Emerson 3-9000-771A User Manual

Installation Manual
Part Number 3-9000-771Revision A
May 2012
Daniel
TM
3818 LNG Liquid Ultrasonic Meter
For Cryogenic Liquefied Natural Gas Applications

Important Safety Instructions

Failure to follow the Installation, operation or maintenance instructions for a Daniel product could lead to serious injury or death from explosion or exposure to dangerous substances. To reduce this risk:
Comply with all information on the product, in this manual, and in any local and national
codes that apply to the product.
Do not allow untrained personnel to work with this product.
Use Daniel parts and work procedures specified in this manual.
Daniel also urges you to integrate this manual into your training and safety program.
BE SURE ALL PERSONNEL READ AND FOLLOW THE INSTRUCTIONS IN THIS MANUAL AND ALL NOTICES AND PRODUCT WARNINGS.
Product owners (Purchasers):
Use the correct product for the environment and pressures present. See technical data
for limitations. If you are unsure, discuss your needs with your Daniel representative.
Inform and train all personnel in the proper installation, operation, and maintenance of
this product.
To ensure safe and proper performance, only informed and trained personnel should
install, operate, repair and maintain this product.
Verify that this is the correct instruction manual for your Daniel product. If this is not
the correct documentation, contact Daniel at 1-713-827-6314. You may also download the correct manual from:
http://www.daniel.com
Save this instruction manual for future reference.
If you resell or transfer this product, it is your responsibility to forward this instruction
manual along with the product to the new owner or transferee.
ALWAYS READ AND FOLLOW THE INSTALLATION, OPERATIONS, MAINTENANCE AND
TROUBLESHOOTING MANUALS AND ALL PRODUCT WARNINGS AND INSTRUCTIONS.
Do not use this equipment for any purpose other than its intended service. This may
result in property damage and/or serious personal injury or death.
Product operation (Personnel):
To prevent personal injury, personnel must follow all instructions of this manual prior to
and during operation of the product.
Follow all warnings, cautions, and notices marked on, and supplied with, this product.
Verify that this is the correct instruction manual for your Daniel product. If this is not
the correct documentation, contact Daniel at 1-713-827-6314. You may also download the correct manual from:
http://www.daniel.com
Read and understand all instructions and operating procedures for this product.
If you do not understand an instruction, or do not feel comfortable following the
instructions, contact your Daniel representative for clarification or assistance.
Install this product as specified in the INSTALLATION section of this manual per
applicable local and national codes.
Follow all instructions during the installation, operation, and maintenance of this
product.
Connect the product to the proper pressure sources when and where applicable.
Use only replacement parts specified by Daniel. Unauthorized parts and procedures can
affect this product's performance, safety, and invalidate the warranty. "Look-a-like" substitutions may result in deadly fire, explosion, release of toxic substances or improper operation.
Save this instruction manual for future reference.

Signal words and symbols used in this manual

Pay special attention to the following signal words, safety alert symbols and statements:
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Used to address practices associated with possible equipment damage and miscellaneous practices not related to personal injury.
Safety alert symbol
This is a safety alert symbol. It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
Daniel Measurement and Control, Inc.
COPYRIGHT
©
2012 BY DANIEL MEASUREMENT AND CONTROL, INC., HOUSTON, TEXAS, U.S.A.
All rights reserved. No part of this work may be reproduced or copied in any form or by any means - graphic,
electronic, or mechanical – without first receiving the written permission of Daniel Measurement and Control,
Inc. Houston, Texas, U.S.A.
DanielTM 3818 Liquid Ultrasonic Flow Meters
NOTICE
THE CONTENTS OF THIS PUBLICATION ARE PRESENTED FOR INFORMATIONAL PURPOSES ONLY, AND WHILE EVERY EFFORT HAS BEEN MADE TO ENSURE THEIR ACCURACY, THEY ARE NOT TO BE CONSTRUED AS WARRANTIES OR GUARANTEES, EXPRESSED OR IMPLIED, REGARDING THE PRODUCTS OR SERVICES DESCRIBED HEREIN OR THEIR USE OR APPLICABILITY. ALL SALES ARE GOVERNED BY DANIEL'S TERMS AND CONDITIONS, WHICH ARE AVAILABLE UPON REQUEST. WE RESERVE THE RIGHT TO MODIFY OR IMPROVE THE DESIGNS OR SPECIFICATIONS OF SUCH PRODUCTS AT ANY TIME.
DANIEL DOES NOT ASSUME RESPONSIBILITY FOR THE SELECTION, USE OR MAINTENANCE OF ANY PRODUCT. RESPONSIBILITY FOR PROPER SELECTION, USE AND MAINTENANCE OF ANY DANIEL PRODUCT REMAINS SOLELY WITH THE PURCHASER AND END-USER.
TO THE BEST OF DANIEL'S KNOWLEDGE THE INFORMATION HEREIN IS COMPLETE AND ACCURATE. DANIEL MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THIS MANUAL AND, IN NO EVENT, SHALL DANIEL BE LIABLE FOR ANY INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF PRODUCTION, LOSS OF PROFITS, LOSS OF REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF THIRD PARTIES.
PRODUCT NAMES USED HEREIN ARE FOR MANUFACTURER OR SUPPLIER IDENTIFICATION ONLY AND MAY BE TRADEMARKS/REGISTERED TRADEMARKS OF THESE COMPANIES.
DANIEL AND THE DANIEL LOGO ARE REGISTERED TRADEMARKS OF DANIEL INDUSTRIES, INC. THE EMERSON LOGO IS A TRADEMARK AND SERVICE MARK OF EMERSON ELECTRIC CO.
.
Warranty
1. LIMITED WARRANTY: Subject to the limitations contained in Section 2 herein, Daniel Measurement & Control, Inc. ("Daniel") warrants that the licensed firmware embodied in the Goods will execute the programming instructions provided by Daniel, and that the Goods manufactured by Daniel will be free from defects in materials or workmanship under normal use and care and Services will be performed by trained personnel using proper equipment and instrumentation for the particular Service provided. The foregoing warranties will apply until the expiration of the applicable warranty period. Goods are warranted for twelve (12) months from the date of initial installation or eighteen (18) months from the date of shipment by Daniel, whichever period expires first. Consumables and Services are warranted for a period of 90 days from the date of shipment or completion of the Services. Products purchased by Daniel from a third party for resale to Buyer ("Resale Products") shall carry only the warranty extended by the original manufacturer. Buyer agrees that Daniel has no liability for Resale Products beyond making a reasonable commercial effort to arrange for procurement and shipping of the Resale Products. If Buyer discovers any warranty defects and notifies Daniel thereof in writing during the applicable warranty period, Daniel shall, at its option, correct any errors that are found by Daniel in the firmware or Services or repair or replace F.O.B. point of manufacture that portion of the Goods or firmware found by Daniel to be defective, or refund the purchase price of the defective portion of the Goods/Services. All replacements or repairs necessitated by inadequate maintenance, normal wear and usage, unsuitable power sources or environmental conditions, accident, misuse, improper installation, modification, repair, use of unauthorized replacement parts, storage or handling, or any other cause not the fault of Daniel are not covered by this limited warranty, and shall be at Buyer's expense. Daniel shall not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by Daniel. All costs of dismantling, reinstallation and freight and the time and expenses of Daniel's personnel and representatives for site travel and diagnosis under this warranty clause shall be borne by Buyer unless accepted in writing by Daniel. Goods repaired and parts replaced by Daniel during the warranty period shall be in warranty for the remainder of the original warranty period or ninety (90) days, whichever is longer. This limited warranty is the only warranty made by Daniel and can be amended only in a writing signed by Daniel. THE WARRANTIES AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE. THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS OR SERVICES. Buyer acknowledges and agrees that corrosion or erosion of materials is not covered by this warranty.
2. LIMITATION OF REMEDY AND LIABILITY PERFORMANCE. THE REMEDIES OF BUYER SET FORTH IN THIS AGREEMENT ARE EXCLUSIVE. IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR OTHERWISE), SHALL DANIEL'S LIABILITY TO BUYER AND/OR ITS CUSTOMERS EXCEED THE PRICE TO BUYER OF THE SPECIFIC GOODS MANUFACTURED OR SERVICES PROVIDED BY DANIEL GIVING RISE TO THE CLAIM OR CAUSE OF ACTION. BUYER AGREES THAT IN NO EVENT SHALL DANIEL'S LIABILITY TO BUYER AND/OR ITS CUSTOMERS EXTEND TO INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES. THE TERM "CONSEQUENTIAL DAMAGES" SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF ANTICIPATED PROFITS, REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL, FUEL AND POWER, AND CLAIMS OF BUYER'S CUSTOMERS.
: DANIEL SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Table of Contents
3-9000-771 Rev A May 2012

Contents

Important Safety Instructions
Section 1: Introduction
1.1 Typical Applications .................................................................................... 1
1.2 Features and benefits: ................................................................................. 1
1.3 Acronyms, abbreviations and definitions ....................................................... 2
1.4 Daniel MeterLink software ........................................................................... 5
1.5 3818 LNG Liquid Ultrasonic Flow Meter design .............................................. 6
1.6 Meter specifications .................................................................................... 8
1.7 Pre-installation considerations ................................................................... 11
1.8 Safety ...................................................................................................... 11
1.9 Certifications and approvals....................................................................... 12
1.10 FCC compliance....................................................................................... 13
Section 2: Mechanical installation
2.1 Meter piping, lifting and mounting ............................................................. 15
2.2 Meter components .................................................................................... 17
2.3 Piping recommendations ........................................................................... 18
2.4 Field hydrostatic pressure testing ............................................................... 21
2.5 Meter safety for hoist rings and lifting slings ............................................... 22
2.5.1 Use of appropriate safety engineered swivel hoist rings
in meter end flanges ....................................................................................... 23
2.5.2 Appropriately rated lifting slings ..................................................................... 28
2.6 Mounting requirements in Liquefied Natural Gas pipelines ........................... 31
Section 3: Electrical installation
3.1 Cable length TTL mode .............................................................................. 35
3.2 Cable length Open Collector mode ............................................................. 35
3.3 Grounding meter electronics ..................................................................... 36
3.4 Conduit seals ............................................................................................ 38
3.4.1 Startup for systems using explosion-proof conduit ......................................... 39
3.4.2 Startup for systems that use flame-proof cable ............................................... 40
3.5 Wiring and I/O .......................................................................................... 41
3.5.1 CPU Module labeling and LED indicators......................................................... 42
Table of Contents i
Table of Contents Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
3.6 Daniel Ultrasonic Meters I/O connections ....................................................47
3.6.1 Frequency/Digital outputs...............................................................................48
3.6.2 Analog input settings ......................................................................................52
3.6.3 Analog output settings....................................................................................52
3.6.4 Digital Input ....................................................................................................52
3.6.5 DHCP server switch settings ............................................................................53
3.6.6 Configuration protect switch settings .............................................................53
3.6.7 External power source connection and fuse.....................................................53
3.6.8 Securing the meter..........................................................................................54
3.6.9 Sealing the unit ...............................................................................................57
Section 4: Configuring a 3818 LNG Meter
4.1 Using Daniel MeterLink to configure the meter ............................................59
4.1.1 Field Setup Wizard using Daniel MeterLink ......................................................61
4.2 Using AMS Device Manager to configure the meter...................................... 62
4.3 Using a Field Communicator to configure the meter ....................................77
4.4 Security seals for the meter ........................................................................80
Appendix A: Engineering drawings
A.1 Daniel 3818 LNG Liquid Ultrasonic Flow Meter drawings ................................................... 81
Appendix B: Open source licenses
B.1 GNU General Public License............................................................................................... 84
B.2 GNU Lesser General Public License .................................................................................... 95
B.3 BSD Open Source License.................................................................................................. 99
B.4 M.I.T License ................................................................................................................... 100
Appendix C: Index
C.1 Manual index................................................................................................................... 101
ii Table of Contents
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual List of Tables
3-9000-771 Rev A May 2012

List of Tables

Table 1-1 Acronyms, abbreviations and definitions........................................................................ 2
Table 1-2 Meter specifications ....................................................................................................... 8
Table 2-1 Hoist ring part number................................................................................................. 27
Table 2-2 Hoist ring table for Daniel 3818 LNG Liquid Ultrasonic Flow Meters ............................. 27
Table 3-1 Configurations for open collector frequency outputs ................................................... 35
Table 3-2 CPU Module labeling and LED functions........................................................................ 43
Table 3-3 Ethernet cable to PC communication ........................................................................... 44
Table 3-4 Serial Port A parameters ............................................................................................... 45
Table 3-5 Frequency/Digital Outputs possible configurations ...................................................... 50
Table 3-6 DHCP server switch settings ......................................................................................... 53
Table 3-7 Configuration protect switch settings .......................................................................... 53
Table B-1 Open source licences ................................................................................................... 83
List of Tables iii
List of Tables Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
iv List of Tables
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual List of Figures
3-9000-771 Rev A May 2012

List of Figures

Figure 1-1 Daniel MeterLink download and registration ................................................................ 5
Figure 1-2 3818 LNG Meter with remote mount electronics and band shroud assembly................ 6
Figure 1-3 Daniel 3810 Series Liquid Ultrasonic Meter ATEX approval ......................................... 12
Figure 2-1 Daniel 3818 Liquid Ultrasonic Flow Meter assembly .................................................. 17
Figure 2-2 Piping recommendations unidirectional flow.............................................................. 19
Figure 2-3 Piping recommendations bidirectional flow................................................................ 19
Figure 2-4 Meter end flange with tapped flat-counterbore hole for hoist ring ............................ 23
Figure 2-5 Safety approved hoist ring and non-compliant eye bolt ............................................. 24
Figure 2-6 90 Degree angle between slings ................................................................................. 25
Figure 2-7 Incorrect sling attachment ......................................................................................... 26
Figure 2-8 Correct sling attachment with spreader bar ............................................................... 29
Figure 2-9 Incorrect sling attachment.......................................................................................... 30
Figure 2-10 Transducer cabling conduit......................................................................................... 32
Figure 3-1 Internal Transmitter Electronics Enclosure chassis ground .......................................... 36
Figure 3-2 External ground lug .................................................................................................... 37
Figure 3-3 CPU Module labeling and LED indicators ..................................................................... 42
Figure 3-4 PC to meter serial connection wiring ........................................................................ 46
Figure 3-5 CPU Module I/O connections...................................................................................... 47
Figure 3-6 CPU Module - Frequency/Digital inputs common ground ........................................... 51
Figure 3-7 CPU Module power source connections ..................................................................... 53
Figure 3-8 Transmitter electronic enclosure security latch .......................................................... 54
Figure 3-9 Transmitter Electronics Enclosure security seal installation ........................................ 55
Figure 3-10 Base Enclosure wire seal installation ........................................................................... 56
Figure 4-1 Daniel MeterLink - Meter Directory ............................................................................ 59
Figure 4-2 AMS Device Description search................................................................................... 62
Figure 4-3 AMS file download complete ...................................................................................... 63
Figure 4-4 AMS Device Manager ................................................................................................ 64
Figure 4-5 AMS Device Manager - Overview ............................................................................... 64
Figure 4-6 AMS Device Manager - Guided Setup ......................................................................... 65
Figure 4-7 AMS Device Manager - Zero Flow .............................................................................. 66
Figure 4-8 AMS Device Manager - Service Tools All Variables status indicators............................. 68
Figure 4-9 Display Meter K-Factors .............................................................................................. 68
Figure 4-10 AMS Device Manager - Configure Manual Setup.......................................................... 69
List of Figures v
List of Figures Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
Figure 4-11 Gating configuration parameter Edge gated, active high ............................................71
Figure 4-12 Gating configuration parameter Edge gated, active low..............................................71
Figure 4-13 Gating configuration parameter State gated, active high............................................71
Figure 4-14 Gating configuration parameter State gated, active low .............................................71
Figure 4-15 Configure Flow Analysis Alert .....................................................................................72
Figure 4-16 AMS Device Manager - Service Tools Alerts .................................................................73
Figure 4-17 Configuration changes dialog .....................................................................................73
Figure 4-18 AMS Device Manager - Service Tools ..........................................................................74
Figure 4-19 AMS Device Manager - Service Tools All Variables ......................................................75
Figure 4-20 AMS Device Manager - Service Tools Trends ..............................................................76
Figure 4-21 3818 transmitter field wiring conduit entries ..............................................................78
Figure 4-22 Field Communicator wiring diagram for the 3818 LNG Meter ....................................79
vi List of Figures

Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction

3-9000-771 Rev A May 2012
Section 1: Introduction
Daniel 3818 LNG Liquid Ultrasonic Flow Meters have various configurations that meet a broad range of customer requirements. Each meter comes fully assembled from Daniel Measurement and Control, Inc. and all parts and assemblies are tested prior to shipment.
Refer to the following documents for additional details:
P/N 3-9000-762 HART® Field Device Specification Guide Liquid Ultrasonic Meter
P/N 3-9000-772 Daniel 3818 LNG Liquid Ultrasonic Flow Meter Maintenance and
Troubleshooting Manual

1.1 Typical Applications

Custody transfer measurement
Allocation measurement
LNG applications
- LNG liquefaction to storage (loading terminals)
- LNG liquefaction loading (loading terminal)
- LNG receiving to storage (receipt terminal)
- LNG storage to regasification (receipt terminal)

1.2 Features and benefits:

Two remote mountable explosion-proof transmitter electronics enclosures with CPU
Module, Power Supply, Intrinsic Safety Barrier Module and Backplane
TM
Two remote mountable intrinsically safe transmitter electronics enclosures with the
Acquisition Module
Transducer housings seal-welded to meter body to eliminate leak potential
Meter body insulated and shroud assembly covering transducers and cabling
HART®
architecture
Suitable for measuring process fluid temperature ranges from -196
to +60
Reduce unaccounted measurement
Extensive self diagnostics
Immediate alarm reporting
Auto-detected ASCII/RTU Modbus communications protocol
and AMS Suite: Intelligent Device Manager communications for PlantWebTM
o
C (-321 oF)
o
C (140 oF)
Section 1: Introduction 1
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
Internet-ready communications
Ethernet access
Modbus TCP/IP
On-board LED status indicators
Analog pressure and temperature inputs
TM
Daniel MeterLink
(a Windows®-based interface software)

1.3 Acronyms, abbreviations and definitions

Table 1-1 Acronyms, abbreviations and definitions
Acronym or abbreviation Definition
°degree (angle)
o
C
o
F
ADC analog-to-digital converter
AI analog input
AMS® Suite Device Manager Asset Management Software - Device Manager
AO analog output
ASCII MODBUS A Modbus protocol message framing format in which ASCII characters are used to
Backplane board Backplane board for CPU board, I.S Barrier board, Power Supply, and Acquisition
boolean A type of data point that can only take on values of TRUE or FALSE (generally TRUE is
bps Bits per second (baud rate)
cPoise Centipoise (viscosity unit)
CPU Central Processing Unit
CTS Clear-to-Send; the RS-232C handshaking signal input to a transmitter indicating that
DAC Digital-to-Analog Converter
Daniel MeterLink
DI Digital Input
DO Digital Output
DHCP Dynamic Host Configuration Protocol
dm
ECC Error Correction Code
EEPROM Electrically-Erasable, Programmable Read-Only Memory
Flash non-volatile, programmable read-only memory
3
f
3
f
/s
TM
degrees celsius (temperature unit)
degrees fahrenheit (temperature unit)
delineate the beginning and end of the frame. ASCII stands for American Standard Code for Information Interchange.
cable connections
represented by a value of 1, FALSE is represented by a value of 0)
it is okay to transmit data – i.e., the corresponding receiver is ready to receive data. Generally, the Request-to-Send (RTS) output from a receiver is input to the Clear-to­Send (CTS) input of a transmitter.
Daniel Ultrasonic Meter interface software
-1
decimeter (10
cubic foot
Cubic foot per second
meters, length unit)
2 Acronyms, abbreviations and definitions
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
3-9000-771 Rev A May 2012
Table 1-1 Acronyms, abbreviations and definitions
Acronym or abbreviation Definition
f3/min
FODO Output that is user configurable as either a frequency or digital output
Gal Gallon
HART® Communication Protocol Highway Addressable Remote Transducer communications protocol
hr hour (time unit)
Hz Hertz (cycles per second, frequency unit)
I/O Input/Output
IS Intrinsically Safe
K Kelvin (temperature unit)
kHz
LAN Local Area Network
LED lIght-emitting Diode
LLiters
m meter (length unit)
3
/d
m
3
m
/h
3
m
/s
mA milliamp (current unit)
MAC Address Media Access Control (Ethernet Hardware Address -EHA)
Cubic foot per minute
3
Kilohertz (10
cycles per second, frequency unit)
cubic meters per day (volumetric flow rate)
cubic meters per hour (volumetric flow rate)
cubic meters per second (volumetric flow rate)
microinch (
micron
inch)
microinch (10-6 in)
micrometer (10-6 m)
MMU Memory Management Unit
MPa
Megapascal (equivalent to 10
6
Pascal) (pressure unit)
N/A Not Applicable
Nm3/h
normal cubic meters per hour
NOVRAM Non-volatile Random Access Memory
Pa Pascal, equivalent to 1 newton per square meter (pressure unit)
Pas Pascal Second (viscosity unit)
PC Personal Computer
Acronyms, abbreviations and definitions 3
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
Table 1-1 Acronyms, abbreviations and definitions
Acronym or abbreviation Definition
P/N part number
PS power supply (board)
psi pounds per square inch (pressure unit)
psia pounds per square inch absolute (pressure unit)
psig pounds per square inch gage (pressure unit)
RRadius
rad radian (angle)
RAM Random Access Memory
RTS Request-to-Send; the RS-232C handshaking signal output by a receiver when it is
ready to receive data
RTU MODBUS A Modbus protocol framing format in which elapsed time between received charac-
s second (time unit, metric)
SDRAM Synchronous Dynamic Random Access Memory
sec second (time unit, u.s. customary)
TCP/IP Transmission Control Protocol/Internet Protocol
time_t seconds since Epoch (00:00:00 UTC Jan. 1, 1970) (time unit)
UDP User Datagram Protocol
U.L. Underwriters Laboratories, Inc. - product safety testing
V Volts (electric potential unit)
W Watts (power unit)
ters is used to separate messages. RTU stands for Remote Terminal Unit.
and certification organization
4 Acronyms, abbreviations and definitions
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
After the download, follow the instructions in the Readme file. Do not attempt to unzip the zipped firmware file. Daniel MeterLink unzips the compressed file using the
Too ls >P ro gr am
Download
utility.
3-9000-771 Rev A May 2012

1.4 Daniel MeterLink software

Daniel MeterLink software has robust features for setting communications parameters, calibrating your meter, collecting logs and reports and monitoring the meter health and alarm statuses. Daniel MeterLink may be downloaded at no charge from:
http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/MeterLink.aspx
Figure 1-1 Daniel MeterLink download and registration
Select the MeterLink software and firmware bundle appropriate for your meter. Complete the Online registration form and you will receive a conformation email with a hyperlink directing you to the download site.
Refer to the Daniel MeterLink Software for Gas and Liquid Ultrasonic Meters Quick Start Manual (P/N 3-9000-763) for installation instructions and to setup initial communications. You may download the manual from the Daniel MeterLink web page:
http://www2.emersonprocess.com/en-US/brands/daniel/Flow/ultrasonics/Pages/MeterLink.aspx
Daniel MeterLink software 5
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
A. Explosion-proof transmitter enclosure
B. Bracket cover with synchronization cable C. Intrinsically-safe base enclosure includes Acquisition Module
A.
C.
E.
D.
D. Rigid and flexible conduit for transducer cables
(CPU Module, Power Supply, I.S. Barrier Board, and Backplane Bd.)
B.
E. Meter - body and shroud cover for transducers and cables assemblies
May 2012 3-9000-771 Rev A

1.5 3818 LNG Liquid Ultrasonic Flow Meter design

The Daniel 3818 LNG Liquid Ultrasonic Flow Meter is a remote mount, dual transmitter electronics, eight-path (sixteen transducers) in-line meter designed to measure the difference in signal transit time with and against the flow across one or more measurement path(s). A signal transmitted with the direction of flow travels faster than one transmitted against the flow direction. Each measurement path is defined by a transducer pair in which each transducer alternately acts as transmitter and receiver. The meter uses transit time measurements and transducer location information to calculate the mean velocity.
Figure 1-2 3818 LNG Meter with remote mount electronics and band shroud assembly
6 3818 LNG Liquid Ultrasonic Flow Meter design
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
3-9000-771 Rev A May 2012
Computer simulations of various velocity profiles demonstrate that eight measurement paths provide an optimum solution for measuring asymmetric flow. The Daniel 3818 LNG Liquid Ultrasonic Flow Meter utilizes eight cross-bore, parallel-plane measurement paths to offer a high degree of accuracy, repeatability, and superior low-flow capabilities without the compromises associated with conventional technologies. The meter is comprised of two 3810 Transmitter Electronics, designated as co-located primary (master) and secondary (slave) electronics. A syn­chronization cable connects the primary and secondary Acquisition Modules at the J6 terminal block and the liquid ultrasonic flow meter firmware controls the transducers firing sequencing. The Daniel 3818 LNG Liquid Ultrasonic Flow Meter with the 30” diameter meter body utilizes 60 degree port angles with LT-07 transducers.
These features make the Daniel 3818 LNG Liquid Ultrasonic Flow Meter the best choice for cryogenic custody transfer applications as shown in the following sections of this manual.
The Daniel 3818 LNG Liquid Ultrasonic Flow Meter’s U.L. safety listing is accomplished through the combination of a remote mounted, explosion-proof Transmitter Electronics Enclosure that houses the CPU Module, I.S. Barrier Module, Power Supply Board, and the Backplane Board. The flameproof Base Electronics Enclosure houses the Acquisition Module and the acquisition board cable connections. The intrinsically safe transducers and cable assemblies are designed for Class 1, Division 1, Groups C and D areas without need of further protection when installed in accordance with the field wiring diagram (refer to Daniel drawing DMC - 004936, see
Appendix A) and the meter body (spool piece).
3818 LNG Liquid Ultrasonic Flow Meter design 7
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A

1.6 Meter specifications

Specifications for Daniel 3818 LNG Liquid Ultrasonic Flow Meters are below:
Table 1-2 Meter specifications
Liquid meter specifications
Meter type Number of paths:
Eight path (sixteen transducer) chordal design
Ultrasonic type:
Transit-time based measurement
Spool piece with integral mount transducers
Meter performance
Linearity
Repeatability
Velocity range
Upper Viscosity Limit
Body and Flange Pressure rating range
Flange types
Specific Gravity
Accuracy Limits
± 0.15% of measured value over a 10:1 turndown
± 0.20% of measured value over a 20:1 turndown
±0.02% of reading in the specified velocity range
2.0 fps (0.6 m/s) to 40.0 fps (12.2 m/s) (nominal) 48 fps (14.3 m/s) (over-range)
150 centipoise (Transducers LT-07)
U.S. Customary Units - Meter size 30 (Raised face, RTJ or Companion)
Line sizes: 30” (DN 900)
ANSI pressure classes (per ANSI B16.5): 300 ANSI / PN 50
Body and flange material and temperature rating: 316 Stainless steel (forged) body and flanges: (-196° C to 60° C)
Maximum Pressures Dependent on operating temperature
Minimum Pressures 0 psig 0 barg
Raised face for:
ANSI class - 300
0.35 to 1.50
Accuracy limits typically are: ± 2% without a flow calibration
8 Meter specifications
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
3-9000-771 Rev A May 2012
Table 1-2 Meter specifications
Electronic specifications
Power Meter
Tem p er at u re flameproof Transmitter Electronic Enclosure and Base Electronics Enclosure
10.4 VDC to 36 VDC
11 W typical power consumption
Serial cable
Belden #9940 or equivalent (22 gauge) Capacitance (pF/m) 121.397 (conductor to conductor) Capacitance (pF/m) 219.827 (conductor to other conductor and shield) Resistance (DC) DCR @ 20°C (Ohm/km) 48.2307
Nominal Outer shield resistance - DCR @ 20°C (Ohm/km) 16.405
Operating voltage - 300 V RMS (UL AWM Style 2464) Current 2.4 Amps per conductor @ 25°C (recommended)
Ethernet cable
Cat-5 Standard 100Mbps
Frequency (
see Table 3-5)
22 AWG wire characteristics are as follows: Capacitance = 20 pF/ft or 20 nF/1000 ft (between two wires) Resistance = 0.0168 Ohms/ft or 16.8 Ohms/1000 ft Pull-up voltage is 24 VDC
Tr an sd u ce rs
LT- 07
Operating Temperature Range -321
o
F to +140 oF (-196 oC to 60 oC)
Communications specifications
Connectivity protocols One serial RS-232/RS-485 ports (115 kbps baud rate) (Modbus RTU/ASCII)
(1) Serial Port A
(RS-232/RS-485 Full Duplex/RS-485 Half Duplex)
One Ethernet Port (TCP/IP) 100 BaseT
Up to 10 Mbps
Modbus TCP
Device compatibility FloBoss 103, FloBoss S600 flow computer, ROC 107
Digital, analog, and frequency inputs
Digital Input(s) (Selectable)
(1) Single polarity (for flow calibration gating - contact closure)
Single input for starting and stopping
Four pulse configurations available
Analog Input(s) (2) 4-20 mA
AI-1 Temperature
AI-2 Pressure
Note: The analog-to-digital conversion accuracy is within ±0.05% of full scale over the operating
temperature range.
Note: AI-1 and AI-2 are electronically isolated and operate in sink mode. The input contains a
series resistance so HART® Communicators can be connected to configure sensors.
A 24 Volt DC power supply is available to provide power to the sensors.
Meter specifications 9
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
Table 1-2 Meter specifications
Digital, analog, and frequency outputs
Frequency/Digital Output(s)
The meter has user-configurable selections for either a Frequency Output or Digital status (FODO) (Also (3) Frequency/Digital Outputs
see Section 3.6.1)
FODO1 (four possible output configurations)
FODO2(eight possible output configurations)
FODO3(eight possible output configurations)
Frequency or Digital Output parameter pairs ( Frequency or Digital Outputs (FODO 1) source selections:
see Section 3.6.1)
(FO1A, DO1A, FO1B, DO1B)
Frequency or Digital Outputs (FODO 2) source selections
(FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B)
Frequency or Digital Outputs (FODO 3) source selections
(FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B)
Mode options:
Open Collector (requires external excitation supply voltage and pull-up resistor)
TTL (internally powered by the meter 0-5 VDC signal)
Channel B Phase options:
Lag forward, Lead reverse (Phase B lags Phase A while reporting forward flow, leads Phase A
while reporting reverse flow)
Lead forward, Lag reverse (Phase B leads Phase A while reporting forward flow, lags Phase A
while reporting reverse flow)
Phase A and Phase B output (based on flow direction)
Reverse flow - output only reports flow in the reverse direction. For frequency outputs,
Phase B of the output is 90 degrees out of phase with Phase A.
Forward flow - output only reports flow in the forward direction. For frequency outputs,
Phase B of the output is 90 degrees out of phase with Phase A.
Absolute - output reports flow in both directions. For frequency outputs, Phase B of the
output is 90 degrees out of phase with Phase A.
Bidirectional - output reports flow on Phase A only in the forward direction and on Phase B
only in the reverse direction.
Maximum frequency for the frequency outputs
1000Hz
5000Hz
Analog Output(s)
10 Meter specifications
(2) 4-20 mA independently configurable analog outputs
The analog output zero scale offset error is within ±0.1% of full scale and gain error is within ±0.2% of full scale. The total output drift is within ±50 ppm of full scale per °C.
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
EXPLOSION OR FIRE HAZARD
Read and follow the instructions below:
Conduit runs must have a sealing fitting within 457mm (18 inches) of the enclosure to reduce the
risk of an explosion or a fire.
During operation, keep covers tightly closed. DO NOT open the transmitter electronics
enclosures when an explosive atmosphere may be present.
During equipment maintenance, disconnect power before opening the transmitter electronics
enclosures. Clean cover joints before replacing.
DO NOT substitute meter components. Substituting components may compromise the intrinsic
safety of the device.
Failure to follow these safety instructions may result in severe injury to personnel or cause damage to the equipment.
3-9000-771 Rev A May 2012

1.7 Pre-installation considerations

Pipeline equipment code compliance, ANSI, ASME, etc.
Proper Inlet/outlet meter tube piping for reasonable stable flow to the settling chamber
(first meter tube spool upstream of the meter).
Electrical safety compliance; UL, ULC, ATEX, IECEx etc.
Civil and structural good practices compliance
Contractual agreements or governmental compliance (or both)
In-situ performance test procedures
Field tested advanced meter health and flow dynamics diagnostics
Data collection and retention procedures
All piping and the meter body must be sufficiently insulated for bubble-free flow
through the meter

1.8 Safety

The Daniel 3818 LNG Liquid Ultrasonic Flow Meter is suitable for use in U.L. Class 1, Division 1, Group C and D hazardous locations.
Pre-installation considerations 11
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
The Daniel 3810 Series Liquid Ultrasonic Meter is approved to the ATEX Directive 94/9/E
Figure 1-3 Daniel 3810 Series Liquid Ultrasonic Meter ATEX approval

1.9 Certifications and approvals

Daniel 3818 LNG Liquid Ultrasonic Flow Meters have electrical, metrology, intrinsic safety and Pressure Equipment Directive certifications and approvals by the agencies listed below. Refer to the nameplate tag on the meter body, the wiring diagram (P/N DMC - 004936) in Appendix A and observe all safety precautions. Daniel 3810 Series Liquid Ultrasonic Flow Meters operate within the pressure and temperature range of the device (also see Section 1.6 for meter specifi­cations).

Standards

US
Canada
Europe
- Explosive Atmospheres (ATEX)
- International Electro-technical Commission (IECEx)
- Pressure Equipment Directive (PED)
- Electromagnetic Compatibility (EMC)
- International Organization of Legal Metrology (OIML)
12 Certifications and approvals
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 1: Introduction
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
3-9000-771 Rev A May 2012

Approval Agencies

UL
ULC
DEMKO
NMi
INMETRO
NEPSI
GOSTR
IMPORTANT
Please consult Daniel for a complete metrology approvals list.

1.10 FCC compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio com­munications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
FCC compliance 13
Section 1: Introduction Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
14 FCC compliance
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 2: Mechanical installation
SURFACE TEMPERATURE HAZARD
The meter body and piping may be extremely cold.
Wear appropriate personal protective equipment when coming in contact with the meter. Failure to do so may result in injury.
TRIPPING HAZARD
Clear all obstacles or obstructions from the work area when transporting, installing or removing the meter.
Failure to clear the work area may cause injury to personnel.
CUTTING HAZARD
Sharp edges may be present on the meter.
Wear appropriate personal protective equipment when working on the meter. Failure to do so may cause serious injury.
TRANSPORTATION HAZARD
When moving the meter, do not insert the forks of a forklift into the bore.
inserting the forks may cause the meter to become unstable, resulting in injury or damage to the bore and sealing face.
3-9000-771Rev A May 2012

Section 2: Mechanical installation

2.1 Meter piping, lifting and mounting

Refer to the following sections for piping recommendations, lifting with hoist rings and slings, mounting in cooled pipelines and safety warnings and precautions.
Section 2: Mechanical installation 15
Section 2: Mechanical installation Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
CRUSHING HAZARD
Do not remove flange stabilizers.
Attempting to do so may allow the meter to roll, resulting in serious injury or equipment damage.
A.
A. Flange stabilizers
ESCAPING FLUIDS HAZARD
The purchaser of the meter is responsible for the selection of Daniel components/seals and materials compatible with the chemical properties of the measurement fluid.
Failure to select suitable meter components/seals may cause escaping fluids, resulting in injury or equipment damage.
.
May 2012 3-9000-771 Rev A
16 Meter piping, lifting and mounting
Loading...
+ 94 hidden pages