947­6-1 compliant Transfer Switches in the world which have been certified by a notified body of the European Union.
The Recognized Leader in Power Transfer Switch Technology
Conventional two-position transfer configuration,
plus closed and delayed transition modes of operation. All configurations available with either automatic or non-automatic control.
UL listed to 1008 Transfer Switch Equipment &
CSA certified to CSA 22.2 No.178-1978 Automatic Transfer Switches.
Independently qualified and certified to IEC 60947-6-1,
CE marked (optional). (Limited to certain accessories.)
Rated up to 600 VAC, 30 through 4000 amperes.
Reliable and field proven solenoid operating mechanism.
High withstand and close-on ratings including short
time withstand current rating for optimum flexibility in circuit breaker coordination (600-4000 amperes).
Solid, switched, or overlapping neutral conductor options.
ASCO Power Transfer Switches are the standard of the industry. High speed transfer of loads between alternate sources of power, regardless of ampacity size, is achieved by a reliable, field proven solenoid operating mechanism. When combined with a programmable microprocessor controller with keypad and LCD display, they offer the most advanced method of transferring all types of loads, such as motors, electronic drives, UPSs and microprocessor based systems. 7000 Series Power Transfer Switches are available open or enclosed, in ampacity sizes from 30 through 4000 amperes with the largest selection of optional accessories offered anywhere. All switching configurations are available with an integrally mounted bypass-isolation switch and/or rated for use in service entrance applications.
Front replaceable main and arcing contacts (600-4000 amperes).
Programmable microprocessor controller with keypad and
LCD display.
Centrally located terminal block for customer control
connections (260-4000 amperes).
16mm, industrial grade control switches and indicating lights.
Switch position LED indicators and source acceptability
lights.
Standard ground conductor connections.
Four auxiliary contacts, two contacts closed when switch
is in normal position and two contacts closed when switch is in emergency position.
Local/remote communications capability for interfacing
with ASCO PowerQuest
®
or SiteWebTMcommunication
products.
Page 3
7000 Series
7000 Series Power Transfer Switches Product Features
Offers the Most Advanced Transfer Switches in the World.
Fig. 1: Three Pole 7000 Series Automatic Transfer Switch
rated 1600 amperes (shown with optional front
connected terminals and Power Manager).
ASCO
Delayed Transition Transfer Switching
Fig. 3: Four pole, Delayed-Transition
Transfer Switch rated 2000 amperes.
ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time. Applications include older style variable frequency drives, rectifier banks, and load management applications.
Available 150 through 4000 amperes.
Utilizes reliable, field proven solenoid operating
mechanisms.
Mechanical interlocks to prevent direct connection of
both sources.
Indicator light (16mm, industrial grade
type LED) for load disconnect position.
Adjustable time delay for load disconnect position.
Closed-Transition Transfer Switching
ASCO Automatic Closed-Transition Transfer Switches feature main contacts that overlap, permitting the transfer of electrical loads without power interruption. The switch transfers in a make-before-break mode if both sources are within acceptable parameters. Control logic continuously monitors source conditions and automatically determines whether the load transfer should be open (conventional non-overlap mode) or closed transition. Available 150 through 4000 amperes.
Closed-Transition Transfer within 5 electrical degrees is achieved passively, without control of engine generator set. Therefore, no additional control wire runs are required between the ATS and engine generator set governor. Plus, protective relaying may not be required under normal operation since the contact overlap time is less than 100 milliseconds (consult your local utility on protective relay requirements).
Failure to synchronize indication and extended parallel time protection is built-in to all 7000 Series closed transition controls to prevent abnormal operation.
Fig. 2: Four pole, Closed-Transition Transfer
Switch rated 1000 amperes in Type 1 enclosure.
Page 4
7000 Series Power Switching Solutions
ASCO
-
-
-
150, 260, 400
600, 800
1000, 1200
1600, 2000
3000
4000
-
-
-
-
18
30
30
30
UL 1008 Withstand and Close-On Ratings at 480 Volts AC
Withstand and Close-On Ratings for all 7000 Series Products
(1)(2)
Notes: 1) All values are available symmetrical RMS amperes and tested in accordance with the withstand and close-on requirements of UL 1008.
See publication 1128 for more information on withstand and close-on ratings for ASCO transfer switches.
2) Application requirements may permit higher withstand ratings for certain size switches. Contact ASCO for guidance if available short circuit current exceeds the WCR ratings shown.
3) “Any” breaker ratings are based on 1.5 cycles for 30 - 230 amp & 3 cycles for 260 - 4000 amps. Applicable to breakers with instantaneous trip elements.
4) Short time ratings are provided for applications involving breakers that do not have instantaneous trips for system coordination.
5) Short time rating applicable to transfer switch design only.
6) Optional front connected service limited to 85,000 amps for specific and any breaker rating.
Non-Automatic Transfer Switching
ASCO Non-Automatic Transfer Switches are electrically operated units which are operated with manual control switches mounted locally or at remote locations.
Sizes from 30 through 4000 amperes.
Microprocessor based controller provides for addition
of optional accessories.
Controller prevents inadvertent operation under low
voltage conditions.
Low control circuit operating currents allow for long
line runs between remotely mounted manual control switches and the transfer switch.
Source acceptability lights inform operator if sources
are available to accept load.
Standard inphase monitor can be activated for
transferring motor loads.
Fig. 4: Three pole Non-Automatic,
electrically operated 400 ampere switch
shown in Type 1 enclosure.
Page 5
30
70, 100, 150, 200
230
260, 400
600, 800,
1000, 1200
1600, 2000
6
3000
4000
100,000
200,000
100,000
200,000
200,000
200,000
200,000
200,000
J
J
J
J
L
L
L
L
10,000
10,000
10,000
35,000
50,000
100,000
100,000
100,000
N/A
N/A
N/A
N/A
36,000
5
65,000
65,000
65,000
Short Time
Withstand Ratings(4)
Short Time
Duration
(Cycles)
“Any” Breaker
(3) Rating
Specific Breaker
Rating
10,000
22,000
22,000
42,000
65,000
100,000
100,000
100,000
Max. Fuse Type
amps
types
60
200
300
600
1600
3000
4000
6000
Current - Limiting
Fuse Rating
Bypass Switches
Transfer Switches
Switch Rating (Amps)
7000 Series Power Switching Solutions
ASCO
Automatic Transfer Bypass-Isolation Switching
ASCO Automatic Transfer & Bypass-Isolation Switches are available in open transition, closed transition and delayed transition designs. The bypass and isolation features allow power transfer switches to be inspected, tested, and maintained without any interruption of power to the load.
Available 150 to 4000 amperes.
Allows bypass-isolation without load interruption.
Bypass switch and transfer switch have identical electrical ratings.
Heavy duty mechanical interlocks prevent undesirable operation.
Bypass contacts carry current only during bypass mode.
Transfer switch is drawout design for ease of maintenance.
Bypass and isolation handles are permanently mounted. The bypass
switch has dead front quick-make, quick-break operation for transferring of loads between live sources.
Bypass switch is fully rated for use as a manual 3-position
transfer switch.
Bypass and isolation functions are simple, requiring a total of two
operating handles.
No toggle switches, push buttons, selector switches or levers are
required for bypass-isolation operation.
Mechanical indicators show bypass and transfer switch positions.
Fig. 5: Three Pole 7000 Series Automatic Bypass-
Isolation Transfer Switch Rated 1000 Amps
Transfer Switch Drawout Features (600-3000 amperes)
Automatic secondary disconnects
remove all control power as switch is withdrawn.
Drawout carriage provides for easy
transfer switch maintenance and/or removal via commercially available breaker hoists.
For optional transfer switch lifting yoke,
specify accessory 82B.
For optional automatic shutters which
close when the transfer switch is withdrawn to provide bus isolation, specify accessory 82C.(1600-3000A only)
Automatic
Secondary
Disconnects
Automatic
Shutters
(optional)
Fig. 6: Bypass-Isolation Transfer
Switch secondary disconnects and
optional automatic shutters.
Page 6
Self
Aligning
Jaws
Fig. 7: Bypass-Isolation
Transfer Switch self
aligning power jaws.
7000 Series Power Switching Solutions
ASCO
Push in bypass handle and turn it counter clockwise
Page 7
Bypass Switch
E
L
N
Automatic Transfer Switch
Bypass Switch
E
L
N
Automatic Transfer Switch
Bypass Switch
E
L
N
Automatic Transfer Switch
Turn isolation handle counter clockwise until window shows “Test”
Mechanical isolation handle position
window (connected/test/isolate)
Padlocking provisions
Mechanical bypass switch position flags
Turn isolation handle counter clockwise until window shows “Isolate”
Bypass to Normal
Test Position
Isolation Position
Isolation Handle
Bypass Handle
Isolation Handle
Isolation Handle
Isolation handle
Bypass and Isolation Handles - Simple as 1, 2, 3
1
2
3
Key:
Represents Current Flow
In test position control panel remains energized to allow for electrical operation of a transfer switch.
7000 Series Power Switching Solutions
Fig. 9: Bypass-Isolation
Switch user interface
Source
availability
Bypass switch
position
Transfer
switch
position
Isolation handle position
Not in “auto” flashing LED
Fig. 8: Transfer Bypass
Status Panel
LED Indicators
ASCO
7000 Series Service Entrance Power Transfer Switches
The ASCO Service Entrance Power Transfer Switch combines automatic power switching with a
disconnect and overcurrent protective device on the utility source. The power transfer switch meets all National Electric Code requirements for installation at a facility’s main utility service entrance. Service entrance rated transfer switches generally are installed at facilities that have a single utility feed and a single emergency power source. A circuit breaker serves as the utility disconnect and links are provided to disconnect both neutral and ground connections.
This product is UL 1008 and UL 891 listed and is available up to 600V and 4000A in Standard, Delayed, Closed Transition, Soft Load, and Bypass Isolation Configurations.
Page 8
Standard Features
Available from 150 to 4000 amperes
ASCO 7000 Series Power Transfer Switch,
UL 1008 Listed
Standard UL Type 1 Enclosure
Disconnect and overcurrent protective device on
the utility source: molded case circuit breaker 150 to 2000 Amp; insulated case 3000 to 4000 Amp
Disconnect link on Neutral
Disconnect link on Ground
Ground and Neutral Bus, all silver-plated copper
Solderless screw type terminals for External
Power Connections
Labeled UL 891, meets all NEC requirements for
service entrance
Internet Enabled Command and control available with optional
ASCO SiteWeb™
Neutral
Disconnect
Link
Ground Disconnect
Link
Ground Fault
Current
Transformer
*
Utility
Circuit
Breaker
AT S
Emergency
Load
N
Ø
N
Ø
GFCT ­Ground Fault
Current Transformer
ATS - Automatic Transfer Switch
Switched
Neutral
One line diagram of a typical service entrance rated transfer switch available in Solid, Switched or Overlapping Neutral
* Ground fault trip protection provided on sizes of 1000 amperes
and above
ASCO
Fig. 10: Ground and neutral
disconnect links
70 - 225 36.5 (927) 48.5 (1232) 13.25 (337) 408 (188)
250, 400 36.5 (927) 48.5 (1232) 13.25 (337) 408 (188)
600, 800 38 (965) 91 (2311) 28 (711) 820 (378)
1000-1200 38 (965) 91 (2311) 48 (1219) 1105 (510)
1600, 2000 38 (965) 91 (2311) 48 (1219) 2590 (1198)
3000 38 (965) 91 (2311) 72 (1829) 4590 (2148)
4000 46 (1168) 91 (2311) 72 (1829) 5640 (2609)
Optional Features
The Example Catalog Number above is 7AUSB3400N5XC (X is used to specify optional accessories).
Enclosures - Secure Double Door
UL Type 3R w/strip heater & thermostat
UL Type 4X
UL Type 12
Connections
Crimp lugs
Bus Riser on Normal, Emergency or Load
Protective Relays/Metering
ASCO 5200 Series Power Manage
r
Surge Suppression
ASCO 451, 80KA Surge protector (see pg. 14)
Communications
ASCO 72A Communication interface moduleASCO PowerQuest
®
ASCO 5500 Series Thin Web Server for internet
connection
Additional Breaker(s)
Circuit Breaker on EmergencyLoad Distribution Panel
7000 Series Service Entrance Power Transfer Switches
Page 9
Consult ASCO for additional features
Dimensions and Weights for non-bypass configurations only in type 1 enclosures. Consult ASCO for all other product configurations.
Height
inches (mm)
Width
inches (mm)
Switch Rating
amps
Depth
inches (mm)
Weight
lbs (kg)
A Automatic
N Non-
Automatic
C Type 1 enclosure M Type 3R secure
double door
N Type 4 secure
double door
P Type 4X secure
double door
Q Type 12 secure
double door
US Conventional
2-Position
UB Open
Transition Bypass
CUS Closed
Transition
CUB Closed
Transition Bypass
DUS Delayed
Transition
DUB Delayed
Transition Bypass
--- No Neutral A Solid Neutral B Switched
Neutral
C Overlapping
Neutral
2 3
70 100 150 200 225 250 400 600 800
1000 1200 1600 2000 3000 4000
C 208 D 220 E 230 F 240 H 380 J 400 K 415 L 440 M 460 N 480 P 550 Q 575 R 600
5
5X-
optional
acces-
sories
Ordering Information
Product
Neutral
Code*
Phase
Poles
Voltage
Code
Grp
Code
Enclosure
Amperes
To order an ASCO 7000 Series Service Entrance Power Transfer Switch, complete the following catalog number.
7 A US + B + 3 + 400 + N + 5X + C
*Note. Switches rated 150, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional). For 4 pole applications on switches rates 260 to 400 amps and 4000 amps specify overlapping switched neutral (optional). Conventional switched neutral is provided on delayed transition transfer products when specified.
ASCO
The 7000 Series Microprocessor Based Controller is used with all sizes of Power Transfer Switches from 30 through 4000 amperes. It represents the most advanced digital controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power applications.
Because of severe voltage transients frequently encountered with industrial distribution systems, the microprocessor logic board is separated and isolated from the power board as shown below. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards highlighted below.
Page 10
Fig.12: Microprocessor Power and Logic PC Boards.
Fig. 11: 7000 Series
Microprocessor Controller.
7000 Series Microprocessor Based Controller
Emission Standard - Group 1, Class A EN 55011:1991 Generic Immunity Standard, from which: EN 50082-2:1995
Electrostatic Discharge (ESD) Immunity EN 61000-4-2:1995 Radiated Electromagnetic Field Immunity ENV 50140:1993 Electrical Fast Transient (EFT) Immunity EN 61000-4-4:1995 Surge Transient Immunity EN 61000-4-5:1995 Conducted Radio-Frequency Field Immunity EN 61000-4-6:1996 Voltage Dips, Interruptions and Variations Immunity EN 61000-4-11:1994
7000 Series Microprocessor Controller
ASCO
Voltage and Frequency Sensing
3-Phase under and over voltage settings on normal
and emergency sources.
Under and over frequency settings on normal and
emergency.
True RMS Voltage Sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.
Selectable settings: single or three phase voltage
sensing on normal and emergency; 50 or 60Hz.
Phase sequence sensing for phase sensitive loads.
Voltage unbalance detection between phases.
Status and Control Features
Output contact (N/O or N/C) for engine-start signals.
Selection between “commit/no-commit” on transfer
to emergency after engine start and normal restores before transfer.
Advanced inphase algorithm which automatically
measures the frequency difference between the two sources and initiates transfer at appropriate phase angles to minimize disturbances when transferring motor loads.
Event log displays 99 logged events with the time and
date of the event, event type and event reason.
Output signals for remote indication of normal and
emergency source acceptability
Statistical ATS/System monitoring data screens which provide:
Total number of ATS transfers.
Number of ATS transfers caused by power source failure.
Total number of days ATS has been in operation.
Total number of hours that the normal and emergency
sources have been available.
Time Delays
Engine start time delay - delays engine starting signal to
override momentary normal source outages - adjustable 0 to 6 seconds.
Transfer to emergency time delay - adjustable 0 to 60
minutes.
Emergency source stabilization time delay to ignore
momentary transients during initial generator set loading - adjustable 0 to 6 seconds.
Retransfer to normal time delay with two settings:
Power failure mode - 0 to 60 minutes.
Test mode - 0 to 60 minutes.
Unloaded running time delay for engine cooldown -
adjustable 0 to 60 minutes.
Pre and post transfer signal time delay for selective
load disconnect with a programmable bypass on source failures - adjustable 0 to 5 minutes. This signal can be used to drive a customer furnished relay, or for (2) sets of double throw contacts rated 3 amps at 480 volts AC, specify ASCO optional accessory 31Z.
Fully programmable engine exerciser with seven
independent routines to exercise the engine generator, with or without loads, on a daily, weekly, bi-weekly or monthly basis.
Contains all alarm signals, logic and time delays for
use with closed transition switches.
Insynch time delay - 0 to 3 seconds.
Failure to synchronize - 1 to 5 minutes.
Extended parallel - 0.1 to 1.0 seconds.
Delayed transition load disconnect time delay -
adjustable 0 to 5 minutes.
Page 11
7000 Series Microprocessor Controller
Features
Digital microprocessor.
Touch pad programming of features and settings without the need for meters, or variable power supplies.
Sixteen (16) selectable operating voltages available in
a single Controller.
On-board diagnostics provide control panel and ATS
status information to analyze system performance.
Displays and counts down active timing functions.
Selectable multi-language display
(English, German, Portuguese, Spanish, or French. For others contact ASCO).
Password protection to prevent unauthorized tampering
of settings.
Serial communications board (RS-485 protocol)
for remote monitoring and control with ASCO PowerQuest
®
and SiteWeb™ communications
products. Specify optional accessory 72A.
Load shed option for SYNCHROPOWER® bus
optimization applications. Specify optional accessory 30B.
ASCO
Page 12
The 7000 Series microprocessor controller is a Transfer Control Center which allows the user to easily access detailed information on: system status; power source parameters; voltage, frequency and time delay settings; optional feature settings; historical event log; and system diagnostics. A four line, (20) character LCD has a backlit display which enables easy viewing under all conditions. The user can navigate through all screens using only six buttons, which also allows selection of: (18) different source parameter settings; (16) standard time delays; (12) standard feature settings; up to seven independent engine exercise routines; and even the language (English, German, Spanish, French, etc.) which appears on the display.
Since the Transfer Control Center must be visible and operable through the enclosure door, it has been qualified for use in industrial and outdoor applications. This includes installation in Type 3R (outdoor/rainproof), 4 (weatherproof) and 12 (indoor/industrial) enclosures.
7000 Series Transfer Control Center
Control Switches and Indicating Lights for Conventional 2-Position Switches
Control Switches and Indicating Lights for Closed Transition Switches
Fig. 13: 7000 Series User Controls and Indicators.
Fig. 15: 7000 Series
Transfer Control Center.
Fig. 14: 7000 Series User Controls and Indicators.
Switch position indicating lights (16 mm, industrial grade LEDs).
Source acceptability indicating lights with true indication of the
acceptability of each source, as determined by the voltage, frequency, voltage unbalance, and phase sequence settings of the control panel (16mm, industrial grade LEDs).
Three position (16mm, industrial grade type) selector switch:
Automatic: Normal maintained position.
Test: Momentary position to simulate normal source failure for
system test function.
Reset Delay Bypass: Momentary position to bypass transfer and
re-transfer time delay.
Extended Parallel Time - Provides visual indication when the
pre-set extended parallel time has been exceeded. The controls automatically open the emergency or normal main contacts. Separate contact also available to shunt trip external breaker.
Failure To Synchronize - Visually displays a failure to synchronize
alarm if the time delay settings is exceeded, during closed transition transfer operation.
TS Locked Out - Prevents transfer in either direction if the
extended parallel time is exceeded.
Alarm Reset - Resets extended parallel and failure to
synchronize alarms.
Closed Transition Bypass - Pushbutton allows transfer
between sources in an open transition mode.
7000 Series User Controls and Indicators
ASCO
Normal Source
Vab=480V....................ABC
Vbc=480V.........Vunbal=1%
Vca=480V................60.0Hz
P1..................Engine.Exerciser
Enable:.....Yes....WLoad:....Yes
Start:19h30. ALL MON
Run.Time:...............2h15min
16.AUG02/95..........13h10:17
Eng.Start...............NormFail.
15.AUG02/95...........13h10:25
Xfer.N>E................................
Normal OK
TD.Engine.Cooldown:
4min15s
Normal OK
Load on Normal
Normal Voltage
Dropout.............85%.408V
Pickup...............90%.432V
O.V. Trip.........110%.528V
Displays voltage for each phase, frequency,
phase rotation and voltage unbalance for both
normal and emergency sources.
Provides voltage and frequency setting values for normal and emergency sources. Voltage pick-up,
dropout and trip settings are set in percentage of nominal
voltage and are also displayed in rms voltage values.
Seven independent programs, load/no load
selection, flexible run times and daily, weekly,
bi-weekly and monthly exercise routines.
Active time delay status displays time
remaining until next control event.
TD N>E Xfer Signal Bypass if N Fail: No Pre Xfer: 0 min 20S
Post Xfer: 0 min 20S
Provides direct reading display for setting time delays.
Displays system status in clear, concise language.
Message shown indicates normal source is acceptable
and the load is connected to the normal source.
Displays detailed information for last 99 events,
including time of occurrence, length of event,
date and reason for event.
ATS Statistics
ATS Total Xfers: 46
SRC Fail Tot Xfers: 20
Days Energized: 36.5
Instant availability of statistical information on total number of
ATS transfers, number of transfers caused by power failures
and total days controller has been energized, plus more.
Page 13
Source Status
Time Delay Status
Voltage and Frequency Settings
Time Delay Settings
Engine Exerciser
Historical Event Log
System Status
ATS Statistics
Emerg OK
Waiting for In-Sync
-45o 0.02Hz
Displays the relative phase angle between
sources and frequency differential to indicate
the controller is awaiting an inphase condition.
Shed Load
Direction: From E Inphase: No TD/0.25
Standard features can be activated with the keypad. As an example, when enabled, the “shed load” option causes the
transfer switch to transfer the load off of the specified source.
If desired, the load shed transfer can be made inphase.
Inphase Transfer Mode
Feature Settings
Status
Settings
Data Logging
7000 Series Transfer Control Center Screens
ASCO
Page 14
Time Delays
2C The standard feature one time delay is adjustable
from 0 to six seconds to delay engine starting. If necessary, extended time delay on engine starting is available. Adjustable from 0 to 60 min in one second steps. Factory set at five minutes.
1G Similar to accessory 2C except using 24 volt DC
external input signal.
Manual Controls for Automatic Transfer Switches
6C Reset switch for manual retransfer to normal with
automatic retransfer in the event of emergency source failure.
6D Selector switch for automatic/manual retransfer to
normal. Automatic bypass if emergency fails.
Engine Generator Controls and Accessories
12 Three position engine control selector switch.
Positions: 1- Stop 2 - Automatic 3 - Engine Test
Note: Switches with accessory 12 must be labelled as a non-automatic
transfer switch according to UL 1008.
Engine controls containing “engine stop” positions should be located at the engine generator. (Consult ASCO for application assistance.)
Indicators
14A/14B Additional auxiliary contact sets to indicate switch
position. Two sets are standard. Specify total number of sets if more are required.
18B Two-pole, double-throw contacts operate when
emergency source voltage is present at transfer switch terminals.
18G Two-pole, double-throw contacts operate when normal
source voltage is present at transfer switch terminals.
99 “Push-to-Test” feature on all pilot light indicators.
Customer Control Circuits
30A Load-shedding circuit initiated by opening of a
customer-supplied contact.
30B Load-shedding circuit initiated by removal of
customer-supplied control voltage. (Specify voltage).
31Z Selective load disconnect control contacts (two
provided) which operate with time delay prior to and/or after load transfer and retransfer.
43R Terminal block for all customer control connections
on 30-150 amp only (standard on all other sizes).
Neutral Conductor Options
Solid neutral, with fully-rated terminals. (AL-CU) UL Listed.
Conventional neutral switching pole.
Overlapping neutral transfer contacts. Allows for proper
ground-fault sensing and avoids generator voltage transients during transfer.
Note: Specify neutral option in catalog number, see page 21 for instructions.
Extension Harness
37B
Six foot (6’) extension harness to increase distance between transfer switch and control panel on open-type units.
Analog Load Metering Options
23B Three phase ammeter with selector switch
(with current transformers and shorting blocks).
24B Three phase voltmeter with selector switch.
Note: Refer to ASCO 7000 Series Data Monitor on page 15 which provides
voltage, frequency and power monitoring.
Serial Communications
72A Serial communication module for remote
communications to ASCO PowerQuest
®
products.
Surge Protection
ASCO Pulsar 450 rated 40KA
73AC1 Normal source protection. (3Ø, 4wire WYE) 73AC2 Emergency source protection. (3Ø, 4wire WYE) 73AC3 Load side protection. (3Ø, 4wire WYE)
Note: Other distribution voltages available (Contact ASCO).
Special Applications
111A Generator - to - Generator for Standby Applications
111B Generator - to - Generator for Prime Power
Applications
Bypass Isolation Switch Options
14A1 Auy contact to close in “Bypass to Normal” position.
14B1
Auxiliary contact to close in “Bypass to Emergency” position.
14T Auxiliary contact to close when transfer switch is in
“Automatic” position.
14U Auxiliary contact to close when transfer switch is in
“Isolate” position.
14V Auxiliary; contact to close when transfer switch is in
“Test” position.
Note: An externally operable quick-make, quick-break (QMQB), manual handle is available on some 7000 Series product configurations.
(Consult ASCO for guidance.)
7000 Series Optional Accessories
ASCO
Power Metering
Voltage:
Line - Line: VAB, VBC, VCA, VAVERAGE Line - Neutral: VAN, VBN, VCN, VAVERAGE
Frequency: 45.0 to 66.0 Hertz
Current: IA, IB, IC, IAVERAGE
Unbalance %: Voltage, Amps
Real Power: KWA, KWB, KWC, KWNET
Reactive Power: KVARA, KVARB, KVARC, KVARNET
Apparent Power: KVAA, KVAB, KVAC, KVANET
Real Energy: KWHIMPORT, KWHEXPORT, KWHNET
Reactive Energy: KVARHIMPORT, KVARHEXPORT,
KVARHNET
Power Factor: PFA, PFB, PFC, PFNET
Data Access
Eight digital inputs, four relay outputs.
Input/Output 15-character, user definable screen
display for identification of input/output signals.
Page 15
Fig. 16: ASCO Power Manager.
Configurable Designations
Local - A four line 20 character LCD backlit display.
Remote - With optional Acc. 72A communication module
and Power Manager monitoring systems.
Provides a user programmable setpoint based on watt
demand and can be used to control one of the four relay outputs. Used for peak shaving applications
Integrated ATS Features
When configured on load of ATS:
Displays ATS position.
Displays power data as a function of ATS position
(normal/emergency).
Accumulates energy data separately for normal and
emergency sources.
Power Manager
Optional Configurations and Connection Arrangements
Connected To: With Display Without Display Load Acc. 85L Acc. 75L Normal Acc. 85N Acc. 75N Emergency Acc. 85M Acc. 75M Load (BPS only) Acc. 85R* Acc. 75R
*
Add suffix “A” to above designations if neutral conductor monitoring is required.
Note: Accessory 75 and 85 includes component mounting, CTs, shorting
blocks and all necessary interwiring.
* Bypass & isolation switch contacts wired to discrete Power Manager
inputs.
The ASCO Power Manager is a microprocessor based metering device that provides real-time measurements of single and three phase power systems. The Power Manager uses digital signal processing technology to measure voltage and current per phase; real, reactive and apparent power, and bi-directional energy. All measurements can be viewed locally with a backlit liquid crystal display and/or displayed remotely with ASCO PowerQuest
®
or SiteWeb™ products.
Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PTs). Measures three phase currents and a fourth current input is available for measuring current in the neutral conductor. The Power Manager includes one discrete input for transfer switch position, eight general purpose discrete inputs, and four relay outputs for controlling or monitoring external devices.
Note: The ASCO Power Manager is also available as a separate unit for monitoring electrical parameters anywhere in the power distribution system.
POWER SYSTEM TOTAL 404 KW +1.00 PF 0 KVAR 60.00 Hz 404 KVA ATSºn NORM
7000 Series Optional Accessories
ASCO
ASCO
Page 16
7000 Series Power Monitoring & Control
Features
Monitors and Controls Power Transfer Switches and Engine Generators
Monitors Normal and Emergency Voltages and Frequency
Indicates Transfer Switch Position and Source Availability
Provides Transfer and Retransfer of Loads for System Testing
View Normal and Emergency Voltage and Frequency Settings
View Transfer Switch Time-Delay Settings
Provides Transfer Switch Rating and Identification
Automatic Paging Notifies Personnel, by E-mail or Pager, of Selected System Alarms
View Current, Power and Power Factor with ASCO Power Managers Connected to the System
Adjust and Set Transfer Switch Controller Parameters
Activate Transfer Switch Control Functions, Such as Inphase Transfer, Selective Load Disconnect
Time Displays and Engine Exerciser Programming
View Transfer Switch Event Log
Provides Transfer Switch Test Schedule
ASCO Connectivity Solutions
ASCO PowerQuest®and SiteWeb™ communications products allow for the monitoring and control of power transfer switches in your Emergency or Standby Power Distribution System. Local Area networks and Remote networks are supported with either single or multiple points of access, and web-enabled communications allow access to your power system from anywhere around the world.
ASCO
PowerQuest
®
Typical Network Connection
ASCO
ATS 1
ASCO ATS 2
ASCO 5200
Power Manager
Generator
Generator
RS-485
ASCO 5200 Power Manager
ASCO 5100
Telephone
Interface
Module
ASCO 5150 (72E)
Connectivity Module
ASCO 5110 (72A) Serial Modules
ASCO 5110 (72A) Serial Modules
To Additional
Automatic
Transfer
Switches
ASCO
ATS 1
ASCO ATS 2
ASCO
ATS
Ethernet
Dial - Up
Serial
ASCO
PowerQuest
VPi 32.15
Software
To Additional
Automatic
Transfer
Switches
Page 17
7000 Series Power Monitoring & Control
5100 Telephone Interface Module
(for use with PowerQuest®)
The ASCO Telephone Interface Module (TIM) allows users to dial directly into their ASCO communications network for monitoring and/or control. The TIM connects to the ASCO communication network via RS-485 and the phone port connects directly into an analog phone jack. Also, the TIM has an RS-232 connector which allows the TIM to be used as the dialing modem.
Supplied with 120 VAC to 18 VDC (nominal) UL approved, class 2 power supply.
Fig. 19:
Telephone
Interface Module
ASCO
PowerQuestis a PC based software package. When combined with the ASCO Communication Interface Module (Acc 72A), the ASCO 5120 Telephone Interface Module and ASCO 5200 Series Power Manager, as shown above, it provides the most economical communication system for monitoring and control of power transfer switches and engine generators.
The local RS-485 network allows communications with up to 32 power transfer switches and four engine generators. An analog phone connection and ASCO telephone interface module allow for direct dial up, monitoring and control of remote locations. The ASCO Power Manager not only allows you to view current power and power factor readings, but also has a programmable KW set point to initiate transfer of loads to a standby source for peak shaving operations.
5110 Serial Module
Serial Module (5110) is used to allow local or remote communications with ASCO
PowerQuest
®
or SiteWeb™communication products. The module is used to connect the 7000 Series Transfer Switches, and ASCO Power Managers to the serial network via an RS-485 interface. The module has two port connectors used for ATS & Standalone Power Manager connectivity. The serial connection is accomplished from a 5-pin terminal header/socket block. The module is designed to communicate with up to 32 devices.
5150 Connectivity Module
Connectivity Module (5150) is used to bring several different serial devices that communicate at different baud rates and with different protocols to a common Ethernet media. The module is used to connect 7000 Series Transfer Switches, and ASCO Remote Annuciators to the standard Ethernet TCP/IP network with standard 10base T(RJ-45) connector. The module has been built in customized JAVA
TM
applets (program applications for an internet browser) for each monitored device that loads automatically to a standard Web Browser. The module is designed to communicate with up to 8 clients simultaneously with Web applications (web pages),
PowerQuest
®
, or third party Modbus devices
over an Ethernet connection.
Fig. 17: Serial
Module 72A
Fig. 18: Connectivity
Module 72E
Summary Screen
Convenient One-Line Diagram
Colored icons highlighted to show source availability and which source is connected to load.
Contacts move on icon to indicate main contact position of transfer and bypass switch.
(Automatic transfer and automatic transfer and bypass isolation switches must be provided with optional accessory 14 auxiliary contacts shown on page 14.)
Bypass switch contacts appear on icon when configured by user input data.
E
E
L
N
N
Page 18
®
ASCO
ASCO
ASCO
ATS 1 - 8 Summary Screen
ATS 1 - 8 Summary Screen
1901 lavg
548 KW
208 NVca
0 EVca
ATS 1
E
E
N
L
N
OTTS
Engine 1 Stopped
0 KW Total
0.00 Frequency
0.00 Power Factor 0 Vavg. 0 lavg.
1901 lavg
548 KW
208 NVca
0 EVca
ATS 2
E
L
N
E
OTTS
N
1901 lavg
548 KW
208 NVca
0 EVca
ATS 3
E
E
N
L
N
OTTS
Re-TransferTransferPrevious
Engine 2 Stopped
0 KW Total
0.00 Frequency
0.00 Power Factor 0 Vavg. 0 lavg.
1901 lavg
548 KW
208 NVca
0 EVca
ATS 4
E
L
N
E
OTTS
TD Bypass
1901 lavg
548 KW
208 NVca
208 EVca
N
E
E
OTTS OTTS
472 lavg 136 KW
208 EVca
E
E
OTTS
ATS 9-16
ATS 5
L
N
Re-Scan
1901 lavg
548 KW
208 NVca
208 EVca
N
E
E
208 EVca
ATS 6
N
L
N
?
1901 lavg
548 KW
208 NVca
ATS 7
E
L
E
OTTS
N
N
Engine 3 Stopped Engine 4 Running
0 KW Total
0.00 Frequency
0.00 Power Factor 0 Vavg. 0 lavg.
136 KW Total
60.01 Frequency
0.82 Power Factor 208 Vavg. 472 lavg.
0 NVca
ATS 8
L
N
N
Engine-Generator Details
Voltage: Phase to phase; Phase to neutral
Current for each phase.
Kilowatts and kilowatt hours total.
Frequency and power factor.
Status and control of four digital outputs which can be
customized by the user.
Status of eight digital inputs.
“Alarm Enabled” selection. These alarms flash the
“engine-generator” icon on the summary screen.
Digital inputs for engine malfunctions are derived
from engine mounted sensors (supplied by others).
Power Manager Detail Screen
Voltage: phase to phase; phase to neutral and
voltage unbalance.
3 phase currents and neutral (optional).
Frequency.
Kilowatt hours - normal and emergency.
Status and control of four relay outputs.
Status of eight digital inputs.
Device ratings: CT and PT ratio.
Transfer Switch Detail Screen
ATS rating and identification data is displayed.
Allows remote testing and time delay bypass.
Voltage, frequency, phase sequence, voltage unbalance
and time delay settings can be checked.
Viewing of engine exercise schedules.
Displays phase to phase voltage on normal and
emergency.
Provides complete system status message from
7000 series microprocessor controller.
View event log on the last 99 events for each ATS.
Arrange test schedules for transfer switches.
Provides for monitoring of local site or remote sites.
Page 19
Power Manager / Data Monitor Screen
Power Manager / Data Monitor Screen
ADDRESS
USER
NONE
8
Voltage AB
Voltage BC
Voltage CA
Voltage AN
Voltage BN
Voltage CN
Voltage
207
209
208
119
120
1
Current A
Current B
Unbal %
469
472
40
136
0
136
KVAR
KVA
475
85
78
163
KVARH lag
KVARH lead
KVARH net
Current
Power
Normal Energy
Status Input 1
Bypass to Normal
Bypass to Emergency
ATS Test
ATS Isolated
Normal Breaker Trip
Digital Input
Status
121
Start Engine
Output 2
Output 3
Output 4
Digital Output
Status
on
off
off
off
Relay 1
PreviousPreviousRelay 3
Relay 2
PreviousPreviousRelay 4
Toggle
Reset Emergency
ATS Summary
Unbal % L-L
KWatt
Current C
Status Input 7
Status Input 8
Frequency
1
59.97
Power Factor
2
1
3
KVARH lag
KVARH lead
KVARH net
Emergency Energy
890763
0
890763
KWH imp
KWH exp
KWH net
21
7
25
KWH imp
KWH lead
KWH net
Reset Normal
1000
120
CT Ratio
PT Ratio
Device
ASCOᓼASCO
®
ASCO
Engine-Generator Screen
ASCOᓼASCO
Vol ta ge
Voltage AB
Voltage BC
Voltage CA
Voltage AN
Voltage BN
Voltage CN
Unbal % L-L
USER
Digital Input
Engine Oil Temp
Low Fuel
Low Oil Pressure
Bypass Closed
Bypass on Test
Normal Brkr Temp
Status Input 7
Status Input 8
NONE
207
209
208
119
120
121
1
Engine-Generator Screen
ENGINE
Current Power Energy
Current A
Current B
Current C
Unbal %
475
KW Total
469
KWH net
472
Frequency
Power Factor
40
Alarm
Enabled Status
No
No
Yes
No
No
No
No
No
4
136
43441
60
60
Digital Output
Start Engine
Output 2
Output 3
Output 4
KWH imp
KWH exp
KWH net
890784
0
890784
Toggle
KVARH lag
KVARH lead
KVARH net
Relay 1
Relay 2
PreviousPreviousRelay 3
PreviousPreviousRelay 4
Reset
Status
on
off
off
off
ATS Summary
ASCO
Description
ATS 8 Location Switch 1
Transfer
Re Transfer
Timer Bypass
Normal Voltage Frequency Settings
Voltage or Freq % Nom Value
Vol tag e P.U.
Vol tag e D.O .
Voltage Trip
Freq P.U.
Freq D.O.
Freq Trip
Volt Unbal P.U.
Volt Unbal D.O.
Select Emergency Settings
None
USER
85
78
163
ATS Details Screen
ATS Details Screen
Transfer Switch
PRESENT STATE
Load On Normal
Normal OK
Time Delay Settings [min]:[sec]
Engine Start-Norm Fail
95
70
0 95
90
0
10
20
Norm to Emerg
197.6
Emerg to Norm-Src Fail
197.6
Emerg to Norm-Test Xfer
0
Emerg to Norm-Emerg Fail
47.5
Engine Cool Down
45
Select
0
Standard TD
20.8
Pre/Post Signal TD
41.6
Non - Standard TD
ADRTST-E12
Ver.
205 NVca
0 EVca
ATS1
ELN
8
Locked Out
In-Phase Monitor Enabled
6/15/99
OTTS
11:08:54 AM
6/13/99
00 : 03
10:02:42
00 : 10
Update Time
30 : 00
02 : 00
Event Logging (Max. 99 Entries)
00 : 00
03 : 00
Event Log
Event Cause
Date 06/12/01
Time 16:05:42
Test Schedules
ATS
N0
Yes
PC
CP
Switch Data
Nom Voltage
Current Rating
Nom Freq
# Phases
Normal Vab
Normal Vbc
Normal Vca
Normal Freq
Emerg Vab
Emerg Vbc
Emerg Vca
Emerg Freq
1
208
1200
50
1
202
205
205
59
0
0
0
0
Emerg Became
Not Vail
Emergency
Failure
ATS Summary
Page 20
SiteWeb
TM
ASCO
Internet
Ethernet Hub
Remote Access
Computer
Local Computer
Firewall
ASCO 5500 Thin Web Server
Email Server
Pager
Building Management Computer
Ethernet Hub
RS 422 Modbus
ASCO
5110 (72A)
Serial
Modules
ASCO 5150 (72E) Connectivity Modules
ASCO
ATS 1
ASCO ATS 2
Ethernet
ASCO
Engine Generator
Paralleling
System
RS 485
ASCOA
TS 1
ASCO ATS 2
To Additional
Automatic
Transfer
Switches
To Additional
Automatic
Transfer
Switches
Ethernet
RS 485
Monitoring
and Control
Monitoring
Monitoring and Control
PowerQuest
®
Fig. 20: Thin Web Server
5500 Series Thin Web Server
(for use with products)
The ASCO Thin Web Server allows you to monitor and control transfer switches and engine generators anytime over the Internet or an Intranet from anywhere in the world. It also transmits a page message that an alarm has occurred with one or more of the transfer switches. Plus, this is possible from your home computer or anywhere that has Internet service, using the ASCO Thin Web Server single-board computer with its embedded SiteWeb™ HTML web pages.
SiteWebTMis a client-server application requiring no software to be installed on the client computer. When combined with the ASCO Communication Interface Modules (Acc 72A / Acc 72E), the ASCO 5500 Series Thin Web Server and the ASCO 5200 Series Power Manager, as shown above, it provides the most comprehensive Intranet and Internet communication system for the monitoring and control of power transfer switches and engine generators located in your emergency or standby power distribution system.
The SiteWebTMcommunication system allows multiple client access, from local or remote locations, and provides for the monitoring of up to 64 power transfer switches and eight engine generators. In addition, automatic paging is provided for all alarm signals.
Communications Products for Series 7000 Transfer Switches
Description Acc. Option Catalog No.
Serial Module 72A 5110
Connectivity Module 72E 5150
Telephone Interface Module for Remote Monitoring* 5120
Power Manager with Display* 5200D
Thin Web Server* 5510E
Thin Web Server with Modem* 5510M
PowerQuest VPi Software Package* VPi 32.15
*Note: These products are available as separate items only. They can be ordered by catalog numbers shown in above chart.
SiteWeb
TM
ASCO
Page 21
ASCO Connectivity Solution Guide
Feature
PowerQuest
Vpi 32.15
Thin Web Server
with SiteWeb
Series 5150
Connectivity Module
Quantity of Monitored / Controlled Power Transfer Switches per LAN
Number of Monitored / Controlled Gensets
Control & Monitoring Capability
Embedded Web Pages
Ethernet Network Compatible
Monitor Multiple Protocols & Baud Rates (ASCO I, ASCO II, Modbus)
Monitor Multiple Sites
Multiple Client Access
Client Software Required
Monitors Dissimilar ASCO Controllers on Common LAN
Communicates with ASCO Remote Annuciators
Email / Paging Alarms
Historical Trending Option Alarms
32
4
Yes
No
Yes
No
Dial-Up
No
Yes
No
No
No
No
64
8
Yes
Yes
Yes
No
Internet
Up to 8
Internet Explorer
No
No
Yes
Yes
1024+
1024+
No
Yes
Yes
Yes
Intranet
Up to 8
Internet Explorer
Yes
Yes
No
No
Connectivity Modules
++
++
++
TSA A 3 400 N 5X C
Page 22
To order an ASCO 7000 Series Power Transfer Switch, complete the following catalog number:
The Example Catalog Number above is 7ATSA3400N5XC
(X is used to specify optional accessories).
7
*Note: Switches rated 30-230, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional).
For 4 pole applications on switches rated 260 to 400 amps and 4000 amps specify overlapping switched neutral (optional). Conventional switch neutral is provided on delayed transition transfer products when specified. 200 and 230 amp switch limited to 480 volts maximum.
Amperes
Voltage
Code
Grp
Code
Enclosure
Neutral
Code*
Product
Phase
Poles
115 120 208 220 230 240
380
400 415 440 460 480 550 575 600
TS
TB
CTS
CTB
DTS
DTB
2 3
A
N
M
Automatic
Non­Automatic
Manually Operated
5
5X-
optional
acces-
sories
---
C
E
F
G
H
K
L
M
N
P
Q
---
A
B
C
Conventional 2-Position
Open Transition Bypass
Closed Transition
Closed Transition Bypass
Delayed Transition
Delayed Transition Bypass
No Neutral
Solid Neutral
Switched Neutral
Overlapping Neutral
30
70 100 150 200 230 260 400 600 800
1000 1200 1600 2000 3000 4000
A
B C D
E
F
H
J K L
M N
P
Q R
No enclosure
Type 1 enclosure
Type 2 enclosure
Type 3R enclosure
Type 4 enclosure
Type 4X enclosure (stainless steel)
Type 7 enclosure
Type 12 enclosure
Type 3R secure double door
Type 4 secure double door
Type 4X secure double door
Type 12 secure double door
Transfer Switch Configurations
7A TS, 7N TS, 7A DTS, 7A CTS, 7N DTS, 7N CTS
Transfer/Bypass Configurations
7A TB, 7N TB, 7A DTB, 7A CTB, 7N DTB, 7N CTB
Sizes of UL-Listed Solderless Screw-Type
Terminals for External Power Connections
Notes: 1. Unit is designed for top cable entry of emergency and load and bottom
entry of normal. Optionally, the switch may be supplied with reverse source and/or bottom entry load, when specified.
2. All main terminals are rear connected. The 4000 amp switch is arranged for bus bar connection. Contact ASCO if provisions for cable connection are required.
Switch Rating
amps
Max # of Conductors
per Terminal
Range of AL-CU
Conductor Sizes
One
One
Two
Two
Four
Six
Twelve
#14 to 4/0 AWG
#4 AWG to 600 MCM
#1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
#1/0 AWG to 250 MCM
#1/0 AWG to 600 MCM
30 -230
3
600
800-1200
1
1600-2000
3000
4000
2
260-400
Sizes of UL-Listed Solderless Screw-Type
Terminal for Power Connections
Switch Rating
amps
Max # of Conductors
per Terminal
Range of AL-CU
Conductor Sizes
One
Two
Two
Four
Six
Te n
Twelve
# 1/0 AWG to 250 MCM
# 4 AWG to 600 MCM
# 2 AWG to 600 MCM
# 2 AWG to 600 MCM
# 2 AWG to 600 MCM
# 1/0 AWG to 600 MCM
# 1/0 AWG to 600 MCM
150,260,400
600
4
800,1000,1200
4
1600-2000
4
3000
4
4000
4
3. 200 and 230 amp rating for copper conductors only.
4. All main terminals are rear connected. A front connected version is available in 600 and 800 amp ratings only with top cable entry only. See pages 24 and 25 for dimensional data.
7000 Series Ordering Information
Suitable for Bus Bar Connection or Lugs Can Be Field Modified
*
ASCO
*
Page 23
2-Position Transfer Switching 7A TS, 7N TS (Non-Bypass)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back.
2. Consult ASCO for dimensions on enclosures other than UL type 1.
Depth
inches (mm)
Height
inches (mm)
Width
inches (mm)
Poles
Switch Rating
amps
7000 Series Designed to Fit Anywhere
Enclosed UL Type 1
2
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral A/B/C 18 (457) 48 (1219) 13 (330)
260, 400 2, 3 or 3 with neutral A/C 22 (559) 48 (1219) 13 (330)
600, 800, 1000 2, 3 or 3 with neutral A/B/C 34 (864) 72 (1829) 20 (508)
1200 2, 3 or 3 with neutral A/B/C 38 (965) 87 (2210) 23 (584)
1600, 2000
1
2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 48 (1219)
3000
1
2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 60 (1524)
4000
1
2, 3 or 3 with neutral A/C 46 (1168) 91 (2311) 72 (1829)
Open Configuration
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral B/C 10-1/4 (260) 10-1/4 (260) 5-1/2 (140)
260, 400 2 or 3 12 (305) 18-1/2 (470) 6-7/8 (175)
260, 400 2 or 3 with neutral C 14-1/2 (368) 18-1/2 (470) 6-7/8 (175)
600, 800, 1000, 1200 2, 3 or 3 with neutral B/C 27 (686) 31 (787) 12-7/8 (327)
1600, 2000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 26-1/4 (667)
3000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 30-3/4 (781)
4000 2, 3 or 3 with neutral C 41 (1041) 52 (1321) 25-1/2 (648)
2-Position Transfer Switching 7A TS, 7N TS
Open
lb (kg)*
Enclosed
lb (kg)
Poles
Switch Rating
amps
30, 70, 100 2 67 (31) 15 (7)
30, 70, 100 3 70 (32) 18 (8)
30, 70, 100 3 with B/C 73 (33) 21 (10)
150, 200, 230 (Open) 2 69 (32) 17 (8)
150, 200, 230 (Open) 3 72 (33) 20 (9)
150, 200, 230 (Open) 3 with B/C 75 (34) 23 (11)
230, 260, 400 2 117 (53) 37 (17)
230, 260, 400 3 125 (57) 45 (21)
230, 260, 400 3 with C 133 (61) 53 (24)
600, 800, 1000 2 400 (182) 150 (68)
600, 800, 1000 3 420 (192) 170 (78)
600, 800, 1000 3 with B/C 446 (203) 196 (90)
1200 2 685 (312) 150 (68)
1200 3 705 (321) 170 (78)
1200 3 with B/C 731 (333) 196 (90)
1600, 2000 2 1110 (503) 370 (167)
1600, 2000 3 1160 (525) 420 (190)
1600, 2000 3 with B/C 1210 (548) 470 (213)
3000 2 1365 (620) 405 (184)
3000 3 1430 (649) 470 (213)
3000 3 with B/C 1495 (679) 535 (243)
4000 2 2208 (1002) 975 (443)
4000 3 2433 (1104) 1200 (545)
4000 3 with C 2533 (1149) 1300 (590)
Shipping Weights
Notes: *Open weights include transfer switch and control panel.
1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
ASCO
7000 Series Designed to Fit Anywhere
Closed Transition and Delayed Transition Transfer Switching
7A DTS, 7A CTS, 7N DTS, 7N CTS
Notes: 1. For 400 amp, 7A DTS and 7N DTS with neutral code B; dimensions are 34 (864) X 72 (1829) x 20 (508).
2. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back.
3. Consult ASCO for dimensions on enclosures other than UL type 1
Depth
inches (mm)
Height
inches (mm)
Width
inches (mm)
Poles
Switch Rating
amps
Enclosed UL Type 1
3
150, 260, 400
1
2, 3 or 3 with neutral A/C 24 (610) 63 (1600) 17-1/2 (445)
600, 800, 1000 2, 3 or 3 with neutral A/B 34 (864) 72 (1829) 20 (508)
1200 2, 3 or 3 with neutral A/B 38 (965) 87 (2210) 23 (584)
1600, 2000
2
2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 48 (1219)
3000
2
2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 60 (1524)
4000
2
2, 3 or 3 with neutral A/C 46 (1168) 91 (2311) 72 (1829)
Open Configuration
150, 260, 400 2, 3 or 3 with neutral C 14-3/4 (375) 30 (762) 5-7/8 (149)
600, 800, 1000, 1200 2, 3 or 3 with neutral B 27 (686) 31 (787) 12-7/8 (327)
1600, 2000 2, 3 or 3 with neutral B 33-1/4 (845) 28 (711) 26-1/4 (667)
3000 2, 3 or 3 with neutral B 33-1/4 (845) 28 (711) 30-3/4 (781)
4000 2, 3 or 3 with neutral C 41 (1041) 52 (1321) 29-1/2 (749)
Closed Transition and Delayed Transition Transfer Switching
7A DTS, 7A CTS, 7N DTS, 7N CTS
Open*
lb (kg)
Enclosed
lb (kg)
Poles
Switch Rating
amps
150, 260, 400 2 137 (62) 45 (21)
150, 260, 400 3 145 (66) 53 (24)
150, 260, 400 3 with C 153 (69) 63 (28)
600, 800, 1000 2 420 (192) 175 (80)
600, 800, 1000 3 450 (205) 205 (94)
600, 800, 1000 3 with B 480 (219) 235 (108)
1200 2 710 (324) 175 (80)
1200 3 740 (337) 205 (94)
1200 3 with B 770 (351) 235 (108)
1600, 2000 2 1300 (590) 505 (229)
1600, 2000 3 1350 (612) 555 (252)
1600, 2000 3 with B 1400 (635) 605 (274)
3000 2 1555 (706) 540 (245)
3000 3 1620 (735) 660 (300)
3000 3 with B 1685 (765) 725 (329)
4000 2 2360 (1071) 1127 (511)
4000 3 2580 (1171) 1347 (611)
4000 3 with C 2680 (1217) 1447 (657)
Shipping Weights
Notes: *Open weights include transfer switch and control panel.
1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
ASCO
Page 24
7000 Series Designed to Fit Anywhere
Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB
Notes: 1. Handles extend 3-1/2 inches (89mm).
2. Handles extend 6-1/4 inches (159mm).
3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout). Side or rear access required.
4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout).
5. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amp. All service and load cables limited to top entry only.
Depth
inches (mm)
Height
inches (mm)
Width
inches (mm)
Poles
Switch Rating
amps
Enclosed UL Type 1
150, 260, 400
1
2, 3 or 3 with neutral A/C 28-1/2 (724) 62-1/2 (1588) 19 (483)
600, 800( Front Connected)
2, 5
2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 32 (813)
600, 800, 1000, 1200
2, 3
2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 48 (1219)
1600, 2000
2, 3
2, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 60 (1524)
3000
2, 3
3 or 3 with neutral A/B/C 38 (965) 91 (2311) 72 (1829)
4000
4
3 or 3 with neutral A/C 96-1/2 (2451) 91 (2311) 72 (1829)
150, 260, 400
1
2 or 3 14-3/4 (375) 37-1/8 (946) 22-1/4 (565)
150, 260, 400
1
2 or 3 with neutral C 19-3/4 (500) 61-1/2 (1553) 22-1/4 (565)
600, 800, 1000, 1200
2, 3
2, 3 or 3 with neutral B/C 38 (965) 72 (1829) 38 (965)
1600, 20003, 3000
2, 3
2, 3 or 3 with neutral B/C 38 (965) 72 (1829) 38 (965)
Automatic Transfer Bypass-Isolation Switching with Transfer Switch Engaged 7A TB, 7N TB
Open*
lb (kg)
Enclosed
lb (kg)
Poles
Switch Rating
amps
150, 260, 400 2 340 (154) 135 (61)
150, 260, 400 3 350 (158) 145 (66)
150, 260, 400 3 with C 360 (163) 155 (70)
600, 800, 1000, 1200 2 1510 (685) 920 (417)
600, 800, 1000, 1200 3 1580 (717) 990 (449)
600, 800, 1000, 1200 3 with B/C 1650 (748) 1060 (481)
1600, 2000 2 2180 (989) 1300 (589)
1600, 2000 3 2360 (1070) 1550 (702)
1600, 2000 3 with B/C 2540 (1152) 1800 (815)
3000 3 2730 (1240) 1690 (768)
3000 3 with B/C 3360 (1525) 1980 (899)
4000 3 6300 (2858)
4000 3 with C 6900 (3130)
Shipping Weights
Notes: *Open weights include transfer switch, bypass-isolation switch and control panel.
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
Open Configuration
ASCO
Page 25
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB
6
, 7A CTB, 7N DTB6, 7N CTB
Notes: 1. Handles extend 3-1/2 inches (89mm).
2. Handles extend 6-1/4 inches (159mm).
3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout).Side or rear access required.
4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout).
5. Dimensions for 400 amp, 7A DTB and 7N DTB with neutral code B are 38(965)W x 91(2311)H x 48(1219)H.
6. Conventional switched neutral is provided on 7A DTB and 7N DTB switching arrangements when specified (optional Code B).
7. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amps. All service and load cables limited to top entry only.
Depth
inches (mm)
Height
inches (mm)
Width
inches (mm)
Poles
Switch Rating
amps
Enclosed UL Type 1
150, 260, 400
1, 5
2, 3 or 3 with neutral A/C 28-1/2 (724) 74 (1880) 19 (483)
600, 800 (Front Connected)
2, 7
2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 32 (813)
600, 800, 1000, 1200
2, 3
2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 48 (1219)
1600, 2000
2, 3
2, 3 or 3 with neutral A/B 38 (965) 91 (2311) 60 (1524)
3000
2, 3
3 or 3 with neutral A/B 38 (965) 91 (2311) 72 (1829)
4000
4
3 or 3 with neutral A/C 96-1/2 (2451) 91 (2311) 72 (1829)
150, 260, 400
1, 5
2 or 3 14-3/4 (375) 61-1/2 (1553) 22-1/4 (565)
150, 260, 400
1, 5
2 or 3 with neutral C 19-3/4 (500) 61-1/2 (1553) 22-1/4 (565)
600, 800, 1000, 1200
2, 3
2, 3 or 3 with neutral B 38 (965) 72 (1829) 38 (965)
1600, 20003, 3000
2, 3
2, 3 or 3 with neutral B 38 (965) 72 (1829) 38 (965)
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed Transition Switching. 7A DTB, 7A CTB, 7N DTB, 7N CTB
Open*
lb (kg)
Enclosed
lb (kg)
Poles
Switch Rating
amps
150, 260, 400 2 340 (154) 145 (66)
150, 260, 400 3 350 (158) 155 (70)
150, 260, 400 3 with C 360 (163) 165 (75)
600, 800, 1000, 1200 2 1560 (708) 970 (440)
600, 800, 1000, 1200 3 1630 (739) 1040 (472)
600, 800, 1000, 1200 3 with B 1700(771) 1110(503)
1600, 2000 2 2315 (10550) 1435 (651)
1600, 2000 3 2495 (1132) 1685 (764)
1600, 2000 3 with B 2675 (1213) 1935 (878)
3000 3 2730 (1240) 1690 (768)
3000 3 with B 3360 (1525) 1980 (899)
4000 3 6300 (2858)
4000 3 with C 6900 (3130)
Shipping Weights
Notes: *Open weights include transfer switch, bypass-isolation switch and control panel.
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
Open Configuration
7000 Series Designed to Fit Anywhere
ASCO
Page 26
ASCO Services, Inc., pro­vides a wide range of techni­cal services to users of automatic transfer switches in emergency and standby power systems. These serv­ices include comprehensive scheduled maintenance programs, modifications, upgrades and emergency repairs. Systems serviced range in complexity from a single automatic transfer switch to multiple transfer switches and engine genera­tors.
ASCO Services is a wholly owned subsidiary and the exclusive OEM service arm of ASCO Power Technologies, the world’s
largest manufacturer of power transfer switching and control equipment. Serving the needs of ASCO’s customers is a major focus; however, ASCO Services is also routinely called upon to perform regular maintenance and emergency repairs on equipment manufactured by others.
ASCO Services offers comprehensive maintenance agreements that detail the preventive care needed to keep emergency power systems ready to respond. A service agreement is an effective way to budget in advance and avoid unex­pected expenditures. A 35-
point checklist is utilized to assure critical systems and components are kept in top operating condition. These preventive programs can be customized for national accounts. This customization permits centralcorporate control of costs and schedul­ing. Periodic reports provide detailed information as to activity, maintenance performed and corrective action.
ASCO Services deploys more than 75 service person­nel strategically located throughout the nation to provide 24-hour response in emergency situations. Each region is manned by ex-
perienced personnel who receive ongoing support and training in the newest equipment concepts, design and controls. Because equipment can be utilized for a long number of years, field representatives also receive education on older designs. This knowledge can be invaluable in addressing total system concerns, evaluating problems and providing solutions on site. Service vans are equipped with parts and advanced testing equipment that facilitate these on-the-spot repairs.
ASCO
Services
1-800-800-ASCO.
Start-Up Commissioning, Service & Scheduled Maintenance
ASCO
Page 27
ASCO POWER TECHNOLOGIES
FLORHAM PARK, NEW JERSEY 07932
USA
800 800 ASCO
WWW.ASCO.COM
ASIA
AUSTRALIA
BRAZIL
CANADA
GERMANY
JAPAN
MEXICO
SOUTH AFRICA
SOUTH AMERICA
UNITED ARAB EMIRATES
UNITED KINGDOM
UNITED STATES
Publication 3040-R7
ASCO December, 2004
Printed in the U.S.A.
We Keep Your Power On