Emerson 300 User Manual 2

Operator’s
Manual
DANGER is used in this manual to warn of a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
Series 300
Automatic Transfer Switches
Refer to the outline and wiring drawings provided with your ASCO Series 300 ATS for all installation details.
Rating Label
Each automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
An experienced licensed electrician must install the Automatic Transfer Switch (ATS).
TABLE OF CONTENTS
section-page
INSTALLATION 1-1........................
Mounting and Line Connections 1-1.........
Engine Starting Contacts 1-2...............
Input / Output Label 1-2....................
Functional Test 1-3, 1-4, 1-5.................
SEQUENCE OF OPERATION 2-1...........
TESTING & SERVICE 3-1..................
Preventive Maintenance 3-1................
Transfer Test 3-1..........................
Disconnecting the Controller 3-1............
Manual Load Transfer 3-2..................
Trouble-Shooting 3-2......................
ADJUSTMENTS 4-1.......................
Time Delay and Sensor Adjustments 4-1.....
How to Change a Setting 4-2...............
CONTROL FEATURES 5-1.................
Engine Exercisers 5-1, 5-2, 5-3..............
Motor Load Transfer 5-4...................
Load Disconnect & Remote Control 5-4......
INDEX back of manual.....................
600, 800, 1000 A sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
381333–201 G
Nameplate
The Transfer Switch nameplate includes data for each specific ASCO Series 300 ATS. Use the ATS only within the limits shown on this nameplate.
H 300 B 3 600 N 1 C
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a Series 300 ATSwithswitchedneutral,3pole,600ampere, 480 V, in a Type 1 enclosure:
B –switched C – overlapping
blank – solid
neutral
connections
power
connections
Neutral
Phase Poles
2 –singleØ 3 –threeØ
Amperes Voltage Controller Enclosure
600
800 1000
1200
C 208
D 220 E 230
F 240
H 380
J 400
K 415
L 440
M 460 N 480
Q 575
R 600
1 –standard
1X –if
accessories
ordered
* available 600 – 1000 A sizes only
C –type1
F –type3R
G –type4 *
L –type12 *
blank – open type
Controller
membrane
controls
Transfer
Switch
terminal block TB
for engine start
and switch
position contacts
power
connections
neutral
connections
600 ampere size in typical enclosure with location of customer connections
neutral
connections
power
connections
Transfer
Switch
terminal block TB
for engine start
and switch
position contacts
Controller
membrane
controls
power
connections
neutral
connections
800 and 1000 ampere sizes in typical enclosure with location of customer connections
neutral
connections
power
connections
Transfer
Switch
Controller
membrane
controls
terminal block TB
for engine start
and switch
position contacts
power
connections
neutral
connections
1200 ampere size in typical enclosure with location of customer connections
SECTION 1 INSTALLATION
Series 300 Automatic Transfer Switches are factory wired and tested. Installation requires skid removal then securing the enclosure to the supporting foundation.
Remove the Shipping Skid
Open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the Series 300 for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending spaceandclearancetolivemetalparts. Whena concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting
Refer to the applicable enclosure outline drawing furnished with this switch and mount the Series 300 according to details and instructions shown on diagram.
Testing Power Conductors
Do not connect the power conductors to the ASCO Series 300 transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before verify that they are not defective or have been damaged during installation.
they are connected, they should be tested to
NOTICE
Protect the automatic transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the AT S.
Connecting Power Conductors
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with this Series 300. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept thewiresizeslistedonthedrawingsprovidedwiththe Series 300. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Line Connections
Refer to the Wiring Diagram provided with your Series 300 ATS. All wiring must be made in accordance with the National Electrical Code and local codes.
It is unnecessary to remove pole covers from the transfer switch. If you do remove them, reinstall them carefully.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Controller Ground
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Harnesses
The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).
1 --- 1
INSTALLATION (continued)
Engine Starting Contacts
Customer connections for engine control contact and TS auxiliary contacts connec tion s are located on terminal block TB which is mounted on the front lower left of the transfer switch. Refer to wiring diagram provided with the Series 300 A TS and connec t the engine start wires to the appropr iate terminals. See Figure 1–1 and Table A.
Table A. Engine s tart connections.
When normal
source fails
Te r m i na l s
on transfer
switch
contact closes TB1 and TB2 contact opens TB1 and TB3
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this Series 300 Automatic Transfer Switch. Make the neces­sary auxiliary connections by referring to Section 5, Control Fea tures.
COMMON
FEATURE 7
closes to start
FEATURE 8
opens to start
COMMON
FEATURE 14B
closed o n emergency
FEATURE 14A
closed on normal
COMMON
FEATURE 14BA
closed o n emergency
FEATURE 14AA
closed on normal
terminal block for engine start and
auxiliary circuit connections
left side of
transfer switch
Engine Starting
Signals
5amps,32VDC
5ampsresistive28VDC
or 120 V AC max.
TS Auxiliary Contacts
Feature 14A & 14B
10 amps, 32 V DC
10 amps 250 V AC
general purpose
Optional
TS Auxiliary Contacts
Feature 14AA & 14BA
10 amps, 32 V DC 10 amps 250 V AC
general purpose
Connections to Controller for other Control Features
(located on bottom of Controller)
Load Disconnect
Feature
Connections
(see Wiring Diagram
& refer to page 5–4
for DIP switch settings)
Programmable
Engine Exerciser
connection,
if provided
(refer to
page 5–3)
Figure 1-1. Engine start and auxiliary circuit
terminal block TB located on the transfer switch.
Remote Control Features Connections
(refer to the Wiring Diagram &
page 5–4 for DIP switch settings)
Each control contact must be suitable
for a 5 V DC low energy circuit.
for factory
use only
Figure 1-2. Input / output label on the Controller showing possible connections to the lower terminal block.
1 --- 2
INSTALLATION (continued)
Functional Test
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid damaging the automatic transfer switch.
Read all instructions on the Wiring Diagram and labels affixed to the automatic transfer switch. Note the control features that are provi ded and review their operation before proceeding.
1 – Manual Operation Test
A detachable maintenance handle is provided on the frame of the T r ans fer Switch for maintenance purpose
. Manual operation of the transfer switch should be
only checked before it is energized (operated electrically).
s
left side of
transfer switch
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1. After deenergizing both power sources, open the enclosure door. Locate and remove the mainte­nance handle from the clips on the left side of the transfer switch frame. Insert the handle into the holeinthemoldedhubontheleftsideofthe operator. See Figures 1–3 and 1–4 and Table B.
2. Move the maintenance handle up or down as shown to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
Table B. Maintenance handle positions.
ATS Position Handle Indicators
Normal
Emergency
E
N
E
N
up
down
E=O
upper contacts open
N=C
lower contacts closed
E=C
upper contacts closed
N=O
lower contacts open
maintenance
handle
storage clips
Figure1-3.Maintenancehandle&storagelocation.
3. Return the transfer switch to the Normal position. Observe that window indicators (right side) show the top shaft O (open) and the bottom shaft C (closed).
Note: If Normal and Emergency connections are
reversed this operation is also reversed.
4. Remove the maintenance handle and store it on the frame (left side) in the clips provided.
NOTICE
Verify that the maintenance handle has been removed before proceeding!
Now continue to 2–VoltageCheckson next page.
handle
hub
frame
UP closes the
contacts
Normal source
Emergency
contacts (lower)
DOWN closes the Emergency source contacts (upper)
window
indicators
O is open C is closed
Normal
contact position
indicators (right side)
contacts
Figure 1-4. Maintenance handle operation and contact position indicators.
1 --- 3
INSTALLATION (continued)
Figure 1–5. St andard controls and indicators.
observe these lights
2–VoltageChecks
First check na meplat e on transfer switch; rated voltage mustbethesameasnormalandemergencyline voltages.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–5.
O Black circle means light is on.
P White circle means light is off.
* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switch will respondonlytotheratedvoltagespecifiedonthe Transfer Switch nameplate.
Also see page 4–1 for the HI–LOW voltage adjust setting in the controller. The LOW setting shifts all voltage settings down 4.2%; for example, 240 V to 230V.
Close the normal source circuit breaker. The Normal Transfer Switch Position and the Normal
1
Source Accepted lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
2
entatthetransferswitchnormal source terminals.
Close the emergency source circuit breaker. (Start generator, if necessary.) The Emergency
3
Source Accepted light should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
4
ent at the transfer switch emer­gency source terminals.*
Useaphaserotationmeterto check phase rotation of emer-
5
gency source; it must be the same
as the normal source.
Shut down the engine–genera­tor , if applicable. The Emergen- cy Source Accepted light should go off. Then put the starting
6
control selector switch (on the generator set) in the automatic position. Close enclosure door.
Source Accepted
Normal
Emergency
Source Accepted
Normal
Emergency
C
B
A
Source Accepted
Normal
Emergency
1 --- 4
Now continue to 3 – Electrical Operation on next page.
pressthisbutton
INSTALLATION (continued)
observe these lights
Figure 1–6. Standard controls and indicators.
3 – Electrical Operation
This procedure will check the electrical opertion of the Automatic Transfer Switch. See Figure 1–6.
Close the transfer switch enclosure door and tighten the screws before you test electrical operation.
Transfer Test
Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.
Perform steps 1 through 8 at the right. Observe the status lights.
O Black circle means light is on.
P White circle means light is off.
NOTE: If Motor Load Tra nsfer feature is activated, then transfer may not occur i mmediately after the respective time delays. Transfer will only occur when the phase relation­ship between sources is correct.
This completes the Functional Test of the ASCO Series 300 A u tom atic T ran sfer Switch. Leave the engine–generator starting control in the automatic position.
The normal source must be available and the generator must be ready to start.
1
Check that the Normal Source Accepted light is on.
Press and hold the Transfer Test button until the engine starts
2
and runs. This should happen within 15 sec.
The Emergency Source
3
Accepted light should come on.
The transfer switch should transfer to the Emergency position. The Emergency
4
Transfer Switch Position light should come on and the Normal light should go off.
If the transfer to emergency delay is used the transfer should occurs after a time delay
5
(up to 5 minutes). Forimmediatetransferpress the Bypass Time Delay button.
The transfer switch should transfer back to the Normal position. The Normal Transfer
6
Switch Position light should come on and the Emergency light should go off.
If the retransfer to normal delay is used the retransfer should occur after a time delay
7
(up to 30 minutes). Forimmediateretransferpress the Bypass Time Delay button.
Source Accepted
Normal
Emergency
Trans fer
Tes t
Source Accepted
Normal
Emergency
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
Trans fer Switch
Position
Normal
Emergency
Bypass
Time Delay
1 --- 5
The unloaded running delay keeps the generator running for 5 minutes (cool–down period).
8
Then the generator should stop and the Emergency Source Accepted light should go off.
Source Accepted
Normal
Emergency
SECTION 2 SEQUENCE OF OPERATION
Lights show position of transfer switch.
Transfer To Emergency
Thesequenceforloadtransferto emergency source begins automatical­ly when normal source voltage falls below the preset dropout point or when Transfer Test button is pressed. An under voltage condition on any phase of the normal source is de­tected by the sensor.
When the normal source voltage fails or the Transfer Test button is pressed, the SE relay de-energizes and relay NR begins its timing cycle (1 or 3 seconds, momentary
normal source outage delay). The NR relay is provided with a time delay on
dropout to override momentary outages and prevent nuisance starting of the engine-driven generator. If the normal source voltage returns above the sensor dropout setting before the time delay expires, the NR relay timing cycle is reset to zero and relay SE energizes.
If the normal source voltage does not return above the sensor dropout setting before the time delay expires, the NR relay de-energizes and signals the engine-driven gen­erator to start. At the same time, a voltage and frequen­cy sensor begins monitoring the emergency source. The sensor will accept the emergency source only when both voltage and frequency reach preset pickup points. Usual­ly about ten seconds elapse from dropout of the NR relay to acceptance by the sensor. This time span occurs be­cause the engine-driven generator must crank, start, and run up to nominal pickup points. For this reason, if the Transfer Test button is pressed it must be held for 15 sec­onds. If the emergenc y source is available immed iately, the sensor may accept it as soon as NR relay drops out.
When the emergency source is accepted by the sensor, relay ER begins its timing cycle (transfer to emergency delay). ER relay is provided with an adjustable (0 to 5 minutes) time delay on pickup to delay transfer of the load to the emergency source. For immediate transfer press Bypass Time Delay button.
ER relay energizes , the TS coil is energiz ed , the transfer switch operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transf er switch is now supplying the load from the emergency source.
ThetransferswitchwillremainintheEmergency position until the normal source is restored. If the Transfer Test button is used, the transfer switch will remain on emergency until the retransfer to normal delay times out.
Hold 15 sec.to start the engine generator and to transfer the load to emergency.
Press to cancel the active exercise period (stops engine now or after cooldown) See page 5–1.
Lights show the sources accepted.
Light for built–in
engine exercise timer:
³ blinks rapidly when
button is held 5 sec.
while being set
³ blinks slowly when
button is released (set) and during 20 min. exercise period.
³ stays on after engine
stops (exerciser is
enabled for weekly
operation)
Seepage5–1
Hold 5 sec 20 min. engine exercise period immediately (engine starts) and weekly thereafter.
.toset
Figure 2–1. Membrane controls and indicator lights.
Retransfer to Normal
The sequence for load retransfer to the normal source automatically begins when the voltage sensor detects restoration of the normal source. The voltage level must rise above the preset pickup point on all phases before the sensor will accept the normal source.
Whenthenormalsourceisacceptedbythesensor, relay SE begins its timing cycle (adjustable 1 sec. to 30 min., retransfer to normal delay). For immediate retransfer press Bypass Time Delay button. SE relay is provided with a time delay on pickup to prevent immediate load retransfer to the normal source. The delay insures that the normal source has stabilized before reconnection of vital loads. If the normal source voltage falls below the present dropout point before the time delay expires, the timing cycle is reset to zero. If the emergency source fails for more than 4 seconds during the timing cycle, ER relay drops out and the load is immediately retransferred to the normal source, if that source is acceptable.
SE relay energi zes and ER relay is dropped out . The TS coil is energized, the transfer switch operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the normal source a gai n.
Upon retransfer to the normal source, NR relay begins its timing cyc le (unloaded running delay , engine cooldown). NR relay is provided with a 5 min. time delay on picku p to keep the engine running for a cool-down period.
NR relay energizes after the time delay and signals the engine-driven generator to shut down. All circuits are reset for any future normal source failure.
Activationof standard control features shown in Section 5 will alter the sequence of operation and introduce additional time delays during transfer operations.
2 --- 1
for complete
instructions
SECTION 3 TESTING & SERVICE
PREVENTIVE MAINTENANCE
For high reliability and long life for the ATS:
Operate the swi tch at least once a month.Performthis 4–step Electrical Operation Test (test with load transfer).
Transfer Switch Test
Press and hold the door-mounted Transfer Test button
1.
until the engine starts and runs. This should happen within 15 seconds.
The transfer switch will operate to the Emergency
2.
position. If the Transfer To Emer g ency Delay is used, thetransferwilloccurafteratimedelay(upto5 minutes). For immediate transfer press Bypass Time Delay button .
The Transfer Switch will operate back to the Norm al
3.
position a f ter the Retransfer To Normal Delay (up to 30 minutes). For immediate retransfer press Bypass Time Delay button .
Unloaded Running (Engine Cooldown) Delay allows
4.
engine to run unloaded for 5 minutes.
Checklist for Y early Inspection
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal & Emergency power sources before performing inspections!
S Check all cable connections & retighten them.
Torquetovaluesshownontransferswitchlabel.
Replacement parts. When ordering parts provide the Serial and Catalog Nos. from the transfer switch nameplate. Contact ASI. In the US call 1–800–800–ASCO (2726)).
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps carefully.
Disconnecting the Plugs
1. Observe the position of the transfer switch. a. If the transfer switch is in the Normal position,
place standby engine starting control in the off position. Then open the emergency source circuit breaker.
b. If the transfer switch is in the Emergency position,
open the normal source circuit breaker. Place the engine starting control in the test or run position.
2. Separate the quick disconnect plugs by squeezing
the latches. Do not pull on the harness wires.
3. Label, remove, and tape the signal wires connected
to the engine start terminals on the transfer switch: TB1 and TB3, or TB1 and TB2.
Reconnecting the Plugs
1. Observe the position of the transfer switch. a. If the transfer switch is in the Normal position, be
sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open.
b. If the transfer switch is in the Emergency position,
normal source circuit breaker still should be open.
2. Reconnect the signal wires connected to the
appropriate engine start terminals on the transfer switch. See Section 1, Engine Starting Contacts.
S Clean the enclosur e. De–energize all sources,
then brush and vacuum away any excessive dust accumulation. Remove moisture with a clean cloth.
S Check the transfer switch contacts. De-energize
all sources, then remov e the transfer switch barriers and check contact condition. Replace the contacts if they become pitted or worn excessively. R eins tal l the barriers carefully.
S Maintain transfer switch lubrication.Under
normal operating conditions no further lubricating is required. Renew factory lubrication if the switch is subjected t o severe dust or abnormal operating conditions or if TS coil is replaced. Order lubricant kit 75–100.
3. The harness plugs and sockets are keyed.
Carefully align the plugs with the sockets and press straight in until both latches click.
4. Restore the opposite source as follows: a. If the transfer switch is in the Normal position,
place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker.
b. If the transfer switch is in the Emergency position,
close the normal source circuit breaker. The load will be automatically retransferred to the normal source after the Retran sf er to Norma l Delay.For immediate retransfer, press Bypass Time Delay button. Place the engine starting control in the automati c position.
3 --- 1
TESTING & SERVICE
PROBLEM
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the controller is disconnected.
(continued)
1. Open normal and emergency source circuit breakers.
2. Use the maintenance handle to manually operate
transfer switch to the opposite source. See page 1–3, Manual Operation Test.
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
TROUBLE-SHOOTING
Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features.
Table 3-1. Trouble-Shooting Checks.
1OPERATION 2 GEN-SET 3VOLTAGE
Gen-Set does not start when the Transfer Test button is pressed and held for 15 seconds or when the normal source fails.
T ransfer switch does not transfer the load to emergency source after the gen-set starts.
T ransfer switch does not transfer the load to normal source when normal returns or when Transfer Test button is released.
Gen-Set does not stop after load retransfer to the normal source.
Hold the Transfe r Test button 15sec.ortheoutagemustbe long enough to allow for the 1 or 3 sec. Momentary Normal Source Outage Delay plus engine cranking and starting time.
Wait for T ransfer to Emergen- cy Delay (0 to 5 min.) to time out. For immediate transfer, press the Bypass Time Delay button. If Motor Load Transfer is active, wait for inphase con­dition (see below).
Wait for Retransfer to Normal Delay (1 sec. to 30 min.) to time out. For immediate re– transfer, press Bypass Time Delay button. If Motor Load Transfer is active, wait for in­phase condition (see below).
Wait for the 5 minute Unloaded Running Delay to time out.
3. If the transfer switch is in the Emergency position
manually start the engine generator and then close the emergency source circuit breaker.
Proceed with care! The automatic transfer switch is energized.
CHECK IN NUMERICAL SEQUENCE
Starting control must be in automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.
Generator output circuit breaker must be closed. Generator frequency must be at least 57 Hz.
Starting control must be in automatic position.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals EA and EC (or EL1 and EL2 for 2 pole switches). *
* These are factory settings.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches).
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–4)
3. Press and hold should transfer to emergency source when meter
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch powe r terminals; shock, burns, or death could result !
1. Connect a voltmeter (set for twice system phase–to–phase voltage) between Transfer Switch terminals NA and EA.
2. Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.
needle is near 0 volts. If transfer does not occur, Motor L oad Transfer feature is not opera ting.
4. Release the Transfer Test button. The load should retransfer back to the normal source after the Retransfer to Normal Delay,ifused. Theretransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor L oad Transfer feature is not opera ting.
5. For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.
If the problem is isolated to circuits on the controlle r or the transfer switch, c all your local ASCO Power Technolog ies sales office, representative, or ASI. In the United States, call 1–800–800–2726. Furnish the Serial No., Bill of Material (BOM) No., and Catalog N o. from transfer switch nameplate.
3 --- 2
Transfer Test button. The load
SECTION 4 ADJUSTMENTS
y
OverrideMomentary
TDE
S
T
TIMER
0minute
s
0to
5
——P
R
lTIME
R
30minutes
1secondto
——P
DESCRIPTIONLABELSSETTIN
G
S1DIP
PU/NP
ick
EmergencySource
equecy60/50
Vol
P
h
LOW/
Vol
Adj
)
LOW
/
H
I
Time Delay Adjustment
Standard time delays are set to customer specifications (if none specified, standard factory settings are used).
Table4-1.TimeDelaySettings
DESCRIPTION LABELS
Override Momentar
Normal Source Outages
ransfer toEmergency
Override Momentary
Emergency S. Outages
etransfer toNorma
Unloaded Running
(Engine Cooldown)
FACTORY
SETTING
3seconds
TIMER 0 minutes 0to5
N/E
4seconds non-adjustable
TIMER 30 minutes 1secondto
E/N
5 minutes non-adjustable
(full ccw)
(full cw)
ADJUSTMENT
RANGE
1second Actuator 1 on
3seconds Actuator 1 off
minutes
30 minutes
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points are set to customer specifications (if none specified, standard factory settings are used). To change a setting, follow procedure on page 4–2. Use Tables 4-2 and 4–3 for settings and corresponding DIP switch actuators.
To change a setting, follow procedure on page 4-2. Use Table 4-1 as a guide to time delay values and their cor­responding adjustment DIP switch or potentiometer.
S3 DIP
SWITCH
1
1
ADJUSTMENT
POTENTIOMETER
2
1
NOTICE
Any change in these settings may affect the normal operation of the automatic transfer switch. This change could allow the load circuits to remain connected to a low voltage source.
Table 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).
Normal Source Voltage
EmergencySource
Voltage
Emergency Source
Frequency
tage
ases 3, 1 3/1 3
%ofnominal
FACT. S ET ADJ RANGE
up 90 %
DO/N Dropout
–– Pickup 90 % non-adjustable –– Dropout 75 % non-adjustable –– Pickup 95 % non-adjustable –– Dropout 85 % non-adjustable
60/50
Hz
60/50Hz 60Hz
85 %
95 % * Actuator 3 off
90 % Actuator 3 on
90 % *
85 %
80 %
70 %
60 Hz Actuator 4 off
50 Hz Actuator 4 on
3phase Actuator 6 off
1phase Actuator 6 on
Actuator 1 off Actuator 2 off
Actuator 1 on Actuator 2 off
Actuator 1 off Actuator 2 on
Actuator 1 on Actuator 2 on
––
––
S1 DIP
SWITCH
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
3
3
21
21
21
21
4
4
6
6
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION LABELS FACT ORY SET T ING ADJUSTMENT S3 DIP SWITCH
tage
ust(4.2%
HI
LOW Actuator 2 off
HI Actuator 2 on
4 --- 1
2
2
ADJUSTMENTS
(continued)
NOTICE
Do not make any setting changes while the controller is energized.
How to Change a Setting
1. Prevent the transfer switch from operating by discon­necting one source first, then the other, as follows :
a. If the transfer switch is in the Normal position,
open the emergency source circuit breaker. Turn the engine starting control to off.Then open the normal source circuit breaker.
b. If the transfer switch is in the Emergency
position, open the normal source circuit breaker. Turn engine starting control to test or run.Then open the emergency source circuit breaker.
2. Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustment potentiometer or DIP switch for the setting that you want to change. Refer to T able 4-1 and Table 4–2 on page 4-1 and Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer clockwise to increase the time delay or counter­clockwisetodecreaseit. SeeFigure4-3.
6. Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the illustration next to the setting (left = off, right = on). Recheck the setting. See Figure 4-4.
7. Install the cover on the controller by hooking it on the left side and latching the right side.
8. Reconnect both harness plugs to the controller by aligning and pressing straight in until lat ches click.
cover
hook on left side
Figure 4-1. Controller cover latch.
harness
plugs
S3 DIP
switch
S1 DIP
switch
Figure 4-2. Location of potentiometers.
clockwise to
increase
P1 or P2
potentiometer
counterclockwise
to decrease
S2 DIP
switch
thumb latch
9volt
alkaline
battery
J5
battery on/off jumper
P1 retransfer to normal
time delay
P2
transfer to
emergency
time delay
Close the transfer switch enclosure door.
9. Close the enclosure door, then restore both sources:
a. If the transfer switch is in the Normal position
first close the normal source circuit breaker, then close the emergency source circu it breaker.
b. If the transfer switch is in the Emergency
position, close the normal source circuit breaker. Theloadwillbeautomatically retransferred to the normal source. Then close the emergency source circuit breaker.
10. Turn the engine starting control to automatic.
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1 SW2 SW3
actuator
(8 on each DIP switch)
onoff
Figure 4-4. Setting DIP switch actuators.
4 --- 2
SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS
These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without load transfer, or they can be compl etely disabled. The engine-generator should be exercised under load once a week for a minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.
BUILT–IN ENGINE EXERCISER
The engine exerciser included in ASCO Series 300 Automatic Transfer Switches provides a once a week 20–minute exercise period. It occurs immediately the Set Engine Exerciser push button is pressed (and held
for at least 5 seconds), and then at the same time weekly thereafter. A 9 volt alkaline battery (Duracell MN1604, Everready 522, or Panasonic 6AM6) is furnished and installed in the controller to maintain the setting. The battery jumper block must be shifted to ON position
. See Figure 4–2 on page 4–2.
when
the
FUNCTION
Std. Timer
Enabled
Std. Timer
Disabled
Exercise
without
Load
Exercise
with Load
Shaded DIP switches are standard factory settings.
DIP Switch Settings
S1 DIP
SWITCH
Actuator
7on
Actuator
7off
Actuator
8off
Actuator
8on
7
7
8
8
Actuator
5on
Actuator
5on
S2 DIP
SWITCH
5
5
Fill in day and t ime set. Week Day ______ Time _______.
Press to cancel an active exercise period (stops generator).
If Exercise with Load is set, retransfers load to Normal, then stops generator after min. cooldown.
status light
Press and hold for 5 sec blinks rapidly to set exercise period immediately and every week hereafter (generator starts).
. or until status light
If Exerciser with Load is set, transfers load to Emergency.
Figure 5-1. Operator panel pushbuttons and light.
Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1, actuator 8. The load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.
Exercise without Load, DIP Switch S1, Actuator 8 off
8
How to Set Built–In Timer
Step Function Explanation
Push Button Status Light
Set Engine
1
Exercise r
hold
5sec.
2 release
press Bypass
3
Time Delay
blinks rapidly
OPOPOP
blinks slowly
OPPOPP
set exercise period
exercise period now active Generator starts and runs.
Exercise the generator now and
every week at this time hereafter.
O stays on cancel active exercise period Generator stops.
4 O stays on generator off Exerciser enabled; repeats every 7 days.
Exercise with Load, DIP Switch S1, Actuator 8 on
8
How to Set Built–In Timer
Step Function Explanation
Push Button Status Light
Set Engine
1
Exercise r
hold
5sec.
2 release
press Bypass
3
Time Delay
blinks rapidly
OPOPOP
blinks slowly
OPPOPP
blinks slowly
OPPOPP
set exercise period
exercise period now active
cancel active exercise period
Exercise the generator now and
every week at this time hereafter.
Generator starts and runs;
the load transfers to Emergency.
The load retransfers to Normal; then
generator runs for 5 minute cooldown
( light blinks slowly during cooldown ).
4 O stays on generator off Exerciser enabled; repeats every 7 days.
NOTE:EverytimeSET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.
5 --- 1
2–line display
3 buttons
CONTROL FEATURES (continued)
Optional Accessory 11BG – SOURCE AVAILABILITY SIGNAL
& PROGRAMMABLE ENGINE EXERCISER MODULE
connections for source availability signal contacts
Figure 5–2. Accessory 11BG module (mounted behind operator interface and connected to the controller)
includes source availability signal contacts and a programmable engine exerciser.
Source Availability Signal Contacts
ThemoduleprovidesoneFormCcontacteachforthe normal and emergency sources signal the acceptability of the source as sensed by the controller. The signal contacts operate i n conjunction with the Source Accepted lights on the operator i nterface. Field wiring terminals are provided as shown i n Figure 5–3 and the
SOURCE
AVAILABILITY SIGNALS
2 AMPS @ 30 VDC , resisti ve
0.5 AMP @ 125 VAC, resistive contacts shown de–energized
wiring diagram.
Contact ratings:
2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive
Figure 5–3. Source availability signal contacts.
ProgrammableEngineExerciser
Themoduleincludesaprogrammableengineexerciser that provides for weekly or biweekl y operation. This optional exercise timer may have to be turned on (enabled) by setting the S1 DIP switch actuator 7 to off, and S2 DIP switch actuator 5 to off. A backup battery
in the controller (see page 4–2 and page 5–3) must be turned on to maintain the settings and to allow programming with the normal and emergency power turned off (page 5–1).
Theprogrammableengineexerciserincorporatesa7 day or 14 day time base. Proper controller settings must be made to determine whether or not the test will be done with or without load transfer (S1 DIP switch actuator 8). Seenextpageforinstructionsonsettingthetimer.
5 --- 2
DIP Switch Settings in the Controller
(see page 4–2)
FUNCTION
Opt. Timer
Enabled
Opt. Timer
Disabled
Exercise
without
Load
Exercise
with
Load
SWITCH
Actuator
7off
Actuator
7off
Actuator
8off
Actuator
8on
S1 DIP
7
7
8
8
Shaded DIP switches are standard factory settings.
S2 DIP
SWITCH
Actuator
5off
Actuator
5on
5
5
CONTROL FEATURES (continued)
How to Set Optional Programmable Engine Exerciser (part of Acc. 11BG module)
NOTE: When choosing bi–weekly operation, the exerciser will always run on the week designated “(1)”
Hazardous voltage capable of causing shock, burns, or death is used in this transfer switch. Deenergize both Normal and Emergency power sources before programming the exerciser.
Navigating the Menu
Use the UP and DOWN arrow keys to move through the displays .
Changing the Parameters
Use the UP and DOWN arrow keys to move though the displays to the parameter to be changed. Push the ENTER key to start the editing process . The first parameter will flash. Use the UP and DOWN arrow keys to adjust the parameter to the desired value and press the ENTER key to save the value. The next parameter will now flash. Repeat the process until each param eter is properly configured.
Fast/Slow Ad ju st
Daylight Saving
Time Adjust
Date
Time
Run TIme
Start TIme
Engine Exerciser
Engine Exerciser Display
TheEngineExerciserDisplayshowsthestatusofthe engine exerciser. When the unit is shipped from the factory the programmable engine exerciser is “Disabled” and must be set to “Enabled” by the customer. When the engine exerciser is running, this display will count down the remaining ti me until the end of the exercise period.
Start Time Display
TheStartTimeDisplayshowstheengineexerciserstart time. There are four parameters that determine the start time:
weekly (”Every”) or bi–weekly (”Alt”) operation
day of week (”Sun” through “Sat”)
start hour (0 through 23)
start minutes (0 through 59)
For example, if the user wants the exerciser to run every other Saturday a t 3 PM, the proper configuration would be: “Alt Sat @ 15:00”
Fill in your settings for future reference
Weekly or Bi–weekly Day of Week Start Time Run Time
Every = weekly
Alt = bi–weekly
Sun through Sat
onthedatedisplay.
Run Time Display
The Run Time Display shows the run time for the engine exerciser. The default setting from the factory is 30 min.
Time Display
The Time Display shows the present system time. The format is “hours:minutes:seconds”.
NOTE: During total power outages, power to the accessory is maintained by a battery in the Controller (see page 4–2). Be sure that the 9–volt alkaline battery is fresh and enabled (jumper in ON position) so that the time and date settings are not lost.
Date Display
The Date Display shows the present system date. The format is “day of week (week) month/day of month/year”.
NOTE: Week is either week 1 or week 2. This i s used in conjunction with the bi–weekly timer.
Daylight Savings Time Adjust Display
This display shows whet her the automatic daylight saving time adjustment is active. The factory default is “NO”. If enabled, the unit will automatically adjust for daylight saving time at 2 AM on Sunday as follows:
Part No. Start first Sunday in April 2nd Sunday in March Stop last Sunday in Oct first Sunday in Nov
* Part no. on back of circuit board. New DST starts in 2007.
629857–001* 629857–002*
Fast / Slow Adjust Display
This display shows the automatic fast/slow adjustment value. Thefactorydefaultis0. Thisfeaturecanbe used to trim a clock that runs fast or slow. For example, if your clock runs 10 seconds slow per week, change the fast/slow adjust value to “+10” and the unit will automatically add 10 seconds to the clock every week.
NOTE: Adjustments are made Sunday morning at 2 AM. If you want your exerciser period to start at 2 AM on Sunday, you cannot use this feature and the adjustment must be set to 0.
Date exerciser was set ___________________________
0–23hour
0–59minute
0–23hour
0–59minute
30 min. is default setting
5 --- 3
CONTROL FEATURES (continued)
INPHASE MONITOR
FOR MOTOR LOAD TRANSFER
Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.
The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.
FUNCTION S1 DIP SWITCH
enable Actuator 5 on
disable Actuator 5 off
Shaded DIP switches are standard factory settings.
Note
If the Motor L oad Transfer feature is enabled, it will be activated following
the Load Disconnect
Feature Delay Before Transfer delay.
5
5
LOAD DISCONNECT FEATURE
Connect external circuits to the terminals indicated on the Wiring Diagram provided with the ATS.
The double throw (Form C) contact is rated for 28 VDC or 120 VAC (5 amperes resistive). The contact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the Automatic Transfer Switch. The contact resets either immediately following transfer or after the same
delay as set for pre–signal before
transfer.
Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:
Delay Before Transfer
LD TDBT S2 DIP SWITCH
0 (disable)
3seconds
10 seconds
20 seconds
Actuator 7 on Actuator 8 on
Actuator 7 on Actuator 8 off
Actuator 7 off Actuator 8 on
Actuator 7 off Actuator 8 off
87
87
87
87
Shaded DIP switches are standard factory settings.
Delay After Transfer*
LD TDAT S2 DIP SWITCH
enable Actuator 6 on
disable Actuator 6 off
6
6
*Enabling the Delay After Transfer will cause the control signal to reset after the same delay
as set for the
Delay Before Transfer.
REMOTE CONTROL FEATURES
These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.
Remote Test (terminals CP6–7)
RTSW S2 DIP SWITCH
disable Actuator 3 on
enable Actuator 3 off
3
3
Remote Transfer to Emergency (CP8–9)
RT /E S2 DIP SWITCH
disable Actuator 2 on
enable Actuator 2 off
2
2
Bypass Transfer Time Delay (CP12–13)
TD E/N BYP. S2 DIP SWITCH
disable Actuator 1 on
enable Actuator 1 off
1
1
Inhibit Transfer to Emergency (CP10–11)
N/E INHIB. S2 DIP SWITCH
disable Actuator 4 on
enable Actuator 4 off
5 --- 4
4
4
CONTROL FEATURES (continued)
OPTIONAL STRIP HEATER (Accessory 44)
Accessory 44 Strip Heater is designed to keep ambient temperatures within the Automatic Transfer Switch enclosure at acceptable levels. This accessory consists of a mounting bracket with strip heater, thermostat, and terminal block. A transformer with fuses is included when the power for the assembly is derived from voltages above 120 V ac. The 120 V ac customer powered assembly does not include a transformer. This optional accessory is available factory installed or in kit form.
Turn the thermostat’s dial to required setting as shown.
thermostat
dial
turn counterclockwise
to lower temperature
turn clockwise
to raise temperature
AVAILABLE KITS
Controls
Description Accessory Kit
ProgrammableEngineExerciser
& Source Availability Contacts
Serial Communication Module 72A K601110
11BG K629830
Figure 5–4. Thermostat.
Strip Heater – Accessory 44
Description Accessory Kit
120 volt
customer supplied voltage
(without transformer)
208 – 480 volt
ATS derived voltage
(with transformer)
380 volt
ATS derived voltage
(with transformer)
44A K613127–001
44G K613127–002
44G K613127
5 --- 5
550 – 600 volt
ATS derived voltage
(with transformer)
44G K613127–003
A
G
INDEX
strip heater, 5–5
accessories, 5–2, 5–5
auxiliary circuits, 1–2
B
battery, 4–2, 5–1
buttons, push, 3–1
bypass time delay, 1–5, 2–1, 3–1
C
cable
lugs, 1–1 preparation, 1–1
catalog number, inside cover
cleaning, 3–1
connections
engine control contact, 1–2 line, 1–1
contact position indicators, 1–3
contacts
auxiliary, 1–2 engine control, 1–2 main, 1–3, 3–1 source availability signal, 5–2
control features, 5–1
load disconnect, 5–4 motor load transfer, 5–4 plant exerciser, 5–1, 5–2, 5–3
controller, 4–1, 4–2
codes, cover cover removal, 4–2 disconnecting, 3–1 time delay potentiometers, 4–2
D
DIP Switches, 4–1, 4–2, 5–1, 5–2, 5–4
E
electrical operation, 1–5
engine exerciser, 5–1, 5–2, 5–3
engine starting contacts, 1–2
F
features, see control features
frequency, pi ckup and dropout
settings, 4–1
functional test, 1–3, 1–4, 1–5
ground, controller, 1–1
H
handle, maintenance, 1–3
warning, 1–3
harness, 1–2
disconnect plugs, 3–1
HELP
800–800–2726 (ASCO) customercare@asco.com
I
inphase monitor, 5–4
inspection, 3–1
installation, 1–1
L
labels,
engine starting contacts, 1–2 inputs / outputs, 1–2 rating, cover
lights, 1–4, 5–1
load disconnect feature, 5–4
lubrication, 3–1
M
maintenance, preventive, 3–1
manual load transfer, 3–2
warning, 3–2
manual operation, 1–3
warning, 1–3
motorloadtransferfeature,5–4
N
nameplate, cover
O
operation
electrical, 1–5 manual, 1–3
illustration of, 1–3 warning, 1–3
sequence of, 2–1
optional accessories
programmableengineexerciser
& source availability signal contacts, 5–2, 5–3
serial communication module, 5–5
P
parts, 3–1
problem, 3–2
programmable engine exerciser, 5–2,
5–3
R
rating label, cover
remote control features, 5–4
bypass transfer time delay, 5–4 inhibit transfer to emergency, 5–4 remote test, 5–4 remote transfer to emergency, 5–4
replacement parts, 3–1
S
service, call 800–800–2726 (ASCO)
set engine exerciser, 5–1, 5–2, 5–3
settings
changing, 4–1 factory, 4–1 frequency, 4–1 phase, 4–1 time delay, 4–1 voltage, 4–1
source accepted lights, 1–4, 1–5
T
terminal block, 1–2
test, functional, 1–3, 1–4, 1–5
time delay
adjustment, 4–1 gen–set cooldown, 4–1 how to change, 4–2 override momentary outages, 4–1 transfer to emergency, 4–1 transfer to normal, 4–1
timer (plant exerciser), how to set,
5–1, 5–2, 5–3
transfer switch position lights, 1–4,
1–5
transfer test, 1–5, 3–1
trouble–shooting, 3–2
V
voltage, phase, 4–1
voltage, pickup and dropout settings,
4–1
Printed in U.S.A.
Copyright --- ASCO Power Technologies, L.P. 2011
Loading...