Failure to follow these instructions or to
properly install and maintain this
equipment could result in an explosion,
re and/or chemical contamination
causing property damage and personal
injury or death.
Fisher® regulators must be
installed, operated and maintained
in accordance with federal, state and
local codes, rules and regulations and
Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents gas or a leak
develops in the system, service to
the unit may be required. Failure to
correct trouble could result in a
hazardous condition.
TYPE 67DF OR 67DFR FILTERED REGULATORTYPE 67D OR 67DR REGULATOR
Installation, operation and maintenance
procedures performed by unquali ed
personnel may result in improper
adjustment and unsafe operation. Either
condition may result in equipment
damage or personal injury. Use quali ed
personnel when installing, operating
and maintaining the 67D Series Pressure
Reducing Regulators.
Introduction
Scope of the Manual
This manual provides instructions for the installation,
maintenance and parts ordering information for
67D Series regulators. Instructions and parts lists for
other equipment mentioned in this instruction manual,
as well as for other 67 Series regulators, are found in
separate manuals.
www.fisherregulators.com
D103151X012
67D Series
Specications
This section lists the specications for the 67D Series regulators. Factory specication such as type, maximum
inlet pressure and outlet pressure are stamped on the nameplate fastened on the regulator at the factory.
Available CongurationsType 67D: Direct-operated regulator with
aluminum body and without internal relief
Type 67DR: Aluminum body with internal reliefType 67DS: Stainless steel body without internal reliefType 67DSR: Stainless steel body with internal reliefType 67DF: Aluminum body with lter and without
internal relief
Type 67DFR: Aluminum body with lter and
internal relief
Type 67DFS: Stainless steel body with lter and
without internal relief
Type 67DFSR: Stainless steel body with lter and
internal relief
Body Size, Inlet and Outlet Connection Style1/2 NPT
Maximum Inlet Pressure (Body Rating)
(1)
All ltered models: 250 psig / 17.2 bar
All unltered models: 400 psig / 27.6 bar
Outlet Pressure Ranges
See Table 1
Maximum Emergency Outlet Pressure
(1)
150 psi / 10.3 bar over outlet pressure setting up to a
pressure can exceed the maximum pressure rating
of downstream equipment or exceeds maximum
outlet pressure rating of the regulator.
Approximate Weights
Types 67D and 67DR: 1.2 pounds / 0.5 kg
Types 67DF and 67DFR: 2.0 pounds / 1 kg
Types 67DS and 67DSR: 2.8 pounds / 1 kg
Types 67DFS and 67DFSR: 4.6 pounds / 2 kg
Smart Bleed™ Check Valve Setpoint
6 psi / 0.41 bar differential
Temperature Capabilities
(1)
With Nitrile (NBR):
Standard Bolting: -20 to 180°F / -29 to 82°CStainless Steel Bolting: -40 to 180°F / -40 to 82°C
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Silicone (VMQ) is not compatible with hydrocarbon gas.
3. Product complies with the material requirements of NACE International MR0175 or MR0103. Environmental limits may apply.
4. Do not use in high aromatic hydrocarbon service.
Temperature Capabilities
With Fluorocarbon (FKM):
Polyethylene Filter
0 to 180°F / -18 to 82°C
Polyvinylidene (PVDF), Stainless steel or
Glass Filter (Optional):
0 to 300°F / -18 to 149°C
With Silicone (VMQ)
Low Temperature Nitrile (NBR) O-rings and
Low Temperature Bolting:
-60 to 180°F / -51 to 82°C
With Gauges: -20 to 180°F / -29 to 82°CWith Automatic Drain: 40 to 175°F / 4 to 79°C
Types 67DF, 67DFR, 67DFS and 67DFSR
Filter Capabilities
Micron Rating:
Aligned with inlet standard, other positions optional
Drain Valve Location
Aligned in the center of the dripwell
Pressure Registration
Internal
Options
All Types
• Handwheel adjusting screw
• NACE International MR0175 or
MR0103
(3)
construction
• Panel mount (includes spring case with 1/4 NPT
vent, handwheel and panel mounting nut)
• Closing cap (available on spring case with
1/4 NPT vent)
• Fluorocarbon (FKM) elastomers for high
temperatures and/or corrosive chemicals
• Silicone (VMQ) elastomers for cold temperatures
• Fixed Bleed Restriction
• Triple scale outlet pressure gauge (Brass or
Stainless steel)
• Stainless steel stem and valve plug
• Pipe plug in second outlet
Types 67DFR and 67DFSR
• Smart Bleed internal check valve
Types 67DF, 67DFR, 67DFS and 67DFSR
• Stainless steel drain valve
(1)
(continued)
(4)
(Standard):
(2)
Diaphragm,
(4)
(Standard): 5 microns
2
67D Series
Type XXXX
TYPE 67D OR 67DSTYPE 67DF OR 67DFS
M1153M1154
SMART BLEED OPTION FOR
TYPE 67DFR OR 67DFSR
TYPE 67DR OR 67DSR
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
Figure 2. 67D Series Operational Schematics
TYPE 67DFR OR 67DFSR
Product Descriptions
The 67D Series direct-operated regulators are typically
used to provide constantly controlled, reduced pressures.
They are suitable for most air or gas applications.
• The Types 67D and 67DS are the standard
instrument supply regulators without a lter or
internal relief.
• The Types 67DF and 67DFS are equipped with a
lter for removing particles from the supply gas.
• The Types 67DR and 67DSR have an internal relief
valve with a soft seat for reliable shutoff with no
discernible leakage.
• The Types 67DFR and 67DFSR have a lter and
internal relief valve with a soft seat for reliable
shutoff with no discernible leakage.
Principle of Operation
Downstream pressure is registered internally on the
lower side of the diaphragm. When the downstream
pressure is at or above the set pressure, the valve plug
is held against the ori ce and there is no ow through
the regulator. When demand increases, downstream
pressure drops slightly allowing the spring to extend,
moving the stem down and the valve plug away from
the ori ce. This allows ow through the regulator.
Internal Relief (Types 67DR, 67DSR,
67DFR and 67DFSR)
If for some reason, outside of normal operating
conditions, the downstream pressure exceeds the
setpoint of the regulator, the force created by the
downstream pressure will lift the diaphragm until the
diaphragm is lifted off the relief seat. This allows ow
through the token relief. The relief valve on the
Type 67DR, 67DSR, 67DFR or 67DFSR is an
elastomer plug that prevents leakage of air from the
downstream to atmosphere during normal operation,
thereby conserving plant air.
Smart Bleed™ Airset
In some cases, it is desired to exhaust downstream
pressure if inlet pressure is lost or drops below the
setpoint of the regulator. For example, if the regulator
is installed on equipment that at times has no ow
demand but is expected to back ow on loss of inlet
pressure. The Type 67DFR or 67DFSR can be ordered
with the Smart Bleed option which includes an internal
check valve for this application. During operation, if
inlet pressure is lost, or decreases below the setpoint of
the regulator, the downstream pressure will back ow
upstream through the regulator and check valve. This
option eliminates the need for a xed bleed downstream
of the regulator, thereby conserving plant air.
3
67D Series
OUTLET PRESSURE
TYPE
67D, 67DR,
67DF and
67DFR
67DS, 67DSR,
67DFS and
67DFSR
Inconel® is a mark owned by Special Metals Corporation.
RANGES
psigbarInchmmInchmm
0 to 20
0 to 35
0 to 60
0 to 125
0 to 35
0 to 60
0 to 125
0 to 20
0 to 35
0 to 60
0 to 125
0 to 150
0 to 1.4
0 to 2.4
0 to 4.1
0 to 8.6
0 to 2.4
0 to 4.1
0 to 8.6
0 to 1.4
0 to 2.4
0 to 4.1
0 to 8.6
0 to 10.3
Table 1. Outlet Pressure Ranges and Control Spring Data
CONTROL SPRING DATA
Part NumberColorMaterial
GE07809T012
T14059T0012
T14058T0012
T14060T0012
T14113T0012
T14114T0012
T14115T0012
10C1729X012
T14113T0012
T14114T0012
T14115T0012
10C1730X012
Green stripe
Unpainted
Blue stripe
Red stripe
Silver stripe
Blue
Red
Green
Silver stripe
Blue
Red
Black
Music Wire
Inconel
Inconel
®
®
Wire DiameterFree Length
0.135
0.156
0.170
0.207
0.156
0.172
0.207
0.135
0.156
0.172
0.207
0.250
3.43
3.96
4.32
5.26
3.96
4.37
5.26
3.43
3.96
4.37
5.26
6.35
1.43
1.43
1.43
1.43
1.43
1.43
1.43
1.50
1.43
1.43
1.43
1.77
36.2
36.2
36.2
36.2
36.2
36.2
36.2
38.1
36.2
36.2
36.2
44.9
Installation
Note
If the regulator is shipped mounted on
another unit, install that unit according
to the appropriate Instruction Manual.
WARNING
!
Personal injury, property damage,
equipment damage or leakage due to
escaping gas or bursting of pressurecontaining parts may result if this
regulator is overpressured or is installed
where service conditions could exceed
the limits given in the Specications
section, or where conditions exceed any
ratings of the adjacent piping or piping
connections. To avoid such injury or
damage, provide pressure-relieving or
pressure-limiting devices (as required
by the appropriate code, regulation or
standard) to prevent service conditions
from exceeding those limits.
The internal relief valve of the
Type 67DR, 67DSR, 67DFR or 67DFSR
does not provide full overpressure
protection. The internal relief valve is
designed for minor seat leakage only. If
maximum inlet pressure to the regulator
exceeds maximum pressure ratings of
the downstream equipment or exceeds
maximum allowable outlet pressure of
the regulator, additional overpressure
protection is required.
A regulator may vent some gas to
the atmosphere. In hazardous or
ammable gas service, vented gas may
accumulate and cause personal injury,
death or property damage due to re or
explosion. Vent a regulator in hazardous
gas service to a remote, safe location
away from air intakes or any hazardous
area. The vent line or stack opening
must be protected against condensation
or clogging.
Before installing a Type 67D, 67DR, 67DS, 67DSR,
67DF, 67DFR, 67DFS or 67DFSR regulator, be
sure the installation complies with the following
installation guidelines:
1. Regulator operation within ratings does not
preclude the possibility of damage from debris
in the lines or from external sources. Regulators
should be inspected for damage periodically and
after any overpressure condition.
2. Only personnel qualied through training and
experience should install, operate and maintain
the regulator. Make sure that there is no damage
to or foreign material in the regulator. Also ensure
that all tubing and piping is free of debris.
3. Install the regulator so that ow is from the IN to the
OUT connection as marked on the regulator body.
4. A clogged spring case vent hole may cause the
regulator to function improperly. To keep this
vent hole from being plugged (and to keep the
spring case from collecting moisture, corrosive
chemicals or other foreign material) orient the vent
to the lowest possible point on the spring case or
otherwise protect it.
4