TYPE 67DF OR 67DFR FILTERED REGULATORTYPE 67D OR 67DR REGULATOR
• Easy Maintenance
• Optional Integral Filter
• Optional Internal Relief Valve
• Rugged Construction
www. sherregulators.com
D103152X012
Bulletin 71.1:67D
Introduction
The 67D Series regulators are typically used to deliver constant reduced pressure of gaseous uids to pilot-operated
controllers and other pneumatic instrumentation. As shown in the Available Congurations table, an assortment of regulators
is available to meet diverse ow requirements.
Features
•
Compact—The 67D Series regulators are
engineered for outstanding performance in a
compact, lightweight package.
• Pilot Supply Regulator—Improves the accuracy
of two-path control regulators by reducing inlet
sensitivity caused by uctuating inlet pressures.
• Pressure Loading Regulator—Provides accuracy and
improved performance in dirty steam service by
eliminating the need for a pilot regulator.
• Sour Gas Service Capability—NACE International MR0175
and MR0103 compliant construction available.
• Optional Stainless Steel Construction—The
Types 67DS, 67DSR, 67DFS, and 67DFSR
provide high resistance to corrosion, which is especially
benecial for offshore applications.
• Full Usable Capacity—Fisher® regulators are
laboratory tested. 100% of the published capacities
can be used with condence.
• Internal Relief—The Types 67DR, 67DSR, 67DFR,
and 67DFSR have an internal relief valve with a soft seat
for reliable shutoff with no discernible leakage. These
regulators are recommended for conserving plant air.
• Smart Bleed™—Opens to exhaust downstream
pressure when inlet pressure drops below outlet
pressure. Recommended for dead-end service.
• Integral Filter—The Types 67DF, 67DFR, 67DFS,
and 67DFSR have an integral lter ensuring clean
downstream air supply.
• Ease of Maintenance—No special tools are
required to perform maintenance, and all maintenance
can be performed with the regulator in the line. Filter
elements are easily replaced.
• Rugged Construction—The 67D Series regulators
are engineered for longer service life with minimal
maintenance requirements.
• Dual Second Outlets—Body side outlets for
pressure gauge or other uses.
• Corrosion Resistant Fasteners—Bolting and
adjusting screw are double zinc-chromated for
enhanced corrosion resistance. Optional stainless
steel bolting and adjusting screw are also available.
2
Specications
Bulletin 71.1:67D
Available Congurations
Type 67D: Direct-operated regulator with
aluminum body and without internal relief
Type 67DR: Aluminum body with internal relief
Type 67DS: Stainless steel body without
internal relief
Type 67DSR: Stainless steel body with internal relief
Type 67DF: Aluminum body with lter and without
internal relief
Type 67DFR: Aluminum body with lter and
internal relief
Type 67DFS: Stainless steel body with lter and without
internal relief
Type 67DFSR: Stainless steel body with lter and
internal relief
See also Table 1
Body Size, Inlet and Outlet Connection Style
1/2 NPT
Construction Materials
See Table 3
Maximum Inlet Pressure (Body Rating)
(1)
All ltered models: 250 psig / 17.2 bar
All unltered models: 400 psig / 27.6 bar
Outlet Pressure Ranges
See Table 2
Maximum Emergency Outlet Pressure
(1)
150 psi / 10.3 bar over outlet pressure setting up to a
maximum of 250 psi / 17.2 bar
Types 67DR, 67DSR, 67DFR, and 67DFSR Internal
Relief Performance
Low capacity for minor seat leakage only, other
overpressure protection must be provided if inlet
pressure can exceed the maximum pressure rating
of downstream equipment or exceeds maximum
outlet pressure rating of the regulator.
Approximate Weights
Types 67D and 67DR: 1.2 pound / 0.5 kg
Types 67DF and 67DFR: 2.0 pounds / 0.9 kg
Types 67DS and 67DSR: 2.8 pounds / 1.2 kg
Types 67DFS and 67DFSR: 4.6 pounds / 2.1 kg
Smart Bleed™ Check Valve Setpoint
6 psi / 0.41 bar differential
Pressure Registration
Internal
Spring Case Vent Location
Aligned with inlet standard, other positions optional
Drain Valve Location
Aligned in the center of the dripwell
Temperature Capabilities
(1)
With Nitrile (NBR)
Standard Bolting: -20 to 180°F / -29 to 82°C
Stainless Steel Bolting: -40 to 180°F / -40 to 82°CWith Fluorocarbon (FKM): Polyethylene Filter
(4)
(Standard):
0 to 180°F / -18 to 82°C Polyvinylidene (PVDF), Stainless Steel, or Glass Filter (Optional):
0 to 300°F / -18 to 149°C
With Silicone (VMQ)
(2)
diaphragm, Low Temperature
Nitrile (NBR) O-rings, and Low Temperature
bolting: -60 to 180°F / -51 to 82°C
With Gauges: -40 to 180°F / -40 to 82°C
With Automatic drain: 40 to 175°F / 4 to 79°C
Types 67DF, 67DFR, 67DFS, and 67DFSR Filter Capabilities
Downstream pressure is registered internally on the lower side of
the diaphragm. When the downstream pressure is at or above
the set pressure, the valve plug is held against the ori ce and
there is no ow through the regulator. When demand increases,
downstream pressure drops slightly allowing the spring to
extend, moving the stem down and the valve plug away from the
ori ce. This allows ow through the regulator.
Internal Relief
(Types 67DR, 67DSR, 67DFR, and 67DFSR)
If for some reason, outside of normal operating conditions,
the downstream pressure exceeds the setpoint of the
regulator, the force created by the downstream pressure
will lift the diaphragm until the diaphragm is lifted off the
relief seat. This allows ow through the token relief. The
relief valve on the Type 67DR, 67DSR, 67DFR, or 67DFSR
is an elastomer plug that prevents leakage of air from
the downstream to atmosphere during normal operation,
thereby conserving plant air.
Smart Bleed™ Airset
In some cases, it is desired to exhaust downstream pressure
if inlet pressure is lost or drops below the setpoint of the
regulator. For example, if the regulator is installed on
equipment that at times has no ow demand but is expected
to back ow on loss of inlet pressure. The Type 67DFR or
67DFSR can be ordered with the Smart Bleed option which
includes an internal check valve for this application. During
TYPE 67DF OR 67DFS
M1154
SMART BLEED™ OPTION FOR
TYPE 67DFR OR 67DFSR
operation, if inlet pressure is lost, or decreases below the
setpoint of the regulator, the downstream pressure will back
ow upstream through the regulator and check valve. This
option eliminates the need for a xed bleed downstream of
the regulator, thereby conserving plant air.
Note
During normal operation the check valve’s metal
to metal seat allows limited ow through the
regulator from the inlet to outlet, even when
there is no downstream demand. To prevent
downstream pressure buildup, the Smart Bleed
option is only avilable with the internal relief
version of the 67 Series.
Installation
The 67D Series regulators may be installed in any position.
Spring case vents must be protected against the entrance
of rain, snow, debris, or any other foreign material that might
plug the vent openings. The inlet connection is marked “In”
and the main outlet connection is marked “Out”. If a pressure
gauge is not installed in one of the two secondary outlet
connections, plug the unused connections. See Figures 4
and 5 for dimensions.
Emerson Process Management Regulator Technologies,
Inc. provides an instruction manual with every regulator
shipped. Refer to this for complete installation, operation and
maintenance instructions. Included is a complete listing of
individual parts and recommended spare parts.
5
Bulletin 71.1:67D
Overpressure Protection
The 67D Series regulators have maximum outlet pressure
ratings that are lower than their maximum inlet pressure
ratings. A pressure-relieving or pressure-limiting device is
needed if inlet pressure can exceed the maximum outlet
pressure rating.
Types 67DR, 67DSR, 67DFR, and 67DFSR regulators have
a low capacity internal relief valve for minor seat
Other overpressure protection must be provided if the maximum
inlet pressure can exceed the maximum pressure rating of the
downstream equipment or exceeds maximum outlet pressure
rating of the Type 67DR, 67DSR, 67DFR, or 67DFSR regulator.
Overpressuring any portion of a regulator or associated
equipment may cause leakage, parts damage, or personal
injury due to bursting of pressure-containing parts or
explosion of accumulated gas. Regulator operation within
ratings does not preclude the possibility of damage from
external sources or from debris in the pipeline. A regulator
should be inspected for damage periodically and after any
overpressure condition.
Refer to the Capacity Information section and the Wide-
Open Flow Coefcients for Relief Valve Sizing in the
Specications section on page 3 to determine the required
relief valve capacity.
leakage only.
Note
The 67D Series regulators may be sized for 100%
ow using capacities as shown in Table 4. It is
not necessary to reduce published capacities.
To determine the equivalent capacities for other gases,
multiply the table capacity by the following appropriate
conversion factor: 1.29 for 0.6 specic gravity natural gas,
0.810 for propane, 0.707 for butane, or 1.018 for nitrogen.
For gases of other specic gravities, divide the table
capacities by the square root of the appropriate specic
gravity. To nd wide-open ow capacities for relief sizing at
any inlet pressure, perform one of the following procedures.
Then, if necessary, convert using the factors provided above.
For critical pressure drops (absolute outlet pressure equal
to or less than one-half of absolute inlet pressure), use the
following formula:
Q = (P1)(Cg)
For pressure drops lower than critical (absolute outlet
pressure greater than one-half of absolute inlet pressure),
use the following formula:
SIN
3417
)
C
P
DEG
)
P
1
1
where,
520
=
Q
GT
C
gP1
Capacity Information
Table 4 shows the air regulating capacities of the
67D Series regulators at selected inlet pressures and
outlet pressure settings. Flows are shown in SCFH (at
60°F and 14.7 psia) and in Nm3/h (at 0°C and 1.01325 bar)
of air.
POSITION 3
POSITION 2POSITION 4
GE31784
POSITION 1 (ALIGNED WITH INLET) (STANDARD)
Figure 3. 67D Series Vent Positions
Q = gas ow rate, SCFH
P1 =
Cg = gas sizing coefcient
G = specic gravity of the gas
T = absolute temperature of gas at inlet, °Rankine
C1 = ow coefcient (Cg ÷ Cv)
P = pressure drop across the regulator, psi
Then, if capacity is desired in normal cubic meters per hour
(at 0°C and 1.01325 bar), multiply SCFH by 0.0268.
absolute inlet pressure, psia (P1 gauge + 14.7)
NACE Universal Compliance
Optional materials are available for applications handling sour
gases. These constructions comply with the recommendations
of NACE International sour service standards.
The manufacturing processes and materials used by
Regulator Technologies assure that all products specied
for sour gas service comply with the chemical, physical, and
metallurgical requirements of NACE MR0175 and/or NACE
MR0103. Customers have the responsibility to specify
correct materials. Environmental limitations may apply and
shall be determined by the user.
6
Table 4. 67D Series Flow Capacities
Bulletin 71.1:67D
OUTLET PRESSURE
RANGE, SPRING PART
NUMBER AND
COLOR CODE
0 to 20 psig / 0 to 1.4 bar
GE07809T012
(Green Stripe)
10C1729X012
(Green)
0 to 35 psig / 1 to 2.4 bar
T14059T0012 (Silver)
T14113T0012
(Silver Stripe)
1. Inlet pressures above 250 psig / 17.2 bar with a maximum of 400 psig / 27.6 bar are only available on unltered models (Types 67D, 67DR, 67DS, and 67DSR).
OUTLET
PRESSURE
psigbarpsigbar
50.34
100.69
201.4
151.0
201.4
352.4
INLET
PRESSURE
25
1.7
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
25
1.7
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
25
1.7
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
25
1.7
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
50
3.4
75
5.2
100
6.9
150
10.3
200
13.8
250
17.2
(1)
400
27.6
Types 67D, 67DR, 67DS, and 67DSRTypes 67DF, 67DFR, 67DFS, and 67DFSR
1. Inlet pressures above 250 psig / 17.2 bar with a maximum of 400 psig / 27.6 bar are only available on unltered models (Types 67D, 67DR, 67DS, and 67DSR).
2. Available for Types 67DS, 67DSR, 67DFS, and 67DFSR only.
(2)
OUTLET
PRESSURE
psigbarpsig bar
352.4
604.1
604.1
805.5
1258.6
1107.6
1359.3
150 10.3
INLET
PRESSURE
50
75
100
150
10.3
200
13.8
250
17.2
(1)
400
27.6
75
100
150
10.3
200
13.8
250
17.2
(1)
400
27.6
75
100
135
150
10.3
200
13.8
250
17.2
(1)
400
27.6
100
135
150
10.3
200
13.8
250
17.2
(1)
400
27.6
135
150
10.3
200
13.8
250
17.2
(1)
400
27.6
150
10.3
200
13.8
250
17.2
(1)
400
27.6
150
10.3
200
13.8
250
17.2
(1)
400
27.6
200
13.8
250
17.2
(1)
400
27.6
Types 67D, 67DR, 67DS, and 67DSRTypes 67DF, 67DFR, 67DFS, and 67DFSR
When ordering, complete the Ordering Guide on pages 11
and 12. Refer to the Specications section on page 3.
Review the description to the right of each specication and
the information in each referenced table or gure. Specify
your choice whenever a selection is offered.
8
Bulletin 71.1:67D
C
SIDE OUTLET
1/4 NPT
GG01138
VENT
B MAX
A
D
E
SIDE OUTLET
1/4 NPT
INLET CONNECTION
1/2 NPT
OPTIONAL
GAUGE
F
G
OUTLET
CONNECTION
1/2 NPT
TYPE 67D OR 67DR
1.44 /
C
D
E
37
F
G
CLOSING CAP
B
1.33 /
34
A
OPTIONAL
GAUGE
GG01145
SIDE OUTLET
1/4 NPT
TYPE 67DS OR 67DSR
STANDARD DIMENSIONS FOR GAUGE OPTION
Figure 4. Types 67D, 67DR, 67DS, and 67DSR Dimensions
Table 5. Types 67D, 67DR, 67DS, and 67DSR Dimensions
Figure 5. Types 67DF, 67DFR, 67DFS, and 67DFSR Dimensions
Table 6. Types 67DF, 67DFR, 67DFS, and 67DFSR Dimensions
TYPES
67DF and 67DFR5.931513.6693
67DFS and 67DFSR 6.271595.12130
10
ABCDEFGHI
Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm
4.54 11 52.98761.49382.88730.63160.69182.2557
DIMENSIONS
MOUNTING HOLES
FOR 5/16 / 7.9
DIAMETER BOLTS
I
STANDARD DIMENSIONS
INCHES /
mm
Ordering Guide
Bulletin 71.1:67D
Type (Select One)
67D (aluminum without internal relief)***
67DR (aluminum with internal relief)***
67DS (stainless steel without
internal relief)***
67DSR (stainless steel with internal relief)***
67DF (aluminum with lter and without
internal relief)***
67DFR (aluminum with lter and
internal relief)***
67DFS (stainless steel with lter and without
internal relief)***
67DFSR (stainless steel with lter and
internal relief)***
Quantity (Specify)
Spring Case Style (Select One)
Drilled hole vent (Types 67D, 67DR, 67DF, and
67DFR standard)***
1/4 NPT vent (Types 67DS, 67DSR, 67DFS,
and 67DFSR standard)***
Single hole panel mount***
Adjusting Screw (Select One)
Square head (Types 67D, 67DR, 67DF,
67DFR standard)***
Square head with closing cap (Types 67DS,
67DSR, 67DFS, and 67DFSR standard)***
Handwheel***
Outlet Pressure Range (Select One)
0 to 20 psig / 0 to 1.4 bar***
0 to 35 psig / 0 to 2.4 bar***
0 to 60 psig / 0 to 4.1 bar***
0 to 125 psig / 0 to 8.6 bar***
0 to 150 psig / 0 to 10.3 bar (Types 67DS, 67DSR,
67DFS, and 67DFSR only)***
Diaphragm, O-Rings, and Valve Seat Plug (Select One)
Nitrile (NBR) (standard)***
Fluorocarbon (FKM)**
Silicone (VMQ) diaphragm, Low Temperature
Nitrile (NBR) O-rings, and Nitrile (NBR) valve seat*
Drain Valve (Select One)
Brass (Types 67DF and 67DFR standard)***
Stainless steel (Types 67DFS and
67DFSR standard)***
Automatic Drain with Nitrile (NBR) elastomers***
Automatic Drain with Fluorocarbon (FKM) elastomers**
Spring Case Vent Location (Select One)
Position 1 - Aligned with inlet (standard)***
Position 2
Position 3
Position 4
External Fixed Bleed for Type 67DR, 67DSR, 67DFR, or
67DFSR (Optional)
Yes**
Smart Bleed™ Internal Check Valve Airset
(Optional - Types 67DFR and 67DFSR only)
Yes**
Second Outlet (Select One)
Open (Types 67D, 67DR, 67DF, and
67DFR standard)***
Plugged with pipe plug (Types 67DS, 67DSR,
67DFS, and 67DFSR standard)***
Pressure Gauge (see below)
Triple Scale Pressure Gauge (Optional)
Brass Gauge or Stainless Steel Gauge
0 to 30 psig / 0 to 0.2 MPa / 0 to 2.1 bar***
0 to 60 psig / 0 to 0.4 MPa / 0 to 4.1 bar***
0 to 160 psig / 0 to 1.1 MPa / 0 to 11.0 bar***
- continued -
11
Bulletin 71.1:67D
Ordering Guide (continued)
NACE International MR0175 Construction (Optional)
Yes (not available with gauge)**
NACE International MR0103 Construction (Optional)
Yes (not available with gauge)**
Replacement Parts Kit (Optional)
Yes, send one replacement parts kit to match
this order.
1. Product complies with the material requirements of NACE International MR0175.
Environmental limits may apply.
Regulators Quick Order Guide
Readily Available for Shipment
* * *
Allow Additional Time for Shipment
* *
Special Order, Constructed from Non-Stocked Parts.
*
Consult Your local Sales Ofce for Availability.
Availability of the product being ordered is determined by the component
with the longest shipping time for the requested construction.
(1)
Specication Worksheet
Application (Please designate units):
Specic Use
Line Size
Gas Type and Specic Gravity
Gas Temperature
Does the Application Require Overpressure Protection?
Yes No If yes, which is preferred:
Relief Valve Monitor Regulator
Shut-off Device
Is overpressure protection equipment selection assistance
desired?
Pressure (Please designate units):
Maximum Inlet Pressure (P
Minimum Inlet Pressure (P
1max
1min
)
)
Downstream Pressure Setting(s) (P2)
Maximum Flow (Q
max
)
Performance Required:
Accuracy Requirements?
Need for Extremely Fast Response?
Other Requirements:
Industrial Regulators
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9000
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.
Natural Gas Technologies
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Singapore 128461, Singapore
Tel: +65 6770 8337
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Gallardon 28320, France
Tel: +33 2 37 33 47 00
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250
Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287