voltages capable of causing shock, burns, or death.
4–line
LCD
display
Enter/Save
Settings
key
Refer to the Operator’s Manual for the ASCO 4000 or
7000 Series ATS product for installation, functional
testing, sequence of operation,and troubleshooting.
Description
ASCO 4000 & 7000 Series Automatic Transfer Switch
products utilize the Group 5 Controller for sensing,
timing, and control functions. This state–of–the art
microproce ssor– based controller includes a built–in
keypad and a four–line LCD display. All monitoringand
control functions can be done with the enclosure door
closed for greater convenience. In addition, all changes
in voltage settings (except for nominal voltage) and time
delayscanbemadethroughasystemofmenus.
TABLE OF CONTENTS
section-page
OVERVIEW
Controls1-1..............................
Settings1-2..............................
SETTINGS
How to Change a Setting2-1...............
Voltage & Frequency2-2...................
Time Delays2-4..........................
Features2-6..............................
General2-8..............................
Engine Exerciser2-10.....................
View Event Log2-12.......................
Service — Statistics / Diagnostics2-13......
OPERATING the CONTROLS
Status of ATS and Sources3-1.............
WARNINGisusedinthismanualtowarn
of possible personal injury.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
Refer to the outline and wiring drawings provided with
the 4000 or 7000 Series ATS product for all inst allation
and connection details and accessories.
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO)www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO)www.asco.ca
Display Messages and Their Meanings3-2...
DESCRIPTION of OPERATION
Open–Transition4-1.......................
Closed–Transition4-3......................
Delayed–Transition4-6....................
APPENDIX
DIP switch actuatorsA-2...................
Voltage jumper blocksA-4.................
INDEXback page..........................
381333–126 K
1--1Overview
Control Overview
4–line LCD display
On the Power Control Center, six keys allow access to all monitoring and setting
functions. Two levels of screens are used. The status level provides information
about the automatic transfer switch. The settings level allows configuration of the
controller. Access to some settings may require entering a password (if the
controller is set for one – see page 2–1 and Appendix A–3).
top 2 lines show the
cause of any action
lower 2 lines show the
status of transfer sequence
tactile keys
(see below)
Power Control Center display and keypad.
Left–Right Arrows
The left A and right " arrow keys (Menu Scroll) navigate through the screens.
Enter/Save Settings
The Enter/Save Settings ¿ key move from the status level to the settings level
screens. It also is used to enter a new s etting.
Up–Down Arrows
The up Y and down B arrow keys (Increase Value and Decrease Value) modifies
a setting (setup parameter) while in the settings level screens.
Esc key
The Esc key ignores a change and returns to the status level.
Settings Overview
1--2Overview
The controller settings can be displayed and changed from the keypad.
Some settings may require a password (if the controller is set up for one).
From the ATS Status display, press Enter/Save Settings ¿ keytomovetothe
Settings level of menus.
SETTINGS
SETTINGS
Voltage DO PU
Frequency DO PU
VIEW
Event Log
Press the right arrow key " to see the eight parameter information headings (as
shown below). An overview of each setting is listed below. The detailed menus
for each setting are on the following pages.
8 Parameter Menus (loop back to beginning)
SETTINGS
General
SETTINGS
Time Delays
SETTINGS
Engine Exerciser
SERVICE
Statistics
Diagnostics
SETTINGS
Features
SERVICE
Factory
Selectable Features
Voltage and Frequency Settingsseepage2–2
CP settings and Normal & Emergency voltage and frequency pickup & dropout.
Time Delay Settingsseepage2–4
Bypass running time delay, and settings for all standard time delays.
Features Settingsseepage2–6
Commit on transfer, shed load, phase rotation, and inphase monitor settings.
General Settingsseepage2–8
Reset settings, language, communication, logging, and password.
Engine Exerciser Settingsseepage2–10
Present date and time, seven exercise programs each with six parameters.
View Event Logseepage2–12
Last 99 events in date and time order; six types and seven reasons are logged.
Service Statistics/Diagnostics, Factory Selectable Features
¢ Press up Y and downB arrow keys to changeflashing digit(s)or word and press
Enter/Save Settings ¿ keytomovetonextfield.
£ Repeat step ¢until all the fields have been entered.
If a field is blinking, the CP is waiting for information to be entered.
The Esc key will end the editing session.
Tip
Enter
Password
0
000
Tip
☞
☞
Password
Default password is 1111 (see page 2–8)
If Enter Password displays, y ou must enter the correct password first.
Use the up Y and down B arrow keys to change the flashing digit of the
password. Press the Enter/Save Settings ¿ keytomovetonextnextdigit
(left to right). When the correct password is displayed, press the Enter/Save Settings ¿ key.
If WRONG PASSWORD !!! displays, you are returned to the first flashing
digit. When the correct password is displayed, press the Enter/SaveSettings ¿ key.
You can now change the settings on the selected screen.
Once the password is entered it will stay unlocked for 5 minutes after last
key is pushed so that you do not have to keep entering it. So, to save time,
plan to make all your settings at one time.
Voltage & Frequency Settings
S
S
Frequency
Frequency
Unless otherwise specified on the order, the controller voltage and frequency
settings are set at the factory to the default values. If a setting must be changed,
carefully follow the procedure on the next page. Some settings may require a
password (if the controller is set up for one).
Any indiscriminate change in these settings may affect the normal
operation of the Automatic Transfer Switch. This change could allow
the load circuits to remain connected to an inadequate source.
2 --- 2Settings
DescriptionSettings
Dropout85 %70 to 98 %
Pickup90 %85 to 100 %
Normal
ource
Voltage
Emergency
ource
Voltage
Normal
Source
Emergency
Source
Over Voltage Trip *off102 to 115 %
Unbalance Enablenoyes or no
Unbalance Dropout20 %5to20%
Unbalance Pickup10 %3to18%
Dropout75 %70 to 98 %
Pickup90 %85 to 100 %
Over Voltage Trip *off102 to 115 %
Unbalance Enablenoyes or no
Unbalance Dropout20 %5to20%
Unbalance Pickup10 %3to18%
Dropout90 %85 to 98 %
Pickup95 %90 to 100 %
Over Frequency Trip *off102 to 110 %
Dropout90 %85 to 98 %
Pickup95 %90 to 100 %
Over Frequency Trip *off102 to 110 %
Default Setting
%ofnominal
Adjustment Range
increments of 1%
Display Screen
(see next page)
NORMAL VOLTAGE
Dropout
NORMAL VOLTAGE
Pickup
NORMAL VOLTAGE
OV Trip
NORMALVOLTAGEUNBAL
Enable
NORMALVOLTAGEUNBAL
Dropout
NORMALVOLTAGEUNBAL
Pickup
EMERG VOLTAGE
Dropout
EMERG VOLTAGE
Pickup
EMERG VOLTAGE
OV Trip
EMERG VOLTAGE UNBAL
Enable
EMERG VOLTAGE UNBAL
Dropout
EMERG VOLTAGE UNBAL
Pickup
NORMAL FREQUENCY
Dropout
NORMAL FREQUENCY
Pickup
NORMAL FREQUENCY
OF Trip
EMERG FREQUENCY
Dropout
EMERG FREQUENCY
Pickup
EMERG FREQUENCY
OF Trip
* The Over Voltage and Over Frequency reset is fixed at 2% below the trip setting.
2--3Settings
Voltage & Frequency Settings
The controller (CP) voltage and frequency setting can be displayed and changed
from the keypad. See the table on the previous page. Some settings may require
a password (if the controller is set up for one).
¡ From any of the Status displays, press the Enter/Save Settings ¿ key to move
5 Voltage & Frequency Menus (last menu loops back to first)
CP Settingsseepage2–1
This display shows the base configuration of the controller. These settings are
hardware activated and cannot be changed from the keypad:
Nominal source voltage — Normal and Emergency sources
Nominalsourcefrequency—50or60Hz
Normal & Emergency source sensing — single or 3 phase
Switch type — open, closed, or delayed transition
Normal Voltageseepage2–1
This display shows pickup, dropout, and over–voltage trip settings for the
Normal source. They are in percentage of nominal voltage and volts rms.
Normal Frequencyseepage2–1
This display shows pickup, dropout, and over–frequency trip settings for the
Normal source. They are in percentage of nominal frequency and Hz.
Normal Voltage Unbalanceseepage2–1
This display appears only if the CP is set for3 phase sensing onNormal. When
enabled, the CP considers the Normal source unacceptable if the calculated
voltage unbalance is greater than the specified dropout.
Emerg Voltageseepage2–1
This display shows pickup, dropout, and over–voltage trip settings for the
Emergency source. They are in percent of nominal voltage and volts rms.
Emerg Frequencyseepage2–1
This display shows pickup, dropout, and over–frequency trip settings for
Emergency source. They are in percentage of nominal frequency and Hz.
Emerg Voltage Unbalance (not shown)see page 2–1
This display appears only if the CP is set for 3 phase sensing on Emergency.
When enabled, the CP considers the Emergency source unacceptable if the
calculated voltage unbalance is greater than the specified dropout.
Time Delay Settings
A
4ACTS
Unless otherwise specified on the order, the Controller time delay settings are set at the
factory to the default values. If a setting must be changed, follow the procedure on the
next page. Some settings may require a password (if controller is set up for one).
Any indiscriminate change in these settings may affect the normal operation of the Automatic Trans-
fer Switch. This change could allow the load circuits to remain connected to an inadequate source.
2 --- 4Settings
FeatureTime DelayDefault Setting
1C ③
1F
2Btransfer to Emergency00to60min59secTD N>E
2E
3
31F ④
31M ④
31F, 31M
31G ④
31N ④
31G, 31N
,
7ACTS,
7ACTB
only①
4ADTS,
7ADTS/B
only
②
override momentary
Normal source outages
override momentary
Emergency source outages
unloaded running
(engine cooldown)
retransfer to Normal
(if Normal fails)
retransfer to Normal
(if just a test)
Normal to Emergency
pre–transfer signal
Normal to Emergency
post–transfer signal
bypass 31F & 31M
if Normal fails
Emergency to Normal
pre–transfer signal
Emergency to Normal
post–transfer signal
bypass 31G & 31N
if Emergency fails
in sync1.5 second
failure to s ynchronize5 minutes0to5min59sec
extended parallel time0.5 second
delay transition time00to5min59sec
1second
00to60min59secTD EmrgFail
5 minutes0to60min59secTD EngCool
30 minutes0to60min59sec
30 seconds
00to5min59sec
00to5min59sec
noyes or no
00to5min59sec
00to5min59sec
noyes or no
Adjustment Range
1 sec. increments
0to6sec
see CAUTION below
0 to 9 hours
59 min 59 s ec
0to3.0seconds
0.1 sec increments
0.100 to 1.000 sec
0.01 sec increments
Display Screen
(see next page)
TD NormFail
TD E>N if
Normal Fail
TD E>N if
Tes t M od e
TD N>E Xfer Signal
TD N>E Xfer Signal
TD N>E Xfer Signal
BypassIfNFail
TD E>N Xfer Signal
TD E>N Xfer Signal
TD E>N Xfer Signal
BypassIfEFail
CTTS TD
SyncMonitorTD
CTTS TD
FailToSyncTD
CTTS TD
XtdParallelTD
DTTS TD
LoadDisconnDelay
PreXfer
PostXfer
PreXfer
PostXfer
① These time delays appear only on the display for a 4ACTS, 7ACTS, or 7ACTB closed–transition transfer switch.
② This time delay appears only on the display for a 4ADTS, 7ADTS, or 7ADTB delayed–transition transfer switch
③ Standard adjustment up to 6 seconds (total power outage). For additional time delay contact ASI. See CAUTION.
④ If output contacts required, contact ASI at 1–800–800–2726.
Do not set Feature 1C TD longer than 6 sec. unless an external 24 V dc
power supply is included. Contact ASI if longer than 6 sec. is required.
2 --- 5
Settings
Time Delay Settings
The controller time delay (TD) settings can be displayed and changed from the
keypad. Some settings may require a password (if the control panel is set up for
one).
①
SETTINGS
Voltage DO PU
Frequency DO PU
②
SETTINGS
Time Delays
③
Bypass Currently
Running TD:_
External Battery: No
④
TD NormFail:mins
TD N>E:mins
TD EmrgFail:mins
TD EngCool:mins
① From any of the Status displays, press the Enter/Save Settings key to move to
the Settings level of menus.
② Press the right arrow keytomovetotheSetting Time Delays display.
③ Now press Enter/Save Settings keytomovetothefirstTime Delay menu.
④Yo u c a n p r e s s t h e right arrow key to see the other time delay menus (as shown
below). An overview explanation of each setting is listed below.
5 Time Delay Menus (last menu loops back to first)
Bypass Currently Runni ng TDseepage2–1
This display allows you to bypass some time delays. When the display is set
to Yes the controller will bypass any of these time delays
Feature 1C — Momentary Normal failure time delay
Feature 2B — Normal to Emergency transfer time delay
Feature 3A — Emergency to Normal transfer time delay
External Battery: see CAUTION on bottom of page 2–4
Ye s means externalbattery connected, Feature 1C can be set longer than 6 sec.
No mean there is no external battery, Feature 1C can be set for 0–6 sec. only
Standard Time Delaysseepage2–1
This display shows the settings for the following standard time delays:
Feature 1C — Momentary Normal source failure time delay
Feature 2B — Normal to Emergency transfer time delay
Feature1F—MomentaryEmergencysourcefailuretimedelay
Feature 2E — Engine cooldown time delay
TD E>N if
Normal Fail:mins
Test Mode:hmins
TD N>E X fer Signal
BypassIfNFail:
PreXfer:mins
PostXfer:mins
TD E>N X fer Signal
BypassIfEFail:
PreXfer:mins
PostXfer:mins
TD E>N ifseepage2–1
This display shows the settings for Feature 3A retransfer to Normal time
delay. There are two modes:
Normal source outage — retransfer TD if Normal fails
Transfer Test — retransfer TD if just a test
TD N>E Xfer Signalseepage2–1
This display shows the settings for the time delays used to signal external
equipment before and after transfer from Normal to Emergency:
Feature 31F — Pre–transfer time delay signal
Feature 31M — Post–transfer time delay signal
TD E>N Xfer Signalseepage2–1
This display shows the settings for the time delays used to signal external
equipment before and after retransfer from Emergency to Normal:
Feature 31G — Pre–transfer time delay signal
Feature 31N — Post–transfer time delay signal
CTTS TDs (not shown)see page 2–1
DTTS TD (not shown)see page 2–1
Features Settings
Unless otherwise specified on the order, the controller features settings are set at the
factory to the default values. If a setting must be changed, follow the procedure on the
next page. Some settings may require a password (if the controller is set up for one).
Any indiscriminate change in these settings may affect the normal operation of the Automatic Trans-
fer Switch. This change could allow the load circuits to remain connected to an inadequate source.
2 --- 6Settings
FeatureDefault SettingAdjustment Range
commit to transfernoyes or no
shed load directionfrom Efrom N or from E
shed load in phasenoyes or no
shed load in phase time delay1.5 second
shed load isolate load
on source failure
shed load isolate load on test 17②
phase rotation monitor enable ③
phase rotation monitor reference ③
inphase monitor enable ④
②
0to3.0seconds
0.1 sec increments
yesyes or no
noyes or no
noyes or no
ABCABC or CBA
noyes or no
Display Screen
(see next page)
Commit to Xfer After
TD Norm Fail
SHED LOAD
Direction
SHED LOAD
InPhase
SHED LOAD
TD
SHED LOAD
IsoLoadOnSrcFail
SHED LOAD
IsoLoadOnTest17
PHASE ROTATION
MONITOR
Enable
PHASE ROTATION
MONITOR
Reference
IN–PHASE
MONITOR
Enable
inphase monitor time delay ④
failure to sync auto bypass ①
bypass time delay ①
bypass in phase ①
Y–Y primary failure detection enablenoyes or no
Y–Y primary failure sensing time delay1.0 second
Y–Y primary failure retransfer time delay1.0 hour
1.5 second
noyes or no
0second
noyes or no
0to3.0seconds
0.1 sec increments
0to59seconds
1 sec increments
0to9.9seconds
0.1 sec increments
0to23hrs59min.
1 min. increments
CTTS BYPASS/SHED LD
CTTS BYPASS/SHED LD
CTTS BYPASS/SHED LD
IN–PHASE
MONITOR
Time Delay
FailSyncAutoByps
Bypass DT Delay
Bypass InPhase
Y–Y PRI FAIL DETECT
Enable
Y–Y PRI FAIL DETECT
Sense Delay
Y–Y PRI FAIL DETECT
TD E>N Y–Y
① These features appear only on the display for a 4ACTS, 7ACTS, or 7ACTB closed–transition transfer switch.
② These features appear only on the display for a 4ACTS, 7ACTS or 7ACTB closed–transition transfer switch
or a 4ADTS, 7ADTS, or 7ADTB delayed–transition transfer switch.
③ These features do not appear on the display unless both sources have 3 phase sensing enabled.
④ These features appear only on a 4ATS, 7ATS, or 7ATB (open–transition automatic transfer switch).
The controller (CP) Features settings can be displayed and changed from the keypad. Some settings may require a password (if the controller is set up for one).
¡ From any of the Status displays, press the Enter/Save Settings ¿ key to move
below). An overview explanation of each setting is listed below.
7 Features Menus (last menu loops back to first)
Commit to Xfer After TD Normal Failseepage2–1
This display shows the commit to transfer setting. It affects the transfer
sequence as follows:
Ye s — If Normal fails, CP continues transfer sequence to emergency
even if Normal returns before Emergency becomes acceptable.
No — If Normal fails, C P cancels the transfer sequence to emergency
if Normal returns before Emergency becomes acceptable.
Shed Loadseepage2–1
This display shows status of 3 load shed parameters:
Direction — from Emergency or from Normal
InPhase — yes means transfer delayed until sources are in phase
TD — 3 second default time delay
¤
SHED LOAD
Direction:
InPhase:TD:s
SHED LOAD
IsoLoadOnSrcFailyes
IsoLoadOnTest17no
PHASE ROTATION
MONITOR
Enable:
Reference:
IN--PHASE
MONITOR
Enable:
Time Delay:s
Shed Load Optionsseepage2–1
This display appears only for 4ACTS, 4ADTS, 7ACTS, 7ACTB, 7ADTS, or
7ADTB. It determines switch position after the shed load transfer.
IsoLoadOnSrcFail — determines switch position during a source failure.
IsoLoadOnTest17 — deterines switch position during feature 17 activation.
Ye s — Load is not connected to eithersource.(see wiring diagram
No — Load is connected to the opposite source. for feature 17 desc.)
Phase Rotation Monitorseepage2–1
This display shows status of phase rotation monitor and desired reference
phase rotation. It only appears if both sources are set to 3–phase sensing.
Enabled — Ye s means phase rotation is considered as part of the
source acceptability criteria for each source. If the phase rotation of the
source does not match the reference phase rotation, that source is considered
unacceptable. If phase rotation of the two sources is different, the load will
be transferred to the source with the reference phase rotation.
Reference — phase rotation order: ABC or CBA (ABC is default)
In–Phase Monitorseepage2–1
This display appears only for 4ATS, 7ATS or 7ATB. This display shows status
of in–phase monitor and in–phase time delay (1.5 seconds is default setting).
Enabled — Ye s means in–phase transfer is initiated when any of these
conditions are met: Transfer Test (Feature 5) signal, connected source fails,
retransfer to acceptable Normal occurs and Emergency source acceptable.
CTTS Bypass / Shed Load (not shown)see page 2–1
This display shows status of the closed–transition bypass options.
FailSyncAutoBy pass — Ye s means if the fail to sync alarm occurs, the controller
will bypass the closed–transition mode and will make a delayed–transiton
transfer. The load disconnect time is set by the Bypass DT Delay parameter.
Bypass InPhase — Ye s means the inphase monitor is active during load transfer.
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.